Lines, conductors and switches¶
Everything that carries current between two buses and is not a transformer: the conductor catalogs, spacings and configurations, lines, switching devices, and series reactors. How to read the tables is on the reference landing page.
| GLM | CIM (cim18v17) | Import (shape) | Export |
|---|---|---|---|
overhead_line_conductor |
OverheadWireInfo |
overhead_line_conductor.cimtbl (wire_info) |
overhead_line_conductor |
underground_line_conductor |
ConcentricNeutralCableInfo, TapeShieldCableInfo, or a bare OverheadWireInfo |
underground_line_conductor.cimtbl (wire_info) |
underground_line_conductor |
triplex_line_conductor |
OverheadWireInfo |
triplex_line_conductor.cimtbl (wire_info) |
triplex_line_conductor |
line_spacing |
ConductorDistanceSpacing (template) + ConductorDistance |
line_spacing.cimtbl |
line_spacing, one per way lines use it |
line_configuration, geometry |
WireConfiguration + WireSequenceConfiguration |
line_configuration.cimtbl (line_by_wire_configuration) |
line_configuration |
line_configuration, matrix |
PerLengthPhaseImpedance (template) + PhaseImpedanceData; a WireConfiguration lc_<name>_wc |
line_configuration.cimtbl (line_by_impedance) |
line_configuration |
triplex_line_configuration |
WireConfiguration + WireSequenceConfiguration on a derived ConductorDistanceSpacing |
triplex_line_configuration.cimtbl |
triplex_line_configuration |
overhead_line, underground_line, triplex_line |
ACLineSegment, OperationalLimitSet + CurrentLimit |
overhead_line.cimtbl, underground_line.cimtbl, triplex_line.cimtbl |
the three line classes |
switch |
LoadBreakSwitch |
switch.cimtbl (switch) |
switch, for every Switch class but the next three |
fuse |
Fuse |
fuse.cimtbl (switch) |
fuse |
recloser |
Recloser |
recloser.cimtbl (switch) |
recloser |
sectionalizer |
Sectionaliser |
sectionalizer.cimtbl (switch) |
sectionalizer |
series_reactor |
SeriesCompensator |
series_reactor.cimtbl (series_compensator) |
series_reactor |
The shapes are on the core site's shapes page, and the
getters the exporter reads through (get_line_code, get_line_geometry, get_wire_info, get_stored_distances,
get_current_limits) are on its lines reference.
Geometry stays geometry. A line_configuration with a line_spacing and conductors becomes a WireConfiguration
that names a ConductorDistanceSpacing and the wires. GridLAB-D gives distances between conductors and heights above
earth, never coordinates, so the spacing keeps them as distances. No impedance is computed from geometry, on import or
export; the consumer's line constants do that. A matrix configuration is a template: its impedance has isTemplate=true
and sits on a WireConfiguration that names no spacing, and the lines that use it name that WireConfiguration.
Units. On import every length-based value keeps the deck's unit, in the column header (gmr (ft),
rAC50 (ohm/mile), length (ft), b (nS/mile)); a value with an inline unit (length 21 m) gets its own header and its
own table. On export every value is in the unit the GLM slot declares: lengths in feet, conductor diameters in inches,
resistances and impedances per mile, capacitance in nF per mile, ratings in amperes.
Ratings. A link's continuous_rating_X and emergency_rating_X become the normal and emergency CurrentLimit of
the equipment's own OperationalLimitSet <mRID>_limits. One rating per link is mapped, so per-phase ratings that differ
raise. On export the limits are written on each of the link's phases (a triplex line's on its service letter).
Conductors¶
One WireInfo per conductor, in one artifact per GLM class, with the values as the deck writes them. An underground
conductor with neutral_strands above zero is a ConcentricNeutralCableInfo; with shield_thickness above zero a
TapeShieldCableInfo; with neither, a bare OverheadWireInfo. Both set raises. A triplex conductor is an
OverheadWireInfo, since CIM has no triplex class and the insulation is on the configuration. A conductor that sets its
summer ratings gets ratedCurrent and an OperationalLimitSet <mRID>_limits on AssetInfo; ratings left unset are
not filled, and the row comment says so.
The three WireInfo mRIDs are ohc_, ugc_ and tpc_ plus the GLM name.
overhead_line_conductor and triplex_line_conductor¶
| property | import | export |
|---|---|---|
name |
copied to OverheadWireInfo.name |
written: Names |
geometric_mean_radius |
copied to gmr (ft); unset raises (GridLAB-D would take 0, and ln(1/GMR) fails) |
written: get_wire_info gmr (ft); unset raises |
resistance |
copied to rAC50 (ohm/mile), the 50 C AC value; unset raises |
written: rAC50, else rAC25; neither raises |
diameter (overhead only) |
derived: radius = diameter / 2 (in) |
written: 2 x radius; unset when the radius is |
rating_summer_continuous |
copied to ratedCurrent (A); also the normal CurrentLimit of the wire's limit set |
written: the wire's normal limit, else ratedCurrent |
rating_summer_emergency |
structural: the emergency CurrentLimit |
written: the wire's emergency limit |
rating_winter_continuous, rating_winter_emergency |
untranscribed; a value that differs from its summer rating raises | not written |
object header (parent, groupid, latitude, longitude, in_svc, out_svc, rank, flags) |
untranscribed | not written |
underground_line_conductor¶
| property | import | export |
|---|---|---|
name |
copied to the cable's name |
written: Names; <wire>_<class> when one WireInfo is two GLM classes |
conductor_gmr |
copied to gmr (ft); unset raises |
written: gmr |
conductor_resistance |
copied to rAC50 (ohm/mile); unset raises |
written: rAC50, else rAC25 |
conductor_diameter |
derived: radius = conductor_diameter / 2 (in) |
written: 2 x radius; a buried bare wire without a radius raises |
outer_diameter |
copied to diameterOverJacket (in) on a cable; untranscribed on a bare wire |
written: a cable's diameterOverJacket; a bare wire's 1.2 x its diameter (CIM has no jacket, GridLAB-D needs one) |
neutral_strands |
copied to neutralStrandCount; above zero selects ConcentricNeutralCableInfo |
written: neutralStrandCount |
neutral_gmr |
copied to neutralStrandGmr (ft) |
written |
neutral_diameter |
derived: neutralStrandRadius = neutral_diameter / 2 (in) |
written: 2 x neutralStrandRadius |
neutral_resistance |
copied to neutralStrandRDC20 (ohm/mile), the strand's DC value |
written |
shield_thickness |
copied to tapeThickness (in); above zero selects TapeShieldCableInfo |
written |
shield_diameter |
copied to diameterOverScreen (in) |
written |
shield_gmr, shield_resistance |
untranscribed: no CIM home; they follow from the screen diameter and tape thickness | written, for a tape shield only: shield_gmr = diameterOverScreen / 2, shield_resistance = 18.826 / (d x T) ohm/mile, d in inches and T in mils (a tape-shield cable is told by shield_gmr above zero) |
insulation_relative_permitivitty |
untranscribed: no CableInfo home |
not written |
rating_summer_*, rating_winter_*, object header |
as the overhead conductor | as the overhead conductor |
Fail fast. A conductor without its GMR or resistance. An underground conductor with both neutral_strands and
shield_thickness. A cable property set on the wrong kind (a neutral strand on a tape shield). A winter rating that
differs from its summer one. On export, a WireInfo with neither rAC50 nor rAC25, or without a gmr, and a tape
shield without diameterOverScreen and tapeThickness.
Expected differences. A conductor comes back in the class of the configuration that uses it: underground_line_conductor
where any wire of the configuration is a cable, triplex_line_conductor in a triplex configuration, else
overhead_line_conductor. Only conductors some line uses are written. A cable's shield_gmr and shield_resistance are
recomputed.
Excerpt from cimhub_gridlabd/tests/atoms/catalog/catalog.overhead_line_conductor.cimtbl:
Table OverheadWireInfo: mRID, name, gmr (ft), rAC50 (ohm/mile), ratedCurrent (A), OperationalLimitSet
# not filled: rating.summer.emergency
ohc_overhead_line_conductor:3, overhead_line_conductor:3, 0.00814, 0.563, 334.0, ohc_overhead_line_conductor:3_limits
# derived (radius_from_diameter): radius = diameter / 2
Table OverheadWireInfo: mRID, name, gmr (ft), rAC50 (ohm/mile), ratedCurrent (A), radius (in), OperationalLimitSet
# untranscribed: rating_winter_continuous=730.0, rating_winter_emergency=730.0
ohc_wire_acsr_556_5, wire_acsr_556_5, 0.0311, 0.18972, 730.0, 0.4635, ohc_wire_acsr_556_5_limits
line_spacing¶
A line_spacing is a ConductorDistanceSpacing template, spc_<name>, with isTemplate=true, and a
ConductorDistance for each distance the deck writes. A distance between two conductors names both ends (sequenceNumber1,
fromPhase, sequenceNumber2, toPhase); a height is a distance to a position of kind earth, with no second number or
phase. The sequence numbers are 1 to n, in A, B, C, N order, over the phases the written non-zero distances name. A
distance of 0 is GridLAB-D's "no mutual term" (and its default), not two coincident conductors, so it is not written; the
spacing's comment lists it. One ConductorDistance table is written per unit.
| property | import | export |
|---|---|---|
name |
copied to ConductorDistanceSpacing.name; mRID spc_ + name; isTemplate is true |
written: Names; <spacing>_<letters> when lines use it on different phases |
distance_AB, distance_AC, distance_BC, distance_AN, distance_BN, distance_CN |
structural: one ConductorDistance, distance in the written unit; unset or 0 is no row |
written: get_stored_distances between the two phases' sequence numbers; none stored: unset |
distance_AE, distance_BE, distance_CE, distance_NE |
structural: the conductor's height, a distance to earth; unset or 0 is no row | written: the stored height (an XYSpacing's y; a line with a ySpacingOffset raises) |
| object header | untranscribed | not written |
Fail fast. A configuration whose conductors are not the phases its spacing names.
Expected differences. A spacing is written once per way the lines use it. A spacing that came from CIM coordinates
(an XYSpacing) is written as distances and heights, which is all GridLAB-D keeps.
Excerpt from cimhub_gridlabd/tests/atoms/catalog/catalog.line_spacing.cimtbl:
Object ConductorDistanceSpacing: mRID=spc_spc_601_ABCN, name=spc_601_ABCN, isTemplate=true
Table ConductorDistance: mRID, ConductorDistanceSpacing=spc_spc_601_ABCN, sequenceNumber1, conductorKind1, fromPhase, sequenceNumber2, conductorKind2, toPhase, distance (ft)
spc_spc_601_ABCN_AB, 1, phase, A, 2, phase, B, 2.5
spc_spc_601_ABCN_AN, 1, phase, A, 4, neutral, N, 5.6569
spc_spc_601_ABCN_AE, 1, phase, A, , earth, , 28.0
spc_spc_601_ABCN_NE, 4, neutral, N, , earth, , 24.0
(rows abridged) The spacing's own name is spc_601_ABCN, so its mRID reads spc_spc_601_ABCN.
line_configuration¶
A configuration is geometry (spacing with conductor_A to conductor_N) or a matrix (z11 to z33, c11 to c33),
never both. A record with both raises, as does one with neither, because GridLAB-D would use the matrix.
Geometry. A WireConfiguration wc_<name>, numberOfPhases the A, B, C conductors set, WireSpacing the
spacing, and a WireSequenceConfiguration per conductor, numbered 1 to n in A, B, C, N order, as its spacing's positions
are. The conductors must be the phases the spacing names.
Matrix. A template PerLengthPhaseImpedance lc_<name> (isTemplate=true, calculatedFrequency the base frequency),
a PhaseImpedanceData row per lower-triangle element, and a WireConfiguration lc_<name>_wc that holds it and names no
spacing. The rows and columns are compacted to 1 to n over the phases whose z_ii is set and non-zero, so a matrix on A and
C has two rows. r and x are the real and imaginary parts of z, in the written unit (ohm/mile). b is derived from
c as 2 pi f c (b_from_c, nF to nS) at the base frequency, in nS/mile. A mutual term left unset is GridLAB-D's 0 and
the row comment says defaulted. GridLAB-D's matrix is the Kron-reduced A, B, C one and has no neutral terms, so it is
written as given.
| property | import | export |
|---|---|---|
name |
copied to WireConfiguration.name and PerLengthPhaseImpedance.name; mRID wc_ or lc_ + name |
written: Names; <template>_<letters> when lines use it on different phases |
spacing |
structural: geometry, WireConfiguration.WireSpacing = spc_ + spacing; without conductors raises |
written: the line_spacing of the configuration |
conductor_A, conductor_B, conductor_C, conductor_N |
structural: geometry, one WireSequenceConfiguration each, WireInfo the conductor's mRID; must be a conductor of the line's class |
written: the wire at the line's phase's sequence number |
z11 to z33 |
structural: matrix, PhaseImpedanceData.r and x; z_ij must equal z_ji; an off-diagonal term without both diagonals raises |
written: r + jx (ohm/mile) by phase letter, a neutral row Kron-reduced out; a sequence code is expanded by the getter |
c11 to c33 |
derived: PhaseImpedanceData.b = b_from_c(c) (nS/mile); in nF per length only |
written: c_from_b(b) (nF/mile) at the base frequency; b unset: unset |
rating_summer_*, rating_winter_* |
structural: not on the template; the line mapper puts the configuration's on each line that sets none | unset: ratings are each line's own |
| object header | untranscribed | not written |
Fail fast. A matrix and geometry together, or neither. spacing without conductors or the reverse. Conductors that
are not the spacing's phases. A conductor or spacing that names no object, or an object of the wrong class (a triplex
conductor on a line_configuration). A z_ij that differs from z_ji. Every z_ii unset or 0. A c written in other
than nF per length. A matrix whose z values are in different units. On export, a WireConfiguration that has neither a
WireSpacing nor a PerLengthImpedance (its own or the line's); a PerLengthImpedance and a different WireConfiguration
impedance on one line.
Expected differences. A template that lines use on different phases is one GLM configuration per use,
<template>_<letters>; a template no line uses is not written. A sequence code (PerLengthSequenceImpedance) comes back
as a matrix, since GridLAB-D has no sequence form. A neutral row of a matrix is Kron-reduced out. Geometry lines are not
reduced to impedance in either direction, so each engine computes its own line constants.
Excerpt from cimhub_gridlabd/tests/atoms/catalog/catalog.line_configuration.cimtbl (geometry lcon_601, matrix
lcon_mtx604_AC):
Object WireConfiguration: mRID=wc_lcon_601, name=lcon_601, numberOfPhases=3, WireSpacing=spc_spc_601_ABCN
Table WireSequenceConfiguration: mRID, WireConfiguration=wc_lcon_601, sequenceNumber, WireInfo
wc_lcon_601_A, 1, ohc_wire_acsr_556_5
wc_lcon_601_N, 4, ohc_overhead_line_conductor:3
Object PerLengthPhaseImpedance: mRID=lc_lcon_mtx604_AC, name=lcon_mtx604_AC, conductorCount=2, calculatedFrequency (Hz)=60.0, isTemplate=true
# derived: b = 2 pi f c (b_from_c)
Table PhaseImpedanceData: identifier, PhaseImpedance=lc_lcon_mtx604_AC, row, column, r (ohm/mile), x (ohm/mile), b (nS/mile)
# z31 (CA); defaulted: c = 0
lc_lcon_mtx604_AC_21, 2, 1, 0.2066, 0.4591, 0.0
(rows abridged)
triplex_line_configuration¶
A triplex configuration is geometry too, but GridLAB-D computes its spacing from diameter and insulation_thickness:
the two insulated phase conductors touch, and the bare neutral touches both. The importer writes that spacing as a derived
ConductorDistanceSpacing wc_<name>_spc with positions s1, s2, N (1, 2, 3), and a WireConfiguration
wc_<name> with numberOfPhases 2 and a WireSequenceConfiguration per conductor.
| property | import | export |
|---|---|---|
name |
copied to WireConfiguration.name; mRID wc_ + name |
written: Names, as line_configuration |
conductor_1, conductor_2, conductor_N |
structural: WireSequenceConfiguration 1, 2, 3 (spacing phases s1, s2, N); required |
written: the wire at s1, s2, N |
diameter, insulation_thickness |
derived: the spacing's distances, D12 = diameter + 2 insulation_thickness, D1N = D2N = diameter + insulation_thickness (in); both required, in one unit |
written: insulation_thickness = D12 - D1N, diameter = 2 D1N - D12 |
spacing, conductor_A, conductor_B, conductor_C |
raises when set: GridLAB-D's triplex line does not read them | unset |
z11, z12, z21, z22 |
structural: the matrix form, which GridLAB-D uses as given on legs 1 and 2. A template PerLengthPhaseImpedance lc_<name> on s1, s2 with b 0 (no shunt admittance), held by WireConfiguration lc_<name>_wc; its lines are s1s2. z11 and z22 required, z12 equal to z21; with geometry raises |
written, for a line whose impedance is a matrix: on s1, s2, with N Kron-reduced out |
the other z and every c |
raises when set: GridLAB-D's triplex line does not read them | unset: c is never written |
rating_summer_*, rating_winter_* |
structural: as line_configuration |
unset: ratings are each line's own |
| object header | untranscribed | not written |
Fail fast. A conductor, diameter or insulation_thickness unset. A D12 or D1N that is not positive. A conductor of
a class other than triplex_line_conductor. On export, a triplex spacing without s1, s2 and N positions, or whose
D1N and D2N differ by more than a relative 1e-5: GridLAB-D's triplex spacing is symmetric.
Expected differences. A triplex matrix's susceptance is not written, and is logged once per configuration:
GridLAB-D's triplex_line has no shunt admittance, so no slot holds it. IEEE 8500's triplex codes carry about 0.1 VAr
per kft at 240 V. The importer reads the exported z11 to z22 back as the same s1, s2 matrix; a CIM triplex
matrix with a neutral row comes back without it (Kron-reduced).
Excerpt from cimhub_gridlabd/tests/atoms/catalog/catalog.triplex_line_configuration.cimtbl:
# derived (triplex_spacing): D12 = diameter + 2 insulation_thickness, D1N = D2N = diameter + insulation_thickness; diameter=0.522, insulation_thickness=0.08 in
Object ConductorDistanceSpacing: mRID=wc_triplex_line_configuration:1_spc, name=triplex_line_configuration:1, isTemplate=true
Table ConductorDistance: mRID, ConductorDistanceSpacing=wc_triplex_line_configuration:1_spc, sequenceNumber1, conductorKind1, fromPhase, sequenceNumber2, conductorKind2, toPhase, distance (in)
wc_triplex_line_configuration:1_spc_12, 1, phase, s1, 2, phase, s2, 0.682
wc_triplex_line_configuration:1_spc_1N, 1, phase, s1, 3, neutral, N, 0.602
overhead_line, underground_line, triplex_line¶
A line is an ACLineSegment ln_<name>, in EquipmentContainer fdr_<feeder>, that names its configuration's
WireConfiguration (wc_<configuration>, or lc_<configuration>_wc for a matrix) and the walk's BaseVoltage. Its
node1 and node2 are the root buses of from and to. The phases cell is written in the configuration's own order
(A, B, C, then N, and s1s2N on a triplex line) because the per-phase objects are numbered in that order, and it must
name the configuration's phases: a geometry line's must equal its conductors, a matrix line's its diagonal (a matrix
line never reads N, so it is dropped from the cell). A table is written per length unit, then the limit sets.
| property | import | export |
|---|---|---|
name |
copied to ACLineSegment.name; mRID ln_ + name |
written: Names |
phases |
structural: the phases cell as above; D on any line, S on a non-triplex line, or a triplex line other than AS, BS, CS raises |
written: the line's A, B, C, then N when it has a neutral conductor; a triplex line its buses' service letter, then S |
from, to |
structural: node1, node2, the root bus of the object named |
written: terminal 1's and terminal 2's bus |
length |
copied to length (ft, or the unit the deck writes); unset raises (GridLAB-D's 0 is a line of no impedance) |
written: ACLineSegment.length (ft); unset raises |
configuration |
structural: the WireConfiguration; must be this line class's configuration (a triplex_line_configuration on a triplex_line, a line_configuration on the others); unset raises |
written: the configuration of the line's template |
continuous_rating_A to _C, emergency_rating_A to _C |
structural: the normal and emergency CurrentLimit of ln_<name>_limits; else the configuration's, noted ratings: from ... |
written: get_current_limits on each of the line's phases |
status |
structural: unset or CLOSED; OPEN raises (a line is not a switch) |
not written |
nominal_voltage, mean_repair_time, pdispatch, pdispatch_offset, set_pdispatch, solver outputs (power_*, current_*, fault_*, flow_direction, overloaded_status), inrush_*, object header |
untranscribed | not written |
A line's own rating that differs from its configuration's raises.
The exporter picks the GLM class from the line. A split-phase line (s1, s2) is a triplex_line; a geometry line whose
wires include a cable is an underground_line; every other line is an overhead_line. A line is geometry when its
WireConfiguration names a WireSpacing, whatever else it has; otherwise its impedance (the line's own
PerLengthImpedance, else its WireConfiguration's) is a matrix configuration; neither raises.
Fail fast. A line without configuration, length or phases. A configuration of the wrong class. An overhead line on
underground conductors, or the reverse, and an underground line whose phase cables are not one kind. A geometry line
whose phases are not its configuration's conductors, or a matrix line whose phases are not its diagonal. A triplex line
whose ends the walk does not put on a split-phase system. A status OPEN. Ratings that differ across a link's phases.
Expected differences. The configuration's ratings come back on each line. A line length is written in feet, so a
21 m line comes back as 68.8976 ft. A line keeps its name; the configuration it names may be renamed (line_configuration:18
returns as line_configuration_18). Phases come back in A, B, C, N order (CA returns as AC).
Excerpt from cimhub_gridlabd/tests/atoms/line/line.overhead_line.cimtbl:
Table ACLineSegment: mRID, name, node1, node2, phases, length (ft), WireConfiguration, BaseVoltage, EquipmentContainer=fdr_line
ln_l1, l1, src, n1, ABCN, 500.0, wc_lcon_601, bv_4p16kv
ln_line_l2, line_l2, n1, n4, AC, 300.0, lc_lcon_mtx604_AC_wc, bv_4p16kv
Table ACLineSegment: mRID, name, node1, node2, phases, length (m), WireConfiguration, BaseVoltage, EquipmentContainer=fdr_line
ln_overhead_line:3, overhead_line:3, n1, n5, AN, 21.0, wc_line_configuration:18, bv_4p16kv
The steps from a deck to this table, and back to a deck:
from cimtables.document import format_document
from cimhub_gridlabd.glm_reader import GlmReader
from cimhub_gridlabd.importer.glm_to_cimtbl import GlmImporter, glm_to_cim
from cimhub_gridlabd.exporter.cim_to_glm import GlmExporter
model = GlmReader("cimhub_gridlabd/tests/atoms/line/line.glm").read_all()
documents = GlmImporter("line").to_cimtbl(model)
lines = next(part for part in documents.parts if part.name == "overhead_line")
print("\n".join(format_document(lines).splitlines()[6:9]))
network = glm_to_cim(model, name="line")
exported = GlmExporter().to_model(network, name_source="name")
cls = next(c for c in exported.graph if c.class_name == "line_configuration")
print(sorted(record.name for record in exported.graph[cls].values()))
switch, fuse, recloser, sectionalizer¶
A switching device is a LoadBreakSwitch, Fuse, Recloser or Sectionaliser sw_<name>, in one artifact per GLM
class. A sectionalizer adds no properties to switch, so it maps the same way. GLM gives a
device one state, status, so it becomes both open and normalOpen. The phases cell is the switched conductors with
N dropped, and blank when they are A, B and C. A switching device OPEN between laterals on different phases (a tie from
an A lateral to a B one) takes phaseSide1, the switched conductors, and phaseSide2, its to end's, instead of
phases, with a row note. GridLAB-D cannot load that deck, but CIM holds it.
| property | import | export |
|---|---|---|
name |
copied to the device's name; mRID sw_ + name |
written: Names |
phases |
structural: the switched conductors A, B, C, N dropped; blank when ABC; none of A, B, C raises |
written: side 1's A, B, C |
from, to |
structural: node1, node2, root buses |
written: terminal 1's and terminal 2's bus |
status |
structural: OPEN is open and normalOpen true; unset is CLOSED, listed as defaulted |
written: OPEN or CLOSED from get_switch_state, by the caller's switch_state: "actual" (Switch.open, the default) or "normal" (normalOpen) |
phase_A_state, phase_B_state, phase_C_state (switch, recloser) |
structural: must equal status on a phase the device has, else raises; on a phase it lacks, listed on the row |
not written |
phase_A_status, phase_B_status, phase_C_status (fuse) |
structural: unset or GOOD; BLOWN on a phase the fuse has raises |
not written |
current_limit (fuse) |
copied to Fuse.ratedCurrent (A); unset: not filled, the row says so |
written: Fuse.ratedCurrent |
continuous_rating_A to _C, emergency_rating_A to _C |
structural: the device's <mRID>_limits |
written: get_current_limits, on side 1's phases |
operating_mode, switch_impedance, switch_resistance, switch_reactance, fuse_resistance |
untranscribed: a numerical stand-in for a closed device, or the operating mode (with every phase state equal to status the modes act alike) |
not written |
retry_time, max_number_of_tries, number_of_tries (recloser) |
untranscribed: protection settings and state | not written |
repair_dist_type, mean_replacement_time (fuse), mean_repair_time |
untranscribed: reliability data | not written |
nominal_voltage, solver outputs, object header |
untranscribed | not written |
Fail fast. A phase state that differs from status on a phase the device has; a BLOWN fuse phase; phases other
than A, B, C and N; an end that is no bus object; phases that are not on both end objects (only an OPEN device between laterals on different phases may differ).
Expected differences. On export a CIM Sectionaliser is a sectionalizer, a Fuse a fuse, a Recloser a recloser, and every other switch class a
switch: GridLAB-D has no breaker. A recloser's retry settings, a fuse's resistance and all per-phase states are lost.
A tie across phases is written on side 1's phases.
Excerpt from cimhub_gridlabd/tests/atoms/line/line.switch.cimtbl and line.fuse.cimtbl:
Table LoadBreakSwitch: mRID, name, node1, node2, phases, open, normalOpen, BaseVoltage, EquipmentContainer=fdr_line
sw_swt_s1, swt_s1, n1, n2, , false, false, bv_4p16kv
sw_swt_s2, swt_s2, n5, n7, A, true, true, bv_4p16kv
Table Fuse: mRID, name, node1, node2, phases, ratedCurrent (A), open, normalOpen, BaseVoltage, EquipmentContainer=fdr_line
# untranscribed: mean_replacement_time=3600.0
sw_fuse_1, fuse_1, n4, n8, C, 50000.0, false, false, bv_4p16kv
# not filled: current_limit
sw_fuse_2, fuse_2, n5, n9, A, , false, false, bv_4p16kv
series_reactor¶
A series_reactor is a SeriesCompensator rx_<name>. GridLAB-D's reactor is one impedance per phase with no coupling
between phases, while CIM's SeriesCompensator is one r + jx for every phase, so the phases' phase_X_impedance must
be equal. r0 and x0 are written equal to r and x. SeriesCompensator has no per-phase class, so a reactor on fewer
than three phases gives its two Terminals those phases in an Update Table Terminal.
| property | import | export |
|---|---|---|
name |
copied to SeriesCompensator.name; mRID rx_ + name |
written: Names |
phases |
structural: A, B, C, N dropped; fewer than three also sets the Terminals' phases |
written: the compensator's A, B, C |
from, to |
structural: node1, node2, root buses |
written: terminal 1's and terminal 2's bus |
phase_A_impedance, phase_B_impedance, phase_C_impedance |
copied to r, x, r0, x0 (ohm): the real and imaginary parts, r0 = r, x0 = x; the reactor's phases must agree, and one unset raises (GridLAB-D's 0 is a switch stand-in under NR, not a reactor) |
written: get_series_compensator r + jx (ohm) on each of its phases; r0 or x0 that differ from r or x raise, and so does a varistor |
phase_A_resistance, phase_A_reactance, and the B and C pairs |
raises when set: GridLAB-D's aliases of the impedance's parts | not mapped: phase_X_impedance is written |
continuous_rating_A to _C, emergency_rating_A to _C |
structural: the reactor's <mRID>_limits |
written: get_current_limits |
status |
structural: unset or CLOSED; OPEN raises |
not written |
| object header, solver outputs | untranscribed | not written |
Fail fast. Phases whose impedances differ, or an impedance unset or in different units; phase_X_resistance or
phase_X_reactance set; status OPEN. On export, r0 or x0 that differ from r or x; a varistor.
Expected differences. Impedances are written in ohms on every phase of the compensator. A reactor on one phase comes back with that phase's impedance only.
Excerpt from cimhub_gridlabd/tests/atoms/series_reactor/series_reactor.series_reactor.cimtbl:
# r0 = r, x0 = x: GridLAB-D's reactor has no coupling between phases
Table SeriesCompensator: mRID, name, node1, node2, r (ohm), x (ohm), r0 (ohm), x0 (ohm), BaseVoltage, EquipmentContainer=fdr_atom
rx_hsb, hsb, n2, rb1, 0.0, 14.798307, 0.0, 14.798307, bv_4p16kv
rx_r1, r1, rb1, rb2, 0.5, 2.0, 0.5, 2.0, bv_4p16kv
# SeriesCompensator has no per-phase class: a reactor on fewer than three phases gives its Terminals their phases here
Update Table Terminal: mRID, phases
rx_r1_T1, B
rx_r1_T2, B