Skip to content

Getter reference

Every function in cimhub_core.getters, grouped by the CIM concept it reads. A getter takes a cim18v17 object, reads what CIM holds about it, and returns plain numbers in the units the caller asked for. For a task-oriented tour, see Using the getters; to add or change one, see Writing a getter.

Conventions

Every getter follows the same rules, so a call on one concept reads like a call on any other.

Rule What it means
The caller names the unit unit, impedance_unit, voltage_unit, power_unit and similar arguments take a unit string ('kV', 'ohm/km', 'MVA', 'pu', 'percent'). The result is a plain float in that unit; no CIMUnit leaves a getter. See Units, bases and signs.
Conversion is get_qty Every unit and per-unit conversion goes through cimtables.graph_write.get_qty, which picks the base the same way the importers do. A getter never multiplies by 1e3 itself. The one exception is a RegulatingControl target, which the profile types as a plain float, not a CIMUnit: get_regulating_control builds the CIMUnit for its mode and calls .to().
NamedTuple returns One getter returns all the fields of its concept as a NamedTuple (z.x, not a bare tuple), so a new field never breaks a caller.
None means unset An optional value CIM leaves unset comes back as None, never 0.0. "Not modelled" and "zero" stay distinguishable, and the spoke decides what to write. One read fills in a zero, and says so in its docstring: get_transformer_model counts an unset end x as 0 when it sums the ends' star x into a mesh, and only for a two-winding transformer (CIM's two-winding rule; with three or more windings an unset end x raises). get_shunt_admittance returns g = None when gPerSection is unset.
Required values raise A value the getter cannot go on without raises ValueError naming the class and mRID: ACLineSegment 'ln_l2': a per-length impedance needs the line's length.
No defaults for a meaning Where two readings differ in a model that is not as built, the argument has no default and is keyword-only: which='actual' or 'normal' (switch state, tap position, in service), sign='load' or 'generation' (DER), sections= and voltage= (shunt Q).
Getters are pure They read and return. They never add objects to the graph or write a computed value back onto a CIM object.
cim18v17 only Paths are the cim18v17 profile's. A getter never reads an electrical *Info catalog (TransformerTankInfo, WireSpacingInfo); it reads the templates (TransformerTankConfiguration, WireConfiguration, XYSpacing). The only WireInfo kinds read are the conductor catalog entries (see Lines and wires).

The examples on these pages load the public shapes in cimhub_core/shapes/ with cimtables.load_model. In a test, wrap the loading and the getter calls in cimhub_core.cimtbl_testing.cim_scope(), which puts back the profile and model scope that load_model sets process-wide.

from pathlib import Path

import cimprofiles.cim18.cim18v17 as cim
from cimtables import load_model

from cimhub_core.getters.current_limits import get_current_limits

SHAPES = Path("cimhub_core/src/cimhub_core/shapes")  # from the repo root

network = load_model(SHAPES / "line_by_impedance.cimtbl")
line = next(obj for obj in network.graph[cim.ACLineSegment].values() if obj.mRID == "ln_l1")
print(get_current_limits(line, "A"))
# CurrentLimits(normal=340.0, short_term=None, emergency=600.0)

All getters

Function and module are under cimhub_core.getters. The last column is the page that documents it.

Function Module Returns What it reads Page
get_line_sequence_impedance line_impedance SequenceImpedance A line's whole-line r, x, b, g and zero-sequence values, from lumped values or a per-length source. lines
get_line_sequence_impedance_per_length line_impedance SequenceImpedance A line's per-length sequence values. lines
get_line_phase_impedance_matrix line_impedance PhaseMatrix A line's per-length phase matrix in conductor order. lines
get_phase_impedance_code line_impedance CodeMatrix A PerLengthPhaseImpedance on its own, used or not. lines
get_sequence_impedance_code line_impedance SequenceImpedance A PerLengthSequenceImpedance on its own, used or not. lines
get_line_code line_impedance PerLengthImpedance \| None The line's own PerLengthImpedance, else its WireConfiguration's. lines
get_line_geometry line_impedance WireConfiguration \| None The line's WireConfiguration when it names a WireSpacing. lines
get_line_conductor_xy spacing tuple[ConductorXY, ...] A line's conductor positions, y above ground. lines
get_spacing_xy spacing tuple[ConductorXY, ...] A spacing's conductor positions in its own frame. lines
get_stored_distances spacing StoredDistances A spacing's distances and heights as it stores them. lines
get_wire_info wire WireValues A conductor catalog entry: resistances, gmr, radius, ratings, cable construction. lines
get_configuration_wires wire tuple[(int, WireInfo), ...] A WireConfiguration's conductors by sequence number. lines
get_line_phase_wires wire tuple[(int, WireInfo), ...] A line's own per-phase conductors by sequence number. lines
get_current_limits current_limits CurrentLimits An equipment's normal, short-term and emergency current limits. lines
get_asset_info_current_limits current_limits CurrentLimits A catalog entry's (a wire's) current limits. lines
equipment_limit_sets current_limits list[OperationalLimitSet] The limit sets on an equipment and its terminals, each once. lines
agreed_limit current_limits float \| None The one value of a limit kind; differing values raise. lines
get_impedance_table impedance_table tuple[ImpedanceTablePoint, ...] An ImpedanceTapChangerTable's points. lines
get_earth_resistivity earth EarthData \| None A WireConfiguration's earth model and resistivity. lines
get_network_earth earth EarthData The network's one EarthResistivity, for a line with a direct spacing. lines
get_transformer_units transformer tuple The units get_transformer_model reads: a transformer's tanks, else itself. transformers
get_transformer_model transformer TransformerModel A transformer's windings, mesh impedance and core, on one power base. transformers
get_tap_steps tap_changer TapSteps A ratio tap changer's positions, increment and neutral voltage. transformers
get_phase_tap_steps tap_changer PhaseTapSteps A linear phase tap changer's positions and angle per step. transformers
get_tap_ratio tap_changer float The turns ratio at a tap position. transformers
get_tap_voltage tap_changer float The end's voltage at a tap position. transformers
get_regulating_control control RegulatingSettings A RegulatingControl's mode, target, band and monitored terminal. transformers
get_tap_changer_control control TapChangerSettings A tap changer's control, delays and line drop compensation. transformers
get_equipment_control control EquipmentControl \| None The control of a regulated shunt, machine or inverter. transformers
get_phase_loads load PhaseLoads An EnergyConsumer's p and q, total and per phase. loads
get_load_response load LoadResponse A load's ZIP fractions or voltage exponents. loads
device_power phase_power DevicePower A device's p and q in total and per phase (loads and DER). loads
get_shunt_reactive_power shunt ShuntReactivePower A shunt's Q at a named voltage and section count. loads
get_shunt_admittance shunt ShuntAdmittance A shunt's g and b for the sections in service. loads
get_series_compensator series_compensator SeriesCompensatorData A series compensator's r, x and varistor. loads
get_load_schedule load_schedule LoadSchedule \| None A consumer's group and its one schedule. loads
get_group_schedule load_schedule LoadSchedule A load group's one time series, or its days. loads
get_schedule_points load_schedule SchedulePoints \| None A schedule's RegularTimePoint rows. loads
log_dropped_schedules load_schedule None Log the schedule groups an exporter does not write. loads
get_device_schedule device_schedule DeviceSchedule \| None A device's one EnergyConnectionSchedule that has points. loads
get_der_output der DerOutput An inverter's or machine's p and q in a named sign. der
get_inverter_rating der InverterRating An inverter's nameplate and q limits. der
get_inverter_unit der PowerElectronicsUnit The connection's one PowerElectronicsUnit. der
get_inverter_units der tuple[InverterUnitShare, ...] Each unit's share of a connection that has several. der
get_photovoltaic_unit der PhotoVoltaicRating A PV unit's p limits and irradiance. der
get_photovoltaic_datasheet der PhotoVoltaicDatasheet \| None A PV unit's array and panel datasheets. der
get_inverter_datasheet der InverterDatasheet \| None An inverter's datasheet. der
get_unit_limits der UnitLimits A unit's active power limits as (min, max). der
get_battery_unit der BatteryRating A battery's limits, energies, efficiencies and state. der
get_machine_rating der MachineRating A synchronous machine's nameplate and q limits. der
get_machine_impedance der MachineImpedance A synchronous machine's r and zero- and negative-sequence impedance. der
get_source source Source An EnergySource's voltage and impedance. der
get_terminal_nodes terminals tuple Each terminal's connectivity or topological node. topology
get_conductor_phases terminals tuple[SinglePhaseKind, ...] An equipment's conductors in order. topology
get_switch_sides terminals tuple[tuple, tuple] A switch's conductors on each side. topology
get_terminal_phases terminals tuple[SinglePhaseKind, ...] One terminal's conductors. topology
phase_code_tokens terminals tuple[SinglePhaseKind, ...] A PhaseCode's conductors. topology
get_base_voltage base_voltage float A node's or equipment's base voltage, line to line or line to neutral. topology
get_node_voltage voltage NodeVoltage \| None A topological node's solved voltage. topology
get_voltage_limits voltage VoltageLimits An equipment's voltage limits. topology
get_switch_state switch_state bool Whether a switch is open, actual or normal. topology
get_reclose_delays switch_state tuple[float, ...] The delay before each automatic reclosure. topology
get_in_service in_service bool \| None Whether an equipment is in service, actual or normal. topology
get_location_coordinates location LocationCoordinates \| None An equipment's and its terminals' location points. topology
get_limits_by_type limits_by_type dict[OperationalLimitType, float] An equipment's limits of one class, keyed by type. topology
get_configuration_limits_by_type limits_by_type dict[OperationalLimitType, float] A template's limits of one class, keyed by type. topology

Two helpers in getters/__init__.py are what the getters themselves are built from: describe(obj) gives ClassName 'mRID' for an error message, and required_qty(obj, attribute, unit, **bases) is get_qty that raises when the attribute is unset.

The values CIM has no attribute for (a susceptance from a capacitance, a Kron-reduced matrix) are not in the getters. They are pure functions in Derived values.