Sources, DER and machines¶
These getters read what puts power into the network: the energy source at the substation, inverter-based resources
(PowerElectronicsConnection with its PV and battery units) and synchronous machines. Calling conventions are on the
reference index. The sign rules below are the part that differs from every other getter page.
| Getter | Reads | Returns |
|---|---|---|
get_source |
EnergySource voltage and Thevenin impedance |
Source |
get_der_output |
p and q of an inverter or a machine | DerOutput |
get_inverter_rating |
PowerElectronicsConnection nameplate |
InverterRating |
get_inverter_unit |
the one PowerElectronicsUnit of a connection |
the unit |
get_inverter_units |
each unit's share of a shared connection | tuple of InverterUnitShare |
get_photovoltaic_unit |
PhotoVoltaicUnit limits and irradiance |
PhotoVoltaicRating |
get_photovoltaic_datasheet |
SolarArrayInfo and SolarPanelInfo |
PhotoVoltaicDatasheet or None |
get_inverter_datasheet |
GenerationInverterInfo or StorageInverterInfo |
InverterDatasheet or None |
get_unit_limits |
active power limits of a GeneratingUnit or PowerElectronicsUnit |
UnitLimits |
get_battery_unit |
BatteryUnit limits, energy, efficiency, state |
BatteryRating |
get_machine_rating |
SynchronousMachine nameplate and mode |
MachineRating |
get_machine_impedance |
SynchronousMachine r and sequence impedances |
MachineImpedance |
A device's own schedule over time (a PV array's or battery's output curve) is
get_device_schedule. Terminal, phase and node lookups are on the
topology page.
The examples run a public test atom through the OpenDSS importer (and one GridLAB-D atom for the datasheets), inside
cim_scope(), which restores the profile and model scope that loading a model sets process-wide.
from pathlib import Path
import cimprofiles.cim18.cim18v17 as cim
from cimtables import load_model
from cimhub_core.cimtbl_testing import cim_scope
from cimhub_core.getters.der import *
from cimhub_core.getters.source import get_source
from cimhub_gridlabd.glm_reader import GlmReader
from cimhub_gridlabd.importer.glm_to_cimtbl import glm_to_cim
from cimhub_opendss import DssImporter, DssReader
DSS_ATOMS = Path("cimhub_opendss/tests/atoms")
GLM_ATOMS = Path("cimhub_gridlabd/tests/atoms")
def dss_network(atom: str):
path = DSS_ATOMS / atom
return DssImporter(path.stem).to_cim(DssReader(path).read_all())
def find(network, cim_class, mrid):
return next(obj for obj in network.graph[cim_class].values() if obj.mRID == mrid)
The sign convention¶
CIM's terminal sign is the load's: p and q are positive into the equipment. A generator, a PV array and a
discharging battery therefore carry negative p. A spoke never negates on its own; it asks the getter for the sign
its format wants with sign=, a keyword that has no default:
sign= |
p and q returned | Limit pairs returned |
|---|---|---|
'load' |
as stored (generation negative) | negated and swapped, so still (min, max) |
'generation' |
negated (positive output) | as stored |
Limits. Nameplate limits (minQ/maxQ, minP/maxP, a GeneratingUnit's minOperatingP/maxOperatingP)
are written in the generation sign: a PV unit's maxP is its output, a battery's minP is its charging power
(negative). Every limit pair comes back as (min, max) in the sign you asked for. For 'load' the stored maximum
is negated into the new minimum, and the stored minimum into the new maximum. Zero stays 0.0, never -0.0.
A minimum above its maximum raises ValueError (a producer wrote the load sign into a generation-sign field). The
exception is get_unit_limits, which returns the pair as stored.
BatteryUnit.idlingP is a loss, "consumed while idling", and is returned as stored in either sign.
Voltage. ratedU is line to line, as stored.
get_source¶
get_source(source: EnergySource, *, angle_unit: str, voltage_unit: str = "V", impedance_unit: str = "ohm",
base_power=None) -> Source
Reads nominalVoltage and voltageMagnitude (both required), voltageAngle, and the Thevenin impedance
r, x, r0, x0, r2, x2. angle_unit ('deg' or 'rad') has no default. impedance_unit is 'ohm' or
'pu'; 'pu' is on the source's BaseVoltage and base_power (network.base_power).
| Field | Meaning |
|---|---|
phases |
the source's conductors (get_conductor_phases, in PhaseCode order, neutral included if present) |
nominal_u |
nominalVoltage in voltage_unit |
magnitude |
voltageMagnitude in voltage_unit |
magnitude_pu |
magnitude / nominal_u |
angle |
voltageAngle in angle_unit, or None |
impedance |
SourceImpedance(r, x, r0, x0, r2, x2), each in impedance_unit or None when unset |
An unset impedance stays None: the spoke decides what its format assumes. Raises ValueError for an
impedance_unit other than 'ohm' or 'pu', an unset nominalVoltage or voltageMagnitude, a source with no
terminals, or (from cimtables) 'pu' without base_power.
with cim_scope():
network = dss_network("vsource/ohms.dss")
source = get_source(next(iter(network.graph[cim.EnergySource].values())), angle_unit="deg", voltage_unit="kV")
print(source.nominal_u, source.magnitude_pu, source.angle)
print(source.impedance.x, source.impedance.r2)
# 4.16 1.0 0.0
# 0.0001 None
Called by cimhub_opendss, cimhub_gridlabd and cimhub_gdm.
get_der_output¶
get_der_output(equipment: PowerElectronicsConnection | RotatingMachine, active_unit: str = "W",
reactive_unit: str = "VAr", *, sign: str) -> DerOutput
Reads p and q (both required) of an inverter or a machine, in the requested sign. Per-phase values follow the
rule on the loads page: an inverter's PowerElectronicsConnectionPhase
values when every child has them, otherwise the total split evenly. A machine's phase objects hold no p or q, so a
machine's total is always split evenly.
| Field | Meaning |
|---|---|
phases |
the phase conductors, no neutral |
connection |
PhaseShuntConnectionKind for an inverter; None for a machine, which has none in cim18v17 |
total |
PhasePower(p, q) in the caller's units and sign |
per_phase |
{SinglePhaseKind: PhasePower} in the caller's units and sign |
split |
True: the total split evenly; False: the children's own values |
Raises ValueError for a sign other than 'load' or 'generation', for equipment that is neither a
PowerElectronicsConnection nor a RotatingMachine, and for the per-phase cases on the loads page.
with cim_scope():
network = dss_network("der/der.dss")
inverter = find(network, cim.PowerElectronicsConnection, "pv_house")
print(get_der_output(inverter, "kW", "kVAr", sign="generation").total)
print(get_der_output(inverter, "kW", "kVAr", sign="load").total)
print([phase.value for phase in get_der_output(inverter, "kW", "kVAr", sign="load").phases])
# PhasePower(p=4.0, q=0.0)
# PhasePower(p=-4.0, q=0.0)
# ['s1', 's2']
Called by cimhub_opendss, cimhub_gridlabd, cimhub_gdm and cimhub_raw.
get_inverter_rating¶
get_inverter_rating(connection: PowerElectronicsConnection, apparent_unit: str = "VA", reactive_unit: str = "VAr", *,
sign: str, voltage_unit: str = "V") -> InverterRating
The connection's nameplate: ratedS and ratedU (both required), minQ/maxQ in the requested sign, and
maxIFault.
| Field | Meaning |
|---|---|
rated_s |
ratedS in apparent_unit |
rated_u |
ratedU in voltage_unit, line to line |
min_q, max_q |
the q limits as (min, max) in reactive_unit and the caller's sign, each None when unset |
max_fault_current |
maxIFault, per unit of rated current, or None |
Raises ValueError for a bad sign, an unset ratedS or ratedU, a ratedS, ratedU or maxIFault of 0 or
less, or a minQ above maxQ.
with cim_scope():
network = dss_network("der/der.dss")
inverter = find(network, cim.PowerElectronicsConnection, "pv_house")
rating = get_inverter_rating(inverter, "kVA", "kVAr", sign="generation", voltage_unit="kV")
print(rating.rated_s, round(rating.rated_u, 3), rating.min_q, rating.max_q, round(rating.max_fault_current, 3))
# 5.0 0.208 -5.0 5.0 1.111
Called by cimhub_opendss, cimhub_gridlabd, cimhub_gdm and cimhub_raw.
get_inverter_unit¶
The connection's one PowerElectronicsUnit, a PhotoVoltaicUnit or a BatteryUnit. This is the strict form: no
unit or several raise ValueError. Use get_inverter_units when several can share a
connection. Called by cimhub_raw.
get_inverter_units¶
get_inverter_units(connection: PowerElectronicsConnection, active_unit: str = "W", reactive_unit: str = "VAr", *,
sign: str) -> tuple[InverterUnitShare, ...]
CIM lets several units share one connection, a PV array and a battery behind one inverter. A format with one DC
device per inverter takes each unit's share of the connection. The share is the unit's maxP over the units' total
maxP. share is the fraction a spoke applies to the connection's ratedS and q limits; the getter itself splits only p and q.
InverterUnitShare fields:
| Field | Meaning |
|---|---|
unit |
the PowerElectronicsUnit |
share |
the fraction of the connection (1.0 for a single unit) |
p |
the unit's active power in active_unit and the caller's sign |
q |
share x the connection's q in reactive_unit and the caller's sign (a unit has no q of its own) |
The units come back in the connection's order. Rules for p:
- one unit is the whole connection, and its own
p, when set, must equal the connection's; - several units each need a positive
maxP, which sets the share; - when every unit has its own
p(cim18v17'sPowerElectronicsUnit.p) those are used and must sum to the connection's p (relative tolerance 1e-6); when none has, each takesshare xthe connection's p.
Raises ValueError for a bad sign, a connection with no unit, a missing or non-positive maxP among several
units, units where only some have p, or a p sum that disagrees with the connection.
with cim_scope():
network = dss_network("der/der.dss")
shares = get_inverter_units(find(network, cim.PowerElectronicsConnection, "storage_share"), "kW", "kVAr",
sign="generation")
print([(type(item.unit).__name__, item.share, item.p, item.q) for item in shares])
# [('BatteryUnit', 1.0, 50.0, 0.0)]
Called by cimhub_opendss, cimhub_gridlabd and cimhub_gdm.
get_photovoltaic_unit¶
get_photovoltaic_unit(unit: PhotoVoltaicUnit, active_unit: str = "W", irradiance_unit: str = "W/m2", *,
sign: str) -> PhotoVoltaicRating
| Field | Meaning |
|---|---|
min_p, max_p |
minP and maxP as (min, max) in active_unit and the caller's sign, each None when unset |
irradiance |
the irradiance attribute in irradiance_unit (a GridAPPS-D extension), or None |
Raises ValueError for a bad sign, a unit that is not a PhotoVoltaicUnit, or minP above maxP.
with cim_scope():
network = dss_network("der/der.dss")
unit = get_inverter_unit(find(network, cim.PowerElectronicsConnection, "pv_house"))
print(get_photovoltaic_unit(unit, "kW", sign="generation"))
print(get_photovoltaic_unit(unit, "kW", sign="load"))
# PhotoVoltaicRating(min_p=0.0, max_p=5.0, irradiance=800.0)
# PhotoVoltaicRating(min_p=-5.0, max_p=0.0, irradiance=800.0)
Called by cimhub_opendss, cimhub_gridlabd and cimhub_gdm.
get_photovoltaic_datasheet¶
get_photovoltaic_datasheet(unit: PhotoVoltaicUnit, angle_unit: str = "deg",
irradiance_unit: str = "W/m2") -> PhotoVoltaicDatasheet | None
Reads the unit's AssetDatasheet, a SolarArrayInfo, and the array's one SolarPanelInfo. Returns None when the
unit has no datasheet.
| Field | Meaning |
|---|---|
tilt, azimuth |
tiltAngle and orientationAzimuth in angle_unit, or None |
shading |
shadingFactor in percent, or None |
panel_efficiency |
the panel's efficiency in percent; None without a panel |
reference_irradiance |
the panel's referenceIrradiation in irradiance_unit; None without a panel |
Raises ValueError for a unit that is not a PhotoVoltaicUnit, a datasheet that is not a SolarArrayInfo, or more
than one panel. Called by cimhub_gridlabd.
get_inverter_datasheet¶
get_inverter_datasheet(connection: PowerElectronicsConnection, apparent_unit: str = "VA",
reactive_unit: str = "VAr", active_unit: str = "W") -> InverterDatasheet | None
Reads the connection's AssetDatasheet, a GenerationInverterInfo or a StorageInverterInfo. Returns None when
there is none; another datasheet class raises ValueError. The sign is not a choice here: datasheet values are
magnitudes.
| Field | Meaning |
|---|---|
apparent_power_max |
apparentPowerMaximum in apparent_unit, or None |
reactive_injected_max |
reactivePowerInjectedMax in reactive_unit, or None |
reactive_absorbed_max |
reactivePowerAbsorbedMax in reactive_unit, or None |
charge_rate_max |
chargeRateActiveMax in active_unit; a StorageInverterInfo only, otherwise None |
with cim_scope():
path = GLM_ATOMS / "inverter/inverter.glm"
network = glm_to_cim(GlmReader(path).read_all(), name="inverter_case")
inverter = find(network, cim.PowerElectronicsConnection, "pv_inv_pv1")
unit = get_inverter_unit(inverter)
print(get_inverter_datasheet(inverter, "kVA", "kVAr").apparent_power_max)
panel = get_photovoltaic_datasheet(unit)
print(panel.tilt, panel.azimuth, panel.shading, panel.panel_efficiency)
# 10.0
# 45.0 180.0 100.0 20.0
Called by cimhub_gridlabd.
get_unit_limits¶
get_unit_limits(unit: GeneratingUnit | PowerElectronicsUnit, active_unit: str = "W", *, sign: str) -> UnitLimits
The active power limits of any unit as UnitLimits(min_p, max_p): minOperatingP/maxOperatingP for a
GeneratingUnit, minP/maxP for a PowerElectronicsUnit, each None when unset. Unlike the other limit
getters it does not raise on a minimum above its maximum. A source such as a PSS/E case can hold PB above PT on
a unit that is out of service, and an exporter maps the pair as written. Raises ValueError for a bad sign or any
other class.
with cim_scope():
network = dss_network("der/der.dss")
unit = get_inverter_unit(find(network, cim.PowerElectronicsConnection, "pv_house"))
print(get_unit_limits(unit, "kW", sign="load"))
# UnitLimits(min_p=-5.0, max_p=0.0)
Called by cimhub_raw.
get_battery_unit¶
get_battery_unit(unit: BatteryUnit, active_unit: str = "W", energy_unit: str = "Wh", *, sign: str) -> BatteryRating
| Field | Meaning |
|---|---|
min_p, max_p |
minP (charging, negative in generation sign) and maxP as (min, max) in the caller's sign |
rated_e, stored_e, minimum_e |
ratedE, storedE, minimumE in energy_unit |
charging_efficiency, discharging_efficiency |
percent |
idling_p |
idlingP in active_unit, as stored in either sign |
state |
BatteryStateKind (charging, discharging, ...) or None |
Every field is None when unset. Raises ValueError for a bad sign, a unit that is not a
BatteryUnit, a ratedE of 0 or less, or minP above maxP.
with cim_scope():
network = dss_network("der/der.dss")
battery = get_inverter_unit(find(network, cim.PowerElectronicsConnection, "storage_ess"))
rating = get_battery_unit(battery, "kW", "kWh", sign="generation")
print(rating.min_p, rating.max_p, rating.rated_e, rating.charging_efficiency, rating.idling_p)
print(rating.state.value)
# -250.0 250.0 500.0 90.0 2.5
# discharging
Called by cimhub_opendss, cimhub_gridlabd and cimhub_gdm.
get_machine_rating¶
get_machine_rating(machine: SynchronousMachine, apparent_unit: str = "VA", reactive_unit: str = "VAr", *,
sign: str, voltage_unit: str = "V") -> MachineRating
| Field | Meaning |
|---|---|
rated_s, rated_u |
ratedS in apparent_unit and ratedU in voltage_unit (line to line); both required |
rated_power_factor |
ratedPowerFactor, or None |
min_q, max_q |
the q limits as (min, max) in the caller's sign, each None when unset |
q_percent |
qPercent, a share of a coordinated reactive control, in percent, or None |
reference_priority |
referencePriority or None |
type |
SynchronousMachineKind or None |
operating_mode |
SynchronousMachineOperatingMode or None |
earthing |
bool or None |
Raises ValueError for a bad sign, an object that is not a SynchronousMachine, an unset ratedS or ratedU,
either of them 0 or less, or minQ above maxQ.
with cim_scope():
network = dss_network("generator/gens.dss")
machine = find(network, cim.SynchronousMachine, "gen_delta")
rating = get_machine_rating(machine, "kVA", "kVAr", sign="generation", voltage_unit="kV")
print(rating.rated_s, rating.rated_u, rating.type.value, rating.earthing)
print(get_der_output(machine, "kW", "kVAr", sign="generation").total.p)
# 250.0 0.48 generator False
# 50.0
Called by cimhub_opendss and cimhub_raw.
get_machine_impedance¶
Reads r, r0, x0, r2 and x2, in ohm or in pu on the machine's own ratedU and ratedS; an unset value is
None. MachineImpedance has the fields r, r0, x0, r2, x2. It has no positive-sequence x: cim18v17 has
no machine reactance. Machine short-circuit data (ikk, mu, star point earthing), voltage limits and capability
curves, wind units and AsynchronousMachine are not read by any DER getter.
Raises ValueError for a unit other than 'ohm' or 'pu', or an object that is not a SynchronousMachine.
with cim_scope():
network = dss_network("generator/gens.dss")
print(get_machine_impedance(find(network, cim.SynchronousMachine, "gen_delta")))
# MachineImpedance(r=None, r0=None, x0=None, r2=None, x2=None)
Called by cimhub_raw.