Class: TransformerConfiguration

Copyright (C) 2008 Battelle Memorial Institute

@file transformer_configuration.cpp

@addtogroup transformer_configuration Transformer Configuration

@ingroup powerflow_transformer

The transformer configuration specifies a type of transformer. The

total rating of the transformer must be the sum of the individual

phase ratings of the transformer. The defaults are worked out as

follows:

- if the /e kVA_rating is omitted and some or all of the phase ratings

are provided, then the /e kVA_rating is the sum of the phase ratings.

- if the /e kVA_rating is provided and all of the phase ratings are

omitted, then the a 3 phase transformer is assumed and the phase

ratings are equal to 1/3 of the /e kVA_rating

For the forward/backsweep solver, the primary voltage must be greater

than the secondary voltage.

@{

__

Inherits from: powerflow_library

__

Type: Configuration (physical asset template)

__

Note: Inherits from powerflow_library (not in powerflow module)

URI: glm:TransformerConfiguration

 classDiagram
    class TransformerConfiguration
    click TransformerConfiguration href "../TransformerConfiguration/"
      GlmObject <|-- TransformerConfiguration
        click GlmObject href "../GlmObject/"

      TransformerConfiguration : connect_type

      TransformerConfiguration : coolant_type

      TransformerConfiguration : cooling_type

      TransformerConfiguration : core_coil_weight

      TransformerConfiguration : flags

      TransformerConfiguration : full_load_loss

      TransformerConfiguration : groupid

      TransformerConfiguration : I_M

      TransformerConfiguration : impedance





        TransformerConfiguration --> "0..1" Complex : impedance
        click Complex href "../Complex/"



      TransformerConfiguration : impedance1





        TransformerConfiguration --> "0..1" Complex : impedance1
        click Complex href "../Complex/"



      TransformerConfiguration : impedance2





        TransformerConfiguration --> "0..1" Complex : impedance2
        click Complex href "../Complex/"



      TransformerConfiguration : in_svc

      TransformerConfiguration : inrush_saturation_enabled

      TransformerConfiguration : install_type

      TransformerConfiguration : installed_insulation_life

      TransformerConfiguration : L_A

      TransformerConfiguration : latitude

      TransformerConfiguration : longitude

      TransformerConfiguration : magnetization_location

      TransformerConfiguration : name

      TransformerConfiguration : no_load_loss

      TransformerConfiguration : oil_volume

      TransformerConfiguration : out_svc

      TransformerConfiguration : parent

      TransformerConfiguration : phi_K

      TransformerConfiguration : phi_M

      TransformerConfiguration : power_rating

      TransformerConfiguration : powerA_rating

      TransformerConfiguration : powerB_rating

      TransformerConfiguration : powerC_rating

      TransformerConfiguration : primary_voltage

      TransformerConfiguration : rank

      TransformerConfiguration : rated_top_oil_rise

      TransformerConfiguration : rated_winding_hot_spot_rise

      TransformerConfiguration : rated_winding_time_constant

      TransformerConfiguration : reactance

      TransformerConfiguration : reactance1

      TransformerConfiguration : reactance2

      TransformerConfiguration : reactance_resistance_ratio

      TransformerConfiguration : resistance

      TransformerConfiguration : resistance1

      TransformerConfiguration : resistance2

      TransformerConfiguration : secondary_voltage

      TransformerConfiguration : shunt_impedance





        TransformerConfiguration --> "0..1" Complex : shunt_impedance
        click Complex href "../Complex/"



      TransformerConfiguration : shunt_reactance

      TransformerConfiguration : shunt_resistance

      TransformerConfiguration : T_D

      TransformerConfiguration : tank_fittings_weight

Inheritance

Slots

Name Cardinality and Range Description Inheritance
connect_type 0..1
String
connect type enum: Wye-Wye, single-phase, etc direct
install_type 0..1
String
Defines location of the transformer installation direct
coolant_type 0..1
String
coolant type, used in life time model direct
cooling_type 0..1
String
type of coolant fluid used in life time model direct
primary_voltage 0..1
Float
primary voltage level in L-L value kV direct
secondary_voltage 0..1
Float
secondary voltage level kV direct
power_rating 0..1
Float
kVA rating of transformer, total direct
powerA_rating 0..1
Float
kVA rating of transformer, phase A direct
powerB_rating 0..1
Float
kVA rating of transformer, phase B direct
powerC_rating 0..1
Float
kVA rating of transformer, phase C direct
resistance 0..1
Float
Series impedance, pu, real direct
reactance 0..1
Float
Series impedance, pu, imag direct
impedance 0..1
Complex
Series impedance, pu direct
resistance1 0..1
Float
Secondary series impedance (only used when you want to define each individual... direct
reactance1 0..1
Float
Secondary series impedance (only used when you want to define each individual... direct
impedance1 0..1
Complex
Secondary series impedance (only used when you want to define each individual... direct
resistance2 0..1
Float
Secondary series impedance (only used when you want to define each individual... direct
reactance2 0..1
Float
Secondary series impedance (only used when you want to define each individual... direct
impedance2 0..1
Complex
Secondary series impedance (only used when you want to define each individual... direct
shunt_resistance 0..1
Float
Shunt impedance on primary side, pu, real direct
shunt_reactance 0..1
Float
Shunt impedance on primary side, pu, imag direct
shunt_impedance 0..1
Complex
Shunt impedance on primary side, pu direct
core_coil_weight 0..1
Float
The weight of the core and coil assembly in pounds direct
tank_fittings_weight 0..1
Float
The weight of the tank and fittings in pounds direct
oil_volume 0..1
Float
The number of gallons of oil in the transformer direct
rated_winding_time_constant 0..1
Float
The rated winding time constant in hours direct
rated_winding_hot_spot_rise 0..1
Float
winding hottest-spot rise over ambient temperature at rated load, degrees C direct
rated_top_oil_rise 0..1
Float
top-oil hottest-spot rise over ambient temperature at rated load, degrees C direct
no_load_loss 0..1
Float
Another method of specifying transformer impedances, defined as per unit powe... direct
full_load_loss 0..1
Float
Another method of specifying transformer impedances, defined as per unit powe... direct
reactance_resistance_ratio 0..1
Float
the reactance to resistance ratio (X/R) direct
installed_insulation_life 0..1
Float
the normal lifetime of the transformer insulation at rated load, hours direct
magnetization_location 0..1
String
winding to place magnetization influence for in-rush calculations direct
inrush_saturation_enabled 0..1
Boolean
flag to include saturation effects during inrush calculations direct
L_A 0..1
Float
Air core inductance of transformer direct
phi_K 0..1
Float
Knee flux value where the air core inductance interstes the flux axis of the ... direct
phi_M 0..1
Float
Peak magnetization flux at rated voltage of the saturation curve direct
I_M 0..1
Float
Peak magnetization current at rated voltage of the saturation curve direct
T_D 0..1
Float
Inrush decay time constant for inrush current direct
name 1
String
The object's name; unique across the model GlmObject
parent 0..1
String
The parent object's name GlmObject
groupid 0..1
String
Free-text group label GlmObject
latitude 0..1
String
Latitude, as written (decimal degrees or GridLAB-D's 37N26:12 form) GlmObject
longitude 0..1
String
Longitude, as written GlmObject
in_svc 0..1
String
Timestamp the object enters service GlmObject
out_svc 0..1
String
Timestamp the object leaves service GlmObject
rank 0..1
String
Solver rank GlmObject
flags 0..1
String
Core object flags GlmObject

Comments

  • Import: TransformerTankConfiguration, mRID xc_ + name (transformer_configuration.cimtbl); a bank of lugged cans is a TransformerBankConfiguration, mRID xb_ + name, with a tank per can. Export: the TransformerTankConfiguration of each unit, written as one configuration; a bank's cans become one.

Identifier and Mapping Information

Schema Source

  • from schema: https://gridlabd.org/schema/glm

Mappings

Mapping Type Mapped Value
self glm:TransformerConfiguration
native glm:TransformerConfiguration
exact cim:TransformerTankConfiguration
close cim:TransformerBankConfiguration

LinkML Source

Direct

name: transformer_configuration
description: 'Copyright (C) 2008 Battelle Memorial Institute

  @file transformer_configuration.cpp

  @addtogroup transformer_configuration Transformer Configuration

  @ingroup powerflow_transformer

  The transformer configuration specifies a type of transformer.  The

  total rating of the transformer must be the sum of the individual

  phase ratings of the transformer.  The defaults are worked out as

  follows:

  - if the /e kVA_rating is omitted and some or all of the phase ratings

  are provided, then the /e kVA_rating is the sum of the phase ratings.

  - if the /e kVA_rating is provided and all of the phase ratings are

  omitted, then the a 3 phase transformer is assumed and the phase

  ratings are equal to 1/3 of the /e kVA_rating

  For the forward/backsweep solver, the primary voltage must be greater

  than the secondary voltage.

  @{


  Inherits from: powerflow_library


  Type: Configuration (physical asset template)


  Note: Inherits from powerflow_library (not in powerflow module)'
comments:
- 'Import: TransformerTankConfiguration, mRID xc_ + name (transformer_configuration.cimtbl);
  a bank of lugged cans is a TransformerBankConfiguration, mRID xb_ + name, with a
  tank per can. Export: the TransformerTankConfiguration of each unit, written as
  one configuration; a bank''s cans become one.'
from_schema: https://gridlabd.org/schema/glm
exact_mappings:
- cim:TransformerTankConfiguration
close_mappings:
- cim:TransformerBankConfiguration
is_a: glm_object
attributes:
  connect_type:
    name: connect_type
    annotations:
      order:
        tag: order
        value: 1
      value_type:
        tag: value_type
        value: string
      native_name:
        tag: native_name
        value: connect_type
    description: 'connect type enum: Wye-Wye, single-phase, etc.'
    comments:
    - 'Import: sets the form and each end''s connectionKind (WYE_WYE and SINGLE_PHASE
      Y/Y, DELTA_GWYE D/Y, DELTA_DELTA D/D, SINGLE_PHASE_CENTER_TAPPED lugs); unset
      raises. Export: chosen from the connectionKinds and phases (WYE_WYE, SINGLE_PHASE,
      DELTA_DELTA, DELTA_GWYE, SINGLE_PHASE_CENTER_TAPPED).'
    from_schema: https://gridlabd.org/schema/glm/powerflow/transformer_configuration
    close_mappings:
    - cim:TransformerTankEnd.connectionKind
    domain_of:
    - regulator_configuration
    - transformer_configuration
    range: string
    required: false
  install_type:
    name: install_type
    annotations:
      order:
        tag: order
        value: 2
      value_type:
        tag: value_type
        value: string
      native_name:
        tag: native_name
        value: install_type
    description: Defines location of the transformer installation
    from_schema: https://gridlabd.org/schema/glm/powerflow/transformer_configuration
    rank: 1000
    domain_of:
    - transformer_configuration
    range: string
    required: false
  coolant_type:
    name: coolant_type
    annotations:
      order:
        tag: order
        value: 3
      value_type:
        tag: value_type
        value: string
      native_name:
        tag: native_name
        value: coolant_type
    description: coolant type, used in life time model
    from_schema: https://gridlabd.org/schema/glm/powerflow/transformer_configuration
    rank: 1000
    domain_of:
    - transformer_configuration
    range: string
    required: false
  cooling_type:
    name: cooling_type
    annotations:
      order:
        tag: order
        value: 4
      value_type:
        tag: value_type
        value: string
      native_name:
        tag: native_name
        value: cooling_type
    description: type of coolant fluid used in life time model
    from_schema: https://gridlabd.org/schema/glm/powerflow/transformer_configuration
    rank: 1000
    domain_of:
    - transformer_configuration
    range: string
    required: false
  primary_voltage:
    name: primary_voltage
    annotations:
      order:
        tag: order
        value: 5
      value_type:
        tag: value_type
        value: float
      precision:
        tag: precision
        value: 6
      native_name:
        tag: native_name
        value: primary_voltage[V]
    description: primary voltage level in L-L value kV
    comments:
    - 'Import: TransformerWinding.ratedU (V) line to line and baseU (V) the coil,
      from winding 1. Export: winding 1 ratedU, a coil''s baseU; an LTC''s actual
      ratio folded in.'
    from_schema: https://gridlabd.org/schema/glm/powerflow/transformer_configuration
    close_mappings:
    - cim:TransformerWinding.ratedU
    - cim:TransformerWinding.baseU
    rank: 1000
    domain_of:
    - transformer_configuration
    range: float
    required: false
    unit:
      ucum_code: V
  secondary_voltage:
    name: secondary_voltage
    annotations:
      order:
        tag: order
        value: 6
      value_type:
        tag: value_type
        value: float
      precision:
        tag: precision
        value: 6
      native_name:
        tag: native_name
        value: secondary_voltage[V]
    description: secondary voltage level kV
    comments:
    - 'Import: TransformerWinding.ratedU and baseU (V) of winding 2; a center tap''s
      half is ratedU x 2. Export: winding 2''s, likewise.'
    from_schema: https://gridlabd.org/schema/glm/powerflow/transformer_configuration
    close_mappings:
    - cim:TransformerWinding.ratedU
    - cim:TransformerWinding.baseU
    rank: 1000
    domain_of:
    - transformer_configuration
    range: float
    required: false
    unit:
      ucum_code: V
  power_rating:
    name: power_rating
    annotations:
      order:
        tag: order
        value: 7
      value_type:
        tag: value_type
        value: float
      precision:
        tag: precision
        value: 6
      native_name:
        tag: native_name
        value: power_rating[kVA]
    description: kVA rating of transformer, total
    comments:
    - 'Import: TransformerWinding.ratedS (kVA) of the whole unit, else the phase sum;
      baseS the tank''s share. Export: winding 1 ratedS (kVA).'
    from_schema: https://gridlabd.org/schema/glm/powerflow/transformer_configuration
    close_mappings:
    - cim:TransformerWinding.ratedS
    - cim:TransformerWinding.baseS
    rank: 1000
    domain_of:
    - transformer_configuration
    range: float
    required: false
    unit:
      ucum_code: kVA
  powerA_rating:
    name: powerA_rating
    annotations:
      order:
        tag: order
        value: 8
      value_type:
        tag: value_type
        value: float
      precision:
        tag: precision
        value: 6
      native_name:
        tag: native_name
        value: powerA_rating[kVA]
    description: kVA rating of transformer, phase A
    comments:
    - 'Import: a can''s TransformerWinding.ratedS (kVA) when the phases are rated
      unequally; a center tap''s on its phase. Export: a coil''s or center tap''s
      kVA on phase A.'
    from_schema: https://gridlabd.org/schema/glm/powerflow/transformer_configuration
    close_mappings:
    - cim:TransformerWinding.ratedS
    rank: 1000
    domain_of:
    - transformer_configuration
    range: float
    required: false
    unit:
      ucum_code: kVA
  powerB_rating:
    name: powerB_rating
    annotations:
      order:
        tag: order
        value: 9
      value_type:
        tag: value_type
        value: float
      precision:
        tag: precision
        value: 6
      native_name:
        tag: native_name
        value: powerB_rating[kVA]
    description: kVA rating of transformer, phase B
    comments:
    - 'Import: a can''s TransformerWinding.ratedS (kVA) when the phases are rated
      unequally; a center tap''s on its phase. Export: a coil''s or center tap''s
      kVA on phase B.'
    from_schema: https://gridlabd.org/schema/glm/powerflow/transformer_configuration
    close_mappings:
    - cim:TransformerWinding.ratedS
    rank: 1000
    domain_of:
    - transformer_configuration
    range: float
    required: false
    unit:
      ucum_code: kVA
  powerC_rating:
    name: powerC_rating
    annotations:
      order:
        tag: order
        value: 10
      value_type:
        tag: value_type
        value: float
      precision:
        tag: precision
        value: 6
      native_name:
        tag: native_name
        value: powerC_rating[kVA]
    description: kVA rating of transformer, phase C
    comments:
    - 'Import: a can''s TransformerWinding.ratedS (kVA) when the phases are rated
      unequally; a center tap''s on its phase. Export: a coil''s or center tap''s
      kVA on phase C.'
    from_schema: https://gridlabd.org/schema/glm/powerflow/transformer_configuration
    close_mappings:
    - cim:TransformerWinding.ratedS
    rank: 1000
    domain_of:
    - transformer_configuration
    range: float
    required: false
    unit:
      ucum_code: kVA
  resistance:
    name: resistance
    annotations:
      order:
        tag: order
        value: 11
      value_type:
        tag: value_type
        value: float
      precision:
        tag: precision
        value: 6
      native_name:
        tag: native_name
        value: resistance[pu]
    description: Series impedance, pu, real
    comments:
    - 'Import: percentImpedance (percent) = |R + jX| x k x 100 and loadLoss (kW) =
      R x k x S, k moving GridLAB-D''s base to the tank''s. Export: the (1, 2) R in
      pu on winding 1 ratedS; not positive is written 1e-6.'
    from_schema: https://gridlabd.org/schema/glm/powerflow/transformer_configuration
    close_mappings:
    - cim:TransformerTankConfiguration.percentImpedance
    - cim:TransformerTankConfiguration.loadLoss
    domain_of:
    - overhead_line_conductor
    - transformer_configuration
    - triplex_line_conductor
    range: float
    required: false
    unit:
      ucum_code: pu
  reactance:
    name: reactance
    annotations:
      order:
        tag: order
        value: 12
      value_type:
        tag: value_type
        value: float
      precision:
        tag: precision
        value: 6
      native_name:
        tag: native_name
        value: reactance[pu]
    description: Series impedance, pu, imag
    comments:
    - 'Import: with resistance, percentImpedance (percent). Export: the (1, 2) X in
      pu; not positive is written 1e-6.'
    from_schema: https://gridlabd.org/schema/glm/powerflow/transformer_configuration
    close_mappings:
    - cim:TransformerTankConfiguration.percentImpedance
    rank: 1000
    domain_of:
    - transformer_configuration
    range: float
    required: false
    unit:
      ucum_code: pu
  impedance:
    name: impedance
    annotations:
      order:
        tag: order
        value: 13
      value_type:
        tag: value_type
        value: complex
      native_name:
        tag: native_name
        value: impedance[pu]
    description: Series impedance, pu
    comments:
    - 'Import: R + jX as resistance and reactance; a center tap''s is the full winding''s.
      Export: the (1, 2) R + jX in pu; a center tap''s or star leg''s star branch.'
    from_schema: https://gridlabd.org/schema/glm/powerflow/transformer_configuration
    close_mappings:
    - cim:TransformerTankConfiguration.percentImpedance
    - cim:TransformerTankConfiguration.loadLoss
    rank: 1000
    domain_of:
    - transformer_configuration
    range: Complex
    required: false
    unit:
      ucum_code: pu
  resistance1:
    name: resistance1
    annotations:
      order:
        tag: order
        value: 14
      value_type:
        tag: value_type
        value: float
      precision:
        tag: precision
        value: 6
      native_name:
        tag: native_name
        value: resistance1[pu]
    description: Secondary series impedance (only used when you want to define each
      individual winding seperately, pu, real
    from_schema: https://gridlabd.org/schema/glm/powerflow/transformer_configuration
    rank: 1000
    domain_of:
    - transformer_configuration
    range: float
    required: false
    unit:
      ucum_code: pu
  reactance1:
    name: reactance1
    annotations:
      order:
        tag: order
        value: 15
      value_type:
        tag: value_type
        value: float
      precision:
        tag: precision
        value: 6
      native_name:
        tag: native_name
        value: reactance1[pu]
    description: Secondary series impedance (only used when you want to define each
      individual winding seperately, pu, imag
    from_schema: https://gridlabd.org/schema/glm/powerflow/transformer_configuration
    rank: 1000
    domain_of:
    - transformer_configuration
    range: float
    required: false
    unit:
      ucum_code: pu
  impedance1:
    name: impedance1
    annotations:
      order:
        tag: order
        value: 16
      value_type:
        tag: value_type
        value: complex
      native_name:
        tag: native_name
        value: impedance1[pu]
    description: Secondary series impedance (only used when you want to define each
      individual winding seperately, pu
    comments:
    - 'Import: a center tap''s half, checked against GridLAB-D''s split of one R +
      jX; any other split raises. Export: a center tap''s s1 half of the star.'
    from_schema: https://gridlabd.org/schema/glm/powerflow/transformer_configuration
    close_mappings:
    - cim:TransformerTankConfiguration.percentImpedance
    rank: 1000
    domain_of:
    - transformer_configuration
    range: Complex
    required: false
    unit:
      ucum_code: pu
  resistance2:
    name: resistance2
    annotations:
      order:
        tag: order
        value: 17
      value_type:
        tag: value_type
        value: float
      precision:
        tag: precision
        value: 6
      native_name:
        tag: native_name
        value: resistance2[pu]
    description: Secondary series impedance (only used when you want to define each
      individual winding seperately, pu, real
    from_schema: https://gridlabd.org/schema/glm/powerflow/transformer_configuration
    rank: 1000
    domain_of:
    - transformer_configuration
    range: float
    required: false
    unit:
      ucum_code: pu
  reactance2:
    name: reactance2
    annotations:
      order:
        tag: order
        value: 18
      value_type:
        tag: value_type
        value: float
      precision:
        tag: precision
        value: 6
      native_name:
        tag: native_name
        value: reactance2[pu]
    description: Secondary series impedance (only used when you want to define each
      individual winding seperately, pu, imag
    from_schema: https://gridlabd.org/schema/glm/powerflow/transformer_configuration
    rank: 1000
    domain_of:
    - transformer_configuration
    range: float
    required: false
    unit:
      ucum_code: pu
  impedance2:
    name: impedance2
    annotations:
      order:
        tag: order
        value: 19
      value_type:
        tag: value_type
        value: complex
      native_name:
        tag: native_name
        value: impedance2[pu]
    description: Secondary series impedance (only used when you want to define each
      individual winding seperately, pu
    comments:
    - 'Import: as impedance1, the s2 half. Export: a center tap''s s2 half of the
      star.'
    from_schema: https://gridlabd.org/schema/glm/powerflow/transformer_configuration
    close_mappings:
    - cim:TransformerTankConfiguration.percentImpedance
    rank: 1000
    domain_of:
    - transformer_configuration
    range: Complex
    required: false
    unit:
      ucum_code: pu
  shunt_resistance:
    name: shunt_resistance
    annotations:
      order:
        tag: order
        value: 20
      value_type:
        tag: value_type
        value: float
      precision:
        tag: precision
        value: 6
      native_name:
        tag: native_name
        value: shunt_resistance[pu]
    description: Shunt impedance on primary side, pu, real
    comments:
    - 'Import: noLoadLoss (kW) = S / (Rsh x k); unset is lossless and not filled.
      Export: 1 / the core g in pu; unset when there is no core.'
    from_schema: https://gridlabd.org/schema/glm/powerflow/transformer_configuration
    close_mappings:
    - cim:TransformerTankConfiguration.noLoadLoss
    rank: 1000
    domain_of:
    - transformer_configuration
    range: float
    required: false
    unit:
      ucum_code: pu
  shunt_reactance:
    name: shunt_reactance
    annotations:
      order:
        tag: order
        value: 21
      value_type:
        tag: value_type
        value: float
      precision:
        tag: precision
        value: 6
      native_name:
        tag: native_name
        value: shunt_reactance[pu]
    description: Shunt impedance on primary side, pu, imag
    comments:
    - 'Import: percentMagnetizingCurrent (percent) = 100 / (Xsh x k). Export: 1 /
      the core b in pu.'
    from_schema: https://gridlabd.org/schema/glm/powerflow/transformer_configuration
    close_mappings:
    - cim:TransformerTankConfiguration.percentMagnetizingCurrent
    rank: 1000
    domain_of:
    - transformer_configuration
    range: float
    required: false
    unit:
      ucum_code: pu
  shunt_impedance:
    name: shunt_impedance
    annotations:
      order:
        tag: order
        value: 22
      value_type:
        tag: value_type
        value: complex
      native_name:
        tag: native_name
        value: shunt_impedance[pu]
    description: Shunt impedance on primary side, pu
    comments:
    - 'Import: Rsh + jXsh as shunt_resistance and shunt_reactance; on a delta connection
      raises.'
    from_schema: https://gridlabd.org/schema/glm/powerflow/transformer_configuration
    close_mappings:
    - cim:TransformerTankConfiguration.noLoadLoss
    - cim:TransformerTankConfiguration.percentMagnetizingCurrent
    rank: 1000
    domain_of:
    - transformer_configuration
    range: Complex
    required: false
    unit:
      ucum_code: pu
  core_coil_weight:
    name: core_coil_weight
    annotations:
      order:
        tag: order
        value: 23
      value_type:
        tag: value_type
        value: float
      precision:
        tag: precision
        value: 6
      native_name:
        tag: native_name
        value: core_coil_weight[lb]
    description: The weight of the core and coil assembly in pounds
    from_schema: https://gridlabd.org/schema/glm/powerflow/transformer_configuration
    rank: 1000
    domain_of:
    - transformer_configuration
    range: float
    required: false
    unit:
      ucum_code: lb
  tank_fittings_weight:
    name: tank_fittings_weight
    annotations:
      order:
        tag: order
        value: 24
      value_type:
        tag: value_type
        value: float
      precision:
        tag: precision
        value: 6
      native_name:
        tag: native_name
        value: tank_fittings_weight[lb]
    description: The weight of the tank and fittings in pounds
    from_schema: https://gridlabd.org/schema/glm/powerflow/transformer_configuration
    rank: 1000
    domain_of:
    - transformer_configuration
    range: float
    required: false
    unit:
      ucum_code: lb
  oil_volume:
    name: oil_volume
    annotations:
      order:
        tag: order
        value: 25
      value_type:
        tag: value_type
        value: float
      precision:
        tag: precision
        value: 6
      native_name:
        tag: native_name
        value: oil_volume[gal]
    description: The number of gallons of oil in the transformer
    from_schema: https://gridlabd.org/schema/glm/powerflow/transformer_configuration
    rank: 1000
    domain_of:
    - transformer_configuration
    range: float
    required: false
    unit:
      ucum_code: gal
  rated_winding_time_constant:
    name: rated_winding_time_constant
    annotations:
      order:
        tag: order
        value: 26
      value_type:
        tag: value_type
        value: float
      precision:
        tag: precision
        value: 6
      native_name:
        tag: native_name
        value: rated_winding_time_constant[h]
    description: The rated winding time constant in hours
    from_schema: https://gridlabd.org/schema/glm/powerflow/transformer_configuration
    rank: 1000
    domain_of:
    - transformer_configuration
    range: float
    required: false
    unit:
      ucum_code: h
  rated_winding_hot_spot_rise:
    name: rated_winding_hot_spot_rise
    annotations:
      order:
        tag: order
        value: 27
      value_type:
        tag: value_type
        value: float
      precision:
        tag: precision
        value: 6
      native_name:
        tag: native_name
        value: rated_winding_hot_spot_rise[degC]
    description: winding hottest-spot rise over ambient temperature at rated load,
      degrees C
    from_schema: https://gridlabd.org/schema/glm/powerflow/transformer_configuration
    rank: 1000
    domain_of:
    - transformer_configuration
    range: float
    required: false
    unit:
      ucum_code: degC
  rated_top_oil_rise:
    name: rated_top_oil_rise
    annotations:
      order:
        tag: order
        value: 28
      value_type:
        tag: value_type
        value: float
      precision:
        tag: precision
        value: 6
      native_name:
        tag: native_name
        value: rated_top_oil_rise[degC]
    description: top-oil hottest-spot rise over ambient temperature at rated load,
      degrees C
    from_schema: https://gridlabd.org/schema/glm/powerflow/transformer_configuration
    rank: 1000
    domain_of:
    - transformer_configuration
    range: float
    required: false
    unit:
      ucum_code: degC
  no_load_loss:
    name: no_load_loss
    annotations:
      order:
        tag: order
        value: 29
      value_type:
        tag: value_type
        value: float
      precision:
        tag: precision
        value: 6
      native_name:
        tag: native_name
        value: no_load_loss[pu]
    description: Another method of specifying transformer impedances, defined as per
      unit power values (shunt)
    comments:
    - 'Import: raises when set (it replaces the impedances on a center tap and no
      deck sets it). Export: not written.'
    from_schema: https://gridlabd.org/schema/glm/powerflow/transformer_configuration
    rank: 1000
    domain_of:
    - transformer_configuration
    range: float
    required: false
    unit:
      ucum_code: pu
  full_load_loss:
    name: full_load_loss
    annotations:
      order:
        tag: order
        value: 30
      value_type:
        tag: value_type
        value: float
      precision:
        tag: precision
        value: 6
      native_name:
        tag: native_name
        value: full_load_loss[pu]
    description: Another method of specifying transformer impedances, defined as per
      unit power values (shunt and series)
    comments:
    - 'Import: raises when set, as no_load_loss. Export: not written.'
    from_schema: https://gridlabd.org/schema/glm/powerflow/transformer_configuration
    rank: 1000
    domain_of:
    - transformer_configuration
    range: float
    required: false
    unit:
      ucum_code: pu
  reactance_resistance_ratio:
    name: reactance_resistance_ratio
    annotations:
      order:
        tag: order
        value: 31
      value_type:
        tag: value_type
        value: float
      precision:
        tag: precision
        value: 6
      native_name:
        tag: native_name
        value: reactance_resistance_ratio
    description: the reactance to resistance ratio (X/R)
    from_schema: https://gridlabd.org/schema/glm/powerflow/transformer_configuration
    rank: 1000
    domain_of:
    - transformer_configuration
    range: float
    required: false
  installed_insulation_life:
    name: installed_insulation_life
    annotations:
      order:
        tag: order
        value: 32
      value_type:
        tag: value_type
        value: float
      precision:
        tag: precision
        value: 6
      native_name:
        tag: native_name
        value: installed_insulation_life[h]
    description: the normal lifetime of the transformer insulation at rated load,
      hours
    from_schema: https://gridlabd.org/schema/glm/powerflow/transformer_configuration
    rank: 1000
    domain_of:
    - transformer_configuration
    range: float
    required: false
    unit:
      ucum_code: h
  magnetization_location:
    name: magnetization_location
    annotations:
      order:
        tag: order
        value: 33
      value_type:
        tag: value_type
        value: string
      native_name:
        tag: native_name
        value: magnetization_location
    description: winding to place magnetization influence for in-rush calculations
    from_schema: https://gridlabd.org/schema/glm/powerflow/transformer_configuration
    rank: 1000
    domain_of:
    - transformer_configuration
    range: string
    required: false
  inrush_saturation_enabled:
    name: inrush_saturation_enabled
    annotations:
      order:
        tag: order
        value: 34
      value_type:
        tag: value_type
        value: bool
      native_name:
        tag: native_name
        value: inrush_saturation_enabled
    description: flag to include saturation effects during inrush calculations
    from_schema: https://gridlabd.org/schema/glm/powerflow/transformer_configuration
    rank: 1000
    domain_of:
    - transformer_configuration
    range: boolean
    required: false
  L_A:
    name: L_A
    annotations:
      order:
        tag: order
        value: 35
      value_type:
        tag: value_type
        value: float
      precision:
        tag: precision
        value: 6
      native_name:
        tag: native_name
        value: L_A[pu]
    description: Air core inductance of transformer
    from_schema: https://gridlabd.org/schema/glm/powerflow/transformer_configuration
    rank: 1000
    domain_of:
    - transformer_configuration
    range: float
    required: false
    unit:
      ucum_code: pu
  phi_K:
    name: phi_K
    annotations:
      order:
        tag: order
        value: 36
      value_type:
        tag: value_type
        value: float
      precision:
        tag: precision
        value: 6
      native_name:
        tag: native_name
        value: phi_K[pu]
    description: Knee flux value where the air core inductance interstes the flux
      axis of the saturation curve
    from_schema: https://gridlabd.org/schema/glm/powerflow/transformer_configuration
    rank: 1000
    domain_of:
    - transformer_configuration
    range: float
    required: false
    unit:
      ucum_code: pu
  phi_M:
    name: phi_M
    annotations:
      order:
        tag: order
        value: 37
      value_type:
        tag: value_type
        value: float
      precision:
        tag: precision
        value: 6
      native_name:
        tag: native_name
        value: phi_M[pu]
    description: Peak magnetization flux at rated voltage of the saturation curve
    from_schema: https://gridlabd.org/schema/glm/powerflow/transformer_configuration
    rank: 1000
    domain_of:
    - transformer_configuration
    range: float
    required: false
    unit:
      ucum_code: pu
  I_M:
    name: I_M
    annotations:
      order:
        tag: order
        value: 38
      value_type:
        tag: value_type
        value: float
      precision:
        tag: precision
        value: 6
      native_name:
        tag: native_name
        value: I_M[pu]
    description: Peak magnetization current at rated voltage of the saturation curve
    from_schema: https://gridlabd.org/schema/glm/powerflow/transformer_configuration
    rank: 1000
    domain_of:
    - transformer_configuration
    range: float
    required: false
    unit:
      ucum_code: pu
  T_D:
    name: T_D
    annotations:
      order:
        tag: order
        value: 39
      value_type:
        tag: value_type
        value: float
      precision:
        tag: precision
        value: 6
      native_name:
        tag: native_name
        value: T_D
    description: Inrush decay time constant for inrush current
    from_schema: https://gridlabd.org/schema/glm/powerflow/transformer_configuration
    rank: 1000
    domain_of:
    - transformer_configuration
    range: float
    required: false

Induced

name: transformer_configuration
description: 'Copyright (C) 2008 Battelle Memorial Institute

  @file transformer_configuration.cpp

  @addtogroup transformer_configuration Transformer Configuration

  @ingroup powerflow_transformer

  The transformer configuration specifies a type of transformer.  The

  total rating of the transformer must be the sum of the individual

  phase ratings of the transformer.  The defaults are worked out as

  follows:

  - if the /e kVA_rating is omitted and some or all of the phase ratings

  are provided, then the /e kVA_rating is the sum of the phase ratings.

  - if the /e kVA_rating is provided and all of the phase ratings are

  omitted, then the a 3 phase transformer is assumed and the phase

  ratings are equal to 1/3 of the /e kVA_rating

  For the forward/backsweep solver, the primary voltage must be greater

  than the secondary voltage.

  @{


  Inherits from: powerflow_library


  Type: Configuration (physical asset template)


  Note: Inherits from powerflow_library (not in powerflow module)'
comments:
- 'Import: TransformerTankConfiguration, mRID xc_ + name (transformer_configuration.cimtbl);
  a bank of lugged cans is a TransformerBankConfiguration, mRID xb_ + name, with a
  tank per can. Export: the TransformerTankConfiguration of each unit, written as
  one configuration; a bank''s cans become one.'
from_schema: https://gridlabd.org/schema/glm
exact_mappings:
- cim:TransformerTankConfiguration
close_mappings:
- cim:TransformerBankConfiguration
is_a: glm_object
attributes:
  connect_type:
    name: connect_type
    annotations:
      order:
        tag: order
        value: 1
      value_type:
        tag: value_type
        value: string
      native_name:
        tag: native_name
        value: connect_type
    description: 'connect type enum: Wye-Wye, single-phase, etc.'
    comments:
    - 'Import: sets the form and each end''s connectionKind (WYE_WYE and SINGLE_PHASE
      Y/Y, DELTA_GWYE D/Y, DELTA_DELTA D/D, SINGLE_PHASE_CENTER_TAPPED lugs); unset
      raises. Export: chosen from the connectionKinds and phases (WYE_WYE, SINGLE_PHASE,
      DELTA_DELTA, DELTA_GWYE, SINGLE_PHASE_CENTER_TAPPED).'
    from_schema: https://gridlabd.org/schema/glm/powerflow/transformer_configuration
    close_mappings:
    - cim:TransformerTankEnd.connectionKind
    owner: transformer_configuration
    domain_of:
    - regulator_configuration
    - transformer_configuration
    range: string
    required: false
  install_type:
    name: install_type
    annotations:
      order:
        tag: order
        value: 2
      value_type:
        tag: value_type
        value: string
      native_name:
        tag: native_name
        value: install_type
    description: Defines location of the transformer installation
    from_schema: https://gridlabd.org/schema/glm/powerflow/transformer_configuration
    rank: 1000
    owner: transformer_configuration
    domain_of:
    - transformer_configuration
    range: string
    required: false
  coolant_type:
    name: coolant_type
    annotations:
      order:
        tag: order
        value: 3
      value_type:
        tag: value_type
        value: string
      native_name:
        tag: native_name
        value: coolant_type
    description: coolant type, used in life time model
    from_schema: https://gridlabd.org/schema/glm/powerflow/transformer_configuration
    rank: 1000
    owner: transformer_configuration
    domain_of:
    - transformer_configuration
    range: string
    required: false
  cooling_type:
    name: cooling_type
    annotations:
      order:
        tag: order
        value: 4
      value_type:
        tag: value_type
        value: string
      native_name:
        tag: native_name
        value: cooling_type
    description: type of coolant fluid used in life time model
    from_schema: https://gridlabd.org/schema/glm/powerflow/transformer_configuration
    rank: 1000
    owner: transformer_configuration
    domain_of:
    - transformer_configuration
    range: string
    required: false
  primary_voltage:
    name: primary_voltage
    annotations:
      order:
        tag: order
        value: 5
      value_type:
        tag: value_type
        value: float
      precision:
        tag: precision
        value: 6
      native_name:
        tag: native_name
        value: primary_voltage[V]
    description: primary voltage level in L-L value kV
    comments:
    - 'Import: TransformerWinding.ratedU (V) line to line and baseU (V) the coil,
      from winding 1. Export: winding 1 ratedU, a coil''s baseU; an LTC''s actual
      ratio folded in.'
    from_schema: https://gridlabd.org/schema/glm/powerflow/transformer_configuration
    close_mappings:
    - cim:TransformerWinding.ratedU
    - cim:TransformerWinding.baseU
    rank: 1000
    owner: transformer_configuration
    domain_of:
    - transformer_configuration
    range: float
    required: false
    unit:
      ucum_code: V
  secondary_voltage:
    name: secondary_voltage
    annotations:
      order:
        tag: order
        value: 6
      value_type:
        tag: value_type
        value: float
      precision:
        tag: precision
        value: 6
      native_name:
        tag: native_name
        value: secondary_voltage[V]
    description: secondary voltage level kV
    comments:
    - 'Import: TransformerWinding.ratedU and baseU (V) of winding 2; a center tap''s
      half is ratedU x 2. Export: winding 2''s, likewise.'
    from_schema: https://gridlabd.org/schema/glm/powerflow/transformer_configuration
    close_mappings:
    - cim:TransformerWinding.ratedU
    - cim:TransformerWinding.baseU
    rank: 1000
    owner: transformer_configuration
    domain_of:
    - transformer_configuration
    range: float
    required: false
    unit:
      ucum_code: V
  power_rating:
    name: power_rating
    annotations:
      order:
        tag: order
        value: 7
      value_type:
        tag: value_type
        value: float
      precision:
        tag: precision
        value: 6
      native_name:
        tag: native_name
        value: power_rating[kVA]
    description: kVA rating of transformer, total
    comments:
    - 'Import: TransformerWinding.ratedS (kVA) of the whole unit, else the phase sum;
      baseS the tank''s share. Export: winding 1 ratedS (kVA).'
    from_schema: https://gridlabd.org/schema/glm/powerflow/transformer_configuration
    close_mappings:
    - cim:TransformerWinding.ratedS
    - cim:TransformerWinding.baseS
    rank: 1000
    owner: transformer_configuration
    domain_of:
    - transformer_configuration
    range: float
    required: false
    unit:
      ucum_code: kVA
  powerA_rating:
    name: powerA_rating
    annotations:
      order:
        tag: order
        value: 8
      value_type:
        tag: value_type
        value: float
      precision:
        tag: precision
        value: 6
      native_name:
        tag: native_name
        value: powerA_rating[kVA]
    description: kVA rating of transformer, phase A
    comments:
    - 'Import: a can''s TransformerWinding.ratedS (kVA) when the phases are rated
      unequally; a center tap''s on its phase. Export: a coil''s or center tap''s
      kVA on phase A.'
    from_schema: https://gridlabd.org/schema/glm/powerflow/transformer_configuration
    close_mappings:
    - cim:TransformerWinding.ratedS
    rank: 1000
    owner: transformer_configuration
    domain_of:
    - transformer_configuration
    range: float
    required: false
    unit:
      ucum_code: kVA
  powerB_rating:
    name: powerB_rating
    annotations:
      order:
        tag: order
        value: 9
      value_type:
        tag: value_type
        value: float
      precision:
        tag: precision
        value: 6
      native_name:
        tag: native_name
        value: powerB_rating[kVA]
    description: kVA rating of transformer, phase B
    comments:
    - 'Import: a can''s TransformerWinding.ratedS (kVA) when the phases are rated
      unequally; a center tap''s on its phase. Export: a coil''s or center tap''s
      kVA on phase B.'
    from_schema: https://gridlabd.org/schema/glm/powerflow/transformer_configuration
    close_mappings:
    - cim:TransformerWinding.ratedS
    rank: 1000
    owner: transformer_configuration
    domain_of:
    - transformer_configuration
    range: float
    required: false
    unit:
      ucum_code: kVA
  powerC_rating:
    name: powerC_rating
    annotations:
      order:
        tag: order
        value: 10
      value_type:
        tag: value_type
        value: float
      precision:
        tag: precision
        value: 6
      native_name:
        tag: native_name
        value: powerC_rating[kVA]
    description: kVA rating of transformer, phase C
    comments:
    - 'Import: a can''s TransformerWinding.ratedS (kVA) when the phases are rated
      unequally; a center tap''s on its phase. Export: a coil''s or center tap''s
      kVA on phase C.'
    from_schema: https://gridlabd.org/schema/glm/powerflow/transformer_configuration
    close_mappings:
    - cim:TransformerWinding.ratedS
    rank: 1000
    owner: transformer_configuration
    domain_of:
    - transformer_configuration
    range: float
    required: false
    unit:
      ucum_code: kVA
  resistance:
    name: resistance
    annotations:
      order:
        tag: order
        value: 11
      value_type:
        tag: value_type
        value: float
      precision:
        tag: precision
        value: 6
      native_name:
        tag: native_name
        value: resistance[pu]
    description: Series impedance, pu, real
    comments:
    - 'Import: percentImpedance (percent) = |R + jX| x k x 100 and loadLoss (kW) =
      R x k x S, k moving GridLAB-D''s base to the tank''s. Export: the (1, 2) R in
      pu on winding 1 ratedS; not positive is written 1e-6.'
    from_schema: https://gridlabd.org/schema/glm/powerflow/transformer_configuration
    close_mappings:
    - cim:TransformerTankConfiguration.percentImpedance
    - cim:TransformerTankConfiguration.loadLoss
    owner: transformer_configuration
    domain_of:
    - overhead_line_conductor
    - transformer_configuration
    - triplex_line_conductor
    range: float
    required: false
    unit:
      ucum_code: pu
  reactance:
    name: reactance
    annotations:
      order:
        tag: order
        value: 12
      value_type:
        tag: value_type
        value: float
      precision:
        tag: precision
        value: 6
      native_name:
        tag: native_name
        value: reactance[pu]
    description: Series impedance, pu, imag
    comments:
    - 'Import: with resistance, percentImpedance (percent). Export: the (1, 2) X in
      pu; not positive is written 1e-6.'
    from_schema: https://gridlabd.org/schema/glm/powerflow/transformer_configuration
    close_mappings:
    - cim:TransformerTankConfiguration.percentImpedance
    rank: 1000
    owner: transformer_configuration
    domain_of:
    - transformer_configuration
    range: float
    required: false
    unit:
      ucum_code: pu
  impedance:
    name: impedance
    annotations:
      order:
        tag: order
        value: 13
      value_type:
        tag: value_type
        value: complex
      native_name:
        tag: native_name
        value: impedance[pu]
    description: Series impedance, pu
    comments:
    - 'Import: R + jX as resistance and reactance; a center tap''s is the full winding''s.
      Export: the (1, 2) R + jX in pu; a center tap''s or star leg''s star branch.'
    from_schema: https://gridlabd.org/schema/glm/powerflow/transformer_configuration
    close_mappings:
    - cim:TransformerTankConfiguration.percentImpedance
    - cim:TransformerTankConfiguration.loadLoss
    rank: 1000
    owner: transformer_configuration
    domain_of:
    - transformer_configuration
    range: Complex
    required: false
    unit:
      ucum_code: pu
  resistance1:
    name: resistance1
    annotations:
      order:
        tag: order
        value: 14
      value_type:
        tag: value_type
        value: float
      precision:
        tag: precision
        value: 6
      native_name:
        tag: native_name
        value: resistance1[pu]
    description: Secondary series impedance (only used when you want to define each
      individual winding seperately, pu, real
    from_schema: https://gridlabd.org/schema/glm/powerflow/transformer_configuration
    rank: 1000
    owner: transformer_configuration
    domain_of:
    - transformer_configuration
    range: float
    required: false
    unit:
      ucum_code: pu
  reactance1:
    name: reactance1
    annotations:
      order:
        tag: order
        value: 15
      value_type:
        tag: value_type
        value: float
      precision:
        tag: precision
        value: 6
      native_name:
        tag: native_name
        value: reactance1[pu]
    description: Secondary series impedance (only used when you want to define each
      individual winding seperately, pu, imag
    from_schema: https://gridlabd.org/schema/glm/powerflow/transformer_configuration
    rank: 1000
    owner: transformer_configuration
    domain_of:
    - transformer_configuration
    range: float
    required: false
    unit:
      ucum_code: pu
  impedance1:
    name: impedance1
    annotations:
      order:
        tag: order
        value: 16
      value_type:
        tag: value_type
        value: complex
      native_name:
        tag: native_name
        value: impedance1[pu]
    description: Secondary series impedance (only used when you want to define each
      individual winding seperately, pu
    comments:
    - 'Import: a center tap''s half, checked against GridLAB-D''s split of one R +
      jX; any other split raises. Export: a center tap''s s1 half of the star.'
    from_schema: https://gridlabd.org/schema/glm/powerflow/transformer_configuration
    close_mappings:
    - cim:TransformerTankConfiguration.percentImpedance
    rank: 1000
    owner: transformer_configuration
    domain_of:
    - transformer_configuration
    range: Complex
    required: false
    unit:
      ucum_code: pu
  resistance2:
    name: resistance2
    annotations:
      order:
        tag: order
        value: 17
      value_type:
        tag: value_type
        value: float
      precision:
        tag: precision
        value: 6
      native_name:
        tag: native_name
        value: resistance2[pu]
    description: Secondary series impedance (only used when you want to define each
      individual winding seperately, pu, real
    from_schema: https://gridlabd.org/schema/glm/powerflow/transformer_configuration
    rank: 1000
    owner: transformer_configuration
    domain_of:
    - transformer_configuration
    range: float
    required: false
    unit:
      ucum_code: pu
  reactance2:
    name: reactance2
    annotations:
      order:
        tag: order
        value: 18
      value_type:
        tag: value_type
        value: float
      precision:
        tag: precision
        value: 6
      native_name:
        tag: native_name
        value: reactance2[pu]
    description: Secondary series impedance (only used when you want to define each
      individual winding seperately, pu, imag
    from_schema: https://gridlabd.org/schema/glm/powerflow/transformer_configuration
    rank: 1000
    owner: transformer_configuration
    domain_of:
    - transformer_configuration
    range: float
    required: false
    unit:
      ucum_code: pu
  impedance2:
    name: impedance2
    annotations:
      order:
        tag: order
        value: 19
      value_type:
        tag: value_type
        value: complex
      native_name:
        tag: native_name
        value: impedance2[pu]
    description: Secondary series impedance (only used when you want to define each
      individual winding seperately, pu
    comments:
    - 'Import: as impedance1, the s2 half. Export: a center tap''s s2 half of the
      star.'
    from_schema: https://gridlabd.org/schema/glm/powerflow/transformer_configuration
    close_mappings:
    - cim:TransformerTankConfiguration.percentImpedance
    rank: 1000
    owner: transformer_configuration
    domain_of:
    - transformer_configuration
    range: Complex
    required: false
    unit:
      ucum_code: pu
  shunt_resistance:
    name: shunt_resistance
    annotations:
      order:
        tag: order
        value: 20
      value_type:
        tag: value_type
        value: float
      precision:
        tag: precision
        value: 6
      native_name:
        tag: native_name
        value: shunt_resistance[pu]
    description: Shunt impedance on primary side, pu, real
    comments:
    - 'Import: noLoadLoss (kW) = S / (Rsh x k); unset is lossless and not filled.
      Export: 1 / the core g in pu; unset when there is no core.'
    from_schema: https://gridlabd.org/schema/glm/powerflow/transformer_configuration
    close_mappings:
    - cim:TransformerTankConfiguration.noLoadLoss
    rank: 1000
    owner: transformer_configuration
    domain_of:
    - transformer_configuration
    range: float
    required: false
    unit:
      ucum_code: pu
  shunt_reactance:
    name: shunt_reactance
    annotations:
      order:
        tag: order
        value: 21
      value_type:
        tag: value_type
        value: float
      precision:
        tag: precision
        value: 6
      native_name:
        tag: native_name
        value: shunt_reactance[pu]
    description: Shunt impedance on primary side, pu, imag
    comments:
    - 'Import: percentMagnetizingCurrent (percent) = 100 / (Xsh x k). Export: 1 /
      the core b in pu.'
    from_schema: https://gridlabd.org/schema/glm/powerflow/transformer_configuration
    close_mappings:
    - cim:TransformerTankConfiguration.percentMagnetizingCurrent
    rank: 1000
    owner: transformer_configuration
    domain_of:
    - transformer_configuration
    range: float
    required: false
    unit:
      ucum_code: pu
  shunt_impedance:
    name: shunt_impedance
    annotations:
      order:
        tag: order
        value: 22
      value_type:
        tag: value_type
        value: complex
      native_name:
        tag: native_name
        value: shunt_impedance[pu]
    description: Shunt impedance on primary side, pu
    comments:
    - 'Import: Rsh + jXsh as shunt_resistance and shunt_reactance; on a delta connection
      raises.'
    from_schema: https://gridlabd.org/schema/glm/powerflow/transformer_configuration
    close_mappings:
    - cim:TransformerTankConfiguration.noLoadLoss
    - cim:TransformerTankConfiguration.percentMagnetizingCurrent
    rank: 1000
    owner: transformer_configuration
    domain_of:
    - transformer_configuration
    range: Complex
    required: false
    unit:
      ucum_code: pu
  core_coil_weight:
    name: core_coil_weight
    annotations:
      order:
        tag: order
        value: 23
      value_type:
        tag: value_type
        value: float
      precision:
        tag: precision
        value: 6
      native_name:
        tag: native_name
        value: core_coil_weight[lb]
    description: The weight of the core and coil assembly in pounds
    from_schema: https://gridlabd.org/schema/glm/powerflow/transformer_configuration
    rank: 1000
    owner: transformer_configuration
    domain_of:
    - transformer_configuration
    range: float
    required: false
    unit:
      ucum_code: lb
  tank_fittings_weight:
    name: tank_fittings_weight
    annotations:
      order:
        tag: order
        value: 24
      value_type:
        tag: value_type
        value: float
      precision:
        tag: precision
        value: 6
      native_name:
        tag: native_name
        value: tank_fittings_weight[lb]
    description: The weight of the tank and fittings in pounds
    from_schema: https://gridlabd.org/schema/glm/powerflow/transformer_configuration
    rank: 1000
    owner: transformer_configuration
    domain_of:
    - transformer_configuration
    range: float
    required: false
    unit:
      ucum_code: lb
  oil_volume:
    name: oil_volume
    annotations:
      order:
        tag: order
        value: 25
      value_type:
        tag: value_type
        value: float
      precision:
        tag: precision
        value: 6
      native_name:
        tag: native_name
        value: oil_volume[gal]
    description: The number of gallons of oil in the transformer
    from_schema: https://gridlabd.org/schema/glm/powerflow/transformer_configuration
    rank: 1000
    owner: transformer_configuration
    domain_of:
    - transformer_configuration
    range: float
    required: false
    unit:
      ucum_code: gal
  rated_winding_time_constant:
    name: rated_winding_time_constant
    annotations:
      order:
        tag: order
        value: 26
      value_type:
        tag: value_type
        value: float
      precision:
        tag: precision
        value: 6
      native_name:
        tag: native_name
        value: rated_winding_time_constant[h]
    description: The rated winding time constant in hours
    from_schema: https://gridlabd.org/schema/glm/powerflow/transformer_configuration
    rank: 1000
    owner: transformer_configuration
    domain_of:
    - transformer_configuration
    range: float
    required: false
    unit:
      ucum_code: h
  rated_winding_hot_spot_rise:
    name: rated_winding_hot_spot_rise
    annotations:
      order:
        tag: order
        value: 27
      value_type:
        tag: value_type
        value: float
      precision:
        tag: precision
        value: 6
      native_name:
        tag: native_name
        value: rated_winding_hot_spot_rise[degC]
    description: winding hottest-spot rise over ambient temperature at rated load,
      degrees C
    from_schema: https://gridlabd.org/schema/glm/powerflow/transformer_configuration
    rank: 1000
    owner: transformer_configuration
    domain_of:
    - transformer_configuration
    range: float
    required: false
    unit:
      ucum_code: degC
  rated_top_oil_rise:
    name: rated_top_oil_rise
    annotations:
      order:
        tag: order
        value: 28
      value_type:
        tag: value_type
        value: float
      precision:
        tag: precision
        value: 6
      native_name:
        tag: native_name
        value: rated_top_oil_rise[degC]
    description: top-oil hottest-spot rise over ambient temperature at rated load,
      degrees C
    from_schema: https://gridlabd.org/schema/glm/powerflow/transformer_configuration
    rank: 1000
    owner: transformer_configuration
    domain_of:
    - transformer_configuration
    range: float
    required: false
    unit:
      ucum_code: degC
  no_load_loss:
    name: no_load_loss
    annotations:
      order:
        tag: order
        value: 29
      value_type:
        tag: value_type
        value: float
      precision:
        tag: precision
        value: 6
      native_name:
        tag: native_name
        value: no_load_loss[pu]
    description: Another method of specifying transformer impedances, defined as per
      unit power values (shunt)
    comments:
    - 'Import: raises when set (it replaces the impedances on a center tap and no
      deck sets it). Export: not written.'
    from_schema: https://gridlabd.org/schema/glm/powerflow/transformer_configuration
    rank: 1000
    owner: transformer_configuration
    domain_of:
    - transformer_configuration
    range: float
    required: false
    unit:
      ucum_code: pu
  full_load_loss:
    name: full_load_loss
    annotations:
      order:
        tag: order
        value: 30
      value_type:
        tag: value_type
        value: float
      precision:
        tag: precision
        value: 6
      native_name:
        tag: native_name
        value: full_load_loss[pu]
    description: Another method of specifying transformer impedances, defined as per
      unit power values (shunt and series)
    comments:
    - 'Import: raises when set, as no_load_loss. Export: not written.'
    from_schema: https://gridlabd.org/schema/glm/powerflow/transformer_configuration
    rank: 1000
    owner: transformer_configuration
    domain_of:
    - transformer_configuration
    range: float
    required: false
    unit:
      ucum_code: pu
  reactance_resistance_ratio:
    name: reactance_resistance_ratio
    annotations:
      order:
        tag: order
        value: 31
      value_type:
        tag: value_type
        value: float
      precision:
        tag: precision
        value: 6
      native_name:
        tag: native_name
        value: reactance_resistance_ratio
    description: the reactance to resistance ratio (X/R)
    from_schema: https://gridlabd.org/schema/glm/powerflow/transformer_configuration
    rank: 1000
    owner: transformer_configuration
    domain_of:
    - transformer_configuration
    range: float
    required: false
  installed_insulation_life:
    name: installed_insulation_life
    annotations:
      order:
        tag: order
        value: 32
      value_type:
        tag: value_type
        value: float
      precision:
        tag: precision
        value: 6
      native_name:
        tag: native_name
        value: installed_insulation_life[h]
    description: the normal lifetime of the transformer insulation at rated load,
      hours
    from_schema: https://gridlabd.org/schema/glm/powerflow/transformer_configuration
    rank: 1000
    owner: transformer_configuration
    domain_of:
    - transformer_configuration
    range: float
    required: false
    unit:
      ucum_code: h
  magnetization_location:
    name: magnetization_location
    annotations:
      order:
        tag: order
        value: 33
      value_type:
        tag: value_type
        value: string
      native_name:
        tag: native_name
        value: magnetization_location
    description: winding to place magnetization influence for in-rush calculations
    from_schema: https://gridlabd.org/schema/glm/powerflow/transformer_configuration
    rank: 1000
    owner: transformer_configuration
    domain_of:
    - transformer_configuration
    range: string
    required: false
  inrush_saturation_enabled:
    name: inrush_saturation_enabled
    annotations:
      order:
        tag: order
        value: 34
      value_type:
        tag: value_type
        value: bool
      native_name:
        tag: native_name
        value: inrush_saturation_enabled
    description: flag to include saturation effects during inrush calculations
    from_schema: https://gridlabd.org/schema/glm/powerflow/transformer_configuration
    rank: 1000
    owner: transformer_configuration
    domain_of:
    - transformer_configuration
    range: boolean
    required: false
  L_A:
    name: L_A
    annotations:
      order:
        tag: order
        value: 35
      value_type:
        tag: value_type
        value: float
      precision:
        tag: precision
        value: 6
      native_name:
        tag: native_name
        value: L_A[pu]
    description: Air core inductance of transformer
    from_schema: https://gridlabd.org/schema/glm/powerflow/transformer_configuration
    rank: 1000
    owner: transformer_configuration
    domain_of:
    - transformer_configuration
    range: float
    required: false
    unit:
      ucum_code: pu
  phi_K:
    name: phi_K
    annotations:
      order:
        tag: order
        value: 36
      value_type:
        tag: value_type
        value: float
      precision:
        tag: precision
        value: 6
      native_name:
        tag: native_name
        value: phi_K[pu]
    description: Knee flux value where the air core inductance interstes the flux
      axis of the saturation curve
    from_schema: https://gridlabd.org/schema/glm/powerflow/transformer_configuration
    rank: 1000
    owner: transformer_configuration
    domain_of:
    - transformer_configuration
    range: float
    required: false
    unit:
      ucum_code: pu
  phi_M:
    name: phi_M
    annotations:
      order:
        tag: order
        value: 37
      value_type:
        tag: value_type
        value: float
      precision:
        tag: precision
        value: 6
      native_name:
        tag: native_name
        value: phi_M[pu]
    description: Peak magnetization flux at rated voltage of the saturation curve
    from_schema: https://gridlabd.org/schema/glm/powerflow/transformer_configuration
    rank: 1000
    owner: transformer_configuration
    domain_of:
    - transformer_configuration
    range: float
    required: false
    unit:
      ucum_code: pu
  I_M:
    name: I_M
    annotations:
      order:
        tag: order
        value: 38
      value_type:
        tag: value_type
        value: float
      precision:
        tag: precision
        value: 6
      native_name:
        tag: native_name
        value: I_M[pu]
    description: Peak magnetization current at rated voltage of the saturation curve
    from_schema: https://gridlabd.org/schema/glm/powerflow/transformer_configuration
    rank: 1000
    owner: transformer_configuration
    domain_of:
    - transformer_configuration
    range: float
    required: false
    unit:
      ucum_code: pu
  T_D:
    name: T_D
    annotations:
      order:
        tag: order
        value: 39
      value_type:
        tag: value_type
        value: float
      precision:
        tag: precision
        value: 6
      native_name:
        tag: native_name
        value: T_D
    description: Inrush decay time constant for inrush current
    from_schema: https://gridlabd.org/schema/glm/powerflow/transformer_configuration
    rank: 1000
    owner: transformer_configuration
    domain_of:
    - transformer_configuration
    range: float
    required: false
  name:
    name: name
    annotations:
      order:
        tag: order
        value: 0
      value_type:
        tag: value_type
        value: string
      native_name:
        tag: native_name
        value: name
    description: The object's name; unique across the model.
    comments:
    - 'Import: <CIM class>.name, copied as written; mRID = the class''s prefix + name
      (none on a bus). Export: Names, sanitized for GridLAB-D; a name two objects
      share raises.'
    from_schema: https://gridlabd.org/schema/glm/types/common
    exact_mappings:
    - cim:IdentifiedObject.name
    rank: 1000
    identifier: true
    owner: transformer_configuration
    domain_of:
    - glm_object
    range: string
    required: true
  parent:
    name: parent
    annotations:
      order:
        tag: order
        value: 0
      value_type:
        tag: value_type
        value: string
      native_name:
        tag: native_name
        value: parent
    description: The parent object's name. A child node is solved as its parent's
      bus; a nested object block sets it to the enclosing object.
    comments:
    - 'Import: a bus whose parent is a bus is its root bus''s ConnectivityNode, named
      on the root''s row; no object of its own. On a link it is not mapped.'
    from_schema: https://gridlabd.org/schema/glm/types/common
    rank: 1000
    owner: transformer_configuration
    domain_of:
    - glm_object
    range: string
  groupid:
    name: groupid
    annotations:
      order:
        tag: order
        value: 0
      value_type:
        tag: value_type
        value: string
      native_name:
        tag: native_name
        value: groupid
    description: Free-text group label.
    from_schema: https://gridlabd.org/schema/glm/types/common
    rank: 1000
    owner: transformer_configuration
    domain_of:
    - glm_object
    range: string
  latitude:
    name: latitude
    annotations:
      order:
        tag: order
        value: 0
      value_type:
        tag: value_type
        value: string
      native_name:
        tag: native_name
        value: latitude
    description: Latitude, as written (decimal degrees or GridLAB-D's 37N26:12 form).
    comments:
    - Not converted. Home is the EquipmentLocation shape.
    from_schema: https://gridlabd.org/schema/glm/types/common
    rank: 1000
    owner: transformer_configuration
    domain_of:
    - glm_object
    range: string
  longitude:
    name: longitude
    annotations:
      order:
        tag: order
        value: 0
      value_type:
        tag: value_type
        value: string
      native_name:
        tag: native_name
        value: longitude
    description: Longitude, as written.
    comments:
    - Not converted. Home is the EquipmentLocation shape.
    from_schema: https://gridlabd.org/schema/glm/types/common
    rank: 1000
    owner: transformer_configuration
    domain_of:
    - glm_object
    range: string
  in_svc:
    name: in_svc
    annotations:
      order:
        tag: order
        value: 0
      value_type:
        tag: value_type
        value: string
      native_name:
        tag: native_name
        value: in_svc
    description: Timestamp the object enters service.
    from_schema: https://gridlabd.org/schema/glm/types/common
    rank: 1000
    owner: transformer_configuration
    domain_of:
    - glm_object
    range: string
  out_svc:
    name: out_svc
    annotations:
      order:
        tag: order
        value: 0
      value_type:
        tag: value_type
        value: string
      native_name:
        tag: native_name
        value: out_svc
    description: Timestamp the object leaves service.
    from_schema: https://gridlabd.org/schema/glm/types/common
    rank: 1000
    owner: transformer_configuration
    domain_of:
    - glm_object
    range: string
  rank:
    name: rank
    annotations:
      order:
        tag: order
        value: 0
      value_type:
        tag: value_type
        value: string
      native_name:
        tag: native_name
        value: rank
    description: Solver rank.
    from_schema: https://gridlabd.org/schema/glm/types/common
    rank: 1000
    owner: transformer_configuration
    domain_of:
    - glm_object
    range: string
  flags:
    name: flags
    annotations:
      order:
        tag: order
        value: 0
      value_type:
        tag: value_type
        value: string
      native_name:
        tag: native_name
        value: flags
    description: Core object flags.
    from_schema: https://gridlabd.org/schema/glm/types/common
    rank: 1000
    owner: transformer_configuration
    domain_of:
    - glm_object
    range: string