Units, bases and signs

CIM stores every quantity in SI. The getters hand you the number in the unit you name. This page covers what a unit string can be, how per-unit and percent get their base, and the sign of generation. The code runs against feeder.cimtbl, loaded as in Using the getters.

CIM holds SI

A quantity attribute holds a cim-profiles unit object backed by pint, always in SI base units: W, VAr, VA, V, A, ohm, S, m.

load = find(cim.EnergyConsumer, 'ld_n1')
print(repr(load.p))         # 1155000.0 watt
print(float(load.p))        # 1155000.0
print(load.p.to('kW'))      # 1155.0

Compare a quantity only after .to() or float(). Arithmetic between a unit object and a bare number raises TypeError.

get_qty and the unit strings

Every getter reads through cimtables.graph_write.get_qty(obj, attribute, unit), and you can call it yourself for an attribute no getter covers.

from cimtables.graph_write import get_qty

print(get_qty(load, 'p', 'MW'))                          # 1.155
print(get_qty(find(cim.ACLineSegment, 'ln_trunk'), 'length', 'ft'))   # 2000 (to rounding)
print(get_qty(find(cim.ACLineSegment, 'ln_trunk'), 'r', 'ohm'))       # None: unset
Result Meaning
a float the value in the unit you named
None the attribute is unset
ValueError not a field of the class, an association, or not a quantity
DimensionalityError (pint) the unit does not match the quantity, such as 'ft' for a power

Any pint unit of the right dimension works: kW, MW, kV, ft, mi, ohm/km, uS/km, deg, rad. Some getters narrow this to a few words: a line's unit is 'ohm' or 'pu', a transformer's impedance_unit is 'percent' or 'pu'.

Active power (W) and reactive power (VAr) share a dimension in pint, so a power unit of the wrong kind is not caught: get_qty(load, 'p', 'VAr') returns the active power's number. This is a known gap in the unit registry, filed upstream; check the units you pass.

Per-unit and percent

'pu' and 'percent' on an impedance or admittance divide by a base, z_base = U² / S. The base depends on the class of the object, not on the values on it.

Object Base
A rated object, such as a PowerTransformerEnd its own ratedU and ratedS
An object that points at a rated one, such as a TransformerMeshImpedance the rating of its From end
Anything else, such as an ACLineSegment or an EnergySource its BaseVoltage and the model's base power (a shunt compensator's nomU takes the place of the BaseVoltage)

For the last row the getter needs the base power, which you pass as network.base_power. Without it the read raises.

from cimhub_core.getters.source import get_source

source = find(cim.EnergySource, 'src')
print(get_source(source, angle_unit='deg').impedance.r)                                          # 0.1 ohm
print(get_source(source, angle_unit='deg', impedance_unit='pu', base_power=network.base_power).impedance.r)

The feeder's base power is 10 MVA and the source is at 4.16 kV, so z_base is 4.16² / 10 = 1.7306 ohm, and 0.1 ohm is 0.0578 pu. Change the base power and the same ohms read as a different per-unit value. network.base_power is a cim-profiles ApparentPower, so .to('MVA') reads it.

A transformer's base

A transformer's percent is on a base the result names:

from cimhub_core.getters.transformer import get_transformer_model, get_transformer_units

[tank] = get_transformer_units(find(cim.PowerTransformer, 'xf1'))
own = get_transformer_model(tank, 'percent')
system = get_transformer_model(tank, 'pu', base_power=network.base_power)
print(own.base_power, own.mesh[(1, 2)].x)        # 500000.0 (VA), 2.0 percent
print(system.base_power, system.mesh[(1, 2)].x)  # 10000000.0 (VA), 0.4 pu

With no base_power, every percent is on winding 1's ratedS. With one, the values move to that base by the power alone: 2 percent on 500 kVA is 0.4 pu on 10 MVA. The result's base_power is in power_unit, 'VA' by default.

Percent attributes

An attribute typed PerCent in CIM, such as TransformerTankConfiguration.percentImpedance, holds the percent number. Read it as 'percent'; any other unit raises.

tank_config = find(cim.TransformerTankConfiguration, 'xc_xfm1')
print(get_qty(tank_config, 'percentImpedance', 'percent'))    # 2.2825

Base voltage

get_base_voltage reads the voltage a per-unit value is on, in the form you ask for: 'LL' as stored, or 'LN', the line-to-neutral value LL / √3.

from cimhub_core.getters.base_voltage import get_base_voltage

print(get_base_voltage(find(cim.ACLineSegment, 'ln_trunk'), 'kV', form='LN'))   # 2.4017771...

An 'LN' read on equipment or a transformer end on a split-phase secondary (s1, s2) raises, because the 120 V leg is not LL / √3.

Sign

CIM's sign is the load's: p and q are positive into the equipment. A generator, a PV array or a discharging battery has a negative p. Native formats usually write generation as positive, so the DER getters make you choose with sign=.

from cimhub_core.getters.der import get_der_output

inverter = find(cim.PowerElectronicsConnection, 'pv_p1')
print(get_der_output(inverter, 'kW', 'kVAr', sign='load').total)         # PhasePower(p=-240.0, q=0.0)
print(get_der_output(inverter, 'kW', 'kVAr', sign='generation').total)   # PhasePower(p=240.0, q=0.0)
sign= Result
'load' as CIM stores it: generation is negative
'generation' negated: generation is positive

Nameplate limits are the other way round: a unit's maxP is written in the generation sign (its output), and a battery's minP is its charging, negative. Every limit pair comes back as (min, max) in the sign you asked for. A minimum above its maximum raises, which is how a producer that wrote the load sign shows up. The exception is get_unit_limits (a unit's active power limits), which returns the pair as stored, because a source can hold a minimum above a maximum on a unit that is out of service.

BatteryUnit.idlingP is a loss and comes back as stored in either sign.

Loads have no sign=. get_phase_loads returns the load as CIM stores it, positive into the load.

Where the conversion happens

The developer view of the same rules, including how importers write a source unit in a .cimtbl column header, is Units.