Canonical shapes

A shape is the one table layout for a CIM family. Spokes differ only in which optional columns they fill and in the source units they write, never in structure. So two formats' artifacts for the same network compare row by row, and a getter reads either.

Each shape is a loadable .cimtbl example in cimhub_core/src/cimhub_core/shapes/. The file is the spec: read it before writing a mapper. cimhub_core/tests/test_shapes.py loads every file under cim18v17 and checks that each shape is listed in the cimtbl-shapes skill. The mappers that emit a shape are tested against their own goldens (Testing), and the helpers they use are on The .cimtbl import contract.

from pathlib import Path
from cimgraph.models import BusBranchModel
from cimtables import load_model
from cimhub_core.cimtbl_testing import cim_scope

shapes = Path("cimhub_core/src/cimhub_core/shapes")
with cim_scope():
    network = load_model(shapes / "load.cimtbl")
    for load in network.graph[network.cim.EnergyConsumer].values():
        print(load.mRID, load.phaseConnection, load.p.to("kW"))
    bus_branch = load_model(shapes / "line_bus_branch.cimtbl", model_cls=BusBranchModel)
    [line] = bus_branch.graph[bus_branch.cim.ACLineSegment].values()
    print(line.mRID, round(float(line.r.to("ohm")), 5))

The two bus-branch shapes (line_bus_branch, behind_transformer) need model_cls=BusBranchModel. The rest load with the default.

All shapes

Shape file Native data Main classes Emitted by
common Shared prerequisites Substation, Feeder, BaseVoltage, LoadResponseCharacteristic, OperationalLimitType OpenDSS, GridLAB-D
wire_info Wire and cable catalogs OverheadWireInfo, TapeShieldCableInfo, ConcentricNeutralCableInfo OpenDSS, GridLAB-D
line_by_impedance A line with an impedance code PerLengthPhaseImpedance, PerLengthSequenceImpedance, WireConfiguration, ACLineSegment OpenDSS, GridLAB-D, GDM
line_by_wire_configuration A line by conductor geometry XYSpacing, WireConfiguration, WireSequenceConfiguration, ACLineSegment OpenDSS, GDM
line_bus_branch A line lumped in per unit TopologicalNode, ACLineSegment RAW
transformer_template A 3-phase transformer catalog entry TransformerTankConfiguration, TransformerTankEnd, TransformerWinding, TransformerCore OpenDSS, GridLAB-D, GDM
transformer_template_1ph A single-phase center-tapped catalog entry TransformerTankConfiguration, TransformerLug, TransformerWinding OpenDSS, GridLAB-D, GDM
transformer_by_template A transformer that names a template PowerTransformer, TransformerTank, PowerTransformerEnd, TransformerPhaseEnd OpenDSS, GridLAB-D, GDM
transformer_by_ends A transformer given as data of its ends PowerTransformer, PowerTransformerEnd, TransformerMeshImpedance OpenDSS, RAW
transformer_by_phase_ends A single-phase transformer by coil TransformerTank, TransformerPhaseEnd, TransformerWinding, TransformerMeshImpedance OpenDSS
transformer_by_tank_impedance A transformer given as can nameplates (GIS form) PowerTransformerEnd, TransformerTank None yet; the getters read it
regulator A step-down transformer with a tap changer PowerTransformer, RatioTapChanger, TapChangerControl OpenDSS, RAW
voltage_regulator A step-voltage regulator VoltageRegulator, AutoTransformerEnd, RatioTapChanger, TapChangerControl OpenDSS, GridLAB-D, GDM
behind_transformer Equipment with its own transformer PowerTransformer, TopologicalNode, SynchronousMachine, CsConverter RAW
load A load EnergyConsumer, EnergyConsumerPhase OpenDSS, GridLAB-D, GDM
load_schedule A load that follows a curve ConformLoadGroup, ConformLoadSchedule, ConformLoad, NonConformLoad OpenDSS, GridLAB-D
shunt A shunt capacitor with a control LinearShuntCompensator, RegulatingControl OpenDSS, GridLAB-D, GDM, RAW
switch A switching device Breaker, Fuse, LoadBreakSwitch, Recloser, Disconnector OpenDSS, GridLAB-D, GDM, RAW
source A source EnergySource OpenDSS, GridLAB-D, GDM
der An inverter-based resource PowerElectronicsConnection, PhotoVoltaicUnit, BatteryUnit OpenDSS, GridLAB-D, GDM
synchronous_machine A rotating machine on a distribution node SynchronousMachine, RegulatingControl OpenDSS, RAW
series_compensator A series reactor SeriesCompensator OpenDSS, GridLAB-D, GDM, RAW
location Equipment coordinates CoordinateSystem, PowerSystemResource (wkt) OpenDSS

"Emitted by" lists the spokes whose importers write the classes of that shape, checked against their mappers. GDM is builder-native: it builds the same classes with CIM-Builder and writes no artifact, so its output matches the shape's classes and columns but not its text. RAW's output for the distribution shapes (shunt, switch, synchronous_machine, series_compensator, transformer_by_ends, regulator) is the bus-branch form of the same classes: bus columns instead of node, and TopologicalNodes instead of ConnectivityNodes.

Rules every shape follows

  • Units as written. The header carries the source unit: r (ohm/mi), p (kW), x (percent), r (pu system). Nothing is pre-converted (I2). See Units.
  • mRID is a prefix plus the native ID. The prefix tells the class (lc_, xc_, ln_, ld_, sw_, ...). Source case is kept; only OpenDSS lowercases.
  • Generated, never written: Terminals (<equipment>_T<n>, a transformer end's is <xf>_T<endNumber>), phase children (<mRID>_<phase>), ConnectivityNodes from node, node1, node2, and TopologicalNodes from bus, bus1, bus2. A row that refers to a generated Terminal uses that mRID.
  • Declare before reference. Templates, catalogs and controls come before the rows that name them. The master's Import order is the dependency order. A reference that would form a cycle (a control on its own equipment's terminal) is closed by an Update row afterwards.
  • A balanced three-phase device leaves phases blank (phases_cell): no per-phase children, and CIM's three-phase default. Lines and transformer ends keep their phases.
  • TapChanger.step is a tap position, never a turns ratio.
  • Identity-only classes (PhaseImpedanceData) have no mRID. They carry an identifier, <parent>_<row><column>.

common

common.cimtbl: the prerequisites that every instance shape imports.

Class (mRID) Columns Notes
Substation (sub_shapes), Feeder (fdr_shapes) name; a Feeder also NormalEnergizingSubstation The containers that equipment rows name with EquipmentContainer.
BaseVoltage (bv_<kV>) nominalVoltage (kV) Line to line.
LoadResponseCharacteristic exponentModel, p/qConstantPower, p/qConstantCurrent, p/qConstantImpedance The three fixed rows zip_constant_pq, zip_constant_z, zip_constant_i, from cimhub_core.load_response.zip_fractions() (zip_fractions).
OperationalLimitType name, durationKind, isInfiniteDuration, direction olt_normal and olt_emergency. A rating is an OperationalLimitSet with one CurrentLimit per type.

Templates and wire catalogs need none of this.

wire_info

wire_info.cimtbl: wire and cable catalogs. Emitted for OpenDSS WireData, TSData and CNData and GridLAB-D *_line_conductor.

Class (mRID prefix) Required Optional
OverheadWireInfo (wire_) radius, gmr (in, ft, mm), one resistance (rDC20 (ohm/kft), or rAC25, rAC50, rAC75 per length) name, ratedCurrent (A)
TapeShieldCableInfo (cable_) As above insulationThickness, diameterOverInsulation, diameterOverScreen, diameterOverJacket, tapeThickness, tapeLap (a PerCent attribute: unitless, as in the example)
ConcentricNeutralCableInfo (cable_) As above diameterOverNeutral, neutralStrandCount, neutralStrandRadius, neutralStrandGmr, neutralStrandRDC20

Units are as written. The example holds radius (in), gmr (in) and rAC25 (ohm/mi). These are the catalogs of line_by_wire_configuration: a WireSequenceConfiguration names them with WireInfo.

line_by_impedance

line_by_impedance.cimtbl: a line whose impedance is a per-length matrix or sequence code. There are two forms (the wire-configuration skill has the rule):

Form Impedance Line names
A named code that lines share (DSS LineCode, GLM z-matrix line_configuration, a GDM catalog) isTemplate=true, held by a WireConfiguration <lc>_wc that has no WireSpacing WireConfiguration=lc_mtx604_wc
A line's own values isTemplate=false PerLengthImpedance=ln_l2_lc
Class (mRID) Required Optional
PerLengthPhaseImpedance (lc_) conductorCount, isTemplate name, calculatedFrequency (Hz)
PhaseImpedanceData (identifier <lc>_<row><col>) PhaseImpedance, row, column (conductor indices, lower triangle), r, x (ohm per length) b (nS or uS per length)
PerLengthSequenceImpedance (lc_, or ln_<line>_lc for a line's own) r, x, r0, x0 (ohm per length), isTemplate bch, b0ch (nS or uS per length), calculatedFrequency
WireConfiguration (<lc>_wc) name, PerLengthImpedance
ACLineSegment (ln_) node1, node2, phases, length, BaseVoltage, and WireConfiguration or PerLengthImpedance EquipmentContainer, and a rating through OperationalLimitSet and CurrentLimit

The per-length unit is the source's (ohm/mi, ohm/km, nS/mi). The segment's length unit is its own (length (ft)). A matrix row's row and column are conductor indices, not phases: the line's phases order picks the row.

line_by_wire_configuration

line_by_wire_configuration.cimtbl: a line by geometry. Never substitute an impedance matrix for it.

Class (mRID) Required Optional
XYSpacing (spc_) isTemplate=true name
XYConductorPosition (<spc>_<n>) XYSpacing, sequenceNumber, xCoord, yCoord (ft, m), kind (phase, neutral)
EarthResistivity (earth_) earthModelType, rho name
WireConfiguration (wc_) WireSpacing numberOfPhases, EarthResistivity
WireSequenceConfiguration (<wc>_<n>) WireConfiguration, sequenceNumber, WireInfo
ACLineSegment (ln_) As line_by_impedance, with WireConfiguration

rho is typed Resistance in cim18v17, so the header is rho (ohm) and the value is ohm-metres. The WireInfo mRIDs come from wire_info. OpenDSS LineSpacing and LineGeometry map here, and so do GDM geometry branches. A GLM line_spacing does not map here: it holds pairwise distances and heights, never coordinates, so GridLAB-D's importer writes ConductorDistanceSpacing and ConductorDistance instead of XYSpacing.

line_bus_branch

line_bus_branch.cimtbl: a line lumped in per unit, for formats whose network is a bus-branch graph (RAW).

Class (mRID) Required Optional
BasePower (sbase) basePower (MVA)
TopologicalNode (bus_) BaseVoltage, ConnectivityNodeContainer name
ACLineSegment (ln_) bus1, bus2, r, x (pu system), BaseVoltage phases, bch (pu system)

(pu system) converts on the row's BaseVoltage and the model's BasePower, which must come first. The example (r (pu system)=0.0194 on 115 kV and 100 MVA) loads as 2.56565 ohm. Load it with model_cls=BusBranchModel.

transformer_template

transformer_template.cimtbl: a 3-phase catalog entry. TankEnds are for three-phase templates only.

Class (mRID) Required Optional
TransformerTankConfiguration (xc_) name, percentImpedance, percentMagnetizingCurrent, noLoadLoss, loadLoss
TransformerTankEnd (<xc>_end_<n>) endNumber, connectionKind, TankConfiguration grounded, rground (ohm), xground (ohm)
TransformerWinding (<xc>_wdg_<n>) ratedU, baseU, ratedS, baseS, FromTransformerEnd, TankConfiguration r (percent)
TransformerCore (<xc>_core) TankConfiguration form
TransformerMeshImpedance (<xc>_mesh_<ij>) FromWinding, ToWinding, x (percent) r (percent), r0, x0

A template end has no Terminal and no phases: the instance's PowerTransformerEnd carries them. The nameplate rule: ratedU is phase to phase and ratedS the normal kVA. baseU is the coil voltage (line to line for delta, line to neutral for wye) and baseS the per-phase kVA, which together give the percent-to-ohm basis baseU^2 / baseS. In the example 500 kVA gives baseS 166.667, and x (percent) on the mesh is on the From winding's base.

transformer_template_1ph

transformer_template_1ph.cimtbl: a single-phase can. Every one-phase can uses lugs, never TankEnds. The example is a center tap (H1 H2 X1 X3 X2).

Class (mRID) Required Optional
TransformerTankConfiguration (xc_) name, percentMagnetizingCurrent, noLoadLoss
TransformerLug (<xc>_lug_<designation>) designation (IEEE C57.12.70), sequenceNumber, TankConfiguration
TransformerWinding (<xc>_wdg_<n>) ratedU, baseU, ratedS, baseS, FromTransformerLug, ToTransformerLug, TankConfiguration r (percent)
TransformerMeshImpedance (<xc>_mesh_<ij>) FromWinding, ToWinding, x (percent)

A lug's sequenceNumber names the instance TransformerPhaseEnd it lands on: one phase end per phase of each terminal, end 1 first, neutral last. Several lugs may share one number. X1 is in phase with H1 under either polarity, so s1 = X1 and s2 = X3. Windings run from the polarity end: H1 to H2, X1 to X2 (s1 to N), X2 to X3 (N to s2). A split-phase half is rated kVA / 2, and baseS is winding 1's kVA on every coil.

transformer_by_template

transformer_by_template.cimtbl: an instance of a template. The ratings and impedances live only in the template.

Class (mRID) Required Optional
PowerTransformer (xf_) name, vectorGroup, EquipmentContainer
TransformerTank (<xf>_tank) PowerTransformer, TankConfiguration EquipmentContainer
PowerTransformerEnd (<xf>_<n>) node, phases, endNumber, BaseVoltage, PowerTransformer connectionKind, grounded
TransformerPhaseEnd (<xf>_<n>_<phase>) endNumber, sequenceNumber, phase, Terminal

With a TankEnd template (xf_t1 on xc_xfm1) the instance's end n is the template's end n. With a lug template (xf_t2 on xc_ct5) the instance also has one TransformerPhaseEnd per phase of each terminal, on that end's Terminal (xf_t2_T1). sequenceNumber runs across the whole transformer, end 1 first, neutral last.

transformer_by_ends

transformer_by_ends.cimtbl: a transformer for formats without catalogs, with ratings as data of each end.

Class (mRID) Required Optional
PowerTransformer (xf_) name, vectorGroup, EquipmentContainer
PowerTransformerEnd (<xf>_<n>) node, phases, endNumber, connectionKind, ratedU (kV), ratedS (kVA), r, BaseVoltage, PowerTransformer grounded, rground, xground
TransformerMeshImpedance (<xf>_mesh_<ij>) FromTransformerEnd, ToTransformerEnd, x r

r (percent) is on the end's own ratedU^2 / ratedS. x (percent) is on the mesh, on the From end's rating, so the From end must carry the kVA that the source's percent refers to. Bus-branch formats use bus instead of node and phases.

transformer_by_phase_ends

transformer_by_phase_ends.cimtbl: a single-phase transformer by coil, for a transformer that names no template (OpenDSS Transformer with buses=[n1.1.2, house.1.0, house.0.2]). It has no TransformerTankEnd.

Class (mRID) Required Optional
PowerTransformerEnd (<xf>_<n>) node, phases (AB, s1s2N), endNumber, BaseVoltage, PowerTransformer
TransformerTank (<xf>_tank) PowerTransformer percentMagnetizingCurrent (percent), noLoadLoss (W)
TransformerPhaseEnd (<xf>_<n>_<phase>) endNumber, sequenceNumber, phase phaseNeutralU (kV)
TransformerWinding (<xf>_wdg_<n>) ratedU, baseU, ratedS, baseS, FromTransformerEnd, ToTransformerEnd, TransformerTank r (percent)
TransformerMeshImpedance (<xf>_mesh_<ij>) FromWinding, ToWinding, x (percent)

sequenceNumber is unique in the transformer, runs in terminal phase order, and starts with end 1. phaseNeutralU is the coil voltage of a phase-to-neutral coil, 0 on N, and is unset on a phase-to-phase coil. A winding's From and To are phase ends (xf_t3_1_A to xf_t3_1_B). ratedU is phase to phase (0.24 across the halves of a split phase, each rated kVA / 2), baseU the coil voltage, and baseS the first winding's kVA on every coil.

transformer_by_tank_impedance

transformer_by_tank_impedance.cimtbl: the form a GIS gives: per can, only its nameplate kVA, percent impedance and load loss. No importer in this repo writes it yet, but getters/transformer.py reads it (_tank_impedance_model).

Class (mRID) Required Optional
PowerTransformerEnd (<xf>_<n>) node, phases, endNumber, connectionKind, grounded, ratedU (kV), ratedS (kVA), BaseVoltage, PowerTransformer
TransformerTank (<xf>_tank, in a bank <xf>_<position>) PowerTransformer, percentImpedance, baseS (kVA) loadLoss (W), noLoadLoss (W), percentMagnetizingCurrent

ratedU is the phase-to-phase nameplate. ratedS is the unit's, or the bank's total. baseS is the can's kVA and is required in a bank. An end on s1s2N with connectionKind I is a center tap. A bank's cans land in tank order on end 1's phases: the example xf_t7 is an open wye to open delta, with the L can on A (a-N-b) and the T can on B (b-c). There is no template, winding, mesh or phase end.

regulator

regulator.cimtbl: a step-down transformer (an LTC) with a tap changer, as a PowerTransformer by ends.

Class (mRID) Required Optional
PowerTransformer, PowerTransformerEnd, TransformerMeshImpedance As transformer_by_ends
RatioTapChanger (<xf>_tap) lowStep, highStep, neutralStep, normalStep, step, stepVoltageIncrement, TransformerEnd neutralU, ltcFlag, controlEnabled, ptRatio, ctRating, ctRatio, initialDelay (s), subsequentDelay (s), TapChangerControl
TapChangerControl (<xf>_ctrl) mode, Terminal (the generated <xf>_T2), targetValue, targetDeadband discrete, enabled, monitoredPhase, lineDropCompensation, lineDropR (ohm), lineDropX (ohm)

The tap changer sits on end 2 and the control monitors that end's Terminal. step is a tap position, never a ratio. stepVoltageIncrement is a PerCent attribute: write 0.625 unitless or (percent), never (pu) (see Units). A regulator that is not a step-down transformer is voltage_regulator.

voltage_regulator

voltage_regulator.cimtbl: a step-voltage regulator (an autotransformer), as OpenDSS names a Transformer that a RegControl controls with equal winding kV, a GridLAB-D regulator, or a GDM DistributionRegulator.

Class (mRID) Required Optional
VoltageRegulator (xf_) name, EquipmentContainer
AutoTransformerEnd (<xf>_<n>) node, phase (a PhaseCode: AN, AB, ABCN), endNumber, baseU, BaseVoltage, AutoTransformer grounded, ratedS
TransformerMeshImpedance (<xf>_mesh_12) FromTransformerEnd, ToTransformerEnd r (percent), x (percent)
TapChangerControl (rc_<name>) mode, Terminal, targetValue, targetDeadband as in regulator
RatioTapChanger (rc_<name>_tap) lowStep, highStep, neutralStep, step, stepVoltageIncrement, TransformerEnd as in regulator, no normalStep

baseU is the coil voltage and ratedS the through rating. The mesh impedance is a solver stand-in, because a regulator nameplate has no percent impedance; its percent base is end 1's baseU and ratedS. Both the mesh and ratedS are optional: without a mesh the ends are ideal and need no ratedS (a GridLAB-D regulator has neither). The tap changer sits on the tap-side end, and the control monitors that end's generated Terminal.

behind_transformer

behind_transformer.cimtbl: equipment behind its own transformer in a bus-branch model. The source gives the transformer as data of the equipment: PSS/E RAW's generator step-up (RT, XT, GTAP) and its two-terminal DC converter transformer (EBAS, TR, TAP, RC, XC). Load with model_cls=BusBranchModel.

A two-winding PowerTransformer <eq>_xf joins the network bus (end 1) to an internal TopologicalNode <eq>_int (end 2) that only the transformer and the equipment touch. The equipment sits on the internal node.

Class (mRID) Required Optional
TopologicalNode (<eq>_int) BaseVoltage (end 2's ratedU), ConnectivityNodeContainer (the network bus's Substation) name. No busNumber.
PowerTransformerEnd (<eq>_xf_<n>) bus, endNumber, ratedU (kV), BaseVoltage, PowerTransformer ratedS, r, x (ohm, on end 1 only, on its ratedU)
RatioTapChanger (<eq>_xf_tap1) As regulator A tap on end 1 only
SynchronousMachine (gen_), CsConverter (cs_) bus (the internal node) ratedS, p, q (generation negative), operatingMode, numberOfValves

load

load.cimtbl: an EnergyConsumer on a node. Its BaseVoltage is its node's.

Class (mRID) Required Optional
EnergyConsumer (ld_) node, phases, p (kW), q (kVAr), BaseVoltage name, phaseConnection (Y, D), grounded, customerCount, LoadResponse, EquipmentContainer
LoadResponseCharacteristic (exp_<p>_<q>) exponentModel=true, pVoltageExponent, qVoltageExponent A spoke's own row, written before the loads that name it
EnergyConsumerPhase (<mRID>_<phase>), by Update mRID, p, q
  • The ZIP models are the shared rows from common. An exponential model is a row of the spoke's own.
  • CIM load sign: consumption is positive p.
  • A balanced three-phase load leaves phases blank. An unbalanced one writes its phases, and an Update Table EnergyConsumerPhase gives each generated child its own p and q; the children sum to the total. A single child (one delta branch, the 240 V part) takes no row, because the total is its value.
  • On a split-phase secondary, s1s2 wye is two 120 V legs to neutral, s1 is one leg, and s1s2 delta is 240 V across the legs (GridLAB-D's power_12).

load_schedule

load_schedule.cimtbl: loads that follow a curve. Emitted for OpenDSS yearly LoadShape and GridLAB-D schedule and player. The curve is a multiplier of each load's own p and q.

Class (mRID) Required Optional
ConformLoadGroup, NonConformLoadGroup (lg_) name
ConformLoadSchedule (ls_) startTime (ISO 8601 with its offset), timeStep (s), value1Unit (none), the group name
NonConformLoadSchedule (ls_) As above, with value1Unit W, value2Unit VAr value1Multiplier, value2Multiplier
ConformLoad, NonConformLoad (ld_) The load columns and LoadGroup

A schedule is regular: startTime plus n * timeStep. Its points are not rows here. They are RegularTimePoints in the Parquet sidecar (cimhub_core.time_points), numbered from 0. A group may have no schedule (a load names a curve the source does not define): only its name is kept. No importer writes a NonConformLoadSchedule yet. RAW writes ConformLoad and NonConformLoad in groups per area and zone, without schedules.

shunt

shunt.cimtbl: a shunt capacitor and its control.

Class (mRID) Required Optional
LinearShuntCompensator (cap_) node, nomQ (kVAr), nomU (kV), BaseVoltage name, phases, phaseConnection, grounded, bPerSection (S), sections, normalSections, maximumSections, EquipmentContainer
RegulatingControl (cc_) mode, Terminal name, discrete, enabled, monitoredPhase, targetValue, targetDeadband, ptRatio, ctRatio

The compensator comes first. Its RegulatingControl monitors a Terminal declared earlier: a line's or switch's (an OpenDSS CapControl element=line.j1) or the compensator's own (cap_c2_T1). An Update LinearShuntCompensator then gives the compensator its RegulatingControl, aVRDelay (s) and controlEnabled, which closes the reference cycle of a control on its own terminal. targetValue and targetDeadband are plain floats in primary units by mode (volts for voltage), so no unit goes in the header.

switch

switch.cimtbl: switching devices. Every Switch subclass shares the sw_ prefix, so changing the class keeps the mRID.

Class Required Optional
Breaker, Fuse, LoadBreakSwitch, Recloser, Disconnector (sw_) node1, node2, open, normalOpen, BaseVoltage name, phases, EquipmentContainer, ratedCurrent (A) on a Fuse
RecloseSequence (<sw>_rs<n>) ProtectedSwitch, recloseStep, recloseDelay (s)

One RecloseSequence row per automatic reclosure, in order. OpenDSS's Recloser Shots - 1 intervals become the rows. GridLAB-D has one status, which becomes both open and normalOpen.

source

source.cimtbl: an EnergySource on a node (OpenDSS Vsource and Circuit, GridLAB-D swing node).

Class (mRID) Required Optional
EnergySource (src_) node, nominalVoltage (kV), voltageMagnitude (kV), BaseVoltage name, phases, voltageAngle (deg), r, x, r0, x0 (ohm), EquipmentContainer

The Thevenin r, x, r0, x0 are in ohm, as computed or written by the source.

der

der.cimtbl: an inverter-based resource (OpenDSS PVSystem and Storage, GridLAB-D inverter with its solar or battery).

Class (mRID) Required Optional
PowerElectronicsConnection (pv_, storage_) node, ratedS (kVA), ratedU (line to line), p, q, BaseVoltage name, phases, phaseConnection, maxQ, minQ, maxIFault, EquipmentContainer
PhotoVoltaicUnit (<pec>_unit) PowerElectronicsConnection maxP, minP, irradiance (kW/m2), p
BatteryUnit (<pec>_unit) PowerElectronicsConnection ratedE, storedE, minimumE (kWh), maxP, minP, chargingEfficiency, dischargingEfficiency (percent), idlingP, batteryState, p
  • CIM load sign: generation and discharge are negative p, charging is positive.
  • ratedU is line to line: a one-phase wye unit's kV times the square root of 3. On a split-phase secondary, s1s2 wye is two 120 V legs.
  • maxIFault is per unit of rated current.
  • A battery's p follows its state: discharging negative, charging positive, and waiting at its idlingP.
  • Several units may share one connection (a hybrid inverter). Each unit's p is its own, and they sum to the connection's.
  • A PV unit's irradiance (a GridAPPS-D extension) is the sunlight its p was made under. maxP is at 1 kW/m2.

synchronous_machine

synchronous_machine.cimtbl: a rotating machine on a distribution node (OpenDSS Generator). RAW's machines use the bus-branch form with a GeneratingUnit.

Class (mRID) Required Optional
SynchronousMachine (gen_) node, ratedS (kVA), ratedU (kV) (line to line), p, q, BaseVoltage name, phases, maxQ, minQ, type, operatingMode, earthing, EquipmentContainer
RegulatingControl (<gen>_ctrl) mode=voltage, Terminal (<gen>_T1), targetValue (V, line to line), targetDeadband discrete, enabled

CIM load sign: generation is negative p. The phases column gives one RotatingMachinePhase per phase (a single-phase motor's too). A PV-bus machine (constant P and V) regulates its own terminal, so its control comes after the machine and an Update SynchronousMachine gives the machine its RegulatingControl and controlEnabled.

series_compensator

series_compensator.cimtbl: a series reactor between two nodes (OpenDSS series Reactor, GridLAB-D series_reactor).

Class (mRID) Required Optional
SeriesCompensator (rx_) node1, node2, r (ohm), x (ohm), BaseVoltage name, r0, x0 (ohm), EquipmentContainer
Terminal, by Update mRID (<rx>_T1, <rx>_T2), phases Only for a device of fewer than three phases
OperationalLimitSet (<rx>_limits), CurrentLimit Equipment; normalValue (A), OperationalLimitType, OperationalLimitSet Ratings, as for a line

r and x are per phase, in ohm. With no mutual coupling the zero-sequence values equal them. SeriesCompensator has no per-phase class, so a balanced three-phase one leaves its Terminals' phases unset, and an Update Table Terminal gives a one-phase one its phases.

location

location.cimtbl: equipment coordinates, drawn as a GIS draws them (OpenDSS BusCoords and LatLongCoords files). It is written after every equipment file.

Class (mRID) Required Optional
CoordinateSystem (crs_<kind>) crsUrn name. Declare it first: the Location takes the first one declared.
PowerSystemResource, by Update mRID, wkt

An Update on the abstract PowerSystemResource reaches any equipment. Each ConductingEquipment gets one Location through wkt, never a ConnectivityNode, which is not a PowerSystemResource.

Equipment wkt
A line LINESTRING from its first Terminal's bus to its last, through each Terminal's bus in order
Anything else with one Terminal POINT at its bus
Anything else with more POINT at its buses' centroid (a switch or transformer midway)

cimtables makes the Location (<mRID>_loc) and one PositionPoint per vertex. x is easting or longitude.