Units and impedance bases¶
Units go on the column header¶
Table ACLineSegment: mRID, node1, node2, length (ft), r (ohm), x (ohm), BaseVoltage
Object BasePower: mRID=sbase, basePower (MVA)=100
The unit applies to every cell in the column. Any unit the value's CIM type can convert from works: kV, kW,
MVAr, ohm/mile, uS, ft. A unit-bearing column written without a unit is read in SI base units (W, V, ohm,
S, m).
The model always holds CIM's own SI types, exactly as CIM XML does: length (ft)=2000 is stored as 609.6 m, and
p (kW)=1155 as 1,155,000 W. Read a value back in any unit with cim-graph's .to():
Percent-typed CIM attributes (percentImpedance, pfixedPct) hold the percent number itself: 5, with or
without (percent), is stored as 5.
pu and percent impedances¶
A (pu) or (percent) value on an impedance (ohm) or admittance (siemens) column is converted to ohms or
siemens against a base, z_base = U² / S. Which base depends on the class, never on which values a row happens
to set:
| Class | Base |
|---|---|
A rated class, such as PowerTransformerEnd |
Its own rating: ratedU and ratedS. |
A class that points at a rated one, such as TransformerMeshImpedance |
The rating of its From... end. |
Anything else, such as ACLineSegment or EnergySource |
The system base: its BaseVoltage and the model's BasePower. |
Object BasePower: mRID=sbase, basePower (MVA)=100
Object BaseVoltage: mRID=bv_4160, nominalVoltage (kV)=4.16
Object PowerTransformer: mRID=xf
Table PowerTransformerEnd: mRID, PowerTransformer, endNumber, ratedU (kV), ratedS (kVA), r (percent), BaseVoltage
xf_1, xf, 1, 4.16, 500, 1, bv_4160 # 1% of 4.16² / 0.5 = 0.346 ohm
Object TransformerMeshImpedance: mRID=z_12, FromTransformerEnd=xf_1, x (percent)=5 # on xf_1's rating
The system base¶
The system base power is the model's BasePower object, never a library default. Declare it before any row that
needs it; a system-base value before it is an error, as is a second BasePower that disagrees with the first.
Data already on the system base¶
Source data that is on the system base even for a rated class, such as PSS/E transformer impedances, uses
(pu system) or (percent system):
Table PowerTransformerEnd: mRID, PowerTransformer, endNumber, ratedU (kV), ratedS (kVA), x (pu system), BaseVoltage
xf_1, xf, 1, 4.16, 500, 0.1, bv_4160 # 0.1 × 4.16² / 100 = 0.0173 ohm
system is the only base word, and only pu and percent take it.
What a rated class needs¶
Every value a relative impedance depends on is set before the conversion, wherever it appears in the row: the
ratings, the BaseVoltage and the From... reference. If one of them is missing, the row raises rather than
guessing: