CIMHub works with cim18v17 only. This page is the developer view: how a physical quantity moves through the code in each direction, which base a per-unit value uses, and the traps (PerCent, comparison, sign). For what a user of the getters sees, read Units, bases and signs. The rules for Claude sessions, with the full unit tables, are the cim-units skill.

How a CIM quantity is stored

A CIM quantity attribute (EnergyConsumer.p, BaseVoltage.nominalVoltage, ACLineSegment.length) holds a CIMUnit object from cimprofiles. It is backed by pint and always stores the value in SI base units: W, VAr, VA, V, A, ohm, S, m.

>>> load.p
1155000.0 watt
>>> type(load.p).__name__
'ActivePower'
>>> float(load.p)          # the SI magnitude
1155000.0
>>> load.p.to("kW")        # any compatible unit
1155.0

CIMHub code never converts units by hand. No * 1e3, no / 1000, no * 1.609344. Conversion happens in one place in each direction:

Direction Who converts How you ask for the unit
Import (native to CIM) cimtables, when it binds the .cimtbl text the unit in the column header
Export (CIM to native) cimtables.graph_write.get_qty the unit argument

A column with no unit in its header is read in SI base units, so nominalVoltage=4160 and nominalVoltage (kV)=4.16 bind to the same 4160.0 volt. PerCent attributes are the exception (below).

Import: source value, source unit in the header

An importer writes the native number exactly as the source holds it and names the source unit in the column header. cimhub_core.cimtbl.cell() writes the value as text and never converts or rounds (The .cimtbl import contract). When cimtables builds the CIM it reads the header, converts to SI, and stores the result. Architecture shows the whole import path.

Real headers from the shapes:

Table EnergyConsumer: mRID, name, node, phases, phaseConnection, grounded, p (kW), q (kVAr), ...
Table SynchronousMachine: mRID, name, node, phases, ratedS (kVA), ratedU (kV), p (kW), q (kVAr), ...
Object BaseVoltage: mRID=bv_115kv, nominalVoltage (kV)=115
Object TransformerMeshImpedance: mRID=xc_xfm1_mesh_12, ..., r (percent)=1.1, x (percent)=2.0

And from an OpenDSS atom (seq_3_1_0c.cimtbl), where the line code is in ohm/km and the capacitance has been turned into a susceptance:

Table PerLengthSequenceImpedance: mRID, name, r (ohm/km), x (ohm/km), r0 (ohm/km), x0 (ohm/km), calculatedFrequency (Hz), bch (nS/km), b0ch (nS/km), isTemplate
    lc_3-1/0c_2/0cn_t, 3-1/0C_2/0CN_T, 0.3489, 0.426198, 0.588811, 1.29612, 60, 3932.350000000008, 1690.8100000000002, true

The rules an importer follows (invariants I2 and I5 in the root CLAUDE.md):

  1. Copy the value verbatim and put the source unit in the header.
  2. Spoke code never constructs a CIM object or a unit object: no cim.X(...), no CIMUnit, no z_base.
  3. A unit that depends on the record (the length unit of a line code) is a template, filled once per table: Field("copied", (("PerLengthSequenceImpedance", "r", "ohm/{length}"),)), then copied_columns(FIELDS, cls, length="km").
  4. A value with no unit path to the CIM attribute is derived: a named, tested pure function computes it and the artifact carries a comment. Examples are DSS C1 in nF to bch in nS (b_from_c) and the sign flip below.
# Wrong: unit math in a mapper
row = [cell(code.r1 * 1.609344), cell(load.kw * 1000)]
# Right: the number as the source holds it; the header names the unit
row = [cell(code.r1), cell(load.kw)]      # headers: r (ohm/mi), p (kW)

Per-unit and percent on import

Relative values use relative headers. cimtables multiplies by the base impedance z_base = U^2 / S (it divides for siemens) and stores ohms or siemens. The spoke never computes the base. The base is chosen by the class of the row, never by which values the row happens to set (cimtables.impedance.z_base):

Header unit Base used
(pu) or (percent) 1. The row's own rating, if its class is rated: baseU/baseS where the class has them (TransformerWinding, and baseU/ratedS on an AutoTransformerEnd), else ratedU/ratedS (PowerTransformerEnd). 2. Else the rating of the target of a From* reference (TransformerMeshImpedance.FromWinding, FromTransformerEnd). 3. Else the system base: the row's BaseVoltage (or nomU on a ShuntCompensator) and the model's BasePower.
(pu system) or (percent system) The system base, skipping 1 and 2.

If the class is rated but a rating is unset, the import fails with, for a winding, a pu/percent impedance needs both baseU and baseS set (ratedU and ratedS on a PowerTransformerEnd); it does not fall through to another base. If no base is found, the message ends in .cimtbl: a BasePower declared before this row.

Importing never invents a system base: a (pu system) row with no BasePower bound before it raises. A loaded network always has network.base_power and network.base_frequency, though. cim-graph's set_default_bases takes the file's BasePower and BaseFrequency, and when the file sets none it uses 100 MVA and 60 Hz. So an exporter that reads network.base_power from a file without a BasePower gets cim-graph's default, not a value the case declared. A case whose per-unit values matter declares both.

The artifact must hold what the base needs: the ratings, the BaseVoltage and From* references, and for a system-base row a BasePower bound before it. A bus-branch shape (line_bus_branch.cimtbl) does this:

Object BasePower: mRID=sbase, basePower (MVA)=100
Object BaseVoltage: mRID=bv_115kv, nominalVoltage (kV)=115
Object ACLineSegment: mRID=ln_1_2_1, ..., r (pu system)=0.0194, x (pu system)=0.0592, bch (pu system)=0.0528, BaseVoltage=bv_115kv

A RAW case writes its own SBASE into BasePower and its impedances as (pu system). Two RAW quantities are not a unit path that cimtables can take, so the mapper computes them in named functions in cimhub_raw/importer/cimtbl/derived.py:

  • An admittance given as MW or Mvar at 1 pu voltage (RAW GL, BL, Bi) is divided by SBASE (per_unit_from_mva) and written as gPerSection (pu system).
  • A per-unit voltage whose base is one association further than cimtables reaches (kv_from_per_unit), and a current stated as a power (ka_from_rating).

Each is a derived field, not unit math inside the mapper body.

PerCent attributes

Some CIM attributes are of type PerCent: percentImpedance, percentMagnetizingCurrent, stepVoltageIncrement, efficiencies. They hold the percent number. A unitless cell and a (percent) column both store 5 % as 5.0, never 0.05. A (pu) column on a PerCent attribute raises at binding:

TransformerTankConfiguration.percentImpedance is a PerCent: give it unitless or (percent), not Qty(value=0.05, unit='pu', base=None)
Object TransformerTankConfiguration: mRID=xc_xfm1, name=XFM1, percentImpedance=2.2825, percentMagnetizingCurrent=0, noLoadLoss (kW)=0

(percent) on an ohm- or siemens-typed attribute is a different thing: a relative impedance that goes through z_base, as in the winding and mesh r (percent), x (percent) above. That route is correct.

Export: get_qty, not hand conversion

An exporter asks for each value in the unit the native format wants. The reads live in the getters under cimhub_core/getters/; the exporter formats what the getters return (Converter API, Writing a getter).

from cimtables.graph_write import get_qty

get_qty(source_object, attribute_name, unit, *, base=None, system_base=None, power_base=None) -> float | None
Argument Meaning
unit Any unit pint can convert the attribute to ('kV', 'ohm/mile', 'MVAr'), or 'pu' or 'percent'.
base None, or 'system' to force the system base, mirroring (pu system). Only with pu or percent.
system_base The system base power for a class that has no rating (network.base_power, a CIMUnit, or a number in VA).
power_base Replaces S in z_base, to read a mesh impedance on another power at the same voltage. Only with pu or percent.

It returns None when the attribute is unset, so a getter can pass an unset value through. It raises ValueError for a name that is not a field ('nope' is not a field of EnergyConsumer), an association (EnergyConsumer.LoadResponse is an association, not a quantity), an attribute that is not a CIMUnit (EnergyConsumer.customerCount is not a CIMUnit-typed attribute (holds 1)), a base or power_base with a non-relative unit, and a missing rating, BaseVoltage or system_base. pint raises DimensionalityError on a dimension mismatch, with one gap: W and VAr convert into each other (cim.ActivePower(1, 'kW').to('VAr') is 1000.0), so a swapped active and reactive unit is silent. Core adds no check of its own; the fix is upstream (U18 in UPSTREAM_REQUESTS.md).

Real calls from the repo:

get_qty(wire, "gmr", length_unit)                                   # getters/wire.py
get_qty(base, "nominalVoltage", "kV")                               # opendss exporter/options.py
get_qty(line, "length", LUMPED_UNIT)                                # opendss exporter/line.py
get_qty(cable, "tapeLap", "percent")                                # getters/wire.py, a PerCent
get_qty(connection, "maxIFault", "pu")                              # getters/der.py
network.base_frequency.to("Hz")                                     # a value already in hand

.to(unit) is for an absolute quantity you already hold, such as network.base_frequency. Prefer get_qty: it also handles None, per-unit and percent.

A runnable check against an in-repo shape, run from the repo root:

from pathlib import Path
import cimprofiles.cim18.cim18v17 as cim
from cimtables import load_model
from cimtables.graph_write import get_qty
from cimhub_core.cimtbl_testing import cim_scope

shapes = Path("cimhub_core/src/cimhub_core/shapes")
with cim_scope():
    network = load_model(shapes / "load.cimtbl")
    load = next(iter(network.graph[cim.EnergyConsumer].values()))
    print(get_qty(load, "p", "kW"))      # 1155.0

Per-unit on export

get_qty with 'pu' or 'percent' on an ohm or siemens attribute inverts the import rule through the same z_base, so one rule picks the base in both directions. 'percent' is the per-unit value times 100.

  • The object's own rating, or its From* target's rating, is used by default.
  • An unrated class such as ACLineSegment uses its BaseVoltage and the system base. Pass system_base=network.base_power; without it the call raises.
  • base='system' forces the system base, mirroring (pu system).
  • power_base reads a mesh impedance on another power at the same voltage. DSS and GLM put every percent on winding 1's kVA, so the transformer getter passes it.
from cimgraph.models import BusBranchModel

with cim_scope():
    network = load_model(shapes / "line_bus_branch.cimtbl", model_cls=BusBranchModel)
    line = next(iter(network.graph[cim.ACLineSegment].values()))
    print(get_qty(line, "r", "ohm"))                                   # 2.56565
    print(get_qty(line, "r", "pu", system_base=network.base_power))    # 0.0194, the value the file holds

PerCent on export

get_qty(obj, attr, "percent") returns the stored number ("" also works). Any other unit raises (... is a PerCent: read it as 'percent', not 'pu'). Never call .to("percent") on a PerCent: pint treats it as a dimensionless fraction and returns 100 times the stored value.

with cim_scope():
    network = load_model(shapes / "transformer_template.cimtbl")
    config = next(iter(network.graph[cim.TransformerTankConfiguration].values()))
    get_qty(config, "percentImpedance", "percent")   # 2.2825
    config.percentImpedance.value                    # 2.2825
    config.percentImpedance.to("percent")            # 228.25000000000003  (wrong)

Comparisons

A CIMUnit is not a float. Arithmetic with a bare number raises TypeError, and so does ==. Compare the floats that get_qty returns, or float(x) for the SI magnitude.

load.p - 1000          # TypeError: unsupported operand type(s) for -: 'ActivePower' and 'int'
load.p == 1155000      # TypeError: Cannot compare ActivePower with the plain number 1155000: convert it first with .to(unit) or float() ...
get_qty(load, "p", "kW") == pytest.approx(1155.0)   # right
float(load.p) == pytest.approx(1155000.0)           # right, SI magnitude

For a PerCent, test the stored number with .value.

Generator sign convention

CIM uses the load sign: positive p is power flowing into the equipment. A generator or a battery discharging has negative p and q.

  • Import: a source that reports generation as positive (RAW PG, MATPOWER Pg, DSS kW on a generator) is negated. The negation is a derived field, written by a named function (generation_p_q in cimhub_raw/importer/cimtbl/derived.py) and noted in the artifact. The OpenDSS generator atom shows the result: # p = -kW, q = -kvar (the load sign), then a negative p (kW) for a generator.
  • Export: do not negate in the exporter. get_der_output(equipment, active_unit, reactive_unit, *, sign) in getters/der.py takes sign="generation" (negated, so output is positive) or sign="load" (as stored). sign is keyword-only and has no default: omitting it is a TypeError, and any other value is a ValueError (sign must be one of ['load', 'generation'], not 'x').
from cimhub_core.getters.der import get_der_output

with cim_scope():
    network = load_model(shapes / "synchronous_machine.cimtbl")
    machine = next(m for m in network.graph[cim.SynchronousMachine].values() if m.mRID == "gen_g1")
    print(round(get_qty(machine, "p", "MW"), 6))                                    # -0.1
    out = get_der_output(machine, "MW", "MVAr", sign="generation").total
    print(round(out.p, 6), round(out.q, 6))                                         # 0.1 0.0203

Susceptance and capacitance

SusceptancePerLength has no pint path to farads, so get_qty(data, "b", "nF/mi") raises DimensionalityError. DSS stores line capacitance (C1, cmatrix) and CIM stores susceptance. The conversion uses 2 * pi * f and lives in two named functions in derived/capacitance.py: b_from_c(c, frequency) on import (nF and Hz give nS) and c_from_b(b, frequency) on export (nS and Hz give nF; a frequency of 0 or less raises ValueError). The OpenDSS exporter reads the base frequency with network.base_frequency.to("Hz"). When an exporter needs a CIM value in another absolute unit, it goes through the CIMUnit class and not a factor, as the DSS line exporter does before calling c_from_b:

cim.Susceptance(value, "S").to("nS")      # cimhub_opendss/exporter/line.py

Common mistakes

Mistake Fix
cell(kv * 1000) under a (V) header cell(kv) under a (kV) header
r_ohm = r_pu * base_kv**2 / base_mva in a mapper write r (pu) or r (pu system) and let cimtables convert
percentImpedance (pu), or the fraction 0.05 unitless or (percent), value 5.0
end.ratedU.to("kV") scattered through an exporter one getter that calls get_qty(end, "ratedU", "kV")
a hard-coded 100 MVA base the case's own BasePower on import, network.base_power on export
bv.nominalVoltage - 4160 or == 4160 compare get_qty(bv, "nominalVoltage", "V") to the number
negating generator p inside an exporter get_der_output(..., sign="generation")
storing a turns ratio in TapChanger.step step is a tap position; the ratio comes from stepVoltageIncrement
.to("percent") on a PerCent get_qty(obj, attr, "percent")

The full unit tables and per-attribute header examples are in the skill's reference.md.