Transformers and regulators

transformer_configuration and transformer, and regulator_configuration and regulator: how each becomes CIM templates, power transformers, voltage regulators and tap changers, and how they come back. How to read the tables is on the reference landing page.

GLM CIM (cim18v17) Import (shape) Export
transformer_configuration TransformerTankConfiguration with its ends or lugs, and its windings; a bank under a TransformerBankConfiguration transformer_configuration.cimtbl (transformer_template, transformer_template_1ph) transformer_configuration, one per way a unit uses a template
transformer PowerTransformer, TransformerTank per tank, PowerTransformerEnd per side, TransformerPhaseEnd for lugged templates transformer.cimtbl (transformer_by_template) transformer, from a PowerTransformer or an AutoTransformer that is not a regulator
regulator, with its regulator_configuration VoltageRegulator, two AutoTransformerEnds, TransformerMeshImpedance, TapChangerControl, RatioTapChanger regulator.cimtbl (voltage_regulator) regulator and regulator_configuration

The shapes are on the core site's shapes page, and the getters the exporter reads through (get_transformer_units, get_transformer_model, get_tap_changer_control, get_tap_steps) are on its transformers reference.

The impedance rule. GridLAB-D stores a transformer's impedance as one R + jX in per unit and a parallel shunt, on its own base: secondary_voltage² / power_rating, line to line, as written. The importer puts that on the tank's nameplate fields (percentImpedance, loadLoss, noLoadLoss, percentMagnetizingCurrent), moved to the tank's own base by k = 3 S_coil / S_total, so GridLAB-D's ohms are kept. There is no winding r and no mesh impedance. A wye whose voltages rate the coil, phase to neutral, rather than the line, has k = S_coil / S_total. The deck says which: the written primary_voltage is either the nominal_voltage of its from bus (a coil rating) or that times the square root of three (a line rating); anything else raises.

transformer_configuration

A configuration is written as a template, used or not, in one of three forms. Every transformer that uses one configuration must wire it the same way (the same phases and bus systems), or the importer raises, because there is one template per configuration.

Form When CIM
three-phase tank a WYE_WYE on three phases rated equally or only by power_rating; DELTA_GWYE; DELTA_DELTA a TransformerTankConfiguration xc_<name> with a TransformerTankEnd per winding (connectionKind) and a TransformerWinding per end
lugged cans a wye on one phase (one can), on two (a bank), or on three phases rated unequally (a bank) one TransformerTankConfiguration per can with TransformerLugs H1 H2 X1 X2 and windings H1 to H2, X1 to X2; a bank's cans are xc_<name>_<phase> under a TransformerBankConfiguration xb_<name> (an unrated template's cans are _1, _2)
center tap SINGLE_PHASE_CENTER_TAPPED, or a 240 V one-phase service lugs H1 H2 X1 X3 X2 (numbered 1 to 5) and windings H1 to H2, X1 to X2 (s1 to N), X2 to X3 (N to s2); the %Z is the full winding's, which GridLAB-D splits into its star

Connections: WYE_WYE and SINGLE_PHASE (one case in GridLAB-D) are Y to Y, DELTA_GWYE D to Y, DELTA_DELTA D to D. The grounding is the instance's, not the template's.

Windings carry ratedU and baseU in the unit the deck writes the voltage in, and ratedS and baseS in the unit of power_rating. On a line-rated wye ratedU is the written voltage and baseU is that over the square root of three; a delta's are equal. On a coil-rated wye baseU is the written voltage and ratedU is that on the bus's system. A center tap's halves have baseU = secondary_voltage and ratedU twice that, at half the kVA each (a 240 V service's halves are each half of its secondary_voltage).

property import export
name copied to TransformerTankConfiguration.name; mRID xc_ + name (a bank xb_ + name, its cans xc_ + name + _<phase>) written: the TankConfiguration's name when every instance wires it alike, else <unit>_config
connect_type structural: the form and the connection kinds; unset or any other value raises written: WYE_WYE, SINGLE_PHASE, DELTA_DELTA, DELTA_GWYE, SINGLE_PHASE_CENTER_TAPPED, by the table below
primary_voltage structural: winding 1 ratedU and baseU; unset or 0 raises written: winding 1's ratedU (V), a coil's baseU; an LTC at its actual step is folded in
secondary_voltage structural: winding 2 ratedU and baseU; a center tap's half has baseU = this and ratedU twice it written: winding 2's, likewise; a center tap's half; a star leg's 1000 V
power_rating structural: ratedS of the whole unit (kVA), else the sum of the phase ratings; unset or 0 raises written: winding 1's ratedS (kVA); a star leg's own winding's
powerA_rating, powerB_rating, powerC_rating structural: a can's kVA when the wired phases are rated unequally; a center tap's kVA on its phase (unset or 0 there raises); otherwise unused, and listed when not power_rating over the phase count. They must sum to power_rating within 1 %, else raises written: a coil's or a center tap's kVA on its phase; a bank's each can's
resistance, reactance, impedance derived: percentImpedance = |R + jX| x k x 100, loadLoss = R x k x S (kW); both parts positive, else raises; impedance and its parts that differ raise written: the (1, 2) R + jX in per unit (the windings' r plus the mesh); a center tap's or a star leg's branch; a part that is not positive is written as 1e-6 and logged
resistance1, reactance1, impedance1, and the same for 2 derived: a center tap's star given whole must be GridLAB-D's split of one R + jX (impedance = 0.5 R + j0.8 X, each half R + j0.4 X); any other split, one half only, or another connection raises written: a center tap's impedance1 and impedance2, the halves of the star
shunt_resistance, shunt_reactance, shunt_impedance derived: noLoadLoss = S / (Rsh x k), percentMagnetizingCurrent = 100 / (Xsh x k); unset is GridLAB-D's lossless core, not filled; on a delta connection raises written: shunt_resistance = 1 / the core's g, shunt_reactance = 1 / its b, per unit; unset parts are not written
no_load_loss, full_load_loss, reactance_resistance_ratio raises when set: they replace the impedances, and no deck sets them not written
install_type, coolant_type, cooling_type, the thermal slots (oil_volume, core_coil_weight, ...), the inrush slots (L_A, phi_K, ...), object header untranscribed: listed in the row comment not written: GridLAB-D's default

How a unit is chosen for export (get_transformer_model, per unit on winding 1's ratedS):

Model Written as
two windings, Y, Yn or I on both, on one phase set WYE_WYE, or SINGLE_PHASE for one coil
two windings, D to D on three phases DELTA_DELTA
two windings, D to Yn on three phases, phaseShift unset or -30 degrees DELTA_GWYE
three windings on s1, s2, N SINGLE_PHASE_CENTER_TAPPED, the star written whole
any other two windings WYE_WYE on both windings' phases; the phase shift, zero-sequence path and grounding are lost, and each is logged
three windings, not a center tap three legs to a 1 kV star bus <unit>_star; a D leg DELTA_GWYE, otherwise WYE_WYE; the star branch of winding i is (Zij + Zik - Zjk) / 2
single-phase cans with a phase-to-phase coil on the same buses one bank, then the rows above
one PowerTransformer's lugged cans under a TransformerBankConfiguration one WYE_WYE, powerX_rating each can's, named by the bank configuration

GridLAB-D's base is secondary_voltage² / power_rating: a polyphase unit is written line to line on its whole kVA, a coil on its own voltage and kVA, and a polyphase wye on two phases has a coil base of n/3 of GridLAB-D's. A bank's cans all get GridLAB-D's one impedance, so each can's own per unit times S_total / (3 S_can) must agree, else the export raises.

Fail fast. connect_type unset or unmapped; voltages or kVA unset or 0; phase ratings that miss power_rating by more than 1 %; resistance or reactance unset or not positive; impedance1 and impedance2 on a connection that ignores them, or a split other than GridLAB-D's; a shunt on a connection that ignores it; no_load_loss and the like set; a center tap on a phase it does not rate; two instances that wire one configuration differently. On export, four or more windings; a tap changer on a bank can; a bank's cans that give different impedances; a ratedU unset.

Expected differences. A configuration is written once per distinct use, so a template no transformer uses is not written. A tap changer is folded into its winding's voltage at the actual step, and its control is not written. A winding's grounding impedance is lost, since GridLAB-D grounds a wye solidly. Non-native two-winding models and open delta banks are written as WYE_WYE, with the differences above. The per-unit impedance comes back on GridLAB-D's base (0.011+0.02j returns as 0.011+0.02j, up to rounding); a part that was not positive returns as 1e-6.

Excerpt from cimhub_gridlabd/tests/atoms/transformer/transformer.transformer_configuration.cimtbl, a bank of three cans rated 37.5, 25 and 25 kVA (xc_bank3) and the three-phase xcon_xfm1:

Table TransformerBankConfiguration: mRID, name
    xb_xc_bank3, xc_bank3

Table TransformerTankConfiguration: mRID, name, percentImpedance (percent), loadLoss (kW), noLoadLoss (kW), percentMagnetizingCurrent (percent)
    xc_xcon_xfm1, xcon_xfm1, 2.2825424421026654, 5.5, ,

Table TransformerTankConfiguration: mRID, name, percentImpedance (percent), loadLoss (kW), noLoadLoss (kW), percentMagnetizingCurrent (percent), BankConfiguration
    xc_xc_bank3_A, xc_bank3_A, 0.7486313634675927,  0.054964285714285716, 0.062058718186041396, 0.1826112363302446,  xb_xc_bank3
    xc_xc_bank3_B, xc_bank3_B, 0.49908757564506173, 0.024428571428571424, 0.062058718186041396, 0.27391685449536685, xb_xc_bank3

Table TransformerWinding: mRID, TankConfiguration, ratedU (V), baseU (V), ratedS (kVA), baseS (kVA), FromTransformerLug, ToTransformerLug
    xc_xc_bank3_A_wdg_1, xc_xc_bank3_A, 4160.0, 2401.7771198288433, 37.5, 37.5, xc_xc_bank3_A_lug_h1, xc_xc_bank3_A_lug_h2

(rows abridged)

transformer

A transformer is a PowerTransformer xf_<name> with a TransformerTank for each tank of its template (one, named xf_<name>_tank with no name of its own; a bank has a tank per can, xf_<name>_tank_<phase> named <name>_<phase>), and a PowerTransformerEnd per side, on the root bus of from and to. The values live in the template; the ends carry the node, phases, connection kind and grounding. A lugged template (a center tap, a one- or two-phase wye, a bank) also gets a TransformerPhaseEnd per conductor of each terminal, numbered as the template's lugs, so a center tap's secondary is s1, s2, N.

connect_type End 1: phases, kind, grounded End 2: phases, kind, grounded
WYE_WYE, SINGLE_PHASE the transformer's phases, N; Yn, true (without N, or with S, raises) the same
DELTA_GWYE ABC; D, false ABCN; Yn, true
DELTA_DELTA ABC; D, false ABC; D, false
SINGLE_PHASE_CENTER_TAPPED the phase letter and N; Y, true s1s2N; I, true

A coil-rated one-phase wye whose secondary_voltage is 120 V is a split-phase leg: its end 2 is s1N, kind I, and the bus is a 240 V split-phase system. At 240 V it is a center tap (end 2 s1s2N), with the unit's R + jX taken as the full winding's. Another one-phase secondary (a 277 V coil) is one phase of a wye on a three-phase system. Only loads may sit on a service bus: a link, a capacitor or an inverter there raises.

property import export
name copied to PowerTransformer.name; mRID xf_ + name written: the transformer's; a tank of several <transformer>_<n>; a star leg <unit>_<winding>
phases structural: the ends' phases and kinds above, and the phase ends; unknown letters raise; a delta must be ABC written: winding 1's A, B, C, then N; a center tap's letter, then S
from, to structural: node of end 1 and end 2, the root buses; each end's system must be as the connection needs (a polyphase transformer's three phase, a center tap's secondary split phase) written: winding 1's bus; winding 2's, or a star leg's star bus
configuration structural: TransformerTank.TankConfiguration = xc_ + configuration (a bank: one tank per can); unset raises written: its transformer_configuration
continuous_rating_A to _C, emergency_rating_A to _C structural: the transformer's own <mRID>_limits; per-phase ratings that differ raise written: get_current_limits on the unit's phases
status structural: unset or CLOSED; OPEN raises (a transformer is not a switch) not written
thermal and flux slots (climate, ambient_temperature, percent_loss_of_life, phase_A_primary_flux_value, ...), object header, solver outputs untranscribed not written

Fail fast. A transformer without a configuration, or one that names another class. A center tap on phases other than one letter and S. A wye without N or with S. A delta not on ABC. A status other than CLOSED. An end on the wrong system. A written voltage that is neither the coil's nor the line's. A one-phase service whose secondary bus has a link, capacitor or inverter on it.

Expected differences. A DELTA_DELTA transformer written ABCN comes back ABC, and a DELTA_GWYE written ABC comes back ABCN. Several lugged cans of one transformer come back as one WYE_WYE. A transformer keeps its name; its configuration may be renamed. Tap changers and per-phase ratings follow the template rules above.

Excerpt from cimhub_gridlabd/tests/atoms/transformer/transformer.transformer.cimtbl (a center tap xf_ct and a delta-wye xf_dg):

Table PowerTransformerEnd: mRID, PowerTransformer, node, phases, endNumber, connectionKind, grounded, BaseVoltage
    xf_xf_ct_1, xf_xf_ct, n5,  AN,    1, Y,  true,  bv_4p16kv
    xf_xf_ct_2, xf_xf_ct, tn1, s1s2N, 2, I,  true,  bv_240v
    xf_xf_dg_1, xf_xf_dg, n2,  ABC,   1, D,  false, bv_4p16kv
    xf_xf_dg_2, xf_xf_dg, m_dg, ABCN, 2, Yn, true,  bv_480v

Table TransformerPhaseEnd: mRID, endNumber, sequenceNumber, phase, Terminal
    xf_xf_ct_2_s1, 2, 3, s1, xf_xf_ct_T2
    xf_xf_ct_2_s2, 2, 4, s2, xf_xf_ct_T2
    xf_xf_ct_2_N,  2, 5, N,  xf_xf_ct_T2

(rows abridged)

The steps from a deck to this and back:

from cimhub_gridlabd.glm_reader import GlmReader
from cimhub_gridlabd.importer.glm_to_cimtbl import glm_to_cim
from cimhub_gridlabd.exporter.cim_to_glm import GlmExporter

model = GlmReader("cimhub_gridlabd/tests/atoms/transformer/transformer.glm").read_all()
network = glm_to_cim(model, name="xfmr")  # a model name that no GLM class shares
exported = GlmExporter().to_model(network, name_source="name")
by_class = {cls.class_name: cls for cls in exported.graph}
for record in exported.graph[by_class["transformer_configuration"]].values():
    print(record.name, record.connect_type, record.power_rating)

regulator_configuration and regulator

A GridLAB-D regulator is a 1:1 step-voltage regulator with no nameplate impedance and no kVA, so each unit is a VoltageRegulator (an AutoTransformer) with two AutoTransformerEnds. There is no step-down LTC in GLM, so there is no PowerTransformerEnd and no tank. CIM has no regulator template, so a configuration's values go on every unit that names it, and a configuration no regulator names is listed in the file comment and not written.

control_level Units
INDIVIDUAL (default) one single-phase unit per wired phase, xf_<name>_<phase>, each with its own RatioTapChanger and TapChangerControl
BANK one gang unit xf_<name> on ABC, whose taps must agree; or, when the regulator is wired on its one PT_phase, one unit on that phase
CIM row Written from
VoltageRegulator construction from Type: A is typeA, B is typeB (default B)
AutoTransformerEnd (two) node the root buses of from and to; phase <letters>N; grounded true; baseU (V) the from bus's nominal_voltage, the coil phase to neutral (x the square root of three on a gang unit); ratedS (VA) the continuous rating x baseU (x the square root of three on a gang unit)
TransformerMeshImpedance r (ohm) regulator_resistance, default 1e-4 ohm (GridLAB-D's default_resistance); x a 0.01 percent stand-in on ratedS
TapChangerControl rc_<unit> enabled unless Control is MANUAL; monitoredPhase; ptRatio; targetValue and targetDeadband from the band; lineDropCompensation on LINE_DROP_COMP; lineDropR, lineDropX (ohm)
RatioTapChanger rc_<unit>_tap lowStep, highStep, neutralStep 0, step, stepVoltageIncrement (percent), neutralU (V) = baseU, ltcFlag true, controlEnabled, ptRatio, ctRatio, ctRating (A), initialDelay, subsequentDelay (s)

regulator_configuration

property import export
connect_type structural: WYE_WYE; any other raises (the Newton-Raphson solver takes only that) written: WYE_WYE, since CIM's AutoTransformerEnds are grounded wye coils
Control structural: MANUAL (default) is enabled and controlEnabled false; OUTPUT_VOLTAGE and LINE_DROP_COMP true, with lineDropCompensation on LINE_DROP_COMP only; REMOTE_NODE on the regulator's own to bus is read as OUTPUT_VOLTAGE, elsewhere raises written: MANUAL when the TapChangerControl is disabled or absent, LINE_DROP_COMP with line drop compensation, else OUTPUT_VOLTAGE
Type mapped: A to typeA, B to typeB; default B written: B on construction typeB, else A
band_center, band_width derived: targetValue, targetDeadband (V), primary volts on OUTPUT_VOLTAGE and MANUAL, times power_transducer_ratio on LINE_DROP_COMP, whose band is on the PT secondary; band_width is the full band written: the target and the deadband (V); over ptRatio on LINE_DROP_COMP; unset on a disabled control
raise_taps copied to RatioTapChanger.highStep; also the divisor of the step; unset or not positive raises written: highStep - neutralStep; a fixed tap raises
lower_taps derived: lowStep = -lower_taps; unset or not positive raises written: neutralStep - lowStep
regulation derived: stepVoltageIncrement = regulation / raise_taps, as percent (regulation is a fraction: 0.10 over 16 taps is 0.625); 0 or unset raises unless MANUAL written: stepVoltageIncrement x raise_taps as a per-unit fraction
tap_pos_A, tap_pos_B, tap_pos_C derived: step of the phase's unit, unless the regulator sets its own tap_X; default 0; outside -lower_taps to +raise_taps raises written: step - neutralStep on each phase
current_transducer_ratio copied to RatioTapChanger.ctRatio and ctRating (A: GridLAB-D's compensator takes amperes on a 1 A secondary, so the ratio is the CT primary rating) written: ctRatio
power_transducer_ratio copied to TapChangerControl.ptRatio and RatioTapChanger.ptRatio written: ptRatio
compensator_r_setting_A to _C, compensator_x_setting_A to _C derived: lineDropR, lineDropX (ohm) = the monitored phase's setting x power_transducer_ratio / current_transducer_ratio (line_drop_ohms); set without both ratios raises written wherever CIM holds a line drop: lineDrop x ctRatio / ptRatio on each phase
dwell_time, time_delay derived: initialDelay = subsequentDelay = dwell_time + time_delay (s); default 0 written: dwell_time = initialDelay
control_level structural: see above written: BANK for one VoltageRegulator alone, else unset (INDIVIDUAL)
PT_phase, CT_phase structural: on BANK, TapChangerControl.monitoredPhase, one phase, the same for both; on INDIVIDUAL GridLAB-D ignores them and the row lists them written on BANK: the control's monitored phase, else its first phase; an enabled control without one raises
reverse_flow_control structural: unset or LOCK_NONE; any other raises not written
object header untranscribed not written

regulator

property import export
name derived: VoltageRegulator.name = name (BANK) or <name>_<phase> (INDIVIDUAL); mRID xf_ + that written: Names; units that are <base>_<phase> on the same two buses are the one regulator <base> again
phases structural: the wired phases A, B, C (N optional); S raises written: the A, B, C of end 1
from, to structural: node of end 1 and end 2, the root buses written: end 1's and end 2's bus
configuration structural: a regulator_configuration, else raises; its values go on every unit written: <regulator>_config
tap_A, tap_B, tap_C derived: step of the phase's unit, over tap_pos_X not written: tap_pos_X of the configuration
regulator_resistance copied to TransformerMeshImpedance.r (ohm); unset is 1e-4 ohm, listed as defaulted written: the mesh r (ohm); none: unset
continuous_rating_A to _C structural: ratedS = the rating x baseU; the unit's phase (a gang unit's any); unset raises, since GridLAB-D's default is not the regulator's written: get_current_limits on its phases
emergency_rating_A to _C structural: the emergency CurrentLimit of the unit's <mRID>_limits written: get_current_limits
sense_node structural: REMOTE_NODE only, and it must solve as the regulator's own to bus; on another Control GridLAB-D ignores it and the row lists it not written
status structural: unset or CLOSED; OPEN raises not written
msg_mode, remote_voltage_A to _C, tap_A_change_count to _C, object header, solver outputs untranscribed not written

Fail fast. A connect_type other than WYE_WYE. raise_taps or lower_taps unset or not positive. regulation unset or 0 on an automatic Control. REMOTE_NODE sensing a bus other than the regulator's output. A reverse_flow_control other than LOCK_NONE. A BANK on neither ABC nor its one PT_phase, whose PT_phase and CT_phase are not one equal phase, or whose taps differ. A tap outside the range. Compensator settings without both transducer ratios. Phases with S or none of A, B, C. A unit with no continuous_rating_X. On export, a VoltageRegulator without exactly two ends or one RatioTapChanger; a fixed tap; a line drop without both ratios; an enabled BANK control with no monitored phase; shared settings of one GLM regulator's units that disagree.

Expected differences. A regulator's reactance and kVA are not in GridLAB-D, so only the mesh r is written back. A delta regulator bank (coils between phases) is written as one WYE_WYE regulator, each coil's tap and compensator on its own phase, and logged, since GridLAB-D 6.0 solves no delta regulator under the Newton-Raphson solver. A regulator that came from CIM comes back with <regulator>_config as its configuration. A bus's nominal_voltage is its BaseVoltage's, so a regulator end's baseU and ratedS follow it.

Excerpt from cimhub_gridlabd/tests/atoms/regulator/regulator.regulator.cimtbl, the line-drop-compensating reg_ldc on phase A:

Table VoltageRegulator: mRID, name, construction, EquipmentContainer=fdr_reg
    # configuration rc_ldc
    # defaulted: time_delay=0.0, dwell_time=0.0, control_level=INDIVIDUAL, Type=B
    xf_reg_ldc_A, reg_ldc_A, typeB

Table TapChangerControl: mRID, name, mode=voltage, discrete=true, enabled, monitoredPhase, ptRatio, targetValue, targetDeadband, lineDropCompensation, lineDropR (ohm), lineDropX (ohm), Terminal
    rc_reg_ldc_A, reg_ldc_A, true, A, 20.0, 2440.0, 40.0, true, 0.08571428571428572, 0.2571428571428571, xf_reg_ldc_A_T2

(rows abridged) The band 122 V and 2 V are on the PT secondary, so with power_transducer_ratio 20 they become targetValue 2440 V and targetDeadband 40 V, and the settings 3 and 9 become lineDropR 3 x 20 / 700 and lineDropX 9 x 20 / 700 ohm.