In CIM, equipment never connects to a bus directly. Each piece of equipment has Terminals, each Terminal sits on a ConnectivityNode, and per-phase data lives in child objects such as ACLineSegmentPhase. Writing all of that by hand is most of what makes CIM tedious. A few shorthand columns generate it for you, following the CIM rules.

Nodes and buses

Column The Terminal goes on a Terminal sequenceNumber
node, node1 ConnectivityNode 1
node2 ConnectivityNode 2
bus, bus1 TopologicalNode 1
bus2 TopologicalNode 2
Table ACLineSegment: mRID, node1, node2, length (ft), BaseVoltage
    ln_trunk, sourcebus, n1, 2000, bv_12kv

This makes the Terminals ln_trunk_T1 (on sourcebus) and ln_trunk_T2 (on n1). A node that wasn't declared is created on first use, with the cell value as its mRID. Each node takes the equipment's EquipmentContainer unless it already has one.

Use node columns for a node-breaker or distribution model and bus columns for a bus-branch model. Give both (node1 and bus1) to put one Terminal on a ConnectivityNode and a TopologicalNode at once, as PSS/E RAW's node-breaker substation data does.

A node and a bus are two objects

They need different mRIDs, since mRIDs are unique across the model. A source with a single ID per node has to make up the second one, for example 671 for the node and tn_671 for the bus.

Transformer ends

A PowerTransformerEnd row's node puts its Terminal on the end's transformer, numbered by its endNumber:

Object PowerTransformer: mRID=xf_sub, EquipmentContainer=sub
Table PowerTransformerEnd: mRID, PowerTransformer, endNumber, node, ratedU (kV), ratedS (kVA), connectionKind, BaseVoltage
    xf_sub_1, xf_sub, 1, sourcebus, 115,  5000, D, bv_115
    xf_sub_2, xf_sub, 2, 650,       4.16, 5000, Y, bv_4160

The Terminals are xf_sub_T1 and xf_sub_T2.

Phases

phases lists the conductors in order: ABCN, CB, s1s2N. The order matters: it is the row order of the line's phase impedance matrix.

Table ACLineSegment: mRID, node1, node2, phases, length (ft), PerLengthImpedance, BaseVoltage
    632645, 632, 645, CB, 500, mtx603, base_4160

For each token this makes one per-phase child, named <mRID>_<phase> (632645_C, 632645_B), with its phase and a sequenceNumber where the class has one. Every Terminal of the equipment gets the set's PhaseCode in canonical order (BC).

No phases means balanced three-phase

Leave phases blank for a balanced device. That makes no per-phase children and leaves Terminal.phases unset, which CIM defines as ABC. phases=ABC means something else: a per-phase device with three separate phases.

Split-phase secondaries

Triplex and other split-phase service uses s1 and s2: phases=s1s2N gives children _s1, _s2, _N and the PhaseCode s12N.

Conductor positions on a shared spacing

On a line that uses a WireSpacing, each conductor's sequenceNumber is its position on the spacing. When those aren't simply 1, 2, 3, ..., give them in a sequenceNumbers column, space-separated, one per phase in the same order:

Table ACLineSegment: mRID, node1, node2, phases, sequenceNumbers, WireSpacing, length (ft), BaseVoltage
    ln_c1, p1, p2, ABCN,  ,         sp_double, 300, base_12kv    # positions 1 2 3 4
    ln_c2, p1, p2, ABCN,  8 9 10 4, sp_double, 300, base_12kv    # second circuit, shared neutral
    ln_s1, p2, h7, s1s2N, 5 6 7,    sp_double, 80,  base_240

A blank cell means 1..n. A count that doesn't match phases, a repeated number or one below 1 is an error.

Delta connections

A delta-connected load or capacitor (phaseConnection=D) has one per-phase child per line-to-line branch, and N is ignored. Following the CIM definition ("from the indicated phase to the next logical non-neutral phase"), each child's phase is the branch's from-phase:

Table EnergyConsumer: mRID, node, phases, phaseConnection, p (kW), q (kVAr), BaseVoltage
    ld_692, 692, CA, D, 170, 151, base_4160

makes one child ld_692_AC (named by the branch's canonical PhaseCode) with phase=C and, in profiles that have the extension, phases=AC.

Switches with different phases on each side

A switch whose two sides carry different phases takes phaseSide1 and phaseSide2 instead of phases. The sides pair by position, and each Terminal gets its own side's PhaseCode:

Table Breaker: mRID, node1, node2, phaseSide1, phaseSide2, normalOpen
    brk_1, n1, n2, AB, AC, false        # A to A, B to C

Writing it out yourself

The shorthand is never the only way. Write Terminal, ConnectivityNode and per-phase rows like any other class when you need to, for example to give a Terminal its own mRID or to put per-phase data on a load:

Table Terminal: mRID, ConductingEquipment, ConnectivityNode, sequenceNumber
    t_ld_1, ld_n1, n1, 1

A column whose name is a real CIM attribute of the class (Terminal.phases, EnergyConsumerPhase.phases) is always that attribute, never the shorthand.