Class: RegulatorConfiguration¶
Copyright (C) 2008 Battelle Memorial Institute
@file regulator_configuration.cpp
@addtogroup regulator_configuration
@ingroup regulator
@{
__
Inherits from: powerflow_library
__
Type: Configuration (physical asset template)
__
Note: Inherits from powerflow_library (not in powerflow module)
URI: glm:RegulatorConfiguration
classDiagram
class RegulatorConfiguration
click RegulatorConfiguration href "../RegulatorConfiguration/"
GlmObject <|-- RegulatorConfiguration
click GlmObject href "../GlmObject/"
RegulatorConfiguration : band_center
RegulatorConfiguration : band_width
RegulatorConfiguration : compensator_r_setting_A
RegulatorConfiguration : compensator_r_setting_B
RegulatorConfiguration : compensator_r_setting_C
RegulatorConfiguration : compensator_x_setting_A
RegulatorConfiguration : compensator_x_setting_B
RegulatorConfiguration : compensator_x_setting_C
RegulatorConfiguration : connect_type
RegulatorConfiguration --> "0..1" ConnectType : connect_type
click ConnectType href "../ConnectType/"
RegulatorConfiguration : Control
RegulatorConfiguration : control_level
RegulatorConfiguration : CT_phase
RegulatorConfiguration : current_transducer_ratio
RegulatorConfiguration : dwell_time
RegulatorConfiguration : flags
RegulatorConfiguration : groupid
RegulatorConfiguration : in_svc
RegulatorConfiguration : latitude
RegulatorConfiguration : longitude
RegulatorConfiguration : lower_taps
RegulatorConfiguration : name
RegulatorConfiguration : out_svc
RegulatorConfiguration : parent
RegulatorConfiguration : power_transducer_ratio
RegulatorConfiguration : PT_phase
RegulatorConfiguration : raise_taps
RegulatorConfiguration : rank
RegulatorConfiguration : regulation
RegulatorConfiguration : reverse_flow_control
RegulatorConfiguration : tap_pos_A
RegulatorConfiguration : tap_pos_B
RegulatorConfiguration : tap_pos_C
RegulatorConfiguration : time_delay
RegulatorConfiguration : Type
Inheritance¶
- GlmObject
- RegulatorConfiguration
Slots¶
| Name | Cardinality and Range | Description | Inheritance |
|---|---|---|---|
| connect_type | 0..1 ConnectType |
Designation of connection style | direct |
| band_center | 0..1 Float |
band center setting of regulator control | direct |
| band_width | 0..1 Float |
band width setting of regulator control | direct |
| time_delay | 0..1 Float |
mechanical time delay between tap changes | direct |
| dwell_time | 0..1 Float |
time delay before a control action of regulator control | direct |
| raise_taps | 0..1 Integer |
number of regulator raise taps, or the maximum raise voltage tap position | direct |
| lower_taps | 0..1 Integer |
number of regulator lower taps, or the minimum lower voltage tap position | direct |
| current_transducer_ratio | 0..1 Float |
primary rating of current transformer | direct |
| power_transducer_ratio | 0..1 Float |
potential transformer rating | direct |
| compensator_r_setting_A | 0..1 Float |
Line Drop Compensation R setting of regulator control (in volts) on Phase A | direct |
| compensator_r_setting_B | 0..1 Float |
Line Drop Compensation R setting of regulator control (in volts) on Phase B | direct |
| compensator_r_setting_C | 0..1 Float |
Line Drop Compensation R setting of regulator control (in volts) on Phase C | direct |
| compensator_x_setting_A | 0..1 Float |
Line Drop Compensation X setting of regulator control (in volts) on Phase A | direct |
| compensator_x_setting_B | 0..1 Float |
Line Drop Compensation X setting of regulator control (in volts) on Phase B | direct |
| compensator_x_setting_C | 0..1 Float |
Line Drop Compensation X setting of regulator control (in volts) on Phase C | direct |
| CT_phase | 0..1 String |
phase(s) monitored by CT | direct |
| PT_phase | 0..1 String |
phase(s) monitored by PT | direct |
| regulation | 0..1 Float |
regulation of voltage regulator in % | direct |
| control_level | 0..1 String |
Designates whether control is on per-phase or banked level | direct |
| Control | 0..1 String |
Type of control used for regulating voltage | direct |
| reverse_flow_control | 0..1 String |
Type of control used when power is flowing in reverse through the regulator | direct |
| Type | 0..1 String |
Defines regulator type | direct |
| tap_pos_A | 0..1 Integer |
initial tap position of phase A | direct |
| tap_pos_B | 0..1 Integer |
initial tap position of phase B | direct |
| tap_pos_C | 0..1 Integer |
initial tap position of phase C | direct |
| name | 1 String |
The object's name; unique across the model | GlmObject |
| parent | 0..1 String |
The parent object's name | GlmObject |
| groupid | 0..1 String |
Free-text group label | GlmObject |
| latitude | 0..1 String |
Latitude, as written (decimal degrees or GridLAB-D's 37N26:12 form) | GlmObject |
| longitude | 0..1 String |
Longitude, as written | GlmObject |
| in_svc | 0..1 String |
Timestamp the object enters service | GlmObject |
| out_svc | 0..1 String |
Timestamp the object leaves service | GlmObject |
| rank | 0..1 String |
Solver rank | GlmObject |
| flags | 0..1 String |
Core object flags | GlmObject |
Comments¶
- Import: no CIM template, so no class of its own; its values go on the VoltageRegulator, RatioTapChanger and TapChangerControl of every regulator that names it. Export: written from the VoltageRegulator's tap changer and its control as
_config.
Identifier and Mapping Information¶
Schema Source¶
- from schema: https://gridlabd.org/schema/glm
Mappings¶
| Mapping Type | Mapped Value |
|---|---|
| self | glm:RegulatorConfiguration |
| native | glm:RegulatorConfiguration |
| close | cim:RatioTapChanger, cim:TapChangerControl, cim:VoltageRegulator |
LinkML Source¶
Direct¶
name: regulator_configuration
description: 'Copyright (C) 2008 Battelle Memorial Institute
@file regulator_configuration.cpp
@addtogroup regulator_configuration
@ingroup regulator
@{
Inherits from: powerflow_library
Type: Configuration (physical asset template)
Note: Inherits from powerflow_library (not in powerflow module)'
comments:
- 'Import: no CIM template, so no class of its own; its values go on the VoltageRegulator,
RatioTapChanger and TapChangerControl of every regulator that names it. Export:
written from the VoltageRegulator''s tap changer and its control as <regulator>_config.'
from_schema: https://gridlabd.org/schema/glm
close_mappings:
- cim:RatioTapChanger
- cim:TapChangerControl
- cim:VoltageRegulator
is_a: glm_object
attributes:
connect_type:
name: connect_type
annotations:
order:
tag: order
value: 1
value_type:
tag: value_type
value: string
native_name:
tag: native_name
value: connect_type
description: Designation of connection style
comments:
- 'Import: WYE_WYE only (every AutoTransformerEnd wye, grounded); any other raises.
Export: always WYE_WYE.'
from_schema: https://gridlabd.org/schema/glm/powerflow/regulator_configuration
related_mappings:
- cim:TransformerEnd.grounded
rank: 1000
domain_of:
- regulator_configuration
- transformer_configuration
range: ConnectType
required: false
band_center:
name: band_center
annotations:
order:
tag: order
value: 2
value_type:
tag: value_type
value: float
precision:
tag: precision
value: 6
native_name:
tag: native_name
value: band_center[V]
description: band center setting of regulator control
comments:
- 'Import: TapChangerControl.targetValue (V), primary volts; on LINE_DROP_COMP
x power_transducer_ratio. Export: the target (V), over ptRatio on LINE_DROP_COMP;
unset when the control is disabled.'
from_schema: https://gridlabd.org/schema/glm/powerflow/regulator_configuration
close_mappings:
- cim:RegulatingControl.targetValue
rank: 1000
domain_of:
- regulator_configuration
range: float
required: false
unit:
ucum_code: V
band_width:
name: band_width
annotations:
order:
tag: order
value: 3
value_type:
tag: value_type
value: float
precision:
tag: precision
value: 6
native_name:
tag: native_name
value: band_width[V]
description: band width setting of regulator control
comments:
- 'Import: TapChangerControl.targetDeadband (V), the full band, as band_center.
Export: the deadband (V), likewise.'
from_schema: https://gridlabd.org/schema/glm/powerflow/regulator_configuration
close_mappings:
- cim:RegulatingControl.targetDeadband
rank: 1000
domain_of:
- regulator_configuration
range: float
required: false
unit:
ucum_code: V
time_delay:
name: time_delay
annotations:
order:
tag: order
value: 4
value_type:
tag: value_type
value: float
precision:
tag: precision
value: 6
native_name:
tag: native_name
value: time_delay[s]
description: mechanical time delay between tap changes
comments:
- 'Import: RatioTapChanger.initialDelay and subsequentDelay (s) = dwell_time +
time_delay. Export: see dwell_time.'
from_schema: https://gridlabd.org/schema/glm/powerflow/regulator_configuration
close_mappings:
- cim:TapChanger.initialDelay
- cim:TapChanger.subsequentDelay
domain_of:
- capacitor
- regulator_configuration
range: float
required: false
unit:
ucum_code: s
dwell_time:
name: dwell_time
annotations:
order:
tag: order
value: 5
value_type:
tag: value_type
value: float
precision:
tag: precision
value: 6
native_name:
tag: native_name
value: dwell_time[s]
description: time delay before a control action of regulator control
comments:
- 'Import: with time_delay. Export: the initialDelay (s).'
from_schema: https://gridlabd.org/schema/glm/powerflow/regulator_configuration
close_mappings:
- cim:TapChanger.initialDelay
- cim:TapChanger.subsequentDelay
domain_of:
- capacitor
- regulator_configuration
range: float
required: false
unit:
ucum_code: s
raise_taps:
name: raise_taps
annotations:
order:
tag: order
value: 6
value_type:
tag: value_type
value: string
native_name:
tag: native_name
value: raise_taps
description: number of regulator raise taps, or the maximum raise voltage tap
position
comments:
- 'Import: RatioTapChanger.highStep, also the stepVoltageIncrement divisor; 0
raises. Export: highStep - neutralStep.'
from_schema: https://gridlabd.org/schema/glm/powerflow/regulator_configuration
exact_mappings:
- cim:TapChanger.highStep
rank: 1000
domain_of:
- regulator_configuration
range: integer
required: false
lower_taps:
name: lower_taps
annotations:
order:
tag: order
value: 7
value_type:
tag: value_type
value: string
native_name:
tag: native_name
value: lower_taps
description: number of regulator lower taps, or the minimum lower voltage tap
position
comments:
- 'Import: RatioTapChanger.lowStep = -lower_taps; 0 raises. Export: neutralStep
- lowStep.'
from_schema: https://gridlabd.org/schema/glm/powerflow/regulator_configuration
close_mappings:
- cim:TapChanger.lowStep
rank: 1000
domain_of:
- regulator_configuration
range: integer
required: false
current_transducer_ratio:
name: current_transducer_ratio
annotations:
order:
tag: order
value: 8
value_type:
tag: value_type
value: float
precision:
tag: precision
value: 6
native_name:
tag: native_name
value: current_transducer_ratio[pu]
description: primary rating of current transformer
comments:
- 'Import: RatioTapChanger.ctRatio, and the line drop''s CT ratio. Export: ctRatio.'
from_schema: https://gridlabd.org/schema/glm/powerflow/regulator_configuration
exact_mappings:
- cim:TapChanger.ctRatio
rank: 1000
domain_of:
- regulator_configuration
range: float
required: false
unit:
ucum_code: pu
power_transducer_ratio:
name: power_transducer_ratio
annotations:
order:
tag: order
value: 9
value_type:
tag: value_type
value: float
precision:
tag: precision
value: 6
native_name:
tag: native_name
value: power_transducer_ratio[pu]
description: potential transformer rating
comments:
- 'Import: TapChangerControl.ptRatio and RatioTapChanger.ptRatio. Export: ptRatio.'
from_schema: https://gridlabd.org/schema/glm/powerflow/regulator_configuration
exact_mappings:
- cim:RegulatingControl.ptRatio
- cim:TapChanger.ptRatio
rank: 1000
domain_of:
- regulator_configuration
range: float
required: false
unit:
ucum_code: pu
compensator_r_setting_A:
name: compensator_r_setting_A
annotations:
order:
tag: order
value: 10
value_type:
tag: value_type
value: float
precision:
tag: precision
value: 6
native_name:
tag: native_name
value: compensator_r_setting_A[V]
description: Line Drop Compensation R setting of regulator control (in volts)
on Phase A
comments:
- 'Import: TapChangerControl.lineDropR (ohm) = the setting x power_transducer_ratio
/ current_transducer_ratio; needs both ratios. Export: lineDropR x ctRatio /
ptRatio on phase A.'
from_schema: https://gridlabd.org/schema/glm/powerflow/regulator_configuration
close_mappings:
- cim:TapChangerControl.lineDropR
rank: 1000
domain_of:
- regulator_configuration
range: float
required: false
unit:
ucum_code: V
compensator_r_setting_B:
name: compensator_r_setting_B
annotations:
order:
tag: order
value: 11
value_type:
tag: value_type
value: float
precision:
tag: precision
value: 6
native_name:
tag: native_name
value: compensator_r_setting_B[V]
description: Line Drop Compensation R setting of regulator control (in volts)
on Phase B
comments:
- 'Import: TapChangerControl.lineDropR (ohm) = the setting x power_transducer_ratio
/ current_transducer_ratio; needs both ratios. Export: lineDropR x ctRatio /
ptRatio on phase B.'
from_schema: https://gridlabd.org/schema/glm/powerflow/regulator_configuration
close_mappings:
- cim:TapChangerControl.lineDropR
rank: 1000
domain_of:
- regulator_configuration
range: float
required: false
unit:
ucum_code: V
compensator_r_setting_C:
name: compensator_r_setting_C
annotations:
order:
tag: order
value: 12
value_type:
tag: value_type
value: float
precision:
tag: precision
value: 6
native_name:
tag: native_name
value: compensator_r_setting_C[V]
description: Line Drop Compensation R setting of regulator control (in volts)
on Phase C
comments:
- 'Import: TapChangerControl.lineDropR (ohm) = the setting x power_transducer_ratio
/ current_transducer_ratio; needs both ratios. Export: lineDropR x ctRatio /
ptRatio on phase C.'
from_schema: https://gridlabd.org/schema/glm/powerflow/regulator_configuration
close_mappings:
- cim:TapChangerControl.lineDropR
rank: 1000
domain_of:
- regulator_configuration
range: float
required: false
unit:
ucum_code: V
compensator_x_setting_A:
name: compensator_x_setting_A
annotations:
order:
tag: order
value: 13
value_type:
tag: value_type
value: float
precision:
tag: precision
value: 6
native_name:
tag: native_name
value: compensator_x_setting_A[V]
description: Line Drop Compensation X setting of regulator control (in volts)
on Phase A
comments:
- 'Import: TapChangerControl.lineDropX (ohm), as the r setting. Export: lineDropX
x ctRatio / ptRatio on phase A.'
from_schema: https://gridlabd.org/schema/glm/powerflow/regulator_configuration
close_mappings:
- cim:TapChangerControl.lineDropX
rank: 1000
domain_of:
- regulator_configuration
range: float
required: false
unit:
ucum_code: V
compensator_x_setting_B:
name: compensator_x_setting_B
annotations:
order:
tag: order
value: 14
value_type:
tag: value_type
value: float
precision:
tag: precision
value: 6
native_name:
tag: native_name
value: compensator_x_setting_B[V]
description: Line Drop Compensation X setting of regulator control (in volts)
on Phase B
comments:
- 'Import: TapChangerControl.lineDropX (ohm), as the r setting. Export: lineDropX
x ctRatio / ptRatio on phase B.'
from_schema: https://gridlabd.org/schema/glm/powerflow/regulator_configuration
close_mappings:
- cim:TapChangerControl.lineDropX
rank: 1000
domain_of:
- regulator_configuration
range: float
required: false
unit:
ucum_code: V
compensator_x_setting_C:
name: compensator_x_setting_C
annotations:
order:
tag: order
value: 15
value_type:
tag: value_type
value: float
precision:
tag: precision
value: 6
native_name:
tag: native_name
value: compensator_x_setting_C[V]
description: Line Drop Compensation X setting of regulator control (in volts)
on Phase C
comments:
- 'Import: TapChangerControl.lineDropX (ohm), as the r setting. Export: lineDropX
x ctRatio / ptRatio on phase C.'
from_schema: https://gridlabd.org/schema/glm/powerflow/regulator_configuration
close_mappings:
- cim:TapChangerControl.lineDropX
rank: 1000
domain_of:
- regulator_configuration
range: float
required: false
unit:
ucum_code: V
CT_phase:
name: CT_phase
annotations:
order:
tag: order
value: 16
value_type:
tag: value_type
value: string
native_name:
tag: native_name
value: CT_phase
description: phase(s) monitored by CT
comments:
- 'Import: BANK: the phase whose compensator setting is read, which must be PT_phase;
INDIVIDUAL: ignored. Export: BANK: the monitored phase, else its first.'
from_schema: https://gridlabd.org/schema/glm/powerflow/regulator_configuration
related_mappings:
- cim:RegulatingControl.monitoredPhase
rank: 1000
domain_of:
- regulator_configuration
range: string
required: false
PT_phase:
name: PT_phase
annotations:
order:
tag: order
value: 17
value_type:
tag: value_type
value: string
native_name:
tag: native_name
value: PT_phase
description: phase(s) monitored by PT
comments:
- 'Import: BANK: TapChangerControl.monitoredPhase; INDIVIDUAL: ignored. Export:
BANK: the monitored phase, else its first.'
from_schema: https://gridlabd.org/schema/glm/powerflow/regulator_configuration
related_mappings:
- cim:RegulatingControl.monitoredPhase
rank: 1000
domain_of:
- regulator_configuration
range: string
required: false
regulation:
name: regulation
annotations:
order:
tag: order
value: 18
value_type:
tag: value_type
value: float
precision:
tag: precision
value: 6
native_name:
tag: native_name
value: regulation
description: regulation of voltage regulator in %
comments:
- 'Import: stepVoltageIncrement (percent) = regulation / raise_taps; 0 raises
unless MANUAL. Export: stepVoltageIncrement x raise_taps (per unit).'
from_schema: https://gridlabd.org/schema/glm/powerflow/regulator_configuration
close_mappings:
- cim:RatioTapChanger.stepVoltageIncrement
rank: 1000
domain_of:
- regulator_configuration
range: float
required: false
unit:
ucum_code: pu
control_level:
name: control_level
annotations:
order:
tag: order
value: 19
value_type:
tag: value_type
value: string
native_name:
tag: native_name
value: control_level
description: Designates whether control is on per-phase or banked level
comments:
- 'Import: INDIVIDUAL (default) is a unit per wired phase, BANK one gang unit.
Export: BANK for one VoltageRegulator alone, else INDIVIDUAL.'
from_schema: https://gridlabd.org/schema/glm/powerflow/regulator_configuration
domain_of:
- capacitor
- regulator_configuration
range: string
required: false
Control:
name: Control
annotations:
order:
tag: order
value: 20
value_type:
tag: value_type
value: string
native_name:
tag: native_name
value: Control
description: Type of control used for regulating voltage
comments:
- 'Import: MANUAL (default) is enabled = controlEnabled = false; OUTPUT_VOLTAGE
and LINE_DROP_COMP true, lineDropCompensation on LINE_DROP_COMP only; REMOTE_NODE
on the regulator''s own output as OUTPUT_VOLTAGE. Export: MANUAL when the control
is disabled or absent, LINE_DROP_COMP with line drop compensation, else OUTPUT_VOLTAGE.'
from_schema: https://gridlabd.org/schema/glm/powerflow/regulator_configuration
close_mappings:
- cim:AutomationFunction.enabled
- cim:TapChangerControl.lineDropCompensation
- cim:TapChanger.controlEnabled
rank: 1000
domain_of:
- regulator_configuration
range: string
required: false
reverse_flow_control:
name: reverse_flow_control
annotations:
order:
tag: order
value: 21
value_type:
tag: value_type
value: string
native_name:
tag: native_name
value: reverse_flow_control
description: Type of control used when power is flowing in reverse through the
regulator
from_schema: https://gridlabd.org/schema/glm/powerflow/regulator_configuration
rank: 1000
domain_of:
- regulator_configuration
range: string
required: false
Type:
name: Type
annotations:
order:
tag: order
value: 22
value_type:
tag: value_type
value: string
native_name:
tag: native_name
value: Type
description: Defines regulator type
comments:
- 'Import: A is typeA, B is typeB (default B). Export: B for typeB, else A.'
from_schema: https://gridlabd.org/schema/glm/powerflow/regulator_configuration
exact_mappings:
- cim:VoltageRegulator.construction
rank: 1000
domain_of:
- regulator_configuration
range: string
required: false
tap_pos_A:
name: tap_pos_A
annotations:
order:
tag: order
value: 23
value_type:
tag: value_type
value: string
native_name:
tag: native_name
value: tap_pos_A
description: initial tap position of phase A
comments:
- 'Import: RatioTapChanger.step of phase A''s unit unless the regulator sets tap_A;
default 0. Export: step - neutralStep on phase A.'
from_schema: https://gridlabd.org/schema/glm/powerflow/regulator_configuration
close_mappings:
- cim:TapChanger.step
rank: 1000
domain_of:
- regulator_configuration
range: integer
required: false
tap_pos_B:
name: tap_pos_B
annotations:
order:
tag: order
value: 24
value_type:
tag: value_type
value: string
native_name:
tag: native_name
value: tap_pos_B
description: initial tap position of phase B
comments:
- 'Import: RatioTapChanger.step of phase B''s unit unless the regulator sets tap_B;
default 0. Export: step - neutralStep on phase B.'
from_schema: https://gridlabd.org/schema/glm/powerflow/regulator_configuration
close_mappings:
- cim:TapChanger.step
rank: 1000
domain_of:
- regulator_configuration
range: integer
required: false
tap_pos_C:
name: tap_pos_C
annotations:
order:
tag: order
value: 25
value_type:
tag: value_type
value: string
native_name:
tag: native_name
value: tap_pos_C
description: initial tap position of phase C
comments:
- 'Import: RatioTapChanger.step of phase C''s unit unless the regulator sets tap_C;
default 0. Export: step - neutralStep on phase C.'
from_schema: https://gridlabd.org/schema/glm/powerflow/regulator_configuration
close_mappings:
- cim:TapChanger.step
rank: 1000
domain_of:
- regulator_configuration
range: integer
required: false
Induced¶
name: regulator_configuration
description: 'Copyright (C) 2008 Battelle Memorial Institute
@file regulator_configuration.cpp
@addtogroup regulator_configuration
@ingroup regulator
@{
Inherits from: powerflow_library
Type: Configuration (physical asset template)
Note: Inherits from powerflow_library (not in powerflow module)'
comments:
- 'Import: no CIM template, so no class of its own; its values go on the VoltageRegulator,
RatioTapChanger and TapChangerControl of every regulator that names it. Export:
written from the VoltageRegulator''s tap changer and its control as <regulator>_config.'
from_schema: https://gridlabd.org/schema/glm
close_mappings:
- cim:RatioTapChanger
- cim:TapChangerControl
- cim:VoltageRegulator
is_a: glm_object
attributes:
connect_type:
name: connect_type
annotations:
order:
tag: order
value: 1
value_type:
tag: value_type
value: string
native_name:
tag: native_name
value: connect_type
description: Designation of connection style
comments:
- 'Import: WYE_WYE only (every AutoTransformerEnd wye, grounded); any other raises.
Export: always WYE_WYE.'
from_schema: https://gridlabd.org/schema/glm/powerflow/regulator_configuration
related_mappings:
- cim:TransformerEnd.grounded
rank: 1000
owner: regulator_configuration
domain_of:
- regulator_configuration
- transformer_configuration
range: ConnectType
required: false
band_center:
name: band_center
annotations:
order:
tag: order
value: 2
value_type:
tag: value_type
value: float
precision:
tag: precision
value: 6
native_name:
tag: native_name
value: band_center[V]
description: band center setting of regulator control
comments:
- 'Import: TapChangerControl.targetValue (V), primary volts; on LINE_DROP_COMP
x power_transducer_ratio. Export: the target (V), over ptRatio on LINE_DROP_COMP;
unset when the control is disabled.'
from_schema: https://gridlabd.org/schema/glm/powerflow/regulator_configuration
close_mappings:
- cim:RegulatingControl.targetValue
rank: 1000
owner: regulator_configuration
domain_of:
- regulator_configuration
range: float
required: false
unit:
ucum_code: V
band_width:
name: band_width
annotations:
order:
tag: order
value: 3
value_type:
tag: value_type
value: float
precision:
tag: precision
value: 6
native_name:
tag: native_name
value: band_width[V]
description: band width setting of regulator control
comments:
- 'Import: TapChangerControl.targetDeadband (V), the full band, as band_center.
Export: the deadband (V), likewise.'
from_schema: https://gridlabd.org/schema/glm/powerflow/regulator_configuration
close_mappings:
- cim:RegulatingControl.targetDeadband
rank: 1000
owner: regulator_configuration
domain_of:
- regulator_configuration
range: float
required: false
unit:
ucum_code: V
time_delay:
name: time_delay
annotations:
order:
tag: order
value: 4
value_type:
tag: value_type
value: float
precision:
tag: precision
value: 6
native_name:
tag: native_name
value: time_delay[s]
description: mechanical time delay between tap changes
comments:
- 'Import: RatioTapChanger.initialDelay and subsequentDelay (s) = dwell_time +
time_delay. Export: see dwell_time.'
from_schema: https://gridlabd.org/schema/glm/powerflow/regulator_configuration
close_mappings:
- cim:TapChanger.initialDelay
- cim:TapChanger.subsequentDelay
owner: regulator_configuration
domain_of:
- capacitor
- regulator_configuration
range: float
required: false
unit:
ucum_code: s
dwell_time:
name: dwell_time
annotations:
order:
tag: order
value: 5
value_type:
tag: value_type
value: float
precision:
tag: precision
value: 6
native_name:
tag: native_name
value: dwell_time[s]
description: time delay before a control action of regulator control
comments:
- 'Import: with time_delay. Export: the initialDelay (s).'
from_schema: https://gridlabd.org/schema/glm/powerflow/regulator_configuration
close_mappings:
- cim:TapChanger.initialDelay
- cim:TapChanger.subsequentDelay
owner: regulator_configuration
domain_of:
- capacitor
- regulator_configuration
range: float
required: false
unit:
ucum_code: s
raise_taps:
name: raise_taps
annotations:
order:
tag: order
value: 6
value_type:
tag: value_type
value: string
native_name:
tag: native_name
value: raise_taps
description: number of regulator raise taps, or the maximum raise voltage tap
position
comments:
- 'Import: RatioTapChanger.highStep, also the stepVoltageIncrement divisor; 0
raises. Export: highStep - neutralStep.'
from_schema: https://gridlabd.org/schema/glm/powerflow/regulator_configuration
exact_mappings:
- cim:TapChanger.highStep
rank: 1000
owner: regulator_configuration
domain_of:
- regulator_configuration
range: integer
required: false
lower_taps:
name: lower_taps
annotations:
order:
tag: order
value: 7
value_type:
tag: value_type
value: string
native_name:
tag: native_name
value: lower_taps
description: number of regulator lower taps, or the minimum lower voltage tap
position
comments:
- 'Import: RatioTapChanger.lowStep = -lower_taps; 0 raises. Export: neutralStep
- lowStep.'
from_schema: https://gridlabd.org/schema/glm/powerflow/regulator_configuration
close_mappings:
- cim:TapChanger.lowStep
rank: 1000
owner: regulator_configuration
domain_of:
- regulator_configuration
range: integer
required: false
current_transducer_ratio:
name: current_transducer_ratio
annotations:
order:
tag: order
value: 8
value_type:
tag: value_type
value: float
precision:
tag: precision
value: 6
native_name:
tag: native_name
value: current_transducer_ratio[pu]
description: primary rating of current transformer
comments:
- 'Import: RatioTapChanger.ctRatio, and the line drop''s CT ratio. Export: ctRatio.'
from_schema: https://gridlabd.org/schema/glm/powerflow/regulator_configuration
exact_mappings:
- cim:TapChanger.ctRatio
rank: 1000
owner: regulator_configuration
domain_of:
- regulator_configuration
range: float
required: false
unit:
ucum_code: pu
power_transducer_ratio:
name: power_transducer_ratio
annotations:
order:
tag: order
value: 9
value_type:
tag: value_type
value: float
precision:
tag: precision
value: 6
native_name:
tag: native_name
value: power_transducer_ratio[pu]
description: potential transformer rating
comments:
- 'Import: TapChangerControl.ptRatio and RatioTapChanger.ptRatio. Export: ptRatio.'
from_schema: https://gridlabd.org/schema/glm/powerflow/regulator_configuration
exact_mappings:
- cim:RegulatingControl.ptRatio
- cim:TapChanger.ptRatio
rank: 1000
owner: regulator_configuration
domain_of:
- regulator_configuration
range: float
required: false
unit:
ucum_code: pu
compensator_r_setting_A:
name: compensator_r_setting_A
annotations:
order:
tag: order
value: 10
value_type:
tag: value_type
value: float
precision:
tag: precision
value: 6
native_name:
tag: native_name
value: compensator_r_setting_A[V]
description: Line Drop Compensation R setting of regulator control (in volts)
on Phase A
comments:
- 'Import: TapChangerControl.lineDropR (ohm) = the setting x power_transducer_ratio
/ current_transducer_ratio; needs both ratios. Export: lineDropR x ctRatio /
ptRatio on phase A.'
from_schema: https://gridlabd.org/schema/glm/powerflow/regulator_configuration
close_mappings:
- cim:TapChangerControl.lineDropR
rank: 1000
owner: regulator_configuration
domain_of:
- regulator_configuration
range: float
required: false
unit:
ucum_code: V
compensator_r_setting_B:
name: compensator_r_setting_B
annotations:
order:
tag: order
value: 11
value_type:
tag: value_type
value: float
precision:
tag: precision
value: 6
native_name:
tag: native_name
value: compensator_r_setting_B[V]
description: Line Drop Compensation R setting of regulator control (in volts)
on Phase B
comments:
- 'Import: TapChangerControl.lineDropR (ohm) = the setting x power_transducer_ratio
/ current_transducer_ratio; needs both ratios. Export: lineDropR x ctRatio /
ptRatio on phase B.'
from_schema: https://gridlabd.org/schema/glm/powerflow/regulator_configuration
close_mappings:
- cim:TapChangerControl.lineDropR
rank: 1000
owner: regulator_configuration
domain_of:
- regulator_configuration
range: float
required: false
unit:
ucum_code: V
compensator_r_setting_C:
name: compensator_r_setting_C
annotations:
order:
tag: order
value: 12
value_type:
tag: value_type
value: float
precision:
tag: precision
value: 6
native_name:
tag: native_name
value: compensator_r_setting_C[V]
description: Line Drop Compensation R setting of regulator control (in volts)
on Phase C
comments:
- 'Import: TapChangerControl.lineDropR (ohm) = the setting x power_transducer_ratio
/ current_transducer_ratio; needs both ratios. Export: lineDropR x ctRatio /
ptRatio on phase C.'
from_schema: https://gridlabd.org/schema/glm/powerflow/regulator_configuration
close_mappings:
- cim:TapChangerControl.lineDropR
rank: 1000
owner: regulator_configuration
domain_of:
- regulator_configuration
range: float
required: false
unit:
ucum_code: V
compensator_x_setting_A:
name: compensator_x_setting_A
annotations:
order:
tag: order
value: 13
value_type:
tag: value_type
value: float
precision:
tag: precision
value: 6
native_name:
tag: native_name
value: compensator_x_setting_A[V]
description: Line Drop Compensation X setting of regulator control (in volts)
on Phase A
comments:
- 'Import: TapChangerControl.lineDropX (ohm), as the r setting. Export: lineDropX
x ctRatio / ptRatio on phase A.'
from_schema: https://gridlabd.org/schema/glm/powerflow/regulator_configuration
close_mappings:
- cim:TapChangerControl.lineDropX
rank: 1000
owner: regulator_configuration
domain_of:
- regulator_configuration
range: float
required: false
unit:
ucum_code: V
compensator_x_setting_B:
name: compensator_x_setting_B
annotations:
order:
tag: order
value: 14
value_type:
tag: value_type
value: float
precision:
tag: precision
value: 6
native_name:
tag: native_name
value: compensator_x_setting_B[V]
description: Line Drop Compensation X setting of regulator control (in volts)
on Phase B
comments:
- 'Import: TapChangerControl.lineDropX (ohm), as the r setting. Export: lineDropX
x ctRatio / ptRatio on phase B.'
from_schema: https://gridlabd.org/schema/glm/powerflow/regulator_configuration
close_mappings:
- cim:TapChangerControl.lineDropX
rank: 1000
owner: regulator_configuration
domain_of:
- regulator_configuration
range: float
required: false
unit:
ucum_code: V
compensator_x_setting_C:
name: compensator_x_setting_C
annotations:
order:
tag: order
value: 15
value_type:
tag: value_type
value: float
precision:
tag: precision
value: 6
native_name:
tag: native_name
value: compensator_x_setting_C[V]
description: Line Drop Compensation X setting of regulator control (in volts)
on Phase C
comments:
- 'Import: TapChangerControl.lineDropX (ohm), as the r setting. Export: lineDropX
x ctRatio / ptRatio on phase C.'
from_schema: https://gridlabd.org/schema/glm/powerflow/regulator_configuration
close_mappings:
- cim:TapChangerControl.lineDropX
rank: 1000
owner: regulator_configuration
domain_of:
- regulator_configuration
range: float
required: false
unit:
ucum_code: V
CT_phase:
name: CT_phase
annotations:
order:
tag: order
value: 16
value_type:
tag: value_type
value: string
native_name:
tag: native_name
value: CT_phase
description: phase(s) monitored by CT
comments:
- 'Import: BANK: the phase whose compensator setting is read, which must be PT_phase;
INDIVIDUAL: ignored. Export: BANK: the monitored phase, else its first.'
from_schema: https://gridlabd.org/schema/glm/powerflow/regulator_configuration
related_mappings:
- cim:RegulatingControl.monitoredPhase
rank: 1000
owner: regulator_configuration
domain_of:
- regulator_configuration
range: string
required: false
PT_phase:
name: PT_phase
annotations:
order:
tag: order
value: 17
value_type:
tag: value_type
value: string
native_name:
tag: native_name
value: PT_phase
description: phase(s) monitored by PT
comments:
- 'Import: BANK: TapChangerControl.monitoredPhase; INDIVIDUAL: ignored. Export:
BANK: the monitored phase, else its first.'
from_schema: https://gridlabd.org/schema/glm/powerflow/regulator_configuration
related_mappings:
- cim:RegulatingControl.monitoredPhase
rank: 1000
owner: regulator_configuration
domain_of:
- regulator_configuration
range: string
required: false
regulation:
name: regulation
annotations:
order:
tag: order
value: 18
value_type:
tag: value_type
value: float
precision:
tag: precision
value: 6
native_name:
tag: native_name
value: regulation
description: regulation of voltage regulator in %
comments:
- 'Import: stepVoltageIncrement (percent) = regulation / raise_taps; 0 raises
unless MANUAL. Export: stepVoltageIncrement x raise_taps (per unit).'
from_schema: https://gridlabd.org/schema/glm/powerflow/regulator_configuration
close_mappings:
- cim:RatioTapChanger.stepVoltageIncrement
rank: 1000
owner: regulator_configuration
domain_of:
- regulator_configuration
range: float
required: false
unit:
ucum_code: pu
control_level:
name: control_level
annotations:
order:
tag: order
value: 19
value_type:
tag: value_type
value: string
native_name:
tag: native_name
value: control_level
description: Designates whether control is on per-phase or banked level
comments:
- 'Import: INDIVIDUAL (default) is a unit per wired phase, BANK one gang unit.
Export: BANK for one VoltageRegulator alone, else INDIVIDUAL.'
from_schema: https://gridlabd.org/schema/glm/powerflow/regulator_configuration
owner: regulator_configuration
domain_of:
- capacitor
- regulator_configuration
range: string
required: false
Control:
name: Control
annotations:
order:
tag: order
value: 20
value_type:
tag: value_type
value: string
native_name:
tag: native_name
value: Control
description: Type of control used for regulating voltage
comments:
- 'Import: MANUAL (default) is enabled = controlEnabled = false; OUTPUT_VOLTAGE
and LINE_DROP_COMP true, lineDropCompensation on LINE_DROP_COMP only; REMOTE_NODE
on the regulator''s own output as OUTPUT_VOLTAGE. Export: MANUAL when the control
is disabled or absent, LINE_DROP_COMP with line drop compensation, else OUTPUT_VOLTAGE.'
from_schema: https://gridlabd.org/schema/glm/powerflow/regulator_configuration
close_mappings:
- cim:AutomationFunction.enabled
- cim:TapChangerControl.lineDropCompensation
- cim:TapChanger.controlEnabled
rank: 1000
owner: regulator_configuration
domain_of:
- regulator_configuration
range: string
required: false
reverse_flow_control:
name: reverse_flow_control
annotations:
order:
tag: order
value: 21
value_type:
tag: value_type
value: string
native_name:
tag: native_name
value: reverse_flow_control
description: Type of control used when power is flowing in reverse through the
regulator
from_schema: https://gridlabd.org/schema/glm/powerflow/regulator_configuration
rank: 1000
owner: regulator_configuration
domain_of:
- regulator_configuration
range: string
required: false
Type:
name: Type
annotations:
order:
tag: order
value: 22
value_type:
tag: value_type
value: string
native_name:
tag: native_name
value: Type
description: Defines regulator type
comments:
- 'Import: A is typeA, B is typeB (default B). Export: B for typeB, else A.'
from_schema: https://gridlabd.org/schema/glm/powerflow/regulator_configuration
exact_mappings:
- cim:VoltageRegulator.construction
rank: 1000
owner: regulator_configuration
domain_of:
- regulator_configuration
range: string
required: false
tap_pos_A:
name: tap_pos_A
annotations:
order:
tag: order
value: 23
value_type:
tag: value_type
value: string
native_name:
tag: native_name
value: tap_pos_A
description: initial tap position of phase A
comments:
- 'Import: RatioTapChanger.step of phase A''s unit unless the regulator sets tap_A;
default 0. Export: step - neutralStep on phase A.'
from_schema: https://gridlabd.org/schema/glm/powerflow/regulator_configuration
close_mappings:
- cim:TapChanger.step
rank: 1000
owner: regulator_configuration
domain_of:
- regulator_configuration
range: integer
required: false
tap_pos_B:
name: tap_pos_B
annotations:
order:
tag: order
value: 24
value_type:
tag: value_type
value: string
native_name:
tag: native_name
value: tap_pos_B
description: initial tap position of phase B
comments:
- 'Import: RatioTapChanger.step of phase B''s unit unless the regulator sets tap_B;
default 0. Export: step - neutralStep on phase B.'
from_schema: https://gridlabd.org/schema/glm/powerflow/regulator_configuration
close_mappings:
- cim:TapChanger.step
rank: 1000
owner: regulator_configuration
domain_of:
- regulator_configuration
range: integer
required: false
tap_pos_C:
name: tap_pos_C
annotations:
order:
tag: order
value: 25
value_type:
tag: value_type
value: string
native_name:
tag: native_name
value: tap_pos_C
description: initial tap position of phase C
comments:
- 'Import: RatioTapChanger.step of phase C''s unit unless the regulator sets tap_C;
default 0. Export: step - neutralStep on phase C.'
from_schema: https://gridlabd.org/schema/glm/powerflow/regulator_configuration
close_mappings:
- cim:TapChanger.step
rank: 1000
owner: regulator_configuration
domain_of:
- regulator_configuration
range: integer
required: false
name:
name: name
annotations:
order:
tag: order
value: 0
value_type:
tag: value_type
value: string
native_name:
tag: native_name
value: name
description: The object's name; unique across the model.
comments:
- 'Import: <CIM class>.name, copied as written; mRID = the class''s prefix + name
(none on a bus). Export: Names, sanitized for GridLAB-D; a name two objects
share raises.'
from_schema: https://gridlabd.org/schema/glm/types/common
exact_mappings:
- cim:IdentifiedObject.name
rank: 1000
identifier: true
owner: regulator_configuration
domain_of:
- glm_object
range: string
required: true
parent:
name: parent
annotations:
order:
tag: order
value: 0
value_type:
tag: value_type
value: string
native_name:
tag: native_name
value: parent
description: The parent object's name. A child node is solved as its parent's
bus; a nested object block sets it to the enclosing object.
comments:
- 'Import: a bus whose parent is a bus is its root bus''s ConnectivityNode, named
on the root''s row; no object of its own. On a link it is not mapped.'
from_schema: https://gridlabd.org/schema/glm/types/common
rank: 1000
owner: regulator_configuration
domain_of:
- glm_object
range: string
groupid:
name: groupid
annotations:
order:
tag: order
value: 0
value_type:
tag: value_type
value: string
native_name:
tag: native_name
value: groupid
description: Free-text group label.
from_schema: https://gridlabd.org/schema/glm/types/common
rank: 1000
owner: regulator_configuration
domain_of:
- glm_object
range: string
latitude:
name: latitude
annotations:
order:
tag: order
value: 0
value_type:
tag: value_type
value: string
native_name:
tag: native_name
value: latitude
description: Latitude, as written (decimal degrees or GridLAB-D's 37N26:12 form).
comments:
- Not converted. Home is the EquipmentLocation shape.
from_schema: https://gridlabd.org/schema/glm/types/common
rank: 1000
owner: regulator_configuration
domain_of:
- glm_object
range: string
longitude:
name: longitude
annotations:
order:
tag: order
value: 0
value_type:
tag: value_type
value: string
native_name:
tag: native_name
value: longitude
description: Longitude, as written.
comments:
- Not converted. Home is the EquipmentLocation shape.
from_schema: https://gridlabd.org/schema/glm/types/common
rank: 1000
owner: regulator_configuration
domain_of:
- glm_object
range: string
in_svc:
name: in_svc
annotations:
order:
tag: order
value: 0
value_type:
tag: value_type
value: string
native_name:
tag: native_name
value: in_svc
description: Timestamp the object enters service.
from_schema: https://gridlabd.org/schema/glm/types/common
rank: 1000
owner: regulator_configuration
domain_of:
- glm_object
range: string
out_svc:
name: out_svc
annotations:
order:
tag: order
value: 0
value_type:
tag: value_type
value: string
native_name:
tag: native_name
value: out_svc
description: Timestamp the object leaves service.
from_schema: https://gridlabd.org/schema/glm/types/common
rank: 1000
owner: regulator_configuration
domain_of:
- glm_object
range: string
rank:
name: rank
annotations:
order:
tag: order
value: 0
value_type:
tag: value_type
value: string
native_name:
tag: native_name
value: rank
description: Solver rank.
from_schema: https://gridlabd.org/schema/glm/types/common
rank: 1000
owner: regulator_configuration
domain_of:
- glm_object
range: string
flags:
name: flags
annotations:
order:
tag: order
value: 0
value_type:
tag: value_type
value: string
native_name:
tag: native_name
value: flags
description: Core object flags.
from_schema: https://gridlabd.org/schema/glm/types/common
rank: 1000
owner: regulator_configuration
domain_of:
- glm_object
range: string