Topology, voltage and state¶
These getters answer where equipment connects, what voltage it sits at, what state it is in and where it is drawn. Most exporters call several of them for every device. Calling conventions are on the reference index.
| Getter | Reads | Returns |
|---|---|---|
get_terminal_nodes |
each terminal's node | tuple of nodes |
get_conductor_phases |
the equipment's conductors | tuple of SinglePhaseKind |
get_terminal_phases |
one terminal's conductors | tuple of SinglePhaseKind |
get_switch_sides |
a switch's conductors on each side | pair of tuples |
phase_code_tokens |
a PhaseCode as conductors |
tuple of SinglePhaseKind |
get_base_voltage |
the BaseVoltage of a node or equipment |
float |
get_node_voltage |
a node's solved voltage | NodeVoltage or None |
get_voltage_limits |
an equipment's VoltageLimits |
VoltageLimits |
get_switch_state |
open or normalOpen |
bool |
get_reclose_delays |
a protected switch's RecloseSequences |
tuple of floats |
get_in_service |
inService or normallyInService |
bool or None |
get_location_coordinates |
a Location's PositionPoints |
LocationCoordinates or None |
get_limits_by_type |
limits of one class, by OperationalLimitType |
dict |
get_configuration_limits_by_type |
a template's limits of one class, by OperationalLimitType |
dict |
The examples run public test atoms through the OpenDSS and PSS/E RAW importers and the shape files in core, inside
cim_scope(), which restores the profile and model scope that loading a model sets process-wide.
from pathlib import Path
import cimprofiles.cim18.cim18v17 as cim
from cimtables import load_model
from cimhub_core.cimtbl_testing import cim_scope
from cimhub_core.getters.base_voltage import get_base_voltage
from cimhub_core.getters.in_service import get_in_service
from cimhub_core.getters.limits_by_type import get_configuration_limits_by_type, get_limits_by_type
from cimhub_core.getters.location import get_location_coordinates
from cimhub_core.getters.switch_state import get_reclose_delays, get_switch_state
from cimhub_core.getters.terminals import (get_conductor_phases, get_switch_sides, get_terminal_nodes,
get_terminal_phases)
from cimhub_core.getters.voltage import get_node_voltage, get_voltage_limits
from cimhub_opendss import DssImporter, DssReader
from cimhub_raw.importer.raw_to_cimtbl import raw_to_cim
from cimhub_raw.raw34_reader import Raw34Reader
SHAPES = Path("cimhub_core/src/cimhub_core/shapes")
DSS_ATOMS = Path("cimhub_opendss/tests/atoms")
RAW_ATOMS = Path("cimhub_raw/tests/atoms")
def dss_network(atom: str):
path = DSS_ATOMS / atom
return DssImporter(path.stem).to_cim(DssReader(path).read_all())
def raw_network(atom: str):
path = RAW_ATOMS / atom
return raw_to_cim(Raw34Reader(str(path)).read_all(), name=f"{path.stem}_case")
def find(network, cim_class, mrid):
return next(obj for obj in network.graph[cim_class].values() if obj.mRID == mrid)
Phases and nodes¶
Phases come from Terminal.phases, the unordered PhaseCode of the conductors at a terminal. A blank one is CIM's
balanced three-phase default, ABC. Only a line orders its conductors, through ACLineSegmentPhase.sequenceNumber,
which is the row and column order of its impedance matrix. Spoke spellings (GridLAB-D BCN, OpenDSS .3.2) are
built from the tokens in the spoke.
get_terminal_nodes¶
get_terminal_nodes(equipment: ConductingEquipment, *, topological: bool = False)
-> tuple[ConnectivityNode | TopologicalNode, ...]
Each terminal's ConnectivityNode, or its TopologicalNode with topological=True (a bus-branch model), in
Terminal.sequenceNumber order. Raises ValueError when the equipment has no terminals, a terminal has no
sequenceNumber, or a terminal has no node of the requested kind. A node-breaker model has no TopologicalNode
and a bus-branch model has no ConnectivityNode, so the flag must match the model.
with cim_scope():
network = load_model(SHAPES / "switch.cimtbl")
recloser = find(network, cim.Recloser, "sw_r1")
print([node.mRID for node in get_terminal_nodes(recloser)])
# ['n5', 'n8']
Called by every spoke: cimhub_opendss, cimhub_gridlabd, cimhub_gdm and cimhub_raw.
get_conductor_phases¶
The equipment's conductors. A line's come in ACLineSegmentPhase.sequenceNumber order, for example (C, B).
Every other device's, and a line with no ACLineSegmentPhases, come in PhaseCode order (A, B, C, s1, s2, N). Every terminal must have the same phases; a
transformer's ends differ, so read each end's terminal with get_terminal_phases. Raises
ValueError when the terminals disagree, or when a line's ACLineSegmentPhases are not the conductors at its
terminals.
with cim_scope():
network = load_model(SHAPES / "switch.cimtbl")
print([phase.value for phase in get_conductor_phases(find(network, cim.Fuse, "sw_f1"))])
print([phase.value for phase in get_conductor_phases(find(network, cim.Breaker, "sw_brkr"))])
# ['C']
# ['A', 'B', 'C']
Called by cimhub_opendss, cimhub_gridlabd and cimhub_gdm.
get_terminal_phases¶
One terminal's conductors in PhaseCode order; a blank phases is (A, B, C). Use it for a transformer end or any
equipment whose terminals differ. Called by cimhub_gridlabd and cimhub_gdm.
get_switch_sides¶
Side 1's and side 2's conductors, paired by position. A switch whose terminals agree has the same conductors on both
sides. A switch between laterals on different phases (a tie) pairs them through its SwitchPhases,
phaseSide1 to phaseSide2, in side 1's PhaseCode order. The pairs must be exactly the two terminals'
conductors, or ValueError is raised.
with cim_scope():
network = load_model(SHAPES / "switch.cimtbl")
side1, side2 = get_switch_sides(find(network, cim.Fuse, "sw_f1"))
print([phase.value for phase in side1], [phase.value for phase in side2])
# ['C'] ['C']
Called by cimhub_opendss and cimhub_gridlabd.
phase_code_tokens¶
A PhaseCode's conductors in PhaseCode order. owner names the object holding the code in the error message
when the code is not a set of conductors A, B, C, s1, s2, N. This is the function the other phase getters call, and
the control getters call it for monitoredPhase. No spoke calls it directly.
Base voltage¶
get_base_voltage¶
One rule, CIM's: a ConnectivityNode or ConductingEquipment contained in a VoltageLevel takes
VoltageLevel.BaseVoltage and its own association is disregarded. One in any other container (a feeder, a
substation) takes its own. A TopologicalNode and a TransformerEnd always take their own. There is no walk to a
neighbouring node or connected equipment. A PowerTransformer has no BaseVoltage (CIM: not used for
transformers), so read each end.
form= has no default:
form |
Returns |
|---|---|
'LL' |
BaseVoltage.nominalVoltage as stored, line to line |
'LN' |
nominalVoltage / sqrt(3), the three-phase line-to-neutral value |
'LN' raises for equipment or a transformer end on a split-phase secondary (s1 or s2), because a 120 V leg is not
LL / sqrt(3); read 'LL'. A node carries no phases, so its 'LN' is always LL / sqrt(3). Also raises
ValueError for a form other than 'LL' or 'LN', an object (or its VoltageLevel) with no BaseVoltage, a
BaseVoltage with no nominalVoltage, and a transformer end with no terminal when 'LN' is asked.
with cim_scope():
network = dss_network("load/loads.dss")
delta = find(network, cim.EnergyConsumer, "ld_ca")
print(get_base_voltage(delta, "kV", form="LL"), round(get_base_voltage(delta, "kV", form="LN"), 4))
house = find(network, cim.EnergyConsumer, "ld_house")
print(get_base_voltage(house, "V", form="LL"))
try:
get_base_voltage(house, "V", form="LN")
except ValueError as error:
print(error)
# 4.16 2.4018
# 240.0
# EnergyConsumer 'ld_house': a split-phase leg voltage is not LL / sqrt(3); read form='LL'
Called by cimhub_opendss, cimhub_gridlabd, cimhub_gdm and cimhub_raw.
Solved voltage and voltage limits¶
get_node_voltage¶
get_node_voltage(node: TopologicalNode, voltage_unit: str = "V", angle_unit: str = "deg") -> NodeVoltage | None
A balanced node's SvVoltage is the one with no phase. Per-phase SvVoltages (an unbalanced solution) are not
read here. Returns None when the node has no balanced SvVoltage.
| Field | Meaning |
|---|---|
v |
the line-to-line magnitude in voltage_unit |
angle |
the angle in angle_unit, or None when the SvVoltage has none |
Raises ValueError for two balanced SvVoltages on one node, or one with no v.
with cim_scope():
network = raw_network("branch/line_shunts.raw")
node = find(network, cim.TopologicalNode, "1")
print(get_node_voltage(node, "kV", "deg"))
# NodeVoltage(v=115.0, angle=0.0)
Called by cimhub_raw.
get_voltage_limits¶
Finds every OperationalLimitSet on the equipment and on its terminals, and classifies each VoltageLimit by its
OperationalLimitType: durationKind normal or emergency, direction high or low. Limits of one kind must
agree. The result has one field per kind, each None when the equipment has no limit of that kind:
| Field | durationKind |
direction |
|---|---|---|
normal_high |
normal | high |
normal_low |
normal | low |
emergency_high |
emergency | high |
emergency_low |
emergency | low |
Raises ValueError for a limit with no OperationalLimitType, a seasonal type, any other duration or direction
(none is read yet), an unset normalValue, or two limits of one kind that disagree.
with cim_scope():
network = raw_network("branch/line_shunts.raw")
busbar = next(iter(network.graph[cim.BusbarSection].values()))
limits = get_voltage_limits(busbar, "kV")
print(round(limits.normal_high, 1), round(limits.normal_low, 1))
# 126.5 103.5
Called by cimhub_raw.
State¶
get_switch_state¶
True when the switch is open. which='actual' reads Switch.open; which='normal' reads Switch.normalOpen.
There is no default, because the two differ in any model that is not as built. Raises ValueError for any other
which, or when the chosen attribute is unset; this getter never returns None.
with cim_scope():
network = load_model(SHAPES / "switch.cimtbl")
for name in ("sw_brkr", "sw_s1"):
switch = next(obj for objects in network.graph.values() for obj in objects.values() if obj.mRID == name)
print(name, get_switch_state(switch, which="actual"), get_switch_state(switch, which="normal"))
# sw_brkr False False
# sw_s1 True True
Called by cimhub_opendss, cimhub_gridlabd, cimhub_gdm and cimhub_raw.
get_reclose_delays¶
The delay before each automatic reclosure, in recloseStep order: one per RecloseSequence, and an empty tuple
for a switch that does not reclose. The steps must be 1..n and each needs a recloseDelay, or ValueError is
raised.
with cim_scope():
network = load_model(SHAPES / "switch.cimtbl")
print(get_reclose_delays(find(network, cim.Recloser, "sw_r1")))
# (0.5, 2.0)
Called by cimhub_opendss.
get_in_service¶
which='actual' reads Equipment.inService; which='normal' reads normallyInService. There is no default, as
for a switch's state. Unlike get_switch_state, an unset value is returned as None and the spoke decides what its
format assumes. Raises ValueError for any other which.
with cim_scope():
network = dss_network("load/loads.dss")
off = find(network, cim.EnergyConsumer, "ld_off")
on = find(network, cim.EnergyConsumer, "ld_ca")
print(get_in_service(off, which="normal"), get_in_service(on, which="normal"), get_in_service(on, which="actual"))
# False True None
Called by every spoke.
Coordinates and limits by type¶
get_location_coordinates¶
A ConnectivityNode is not a PowerSystemResource, so CIM puts coordinates on the equipment: one Location with
PositionPoints in sequenceNumber order. The positions are text in CIM and are read as floats in the
CoordinateSystem's own units. zPosition is not read.
| Field | Meaning |
|---|---|
crs_urn |
the Location's CoordinateSystem.crsUrn, or None when it has none |
points |
(x, y) pairs in sequenceNumber order |
terminals |
each terminal's (x, y) in terminal order, or None for a device point |
How points pair with terminals:
| Points | Terminals | terminals |
|---|---|---|
| one per terminal | n | the points, in order |
| more than two | 2 | the first and last point (a line route) |
| one | several | None: a GIS device point (a switch or transformer between its buses); the caller places the buses |
Returns None when the equipment has no Location or the location has no points. Raises ValueError for a point
without a sequenceNumber, xPosition or yPosition, two points with one sequenceNumber, any other count of
points than the table's. The equipment's Terminals are counted directly, so a bus-branch model (terminals on TopologicalNodes only) works like a node-breaker one.
with cim_scope():
network = load_model(SHAPES / "location.cimtbl")
line = find(network, cim.ACLineSegment, "ln_y")
print(get_location_coordinates(line).terminals)
device = get_location_coordinates(find(network, cim.SeriesCompensator, "rx_hsb"))
print(device.points, device.terminals)
# ((200.0, 350.0), (250.0, 300.0))
# ((200.0, 375.0),) None
Called by cimhub_opendss.
get_limits_by_type¶
get_limits_by_type(equipment: ConductingEquipment, limit_class: type, unit: str, *,
terminal: Terminal | None = None) -> dict[OperationalLimitType, float]
For bus-branch formats that number their ratings by set (PSS/E RAW's RATE1 to RATE12), so a limit is read by its
type rather than by duration. It collects every limit_class limit (for example cim.CurrentLimit or
cim.ApparentPowerLimit) from the OperationalLimitSets on the equipment and its terminals, or only those of
terminal when one is named (a transformer's ratings are per winding). It returns each limit's normalValue in
unit, keyed by its OperationalLimitType. An empty dict means the equipment has no limit of that class.
Raises ValueError for a terminal that is not one of the equipment's, a limit with no OperationalLimitType, an
unset normalValue, or two limits of one type that disagree.
with cim_scope():
network = raw_network("branch/line_shunts.raw")
line = next(iter(network.graph[cim.ACLineSegment].values()))
ratings = get_limits_by_type(line, cim.ApparentPowerLimit, "MVA")
print({limit_type.mRID: value for limit_type, value in ratings.items()})
print(get_limits_by_type(line, cim.CurrentLimit, "A"))
# {'olt_rate1': 100.0, 'olt_rate2': 120.0}
# {}
Called by cimhub_opendss (a transformer's seasonal Ratings) and cimhub_raw.
get_configuration_limits_by_type¶
get_configuration_limits_by_type(configuration: EquipmentConfiguration, limit_class: type,
unit: str) -> dict[OperationalLimitType, float]
A template's limits, read as get_limits_by_type reads an equipment's: those of the configuration's one
EquipmentConfiguration.OperationalLimitSet (a GridAPPS-D extension of cim18v17), for example the seasonal ratings of
a TransformerTankConfiguration. An equipment on the template does not inherit them, so get_limits_by_type on the
equipment does not return them. An empty dict means the configuration has no limit set, or no limit of that class.
Raises ValueError for a limit with no OperationalLimitType, an unset normalValue, or two limits of one type
that disagree.
with cim_scope():
network = dss_network("xfmrcode/rated.dss")
code = find(network, cim.TransformerTankConfiguration, "xc_sub")
ratings = get_configuration_limits_by_type(code, cim.ApparentPowerLimit, "kVA")
print({limit_type.mRID: value for limit_type, value in ratings.items()})
print(get_limits_by_type(find(network, cim.PowerTransformer, "xf_sub"), cim.ApparentPowerLimit, "kVA"))
# {'olt_season1': 22000.0, 'olt_season2': 25000.0}
# {}
Called by cimhub_opendss (an XfmrCode's seasonal Ratings).