Skip to content

Import: GLM to CIM

from cimhub_gridlabd.glm_reader import GlmReader
from cimhub_gridlabd.importer.glm_to_cimtbl import glm_to_cim

model = GlmReader("cimhub_gridlabd/tests/decks/IEEE/IEEE13_cdpsm.glm", defines={"VSOURCE": "66395.28"}).read_all()
network = glm_to_cim(model, name="IEEE13_cdpsm", artifact_dir="artifacts/IEEE13_cdpsm")

network is a cim18v17 cim-graph model. artifact_dir keeps the .cimtbl text it was built from.

The IEEE exports drive every load by a player named ieeezipload that the GridAPPS-D run file defines, not the model, so the importer logs one warning: the name is in no player of the deck, and the loads' group has no schedule.

What happens

  1. GlmReader(path, defines=...).read_all() parses the .glm and the files it #includes, and returns a GlmModel of typed records.
  2. GlmImporter(name).to_cimtbl(model) walks the model's topology once (with cimtopology), then runs one mapper per GLM class. Each mapper turns records into a .cimtbl document. It does not build CIM objects.
  3. glm_to_cim writes the documents and cimtables binds them into a network.

The .cimtbl text is the only input to CIM. If a value is wrong in the network, it is wrong in the text, and you can read it there.

Reading a .glm

GlmReader(source, *, defines=None) takes the path of the .glm and the macros the model expects from the command line. read_all() raises FileNotFoundError if the file is missing and GlmParseError for anything it cannot read.

In the .glm What the reader does
${NAME} Expands from a #define or #set earlier in the file, then from defines=. A name in neither raises: macro ${VSOURCE} is not defined (pass it in defines=)
#define name=value, #set name=value Kept in model.defines and model.globals. defines= entries are added to model.defines
#include "other.glm" Read in place, relative to the file that includes it. A missing file raises
any other # directive (#if, #ifdef, ...) Raises: directive '#if' is not read
clock { ... } Its settings are kept as text in model.clock
module name { ... } or module name; Kept in model.modules[name]
schedule name { ... } The statements are kept as written in model.schedules[name]
class player { double value; } Read, in model.classes. Any other class block raises
object type { ... } A record in model.graph, keyed by its class. An object nested in another gets the outer one as its parent. object house:..20 makes 20 objects
a player's file Read beside the file that declares the player, into model.tapes[player name] as (time, value) rows as written. A row with no comma raises

Rules that matter when a model does not convert as you expect:

  • Units stay as written. distance_AN 30 in stores 30.0 and records in in model.written_units. The reader converts nothing. A value with no unit is in the unit the GridLAB-D class declares for the property.
  • Expressions are kept as text. A numeric property whose text is not a number (LIGHTS*1.2, random.normal(1750,400)) is stored in model.expressions and its slot stays unset. The importer raises only if a mapper reads that slot, so an expression on a property the importer ignores does not stop the conversion.
  • Complex values are a+bj, a+bi, m+ad (polar, degrees), m+ar (polar, radians) or a plain number. A polar value is stored as rectangular, and its magnitude and angle as written go to model.polar.
  • Names are unique across the model, as in GridLAB-D. An unnamed object is called <class>:<id>, for example load:3, from its header id or its position in the file. A reference written <class>:<id> resolves to that name.
  • A property set twice keeps the last value, as GridLAB-D does, and the reader logs a warning.
  • An object type the schema does not know (recorder, climate) is counted in model.not_read and its properties are not read. A property a known class does not have raises. Keywords are case-sensitive.

Options

glm_to_cim(model, *, name, authority=..., substation=None, feeder=None, network=None, artifact_dir=None, time_points=None). GlmImporter(name, *, authority=..., substation=None, feeder=None, time_points=None) takes the same keywords except network and artifact_dir, which go to its to_cim method.

Argument Meaning
name Required. The master document's Model and file stem, and the default name of the Substation and Feeder. Do not use the name of a part file (bus, load, player): the documents' names must be distinct, so the importer raises a ValueError naming it.
artifact_dir Keep the .cimtbl files here. Without it they go to a temporary directory that is removed after loading.
network An existing cim18v17 network to bind onto, to merge several models.
authority The master's Authority. Defaults to https://github.com/PNNL-CIM-Tools/CIMHub.
substation, feeder Name the containers. The mRIDs are sub_<substation> and fdr_<feeder>; each is name unless given. Use them when a utility's code is the scope and the feeder's own key is the container.
time_points A dict the importer fills with the points of the players and schedules. See Players and schedules.

To get the documents without binding them, call GlmImporter(name).to_cimtbl(model). It returns a DocumentSet with a master and a list of parts, and touches no files.

The topology walk

Before any mapper runs, the importer walks the model once with cimtopology:

  • Buses. Every node or triplex_node object, and every object of a class derived from one (meter, substation, load, capacitor, triplex_meter, triplex_load, ...), is a bus. A bus whose parent is a bus is solved by GridLAB-D as its parent's bus, so it is not a bus of its own: its equipment lands on the root of its parent chain. A parent that is not a bus, a loop in the parent chain, or a child whose phases are not a subset of its root's raises.
  • The source. Every substation and every bus with bustype SWING is a swing bus, and becomes an EnergySource. Its nominal_voltage is phase to neutral, on a three-phase or a one-phase system, and gives the EnergySource's nominalVoltage; any other phase count raises. Its voltage and angle come from positive_sequence_voltage (a substation) or voltage_A, else from nominal_voltage. GridLAB-D's swing bus has no impedance, so the source gets a default one: 10 000 MVA short circuit, X/R of 10, with a comment that says so. A SWING_PQ bus is a plain bus.
  • Branches. Every line, switch, fuse, recloser, sectionalizer, series reactor and regulator joins two buses, and a transformer carries a voltage ratio from its configuration.
  • Voltages. The walk gives every bus its voltage from the source outward, through the transformers. These are the BaseVoltages. The nominal_voltage the model writes on a bus is only checked against the walk: a bus more than 10 % off is listed in the bus file's comment, not raised.

A bus the walk does not reach has no row. A link, a load, a capacitor or an inverter on it raises a ValueError naming the equipment and the bus.

The artifacts

artifact_dir holds the master, <name>.cimtbl, and one file per mapped GLM class that the model uses. For the IEEE 13-node model:

IEEE13_cdpsm.cimtbl   bus.cimtbl            source.cimtbl        zip_fractions.cimtbl
line_configuration.cimtbl                   transformer_configuration.cimtbl
overhead_line.cimtbl  switch.cimtbl         fuse.cimtbl          recloser.cimtbl
transformer.cimtbl    regulator.cimtbl      player.cimtbl        load.cimtbl
triplex_load.cimtbl   capacitor.cimtbl      inverter.cimtbl

The master holds the Substation and Feeder, the BaseFrequency, one BaseVoltage per distinct bus voltage (highest first), the two operational limit types, and one Import per part. It ends with the feeder head: each link's Terminal on a swing bus is set as the Feeder's NormalHeadTerminal. BaseFrequency is nominal_frequency from module powerflow { ... } or #set powerflow::nominal_frequency=..., else GridLAB-D's 60 Hz, and the master says defaulted in a comment when it used the default. The parts are written in this order, so that a catalog comes before what uses it:

Part file From
bus.cimtbl every root bus: a ConnectivityNode with its BaseVoltage
source.cimtbl every substation and swing bus: an EnergySource
zip_fractions.cimtbl always: the ZIP load-response rows that loads name
overhead_line_conductor.cimtbl, underground_line_conductor.cimtbl, triplex_line_conductor.cimtbl the conductor catalogs
line_spacing.cimtbl line_spacing: geometry
line_configuration.cimtbl, triplex_line_configuration.cimtbl line configurations: a template impedance or a geometry
transformer_configuration.cimtbl transformer ratings and connections
overhead_line.cimtbl, underground_line.cimtbl, triplex_line.cimtbl lines
switch.cimtbl, fuse.cimtbl, recloser.cimtbl, sectionalizer.cimtbl switching devices
series_reactor.cimtbl series_reactor
transformer.cimtbl, regulator.cimtbl transformers and regulators (a regulator's configuration is read with it)
player.cimtbl, schedule.cimtbl players and schedules, as load groups
load.cimtbl, triplex_load.cimtbl, triplex_node.cimtbl loads
capacitor.cimtbl capacitor
inverter.cimtbl inverter, with the solar or battery it names

A class with no records writes no part and no Import. Values keep the units the .glm used, and the unit sits in the column header, for example p (W). A comment above a row says what the importer defaulted. The per-property rules are in the import mapping; how a table is written is in the .cimtbl contract.

What is skipped, loudly

A GLM class no mapper reads is not an error. The master's comment lists it as not mapped: <class> <count>, so nothing disappears silently. It covers the classes the schema knows but no mapper reads, and the object types the reader does not know:

# GridLAB-D model t1
# Mapping: cimhub_gridlabd/docs/CIMTBL_MAPPING.md#master
# not mapped: recorder 1

What the class would have configured is absent from the CIM network. What converts has the list.

What raises

The reader and the importer fail rather than guess. Each message names the file and line, or the GLM object.

Cause What you get
The .glm is not there FileNotFoundError: GLM file not found: <path>
A block with no }, or a last statement with no ; GlmParseError with file and line: t3.glm:1: object 'object meter' is not closed
A property the class does not have GlmParseError: t2.glm:1: meter has no property 'bogus'
A ${NAME} that nothing defines GlmParseError: macro ${VSOURCE} is not defined (pass it in defines=)
A missing #include file or player file GlmParseError for the include; FileNotFoundError: player file not found: <path> for the tape
A value that is not a boolean or an integer for its property GlmParseError: <class>.<property>: '<text>' is not an integer
Two objects with one name GlmParseError: name 'x' is already used by the object at <file>:<line>
A mapped property holds an expression ValueError: load l1 (t4.glm:2): constant_power_A is the expression 'LIGHTS*1.2', which no mapper reads yet
A link whose from or to names no bus object, a transformer with no phases, or status OPEN on a line, series reactor or regulator ValueError naming the class and object, from the walk: overhead_line l1: to zz names no bus object, overhead_line l1: status OPEN on a device that is not a switch
A link or a device on an island no swing bus reaches ValueError naming it and its bus: overhead_line l2: its from bus n2 is on an island no swing bus reaches, so it has no voltage
A model name that is a part file's name (bus, load, player, ...) ValueError: model name 'load' is the name of a part file (load.cimtbl); give the model another name, when the importer is made
A source voltage more than 10 % from the swing bus's nominal_voltage ValueError: substation 150: source voltage 66395.3 V (positive_sequence_voltage) is more than 10% from nominal_voltage 2401.78 V. The .glm or the defines= is wrong: IEEE 123 needs VSOURCE=2401.78, IEEE 13 needs 66395.28
A regulator with no continuous_rating_<phase> ValueError: regulator <name>: no continuous_rating_A; ratedS is the continuous rating x baseU. GridLAB-D's 1000 A default is not the device's rating, so the importer does not use it
A transformer whose coil voltage does not fit the bus it sits on ValueError: Transformer 633-634: its coil on bus 634 gives 0.48 kV, but the island ... is 4.16 kV 3-phase
A property a mapper classifies as raising when set ValueError naming the object and property. Which ones are in the import mapping for each class