Skip to content

The format

A .cimtbl file is a list of statements, one per line. Indented lines under a Table are its rows.

ieee13_excerpt.cimtbl
Profile = cim18v17
Authority = https://example.com/models
Model = ieee13

Import wire_infos.cimtbl

Object BasePower: mRID=sbase, basePower (MVA)=100

Table ACLineSegment: mRID, node1, node2, phases, length (ft), PerLengthImpedance, BaseVoltage, EquipmentContainer=fdr
    650632, RG60, 632, ABCN, 2000, mtx601, base_4160
    632645, 632,  645, BC,   500,  mtx603, base_4160

Statements

Statement Meaning
Profile = cim18v17 The CIM profile the rows are written against.
Authority = ..., Model = ... The model's identity. Every UUID is derived from an object's mRID under these two, so the same file always gives the same UUIDs, and two models can each have a bus 671 without colliding.
Import other.cimtbl Splice another file in at this point. The path is relative to the importing file.
Object <Class>: attr=value, ... One object.
Table <Class>: column, column, ... Many objects, one indented row each.
Update <Class>: mRID=..., attr=value, ... Add properties to an object defined earlier. Update Table <Class>: is the table form.
# ... A comment, on its own line or after content.

Each setting (Profile, Authority, Model) appears at most once in a file. An imported file may declare them too; its value fills one the importing file left unset, and one that disagrees raises.

Object and Table build exactly the same objects. Use Object for a singleton (BasePower, an EnergySource) and Table for many, even when the rows are ragged: blank cells are fine.

Cells

  • A blank cell is unset. Cells are trimmed.
  • Quote a cell as in CSV when it holds , # ( ) or has leading or trailing spaces: "#2_ACSR_6/1", "DEFAULT (DC)". Inside quotes, "" is one quote character, and a quoted "" is the empty string rather than unset. Names are kept exactly as written, never sanitized.
  • Booleans are true, false, 1 or 0.
  • Enumerations are the enumeration's value: phaseConnection=D, phaseConnection=Y.
  • A cell can't span lines.

Header defaults

A header column can carry a default for every row, as EquipmentContainer=fdr does above. Rows fill the columns without defaults, in order; extra cells at the end of a row override the defaulted columns, in order.

Table EnergyConsumer: mRID, node, p (kW), q (kVAr), BaseVoltage, EquipmentContainer=fdr
    load_671, 671,       1155, 660,  base_4160
    load_sub, SourceBus, 2000, 1000, base_115, sub      # this one is in the substation

Identity: mRID

Every row of an IdentifiedObject class needs an mRID, and mRIDs are unique across the whole model, not per class. A common convention is a short prefix per kind of object (ld_671 for the load at bus 671), but any unique string works.

name is ordinary, optional data. Renaming an object never changes its identity or UUID.

A few CIM 18 classes have no mRID (PhaseImpedanceData). Their rows take an optional identifier column instead, which gives the object a stable UUID the same way.

Declaring an object twice. A second Object/Table row with the same mRID, class and values changes nothing. That lets every feeder file declare the BaseVoltages it uses, and a catalog imported from two places load cleanly. A second row with different values raises; adding values is what Update is for.

References

A reference column is named after the CIM association (BaseVoltage, PerLengthImpedance, PowerTransformer) and its cell holds the target's mRID. Where the association points to an abstract class (EquipmentContainer, PerLengthImpedance), any subclass is accepted.

Declare targets first

References are resolved as each row loads, so the target must appear earlier in the file (or in an earlier Import). Order a file the way you would explain the model: bases and catalogs, then containers, then equipment.

A reference that would point forward, such as a regulating control whose terminal belongs to equipment declared after it, is written with Update:

Object LinearShuntCompensator: mRID=cap_c1, node=675, phases=ABC, bPerSection (uS)=34.6, BaseVoltage=base_4160
Object RegulatingControl: mRID=rc_c1, Terminal=cap_c1_T1, mode=voltage
Update LinearShuntCompensator: mRID=cap_c1, RegulatingControl=rc_c1

An Update only adds. It never overwrites a value that is already set, and it can't use the node or phases shorthand (that would make a second set of Terminals).

The same class, different columns

One class can appear in several tables with different columns. A line can be given by its impedance in one table and by a catalog reference in another:

Table ACLineSegment: mRID, bus1, bus2, r (pu), x (pu), bch (pu), BaseVoltage
    line_1_2, bus_1, bus_2, 0.01938, 0.05917, 0.0528, bv_138

Table ACLineSegment: mRID, node1, node2, phases, length (ft), PerLengthImpedance, BaseVoltage
    632645, 632, 645, BC, 500, mtx603, base_4160

Which columns are present decides the representation; rows carry no type flag.

Catalogs and templates

Share wire, cable and transformer data between models with Import: put the catalog in its own file and import it where it's used. A reusable template is a real CIM association, not a special column: ACLineSegment.WireConfiguration for a line, TransformerTank.TankConfiguration for a transformer.

Matrix impedances are written out element by element, one PhaseImpedanceData row each, so every element stays visible and addressable.

Writing the boilerplate yourself

The only column names that aren't CIM names are the connectivity and phase shorthand (node, bus, phases and a few more), described in connectivity and phases. All of it is optional: Terminal and ConnectivityNode rows can be written out like any other class, and a real CIM attribute with the same name as a shorthand column always wins.