Loads, capacitors, players and schedules

This page is the conversion reference for the GridLAB-D classes that draw power or switch a shunt: load, triplex_load (with the power of a plain triplex_node), capacitor, player and schedule. For each one it says what the importer writes, what the exporter reads back and what raises. The field classes (copied, mapped, structural, derived, untranscribed) and the conventions every section follows are on the reference index. The getters the exporter reads through are on the core site's loads, shunts and compensators page.

GLM class CIM classes .cimtbl artifact and shape Importer Exporter
load EnergyConsumer, or ConformLoad when its base reads a player or schedule; LoadResponseCharacteristic load.cimtbl, shape load importer/cimtbl/load.py exporter/load.py
triplex_load the same: one consumer for the 120 V legs and one for the 240 V part triplex_load.cimtbl, shape load importer/cimtbl/load.py exporter/load.py
triplex_node carrying power_1, power_2 or power_12 the same triplex_node.cimtbl, shape load importer/cimtbl/load.py written as a triplex_load
capacitor LinearShuntCompensator, and a RegulatingControl for a VOLT control capacitor.cimtbl, shape shunt importer/cimtbl/capacitor.py exporter/capacitor.py
player ConformLoadGroup, ConformLoadSchedule, and RegularTimePoint rows in a Parquet sidecar player.cimtbl, shape load_schedule importer/cimtbl/player.py exporter/player.py
schedule ConformLoadGroup, one ConformLoadSchedule per Season and DayType, and the sidecar points schedule.cimtbl, shape load_schedule importer/cimtbl/schedule.py exporter/schedule.py

The table shapes are on the core site's shapes page. Source paths are under cimhub_gridlabd/src/cimhub_gridlabd/. The master imports player.cimtbl and schedule.cimtbl before the load artifacts, and capacitor.cimtbl after them, so each reference resolves. The points of a player or schedule are not in any artifact: see Players and schedules and the core site's time points page.

A GLM load or capacitor is itself a bus object, so each one sits on the root bus of its parent chain (a load whose parent is a meter is on the meter's bus), and its BaseVoltage is that bus's.

Quoted error messages leave off the spec code in parentheses that ends some of them. Most start with the GLM class and name, as load a:.

The examples run from the repository root with uv run python. They convert the public test atoms in cimhub_gridlabd/tests/atoms to CIM and back. This helper is shared by all of them:

from pathlib import Path

from cimhub_gridlabd.exporter.cim_to_glm import GlmExporter
from cimhub_gridlabd.glm_reader import GlmReader
from cimhub_gridlabd.glm_writer import GlmWriter
from cimhub_gridlabd.importer.glm_to_cimtbl import glm_to_cim

ATOMS = Path("cimhub_gridlabd/tests/atoms")


def round_trip(atom: str):
    """Import an atom deck to CIM and export it again. Returns the exported GlmModel and the time points."""
    time_points = {}
    network = glm_to_cim(GlmReader(ATOMS / atom).read_all(), name="atom", time_points=time_points)
    return GlmExporter(time_points).to_model(network, name_source="name"), time_points


def show(model, *names: str) -> None:
    """Print the exported GLM text of the named objects."""
    writer = GlmWriter()
    for name in names:
        print(writer.serialize(model.by_name(name), model.expressions))

The model name (name="atom") must not be one of the artifact names (load, capacitor, ...), or the artifact files collide. name_source="name" writes each object under its CIM name, which the importer set to the deck's name. The default is the mRID (ld_ld_delta, cap_c_one_A). The load atoms print a warning that the atom's ld_sched reads a player the deck does not define (see player).

load and triplex_load

One EnergyConsumer per GLM load record, mRID ld_ + the name, on the record's root bus. A record whose base reads a player or a schedule is a ConformLoad of that source's group (see player and schedule). A triplex_load and a plain triplex_node that carries power_1, power_2 or power_12 are the split-phase case below. On export an EnergyConsumer, ConformLoad or NonConformLoad each becomes a load (or a triplex_load on a split-phase bus). CIM gives a load no rated voltage: p and q are the totals at nominal voltage, and the exported nominal_voltage is the bus's.

Power per phase. GLM keeps a load's power per phase, in one of two forms. A phase with constant_power_X gives its p + jq in the unit written in the deck (VA, kVA, ...); the importer converts it to the W and VAr of the headers. A phase with base_power_X is GridLAB-D's split of the base by the ZIP fractions and power factors at nominal voltage. For each part k (power, current, impedance), with the power factor defaulting to 1:

Quantity Value
P_k base_power_X x <k>_fraction_X x abs(<k>_pf_X)
Q_k P_k x sqrt(1 / <k>_pf_X^2 - 1), negative when <k>_pf_X is negative (leading)
pf of 0 P_k = 0 and Q_k = base_power_X x <k>_fraction_X
fractions that do not sum to 1 the power fraction becomes 1 - current - impedance, as GridLAB-D does, and the row comment says defaulted: power_fraction_C=0.4

The consumer's p and q are the sums over its phases. When its phases differ, each phase child gets an EnergyConsumerPhase row with its own p and q (an Update Table row, mRID ld_<name>_A). When they are equal, or there is one child, the consumer's total is the value and no phase rows are written.

Phases and connection. A wye load's phases are the letters that carry power; the row leaves phases blank when they are ABC and equal. It is Y and grounded. A load whose phases has D is delta, D and not grounded, and GridLAB-D reads its _A, _B, _C as the branches AB, BC and CA. So the delta load in the atom, with constant_power_C only, is a consumer on AC whose one branch holds all the power. A load with S in its phases raises: a split-phase record is a triplex_load.

Voltage response. One LoadResponse per record, from the totals of its parts:

The record's parts EnergyConsumer.LoadResponse
all constant power, or no power zip_constant_pq
all constant current zip_constant_i
all constant impedance zip_constant_z
a mix a zip_<pP>_<pI>_<pZ>_<qP>_<qI>_<qZ> row in the artifact, the fractions of P and of Q over the totals; two sets that round to the same six places raise

The three shared rows come from the zip_fractions.cimtbl that the master imports.

Split phase. A triplex_load or plain triplex_node has legs 1 and 2 (120 V to neutral) and a 240 V part 12. The legs are one consumer on s1s2, Y, grounded, with child rows for s1 and s2 when they differ. The 240 V part is a second consumer ld_<name>_12, s1s2, D, not grounded. Only the first consumer of a record has customerCount 1: GLM has no customer count, so each record is counted as one service. A load with no power on any phase is still a consumer of p = q = 0 on its wired phases, listed in the artifact's header.

A load on the secondary bus of a one-phase service transformer (a WYE_WYE or SINGLE_PHASE connection on one phase, rated to its coil, with secondary_voltage 0.12 or 0.24 kV) is on that service's split-phase conductors: at 0.12 kV a consumer on s1 to neutral, at 0.24 kV a delta consumer across s1s2. Only one wye phase of a plain load is mapped there; anything else raises with phases ... on a s1N service; one wye phase of a load is mapped there (s1s2N for 0.24 kV).

On export a split-phase bus makes a triplex_load: a wye consumer is the legs _1 and _2, a delta consumer the 240 V part _12. A delta consumer named <base>_12 on the bus of the wye consumer <base> is that record's _12 again, so the importer's two consumers come back as one record. A consumer from another model that has only a 240 V part comes back as a triplex_load with base_power_12, as the atom's tn_load does.

load properties

Property Import Export
name EnergyConsumer.name; mRID ld_ + name (_12 on a 240 V part) the CIM name or mRID (name_source). A 240 V part with a legs consumer <base> on its bus is written inside that record; one alone loses its trailing _12
parent node: the root bus the consumer's bus
phases phases, phaseConnection, grounded (see above); S on a load raises the letters then N (wye) or D (delta); on a split-phase bus the bus's letter then S
nominal_voltage not written: the bus's BaseVoltage the bus's nominal voltage
constant_power_A, _B, _C (_1, _2, _12 on a triplex_load; power_1, power_2, power_12 on a triplex_node) EnergyConsumer.p (W) and q (VAr), and the phase children not written: the export always uses the base form
base_power_X derived: the split above into p, q; <player>.value*K or <schedule>*K is K, with the load a ConformLoad base_power_X = the sum of the three parts' absolute values, from get_phase_loads; a player or schedule base is written as <player>.value*K or <schedule>*K
power_fraction_X, current_fraction_X, impedance_fraction_X derived, with base_power_X; default 0 each part's share of the base, from get_load_response; a part of zero size is not written
power_pf_X, current_pf_X, impedance_pf_X derived, with base_power_X; default 1 the part's P over its absolute value, negative when its Q is
constant_power_X_real, _reac, constant_current_X, constant_impedance_X and their _real, _reac forms raises when set not written
constant_current_AN to constant_impedance_CA (the explicit line-to-neutral and line-to-line forms) raises when set not written
load_class, load_priority untranscribed: sorting only not written
measured_power, measured_voltage_*, measured_power_*, indiv_measured_power_* untranscribed: solver output not written
phase_loss_protection, inrush_integration_method_capacitance, inrush_integration_method_inductance untranscribed: engine options not written
a bus slot of the load (its initial voltage_X and the like) untranscribed: counted once on the table comment not written
power_A, current_A, shunt_A, current_inj_A and the like on a node, meter or other bus raises: a load on the bus itself not applicable
current_*, shunt_* on a triplex_node raises not applicable

An untranscribed value that a deck sets is listed in a # untranscribed: comment on the row, so nothing disappears silently.

On export a ZIP model is read through get_load_response. A voltage-exponent model whose exponents are 0, 1 or 2 is exactly constant power, current or impedance. Any other exponent raises.

load fail-fast rules

Rule Message
base_power_X with constant_power_X load a: base_power_A and constant_power_A are both set; GridLAB-D keeps only the base form (load.cpp:984)
a base that is not <name>.value*<number> or <name>*<number> load a: base_power_A is the expression '5+sin(2)'; only <player>.value*<number> and <schedule>*<number> are mapped
an explicit current, impedance or connection form load a: constant_current_A Complex({'real': 10.0, 'imag': 2.0}); not mapped
S in the phases of a load load a: phases ABCS; a split-phase load is a triplex_load
a load on the bus itself node x: power_A ... is a load on the bus itself; not mapped
two sources on one record, or a phase with power but no source beside one that has it load a: its bases name [...]; a ConformLoad follows one player or schedule
a base naming a schedule the deck does not define schedules ['s9'] are read by loads [['a']] but not defined in the deck
two ZIP sets that round alike load a: its ZIP fractions (...) differ from another load's beyond the 6 places of zip_...
export: a negative p on a part EnergyConsumer 'x': a negative p; GLM's base_power holds consumption only
export: a voltage exponent other than 0, 1, 2 EnergyConsumer 'x': voltage exponents (...); GLM holds 0, 1 or 2 only
export: a delta load on one phase EnergyConsumer 'x': a delta load on one phase
export: a 240 V part that follows another player than its legs EnergyConsumer 'x': the 240 V part of 'y' follows another player; a GLM record's bases follow one

load round trip

What Why
constant_power_X comes back as base_power_X with power_fraction_X 1 and a power_pf_X the export has one form; base_power_X is the apparent power at nominal voltage
a phase with 0+0j is not written a zero part is no part
a load on ABCD with one branch set comes back on ACD the consumer's phases are the phases that carry power
a record that mixes parts on different phases comes back with every phase on the whole load's mix CIM has one LoadResponseCharacteristic per consumer. The atom's ld_zip has 100 kVA on A and 50 kVA on C, and comes back as 94.6 kVA and 38.2 kVA with the same fractions on both
a triplex_node with power_12 comes back as a triplex_load CIM does not tell them apart
load_class, load_priority, the measured and engine slots are not written untranscribed
nominal_voltage is the bus's (2401.777 for the deck's 2401.78) it follows the BaseVoltage
customerCount is not written GLM has no customer count
a group with no schedule or no points, and a NonConformLoad, are written static a reference to no player would not load; one warning names the groups
model, _ = round_trip("load/load.glm")
show(model, "ld_delta", "ld_sched")
object load {
  name "ld_delta";
  parent "n2";
  phases "ACD";
  nominal_voltage 2401.77711982884;
  base_power_C 227378.539004894;
  power_pf_C 0.747651914485831;
  power_fraction_C 1;
}
object load {
  name "ld_sched";
  parent "n5";
  phases "AN";
  nominal_voltage 2401.77711982884;
  base_power_A 19723.08;
  current_pf_A 0.861934;
  current_fraction_A 1;
}

ld_sched reads the player zipsched, which the deck does not define, so it comes back static.

load excerpt

From cimhub_gridlabd/tests/atoms/load/triplex.load.cimtbl (the load artifact of the load atom):

# p, q: the totals at nominal voltage, consumption positive; phases: the phases that carry power, blank when ABC and equal
Table EnergyConsumer: mRID, name, node, phases, phaseConnection, grounded, p (W), q (VAr), customerCount, LoadResponse, BaseVoltage, EquipmentContainer=fdr_atom
    ld_ld_bal,   ld_bal,   n2, ,   Y, true,  300000.0, 150000.0,          1, zip_constant_pq,                                    bv_4p16kv
    ld_ld_delta, ld_delta, n2, AC, D, false, 170000.0, 151000.0,          1, zip_constant_pq,                                    bv_4p16kv
    # untranscribed: load_class=R
    ld_ld_wye,   ld_wye,   n2, AC, Y, true,  20000.0,  7000.0,            1, zip_constant_pq,                                    bv_4p16kv

# the phases differ, so each child carries its own p, q (a delta child is its branch)
Update Table EnergyConsumerPhase: mRID, p (W), q (VAr)
    ld_ld_wye_A, 12000.0, 4000.0
    ld_ld_wye_C, 8000.0,  3000.0

ld_bal is balanced on ABC, so phases is blank and it has no phase rows. ld_delta is the 170 + 151j kVA branch written as constant_power_C. The triplex part of the same atom is in cimhub_gridlabd/tests/atoms/load/triplex.triplex_load.cimtbl:

Table EnergyConsumer: mRID, name, node, phases, phaseConnection, grounded, p (W), q (VAr), customerCount, LoadResponse, BaseVoltage, EquipmentContainer=fdr_atom
    ld_tl_legs,    tl_legs,    tm1, s1s2, Y, true,  4500.0, 1800.0, 1, zip_constant_pq, bv_240v
    ld_tl_legs_12, tl_legs_12, tm1, s1s2, D, false, 4000.0, 1500.0, ,  zip_constant_pq, bv_240v

capacitor

GridLAB-D switches each capacitor phase on its own. Under control_level INDIVIDUAL, the default, a VOLT control switches only the phases in pt_phase, each on its own phase voltage, and leaves the other phases in their starting state. The importer follows that: a CIM unit is a set of phases that switch together.

Capacitor Units Control
MANUAL (the default), any control_level one gang unit on the connected phases, mRID cap_<name> none
VOLT, BANK one gang unit one RegulatingControl cc_<name> on the one phase of pt_phase
VOLT, INDIVIDUAL one 1-phase unit per connected phase, cap_<name>_<phase> one cc_<name>_<phase> on each unit whose phase is in pt_phase; the others stay at their starting state

So a 3-phase VOLT capacitor with pt_phase B becomes three 1-phase units and one control, on B. GridLAB-D runs it that way. A run of the same feeder written as a single gang unit switched on B (what a DSS import of a DSS-authored deck gives) is a different run: up to two thirds of the bank's kVAr differs whenever B closes. A cross-format check of a GLM capacitor should compare per-phase switched kVAr against GridLAB-D's own solution.

A unit is wye and grounded, with or without N on phases_connected (else phases): GridLAB-D puts the shunt phase to ground either way. Each unit carries these values:

CIM attribute Value
nomQ the sum of the unit's capacitor_X, in the unit the deck wrote them in (VAr, kVAr, MVAr; one per unit)
nomU cap_nominal_voltage (line to neutral; else the bus's nominal_voltage), times sqrt 3 on a 2- or 3-phase unit, in its written unit
bPerSection nomQ / nomU^2 in those units (MVAr/V^2), which cimtables stores in S and the shunt getter reads back as Q = b x nomU^2 x sections
sections, normalSections 1 when the phase's switchX is CLOSED, else 0; an unset switch is OPEN, GridLAB-D's default
maximumSections 1

The control is a RegulatingControl of mode voltage, discrete and enabled. It monitors the unit's own terminal (<unit>_T1) on the controlled phase, in primary phase-to-neutral volts, with no PT. voltage_set_low and voltage_set_high become targetValue (their midpoint) and targetDeadband (their difference): the unit closes at or below the low value and opens at or above the high one. The unit's Update Table row sets aVRDelay (s) to dwell_time + time_delay and controlEnabled true.

capacitor properties

Property Import Export
name LinearShuntCompensator.name = name, or <name>_<phase> for a 1-phase unit of an INDIVIDUAL VOLT capacitor; mRID cap_ + that; control cc_ + that the CIM name; the 1-phase units <base>_<phase> on one bus, one of them with a voltage control, are the capacitor <base> again
parent node: the root bus the unit's bus
phases_connected (else phases) the unit's phases, Y, grounded; D raises phases and phases_connected are the unit's letters then N
nominal_voltage not written: the bus's BaseVoltage the bus's
capacitor_A, capacitor_B, capacitor_C nomQ (the unit's sum, in its written unit) and bPerSection; a phase that is not connected is dropped and listed in the row comment each phase's Q at nomU with every section in (get_shunt_reactive_power, sections='maximum')
cap_nominal_voltage nomU (V) (see above); unset with no nominal_voltage raises nomU line to neutral: over sqrt 3 on a polyphase unit, rounded to 6 places
switchA, switchB, switchC sections and normalSections; default OPEN; a gang unit's must agree CLOSED when the unit's actual sections are above 0, else OPEN
control VOLT: a RegulatingControl; MANUAL: none; VAR, VARVOLT, CURRENT raise VOLT for an enabled voltage control, else MANUAL; a control of another mode is MANUAL at the actual state, with a warning
control_level picks the units (table above) INDIVIDUAL for a split capacitor or when every controlled unit is one phase, else BANK
pt_phase the units that get a control (INDIVIDUAL) or the monitored phase (BANK); with D it raises the control's monitored phases, else the unit's own
voltage_set_low, voltage_set_high RegulatingControl.targetValue, targetDeadband (V); VOLT without both raises target - deadband / 2, target + deadband / 2
dwell_time, time_delay LinearShuntCompensator.aVRDelay (s) = the sum; both default 0 dwell_time = aVRDelay
remote_sense, remote_sense_B, voltage_deadband, VAr_deadband, current_deadband and their _center forms raises when set (a negative deadband is GridLAB-D's unset) not written
VAr_set_high, VAr_set_low, current_set_high, current_set_low, lockout_time untranscribed: read only by the unmapped modes not written
cap_A_switch_count, cap_B_switch_count, cap_C_switch_count untranscribed: solver output not written

The importer lists the defaults it applied in a # defaulted: comment and the values of unconnected phases in a # not connected comment. For a MANUAL capacitor, a pt_phase or set points it carries go in a # MANUAL: not read comment.

capacitor fail-fast rules

Rule Message
control other than MANUAL or VOLT capacitor c: control VAR; MANUAL, VOLT are mapped
a delta phases_connected or pt_phase capacitor c: phases_connected ABCD; a delta capacitor is not mapped
remote_sense or a deadband set capacitor c: remote_sense ...; not mapped
VOLT with no pt_phase, or one off the connected phases capacitor c: pt_phase unset must name connected phases of ABC
VOLT without both voltage set points capacitor c: VOLT without voltage_set_low and voltage_set_high
a BANK that monitors more than one phase capacitor c: a BANK monitors one phase, pt_phase is AB
a gang unit whose switch states differ capacitor c: switch states ['CLOSED', 'OPEN'] differ on a gang unit (MANUAL or BANK)
a gang unit whose phases differ in VAr capacitor c: phases ABC differ ([1000.0, 2000.0, 1000.0] VAr) on a gang unit; a per-phase rating is not mapped
a unit whose phases are written in different units capacitor c: phases ABC are written in ['MVAr', 'kVAr']; one unit per unit
a connected phase with no capacitor_X capacitor c: capacitor_B unset or 0 on a connected phase
no cap_nominal_voltage and no nominal_voltage capacitor c: no cap_nominal_voltage and no nominal_voltage
no connected phase capacitor c: no phase connected
export: a delta unit LinearShuntCompensator 'x': a delta capacitor is not exported yet
export: units of one capacitor at different voltages LinearShuntCompensators [...]: rated at [...] V
export: units with different VOLT settings LinearShuntCompensators [...]: different VOLT settings
export: a voltage control with no deadband LinearShuntCompensator 'x': a voltage control without a deadband

capacitor round trip

What Why
the 1-phase units of an INDIVIDUAL capacitor come back as the one capacitor, VOLT on the controlled phases the exporter joins units named <base>_<phase> on one bus when one of them has a voltage control; a MANUAL cap_B keeps its name
a MANUAL 3-phase capacitor comes back with phases ABCN a unit is wye and grounded with or without N
time_delay comes back inside dwell_time CIM has one delay, aVRDelay
a capacitor_X on a phase that is not connected is not written GridLAB-D ignores it
nominal_voltage is the bus's it follows the BaseVoltage
a unit with only some of its sections in is CLOSED with every section in GLM has one switch per phase
a control with another mode, or a disabled one, is not written GLM's control has no form for it; the unit is MANUAL at its actual state (a control of another mode logs a warning)
a delta unit raises on export GLM's delta capacitor is not mapped either way
model, _ = round_trip("capacitor/capacitor.glm")
show(model, "c_one")
object capacitor {
  name "c_one";
  parent "n5";
  phases "AN";
  nominal_voltage 2401.77711982884;
  pt_phase "A";
  phases_connected "AN";
  switchA "CLOSED";
  control "VOLT";
  voltage_set_high 2500;
  voltage_set_low 2350;
  capacitor_A 50000;
  cap_nominal_voltage 2401.78;
  dwell_time 0;
  control_level "INDIVIDUAL";
}

capacitor excerpt

From cimhub_gridlabd/tests/atoms/capacitor/capacitor.capacitor.cimtbl:

Table LinearShuntCompensator: mRID, name, node, phases, phaseConnection=Y, grounded=true, nomQ (MVAr), nomU (V), bPerSection (MVAr/V^2), sections, normalSections, maximumSections=1, BaseVoltage, EquipmentContainer=fdr_atom
    # defaulted: time_delay=0.0, dwell_time=0.0, control_level=INDIVIDUAL
    # not connected (GridLAB-D ignores it): capacitor_B=0.05 MVAr, capacitor_C=0.05 MVAr
    cap_c_one_A,  c_one_A,  n5, A, 0.05, 2401.78, 8.667693708720823e-09,  1, 1, bv_4p16kv
    cap_c_volt_B, c_volt_B, n2, B, 0.15, 2401.78, 2.6003081126162464e-08, 0, 0, bv_4p16kv

Table RegulatingControl: mRID, name, mode=voltage, discrete=true, enabled=true, monitoredPhase, targetValue, targetDeadband, Terminal
    cc_c_volt_B, c_volt_B, B, 2425.0, 150.0, cap_c_volt_B_T1

Update Table LinearShuntCompensator: mRID, RegulatingControl, aVRDelay (s), controlEnabled=true
    cap_c_volt_B, cc_c_volt_B, 45.0

c_volt is a 3-phase VOLT capacitor with pt_phase B, so only B has a control. The deck gives voltage_set_low 2350 and voltage_set_high 2500, so the target is 2425 V and the deadband 150 V.

player

A load base <player>.value*K scales K by the player's value over time. It is read the way GridAPPS-D's run file declares it: module tape;, class player { double value; }, then object player { name zipload; file zipload.player; }. One player can drive many loads, so a player is a group of conform loads with one regular schedule of multipliers. Each GLM load whose base names it is a ConformLoad of the group, and its p, q are K (the base) split as above, not scaled by the player.

CIM class mRID Attributes
ConformLoadGroup lg_<player> name
ConformLoadSchedule ls_<player> name, startTime (the first row's time, with a UTC offset), timeStep (s), value1Unit none, ConformLoadGroup
RegularTimePoint (sidecar) the schedule's uri sequenceNumber from 0, value1

The points go to the caller's time_points dict, not into player.cimtbl: pass time_points={} to GlmImporter or glm_to_cim. Without it the points drop with one warning. A player that a load names but the deck does not define (the Java exports' run file defines ieeezipload, which no deck does) becomes a group with no schedule and one warning, so the name survives.

On export, a ConformLoadSchedule of a group with points is a player named after the group, its file <name>.player beside the deck (written by GlmWriter.write). The first row is at startTime in GMT, which GridLAB-D reads under any clock zone; each later row is +<step>s. Each ConformLoad of the group writes its bases as <player>.value*K. The deck's clock starts at the earliest player start, so each base is K times the first point; a later stoptime plays the schedule.

player properties

Property Import Export
name ConformLoadGroup.name, ConformLoadSchedule.name; mRIDs lg_ / ls_ + name the group's name
file structural: the rows give startTime, timeStep and the points; unset raises <name>.player, written beside the deck
parent, property, filetype, mode structural: must be unset; set raises not written
loop structural: unset or 0; a repeated tape raises not written
groupid, latitude, longitude, in_svc, out_svc, rank, flags untranscribed: object header not written
all_events_delta untranscribed: an engine option not written
a row's time the first row an absolute YYYY-MM-DD HH:MM:SS ZONE, each later one +N[smhd] after the row before or absolute startTime as GMT, then +<step>s
a row's value RegularTimePoint.value1 value1; a value2 other than value1 raises

The zones the importer reads are UTC, GMT, EST, EDT, CST, CDT, MST, MDT, PST and PDT; each becomes a fixed offset (2009-07-21 00:00:00 EDT is 2009-07-21T00:00:00-04:00). The one step between rows is the timeStep; a one-row tape has no step.

player fail-fast rules

Rule Message
parent, property, filetype or mode set player zl: parent a; only a player read as zl.value is mapped
loop above 0 player zl: loop 2; a repeated tape is not mapped
no file player zl: no file; its rows are the schedule
a file with no rows player zl: its file zipload.player has no rows
no class player { double value; } in the deck player zl: read as zl.value, but the deck has no class player { double value; }
a row time that is not absolute and not +N[smhd] player zl: row time '...'; an absolute 'YYYY-MM-DD HH:MM:SS ZONE' or +N[smhd] after the first row is mapped
a zone that is not one of the ten above player zl: zone XYZ; mapped: UTC, GMT, EST, EDT, CST, CDT, MST, MDT, PST, PDT
steps between rows that differ player zl: steps of [60.0, 120.0] s; a ConformLoadSchedule has one step
a row value that is not a number player zl: row value 'x' is not a number
a player and a schedule of one name ['x'] are both a schedule and a player; their load groups would share lg_<name>
export: a value2 other than value1 ConformLoadSchedule ...: value2 differs from value1; a GLM base scales p and q together
export: a startTime with no UTC offset ConformLoadSchedule ...: startTime ... has no UTC offset
export: a timeStep that is not whole seconds ConformLoadSchedule ...: timeStep ... s; a player steps in whole seconds

player round trip

What Why
the start comes back in GMT (2009-07-21 04:00:00 GMT for 00:00 EDT) the same instant; GridLAB-D reads GMT under any clock zone
+1m steps come back as +60s CIM holds timeStep in seconds
a group with no schedule, a schedule with no points and a NonConformLoad are written static one warning names the groups; a reference to no player would not load
model, time_points = round_trip("player/player.glm")
print(model.tapes)
show(model, "ld_play")
{'zipload': [('2009-07-21 04:00:00 GMT', '0.425364'), ('+60s', '0.42153'), ('+60s', '0.418488'), ('+60s', '0.39988')]}
object load {
  name "ld_play";
  parent "n5";
  phases "AN";
  nominal_voltage 2401.77711982884;
  base_power_A zipload.value*19723.08;
  current_pf_A 0.861934;
  current_fraction_A 1;
}

player excerpt

From cimhub_gridlabd/tests/atoms/player/player.player.cimtbl:

Table ConformLoadGroup: mRID, name
    lg_zipload, zipload

Table ConformLoadSchedule: mRID, name, startTime, timeStep (s), value1Unit, ConformLoadGroup
    # untranscribed: all_events_delta=false
    ls_zipload, zipload, 2009-07-21T00:00:00-04:00, 60.0, none, lg_zipload

and its load, from cimhub_gridlabd/tests/atoms/player/player.load.cimtbl:

Table ConformLoad: mRID, name, node, phases, phaseConnection, grounded, p (W), q (VAr), customerCount, LoadResponse, BaseVoltage, LoadGroup, EquipmentContainer=fdr_atom
    ld_ld_play, ld_play, n5, A, Y, true, 16999.99323672, 10000.005731892072, 1, zip_constant_i, bv_4p16kv, lg_zipload

schedule

A load base <schedule>*K scales K by a GridLAB-D schedule block, a set of cron rules minutes hours days months weekdays [value]. GridLAB-D reads the ranges as inclusive, months from 1, weekdays from 0 = Sunday, a rule with no value as 1 and a time no rule covers as 0; two rules on one minute fail to load. One schedule drives many loads, so it is a ConformLoadGroup lg_<schedule>, and its loads are ConformLoads of it, as for a player. A schedule recurs by day of the year and week, which CIM's SeasonDayTypeSchedule holds, so the curve is one ConformLoadSchedule per Season and DayType, each a day of multipliers.

CIM class mRID Rule
Season season_<first>_<last> (two-digit months) a run of consecutive months whose seven weekdays agree; December's run joins January's. startDate --MM-01, endDate the last month's last day (February's 29th)
DayType dt_<name> the weekdays that agree within a season, named all, weekday, weekend, sunday to saturday; another set joins the day names with _ (monday_wednesday)
ConformLoadGroup lg_<schedule> name
ConformLoadSchedule ls_<schedule> for a one-day schedule, else ls_<schedule>_<first>_<last>_<day type> startTime 00:00:00, timeStep (min) the coarsest step on which the day's value only changes at step boundaries, value1Unit none, Season, DayType, ConformLoadGroup
RegularTimePoint (sidecar) the schedule's uri sequenceNumber from 0 (midnight), value1

A day that no rule covers is a schedule of one point of 0. Only the schedules that a load's base reads are mapped; the others (a house's) are not, and the master's comment counts them (not mapped: schedule 1).

On export, a conform group whose schedules each hold a Season or DayType and have points is a schedule block named after the group, written before the objects. Each day becomes rules: each run of equal values, split at the hours (7-59 1, * 2-5, 0-14 6), on the season's months (* for the year, 12,1-2 across December) and the day type's weekdays. A value of 0 is no rule, which is GridLAB-D's value where none applies. Each ConformLoad of the group writes its bases as <schedule>*K.

schedule properties

Property Import Export
the block's name ConformLoadGroup.name; mRID lg_ + name the group's name
a rule's minutes, hours, months, weekdays the day of multipliers per (season, day type), RegularTimePoint.value1 the cron fields of each run of equal values
a rule's days must be *; another day of the month raises *
a rule's value the multiplier; omitted is 1 the value; 0 is no rule
a field *, a number, a-b or a comma list of them, inside its range; anything else raises the same forms
a nested block (weekday { ... }) raises not written

schedule fail-fast rules

Rule Message
a day of the month other than * schedule s1: rule '0 0 5 * * 1' names days of the month 5; no Season or DayType holds them
two rules on one minute schedule s1: two rules cover monday of month 1 at 00:00; GridLAB-D rejects the overlap
a rule with fewer than five or more than six fields schedule s1: rule '...'; 'minutes hours days months weekdays [value]' is mapped
a field that is not *, a number, a range or a list of them schedule s1: rule '...': 'x' is not *, a number, a range or a list of them
a number outside its field's range schedule s1: rule '...': 61 is outside 0-59
a value that is not a number schedule s1: rule '...': the value 'x' is not a number
a nested block schedule s1: a nested block ('...') is not mapped
a base naming a schedule the deck does not define schedules ['s9'] are read by loads [['a']] but not defined in the deck
export: a day whose startTime is not 00:00:00 ConformLoadSchedule ...: startTime ...; a GLM schedule's day starts at 00:00:00
export: a day whose points do not fill 24 h in whole minutes ConformLoadSchedule ...: 7 points of 60.0 min; a GLM schedule's day is 1440 whole minutes
export: a season off whole months ConformLoadSchedule ...: season ... to ...; a GLM schedule's months are whole
export: a day type that is not all, weekday, weekend or day names joined by _ ConformLoadSchedule ...: day type 'x'; all, weekday, weekend or day names joined by _ are read
export: two days on one month and weekday ... both cover monday of month 1; a GLM schedule gives one value at a time
export: a value2 other than value1 as for a player

schedule round trip

What Why
the rules come back as written but for spacing, number form and rule order the exporter rebuilds them from the days
a rule of value 0 is not written GridLAB-D's value where none applies
a schedule no load reads is not exported it was not imported
a group one of whose days has no points is written static one warning names the group
model, _ = round_trip("schedule/schedule.glm")
print(model.schedules["heat"])
show(model, "ld_zip")
['* 6-21 * 3-11 1-5 0.6', '* 0-6 * 12,1-2 1-5 1.2', '* 7-23 * 12,1-2 1-5 0.9', '* * * 12,1-2 0,6 1.1']
object load {
  name "ld_zip";
  parent "n5";
  phases "AN";
  nominal_voltage 2401.77711982884;
  base_power_A zip1*19723.08;
  current_pf_A 0.861934;
  current_fraction_A 1;
}

schedule excerpt

From cimhub_gridlabd/tests/atoms/schedule/schedule.schedule.cimtbl:

Table Season: mRID, name, startDate, endDate
    season_01_12, 01-12, --01-01, --12-31
    season_03_11, 03-11, --03-01, --11-30
    season_12_02, 12-02, --12-01, --02-29

Table DayType: mRID, name
    dt_all,     all
    dt_weekday, weekday
    dt_weekend, weekend

Table ConformLoadSchedule: mRID, name, startTime, timeStep (min), value1Unit, Season, DayType, ConformLoadGroup
    ls_heat_12_02_weekend, heat, 00:00:00, 1440, none, season_12_02, dt_weekend, lg_heat
    ls_heat_12_02_weekday, heat, 00:00:00, 60,   none, season_12_02, dt_weekday, lg_heat
    ls_zip1,               zip1, 00:00:00, 30,   none, season_01_12, dt_all,     lg_zip1

The heat schedule in the atom has a winter (12,1-2) and the rest of the year, each with weekday and weekend days, and a summer weekend with no rule, which is a day of one point of 0. zip1 is one day of 48 half-hour points, every day of the year.