Buses, meters and the source

Every GridLAB-D object that equipment lands on is a bus: node, meter, triplex_node, triplex_meter and substation. This page covers how those become CIM ConnectivityNodes and BaseVoltages, how the swing bus becomes an EnergySource, and what the master file holds (frequency, containers, the feeder head). How to read the tables is on the reference landing page.

GLM CIM (cim18v17) Import (shape) Export
node, meter, triplex_node, triplex_meter (every root bus) ConnectivityNode, BaseVoltage bus.cimtbl (a ConnectivityNode table) node, or triplex_node on a split-phase bus
substation, any bus with bustype SWING EnergySource, BasePower source.cimtbl (source) substation with bustype SWING; a one-phase swing a node with bustype SWING
module powerflow nominal_frequency BaseFrequency the master module powerflow nominal_frequency
the model Substation, Feeder, Feeder.NormalHeadTerminal the master not written

The shapes are on the core site's shapes page, and the getters the exporter reads through (get_source, get_base_voltage, get_terminal_phases) are on its getters guide.

The topology walk

In GridLAB-D a load, a capacitor and a meter are each a node, and lines end on them, so every bus has to exist before any equipment is written. The importer therefore builds the buses itself, from a topology walk that runs once over the whole model. The walk is cimtopology.core.walk, shared by every importer; the GLM side builds its input (a Network of sources, branches and transformer coils) in importer/topology.py.

Part Rule
Buses every object of a node or triplex_node class, including a load, capacitor or triplex_load that nothing else is parented to
Root buses a bus whose parent is a bus is solved by GridLAB-D as its parent's bus. It gets no ConnectivityNode; its equipment lands on the root of its parent chain, and its name is listed in the root's row comment (# children: ld_611)
Sources every substation, and every bus with bustype SWING. SWING_PQ is a plain bus, and becomes a swing only when its island separates; the row comment says so
Branches every line, switch, fuse, recloser, sectionalizer, series reactor and regulator. A switching device with status OPEN is a normally open branch
Transformers one coil per winding, from the transformer_configuration (transformers)
BaseVoltages the walk's distinct bus voltages, highest first. A voltage of 1 kV or more is rounded to 0.01 kV, a lower one to the volt; the mRID is bv_12p47kv, bv_480v, bv_240v
Phases a link's phases (N and D aside) must be on both of its end objects, as GridLAB-D requires; a center tap's S is on its to end only

A bus's system is read from the walk: three phase (a source, or a polyphase transformer coil), single phase, or split phase (triplex_node). A voltage on a bus object is a phase-to-neutral figure on a three-phase system, so the walk's BaseVoltage (line to line) is nominal_voltage times the square root of three there, and times two on a split-phase bus.

A bus the walk does not reach (an island with no source) has no BaseVoltage: a link, a load, a capacitor or an inverter on it raises a ValueError naming the equipment and the bus, and a bus with nothing on it is left out.

The IEEE decks use ${VSOURCE} without defining it. GlmReader takes the macro from its defines argument, as gridlabd -D would:

from cimtables.document import format_document
from cimhub_gridlabd.glm_reader import GlmReader
from cimhub_gridlabd.importer.glm_to_cimtbl import GlmImporter

model = GlmReader("cimhub_gridlabd/tests/decks/IEEE/IEEE13_cdpsm.glm", defines={"VSOURCE": "66395.28"}).read_all()
documents = GlmImporter("IEEE13_cdpsm").to_cimtbl(model)  # the master plus one document per GLM class
bus = next(part for part in documents.parts if part.name == "bus")
print("\n".join(format_document(bus).splitlines()[:12]))
print(format_document(documents.master))  # the master, excerpted below

The master

The master document holds what no single GLM object owns, then one Import per non-empty part in dependency order (catalogs first), then the feeder head.

Row From Rule
Substation, Feeder the name passed to GlmImporter, or its substation= and feeder= mRIDs sub_<substation> and fdr_<feeder>; the Feeder names the Substation as its NormalEnergizingSubstation. Every bus, line and device names the feeder (or substation) as its container
BaseFrequency module powerflow { nominal_frequency ...; }, else #set powerflow::nominal_frequency=... mRID bf_<f>hz, in Hz. Neither set: GridLAB-D's 60 Hz, listed as # defaulted: powerflow::nominal_frequency=60.0
BaseVoltage the walk nominalVoltage (kV), highest first
OperationalLimitType fixed olt_normal and olt_emergency, which every CurrentLimit names
Update Table Terminal (last) every mapped link that touches a swing bus sets NormalHeadFeeder on that link's Terminal at the swing: <mRID>_T1 for its from, _T2 for its to (a regulator: each unit's)
comment every GLM class no mapper reads, with its count not mapped: <class> <count>, ..., including classes the schema lacks

The frequency is also what turns a line's capacitance c (nF) into the susceptance b (nS) on import, and the exporter writes it back as nominal_frequency.

# defaulted: powerflow::nominal_frequency=60.0
Object BaseFrequency: mRID=bf_60hz, frequency (Hz)=60.0

Table BaseVoltage: mRID, nominalVoltage (kV)
    bv_115kv,  115.0
    bv_4p16kv, 4.16
    bv_480v,   0.48
    bv_240v,   0.24

Excerpt from the master of IEEE13_cdpsm.glm, printed by the example above (documents.master). The master is named after the model, so a model name that equals the name of a part (transformer, load, player, switch, bus, source, ...) raises a ValueError when the importer is made, before anything is read.

Fail fast. A value the reader kept as an expression in a property a mapper reads. The walk raises on a coil that cannot sit on its island, on a parent that is not a bus object, on a parent loop, on a link whose from or to names no bus object, on a link whose phases are not on both of its ends, and on a link or a device on an island no swing bus reaches.

node, meter, triplex_node, triplex_meter

A node is a ConnectivityNode named by the GLM name, with the walk's BaseVoltage, in ConnectivityNodeContainer fdr_<feeder>. A meter is a node with metering and billing properties, and triplex_meter is to triplex_node as meter is to node. Those properties have no CIM home. A triplex_node that carries power_1, power_2 or power_12 also becomes consumers; that is on the loads page.

property import export
name copied to ConnectivityNode.mRID and name, source case, no prefix; root buses only written: Names
parent structural: a bus whose parent is a bus has no node; its equipment lands on the root of the chain, and its name is listed on the root's row not written: every exported bus is a root
phases structural: a child's phase conductors must be a subset of its root's; on a swing bus, EnergySource.phases written: the A, B, C of every terminal on the node, then N; a triplex_node the service's letter, then S
nominal_voltage structural: checked against the walk's kV on the bus's system; a disagreement over 10 % is listed in the table comment, not raised. On a swing bus it is also the source's nominalVoltage written: the BaseVoltage over the square root of three on a three-phase bus, unchanged on a single-phase one, over two (one leg, s1 to N) on a split-phase one
bustype structural: SWING is an EnergySource; PQ, PV and SWING_PQ are a plain bus not written, except SWING on the swing (a substation, or a one-phase swing's node)
voltage_A (voltage_1 on a triplex bus) derived, on a swing bus only: the source's voltageMagnitude and voltageAngle written on a one-phase swing's node: get_source voltageMagnitude at voltageAngle
power_1, power_2, power_12 (a plain triplex_node) copied to EnergyConsumer.p and q; see loads not written here
power_A ... power_CN, current_*, shunt_*, current_inj_* (any bus class but a plain triplex_node's power_1, power_2, power_12) raises when set: a load on the bus object itself; make it a load not written
voltage_B, voltage_C, voltage_2, voltage_N untranscribed: the solver's initial guess not written
object metadata, latitude, longitude, reliability, dynamics (deltamode_*, GFA_*), solver state and outputs, metering and billing untranscribed: listed in the table comment as untranscribed, set here: <class> <slot> <count>, only for slots the model sets not written: GridLAB-D's default

nominal_voltage is checked on the walk's system, so a taxonomy meter that says 480 V on a bus the walk puts at 4.16 kV is listed, not rewritten:

# nominal_voltage disagrees with the walk (10%): 480.0 V (0.8314 kV 3-phase) on bv_480v (1): meter_1

Fail fast. A parent that is not a bus object, or a parent loop. A child whose phases are not a subset of its root's. A load accumulator on a bus object. A nominal_voltage that is an unevaluated expression.

Expected differences. A meter comes back as a node and a triplex_meter as a triplex_node; child buses are gone, their equipment parented to the root bus; a SWING_PQ bus comes back a plain bus. nominal_voltage is the BaseVoltage's, so the deck's 2401.78 returns as 2401.7771198288... (4160 V over the square root of three). The name is the GLM name under name_source="name", and an unsafe name (., :, whitespace) is rewritten (line_spacing:10 returns as line_spacing_10).

Excerpt from cimhub_gridlabd/tests/atoms/bus/feeder.bus.cimtbl:

Table ConnectivityNode: mRID, name, BaseVoltage, ConnectivityNodeContainer=fdr_feeder
    # children: ld_1
    n1,        n1,        bv_12p47kv
    sourcebus, sourcebus, bv_12p47kv
    # bustype SWING_PQ: a plain bus here; it is a swing only when its island separates
    meter_1,   meter_1,   bv_480v
    # children: tn_1
    tm_1,      tm_1,      bv_240v

Export: the bus's system

CIM does not store a bus's system, but GLM's nominal_voltage depends on it. The exporter reads it per voltage zone (the buses joined without a transformer), from what lands in the zone, in this order:

  1. a terminal on s1 or s2: split phase, a triplex_node whose phase letter is the service's (the A, B or C of the primary of the center-tap transformers in the zone, which must agree);
  2. the EnergySource, a transformer end on two or three of A, B, C, or one-phase ends on different phases (a bank): three phase;
  3. one-phase transformer ends all on one phase: single phase.

A zone none of these reach raises (the zone of bus ... has no source and no transformer end: its system is unknown). A split-phase zone whose center taps are not all on one phase raises too.

substation and the swing source

A substation (always a swing) and every bus with bustype SWING becomes one EnergySource named src_<name> on the bus itself. A swing bus with a parent raises. The BasePower is a separate object, sbase_<name>.

property import export
nominal_voltage derived: EnergySource.nominalVoltage = line_voltage(nominal_voltage) on the bus's system (V, as written); unset raises written: get_source nominalVoltage over the square root of three on a three-phase system, as is on a one-phase one
positive_sequence_voltage (voltage_A, or voltage_1 on a triplex bus, when it is unset) derived: voltageMagnitude = line_voltage of the magnitude of V, voltageAngle = arg(V) in degrees; a polar value is taken as written. Unset: nominal_voltage at 0 degrees, listed as defaulted written: get_source voltageMagnitude over the square root of three, at voltageAngle (a one-phase swing: voltage_A on its node, not divided)
phases structural: the phase letters, N dropped, one or three conductors; ABC is a blank cell written, as for any bus
reference_phase structural: unset or PHASE_A; anything else raises not written
base_power copied to BasePower.basePower, in its written unit (12MVA is basePower (MVA)=12.0) written: the graph's BasePower when it holds one
power_convergence_value, the negative and zero sequence voltages, transmission_level_* untranscribed not written
source impedance defaulted: a stiff source, r, x, r0, x0 with a 10,000 MVA short circuit and X/R of 10 (12.47 kV gives about 0.0155 ohm) not written: GridLAB-D's swing is ideal

GridLAB-D's swing bus has no source impedance and CIM's EnergySource needs one for other tools to solve it, so the importer writes a small default and lists it on the row as defaulted. default_source_impedance(kv) returns (r, x) in ohm, with |Z| = kV² / 10000 and x = 10 r:

from cimhub_gridlabd.importer.cimtbl.bus import default_source_impedance

print(default_source_impedance(12.47))  # (0.0015472917861112452, 0.015472917861112451)

Fail fast. A source on any number of conductors but one or three. A source whose voltage (positive_sequence_voltage or voltage_A) is more than 10 % from nominal_voltage: the deck gives the wrong source voltage, or the wrong defines. A reference_phase other than PHASE_A. A swing bus with a parent. On export, two EnergySources (the Newton-Raphson solver takes one swing), an EnergySource that does not have one terminal, and more than one BasePower.

Expected differences. The source impedance is not written, and the swing's nominal_voltage is recomputed from the EnergySource. base_power is written in VA (12000000), the unit the schema declares. A source's zone is three phase on export unless the source is on one conductor: a one-conductor swing (phases AN) is single phase, so its nominal_voltage 7200 comes back 7200. GridLAB-D's substation needs all three phases, so a one-phase swing is written as a node with bustype SWING and voltage_A, and a model with a BasePower then raises on export.

Excerpt from cimhub_gridlabd/tests/atoms/bus/feeder.source.cimtbl:

Object BasePower: mRID=sbase_sourcebus, basePower (MVA)=12.0

Table EnergySource: mRID, name, node, phases, nominalVoltage (V), voltageMagnitude (V), voltageAngle (deg), r (ohm), x (ohm), r0 (ohm), x0 (ohm), BaseVoltage, EquipmentContainer=sub_feeder
    # derived: nominalVoltage = line_voltage(nominal_voltage=7200.0), voltageMagnitude and voltageAngle from positive_sequence_voltage=7200.0+0.0j; defaulted: r x r0 x0 of a stiff source, 10000 MVA short circuit, X/R 10
    src_sourcebus, sourcebus, sourcebus, , 12470.765814495915, 12470.765814495915, 0.0, 0.0015474818382145749, 0.015474818382145749, 0.0015474818382145749, 0.015474818382145749, bv_12p47kv

A taxonomy swing node (voltage_A 7416-30d, a polar value) keeps its written magnitude and angle: tests/atoms/source/swing_node.cimtbl has voltageMagnitude (V) 12844.9 and voltageAngle (deg) -30.0.

Round trip

from pathlib import Path
from cimhub_gridlabd.glm_reader import GlmReader
from cimhub_gridlabd.importer.glm_to_cimtbl import glm_to_cim
from cimhub_gridlabd.exporter.cim_to_glm import cim_to_glm

model = GlmReader("cimhub_gridlabd/tests/decks/IEEE/IEEE13_cdpsm.glm", defines={"VSOURCE": "66395.28"}).read_all()
network = glm_to_cim(model, name="IEEE13_cdpsm")
cim_to_glm(network, "/tmp/IEEE13_back.glm", name_source="name")
text = Path("/tmp/IEEE13_back.glm").read_text()
start = text.index("object substation")
print(text[start:text.index("}", start) + 1])
object substation {
  name "sourcebus";
  phases "ABCN";
  nominal_voltage 66395.28;
  bustype "SWING";
  positive_sequence_voltage 66395.28+0j;
  base_power 12000000;
}

The deck header the exporter writes is one power flow: a clock that starts and stops at one instant, #set relax_naming_rules=1, and module powerflow { solver_method NR; nominal_frequency <f>; line_capacitance TRUE; }. line_capacitance is on because CIM's line susceptance is part of the model and GridLAB-D ignores every c without it. A module generators is added when the deck holds DER.