Inverters, solar and batteries

This page is the conversion reference for the GridLAB-D classes that inject power through an inverter: inverter with its nested solar or battery. For each one it says what the importer writes, what the exporter reads back and what raises. The field classes (copied, mapped, structural, derived, untranscribed) and the conventions every section follows are on the reference index. The getters the exporter reads through, and the sign rules, are on the core site's sources, DER and machines page.

GLM class CIM classes .cimtbl artifact and shape Importer Exporter
inverter with a solar child PowerElectronicsConnection, PhotoVoltaicUnit, and the datasheets GenerationInverterInfo, SolarArrayInfo, SolarPanelInfo inverter.cimtbl, shape der importer/cimtbl/inverter.py exporter/inverter.py
inverter with a battery child PowerElectronicsConnection, BatteryUnit, and the datasheets StorageInverterInfo, BatteryInfo inverter.cimtbl, shape der importer/cimtbl/inverter.py exporter/inverter.py
solar the PhotoVoltaicUnit and its datasheets in inverter.cimtbl importer/cimtbl/inverter.py exporter/inverter.py
battery the BatteryUnit and its BatteryInfo in inverter.cimtbl importer/cimtbl/inverter.py exporter/inverter.py

All three GLM classes are one artifact, inverter.cimtbl: a solar or battery is the child of its inverter (its parent is the inverter), and GridLAB-D requires a battery's parent to be one. The table shapes are on the core site's shapes page. Source paths are under cimhub_gridlabd/src/cimhub_gridlabd/. The master imports inverter.cimtbl after capacitor.cimtbl; it references only buses and its own datasheets.

Quoted error messages leave off the spec code in parentheses that ends some of them. Most start with the GLM class and name, as inverter i:.

The examples run from the repository root with uv run python. They convert the public test atom cimhub_gridlabd/tests/atoms/inverter/inverter.glm to CIM and back. This helper is shared by all of them:

from pathlib import Path

from cimhub_gridlabd.exporter.cim_to_glm import GlmExporter
from cimhub_gridlabd.glm_reader import GlmReader
from cimhub_gridlabd.glm_writer import GlmWriter
from cimhub_gridlabd.importer.glm_to_cimtbl import glm_to_cim

ATOMS = Path("cimhub_gridlabd/tests/atoms")


def round_trip(atom: str):
    """Import an atom deck to CIM and export it again. Returns the exported GlmModel and the CIM network."""
    network = glm_to_cim(GlmReader(ATOMS / atom).read_all(), name="atom")
    return GlmExporter().to_model(network, name_source="name"), network


def show(model, *names: str) -> None:
    """Print the exported GLM text of the named objects."""
    writer = GlmWriter()
    for name in names:
        print(writer.serialize(model.by_name(name)))

name="atom" must not be one of the artifact names, or the artifact files collide. name_source="name" writes each object under its CIM name, which the importer set to the deck's name. The default is the mRID (pv_inv_pv1, storage_inv_b3).

Sign convention

CIM's terminal sign is the load's: p and q are positive into the equipment. A PV array and a discharging battery therefore have negative p, and a charging battery positive. GLM's P_Out and Q_Out are in the generation sign, so the importer writes p = minus the output, and the exporter asks the getters for sign="generation". A battery's minP is its charging power, negative in the generation sign, so the importer writes minP = minus rated_power. The getters' sign rules are on the core site's DER page.

inverter

One PowerElectronicsConnection per inverter, on its parent's root bus, with its one child as the unit. Its mRID is pv_<name> with a solar and storage_<name> with a battery, and the unit is <connection>_unit. An inverter with no child, with more than one, or with a child whose parent is not an inverter raises: GridLAB-D has no hybrid inverter model. The inverter is FOUR_QUADRANT; any other inverter_type, and an unset one (which GridLAB-D reads as a PWM inverter), raise.

Ratings. rated_power is per phase. The inverter's phases give the phases it outputs:

GLM phases CIM phases, phaseConnection Phases out ratedU
A, B, C letters (with N) the letters, Y (3 phases: blank, the balanced default) 1, 2 or 3 the bus's line-to-line voltage
S s1s2, D: across the legs 1 240 V, the bus's
a D or any other letter raises

GridLAB-D has no delta inverter. ratedS = rated_power x phases out, and maxQ = ratedS, minQ = -ratedS: GridLAB-D's four-quadrant inverter caps the total apparent power at that. normallyInService is false when generator_status is OFFLINE, and the output is then 0. V_base is untranscribed, since ratedU is the bus's. The inverter's datasheet holds the nameplate: GenerationInverterInfo under a solar and StorageInverterInfo under a battery, both with apparentPowerMaximum, reactivePowerInjectedMax and reactivePowerAbsorbedMax = ratedS, and on storage chargeRateActiveMax = max_charge_rate.

Control modes. GridLAB-D runs one four_quadrant_control_mode per inverter, and the importer maps the one dispatch each unit has:

Unit four_quadrant_control_mode Result
solar CONSTANT_PF, also the default when unset GridLAB-D's static-weather output (below); a \|power_factor\| other than 1 raises, so q is 0
solar any other mode raises
battery CONSTANT_PQ the set point P_Out, limited as below; Q_Out other than 0 or unset raises, so q is 0
battery CONSTANT_PF, also the default when unset read as CONSTANT_PQ, with a row comment: GridLAB-D never dispatches a CONSTANT_PF battery, so a deck that wrote it meant CONSTANT_PQ. A power_factor it carries goes in the comment
battery any other mode raises

The row comment of every connection names the capability flag that the mode as read stands for (capability: isModeCapableConstantPowerFactor for a PV, isModeCapableActivePowerReactivePower for a battery). The InverterCapabilities object itself is not written yet, because cim-tables cannot reference that kind of row. The volt-var, volt-watt, frequency-watt, load-following, group and voltage-source modes, and the multipoint efficiency model, raise. Their slots are untranscribed.

A solar's output is GridLAB-D's own static-weather result, with no climate object: a solar with a weather or a deck with a climate object raises. With the solar's values after defaults:

Quantity Formula
insolation Rated_Insolation x shading_factor (W/ft^2)
module temperature, degF 59 + (NOCT - 68) / 74.32 x insolation
DC output rated_power x insolation / Rated_Insolation x (1 + Pmax_temp_coeff x (module temperature - 77)) x derating x soiling
CIM p -min(DC x inverter_efficiency, ratedS), or 0 when OFFLINE

The defaults are GridLAB-D's: panel_type SINGLE_CRYSTAL_SILICON, NOCT 118.4, Rated_Insolation 92.902 W/ft^2 (1000 W/m^2), shading_factor 1, soiling and derating 0.95, inverter_efficiency 0.9 and power_factor 1. An unset efficiency and Pmax_temp_coeff default by panel type:

panel_type efficiency Pmax_temp_coeff (per degF)
SINGLE_CRYSTAL_SILICON 0.2 -0.00437 / 33.8
MULTI_CRYSTAL_SILICON 0.15 -0.00416 / 33.8
AMORPHOUS_SILICON 0.07 0.1745 / 33.8
THIN_FILM_GA_AS 0.3 0
CONCENTRATOR 0.15 0
any other 0.1 0

The written P_Out of a solar is an output that GridLAB-D overwrites, so it is not read: the row comment gives it beside GridLAB-D's DC output and module temperature (an unset P_Out shows as None).

A battery's output is GridLAB-D's CONSTANT_PQ limit applied to P_Out (generation sign, default 0): 0 when it asks to charge a full battery (state_of_charge at least 1) or to discharge at or below soc_reserve, else capped at ratedS. CIM p is minus that. The row comment says when the set point was limited. batteryState is discharging for p below 0, charging above 0 and waiting at 0.

inverter properties

Property Import Export
name PowerElectronicsConnection.name; mRID pv_ or storage_ + name the connection's name, or <connection>_<n> for each of several units
parent node: the parent's root bus; a parent that is not a bus object raises the connection's bus
phases phases, phaseConnection (table above) the letters then N; on a split-phase bus the bus's letter then S
inverter_type structural: FOUR_QUADRANT FOUR_QUADRANT
four_quadrant_control_mode structural: the dispatch above a battery CONSTANT_PQ, a PV CONSTANT_PF
generator_status normallyInService: ONLINE (default) true, OFFLINE false OFFLINE when normallyInService is false, else ONLINE
rated_power ratedS (VA) = it x phases out; maxQ, minQ = +-ratedS; the datasheet's apparentPowerMaximum; unset or 0 raises ratedS x the unit's share / phases out
inverter_efficiency derived into p (PV); CIM has no inverter efficiency. Unset, 0 or negative is 0.9, as GridLAB-D runs it a PV's 1: the losses are in CIM's p
P_Out derived into p: a battery's set point (generation sign); a PV's only in the comment a battery's p, generation sign (get_inverter_units)
Q_Out a battery: 0 or unset, else raises a battery's q, generation sign
power_factor a PV: \|pf\| 1, else raises (default 1); a battery: only in the comment a PV's p / abs(p + jq), negative when q is; 1 at no output
soc_reserve BatteryUnit.minimumE (Wh) = it x battery_capacity; default 0 a battery's minimumE / ratedE
max_charge_rate StorageInverterInfo.chargeRateActiveMax (W), copied the StorageInverterInfo's chargeRateActiveMax x the unit's share
use_multipoint_efficiency, pf_reg structural: FALSE and EXCLUDED (the defaults); another value raises not written
V_base untranscribed: read only by the volt-var and volt-watt modes not written
generator_mode, sense_object, max_discharge_rate, the charge and discharge thresholds and lockout times untranscribed: read only by load following and the non-four-quadrant types not written (max_discharge_rate has no CIM home)
the volt-var, volt-watt, frequency-power, VSI, droop, IEEE 1547 and deltamode slots untranscribed: dynamics, not the steady-state snapshot not written
solver state (VA_Out, I_In, phaseA_I_Out, ...) untranscribed: solver output not written
the object header (groupid, latitude, longitude, in_svc, out_svc, rank, flags) untranscribed not written

Every inverter slot is classified, and one that is not in a group raises, so a new schema slot is never silently untranscribed. A value that a deck sets and the importer does not read is listed in the row's # untranscribed: comment, and the defaults it applied in # defaulted:.

inverter fail-fast rules

Rule Message
inverter_type not FOUR_QUADRANT, or unset inverter i: inverter_type unset (PWM); FOUR_QUADRANT is mapped
use_multipoint_efficiency TRUE inverter i: use_multipoint_efficiency TRUE; not mapped
pf_reg other than EXCLUDED inverter i: pf_reg INCLUDED; not mapped
a letter other than A, B, C, N or S in phases inverter i: phases ABCD; A, B, C, N and S are an inverter's
no A, B, C or S in phases inverter i: phases N; no phase
rated_power unset or 0 (GridLAB-D would use 25 kVA) inverter i: rated_power unset or 0; GridLAB-D would use 25 kVA per phase (inverter.cpp:1409)
no solar or battery child, or several inverter i: has 0 solar or battery children; one is mapped
a solar or battery whose parent is not an inverter solar s: parent x is not an inverter; not mapped
a solar not in CONSTANT_PF inverter i: four_quadrant_control_mode CONSTANT_PQ on a solar; CONSTANT_PF is mapped
a battery in any mode but CONSTANT_PQ or CONSTANT_PF inverter i: four_quadrant_control_mode VOLT_VAR on a battery; CONSTANT_PQ is mapped
power_factor with absolute value other than 1 on a solar (the message says < 1) inverter i: power_factor 0.9; \|pf\| < 1 is not mapped
a non-zero Q_Out on a battery inverter i: Q_Out 5.0; a non-zero CONSTANT_PQ Q is not mapped

inverter round trip

What Why
a solar's P_Out is not written; its power_factor is the PV is CONSTANT_PF and GridLAB-D computes the output
a battery comes back at its limited set point a charging full battery or a discharging battery at its reserve comes back with P_Out 0
a CONSTANT_PF battery comes back CONSTANT_PQ the importer read it as CONSTANT_PQ
rated_power is per phase again ratedS over the phases; a split-phase inverter's is the whole
a unit that CIM shares with others is its own inverter, <connection>_<n> each of several PowerElectronicsUnits of one connection takes its maxP share of ratedS, q and the charge rate
V_base, generator_mode, sense_object, max_discharge_rate and the other untranscribed slots are not written GridLAB-D's defaults
model, _ = round_trip("inverter/inverter.glm")
show(model, "inv_b3", "b3")
object inverter {
  name "inv_b3";
  parent "n2";
  inverter_type "FOUR_QUADRANT";
  four_quadrant_control_mode "CONSTANT_PQ";
  generator_status "ONLINE";
  P_Out 50000;
  Q_Out 0;
  rated_power 33333.333;
  soc_reserve 0.2;
  phases "ABCN";
  max_charge_rate 80000;
}
object battery {
  name "b3";
  parent "inv_b3";
  use_internal_battery_model TRUE;
  battery_type "LI_ION";
  rated_power 100000;
  battery_capacity 200000;
  round_trip_efficiency 0.86;
  state_of_charge 0.6;
}

inverter excerpt

From cimhub_gridlabd/tests/atoms/inverter/inverter.inverter.cimtbl, the split-phase PV inv_pvs and the split-phase battery inv_bpf (a CONSTANT_PF battery, read as CONSTANT_PQ):

Table PowerElectronicsConnection: mRID, name, node, phases, phaseConnection, ratedS (VA), ratedU (V), p (W), q (VAr), maxQ (VAr), minQ (VAr), normallyInService, AssetDatasheet, BaseVoltage, EquipmentContainer=fdr_atom
    # defaulted: generator_status=ONLINE, Q_Out=0.0
    # four_quadrant_control_mode CONSTANT_PF read as CONSTANT_PQ (a Java export defect: GridLAB-D never dispatches a CONSTANT_PF battery)
    # CONSTANT_PQ: not read: power_factor=-1.0
    # capability: isModeCapableActivePowerReactivePower (InverterCapabilities not written: cim-tables cannot reference an Identity row yet)
    # untranscribed: generator_mode=CONSTANT_PQ, sense_object=tm1
    storage_inv_bpf,   inv_bpf,   tm1, s1s2, D, 5000.0,    240.0,  3000.0,              0.0, 5000.0,    -5000.0,    true,  storage_inv_bpf_info,   bv_240v
    # defaulted: generator_status=ONLINE
    # P_Out as written (GridLAB-D recomputes it): 4000.0 VA; GridLAB-D's: DC 5965.091 W at Tmodule 122.001 degF
    # capability: isModeCapableConstantPowerFactor (InverterCapabilities not written: cim-tables cannot reference an Identity row yet)
    # untranscribed: V_base=208.0
    pv_inv_pvs,        inv_pvs,   tm1, s1s2, D, 5000.0,    240.0,  -5000.0,             0.0, 5000.0,    -5000.0,    true,  pv_inv_pvs_info,        bv_240v

Both are s1s2 D at 240 V. The PV's DC output of 5965 W is above ratedS (5000 VA), so p is capped at -5000 W. The battery's P_Out of -3000 W is a charge of 3000 W, so p is +3000.

solar

Each solar is the PhotoVoltaicUnit of its inverter, mRID <connection>_unit, with an AssetDatasheet that is a SolarArrayInfo (<connection>_array) holding one SolarPanelInfo (<connection>_panel). The unit's maxP is rated_power and minP is 0. The panel's referenceTemperature is the 25 degC default (GridLAB-D's 77 degF rating point). irradiance (W/m^2) is the static-weather insolation, Rated_Insolation x shading_factor, which is the value that goes into the output formula above.

solar properties

Property Import Export
name PhotoVoltaicUnit.name; mRID <connection>_unit the unit's name
parent structural: its inverter; another parent raises the inverter
rated_power PhotoVoltaicUnit.maxP (W), minP 0, and the DC output; unset or 0 raises maxP; a maxP that is unset raises
Rated_Insolation SolarPanelInfo.referenceIrradiation (W/m^2), and the irradiance SolarPanelInfo.referenceIrradiation
shading_factor SolarArrayInfo.shadingFactor (percent) and the irradiance; default 1 SolarArrayInfo.shadingFactor
efficiency SolarPanelInfo.efficiency (percent); default by panel_type SolarPanelInfo.efficiency
tilt_angle, orientation_azimuth SolarArrayInfo.tiltAngle, orientationAzimuth (deg); defaults 45 and 180 the same attributes
NOCT, Pmax_temp_coeff, panel_type derived into p (table above) not written: GridLAB-D's defaults
derating, soiling derived into p; default 0.95; outside 0 to 1 raises soiling 1; derating = CIM's p over GridLAB-D's lossless output at its defaults: the whole loss
SOLAR_POWER_MODEL, orientation structural: DEFAULT; another value raises not written
weather structural: unset; a climate object raises not written
area structural: raises when set (with efficiency it can override rated_power) not written
SOLAR_TILT_MODEL, latitude_angle_fix untranscribed: read only with a climate object, which raises not written
the PV curve and flat-plate model slots (pvc_*, a_coeff, ...) untranscribed: those models raise not written
Voc, V_Max, Voc_Max, Voc_temp_coeff, Rinternal untranscribed: CIM has no DC array model not written
ambient_temperature, wind_speed untranscribed: with no climate GridLAB-D uses 59 degF and still air not written
Tmodule, Tambient, Insolation, Tcell, P_Out, V_Out, I_Out and other solver state untranscribed: solver output not written

solar fail-fast rules

Rule Message
SOLAR_POWER_MODEL or orientation other than DEFAULT solar s: SOLAR_POWER_MODEL FLATPLATE; DEFAULT is mapped
a climate object, or a weather solar s: a climate object; only GridLAB-D's static weather is mapped
area set solar s: area 100.0; not mapped
rated_power unset or 0 solar s: rated_power unset or 0; not mapped
derating or soiling outside 0 to 1 solar s: derating 1.2 is outside 0..1 (solar.cpp:1023)
export: a maxP that is unset PhotoVoltaicUnit 'x': maxP unset; GLM's solar needs its rated_power
export: p above GridLAB-D's lossless output, or negative PhotoVoltaicUnit 'x': p ... W is outside 0..... W, GridLAB-D's lossless output; its derating is 0..1 (solar.cpp:1039)

solar round trip

What Why
derating carries the whole loss and soiling and inverter_efficiency are 1 CIM holds the output p, not the factors; derating = p over GridLAB-D's lossless static-weather output, so a re-import gives the same p from any origin
panel_type, NOCT and Pmax_temp_coeff are not written CIM holds none of them; the lossless output is taken at GridLAB-D's defaults for them
efficiency, Rated_Insolation, shading_factor, tilt_angle, orientation_azimuth come back as written (or as defaulted) the datasheets hold them
model, network = round_trip("inverter/inverter.glm")
show(model, "inv_pv1", "pv1")
object inverter {
  name "inv_pv1";
  parent "n5";
  inverter_type "FOUR_QUADRANT";
  four_quadrant_control_mode "CONSTANT_PF";
  generator_status "ONLINE";
  rated_power 10000;
  inverter_efficiency 1;
  power_factor 1;
  phases "AN";
}
object solar {
  name "pv1";
  parent "inv_pv1";
  Rated_Insolation 92.902;
  efficiency 0.2;
  soiling 1;
  derating 0.81225;
  rated_power 8000;
  shading_factor 1;
  tilt_angle 45;
  orientation_azimuth 180;
}

The deck's pv1 has every default, so GridLAB-D's output is 6460.19 W (DC 7177.99 W x 0.9). The exported deck gives derating 0.81225 = 0.9 x 0.95 x 0.95 with the efficiency of 1: it makes GridLAB-D's lossless output of 7953 W come to the same 6460.19 W.

battery

Each battery is the BatteryUnit of its inverter, mRID <connection>_unit, with a BatteryInfo (<connection>_battery) as its datasheet. GridLAB-D's internal battery model is the only one mapped.

battery properties

Property Import Export
name BatteryUnit.name; mRID <connection>_unit the unit's name
parent structural: its inverter; another parent raises the inverter
use_internal_battery_model structural: true; false raises TRUE
battery_capacity BatteryUnit.ratedE and BatteryInfo.ratedCapacity (Wh); unset raises ratedE
state_of_charge BatteryUnit.storedE (Wh) = it x battery_capacity; unset raises storedE / ratedE
rated_power BatteryUnit.maxP (W) = it, minP = minus it; unset raises maxP
round_trip_efficiency chargingEfficiency = dischargingEfficiency = its square root, in percent; default 0.8 the product of the two efficiencies
battery_type BatteryInfo.batteryType: LI_ION is lithiumIon, LEAD_ACID is leadAcid; others blank BatteryInfo.batteryType; none: unset. Another kind raises
nominal_voltage BatteryInfo.numberOfCells = floor(it / 4.1) on LI_ION; default 115 V not written: CIM holds no DC voltage yet
rfb_size structural: raises when set (it overrides the battery's ratings) not written
the legacy-model slots (generator_mode, power_type, Energy, E_Max, ...) untranscribed: read only when use_internal_battery_model is false, which raises not written
reserve_state_of_charge untranscribed: set from the inverter's soc_reserve not written
solver state (V_Out, I_Out, VA_Out, battery_load, ...) untranscribed: solver output not written

The square root is GridLAB-D's: it applies the round-trip efficiency once in each direction.

battery fail-fast rules

Rule Message
use_internal_battery_model false battery b: use_internal_battery_model false; the legacy model is not mapped
rfb_size set battery b: rfb_size 5.0; not mapped
battery_capacity, state_of_charge or rated_power unset battery b: battery_capacity unset; not mapped
export: a battery type with no GLM form BatteryUnit 'x': batteryType ... has no GLM battery_type
export: a unit that is neither a PV nor a battery ... 'x': GLM's inverter takes a solar or a battery

battery round trip

What Why
nominal_voltage is not written CIM holds no DC voltage yet, so GridLAB-D takes its default 115 V; a LI_ION battery's numberOfCells of 11 (48 V) comes back as 28 on a second import
battery_type is unset when the unit has no BatteryInfo GridLAB-D's default type
the efficiencies come back as one round_trip_efficiency the product of the charge and discharge efficiencies
a battery that was limited comes back at its limit see the inverter table

battery excerpt

From the same golden, the units and the battery datasheets of the atom's b3 and bpf (the Table BatteryInfo and Table BatteryUnit of inverter.inverter.cimtbl):

Table BatteryInfo: mRID, name, batteryType, ratedCapacity (Wh), numberOfCells
    storage_inv_b3_battery,    b3,    lithiumIon, 200000.0, 11
    storage_inv_bpf_battery,   bpf,   lithiumIon, 13500.0,  11

Table BatteryUnit: mRID, name, ratedE (Wh), storedE (Wh), minimumE (Wh), maxP (W), minP (W), chargingEfficiency (percent), dischargingEfficiency (percent), batteryState, AssetDatasheet, PowerElectronicsConnection, EquipmentContainer=fdr_atom
    storage_inv_b3_unit,    b3,    200000.0, 120000.0, 40000.0, 100000.0, -100000.0, 92.73618495495704, 92.73618495495704, discharging, storage_inv_b3_battery,    storage_inv_b3
    storage_inv_bpf_unit,   bpf,   13500.0,  4995.0,   0.0,     5000.0,   -5000.0,   92.73618495495704, 92.73618495495704, charging,    storage_inv_bpf_battery,   storage_inv_bpf

b3 is 200 kWh at 60 % charge (storedE 120 kWh) with a reserve of 20 % (minimumE 40 kWh), and its round_trip_efficiency of 0.86 is 92.74 % each way. Its numberOfCells 11 is floor(48 / 4.1).