OpenDSS → .cimtbl mapping spec¶
Status: S2 done (2026-11-07): LineCode units, base frequency and short sequence codes; wire catalogs;
LineSpacing/LineGeometry. S3a and S3b done 2026-11-08 (lines, switches, transformers, regulators, RegControl, XfmrCode templates). S4a done 2026-11-08 (Load, Capacitor, CapControl); S4b done 2026-11-08 (PVSystem, Storage, Generator, Reactor); S5 done 2026-11-08 (bus coordinates, the deck sweep test). LineCode (Phase 1) and the inline Transformer are seeded from CIMHub_2_0 with
their atoms; the master, buses and Vsource are S0/S1's. The other DSS classes follow slice by slice
(DSS_REWRITE_PLAN.md), each section approved before its code (DSS-12).
Format: the cimtbl-mapping-spec skill. Contract: the cimtbl-import-contract skill.
The classification tables are generated from each mapper's FIELDS with
cimhub_core.cimtbl.fields_table(..., fields=FIELDS). The samples come from tests/decks/IEEE/IEEE13_CDPSM/ and the
IEEE8500 LineCodes.dss; the S2 tables' samples come from the 31 sweep decks. {length} in a unit is the code's
units; {r_length}, {gmr_length}, {radius_length} are a wire's Runits, GMRunits, radunits.
Artifact files and order¶
| native class | artifact | shape | depends on |
|---|---|---|---|
| (the deck) | <Model>.cimtbl (master) |
settings, common rows (Substation, Feeder, BaseFrequency, BaseVoltage), Imports |
every part |
| (the topology walk) | bus.cimtbl |
one ConnectivityNode per bus, with its BaseVoltage |
the master |
Vsource |
vsource.cimtbl |
source |
the master, bus.cimtbl |
WireData, CNData, TSData |
wiredata.cimtbl, cndata.cimtbl, tsdata.cimtbl |
wire_info |
nothing |
LineSpacing |
linespacing.cimtbl |
line_by_wire_configuration (XYSpacing) |
nothing |
LineGeometry |
linegeometry.cimtbl |
line_by_wire_configuration (WireConfiguration; inline positions get a synthesized XYSpacing) |
the wire catalogs, linespacing.cimtbl |
LineCode |
linecode.cimtbl |
matrix code: PerLengthPhaseImpedance + PhaseImpedanceData per lower-triangle element; sequence code: PerLengthSequenceImpedance |
nothing |
Line (+ Fuse, Recloser, SwtControl) |
line.cimtbl |
line_by_impedance, line_by_wire_configuration, switch; the line's own impedance ln_<name>_lc (isTemplate=false), synthesized ln_<name>_wc; ratings as OperationalLimitSet + CurrentLimit |
the master (Feeder, BaseVoltage, OperationalLimitType), bus.cimtbl, the catalogs |
XfmrCode |
xfmrcode.cimtbl |
transformer_template (3-phase, TankEnd), transformer_template_1ph (1-phase, lugs); seasonal ratings as the template's own OperationalLimitSet + ApparentPowerLimit |
the instances that use it (their bus systems); the master (OperationalLimitType) |
Transformer |
transformer.cimtbl |
3-phase: transformer_by_ends; 1-phase: transformer_by_phase_ends; regulated with equal winding kV: voltage_regulator; seasonal ratings as OperationalLimitSet + ApparentPowerLimit |
the master (Feeder, BaseVoltage, OperationalLimitType) and the topology walk's bus systems |
RegControl |
regcontrol.cimtbl |
voltage_regulator / regulator (RatioTapChanger + TapChangerControl) |
transformer.cimtbl |
LoadShape (those a Load names as yearly) |
loadshape.cimtbl |
load_schedule (ConformLoadGroup + ConformLoadSchedule; the points in the Parquet sidecar, S8) |
nothing |
a shape a PVSystem, Storage or Generator names as yearly is not here but that device's own EnergyConnectionSchedule, in its document (S9) |
|||
Load |
load.cimtbl |
load; exp_<CVRwatts>_<CVRvars> response rows; a ConformLoad of its yearly shape's group (S8) |
the master (Feeder, BaseVoltage, zip_fractions.cimtbl), bus.cimtbl, loadshape.cimtbl |
Capacitor |
capacitor.cimtbl |
shunt (LinearShuntCompensator) |
the master, bus.cimtbl |
CapControl |
capcontrol.cimtbl |
shunt (RegulatingControl + Update of the compensator) |
line.cimtbl, capacitor.cimtbl |
PVSystem, Storage |
pvsystem.cimtbl, storage.cimtbl |
der; a yearly shape: nc_schedule EnergyConnectionSchedule <mRID>_yearly (the points in the Parquet sidecar, S9) |
the master, bus.cimtbl |
Generator |
generator.cimtbl |
synchronous_machine; a yearly shape as for a PVSystem (S9) |
the master, bus.cimtbl |
Reactor |
reactor.cimtbl |
series_compensator |
the master, bus.cimtbl |
Buscoords (BusCoords / LatLongCoords files) |
buscoords.cimtbl (last) |
location |
every equipment part (their bound Terminals: bound_parts, S5-2) |
Master¶
Orchestrator: cimhub_opendss/importer/dss_to_cimtbl.py (DssImporter, map_master, dss_to_cim). Golden:
tests/goldens/IEEE13_CDPSM/IEEE13_CDPSM.cimtbl, tested by tests/test_dss_to_cimtbl.py. Approved 2026-11-07 (D7 as
written); the common rows approved with S1.
- File and settings (plan D7): the caller names the model (
DssImporter("IEEE13_CDPSM")); it is the master's file stem andModel.Authorityishttps://github.com/PNNL-CIM-Tools/CIMHubunless the caller passes another.Profile = cim18v17. - Imports: one per non-empty part, in
MAPPING_ORDER(catalogs before instances, plan section 2). A DSS class with no records writes no part and noImport. - Comment: the deck name, this anchor, and
not mapped:with the record count of every DSS class no mapper reads yet (DSS-11), so a class never disappears silently. The list shrinks as slices land. commonrows (S1). The containers come fromNew Circuit.<circuit>, which the reader keeps asOptions.circuit. A deck with noNew Circuit, or with a second one, raises.
Object Substation: mRID=sub_<circuit>, name=<circuit>
Object Feeder: mRID=fdr_<circuit>, name=<circuit>, NormalEnergizingSubstation=sub_<circuit>
Object BaseFrequency: mRID=bf_60hz, frequency (Hz)=60 # defaulted: defaultbasefreq=60.0
# voltagebases: 115.0, 4.16, 13.2, 0.48, 0.208; on no bus: 0.208; not in voltagebases: 0.24
Table BaseVoltage: mRID, nominalVoltage (kV)
bv_115kv, 115.0
bv_13p2kv, 13.2
...
bv_240v, 0.24
bv_208v, 0.208
mRIDs are lowercased, like every DSS mRID.
- BaseFrequency is Set defaultbasefreq, else the DSS default of 60 Hz (DSS-3b). Set basefrequency raises in
the reader: the engine applies it only to objects defined after it, so the deck could hold two base frequencies.
- The BaseVoltages are one per distinct bus voltage of the topology walk and one per voltagebases value, each
through nominal_kv, highest first. A base on no bus is kept (bv_208v above): it is what the engine's
CalcVoltageBases snaps bus bases to, so the export writes it back (Set voltagebases is every BaseVoltage).
Buses still take the walk's voltage (bus.cimtbl). The comment reconciles the two lists: the deck's
voltagebases, those on no bus, and walk voltages missing from voltagebases (a bus the engine would snap,
plan section 3.1) as not in voltagebases. This amends DSS-1 ("the walk's, never voltagebases"), on
2026-11-24 at the user's direction (test_voltagebases_on_no_bus_are_kept_for_the_engine).
- The OperationalLimitTypes are olt_normal and olt_emergency (the line ratings, R1), then olt_season1 ..
olt_season<N> for the most seasons any Transformer or XfmrCode Ratings rate (limit_types(seasons); see
Transformer). IEEE13_CDPSM rates none, so it has only the first two.
- The Substation holds the EnergySources. The Feeder holds every other piece of equipment and every
ConnectivityNode, so it is the container that mappers receive.
Buses¶
Orchestrator: importer/dss_to_cimtbl.py (map_buses). Golden: tests/goldens/IEEE13_CDPSM/bus.cimtbl.
Approved 2026-11-07: equipment keeps its own BaseVoltage (mandatory).
cim18v17 adds ConnectivityNode.BaseVoltage. The CIM text: it "is used only if the ConnectivityNode is not
contained in a VoltageLevel", and "it is not required that the BaseVoltage of connected equipment is the same".
There are no VoltageLevels here, so the topology walk's result becomes an artifact: one row per bus it reaches.
# Bus voltages from the topology walk (cimtopology.core) from the source buses; 22 buses.
Table ConnectivityNode: mRID, name, BaseVoltage, ConnectivityNodeContainer=fdr_ieee13nodeckt
sourcebus, sourcebus, bv_115kv
650z, 650z, bv_13p2kv
...
mRIDandnameare the bus name, lowercased: the walk's key, and the cell everynodecolumn writes. cimtables binds a laternode=650to this node instead of creating a new one.- Rows are sorted highest voltage first, then by bus name, so the file does not depend on the walk's internals.
- A bus the walk does not reach has no row. Equipment on such a bus raises in its mapper (
no bus voltage), as the transformer mapper already does.
What this solves:
- Every bus has a voltage, written once. A DSS Line, switch or reactor has none of its own. A bus between two
transformers had a voltage only through the TransformerEnds. An exporter that needs a per-bus base (DSS
setkVBase, a GridLAB-D node's nominal_voltage, the MATPOWER and RAW bus tables) reads the node instead of
inferring it from the equipment.
- The walk is visible. Plan section 3.1's result sits in a diffable file, not only in the mappers' buses
argument.
- A check on every equipment row. Equipment keeps its own BaseVoltage column, which cimtables needs as the
system base of a (pu) column and which consumers of ConductingEquipment.BaseVoltage read. The bind test
asserts it equals the BaseVoltage of each of the equipment's nodes. A transformer's ends already carry their own,
per end.
Vsource¶
Mapper: importer/cimtbl/vsource.py (map_vsource). Atoms: tests/atoms/vsource/: mvasc (IEEE13_CDPSM),
ohms (IEEE123), isc (IEEE4_xfmrs B1), defaults (New Circuit.x basekv=12.47) and single_phase, with
prereq.cimtbl; tested by tests/test_cimtbl_vsource.py. Approved 2026-11-07.
One EnergySource per Vsource, New Circuit included (source shape):
# OpenDSS Vsource -> EnergySource on its bus; 1 Vsource.
Table EnergySource: mRID, name, node, phases, nominalVoltage (kV), voltageMagnitude (kV), voltageAngle (deg), r (ohm), x (ohm), r0 (ohm), x0 (ohm), normallyInService, BaseVoltage, EquipmentContainer=sub_ieee13nodeckt
src_source, source, sourcebus, ABC, 115, 115, 30, 0.160376682055275, 0.641506728221101, 0.179603583012336, 0.538810749037007, true, bv_115kv # derived from MVAsc3=20000.0, MVAsc1=21000.0; defaulted: x1r1=4.0, x0r0=3.0
- Identity:
mRID=src_+name, lowercased. - Bus and phases:
bus1(defaultsourcebus) givesnode.phases(default 3) givesABCor, on a 1-phase source, the phase of the bus's single conductor. Any other phase count raises. Abus2raises, because an ungrounded (series) source has nosource-shape home. - Voltage:
nominalVoltage=basekv(default 115), copied.voltageMagnitude=basekv × pu(defaultpu1), derived.voltageAngle=angle(default 0), copied, in degrees. - Impedance. DSS has three ways to give a source's Thevenin impedance, and keeps the one set last
(Vsource properties,
VSource.pasPropertySideEffects). The reader does not record the order, so, as for LineCode, a Vsource that sets two groups raises: R1 X1 R0 X0(ohms): copied. All four must be set; a partial set raises.MVAsc3 MVAsc1(withx1r1,x0r0): derived byvsource.thevenin_from_short_circuit, which followsVSource.pasRecalcElementData:- X1 = kV² / MVAsc3 / √(1 + 1/x1r1²) and R1 = X1 / x1r1;
- R0 is the positive root of (1 + x0r0²)·R0² + 4(R1 + X1·x0r0)·R0 + 4(R1² + X1²) − (3·kV²/MVAsc1)² = 0, and X0 = R0 · x0r0;
- a negative discriminant raises, and so do kV, MVAsc3, MVAsc1 or x1r1 not above 0, x0r0 below 0 and a
negative R0: the engine refuses some and computes a negative, infinite or zero impedance for the rest.
A slot left unset takes its DSS default (
MVAsc32000,MVAsc12100,x1r14,x0r03) under# defaulted. A Vsource that sets no group takes all four defaults, as the engine does. LineCode raises in that case instead, but a bareNew Circuit.x basekv=12.47is the documented minimal deck.
Isc3 Isc1(amps): the short-circuit power, √3·kV·Isc3 and f·kV·Isc1 (f = √3 on 3 phases and 1 on 1 phase;vsource.kvasc_from_isc), then as group 2. kV times A is kVA, and kV² / kVA is kohm, so these rows go in their own table withr (kohm),x (kohm),r0 (kohm),x0 (kohm): the units travel with the values and no factor appears. Both must be set; a partial set raises (Isc3=1000alone at 12.47 kV gives the engine a negative R0).- Checked against the engine (
opendssdirect, 9 digits): IEEE13's MVAsc, all defaults,MVAsc3alone,Isc, and a 1-phase source. Z1 Z0 Z2 puZ1 puZ0 puZ2 baseMVAraise when set: no deck in the sweep uses them, so a mapping waits for one.- Group 2 and 3 values are derived numbers, so the row comment names their inputs. The test oracle is the engine:
r x r0 x0must equal? Vsource.<name>.R1etc. after compile, on every engine deck. enabled→normallyInService, copied.- Untranscribed:
frequencyandbasefreq(the master's BaseFrequency is the deck's),ScanType,Sequence,spectrum(harmonics),Yearly,Daily,Duty(time series),Model,puZideal. - Reader and schema changes of this slice: the reader keeps the circuit name on
Options.circuitand no longer writesbus1=sourcebusinto aNew Circuit's parameters; the schema'sdss_defaults onVsourcecarry the defaults, whichimporter/topology.pytakes throughvsource.with_defaults.Cleardiscards everything before it (the IEEE4 balanced decks build, solve and rebuild).x1r1,x0r0andfrequencyare floats, andpuZ1/puZ0/puZ2are[R, X]arrays likeZ1.
LineCode¶
Mapper: cimhub_opendss/importer/cimtbl/linecode.py (map_linecode). Atoms: tests/atoms/linecode/mtx601.{dss,cimtbl}
(matrix, IEEE13_CDPSM) and seq_3_1_0c.{dss,cimtbl} (sequence, IEEE8500), tested by tests/test_cimtbl_linecode.py.
Identity. mRID = lc_ + name, lowercased (DSS names are case-insensitive). PhaseImpedanceData has no
mRID; its identifier column is <mRID>_<row><column>.
Template (DSS-14, the user's rule 2026-11-21). A LineCode is a template its lines share by name: its impedance
has isTemplate=true, and a WireConfiguration <template>_wc (lc_<name>_wc, or lc_<name>_<unit>_wc per DSS-3)
holds it as PerLengthImpedance, with no WireSpacing. Lines reference that WireConfiguration, not the impedance.
The WireConfiguration is CIM's equivalence route: a configuration with a spacing is geometry, one with only a
PerLengthImpedance is a template LineCode, and one with both is geometry with its equivalent impedance. Exporters
read it through get_line_geometry and get_line_code (cimhub_core.getters.line_impedance). An impedance only one
line uses, the line's own values, is ACLineSegment.PerLengthImpedance with isTemplate=false (Line, below).
Form. A code that sets any of r1 x1 r0 x0 C1 C0 B1 B0 is a sequence code (OpenDSS
Line properties); one that sets rmatrix/xmatrix/cmatrix is a
matrix code. DSS keeps whichever form was set last, and the reader does not record the order, so a code that sets
both raises. So does a code that sets neither (DSS would apply its defaults).
Values. The DSS reader yields floats for most slots (written as repr()), but C1, C0, B1, B0 and
baseFreq as the file's text. One table per header: matrix data per length unit, sequence codes per (length unit,
bch/b0ch source), because a C-derived bch is in nS and a copied B1 in uS.
| Linecode field | type | samples | kind | target |
|---|---|---|---|---|
name |
Union[str, LinecodeName] |
mtx601, mtx602, mtx603 |
copied | PerLengthPhaseImpedance.name, PerLengthSequenceImpedance.name, WireConfiguration.name; mRID = lc_ + name, lowercased; its WireConfiguration's lc_ |
nphases |
Optional[int] |
3, 2 |
copied | PerLengthPhaseImpedance.conductorCount; the matrix order of rmatrix/xmatrix/cmatrix; a 1- or 2-phase sequence code becomes a phase matrix as the engine builds the line (phase_matrix): 1-phase z = Z1, 2-phase Zs = (2 Z1 + Z0)/3 and Zm = (Z0 - Z1)/3 (DSS-4); unset = the engine's default 3 (defaulted) |
r1 |
Optional[float] |
0.769009, 0.3489, 0.535622 |
copied | PerLengthSequenceImpedance.r (ohm/{length}) |
x1 |
Optional[float] |
0.312115, 0.491691, 0.560725 |
copied | PerLengthSequenceImpedance.x (ohm/{length}) |
r0 |
Optional[float] |
1.294322, 0.613107, 0.608571 |
copied | PerLengthSequenceImpedance.r0 (ohm/{length}) |
x0 |
Optional[float] |
0.287695, 1.241561, 1.19452 |
copied | PerLengthSequenceImpedance.x0 (ohm/{length}) |
C1 |
Optional[float] |
154.240283543118, 8.96939698228171, 9.08509466816236 |
derived | PerLengthSequenceImpedance bch = 2 pi baseFreq C1 (b_from_c): nF -> nS |
C0 |
Optional[float] |
154.240283543118, 4.95311934077534, 5.10821052765362 |
derived | PerLengthSequenceImpedance b0ch = 2 pi baseFreq C0 (b_from_c): nF -> nS |
units |
Optional[str] |
mi, km |
mapped | the length unit of every per-length header via LENGTH_UNIT; unset: the unit of the lines that use the code, else the deck's magnitude gate (DSS-3) |
rmatrix |
Union[float, list[float], NoneType] |
[0.3465, 0.1535, 0.3375, 0.158, 0.156..., [0.7526, 0.1535, 0.7475, 0.156, 0.158..., [1.3238, 0.2066, 1.3294] |
structural | PhaseImpedanceData r, one row per lower-triangle element |
xmatrix |
Union[float, list[float], NoneType] |
[1.0179, 0.3849, 1.0478, 0.4236, 0.50..., [1.1814, 0.3849, 1.1983, 0.5017, 0.42..., [1.3569, 0.4591, 1.3471] |
structural | PhaseImpedanceData x, one row per lower-triangle element |
cmatrix |
Union[float, list[float], NoneType] |
[0.0, 0.0, 0.0, 0.0, 0.0, 0.0], [0.0, 0.0, 0.0] |
derived | PhaseImpedanceData b = 2 pi baseFreq C (b_from_c): nF -> nS |
baseFreq |
Optional[float] |
60 |
copied | PerLengthPhaseImpedance.calculatedFrequency (Hz), PerLengthSequenceImpedance.calculatedFrequency (Hz); also the frequency of the derived b; unset with a nonzero C: the deck's base frequency, defaulted (DSS-3b) |
normamps |
Optional[float] |
730.0, 340.0, 230.0 |
untranscribed | catalog ratings have no home on PerLengthImpedance; instance limits or untranscribed (plan D9) |
emergamps |
Optional[float] |
160.0, 310.0, 260.0 |
untranscribed | catalog ratings have no home on PerLengthImpedance; instance limits or untranscribed (plan D9) |
faultrate |
Optional[float] |
0 |
untranscribed | reliability data; no home in the network profile parts |
pctperm |
Optional[float] |
20.0 |
untranscribed | reliability data; no home in the network profile parts |
repair |
Optional[float] |
3 |
untranscribed | reliability data; no home in the network profile parts |
Kron |
Union[bool, Bool, NoneType] |
untranscribed | input of the matrix calculation; no CIM home | |
Rg |
Optional[float] |
untranscribed | Carson earth return per length; home PerLengthImpedance.rg/xg (ohm/ |
|
Xg |
Optional[float] |
untranscribed | Carson earth return per length; home PerLengthImpedance.rg/xg (ohm/ |
|
rho |
Optional[float] |
untranscribed | earth resistivity; home EarthResistivity.rho, an object of its own, not mapped until a deck sets it | |
neutral |
Optional[int] |
untranscribed | input of the matrix calculation; no CIM home | |
B1 |
Optional[float] |
copied | PerLengthSequenceImpedance.bch (uS/{length}); the alternative to C1 |
|
B0 |
Optional[float] |
copied | PerLengthSequenceImpedance.b0ch (uS/{length}); the alternative to C0 |
|
Seasons |
Optional[int] |
untranscribed | catalog ratings have no home on PerLengthImpedance; instance limits or untranscribed (plan D9) | |
Ratings |
Union[float, list[float], NoneType] |
untranscribed | catalog ratings have no home on PerLengthImpedance; instance limits or untranscribed (plan D9) | |
LineType |
Optional[str] |
untranscribed | no home in the network profile parts | |
like |
Optional[str] |
untranscribed | the reader resolves like= before mapping |
Derived. b_from_c(c, f) = 2πfC: C in nF and f in Hz give b in nS. susceptance applies it per value; C = 0
gives b = 0 without a baseFreq (ACEP_PSIL buswork sets none).
Fail fast. A units value with no mapping; a unitless code whose lines give units on some lines only, or a gate
median in no band; both C1 and B1 (or C0 and B0); both forms or neither; B1/B0 on a 1- or 2-phase code; C0 without C1 on a 2-phase code (the engine completes it
with its default C1); a matrix whose length does not fit nphases. A code with no nphases takes the engine's 3
(with_default_phases, noted defaulted: nphases=3). A switch's linecode gives the code no units (DSS-8).
Deck sweep (2026-11-06). 9 of the 24 decks with line codes map and bind. The rest stop on:
| stop | decks | open point |
|---|---|---|
nonzero cmatrix without baseFreq |
ieee9500 (both copies), IEEE8500 and K1 triplex | DSS takes the circuit's default base frequency. Take it from the deck's Circuit/Set DefaultBaseFrequency, else 60 Hz? |
units unset |
IEEE13_original, IEEE123_deconfliction, EPRI M1 and J1 | DSS reads the values per unit of the line's length, so the per-length unit belongs to the instance. Defer the code to the Line mapper, or require units? |
| 1-/2-phase sequence code | EPRI J1 (17 codes) | The engine (J1, 2026-11-06) builds a 1-phase line from Z1 alone (oh_b13552: R = R1, X = X1, C = C1 per length) and a 2-phase line from Zs = (2Z1 + Z0)/3, Zm = (Z0 − Z1)/3 (oh_b41869). The LineCode object itself reports (2Z1 + Z0)/3 for both, so the code alone does not fix the value. Proposal in DSS_REWRITE_PLAN.md (DSS-4) |
| two mRIDs give one UUID | IEEE8500 (lc_1p_#2acsr_#2n vs lc_1p_#2arv_#2n) |
CIM-Profiles bug: the mRID seed drops text up to the last # (CIMTABLES_REQUESTS R10) |
nphases=4 read as 3 |
IEEE13_OCHRE | reader bug: it limits nphases to [1, 3] and substitutes 3, so the 10-value rmatrix no longer fits |
Reader/schema findings (not mapper issues, fixed 2026-11-24): faultrate was typed int, so 0.1 read as 0;
LineType was typed float (DSS values are words such as oh); C1/C0/B1/B0/baseFreq were typed str.
Every slot now has the engine's property type (test_schema_types_match_the_engine), so baseFreq=60 is the float
60.0 and its calculatedFrequency (Hz) cell is 60.0, as every other float cell is written (repr).
Expected differences from the hand translation (CIMTBL-Models/.../IEEE13_CDPSM): it carries the 2011 corrected
off-diagonals; the import keeps the deck's values (mtx601 r21 = 0.1535).
LineCode: units, base frequency, short sequence codes (S2, approved 2026-11-07)¶
S2 lifts three of the fail-fast stops above (the sweep tables below are the pre-S2 record), as decided in DSS_REWRITE_PLAN.md
§6. They are the stops for 16 of the 31 sweep decks.
unitsunset (DSS-3). DSS reads a unitless code per unit of the line's length, so:- (a) a code used by lines that give
unitstakes the line's unit (J1: 1,382 lines, allkft). Lines that disagree give one template per unit,lc_<name>_<unit>. - (b) code and lines both unitless (M1, IEEE123_deconfliction), or a unitless code no line uses (IEEE13_original):
a deck-level magnitude gate on the median positive
r1(orrmatrixdiagonal) of the deck's unitless codes. 0.006 to 10 per unit giveskm; 1e-5 to 0.006 givesm; anything else raises.length_unit=on the importer overrides the gate.
The row comment states the unit's source: # units from its lines: kft (...), # units inferred: km (median r
0.134 per unit over 17 codes; no units on code or line) (M1), or # units given: ... for length_unit=.
Inferred in the sweep: km for M1, IEEE123, IEEE123_deconfliction, IEEE13_original, IEEE37 and J1's 2 unused
codes; J1's 4 used codes take kft from their lines.
Code and line share the unit, so z·length is exact for any label. A wrong label only scales the physical
length. The mapper reads the Lines (their linecode and units) for this; it maps none of them.
- A nonzero C without baseFreq (DSS-3b). b_from_c takes the master's base frequency (Set
defaultbasefreq, else 60 Hz), and the row says # defaulted: baseFreq=60.
- 1- and 2-phase sequence codes (DSS-4; J1, 17 codes). These become a derived PerLengthPhaseImpedance +
PhaseImpedanceData, as the engine builds the line. 1-phase: z = Z1, b from C1. 2-phase: Zs = (2 Z1 + Z0)/3 and
Zm = (Z0 − Z1)/3, the same for C. The function is cimhub_core.derived.sequence.phase_matrix (closed form, not
Carson; a U4 candidate). Atom short_sequence.dss (two J1 codes, one line each): r, x and b equal the engine's
line matrices. A 1-phase row lists the r0/x0/C0 the line does not use; B1/B0 on a short code raises.
- D9: normamps/emergamps stay untranscribed on a LineCode (no home on PerLengthImpedance).
Wire catalogs¶
Mapper: cimhub_opendss/importer/cimtbl/wire.py (map_wires(native, native_class, prefix, fields)). Shape:
wire_info. Atoms: tests/atoms/wire/assets.dss (IEEE13_Assets: Rdc-only ACSR, Rac-only CU, CN_250, TS_1/0)
and metric.dss (one IEEE9500 wire, km/cm), tested by tests/test_cimtbl_wire.py. Approved 2026-11-07, with Rac
filled from Rdc and the TS screen diameter = DiaShield − 2 TapeLayer.
Identity. One file per DSS class (D4): wiredata.cimtbl, cndata.cimtbl, tsdata.cimtbl. mRID = wire_,
cn_ or ts_ + name, lowercased. Each DSS class is its own namespace, so the prefixes keep a WireData and a
CNData of one name apart.
Units. Runits (resistance per length), GMRunits and radunits become header units, values as written. A
cable's dimensions (DiaIns, DiaCable, InsLayer, DiaStrand, DiaShield, TapeLayer) are in radunits.
GmrStrand is in GMRunits and Rstrand in Runits, as DSS states. The mapper writes one table per unit
combination, as LineCode writes one per length unit. IEEE13_Assets gives two tables (kft/in/in and mi/in/in); the
IEEE9500 wires give one (km/cm/cm). An unset selector raises; every wire in the sweep sets all three.
Values the engine fills (DSS-6, in the row comment):
- Rac unset: rAC25 = 1.02 × Rdc, the engine's rule (ac_from_dc; the 9 IEEE4/IEEE13_Assets ACSR wires).
Rdc unset is left unset: the engine only uses Rdc to fill Rac.
- diam: radius = diam / 2 (radius_from_diameter). Setting both radius and diam raises (DSS keeps the
last, which the reader does not record); so does setting neither.
- GMRac unset: raises. The engine would take 0.7788 × radius, but no deck in the sweep omits GMRac.
Cables follow EPRI's ExportCIMXML wherever CIM has no exact twin:
- Rac → rAC25 (DSS gives no temperature) and Rstrand → neutralStrandRDC20 (DSS calls it AC; CIM has only
the one strand resistance). Only rAC25 is written, never the same value copied to rAC50/rAC75.
- CN DiaCable → both diameterOverJacket and diameterOverNeutral: the strands are outermost. CN's
diameterOverScreen is not written; it is derivable and no consumer needs it.
- TS diameterOverScreen = DiaShield − 2 TapeLayer (screen_diameter). DSS measures over the tape; CIM's screen
diameter is the shield's inside.
- EpsR is untranscribed: CableInfo has no permittivity. Every cable in the sweep uses the DSS default, 2.3.
Ratings (approved 2026-11-08). A rated wire's normamps is ratedCurrent, as before. It also becomes an
OperationalLimitSet <mRID>_limits on the new GridAPPS-D AssetInfo.OperationalLimitSet (the serialized side,
so the wire row names its set and the set is written first). The set has two CurrentLimits:
- <mRID>_norm = normamps on olt_normal;
- <mRID>_emerg = emergamps on olt_emergency. An unset emergamps is 1.5 × normamps, the engine's rule
(wire_ratings, # defaulted: emergamps = 1.5 x normamps). An unset normamps with emergamps set is
emergamps / 1.5, also the engine's, written to ratedCurrent and <mRID>_norm (# defaulted: normamps =
emergamps / 1.5).
The two limit types are the master's. An unrated wire gets no set (DSS's 400/600 A defaults are not written).
Seasons/Ratings raise when set, as on a Line. The line mapper uses the same wire_ratings for a geometry
line's first conductor.
Example (wiredata.cimtbl, IEEE13_Assets):
Table OperationalLimitSet: mRID
wire_acsr_1/0_limits
...
Table CurrentLimit: mRID, normalValue (A), OperationalLimitType, OperationalLimitSet
wire_acsr_1/0_norm, 230.0, olt_normal, wire_acsr_1/0_limits
# defaulted: emergamps = 1.5 x normamps
wire_acsr_1/0_emerg, 345.0, olt_emergency, wire_acsr_1/0_limits
...
Table OverheadWireInfo: mRID, name, rDC20 (ohm/kft), rAC25 (ohm/kft), gmr (in), radius (in), ratedCurrent (A), OperationalLimitSet
# defaulted: Rac = 1.02 x Rdc
wire_acsr_1/0, ACSR_1/0, 0.212121212, 0.21636363624000002, 0.05352, 0.199, 230.0, wire_acsr_1/0_limits
...
Fail fast: a unit selector unset; radius and diam both set or neither; GMRac unset; Capradius,
SemiconLayer, Seasons or Ratings set (no deck sets them).
Oracle: every written value equals the engine's property in the engine's units (opendssdirect WireData /
CNData / TSData), including the filled Rac and the normal and emergency ratings, on the vendored IEEE13_Assets and IEEE4 decks
(test_values_match_the_engine).
| Wiredata field | type | samples | kind | target |
|---|---|---|---|---|
name |
Union[str, WiredataName] |
ACSR_1/0, ACSR_4/0, ACSR_556_5 |
copied | OverheadWireInfo.name; mRID = prefix + name, lowercased |
Rdc |
Optional[float] |
0.212121212, 0.112121212, 0.035227273 |
copied | OverheadWireInfo.rDC20 (ohm/{r_length}); DC resistance (DSS gives no temperature) |
Rac |
Optional[float] |
0.607, 1.010411, 0.939016 |
copied | OverheadWireInfo.rAC25 (ohm/{r_length}); DSS: resistance at 60 Hz, temperature unstated; rAC25 as in EPRI's ExportCIMXML. Unset: 1.02 x Rdc, the engine's rule (ac_from_dc), with a defaulted comment |
Runits |
Optional[str] |
kft, mi, km |
mapped | the unit of Rdc, Rac in the header (LENGTH_UNIT); unset raises (every wire in the sweep sets it) |
GMRac |
Optional[float] |
0.05352, 0.09768, 0.3732 |
copied | OverheadWireInfo.gmr ({gmr_length}); unset raises (the engine's 0.7788 x radius default; no deck in the sweep omits it) |
GMRunits |
Optional[str] |
in, cm, ft |
mapped | the unit of GMRac in the header (LENGTH_UNIT); unset raises (every wire in the sweep sets it) |
radius |
Optional[float] |
0.40132, 0.39624, 0.37084 |
copied | OverheadWireInfo.radius ({radius_length}); one of radius and diam; both raise (DSS keeps the last, the reader does not record which), neither raises |
radunits |
Optional[str] |
in, cm |
mapped | the unit of radius, diam and every cable dimension in the header (LENGTH_UNIT); unset raises (every wire in the sweep sets it) |
normamps |
Optional[float] |
230.0, 340.0, 730.0 |
copied | OverheadWireInfo.ratedCurrent (A); also the normal CurrentLimit of the wire's OperationalLimitSet |
emergamps |
Optional[float] |
200.0, 239.0, 172.0 |
structural | the emergency CurrentLimit of the wire's OperationalLimitSet |
diam |
Optional[float] |
0.398, 0.563, 0.927 |
derived | radius = diam / 2 (radius_from_diameter) |
Seasons |
Optional[int] |
structural | raises when set: no deck in the sweep sets it, so a mapping waits for one (an indexed rating array that names no calendar season; home OperationalLimitType.season) | |
Ratings |
Union[float, list[float], NoneType] |
structural | raises when set: no deck in the sweep sets it, so a mapping waits for one (with Seasons) | |
Capradius |
Optional[float] |
structural | raises when set: no deck in the sweep sets it, so a mapping waits for one (the radius for capacitance; not WireInfo.coreRadius) | |
like |
Optional[str] |
untranscribed | the reader resolves like= before mapping |
| Cndata field | type | samples | kind | target |
|---|---|---|---|---|
name |
Union[str, CndataName] |
CN_250, 1/0_Al_15kV_1/3 |
copied | ConcentricNeutralCableInfo.name; mRID = prefix + name, lowercased |
k |
Optional[int] |
13, 6 |
copied | ConcentricNeutralCableInfo.neutralStrandCount |
DiaStrand |
Optional[float] |
0.0641, 0.064 |
derived | neutralStrandRadius = DiaStrand / 2 (radius_from_diameter), radunits |
GmrStrand |
Optional[float] |
0.02496 |
copied | ConcentricNeutralCableInfo.neutralStrandGmr ({gmr_length}); in GMRunits, as DSS says |
Rstrand |
Optional[float] |
14.8722, 2.55 |
copied | ConcentricNeutralCableInfo.neutralStrandRDC20 (ohm/{r_length}); DSS calls it the strand's AC resistance; neutralStrandRDC20 as in ExportCIMXML, CIM's only strand resistance |
SemiconLayer |
Union[bool, Bool, NoneType] |
structural | raises when set: no deck in the sweep sets it, so a mapping waits for one | |
EpsR |
Optional[float] |
2.3 |
untranscribed | insulation relative permittivity; no home on CableInfo (InsulationInfo has a material, not a permittivity). DSS default 2.3, which every cable in the sweep uses |
InsLayer |
Optional[float] |
0.22, 0.445 |
copied | ConcentricNeutralCableInfo.insulationThickness ({radius_length}) |
DiaIns |
Optional[float] |
1.06, 2.11 |
copied | ConcentricNeutralCableInfo.diameterOverInsulation ({radius_length}) |
DiaCable |
Optional[float] |
1.29, 2.74 |
copied | ConcentricNeutralCableInfo.diameterOverJacket ({radius_length}), ConcentricNeutralCableInfo.diameterOverNeutral ({radius_length}); the outer diameter; a CN cable has no jacket over its strands, so it is also the diameter over the neutral (ExportCIMXML) |
Rdc |
Optional[float] |
copied | ConcentricNeutralCableInfo.rDC20 (ohm/{r_length}); DC resistance (DSS gives no temperature) |
|
Rac |
Optional[float] |
0.41, 0.603 |
copied | ConcentricNeutralCableInfo.rAC25 (ohm/{r_length}); DSS: resistance at 60 Hz, temperature unstated; rAC25 as in EPRI's ExportCIMXML. Unset: 1.02 x Rdc, the engine's rule (ac_from_dc), with a defaulted comment |
Runits |
Optional[str] |
mi, km |
mapped | the unit of Rdc, Rac, Rstrand in the header (LENGTH_UNIT); unset raises (every wire in the sweep sets it) |
GMRac |
Optional[float] |
0.2052, 0.338 |
copied | ConcentricNeutralCableInfo.gmr ({gmr_length}); unset raises (the engine's 0.7788 x radius default; no deck in the sweep omits it) |
GMRunits |
Optional[str] |
in, cm |
mapped | the unit of GMRac, GmrStrand in the header (LENGTH_UNIT); unset raises (every wire in the sweep sets it) |
radius |
Optional[float] |
copied | ConcentricNeutralCableInfo.radius ({radius_length}); one of radius and diam; both raise (DSS keeps the last, the reader does not record which), neither raises |
|
radunits |
Optional[str] |
in, cm |
mapped | the unit of radius, diam and every cable dimension in the header (LENGTH_UNIT); unset raises (every wire in the sweep sets it) |
normamps |
Optional[float] |
260.0 |
copied | ConcentricNeutralCableInfo.ratedCurrent (A); also the normal CurrentLimit of the wire's OperationalLimitSet |
emergamps |
Optional[float] |
structural | the emergency CurrentLimit of the wire's OperationalLimitSet |
|
diam |
Optional[float] |
0.567, 0.935 |
derived | radius = diam / 2 (radius_from_diameter) |
Seasons |
Optional[int] |
structural | raises when set: no deck in the sweep sets it, so a mapping waits for one (an indexed rating array that names no calendar season; home OperationalLimitType.season) | |
Ratings |
Union[float, list[float], NoneType] |
structural | raises when set: no deck in the sweep sets it, so a mapping waits for one (with Seasons) | |
Capradius |
Optional[float] |
structural | raises when set: no deck in the sweep sets it, so a mapping waits for one (the radius for capacitance; not WireInfo.coreRadius) | |
like |
Optional[str] |
untranscribed | the reader resolves like= before mapping |
| Tsdata field | type | samples | kind | target |
|---|---|---|---|---|
name |
Union[str, TsdataName] |
TS_1/0 |
copied | TapeShieldCableInfo.name; mRID = prefix + name, lowercased |
DiaShield |
Optional[float] |
0.88 |
derived | diameterOverScreen = DiaShield - 2 TapeLayer (screen_diameter): DSS measures over the tape, CIM's screen diameter is the shield's inside (ExportCIMXML) |
TapeLayer |
Optional[float] |
0.005 |
copied | TapeShieldCableInfo.tapeThickness ({radius_length}) |
TapeLap |
Optional[float] |
20.0 |
copied | TapeShieldCableInfo.tapeLap (percent) |
EpsR |
Optional[float] |
2.3 |
untranscribed | insulation relative permittivity; no home on CableInfo (InsulationInfo has a material, not a permittivity). DSS default 2.3, which every cable in the sweep uses |
InsLayer |
Optional[float] |
0.22 |
copied | TapeShieldCableInfo.insulationThickness ({radius_length}) |
DiaIns |
Optional[float] |
0.82 |
copied | TapeShieldCableInfo.diameterOverInsulation ({radius_length}) |
DiaCable |
Optional[float] |
1.06 |
copied | TapeShieldCableInfo.diameterOverJacket ({radius_length}); the outer diameter |
Rdc |
Optional[float] |
copied | TapeShieldCableInfo.rDC20 (ohm/{r_length}); DC resistance (DSS gives no temperature) |
|
Rac |
Optional[float] |
0.97 |
copied | TapeShieldCableInfo.rAC25 (ohm/{r_length}); DSS: resistance at 60 Hz, temperature unstated; rAC25 as in EPRI's ExportCIMXML. Unset: 1.02 x Rdc, the engine's rule (ac_from_dc), with a defaulted comment |
Runits |
Optional[str] |
mi |
mapped | the unit of Rdc, Rac in the header (LENGTH_UNIT); unset raises (every wire in the sweep sets it) |
GMRac |
Optional[float] |
0.1332 |
copied | TapeShieldCableInfo.gmr ({gmr_length}); unset raises (the engine's 0.7788 x radius default; no deck in the sweep omits it) |
GMRunits |
Optional[str] |
in |
mapped | the unit of GMRac in the header (LENGTH_UNIT); unset raises (every wire in the sweep sets it) |
radius |
Optional[float] |
copied | TapeShieldCableInfo.radius ({radius_length}); one of radius and diam; both raise (DSS keeps the last, the reader does not record which), neither raises |
|
radunits |
Optional[str] |
in |
mapped | the unit of radius, diam and every cable dimension in the header (LENGTH_UNIT); unset raises (every wire in the sweep sets it) |
normamps |
Optional[float] |
165.0 |
copied | TapeShieldCableInfo.ratedCurrent (A); also the normal CurrentLimit of the wire's OperationalLimitSet |
emergamps |
Optional[float] |
structural | the emergency CurrentLimit of the wire's OperationalLimitSet |
|
diam |
Optional[float] |
0.368 |
derived | radius = diam / 2 (radius_from_diameter) |
Seasons |
Optional[int] |
structural | raises when set: no deck in the sweep sets it, so a mapping waits for one (an indexed rating array that names no calendar season; home OperationalLimitType.season) | |
Ratings |
Union[float, list[float], NoneType] |
structural | raises when set: no deck in the sweep sets it, so a mapping waits for one (with Seasons) | |
Capradius |
Optional[float] |
structural | raises when set: no deck in the sweep sets it, so a mapping waits for one (the radius for capacitance; not WireInfo.coreRadius) | |
like |
Optional[str] |
untranscribed | the reader resolves like= before mapping |
LineSpacing and LineGeometry¶
Mapper: cimhub_opendss/importer/cimtbl/geometry.py (map_linespacing, map_linegeometry). Shape:
line_by_wire_configuration. Geometry stays geometry: no impedance is computed (the conductor-geometry skill).
Atom: tests/atoms/geometry/assets.dss from IEEE13_Assets: spacing 500 with geometry 601 (the spacing=
form), 606 (inline CN positions) and 607 (inline: a TS phase and a bare CU neutral), tested by
tests/test_cimtbl_geometry.py. Approved 2026-11-07.
LineSpacing → linespacing.cimtbl. An XYSpacing spc_<name> (isTemplate=true) and one
XYConductorPosition per conductor: sequenceNumber 1..nconds, xCoord/yCoord from x/h in the
spacing's units, and kind phase for 1..nphases, neutral after (DSS's convention). detailed=Yes is the
engine default (LineSpacing.pas:213 sets FEquivalentSpacing := not detailed, FALSE by default at :327) and maps the
positions as usual. The equivalent-spacing form, detailed=No, has no positions and raises, and so does
EqDistPhPh, EqDistPhN, AvgPhaseHeight or AvgNeutralHeight set at any value: it takes every phase-phase and
neutral-neutral distance from EqDistPhPh, every phase-neutral one from EqDistPhN, and the image distances from
2 x AvgPhaseHeight, 2 x AvgNeutralHeight or their sum for a phase-neutral pair (LineConstants.pas:218-297), which no
set of XY positions reproduces in general (M19, decision 10, 2026-11-27; rc_2 had detailed inverted). No deck uses
it, and opendssdirect 0.9.4 does not know these slots, so the tests check the mapper alone.
LineGeometry → linegeometry.cimtbl. A WireConfiguration wc_<name> (numberOfPhases = nphases) and one
WireSequenceConfiguration per conductor, naming its WireInfo. Its WireSpacing is:
- spacing= → spc_<spacing> from linespacing.cimtbl.
- inline positions (cond=1 x=.. h=..) → a synthesized XYSpacing wc_<name>_spc in linegeometry.cimtbl, under
# synthesized, built like a LineSpacing.
Conductor names. The reader gives them in cond order in one of wires, cncables, tscables. A mixed
assembly (607) arrives whole in wires, so the array says nothing about the kind. Each name must therefore be in
exactly one of WireData, CNData and TSData; a name in two raises.
Example (linegeometry.cimtbl, 607):
# synthesized: the inline positions of LineGeometry 607
Object XYSpacing: mRID=wc_607_spc, name=607, isTemplate=true
Table XYConductorPosition: mRID, XYSpacing=wc_607_spc, sequenceNumber, xCoord (ft), yCoord (ft), kind
wc_607_spc_1, 1, 0.0, -4.0, phase
wc_607_spc_2, 2, 0.25, -4.0, neutral
# untranscribed: reduce=true
Object WireConfiguration: mRID=wc_607, name=607, numberOfPhases=1, WireSpacing=wc_607_spc
Table WireSequenceConfiguration: mRID, WireConfiguration=wc_607, sequenceNumber, WireInfo
wc_607_1, 1, ts_ts_1/0
wc_607_2, 2, wire_cu_1/0
Earth. linegeometry.cimtbl opens with the deck's one EarthResistivity earth (Set earthmodel and the
geometry lines' rho), which every WireConfiguration names. A deck without geometry that sets earthmodel still
gets it, floating (no line names it), so the export can write the setting back; a deck with neither gets none
(S6g below).
Untranscribed: reduce (Kron reduction is the consumer's choice from the segment's phases; 242 of 243 set
it), ratings (D9), LineType.
Reader fix: the reader kept the last units of the cond= blocks, so conductors in different units were
misread. It now raises when the blocks disagree; a block without units takes the last given, else DSS's initial
ft. No deck mixes units (engine-checked).
Fail fast: two name arrays; a name count or position count other than nconds; spacing= together with
inline positions; inline positions without units; a name in no catalog or in two; the scalar cond/wire/x/h
without the arrays.
Oracle: for every geometry the conductor names, coordinates and phase count equal the engine's
(LineGeometries.Conductors/Xcoords/Ycoords/Phases; test_geometries_match_the_engine on the vendored
IEEE13_Assets and IEEE4 decks). Checked by hand 2026-11-07, all match: IEEE9500 balanced 70 (both copies), YYD 3.
| Linespacing field | type | samples | kind | target |
|---|---|---|---|---|
name |
Union[str, LinespacingName] |
500, 505, 510 |
copied | XYSpacing.name; mRID = spc_ + name, lowercased; isTemplate = true |
nconds |
Optional[int] |
4, 3, 2 |
structural | one XYConductorPosition per conductor, sequenceNumber 1..nconds; x and h must have nconds values |
nphases |
Optional[int] |
3, 2, 1 |
structural | kind: phase for conductors 1..nphases, neutral after |
x |
Union[float, list[float], NoneType] |
[-4.0, -1.0, 3.0, 0.0], [-4.0, 3.0, 0.0], [0.5, 0.0] |
structural | XYConductorPosition.xCoord ({length}), one per conductor |
h |
Union[float, list[float], NoneType] |
[28.0, 28.0, 28.0, 24.0], [28.0, 28.0, 24.0], [29.0, 24.0] |
structural | XYConductorPosition.yCoord ({length}), one per conductor |
units |
Optional[str] |
ft |
mapped | the length unit of xCoord and yCoord (LENGTH_UNIT); unset raises |
detailed |
Union[bool, Bool, NoneType] |
structural | Yes (the default, LineSpacing.pas:213, :327) maps the positions; No (the equivalent-spacing form) raises: it has no positions | |
EqDistPhPh |
Optional[str] |
structural | raises when set, at any value: detailed=No takes phase-phase and neutral-neutral distances from EqDistPhPh, phase-neutral ones from EqDistPhN and the image distances from 2 x AvgPhaseHeight, 2 x AvgNeutralHeight or their sum (LineConstants.pas:218-297), which no XY positions reproduce in general | |
EqDistPhN |
Optional[str] |
structural | raises when set, at any value: detailed=No takes phase-phase and neutral-neutral distances from EqDistPhPh, phase-neutral ones from EqDistPhN and the image distances from 2 x AvgPhaseHeight, 2 x AvgNeutralHeight or their sum (LineConstants.pas:218-297), which no XY positions reproduce in general | |
AvgPhaseHeight |
Optional[str] |
structural | raises when set, at any value: detailed=No takes phase-phase and neutral-neutral distances from EqDistPhPh, phase-neutral ones from EqDistPhN and the image distances from 2 x AvgPhaseHeight, 2 x AvgNeutralHeight or their sum (LineConstants.pas:218-297), which no XY positions reproduce in general | |
AvgNeutralHeight |
Optional[str] |
structural | raises when set, at any value: detailed=No takes phase-phase and neutral-neutral distances from EqDistPhPh, phase-neutral ones from EqDistPhN and the image distances from 2 x AvgPhaseHeight, 2 x AvgNeutralHeight or their sum (LineConstants.pas:218-297), which no XY positions reproduce in general | |
like |
Optional[str] |
untranscribed | the reader resolves like= before mapping |
| Linegeometry field | type | samples | kind | target |
|---|---|---|---|---|
name |
Union[str, LinegeometryName] |
601, 602, 603 |
copied | WireConfiguration.name; mRID = wc_ + name, lowercased |
nconds |
Optional[int] |
4, 3, 2 |
structural | one WireSequenceConfiguration per conductor, sequenceNumber 1..nconds; the conductor names and (inline) positions must have nconds values |
nphases |
Optional[int] |
3, 2, 1 |
copied | WireConfiguration.numberOfPhases; also the kind of an inline position: phase for 1..nphases, neutral after |
cond |
Optional[int] |
3, 2, 1 |
structural | the reader folds the cond= blocks into the arrays; set alone (no cond=) it raises |
wire |
Optional[str] |
CU_1/0, 2_ACSR, 1/0_TPX |
structural | the reader folds the cond= blocks into the arrays; set alone (no cond=) it raises |
x |
Optional[float] |
0.5, 0.25, 0.1524 |
structural | the reader folds the cond= blocks into the arrays; set alone (no cond=) it raises |
h |
Optional[float] |
-4.0, 8.2296, -1.22 |
structural | the reader folds the cond= blocks into the arrays; set alone (no cond=) it raises |
units |
Optional[str] |
ft, m |
mapped | the length unit of the inline positions (LENGTH_UNIT); unset raises. The reader raises when the cond= blocks give different units |
normamps |
Optional[float] |
untranscribed | no home on a WireConfiguration; instance limits or untranscribed (plan D9) | |
emergamps |
Optional[float] |
untranscribed | no home on a WireConfiguration; instance limits or untranscribed (plan D9) | |
reduce |
Union[bool, Bool, NoneType] |
True |
untranscribed | Kron reduction of the neutrals; a solver choice the consumer makes from the segment's phases |
spacing |
Optional[str] |
500, 505, 510 |
structural | WireConfiguration.WireSpacing = spc_ + spacing; with inline positions it raises |
wires |
Union[str, list[str], NoneType] |
['ACSR_556_5', 'ACSR_556_5', 'ACSR_55..., ['ACSR_4/0', 'ACSR_4/0', 'ACSR_4/0', ..., ['ACSR_1/0', 'ACSR_1/0', 'ACSR_1/0'] |
structural | the conductor names in cond order; each resolves to exactly one of WireData, CNData, TSData (a name in two raises) and is the WireSequenceConfiguration.WireInfo. A mixed assembly (607: a TS phase, a bare neutral) arrives here whole, so the array carries no kind |
cncable |
Optional[str] |
CN_250, 1/0_Al_15kV_1/3 |
structural | the reader folds the cond= blocks into the arrays; set alone (no cond=) it raises |
tscable |
Optional[str] |
TS_1/0 |
structural | the reader folds the cond= blocks into the arrays; set alone (no cond=) it raises |
cncables |
Union[str, list[str], NoneType] |
['CN_250', 'CN_250', 'CN_250'], ['1/0_Al_15kV_1/3'], ['1/0_Al_15kV_1/3', '1/0_Al_15kV_1/3'... |
structural | as wires; only one of wires, cncables, tscables may be set |
tscables |
Union[str, list[str], NoneType] |
structural | as wires; only one of wires, cncables, tscables may be set | |
xs |
Union[float, list[float], NoneType] |
[-0.5, 0.0, 0.5], [0.0, 0.25], [-0.1524, 0.1524] |
structural | inline positions: a synthesized XYSpacing wc_ |
hs |
Union[float, list[float], NoneType] |
[-4.0, -4.0, -4.0], [-4.0, -4.0], [10.5156, 8.2296] |
structural | inline positions: the synthesized XYSpacing's yCoord ({length}) |
Seasons |
Optional[int] |
untranscribed | no home on a WireConfiguration; instance limits or untranscribed (plan D9) | |
Ratings |
Union[float, list[float], NoneType] |
untranscribed | no home on a WireConfiguration; instance limits or untranscribed (plan D9) | |
LineType |
Optional[str] |
untranscribed | no home on a WireConfiguration | |
conductors |
Union[str, list[str], NoneType] |
structural | raises when set: no deck in the sweep sets it, so a mapping waits for one | |
like |
Optional[str] |
603 |
untranscribed | the reader resolves like= before mapping |
XfmrCode (S3b, approved and done 2026-11-08)¶
Mapper: cimhub_opendss/importer/cimtbl/xfmrcode.py (map_xfmrcode(native, buses)). Artifact xfmrcode.cimtbl,
after the line codes; the instances stay in transformer.cimtbl. Atom tests/atoms/xfmrcode/codes.dss:
- ct25: a center tap with two instances on a 3-phase system;
- sub: 3-phase delta-wye;
- yyd: 1-phase Y-Y-D, three cans;
- unused: no instance uses it.
Goldens codes.cimtbl and codes_transformer.cimtbl, tested by tests/test_cimtbl_xfmrcode.py. U2 is closed
(2026-11-08).
Result. 25 of 31 sweep decks bind with every S3 part (the S3a stops only). The center-tap templates are 9 in
IEEE8500 (1,177 instances), 9 in each IEEE9500 copy, 3 in IEEE123_PV and 1 in IEEE13_CDPSM (Tpoletop).
IEEE13_Assets has 2 TankEnd templates, IEEE4 YYD has 1. Every template's winding kV, kVA, %R and mesh x equal the
engine's for each instance, on the atom and the engine decks (IEEE13_CDPSM, IEEE13_Assets, IEEE8500, IEEE9500).
Multi-can tank templating and lug sequencing across a bank wait until CYME's form is seen; the CIM template class
is then updated to match (user, 2026-11-08).
Template forms (the user's model, 2026-11-08; settles D10 and amends DSS-2's "lug to lug" for every code).
Census (the instances that wait for S3b, counting duplicate deck copies):
| code kind | instances | form |
|---|---|---|
| center tap: 1-phase, 3 windings, secondary halves equal (7.2/0.12/0.12, 2.4/0.12/0.12, ...) | 8,828 (IEEE8500, IEEE9500, IEEE123_PV, IEEE13_OCHRE, IEEE13_CDPSM CT5) |
lugs |
| 1-phase, 3 windings Y-Y-D (IEEE4 YYD, 39.83/7.62/2.4 kV) | 3 | lugs (S3b-3; TankEnd before) |
| 3-phase, 2 windings | 3 | TankEnd |
| 1-phase, 2 windings | none outside the regulators (mapped in S3a) | lugs (S3b-3) |
Every center-tap instance has the split-phase secondary bus2.1.0 + bus2.0.2 and a line-to-neutral primary on
one node. No instance overrides its code's values, except ppm_antifloat (untranscribed).
- TankEnd template (3-phase only, S3b-3):
TransformerTankConfigurationxc_<code>. Each DSS winding gives: - a
TransformerTankEndxc_<code>_end_<n>(endNumber,connectionKind,rground/xgroundfromRneut/Xneut; no phases); - a
TransformerWindingxc_<code>_wdg_<n>(FromTransformerEnd= its tank end), withratedU(LL),baseU(the coil),ratedS,baseS(per phase on a 3-phase code) andr.
The mesh between windings carries x. The instance's PowerTransformerEnd n is template end n
(endNumber); it carries the node, phases and grounded. Shapes: transformer_template,
transformer_by_template (xf_t1).
- Lug template (every 1-phase code, S3b-3). Any code but a center tap has two lugs per winding, H1 H2, X1 X2,
Y1 Y2 (IEEE C57.12.70), numbered in each coil's node order (its direction) over the instance's phase ends,
end 1 first, so a 2-winding code's are 1-4 and IEEE4 YYD's 1-6; windings H1→H2, X1→X2, Y1→Y2, baseS each its
own kVA. A center tap is a 3-winding tank, as CIMTBL-Models
distribution/templates/polemount_1ph_50kva_7200_12470y.cimtbl:
- TransformerLugs H1, H2, X1, X3, X2 (sequenceNumber 1-5: the instance phase end each lands on, below);
- windings lug to lug from the polarity end: H1→H2, X1→X2 (DSS winding 2, bus2.1.0: s1→N) and X2→X3 (winding
3, bus2.0.2: N→s2);
- designation per IEEE C57.12.70 (the profile's text). X1 is the low-side terminal in phase with H1 under
either polarity, so s1 (in phase with the primary) is X1 and s2 (at 180°) is X3. Additive polarity (X3, X2,
X1: 1-phase, 200 kVA or less, 8,660 V or less) against subtractive (X1, X2, X3) only says where X1 sits on
the tank, so the model is the same for both (confirmed by the user, 2026-11-08). Y designations belong to
a true 3-winding unit's tertiary (IEEE4 YYD).
The instance has a PowerTransformerEnd per bus (end 1: the primary node and phases; end 2: s1s2N) and, as the
inline 1-phase mapper already does, a TransformerPhaseEnd per phase of each end's terminal, not per lug:
sequenceNumber unique in the transformer, end 1 first, in terminal phase order, neutral last. A lug's
sequenceNumber names the phase end it lands on, so several lugs may share one: three bussed center-tap cans
on bus2.1.2.3.0 are 4 phase ends for 12 lugs. Each DSS Transformer is its own PowerTransformer with one tank
(DSS-2), so here the numbers line up one to one:
- end 1 BN (line to neutral, DSS's default node 0) or AB (line to line) is 1, 2, which H1 and H2 land on;
- end 2 s1s2N is s1 = 3, s2 = 4, N = 5, which X1, X3, X2 land on.
The template's lug numbers are therefore those of a one-tank instance. A bank of tanks on one PowerTransformer
needs a configuration per tank position (CIMTBL-Models bank_oyod_50_50_7200_12470y.cimtbl), which no DSS deck
produces. An instance whose secondary is not bus2.1.0 + bus2.0.2 raises. Shapes:
transformer_template_1ph and transformer_by_template (xf_t2), rewritten from today's phase-end template to
this lug pattern.
Values.
- ratedU is the nameplate: phase to phase. A coil's voltage alone does not fix it, because 7.2 kV is
7200/12470Y on a 3-phase system and 7200 on a single-phase one. So it comes from the bus system its instances
sit on (the S3a rule: × √3 for a phase-to-neutral coil on a 3-phase system, × 2 for a split-phase half), and
instances that disagree raise.
- The rest: baseU = the code's kV, the coil. baseS = winding 1's kVA on every coil. A split-phase half has
ratedS = kVA / 2. r = %Rs per winding (or %loadloss / 2 on windings 1 and 2). The mesh 1-2, 1-3, 2-3
x = Xhl, Xht, Xlt in percent on the From winding's baseU and baseS. %imag and %noloadloss go on the
configuration.
- Defaults (DSS-6, dss_default on XfmrCode): conns wye, %Rs 0.2, Xhl/Xht/Xlt 7/35/30.
Instances (transformer.cimtbl): PowerTransformer xf_<name>, plus TransformerTank xf_<name>_tank with
TankConfiguration = xc_<code>, plus the ends above. A lug template's instance phase ends reference their end's
generated Terminal (xf_<name>_T<n>), which is their link to the PowerTransformer, since the instance has no
windings. Amended 2026-11-09 (DSS S6c, T3): a 1-phase instance of a TankEnd template gets them too, numbered in
its coil's node order, end 1 first (since S3b-3 every 1-phase code is a lug template, whose lugs are numbered so). That order is the coil's direction, which a PhaseCode cannot hold. Without it,
IEEE4 YYD's tert.3.1 came back tert.1.3, and in the engine the 3-can bank's voltages moved by 1.6 kV. A code no unregulated instance uses is not written; the file's comment names it. An instance that sets a slot its code also sets raises
(the template must be the one source), except the untranscribed ones. A regulated instance keeps S3a's rule: it
takes its code's values, because CIM has no AutoTransformer template.
Fail fast: a code of other than 1 or 3 phases; windings other than 2 or 3; Rneut on a 1-phase code; a mesh From winding rated other than winding 1; a tap other than 1 on an
unregulated code; a center-tap code with an
instance that is not a split-phase secondary; instances of one code on different bus systems; Seasons without
Ratings, or a Ratings count other than Seasons (see the Transformer section).
DC resistance and seasonal ratings (2026-11-24). Atom tests/atoms/xfmrcode/rated.dss (code sub with
each winding's RdcOhms and Seasons=2 Ratings=[22000 25000]), golden rated.cimtbl,
test_rated_code_matches_golden_and_binds:
- RdcOhms is copied verbatim to each template winding, Update Table TransformerWinding: mRID, rDC (ohm), only
when set.
- Ratings are the template's own OperationalLimitSet xc_<code>_ratings, written alone (no Equipment), with
one ApparentPowerLimit xc_<code>_ratings_<n> (kVA) of type olt_season<n> per season. The template names it
with Update Table TransformerTankConfiguration: mRID, OperationalLimitSet
(EquipmentConfiguration.OperationalLimitSet, a GridAPPS-D extension of the profile). An instance does not
inherit the set: it gets only
its own ratings, and one that sets Ratings or Seasons its code also sets raises (the one-source rule above).
Engine checks: each template's ratings, r and x against the engine's transformer of each instance.
Decisions (approved 2026-11-08): - S3b-1: AutoTrans stays unmapped until a deck has one; the master's not-mapped count is the signal. - S3b-2: the Y-Y-D 1-phase 3-winding code (IEEE4 YYD) is a TankEnd template (3 tank ends, D on the third). Superseded by S3b-3. - S3b-3 (the user's, 2026-11-19, via clallam_cim request 10): "TransformerTankEnd is only for three-phase templates, single-phase should use TransformerPhaseEnd / TransformerLug." Every 1-phase code is a lug template (above), the instance's phase ends unchanged; a 2-phase code raises (no deck has one). The engine checks are unchanged.
| Xfmrcode field | type | samples | kind | target |
|---|---|---|---|---|
name |
Union[str, XfmrcodeName] |
CT5, FdrXfmr, RegLeg |
copied | TransformerTankConfiguration.name; mRID = xc_ + name, lowercased |
phases |
Optional[int] |
1, 3 |
structural | 3: TankEnd template; 1: lug template (a center tap's H1 H2 X1 X3 X2, else two lugs per winding) |
windings |
Optional[int] |
3, 2 |
structural | one TransformerWinding each; 2 or 3 |
wdg |
Optional[int] |
structural | the winding Rneut/Xneut belong to (the reader's tag); none = the last | |
conn |
Union[str, ForwardRef('ConnectionType'), NoneType] |
structural | the active-winding form; the reader folds wdg= blocks and bare values into the arrays | |
kV |
Optional[float] |
structural | the active-winding form; the reader folds wdg= blocks and bare values into the arrays | |
kVA |
Optional[float] |
structural | the active-winding form; the reader folds wdg= blocks and bare values into the arrays | |
tap |
Optional[float] |
structural | the active-winding form; the reader folds wdg= blocks and bare values into the arrays | |
pct_R |
Optional[float] |
structural | the active-winding form; the reader folds wdg= blocks and bare values into the arrays | |
Rneut |
Optional[float] |
structural | TankEnd rground (ohm) of its winding when >= 0; on a 1-phase code raises | |
Xneut |
Optional[float] |
structural | TankEnd xground (ohm) of its winding, with Rneut >= 0 | |
conns |
Union[str, ForwardRef('ConnectionType'), list[Union[str, ForwardRef('ConnectionType')]], NoneType] |
[ConnectionType(text='wye', descripti..., [ConnectionType(text='delta', descrip... |
structural | TankEnd connectionKind (D, Y; grounding is the instance's); a center tap's secondary halves are I; default wye |
kVs |
Union[float, list[float], NoneType] |
[2.4, 0.12, 0.12], [4.16, 0.48], [2.4, 2.4] |
structural | winding baseU (the coil); ratedU phase-to-phase from the instances' common bus system (x sqrt 3 on a 3-phase system, x 2 for a split-phase half), and instances that disagree raise |
kVAs |
Union[float, list[float], NoneType] |
[5.0, 5.0, 5.0], [500.0, 500.0], [1666.0, 1666.0] |
structural | winding ratedS (a split-phase half: kVA / 2); baseS = winding 1's kVA on every coil (per phase on a 3-phase code) |
taps |
Union[float, list[float], NoneType] |
structural | a tap other than 1 raises (a fixed tap is not mapped yet) | |
Xhl |
Optional[float] |
2.04, 2.0, 0.01 |
structural | mesh 1-2 x (percent on the From winding's baseU and baseS); default 7 |
Xht |
Optional[float] |
2.04, 1.632, 36.0 |
structural | mesh 1-3 x; default 35 |
Xlt |
Optional[float] |
1.36, 1.088, 28.0 |
structural | mesh 2-3 x; default 30 |
Xscarray |
Union[float, list[float], NoneType] |
untranscribed | for more than 3 windings, which raise | |
thermal |
Optional[float] |
untranscribed | thermal model; no home in the network profile parts | |
n |
Optional[float] |
untranscribed | thermal model; no home in the network profile parts | |
m |
Optional[float] |
untranscribed | thermal model; no home in the network profile parts | |
flrise |
Optional[float] |
untranscribed | thermal model; no home in the network profile parts | |
hsrise |
Optional[float] |
untranscribed | thermal model; no home in the network profile parts | |
pct_loadloss |
Optional[float] |
0.01, 1.1 |
derived | when pct_Rs is unset, r = loadloss / 2 on windings 1 and 2; set with pct_Rs, the two must agree |
pct_noloadloss |
Optional[float] |
0.2, 0.6 |
derived | TransformerTankConfiguration.noLoadLoss (kW) = % x winding 1 kVA |
normhkVA |
Optional[float] |
untranscribed | a tank rating; instance OperationalLimitSet or untranscribed | |
emerghkVA |
Optional[float] |
untranscribed | a tank rating; instance OperationalLimitSet or untranscribed | |
MaxTap |
Optional[float] |
1.1 |
untranscribed | tap changer range; a regulated instance takes it (S3a); else untranscribed |
MinTap |
Optional[float] |
0.9 |
untranscribed | tap changer range; a regulated instance takes it (S3a); else untranscribed |
NumTaps |
Optional[int] |
untranscribed | tap changer range; a regulated instance takes it (S3a); else untranscribed | |
pct_imag |
Optional[float] |
0.5, 1.1 |
copied | TransformerTankConfiguration.percentMagnetizingCurrent (percent) |
ppm_antifloat |
Optional[float] |
untranscribed | numerical aid of the DSS solver | |
pct_Rs |
Union[float, list[float], NoneType] |
[0.6, 1.2, 1.2], [0.55, 0.55], [0.0005, 0.0005] |
structural | winding r (percent on its own baseS); default 0.2 |
X12 |
Optional[float] |
structural | alias of Xhl | |
X13 |
Optional[float] |
structural | alias of Xht | |
X23 |
Optional[float] |
structural | alias of Xlt | |
RdcOhms |
Union[float, list[float], NoneType] |
copied | TransformerWinding.rDC (ohm); per template winding |
|
Seasons |
Optional[int] |
structural | the number of Ratings; one by default, and a count other than the Ratings' raises | |
Ratings |
Union[float, list[float], NoneType] |
copied | ApparentPowerLimit.normalValue (kVA); one per season n, of type olt_season |
|
like |
Optional[str] |
untranscribed | the reader resolves like= before mapping |
Transformer¶
Mapper: cimhub_opendss/importer/cimtbl/transformer.py (map_transformer(native, buses, container)). Atoms:
tests/atoms/transformer/ — xfm1 (3-phase, IEEE13), sub3 (3-winding delta-wye-wye, neutral impedance on
winding 2), reg1 (1-phase regulator unit), service (EPRI J1 7.2/0.24 kV), center_tap (phase-to-phase primary,
s1/s2 secondary), with prereq.cimtbl; tested by tests/test_cimtbl_transformer.py. Regulators and LTCs (S3a): see
"Transformer: regulators and LTCs" below. An XfmrCode instance no RegControl names waits for the template (S3b).
Model (the user's, 2026-11-06). Every DSS Transformer is its own PowerTransformer (bank is untranscribed),
with one PowerTransformerEnd per distinct bus, numbered in winding order. The end's terminal holds the phases.
- 3-phase, balanced ends: ratedU = the DSS kV (phase-to-phase), ratedS, r (percent on the end's own
rating) per end. x goes on the end-to-end mesh, in percent on winding 1's kVA at the From end's voltage, so a
From end with another kVA raises. pct_imag/pct_noloadloss become end 1 b/g (percent). Wye gives Yn when
grounded (neutral on node 0, or Rneut >= 0 on that winding) and Y otherwise; delta gives D.
- 1-phase, phase ends: one TransformerTank, one TransformerPhaseEnd per phase conductor on each bus
(sequenceNumber unique in the transformer, end 1 first, in terminal phase order), and one TransformerWinding
per DSS winding from the phase end of its first conductor to that of its second. Windings 2 and 3 on one bus,
both on node 0, with nodes 1 and 2, form a split-phase secondary (s1s2N, I). Otherwise node 1/2/3 is A/B/C,
0 is N, an LN coil's end is Y and an LL coil's is D.
Nameplate ratings (IEEE C57.12.00-2021 Table 7; the catalog rule):
- baseU = the DSS kV, i.e. the coil voltage.
- ratedU (derived) is phase-to-phase:
- an LN coil on a 3-phase system: kV × √3, never rounded (7.2 → 12.4708);
- a split-phase half: 2 × kV;
- an LL coil, or an LN coil on a single-phase system (the J1 240 V services): kV.
- baseS = winding 1's kVA on every coil. A split-phase half has ratedS = kVA / 2. On 1-phase, the kVAs must be
equal, because each %R is on its own winding's kVA.
Whether a bus's system is 3-phase comes from the topology walk (cimtopology.core.BusSystem), as does its
BaseVoltage.
Defaults (listed in the row comment, # defaulted: ...): phases 3, conns wye, %R 0.2 per winding
(pct_loadloss / 2 on windings 1 and 2 when set), XHL/XHT/XLT 7/35/30. Rneut/Xneut belong to the reader's wdg
tag, else the last winding (the old importer's rule). Missing buses take DSS's default nodes: conductor k on node k,
the neutral on 0.
Fail fast:
- phases other than 1 or 3, or windings other than 2 or 3;
- an active-winding scalar (kV, kVA, conn, bus, tap, %R) left over after the reader (it resolves them
to their winding, S3);
- a tap other than 1 on a transformer no RegControl names;
- pct_Rs and pct_loadloss that disagree, or XHL and X12 that disagree;
- 3-phase nodes other than 1.2.3;
- two windings on one bus that are not a split-phase secondary;
- a bus missing from the topology result;
- RdcOhms on some windings only (the reader), on a 3-phase transformer by balanced ends, or on a regulator;
- Seasons without Ratings, or a Ratings count other than Seasons;
- Rneut >= 0 on a 1-phase transformer (a coil's neutral impedance has no row yet), as on a 1-phase XfmrCode;
- Rneut/Xneut on a second winding (the reader: the schema holds one winding's).
DC resistance and seasonal ratings (2026-11-24). Atom tests/atoms/transformer/rated.dss (the EPRI J1
service with each winding's RdcOhms and Seasons=2 Ratings=[44 52]), golden rated.cimtbl,
test_rated_service_binds; the export atom rated_inline.dss is the same record on a circuit of its own.
- RdcOhms is per winding. DSS has no array form, so the reader puts each value at the active wdg='s place in
the RdcOhms list. Some windings set and others not raises: the engine's default for those (85 % of %R in ohms)
is not transcribed. The values are copied verbatim, Update Table TransformerWinding: mRID, rDC (ohm), only when
set, on a 1-phase transformer's coils (and on an XfmrCode template's windings). A 3-phase transformer by balanced
ends has no TransformerWinding, so it raises (RdcOhms on a 3-phase transformer by balanced ends), and so does
a regulator (an AutoTransformerEnd has no rDC).
- Ratings (kVA) are one ApparentPowerLimit <owner>_ratings_<n> per season n, of type olt_season<n>, in
the OperationalLimitSet <owner>_ratings. An inline Transformer's set is on its PowerTransformer
(OperationalLimitSet.Equipment), a regulator's on its VoltageRegulator. The master declares olt_season1 ..
olt_season<N> (name season <n>, durationKind normal, isInfiniteDuration true, absoluteValue) for the
most seasons any Transformer or XfmrCode rates (limit_types(seasons)).
- Seasons is the number of ratings. The engine keeps only Seasons values of Ratings (one by default) and
pads a Seasons alone with zeros, so Seasons without Ratings raises, and so does len(Ratings) != Seasons.
Known limit: the engine also zeroes the Ratings when Seasons comes after Ratings on the line; the reader does
not record that order.
- normhkVA and emerghkVA stay untranscribed.
| Transformer field | type | samples | kind | target |
|---|---|---|---|---|
name |
Union[str, TransformerName] |
Reg1, Reg2, Reg3 |
copied | PowerTransformer.name; mRID = xf_ + name, lowercased |
phases |
Optional[int] |
1, 3 |
structural | 1 = by phase ends, 3 = by balanced ends; default 3 |
windings |
Optional[int] |
3, 2 |
structural | 2 or 3; must match the buses |
wdg |
Optional[int] |
2 |
structural | the winding Rneut/Xneut belong to (the reader's tag); none = the last |
bus |
Optional[str] |
structural | the active-winding form; the reader folds wdg= blocks into the arrays, and a bare value raises | |
conn |
Union[str, ForwardRef('ConnectionType'), NoneType] |
structural | the active-winding form; the reader folds wdg= blocks into the arrays, and a bare value raises | |
kV |
Optional[float] |
structural | the active-winding form; the reader folds wdg= blocks into the arrays, and a bare value raises | |
kVA |
Optional[float] |
structural | the active-winding form; the reader folds wdg= blocks into the arrays, and a bare value raises | |
tap |
Optional[float] |
structural | the active-winding form; the reader folds wdg= blocks into the arrays, and a bare value raises | |
pct_R |
Optional[float] |
structural | the active-winding form; the reader folds wdg= blocks into the arrays, and a bare value raises | |
Rneut |
Optional[float] |
0.0 |
structural | rground (ohm) of its winding's end when >= 0; negative = no impedance; >= 0 on a 1-phase transformer raises |
Xneut |
Optional[float] |
0.4 |
structural | xground (ohm) of its winding's end, with Rneut >= 0 |
buses |
Union[str, list[str], NoneType] |
['BRKR.1', 'RG60.1'], ['BRKR.2', 'RG60.2'], ['BRKR.3', 'RG60.3'] |
structural | end node and terminal phases; one end per distinct bus |
conns |
Union[str, ForwardRef('ConnectionType'), list[Union[str, ForwardRef('ConnectionType')]], NoneType] |
[ConnectionType(text='delta', descrip..., [ConnectionType(text='wye', descripti... |
structural | connectionKind, grounded, default nodes; default wye |
kVs |
Union[float, list[float], NoneType] |
[2.4, 2.4], [115.0, 4.16, 13.2], [4.16, 0.48] |
structural | 3-phase: end ratedU; 1-phase: winding baseU, ratedU derived (x sqrt 3, x 2) |
kVAs |
Union[float, list[float], NoneType] |
[1666.0, 1666.0], [5000.0, 5000.0, 1000.0], [500.0, 500.0] |
structural | end ratedS / winding ratedS (halves / 2); winding 1's kVA is every baseS |
taps |
Union[float, list[float], NoneType] |
[1.0, 1.0625], [1.0, 1.05], [1.0, 1.06875] |
structural | the regulated winding's tap is RatioTapChanger.step (regcontrol.cimtbl); any other tap other than 1 raises; values past the winding count are ignored and missing ones are 1, as in the engine (winding_taps) |
XHL |
Optional[float] |
0.01, 2.0, 5.75 |
structural | mesh 1-2 x (percent on winding 1's kVA); default 7 |
XHT |
Optional[float] |
0.025 |
structural | mesh 1-3 x; default 35 |
XLT |
Optional[float] |
0.025 |
structural | mesh 2-3 x; default 30 |
Xscarray |
Union[float, list[float], NoneType] |
untranscribed | for more than 3 windings, which raise | |
thermal |
Optional[float] |
untranscribed | thermal model; no home in the network profile parts | |
n |
Optional[float] |
untranscribed | thermal model; no home in the network profile parts | |
m |
Optional[float] |
untranscribed | thermal model; no home in the network profile parts | |
flrise |
Optional[float] |
untranscribed | thermal model; no home in the network profile parts | |
hsrise |
Optional[float] |
untranscribed | thermal model; no home in the network profile parts | |
pct_loadloss |
Optional[float] |
0.01, 0.001, 0.7639 |
derived | when pct_Rs is unset, r = loadloss / 2 on windings 1 and 2; set with pct_Rs, the two must agree |
pct_noloadloss |
Optional[float] |
0.0851, 0.34, 0.1348 |
derived | 3-phase: end 1 g (percent); 1-phase: tank noLoadLoss = % x kVA; a regulator has no home for it (row comment) |
normhkVA |
Optional[float] |
25.0, 15.0, 75.0 |
untranscribed | instance OperationalLimitSet or untranscribed |
emerghkVA |
Optional[float] |
35.0, 21.0, 105.0 |
untranscribed | instance OperationalLimitSet or untranscribed |
sub |
Union[bool, Bool, NoneType] |
True |
untranscribed | DSS report flag |
MaxTap |
Optional[float] |
1.1, 1.05 |
structural | the RatioTapChanger range of a regulated transformer (regcontrol.cimtbl); else untranscribed; default 1.1 |
MinTap |
Optional[float] |
0.9, 0.95 |
structural | the RatioTapChanger range of a regulated transformer (regcontrol.cimtbl); else untranscribed; default 0.9 |
NumTaps |
Optional[int] |
16, 32 |
structural | the RatioTapChanger range of a regulated transformer (regcontrol.cimtbl); else untranscribed; default 32 |
subname |
Optional[str] |
M1, HVMV_Sub |
untranscribed | DSS report label |
pct_imag |
Optional[float] |
0.0001, 0.5 |
structural | 3-phase: end 1 b (percent); 1-phase: tank percentMagnetizingCurrent; a regulator has no home for it (row comment) |
ppm_antifloat |
Optional[float] |
0.0, 5.0 |
untranscribed | numerical aid of the DSS solver |
pct_Rs |
Union[float, list[float], NoneType] |
[0.0005, 0.0005, 0.0005], [0.55, 0.55], [0.67, 0.67] |
structural | 3-phase: end r (percent); 1-phase: winding r (percent); default 0.2 |
bank |
Optional[str] |
Reg, FEEDER1_REG1, FEEDER2_REG2 |
untranscribed | each DSS Transformer is its own PowerTransformer |
XfmrCode |
Optional[str] |
CT5, RegLeg, SubXfmr |
structural | a regulated instance takes the code's values (with_code); any other waits for the template (S3b) and is counted on the master |
XRConst |
Union[bool, Bool, NoneType] |
untranscribed | harmonics option | |
X12 |
Optional[float] |
structural | alias of XHL | |
X13 |
Optional[float] |
structural | alias of XHT | |
X23 |
Optional[float] |
structural | alias of XLT | |
LeadLag |
Union[str, ForwardRef('LeadLagType'), NoneType] |
Lag |
untranscribed | PowerTransformer.vectorGroup clock; vectorGroup not mapped yet |
Core |
Union[str, ForwardRef('CoreType'), NoneType] |
untranscribed | core type; no home in the network profile parts | |
RdcOhms |
Union[float, list[float], NoneType] |
copied | TransformerWinding.rDC (ohm); per winding, on a 1-phase transformer's coils; by balanced ends (no TransformerWinding) it raises |
|
Seasons |
Optional[int] |
structural | the number of Ratings; one by default, and a count other than the Ratings' raises | |
Ratings |
Union[float, list[float], NoneType] |
copied | ApparentPowerLimit.normalValue (kVA); one per season n, of type olt_season |
|
normamps |
Optional[float] |
untranscribed | instance OperationalLimitSet or untranscribed | |
emergamps |
Optional[float] |
untranscribed | instance OperationalLimitSet or untranscribed | |
faultrate |
Optional[float] |
untranscribed | reliability data; no home in the network profile parts | |
pct_perm |
Optional[float] |
untranscribed | reliability data; no home in the network profile parts | |
repair |
Optional[float] |
untranscribed | reliability data; no home in the network profile parts | |
basefreq |
Optional[float] |
untranscribed | no home on a transformer | |
enabled |
Union[bool, Bool, NoneType] |
True |
copied | PowerTransformer.normallyInService |
like |
Optional[str] |
reg3a, reg4a, reg1a |
untranscribed | the reader resolves like= before mapping |
Deck sweep (2026-11-06, placeholder bus systems). 1,365 of the 1,378 inline transformers in 11 decks map. Stops:
| stop | count | next |
|---|---|---|
| taps ≠ 1 | 6 (IEEE13_original regulators) | lifted in S3a: regulators |
kVA=750 with no wdg= |
8 (ieee9500 *-DIES1) |
lifted in S3a: the reader's active-winding rule (2-winding kVA sets both) |
%R=0.1 with no wdg= |
2 (J1 ExistingSite*) |
lifted in S3a: winding 2 gets 0.1, winding 1 the default 0.2, as the engine |
Reader fixes this slice needed: numeric bus and wire names stayed floats (634 → 634.0, i.e. node 0); quoted
arrays (conns='delta delta', IEEE37) failed to build, and the reader dropped reg1a with only a log line. A
failed build now raises.
S3 (S3a approved and done 2026-11-08)¶
S3 maps the network: lines and switches, the transformers into the orchestrator, regulators and LTCs, and their RegControls. Census of the 31 sweep decks, 2026-11-07: - Lines: 34,254 in all. By linecode 27,679; by geometry 5,294; inline sequence values 1,162 (678 of them switches); inline matrix 4 (1 a switch); spacing + wires 3; switches with no impedance 112. - Switch controls: 98 Fuses, 161 Reclosers, 336 SwtControls. - Regulators: 176 RegControls.
Scope split (approved, R3). A non-regulator Transformer by XfmrCode waits for U2. In the sweep that is IEEE8500
1,177, IEEE9500 1,275, IEEE123_PV 82, IEEE13_OCHRE 16, IEEE13_CDPSM 1 (Tpoletop). So S3 splits:
- S3a (done): lines, switches, transformers in MAPPING_ORDER, VoltageRegulators and LTCs (a regulator by
XfmrCode included), RegControl.
- S3b (done 2026-11-08): XfmrCode templates and their instances (section XfmrCode). AutoTrans stays unmapped
until a deck has one (S3b-1).
Until S3b a Transformer by XfmrCode that no RegControl names was counted on the master's # not mapped: line;
S3b maps it by template.
Result (2026-11-08). The S3a exit is met:
- IEEE13_CDPSM, IEEE123 and IEEE8500 bind with every line, switch, transformer and regulator. Their XfmrCode
transformers are counted on the master.
- 25 of the 31 sweep decks bind with every S3a part. The six stops:
- DSS-10, a line's phases ≠ its code's nphases: J1, K1, M1, IEEE13_OCHRE;
- the ieee9500_2025 balanced copy (an Open of a line it never defines; the engine fails too);
- the PNNL balanced IEEE9500 deck, whose lines name LineCodes it never loads (the engine fails too).
- Engine checks, on the atoms and the 8 engine decks (IEEE13 ×3, IEEE123, IEEE37, IEEE4, IEEE8500, IEEE9500):
- every line's ratings, and the z and b totals of every line by code or by inline values;
- every switch state;
- every RegControl setting, the tap range and the regulator nameplate and mesh;
- the tap position, on the atom (a deck that solves when compiled moves its taps).
Engine rules found in S3 (each pinned with a probe and kept in a test):
- Ratings. A line copies each of normamps/emergamps it leaves unset from its LineCode, or from its
LineGeometry. A geometry rating left unset is its first conductor's. A wire with normamps and no emergamps is
rated 1.5 × normamps, and one with emergamps and no normamps has normamps = emergamps / 1.5. A spacing +
wires line takes its first wire's.
- Default C. A matrix LineCode without cmatrix keeps the engine's default C matrix: self (2 C1 + C0)/3 and
mutual (C0 − C1)/3 from C1 = 3.4, C0 = 1.6 nF per unit length, on any number of phases
(cimhub_core.derived.sequence.balanced_matrix). IEEE13_original's codes are this case (an amendment to the S2
LineCode mapper; the row says # defaulted: cmatrix from C1=3.4, C0=1.6).
- Inline defaults. A sequence line leaves some of r1, x1, r0, x0, C1, C0 unset; they take the DSS defaults.
r and x stay per unit length as they are. The engine keeps C1 and C0 per kft whatever the line's units, so a
line with units writes them as given, in bch (nS/kft)/b0ch (nS/kft) (or b (nS/kft) on a 1- or 2-phase
line) beside its r (ohm/<units>). A line with no units has no length to be per, and its defaults go in its
gated unit. A line that sets one of C1/C0 (of those it uses: a 1-phase line uses C1 only) and leaves the other to
the per-kft default, in units other than kft, raises: its C would be in two length units.
- Unitless geometry line. Its length is in metres.
Reader fixes in S3 (§3.4 of the plan; each checked against the engine):
- A value with no name goes to the property after the last one named, in the schema's order. {...} is RPN.
The decks use this as Normamps=156 {156 1.25 *}: emergamps = 195 on the J1, K1, M1, IEEE8500 and IEEE9500
triplex codes, which the reader used to drop silently. A positional value on a class the reader rewrites by
blocks (Transformer, XfmrCode, AutoTrans, LineGeometry) raises.
- A bare per-winding property (bus kV kVA conn tap %R) goes to the active winding: the last wdg=, else the last
winding an array set (an array sets every winding), else winding 1. On a 2-winding transformer, kVA sets both
windings, even inside a wdg= block (wdg=1 kva=500 wdg=2 kva=300 is [300, 300] in the engine).
- This lifts the old kVA=750 stop on the ieee9500 *-DIES1/-ESS/-MT transformers.
- A winding no property sets takes the per-winding default (dss_default on Transformer/XfmrCode kV kVA conn
tap %R, as the engine does), with a warning. J1's ExistingSite* %R=0.1 was this case. An unset bus
raises.
Line and switches¶
Mapper: cimhub_opendss/importer/cimtbl/line.py (map_line; CONTROLS for Fuse, Recloser, SwtControl).
Artifact line.cimtbl; shapes line_by_impedance, line_by_wire_configuration, switch. Atoms in
tests/atoms/line/, tested by tests/test_cimtbl_line.py:
- codes.dss (after IEEE13_CDPSM): lines by code (one code without cmatrix), inline sequence lines (one with
defaults, one unitless 1-phase), and a LoadBreakSwitch, Fuse, Recloser, an open SwtControl tie and an Open
section;
- geometry.dss (after IEEE13_Assets): geometry lines (one unitless), a spacing + wires line, ratings from the
first wire.
Identity. An ACLineSegment is ln_ + name and a switch sw_ + name, lowercased. Every Switch subclass shares
sw_, so the switch's class can change without changing its mRID.
Class (DSS-9). A Line with Switch=y is a switch:
- a Fuse whose SwitchedObj (else MonitoredObj, the DSS default) is that line makes it a Fuse, and its
RatedCurrent becomes ratedCurrent;
- a Recloser makes it a Recloser;
- otherwise (a SwtControl, or no control) it is a LoadBreakSwitch.
What raises: a Fuse or Recloser on a line without Switch=y; two controls of different classes on one line; a
control or an Open command whose line no New defines, also in a deck with no Line at all. In the sweep, every Fuse and Recloser switches the line it monitors.
Switch state.
- open: an Open command on either terminal (Options.open_terminals), or a SwtControl with State=Open.
- normalOpen: the SwtControl's Normal, else the same as open.
An Open command and a SwtControl State that disagree raise. A Fuse whose Normal/State give a value count other than its line's
phases raises (found by the S6b export, 2026-11-09). The engine sets a fuse phase by phase, so State=open on a
3-phase line opens phase 1 only, and CIM's open is the whole switch's. No sweep deck sets a Fuse state. So does an Open on a line that is not a switch:
Terminal.connected would be its home, but no deck needs it.
- Sweep: 33 SwtControls are Open with Normal = State on every one. ieee9500 has 9 Open commands and
IEEE123_test_harness 2, all on switch lines.
- Dropped from switches: a switch's impedance, length and ratings stay untranscribed (DSS-8). DSS needs them
only as numerical stand-ins: r1=1e-4, or the Switch=y defaults.
Template (ACLineSegment). Exactly one of the following; a line that combines two raises:
- linecode= → WireConfiguration = the WireConfiguration of the code's template for the line's unit
(lc_<code>_wc, or lc_<code>_<unit>_wc when the code's lines disagree, DSS-3, DSS-14);
- geometry= → WireConfiguration = wc_<geometry>;
- spacing= + wires=/cncables=/tscables= → a synthesized WireConfiguration ln_<name>_wc on
spc_<spacing>, conductors in order (IEEE13_Assets 684652). This is the counterpart of S2's synthesized
spacing;
- inline r1…B0 or rmatrix/xmatrix/cmatrix → PerLengthImpedance = a synthesized
PerLengthSequenceImpedance or PerLengthPhaseImpedance ln_<name>_lc of the line's own, isTemplate=false
(DSS-14), under # synthesized in line.cimtbl (DSS-8). It goes through the
LineCode mapper's own functions, so DSS-3 (units, gate), DSS-3b and DSS-4 apply unchanged.
- Naming: DSS-8 said lc_<line>. A line and a code may share a name, so this proposes ln_<name>_lc.
- Units: a unitless inline line goes through the same magnitude gate, over the deck's unitless inline
lines (its own group, so its inference is stated on its own rows). Sweep: 432 in M1, 8 in IEEE123, 1 in IEEE37.
- Unset sequence values take the engine's defaults (above).
Length and units. length (default 1, defaulted) is in the line's units. A unitless line by code takes the
code's template unit: the code's units, else the gate (DSS-3). A unitless line by geometry (M1, 2 lines) takes
metres, as the engine reads it (# defaulted: units=m).
Phases. They come from bus1's nodes:
- 1/2/3 → A/B/C, in bus order (645.3.2 → CB, the matrix row order);
- on a split-phase island (the walk, DSS-5): 1/2 → s1/s2;
- no nodes → 1..phases;
- a geometry with neutral conductors adds N (601: ABCN).
What raises:
- bus2's phase nodes differing from bus1's (a transposition);
- phases ≠ the code's nphases (DSS-10, deferred). That leaves J1 (1,381 lines), K1 (743), M1 (1,949) and
IEEE13_OCHRE (50) in the sweep table. IEEE8500 and IEEE9500 have no mismatch: their lines take phases from the
code.
Ratings (R1, approved). A line's normamps and emergamps go on an OperationalLimitSet
ln_<name>_limits (Equipment = the segment) with one CurrentLimit (normalValue, A) each:
- ln_<name>_norm on OperationalLimitType olt_normal: durationKind=normal, isInfiniteDuration=true,
direction=absoluteValue;
- ln_<name>_emerg on olt_emergency: durationKind=emergency, isInfiniteDuration=false,
direction=absoluteValue.
The two types (GridAPPS-D LimitDurationKind, added to cim18v17 2026-11-07) are written once in the master, so
later slices (transformers, catalogs) share them. season (CalendarSeasonKind) stays unset. DSS's Seasons and
Ratings are an indexed array that a SeasonSignal loadshape selects, and they name no calendar season. No deck
in the sweep sets them, so they raise until a deck shows the index-to-season convention. Values:
- the line's own value, else what the engine copies: its code's, else its geometry's, else the geometry's first
conductor's, with a wire's emergency rating defaulting to 1.5 × normamps (# ratings: normamps from LineCode
mtx601). DSS keeps the last value set, and the reader does not record the order. Decks give a line's ratings
after its linecode=, and the engine check agrees on every engine deck;
- nothing from DSS's 400/600 A defaults.
Defaults (from the dss_default annotations, filled for Line, Fuse, Recloser and SwtControl in this slice,
DSS-6): length 1, phases 3, units none.
Expected differences from the hand translation: IEEE13_CDPSM Brkr1 becomes a LoadBreakSwitch, not a
Breaker: DSS has no breaker class, and DSS-9 decides by control.
| Line field | type | samples | kind | target |
|---|---|---|---|---|
name |
Union[str, LineName] |
632633, 632645, 632670 |
copied | ACLineSegment.name, Switch.name; mRID = ln_ + name (segment) or sw_ + name (switch), lowercased |
bus1 |
str |
632.1.2.3, 632.3.2, MID.1.2.3 |
structural | node1, and the phases from its nodes: 1/2/3 = A/B/C, s1/s2 on a split-phase island (DSS-5); no nodes = 1..phases |
bus2 |
Optional[str] |
633.1.2.3, 645.3.2, 670.1.2.3 |
structural | node2; its phase nodes must equal bus1's (a transposition raises) |
linecode |
Optional[str] |
mtx602, mtx603, mtx601 |
structural | ACLineSegment.WireConfiguration = the WireConfiguration of the code's template for the line's unit (lc_wc or lc |
length |
Optional[float] |
500.0, 667.0, 300.0 |
copied | ACLineSegment.length ({length}); default 1 (defaulted); none on a switch |
phases |
Optional[int] |
3, 2, 1 |
structural | the phase count; unset = the code's, geometry's or spacing's nphases, else 3 (line_phase_count; a switch has no template); one that differs from the code's nphases raises (DSS-10) |
r1 |
Optional[float] |
0.0001, 0.001, 1.0 |
structural | the line's own PerLengthImpedance ln_ |
x1 |
Optional[float] |
0.0, 0.001, 1.0 |
structural | the line's own PerLengthImpedance ln_ |
r0 |
Optional[float] |
0.0001, 0.001, 1.0 |
structural | the line's own PerLengthImpedance ln_ |
x0 |
Optional[float] |
0.0, 0.001, 1.0 |
structural | the line's own PerLengthImpedance ln_ |
C1 |
Optional[float] |
0.0, 0.000212206590789194, 0.000450939005427037 |
structural | the line's own PerLengthImpedance ln_ |
C0 |
Optional[float] |
0.0, 0.000636619772367581, 0.00135281701628111 |
structural | the line's own PerLengthImpedance ln_ |
rmatrix |
Union[float, list[float], NoneType] |
[1.3238, 0.2066, 1.3294], [0.0001] |
structural | the line's own PerLengthImpedance ln_ |
xmatrix |
Union[float, list[float], NoneType] |
[1.3569, 0.4591, 1.3471], [0.0] |
structural | the line's own PerLengthImpedance ln_ |
cmatrix |
Union[float, list[float], NoneType] |
[0.0] |
structural | the line's own PerLengthImpedance ln_ |
Switch |
Union[bool, Bool, NoneType] |
True |
structural | a Switch (sw_) instead of an ACLineSegment; class from its control (DSS-9) |
Rg |
Optional[float] |
structural | raises when set: no deck in the sweep sets it, so a mapping waits for one (Carson earth return; the consumer's choice for geometry) | |
Xg |
Optional[float] |
structural | raises when set: no deck in the sweep sets it, so a mapping waits for one (Carson earth return; the consumer's choice for geometry) | |
rho |
Optional[float] |
structural | the deck's EarthResistivity.rho (ohm-m), which every geometry line must agree on (geometry.earth_statement); on another line it raises; a switch lists it untranscribed | |
geometry |
Optional[str] |
602, 603, 601 |
structural | ACLineSegment.WireConfiguration = wc_ |
units |
Union[str, ForwardRef('LengthUnit'), NoneType] |
Ft, mi, km |
mapped | the length unit (LENGTH_UNIT); unset: the template's unit (DSS-3) |
spacing |
Optional[str] |
510 |
structural | with spacing=: a synthesized WireConfiguration ln_ |
cncables |
Union[str, list[str], NoneType] |
structural | with spacing=: a synthesized WireConfiguration ln_ |
|
tscables |
Union[str, list[str], NoneType] |
structural | with spacing=: a synthesized WireConfiguration ln_ |
|
wires |
Union[str, list[str], NoneType] |
['ACSR_1/0', 'ACSR_1/0'] |
structural | with spacing=: a synthesized WireConfiguration ln_ |
EarthModel |
Union[str, ForwardRef('EarthModelType'), NoneType] |
untranscribed | the earth model of the impedance calculation; the consumer's choice | |
B1 |
Optional[float] |
structural | the line's own PerLengthImpedance ln_ |
|
B0 |
Optional[float] |
structural | the line's own PerLengthImpedance ln_ |
|
Seasons |
Optional[int] |
structural | raises when set: no deck in the sweep sets it, so a mapping waits for one (an indexed rating array that names no calendar season; home OperationalLimitType.season) | |
Ratings |
Union[float, list[float], NoneType] |
structural | raises when set: no deck in the sweep sets it, so a mapping waits for one (with Seasons) | |
LineType |
Union[str, ForwardRef('LineTypeCode'), NoneType] |
untranscribed | no home in the network profile parts | |
EpsRmedium |
Optional[float] |
structural | raises when set: no deck in the sweep sets it, so a mapping waits for one | |
HeightOffset |
Optional[float] |
structural | raises when set: no deck in the sweep sets it, so a mapping waits for one | |
HeightUnit |
Union[str, ForwardRef('LengthUnit'), NoneType] |
structural | raises when set: no deck in the sweep sets it, so a mapping waits for one | |
conductors |
Union[str, list[str], NoneType] |
structural | raises when set: no deck in the sweep sets it, so a mapping waits for one | |
normamps |
Optional[float] |
230.0, 90.0, 450.0 |
structural | instance OperationalLimitSet ln_ |
emergamps |
Optional[float] |
130.0, 600.0, 300.0 |
structural | instance OperationalLimitSet ln_ |
faultrate |
Optional[float] |
untranscribed | reliability data; no home in the network profile parts | |
pct_perm |
Optional[float] |
untranscribed | reliability data; no home in the network profile parts | |
repair |
Optional[float] |
untranscribed | reliability data; no home in the network profile parts | |
basefreq |
Optional[float] |
structural | the line's own impedance's calculatedFrequency and the frequency of its b; unset: the deck's (DSS-3b) | |
enabled |
Union[bool, Bool, NoneType] |
True, False |
copied | ACLineSegment.normallyInService, Switch.normallyInService |
like |
Optional[str] |
untranscribed | the reader resolves like= before mapping |
| Fuse field | type | samples | kind | target |
|---|---|---|---|---|
name |
Union[str, FuseName] |
Fuse1, 2002200004641085, 2002200004868472 |
untranscribed | the switch takes the Line's name; the Fuse names no CIM object |
MonitoredObj |
Optional[str] |
Line.Fuse1, Line.2002200004641085_sw, Line.2002200004868472_sw |
structural | the Line it switches: SwitchedObj, else MonitoredObj (the DSS default); not a Switch=y line raises |
MonitoredTerm |
Optional[int] |
untranscribed | the switch opens both terminals in CIM; DSS's terminal choice has no home | |
SwitchedObj |
Optional[str] |
Line.2002200004641085_sw, Line.2002200004868472_sw, Line.200220000499_sw |
structural | the Line it switches: SwitchedObj, else MonitoredObj (the DSS default); not a Switch=y line raises |
SwitchedTerm |
Optional[int] |
untranscribed | the switch opens both terminals in CIM; DSS's terminal choice has no home | |
FuseCurve |
Optional[str] |
untranscribed | protection setting; no home in cim18v17's protection function blocks (DSS-11) | |
RatedCurrent |
Optional[float] |
100.0, 65.0, 15.0 |
copied | Fuse.ratedCurrent (A) |
Delay |
Optional[float] |
untranscribed | control timing; no home on a Switch | |
Action |
Optional[str] |
structural | raises when set: no deck in the sweep sets it, so a mapping waits for one (the deprecated form of State) | |
Normal |
Union[str, list[str], NoneType] |
structural | Normal -> normalOpen, State -> open on the switch; with an Open command on the line they must agree | |
State |
Union[str, list[str], NoneType] |
structural | Normal -> normalOpen, State -> open on the switch; with an Open command on the line they must agree | |
basefreq |
Optional[float] |
untranscribed | no home on a switch | |
enabled |
Union[bool, Bool, NoneType] |
untranscribed | a disabled control leaves its switch in place; no home | |
like |
Optional[str] |
untranscribed | the reader resolves like= before mapping |
| Recloser field | type | samples | kind | target |
|---|---|---|---|---|
name |
Union[str, RecloserName] |
Rec1, A333_48332, G9343_48332 |
untranscribed | the switch takes the Line's name; the Recloser names no CIM object |
MonitoredObj |
Optional[str] |
Line.Rec1, Line.A333_48332_sw, Line.G9343_48332_sw |
structural | the Line it switches: SwitchedObj, else MonitoredObj (the DSS default); not a Switch=y line raises |
MonitoredTerm |
Optional[int] |
untranscribed | the switch opens both terminals in CIM; DSS's terminal choice has no home | |
SwitchedObj |
Optional[str] |
Line.A333_48332_sw, Line.G9343_48332_sw, Line.L5397_48332_sw |
structural | the Line it switches: SwitchedObj, else MonitoredObj (the DSS default); not a Switch=y line raises |
SwitchedTerm |
Optional[int] |
untranscribed | the switch opens both terminals in CIM; DSS's terminal choice has no home | |
NumFast |
Optional[int] |
untranscribed | protection setting; no home in cim18v17's protection function blocks (DSS-11) | |
PhaseFast |
Optional[str] |
untranscribed | protection setting; no home in cim18v17's protection function blocks (DSS-11) | |
PhaseDelayed |
Optional[str] |
untranscribed | protection setting; no home in cim18v17's protection function blocks (DSS-11) | |
GroundFast |
Optional[str] |
untranscribed | protection setting; no home in cim18v17's protection function blocks (DSS-11) | |
GroundDelayed |
Optional[str] |
untranscribed | protection setting; no home in cim18v17's protection function blocks (DSS-11) | |
PhaseTrip |
Optional[float] |
1200.0, 200 |
untranscribed | protection setting; no home in cim18v17's protection function blocks (DSS-11) |
GroundTrip |
Optional[float] |
400.0, 40 |
untranscribed | protection setting; no home in cim18v17's protection function blocks (DSS-11) |
PhaseInst |
Optional[float] |
untranscribed | protection setting; no home in cim18v17's protection function blocks (DSS-11) | |
GroundInst |
Optional[float] |
untranscribed | protection setting; no home in cim18v17's protection function blocks (DSS-11) | |
Reset |
Optional[float] |
untranscribed | protection setting; no home in cim18v17's protection function blocks (DSS-11) | |
Shots |
Optional[int] |
3 |
structural | one RecloseSequence |
RecloseIntervals |
Union[float, list[float], NoneType] |
structural | one RecloseSequence |
|
Delay |
Optional[float] |
untranscribed | control timing; no home on a Switch | |
Action |
Optional[str] |
structural | raises when set: no deck in the sweep sets it, so a mapping waits for one (the deprecated form of State) | |
TDPhFast |
Optional[float] |
untranscribed | protection setting; no home in cim18v17's protection function blocks (DSS-11) | |
TDGrFast |
Optional[float] |
untranscribed | protection setting; no home in cim18v17's protection function blocks (DSS-11) | |
TDPhDelayed |
Optional[float] |
untranscribed | protection setting; no home in cim18v17's protection function blocks (DSS-11) | |
TDGrDelayed |
Optional[float] |
untranscribed | protection setting; no home in cim18v17's protection function blocks (DSS-11) | |
Normal |
Optional[str] |
structural | Normal -> normalOpen, State -> open on the switch; with an Open command on the line they must agree | |
State |
Optional[str] |
structural | Normal -> normalOpen, State -> open on the switch; with an Open command on the line they must agree | |
basefreq |
Optional[float] |
untranscribed | no home on a switch | |
enabled |
Union[bool, Bool, NoneType] |
untranscribed | a disabled control leaves its switch in place; no home | |
like |
Optional[str] |
untranscribed | the reader resolves like= before mapping |
| Swtcontrol field | type | samples | kind | target |
|---|---|---|---|---|
name |
Union[str, SwtcontrolName] |
2002200004641085, 2002200004868472, 200220000499 |
untranscribed | the switch takes the Line's name; the SwtControl names no CIM object |
SwitchedObj |
Optional[str] |
Line.2002200004641085_sw, Line.2002200004868472_sw, Line.200220000499_sw |
structural | the Line it switches: SwitchedObj, else MonitoredObj (the DSS default); not a Switch=y line raises |
SwitchedTerm |
Optional[int] |
untranscribed | the switch opens both terminals in CIM; DSS's terminal choice has no home | |
Action |
Optional[str] |
structural | raises when set: no deck in the sweep sets it, so a mapping waits for one (the deprecated form of State) | |
Lock |
Union[bool, Bool, NoneType] |
True |
untranscribed | control lock; no home on a Switch |
Delay |
Optional[float] |
untranscribed | control timing; no home on a Switch | |
Normal |
Optional[str] |
Closed, Open |
structural | Normal -> normalOpen, State -> open on the switch; with an Open command on the line they must agree |
State |
Optional[str] |
Closed, Open |
structural | Normal -> normalOpen, State -> open on the switch; with an Open command on the line they must agree |
Reset |
Union[bool, Bool, NoneType] |
untranscribed | a command, not a setting | |
basefreq |
Optional[float] |
untranscribed | no home on a switch | |
enabled |
Union[bool, Bool, NoneType] |
untranscribed | a disabled control leaves its switch in place; no home | |
like |
Optional[str] |
untranscribed | the reader resolves like= before mapping |
Transformer: regulators and LTCs¶
transformer.py (seeded) joins MAPPING_ORDER. A Transformer named by a RegControl changes as follows
(DSS-13):
- Regulator (equal winding kV; 133 single-phase, 4 three-phase gang in the sweep): a VoltageRegulator
xf_<name> (same prefix, since it is the same DSS object) with two AutoTransformerEnds xf_<name>_1,
xf_<name>_2.
- Each end carries node, endNumber, grounded, baseU (kV, the coil voltage), ratedS (kVA) and
BaseVoltage. Its phase is a PhaseCode: AN for a line-to-neutral unit, AB for a line-to-line unit
(IEEE37), ABCN for a 3-phase gang unit. grounded when the coil ends on node 0: a wye 1-phase coil with
0 among its nodes, a 3-phase gang unit with its star point (the last node) on 0; a star point on node 4
floats in the engine.
- Impedance (the user's model, 2026-11-07): one TransformerMeshImpedance xf_<name>_mesh_12 from end 1 to
end 2, with x = XHL and r = %R1 + %R2 (percent). Their base is end 1's baseU/ratedS, the base CIM-Tables'
z_base gives an AutoTransformerEnd. The row comment says it is the engine's stand-in impedance: a
regulator's nameplate has no %Z, and OpenDSS needs XHL only because it has no real autotransformer.
- What raises: unequal kVAs, a delta winding, more than 2 windings. %imag and %noloadloss have no home on
an AutoTransformerEnd, so they are untranscribed.
- LTC (unequal kV: J1 SubXfmr, M1 M1_XFMR, one 66/13.8 kV): stays a PowerTransformer (DSS-2); the tap
changer goes on the controlled PowerTransformerEnd.
- Taps (the RegControl's winding only; a tap ≠ 1 on any other winding, or on a transformer no RegControl
names, still raises):
- The deck's taps[winding] becomes RatioTapChanger.step = (tap − 1) / increment, where increment =
(MaxTap − MinTap) / NumTaps (defaults 1.1, 0.9, 32). A step that is not whole within 1e-6 raises.
- The range: highStep = (MaxTap − 1) / increment, lowStep = −(1 − MinTap) / increment, neutralStep 0,
stepVoltageIncrement = increment × 100 (percent), neutralU = the winding kV.
- These sit in the RegControl's rows, because they belong to the tap changer.
- A taps list is read as the engine reads it (M46, decision 7, transformer.winding_taps): values past the
winding count are ignored (windings=2 taps=[1.05 1.02 0.98] is 1.05, 1.02), and a shorter list leaves the
other windings at 1.0 (windings=3 taps=[1.05]).
- A regulator by XfmrCode (the 36 coded RegControls in the sweep) takes the code's values, as the engine copies
them; the row comment names the code. CIM has no template for an AutoTransformer, so this needs neither U2 nor
S3b.
The core shape voltage_regulator.cimtbl (added in S3a) holds the pattern: VoltageRegulator +
AutoTransformerEnds + mesh + RatioTapChanger + TapChangerControl. The regulator shape (PowerTransformer + tap) is
the LTC pattern. Atom: tests/atoms/regcontrol/regulators.dss (goldens regulators_transformer.cimtbl,
regulators.cimtbl), tested by tests/test_cimtbl_regcontrol.py.
RegControl¶
Mapper: cimhub_opendss/importer/cimtbl/regcontrol.py (map_regcontrol). Artifact regcontrol.cimtbl, after
transformer.cimtbl. Atom tests/atoms/regcontrol/regulators.dss:
- reg1: 1-phase line-to-neutral, LDC (after IEEE13_CDPSM);
- vr_ll: 1-phase line-to-line (after IEEE37);
- gang: 3-phase gang-operated, PTphase 2;
- coded: by XfmrCode, reversible (after IEEE8500);
- ltc: a step-down LTC (after M1).
Values: targetValue, targetDeadband, the reverse ones and ctRating are plain floats in cim18v17, so their
headers carry no unit (primary volts, amps).
TapChangerControlrc_<name>:mode=voltage,discrete=true,Terminal=xf_<transformer>_T<winding>,monitoredPhasefromPTphase.RatioTapChangerrc_<name>_tap:TransformerEnd=xf_<transformer>_<winding>,ltcFlag=true,ctRatio=CTprim/ 0.2.- Secondary to primary (derived, named functions):
- targetValue (V) =
vreg×ptratio(Reg1: 122 × 20 = 2440 V); the deadband and the reverse settings the same way; - line drop (ohm) =
R×ptratio/CTprim(Reg1: 3 × 20 / 700 = 0.0857 Ω), andXlikewise. - Defaults (
dss_defaultannotations, filled for RegControl from the EPRI property page in this slice):vreg120,band3,ptratio60,CTprim300,delay15,tapdelay2,winding1,revThreshold100,revDelay60. - Fail fast: remote sensing (
bus=; 1 in the sweep),tapwinding,vlimit,TapNum,LDC_Z, any of the idle/cogen modes; two RegControls on one transformer; a transformer no New defines; a tap range the engine takes but no tap changer has (NumTaps < 1, MaxTap ≤ MinTap, a tap outside them); a tap other than 1 on a winding the control does not move (the engine keeps it fixed; a fixed tap is not mapped yet). - Unset means unset or at its default (decision 14, 2026-11-27): an unmapped slot equal to its
dss_defaultcounts as unset, because the engine default changes nothing:vlimit0,LDC_Z0,rev_Z0,CogenNo (engine readback; RegControl.pas:606, 624, 635, 656). Any other value raises. A slot with no default raises at any value:TapNum=0too, because setting TapNum moves the tap (RegControl.pas:1469,Set_TapNum;taps=[1 1.025]withTapNum=0is tap 1.0 in the engine). rc_2 dropped every falsy value (TapNum=0,idle=No).
| Regcontrol field | type | samples | kind | target |
|---|---|---|---|---|
name |
Union[str, RegcontrolName] |
Reg1, Reg2, Reg3 |
copied | TapChangerControl.name, RatioTapChanger.name; mRID = rc_ + name (control) and rc_ + name + _tap (tap changer), lowercased |
transformer |
Optional[str] |
Reg1, Reg2, Reg3 |
structural | the regulator or LTC (DSS-13); a Transformer no New defines, or one two RegControls name, raises |
winding |
Optional[int] |
2 |
structural | RatioTapChanger.TransformerEnd = xf_ |
vreg |
Optional[float] |
122.0, 123.0, 125.0 |
derived | targetValue (V) = vreg x ptratio (secondary_to_primary); default 120 |
band |
Optional[float] |
2.0, 3.0, 1.0 |
derived | targetDeadband (V) = band x ptratio (secondary_to_primary); default 3 |
ptratio |
Optional[float] |
20.0, 60.0, 63.50852961 |
copied | TapChangerControl.ptRatio, RatioTapChanger.ptRatio; default 60 |
CTprim |
Optional[float] |
700.0, 50.0, 300.0 |
copied | RatioTapChanger.ctRating (A); default 300; also ctRatio = CTprim / 0.2 (the DSS CT secondary, 0.2 A) and the LDC base |
R |
Optional[float] |
3.0, 0.4, 0.6 |
derived | lineDropR (ohm) = R x ptratio / CTprim (line_drop_ohms); default 0; lineDropCompensation = R or X nonzero |
X |
Optional[float] |
9.0, 7.5, 0.4 |
derived | lineDropX (ohm) = X x ptratio / CTprim (line_drop_ohms); default 0 |
bus |
Optional[str] |
temp |
structural | raises when set: no deck in the sweep sets it, so a mapping waits for one (remote sensing; 1 RegControl in the sweep, which raises) |
delay |
Optional[float] |
90.0, 47.0, 50.0 |
copied | RatioTapChanger.initialDelay (s); default 15 |
reversible |
Union[bool, Bool, NoneType] |
True |
copied | TapChangerControl.reversible; default false |
revvreg |
Optional[float] |
125.0 |
derived | reverseTargetValue (V) = revvreg x ptratio (secondary_to_primary); default 120 |
revband |
Optional[float] |
2.0 |
derived | reverseTargetDeadband (V) = revband x ptratio (secondary_to_primary); default 3 |
revR |
Optional[float] |
derived | reverseLineDropR (ohm) = revR x ptratio / CTprim (line_drop_ohms); default 0 | |
revX |
Optional[float] |
derived | reverseLineDropX (ohm) = revX x ptratio / CTprim (line_drop_ohms); default 0 | |
tapdelay |
Optional[float] |
30.0, 45.0 |
copied | RatioTapChanger.subsequentDelay (s); default 2 |
debugtrace |
Union[bool, Bool, NoneType] |
untranscribed | DSS report flag | |
maxtapchange |
Optional[int] |
untranscribed | DSS solution control; no home in the network profile parts | |
inversetime |
Union[bool, Bool, NoneType] |
untranscribed | DSS solution control; no home in the network profile parts | |
tapwinding |
Optional[int] |
structural | raises when set: no deck in the sweep sets it, so a mapping waits for one (a tap winding other than the monitored one) | |
vlimit |
Optional[float] |
structural | raises when set: no deck in the sweep sets it, so a mapping waits for one (home TapChangerControl.maxLimitVoltage) | |
PTphase |
Optional[str] |
structural | TapChangerControl.monitoredPhase = the phase of the winding's conductor PTphase (default 1); MAX/MIN raise | |
revThreshold |
Optional[float] |
50.0 |
copied | TapChangerControl.reversingPowerThreshold (kW); default 100 |
revDelay |
Optional[float] |
copied | TapChangerControl.reversingDelay (s); default 60 |
|
revNeutral |
Union[bool, Bool, NoneType] |
copied | TapChangerControl.reverseToNeutral; default false |
|
EventLog |
Union[bool, Bool, NoneType] |
untranscribed | DSS report flag | |
RemotePTRatio |
Optional[float] |
structural | raises when set: no deck in the sweep sets it, so a mapping waits for one | |
TapNum |
Optional[int] |
structural | raises when set: no deck in the sweep sets it, so a mapping waits for one (a tap position that overrides the transformer's tap); even 0 raises: setting it moves the tap, so it has no default | |
Reset |
Union[bool, Bool, NoneType] |
untranscribed | a command, not a setting | |
LDC_Z |
Optional[float] |
structural | raises when set: no deck in the sweep sets it, so a mapping waits for one | |
rev_Z |
Optional[float] |
structural | raises when set: no deck in the sweep sets it, so a mapping waits for one | |
Cogen |
Union[bool, Bool, NoneType] |
structural | raises when set: no deck in the sweep sets it, so a mapping waits for one | |
idle |
Union[bool, Bool, NoneType] |
structural | raises when set: no deck in the sweep sets it, so a mapping waits for one | |
idleReverse |
Union[bool, Bool, NoneType] |
structural | raises when set: no deck in the sweep sets it, so a mapping waits for one | |
idleForward |
Union[bool, Bool, NoneType] |
structural | raises when set: no deck in the sweep sets it, so a mapping waits for one | |
basefreq |
Optional[float] |
untranscribed | no home on a control | |
enabled |
Union[bool, Bool, NoneType] |
True |
copied | TapChangerControl.enabled, RatioTapChanger.controlEnabled; default true |
like |
Optional[str] |
creg3a, creg4a, creg1a |
untranscribed | the reader resolves like= before mapping |
Decisions for S3a (approved 2026-11-08)¶
- R1: line ratings are mapped as above. The season goes on the
OperationalLimitTypewhen a deck gives one. - R2:
RatioTapChanger.normalStepis not written. The converter writesstep(the deck's tap position) only. - R3: S3a/S3b as proposed.
- R4: synthesized templates are
ln_<name>_lcandln_<name>_wc.
S4 (S4a approved and done 2026-11-08)¶
S4 maps the injections.
Result (S4a, 2026-11-08).
- 25 of the 31 sweep decks bind with every load, capacitor and CapControl; the stops are S3's six (DSS-10 in
J1, K1, M1, IEEE13_OCHRE; the two balanced IEEE9500 copies).
- Engine checks pass on the atoms and the 8 engine decks: every load's kW, kvar, model, CVR exponents,
connection and customer count; every capacitor's kvar, kV, connection and steps (states on the atom); every
CapControl's mode, ON and OFF (rebuilt from target and deadband), ratios, delay, element and terminal. IEEE8500
and IEEE9500's kvar controls monitor switches (sw_<name>_T1).
- Each equipment's BaseVoltage is its bus's (the walk's, as ConnectivityNode.BaseVoltage in bus.cimtbl).
- Found on the way: pce/capacitor.yaml was an orphan copy of pde/capacitor.yaml that hid its dss_defaults
from the reader; removed.
Census of the 31 sweep decks, 2026-11-08 (throwaway scripts; the counts include the
repeated IEEE8500/IEEE9500 copies):
- Loads: 17,447 in 19 decks. Model 1 (ConstantPQ) 14,060; 4 (CVR) 3,184; 5 (ConstantI) 112; 2 (ConstantZ) 86.
q from pf 15,535 (13,356 at 0.97), from kvar 3,381; no load sets both. Two ACEP_PSIL loads give kVA and pf
without kW. 320 K1 loads set xfkVA (and allocationfactor) besides kW. 4 are disabled.
- Capacitors: 106 in 11 decks, every one a single step; 78 single-phase, all wye. CapControls: 59. 48 are
kvar (IEEE8500, IEEE9500, M1), 5 voltage (IEEE13_Assets ×2, IEEE13_OCHRE), 3 J1 volt and 3 time
(IEEE13_Assets ×2 + _geo).
- S4b classes: 950 PVSystems (887 of them 2-phase on a split-phase secondary), 27 Storage, 61 Generators
(ACEP_PSIL and the IEEE9500 copies; models 1, 3, 7) and 8 Reactors (7 series HVMV_Sub_HSB in IEEE8500/IEEE9500,
and K1's neutral reactor T2_neutral, node 4 to node 0 on one bus).
Scope split (approved, S4-1). S4a uses only shapes that exist; S4b needs two new ones.
- S4a: Load, Capacitor, CapControl (shapes load, shunt; the core zip_fractions.cimtbl, DSS-7).
- S4b: PVSystem and Storage (der), Generator (new machine shape: SynchronousMachine), Reactor (new
series_compensator shape), and the full IEEE13_CDPSM artifact directory as the reference golden (D6). Its spec
section follows S4a, as S3b's followed S3a.
Findings that change the plan:
- U3 is closed. IEEE13_OCHRE's two voltage controls and IEEE13_Assets' time control monitor their own
capacitor, so the plan's "all CapControls monitor a line" is wrong. CIM-Tables' Update form breaks the reference
cycle: the compensator row comes first, then the control (naming the compensator's generated cap_<name>_T1),
then Update LinearShuntCompensator: mRID=cap_<name>, RegulatingControl=cc_<name>. Checked: this binds, and
RegulatingControl.RegulatingCondEq is the compensator.
- A 2-phase wye load on a split-phase secondary is two legs to neutral, not one 240 V load. The engine reads its
kV as line-to-line by the √3 rule: 0.208 = 0.120 × √3. So IEEE13_CDPSM's House is phases s1s2, wye,
grounded, with each leg at 120 V. A 240 V load across s1 and s2 would be a 1-phase load on .1.2; no deck has one.
- Every load's kV agrees with its bus within 1 % (17,447 of 17,447; the nearest misses are 2.4 kV against 4.16/√3, 0.07 %). CIM gives
a load no rated voltage: EnergyConsumer.p is at the BaseVoltage. So kV is checked and not written.
- Engine rules (pinned with probes; 13 engine decks, every load's kW and kvar equal the engine's):
- kvar wins over pf in either order;
- pf alone gives q = kW·tan(acos |pf|)·sign(pf) (so a negative kW flips q), and the default pf is 0.88; a pf of 0
or above 1 in magnitude gives a NaN or infinite kvar, so the mapper raises (any device);
- kVA without kW gives kW = kVA·|pf|;
- the load spec type (M4, decision 7, 2026-11-27): the last of kW, kvar and kVA the deck assigns picks the
pair the engine computes from: (kW, pf), (kW, kvar) or (kVA, pf); pf never changes it. kVA=100 kW=50 is
50 kW at pf 0.88, kW=50 kVA=100 is 88 kW, kVA=100 kW=50 kvar=30 is 50 kW and 30 kvar;
- at the end of each command the engine recomputes the other values from the pair (Load.pas:681, 1138-1160):
(kVA, pf) sets kW = kVA·|pf|, and (kW, kvar) sets pf = kW / √(kW² + kvar²) with the sign of kW·kvar. A later
pair can read one of them, so the value depends on where the commands end: kVA=100 kvar=30 is 10 kW in one
command and 88 kW with kvar in a later Edit; kW=50 kvar=30 kW=100 is 53.97 kvar in one command and 60 across
two. A ~ line is a command of its own. The mapper replays the history command by command
(load.load_power over DssModel.commands), so every order maps as the engine gives it;
- kW and xfkVA override each other in the order given: kW=10 pf=0.9 xfkVA=20 allocationfactor=0.5 is
9 kW, but with kW last it is 10 kW. xfkVA is not mapped.
- CapControl defaults: type current, ON 300, OFF 200, PTratio 60, CTratio 60, Delay 15; a Capacitor's are
1200 kvar at 12.47 kV.
Shared phase rule (one helper for every S4 mapper): a 1-terminal device's nodes give its phases.
- Nodes 1/2/3 are A/B/C, and s1/s2 on a split-phase island (DSS-5). An omitted node is the DSS default.
- Wye: phaseConnection=Y, grounded=true. A neutral on node 0, or none, is ground; a neutral on another node
raises.
- Delta: D, grounded=false. A 1-phase delta device needs its two nodes: .3.1 is AC (cimtables names its
phase child C, CIM's delta convention).
- A 3-phase device on a split-phase island raises.
Artifact order. MAPPING_ORDER grows by load, capacitor and capcontrol, after regcontrol. A control references
a line's or its capacitor's Terminal, so it comes after both.
Load¶
Mapper: cimhub_opendss/importer/cimtbl/load.py (map_load). Artifact load.cimtbl; shape load. Atom
tests/atoms/load/loads.dss (after IEEE13_CDPSM):
- models 1, 2, 4 (two CVR pairs) and 5;
- q from pf, from kvar, and from neither (pf 0.88), plus kVA-only;
- a 1-phase delta on .3.1, s1 and s2 legs, a 2-phase s1s2 load and a disabled load.
Identity. EnergyConsumer ld_ + name, lowercased.
Voltage response (DSS-7).
- The master imports the fixed zip_fractions.cimtbl that core writes: zip_constant_pq, zip_constant_z and
zip_constant_i, exponentModel=false.
- Model 1, 2 or 5 names one of them.
- Model 4 names exp_<CVRwatts>_<CVRvars> (exp_0.8_3, exp_1_2). That is one LoadResponseCharacteristic row
per distinct pair, first in load.cimtbl, with exponentModel=true and pVoltageExponent/qVoltageExponent.
Its constant fractions are unset.
- Models 3, 6, 7 and 8 raise.
What raises:
- kV more than 1 % off its bus's phase voltage (LL for delta and 2-3 phases, LN for 1-phase wye);
- xfkVA (K1, which stops earlier on DSS-10);
- Rneut ≥ 0;
- the unmapped models.
enabled=false gives normallyInService=false and the row is written, as for a line. EPRI's ExportCIMXML skips
disabled loads.
Capacitor¶
Mapper: cimhub_opendss/importer/cimtbl/capacitor.py (map_capacitor). Artifact capacitor.cimtbl; shape shunt.
Atom tests/atoms/capacitor/caps.dss (after IEEE13_Assets and IEEE13_OCHRE): a 3-phase and a 1-phase wye bank, a
delta bank, and a bank whose states=[0]. The same atom carries the CapControls below.
Identity. LinearShuntCompensator cap_ + name, lowercased.
One section.
- nomQ = kvar (the total over the phases) and nomU = kv, as rated. K1's 10548920-1 is 13.8 kV on a 13.2 kV
bus, and that stays.
- bPerSection (mS) = nomQ / nomU² (b_per_section): kVAr over kV² is mS, so no factor appears. Every CIM
consumer reads b.
- maximumSections=1. sections = normalSections = the steps states closes (M1's Cap1 and Cap2 are 0), as a
switch's normalOpen follows open when nothing else is given.
What raises: more than one step; bus2; cmatrix or cuf; a nonzero R or XL (IEEE4's Stabilizer
writes R=0, which is untranscribed); normamps/emergamps.
CapControl¶
Mapper: cimhub_opendss/importer/cimtbl/capcontrol.py (map_capcontrol). Artifact capcontrol.cimtbl; shape
shunt. Atom: caps.dss, with controls of four kinds:
- kvar on a line (after IEEE8500);
- voltage on a line with PTratio 20 and PTPhase 1 (after IEEE13_Assets Cap2);
- voltage on its own capacitor (after IEEE13_OCHRE);
- time (after IEEE13_Assets Cap1).
Identity. RegulatingControl cc_ + name, lowercased. The shape had <cap>_ctrl; a DSS control has a name of
its own, and rc_<name> is the RegControl precedent (S4-8).
Rows.
- RegulatingControl with discrete=true, enabled, mode, monitoredPhase, ptRatio, ctRatio,
targetValue, targetDeadband, and targetValueUnitMultiplier=k on a kvar control.
- Terminal = ln_<line>_T<terminal> or cap_<capacitor>_T<terminal>. Any other element raises.
- monitoredPhase is the phase of the monitored terminal's conductor PTPhase (EPRI's rule).
- Then Update LinearShuntCompensator: mRID=cap_<capacitor>, RegulatingControl=cc_<name>, aVRDelay (s)=<Delay>,
controlEnabled=<enabled>. So the capacitor mapper knows nothing of controls, and the own-terminal cycle is
broken (U3).
ON/OFF to target and deadband (derived, on_off_target; EPRI ExportCIMXML's convention, made positive):
- targetValue = (ON + OFF) / 2, targetDeadband = |OFF − ON|. Both are plain floats in cim18v17 (S3a), in primary
units by mode:
- voltage: × PTratio, in V;
- current: × CTratio, in A;
- kvar: in kvar, as the deck gives it, with targetValueUnitMultiplier=k (the core getter reads it in var);
- time: hours from midnight.
- The type fixes which side ON is on: below OFF for voltage and time, above it for kvar and current. A control with
ON on the wrong side raises, so the exporter can invert the pair without a sign (EPRI writes a negative deadband
for kvar).
| control | ON / OFF | ratio | targetValue | targetDeadband |
|---|---|---|---|---|
IEEE8500 CAPBank0A_Ctrl (kvar) |
200 / −300 kvar | — | −50 kvar (k) | 500 kvar (k) |
IEEE13_Assets Cap2 (voltage) |
115 / 125 V | PT 20 | 2,400 V | 200 V |
IEEE13_OCHRE CAP1_ctrl (voltage, own terminal) |
1,950 / 2,500 V | PT 1 | 2,225 V | 550 V |
IEEE13_Assets Cap1 (time) |
8 / 19 h | — | 13.5 h | 11 h |
Untranscribed, with no CIM home: VoltOverride, Vmax, Vmin (45 IEEE8500/IEEE9500 kvar controls) and
DelayOFF, DeadTime. maxAllowedTargetValue limits the target, not the bus voltage, so it is not a stand-in.
This changes how those controls act when the engine solves (S4-5).
What raises: PF and Follow types; CTPhase, VBus, UserModel, ControlSignal; PTPhase AVG/MAX/MIN; a
capacitor or element that no New defines.
Schema (DSS-6):
- dss_defaults for CapControl and Capacitor (the defaults listed above);
- OFFsetting, Delay, DelayOFF and DeadTime ranges → float (they are strings today);
- type stays a string read by unique prefix, as the engine reads J1's volt.
Engine checks (S4a)¶
On the atoms and the engine decks, as in S3: - every load's kW and kvar (already equal on 13 decks with the rule above) and its model; - every capacitor's kvar, kV, connection and step count; the states on the atom (a deck that solves when compiled switches them); - every CapControl's mode, ON and OFF (back from target and deadband), PTratio, CTratio, Delay and monitored element and terminal.
Core and shape changes (S4a)¶
cimhub_core: azip_fractions()document (zip_constant_pq,_z,_i). Thecommonshape gainszip_constant_ifrom it, and a test keeps the two equal.shunt.cimtbl: replace the R11 note with the own-terminal form (control, thenUpdate). Drop the(V)ontargetValue/targetDeadbandhere and involtage_regulator.cimtbl(plain floats, S3a).load.cimtbl: anexp_0.8_3row and a model-4 consumer.- The
cimtbl-shapesskill rows to match.UPSTREAM_REQUESTS.md: U3 closed.
Load, Capacitor and CapControl fields¶
Load¶
| Load field | type | samples | kind | target |
|---|---|---|---|---|
name |
Union[str, LoadName] |
611, 634a, 634b |
copied | EnergyConsumer.name; mRID = ld_ + name, lowercased |
bus1 |
str |
611.3, 634.1, 634.2 |
structural | node; the nodes give the phases: 1/2/3 are A/B/C, and s1/s2 on a split-phase island (DSS-5); an omitted node is the DSS default (conductor k on node k) |
phases |
Optional[int] |
1, 3, 2 |
structural | the conductor count; default 3. On a split-phase island 2 wye phases on 1.2 are two legs to neutral (s1s2, kV is LL by the sqrt 3 rule) |
kV |
Optional[float] |
2.4, 0.277, 4.16 |
structural | checked, not written: the phase voltage it gives (LL for delta and 2-3 phases, LN for 1-phase wye) must be within 1 % of the bus's, else it raises; CIM p is at the BaseVoltage |
kW |
Optional[float] |
170.0, 160.0, 120.0 |
copied | EnergyConsumer.p (kW); consumption is positive p; the last of kW, kvar and kVA picks the pair: (kW, pf), (kW, kvar) or (kVA, pf); each command's end recomputes the rest from it, so the history is replayed command by command (load_power); default 10 |
pf |
Optional[float] |
0.85, 0.97, 0.87 |
derived | q (kVAr) = kW x tan(acos abs(pf)) x sign(pf) with kW last (kVA last: see kVA); pf never changes the pair, so kvar wins in either order (engine-checked); raises unless 0 < |pf| <= 1; default 0.88 |
model |
Union[str, ForwardRef('LoadModel'), NoneType] |
ConstantI, ConstantPQ, ConstantZ |
mapped | EnergyConsumer.LoadResponse; 1 zip_constant_pq, 2 zip_constant_z, 5 zip_constant_i, 4 exp_ |
yearly |
Optional[str] |
Other, Commercial, AggLoadProfile |
mapped | ConformLoad.LoadGroup; the shape's group lg_ |
daily |
Optional[str] |
com |
untranscribed | a second shape has no home: a ConformLoad has one LoadGroup, its yearly shape's (S8) |
duty |
Optional[str] |
untranscribed | a second shape has no home: a ConformLoad has one LoadGroup, its yearly shape's (S8) | |
growth |
Optional[str] |
untranscribed | a GrowthShape reference; not mapped (DSS-11) | |
conn |
Union[str, ForwardRef('ConnectionType'), NoneType] |
wye, delta |
mapped | EnergyConsumer.phaseConnection, EnergyConsumer.grounded; wye -> Y, grounded; delta -> D, not grounded; default wye |
kvar |
Optional[float] |
80.0, 110.0, 90.0 |
copied | EnergyConsumer.q (kVAr); with kvar last: p = kW, q = kvar; the last of kW, kvar and kVA picks the pair: (kW, pf), (kW, kvar) or (kVA, pf); each command's end recomputes the rest from it, so the history is replayed command by command (load_power) |
Rneut |
Optional[float] |
structural | raises when set: no deck in the sweep sets it, so a mapping waits for one (>= 0: a wye neutral impedance) | |
Xneut |
Optional[float] |
structural | raises when set: no deck in the sweep sets it, so a mapping waits for one | |
status |
Union[str, ForwardRef('LoadStatus'), NoneType] |
Variable, Fixed |
untranscribed | Fixed/Exempt: whether load multipliers scale it; DSS solution control; no home in the network profile parts |
load_class |
Optional[int] |
1, 2 |
untranscribed | a DSS report grouping |
Vminpu |
Optional[float] |
0.88, 0.85, 0.75 |
untranscribed | below it the engine models the load as constant Z; DSS solution control; no home in the network profile parts |
Vmaxpu |
Optional[float] |
1.15 |
untranscribed | above it the engine models the load as constant Z; DSS solution control; no home in the network profile parts |
Vminnorm |
Optional[float] |
untranscribed | an EnergyMeter UE threshold; DSS solution control; no home in the network profile parts | |
Vminemerg |
Optional[float] |
untranscribed | an EnergyMeter EEN threshold; DSS solution control; no home in the network profile parts | |
xfkVA |
Optional[float] |
1.70148, 397.465666666668, 25.1736633333333 |
structural | raises: not mapped, and with kW the engine takes whichever comes last (K1 only, behind DSS-10) |
allocationfactor |
Optional[float] |
1.2136, 1.2096, 1.2172 |
structural | raises: it scales xfkVA |
kVA |
Optional[float] |
313.0 |
derived | with kVA last: p = kVA x abs(pf), q = kVA x sin(acos abs(pf)) with the sign of pf (ACEP_PSIL); the last of kW, kvar and kVA picks the pair: (kW, pf), (kW, kvar) or (kVA, pf); each command's end recomputes the rest from it, so the history is replayed command by command (load_power) |
pct_mean |
Optional[float] |
untranscribed | a Monte Carlo setting; DSS solution control; no home in the network profile parts | |
pct_stddev |
Optional[float] |
untranscribed | a Monte Carlo setting; DSS solution control; no home in the network profile parts | |
CVRwatts |
Optional[float] |
0.8, 0.7 |
copied | LoadResponseCharacteristic.pVoltageExponent; model 4 only (the exp_ row); default 1; unused by other models |
CVRvars |
Optional[float] |
3.0 |
copied | LoadResponseCharacteristic.qVoltageExponent; model 4 only (the exp_ row); default 2; unused by other models |
kwh |
Optional[float] |
untranscribed | sizes the load only in the AllocateLoads command | |
kwhdays |
Optional[float] |
untranscribed | sizes the load only in the AllocateLoads command | |
Cfactor |
Optional[float] |
untranscribed | sizes the load only in the AllocateLoads command | |
CVRcurve |
Optional[str] |
untranscribed | a LoadShape reference; LoadShape is not mapped (DSS-11) | |
NumCust |
Optional[int] |
1, 2, 6 |
copied | EnergyConsumer.customerCount; default 1 |
ZIPV |
Union[float, list[float], NoneType] |
untranscribed | used only by model 8, which raises | |
pct_SeriesRL |
Optional[float] |
untranscribed | harmonics model; no home in the network profile parts | |
RelWeight |
Optional[float] |
untranscribed | a reliability weighting | |
Vlowpu |
Optional[float] |
untranscribed | below it the engine models the load as open; DSS solution control; no home in the network profile parts | |
puXharm |
Optional[float] |
untranscribed | harmonics model; no home in the network profile parts | |
XRharm |
Optional[float] |
untranscribed | harmonics model; no home in the network profile parts | |
spectrum |
Optional[str] |
untranscribed | harmonics model; no home in the network profile parts | |
basefreq |
Optional[float] |
untranscribed | no home on a load | |
enabled |
Union[bool, Bool, NoneType] |
False |
copied | EnergyConsumer.normallyInService; default true |
like |
Optional[str] |
untranscribed | the reader resolves like= before mapping |
Capacitor¶
| Capacitor field | type | samples | kind | target |
|---|---|---|---|---|
name |
Union[str, CapacitorName] |
Cap1, Cap2, CAPBank1A |
copied | LinearShuntCompensator.name; mRID = cap_ + name, lowercased |
bus1 |
Optional[str] |
675, 611.3, R20185.1 |
structural | node and phases, as a load's (1/2/3 are A/B/C) |
bus2 |
Optional[str] |
structural | raises when set: no deck in the sweep sets it, so a mapping waits for one (an ungrounded wye or a series capacitor) | |
phases |
Optional[int] |
3, 1 |
structural | the conductor count; default 3 |
kvar |
Union[float, list[float], NoneType] |
[600.0], [100.0], [300.0] |
copied | LinearShuntCompensator.nomQ (kVAr); the total over the phases; more than one step raises; default 1200 |
kv |
Optional[float] |
4.16, 2.4, 7.2 |
copied | LinearShuntCompensator.nomU (kV); as rated (LN for 1-phase wye, else LL); also bPerSection (mS) = nomQ / nomU^2 (b_per_section); default 12.47 |
conn |
Union[str, ForwardRef('ConnectionType'), NoneType] |
wye |
mapped | LinearShuntCompensator.phaseConnection, LinearShuntCompensator.grounded; wye -> Y, grounded; delta -> D, not grounded; default wye |
cmatrix |
Union[float, list[float], NoneType] |
structural | raises when set: no deck in the sweep sets it, so a mapping waits for one (a capacitance matrix instead of kvar) | |
cuf |
Union[float, list[float], NoneType] |
structural | raises when set: no deck in the sweep sets it, so a mapping waits for one (microfarads instead of kvar) | |
R |
Union[float, list[float], NoneType] |
[0.0] |
structural | 0 is untranscribed; nonzero raises (a series R is not mapped) |
XL |
Union[float, list[float], NoneType] |
structural | 0 is untranscribed; nonzero raises (a series reactor is not mapped) | |
Harm |
Union[float, list[float], NoneType] |
untranscribed | the tuning harmonic of the R/XL filter | |
Numsteps |
Optional[int] |
structural | maximumSections; more than 1 raises (unequal steps would need a NonlinearShuntCompensator), and so does 0 (the engine refuses it); default 1 | |
states |
Union[int, list[int], NoneType] |
[0], [1] |
structural | sections = normalSections = the step's state, 0 or 1 (a switch's normalOpen = open rule); anything but one 0/1 value raises; default closed |
normamps |
Optional[float] |
structural | raises when set: no deck in the sweep sets it, so a mapping waits for one (an OperationalLimitSet, as a line's) | |
emergamps |
Optional[float] |
structural | raises when set: no deck in the sweep sets it, so a mapping waits for one | |
faultrate |
Optional[float] |
untranscribed | a reliability setting; no home in the network profile parts | |
pctperm |
Optional[float] |
untranscribed | a reliability setting; no home in the network profile parts | |
repair |
Optional[float] |
untranscribed | a reliability setting; no home in the network profile parts | |
basefreq |
Optional[float] |
untranscribed | no home on a compensator; bPerSection is at the model's frequency | |
enabled |
Union[bool, Bool, NoneType] |
True |
copied | LinearShuntCompensator.normallyInService; default true |
like |
Optional[str] |
untranscribed | the reader resolves like= before mapping |
CapControl¶
| Capcontrol field | type | samples | kind | target |
|---|---|---|---|---|
name |
Union[str, CapcontrolName] |
Cap1, Cap2, CAPBank1A_Ctrl |
copied | RegulatingControl.name; mRID = cc_ + name, lowercased |
element |
Optional[str] |
capacitor.cap1, line.684611, line.CAP_1A |
structural | Terminal = ln_ |
terminal |
Optional[int] |
2, 1 |
structural | the element's terminal: 1 or 2 on a Line (the engine refuses 3), 1 on a Capacitor (a LinearShuntCompensator has one); others raise; default 1 |
capacitor |
Optional[str] |
cap1, cap2, CAPBank1A |
structural | the Update row: LinearShuntCompensator cap_ |
type |
Optional[str] |
time, voltage, kvar |
mapped | RegulatingControl.mode; voltage -> voltage, current -> currentFlow, kvar -> reactivePower, time -> timeScheduled (a unique prefix, as the engine reads it: J1's volt); PF and Follow raise; default current |
PTratio |
Optional[float] |
20.0, 1.0, 60.0 |
copied | RegulatingControl.ptRatio; default 60 |
CTratio |
Optional[float] |
1.0 |
copied | RegulatingControl.ctRatio; default 60 |
ONsetting |
Optional[float] |
8.0, 115.0, 150.0 |
derived | targetValue = (ON + OFF) / 2 (on_off_target); voltage x PTratio (V), current x CTratio (A), kvar in kvar (targetValueUnitMultiplier k), time in hours; ON on the wrong side of OFF for the type raises; default 300 |
OFFsetting |
Optional[float] |
19.0, 125.0, -225.0 |
derived | targetDeadband = abs(OFF - ON) (on_off_target); voltage x PTratio (V), current x CTratio (A), kvar in kvar (targetValueUnitMultiplier k), time in hours; default 200 |
Delay |
Optional[float] |
100.0, 101.0, 102.0 |
copied | LinearShuntCompensator.aVRDelay (s); on the Update row; default 15 |
VoltOverride |
Union[bool, Bool, NoneType] |
True, False |
untranscribed | a voltage override band of a kvar/current control; no home (maxAllowedTargetValue limits the target, not the voltage) |
Vmax |
Optional[float] |
7740.0, 126.0 |
untranscribed | the VoltOverride band (V on the PT secondary) |
Vmin |
Optional[float] |
7110.0, 114.0 |
untranscribed | the VoltOverride band (V on the PT secondary) |
DelayOFF |
Optional[float] |
100.0, 101.0, 102.0 |
untranscribed | CIM has one aVRDelay (Delay); DSS solution control; no home in the network profile parts |
DeadTime |
Optional[float] |
0.0 |
untranscribed | DSS solution control; no home in the network profile parts |
CTPhase |
Optional[str] |
structural | raises when set: no deck in the sweep sets it, so a mapping waits for one | |
PTPhase |
Optional[str] |
1, 2 |
structural | monitoredPhase = the phase of the monitored terminal's conductor PTPhase (default 1); AVG/MAX/MIN raise |
VBus |
Optional[str] |
structural | raises when set: no deck in the sweep sets it, so a mapping waits for one (remote voltage sensing) | |
EventLog |
Union[bool, Bool, NoneType] |
untranscribed | DSS report flag | |
UserModel |
Optional[str] |
structural | raises when set: no deck in the sweep sets it, so a mapping waits for one | |
UserData |
Optional[str] |
structural | raises when set: no deck in the sweep sets it, so a mapping waits for one | |
pctMinkvar |
Optional[float] |
untranscribed | used only by PF control, which raises | |
Reset |
Union[bool, Bool, NoneType] |
untranscribed | a command, not a setting | |
ControlSignal |
Optional[str] |
structural | raises when set: no deck in the sweep sets it, so a mapping waits for one | |
basefreq |
Optional[float] |
untranscribed | no home on a control | |
enabled |
Union[bool, Bool, NoneType] |
copied | RegulatingControl.enabled, LinearShuntCompensator.controlEnabled; default true; controlEnabled on the Update row |
|
like |
Optional[str] |
untranscribed | the reader resolves like= before mapping |
S4b¶
The S4b spec is its own section below, S4b.
Decisions for S4 (approved 2026-11-08)¶
- S4-1: split S4a / S4b as above.
- S4-2: a load's
kVis checked against its bus (1 %) and not written; off by more, it raises. The alternative is to rescale p and q to the bus voltage by the model's exponent. No deck needs that. - S4-3:
kWwithkVAorxfkVAraises, because the order decides the value and the record keeps none.kVAwithoutkWis derived (ACEP_PSIL). Superseded for kVA by decision 7 (2026-11-27): the history's last of kW, kvar and kVA picks the pair (S4a engine rules, above); xfkVA still raises. The alternative is the reader keeping the last of the three; K1 is the only user, and it stops on DSS-10 first. - S4-4: CapControl target/deadband by EPRI's midpoint and width, deadband positive, in primary units by mode (V, A, var, hours). The side of ON is checked per type.
- S4-5: VoltOverride/Vmax/Vmin, DelayOFF and DeadTime untranscribed. A GridAPPS-D extension
(
RegulatingControlvoltage override limits, an off delay) is the candidate if power-flow parity on IEEE8500 needs it. - S4-6: one-step capacitors only.
sections=normalSectionsfromstates.bPerSectionis written (derived). - S4-7: the CapControl writes the compensator's
RegulatingControl,aVRDelayandcontrolEnabledbyUpdate(closes U3). - S4-8:
cc_<name>for a CapControl. - S4-9: disabled loads and capacitors are written with
normallyInService=false, as lines are.
S4b (approved and done 2026-11-08)¶
Result (2026-11-08).
- 22 of 31 sweep decks bind, as expected: S3's six stops, the two ieee9500 copies (Mode=7) and
IEEE123_test_harness (Battery5).
- Engine checks pass on the three atoms and the engine decks for every PV (kW, kvar, kVA, Pmpp, kV), every battery
(kW, state, kVA, kWrated, kWhrated, kWhstored, kV), every series reactor (R, X, buses, ratings) and every
machine's kW, kvar, ratings and PV-bus settings, including PNNL IEEE9500's Diesel620 and LNGengine100,
whose kW is edited after their kvar (S4b-8).
- The IEEE13_CDPSM artifact directory is the golden (D6), all 13 files.
Changes from the proposal, found while building it:
- The engine reads a Storage State by its first letter. charge is not a prefix of charging, but the engine
takes it, so the mapper matches on the first letter as well.
- No voltage window in the PV check. Right after Compile, with no solve, PVSystems.kW()/kvar() already give
the dispatch: cut to fit kVA, off below %Cutout, and independent of voltage. The check compares against those.
- The generator check reads the kW/kvar properties, not Generators.kvar(). After a solve, the latter is the
PV bus's solved kvar (SteamGen1: −1000 at Minkvar).
- RotatingMachinePhase comes from the phases column. cimtables writes one per phase for every machine (a 1-phase
motor's too); the mapper adds nothing.
- SeriesCompensator has no per-phase class, so cimtables refuses a phases column on it. The mapper writes
Update Table Terminal: mRID, phases for the generated rx_<name>_T1/_T2. A request for the shorthand (set
Terminal.phases only, as a TransformerEnd's) is U9 in UPSTREAM_REQUESTS.md.
- A balanced three-phase device leaves phases blank (S4b-9, the user's review): cimtables writes a
<Class>Phase child per token, but in CIM, and in the engine's export (if NPhases = 3 then exit), per-phase
children mean a per-phase device. cimhub_core.cimtbl.phases_cell blanks ABC for loads, capacitors, sources,
switches, PVs, batteries, machines and series reactors. This also changes the S1, S3 and S4a artifacts. Lines keep
phases (their ACLineSegmentPhases are the conductor order), and the engine writes them for 3-phase lines too. The
Terminals of a balanced device lose phases=ABC until CIM-Tables can tell balanced from three single phases (U10).
- Line's ratings code is now line.rating_rows/rating_tables, shared with the reactor. line_phases takes a
label for its errors.
- Wrong schema ranges fixed in passing: the curve references (EffCurve, P-TCurve) → string, and the
WattPriority/PFPriority/LimitCurrent switches → boolean, so yes reads as true.
S4b-8: the deck's assignment order is replayed (approved 2026-11-08). For some properties the engine's value
depends on the order of assignment, and a record keeps only each slot's last value. The engine rules, pinned with
probes:
- Generator: the engine keeps kvar as a power factor. Assigning kvar sets pf = kW / √(kW² + kvar²), with kvar's
sign, at the kW of that moment; assigning kW or pf recomputes kvar = kW·tan(acos |pf|). A pf of 0 (kvar at kW 0)
leaves kvar as assigned. So kW=620 kvar=30 then kW=0 is 0 kvar (IEEE9500's Diesel620), kvar=30 kW=100 is 3
(the pf came from the default kW of 1000), and kW=100 kvar=30 then kW=50 is 15. A bare New is kW 1000, pf 0.88,
kvar 60.
- PVSystem: pf and kvar: the last assigned wins; kvar stays absolute.
- Storage: the engine keeps a discharge and a charge setpoint. A kW > 0 sets the first and discharges, a kW < 0
the second and charges, 0 idles; State picks which runs (kW=40, State=idling, State=discharging discharges
at 40); %Discharge/%Charge put the setpoint back to the rating's share. kWhstored and %stored: the last
wins.
- The engine checks a battery's stored energy when its state is assigned, with the energy of that moment: a
%stored assigned after State=discharging does not wake a battery that idled at its reserve. No deck in the sweep
assigns the energy after the state, so that order raises.
How: DssReader.read_all() returns a DssModel, a GraphModel that also keeps each record's assignment history:
every (slot, value) in deck order, from New, edits, BatchEdit, and the slots like= copies (first).
DssModel.assignments(record) and last_of(record, *slots) read it, and the mappers replay it
(generator.dispatched_kvar, storage.battery_dispatch, PVSystem's last_of(pf, kvar)). Only the history replaces
order guesses; the records stay verbatim.
A Load replays its history command by command (load.load_power over DssModel.commands, decision 7). kVA in a
later command takes the pf that kvar implied (kW=10 kvar=3 then kVA=20 is 19.2 kW), but in the same command the
pf before kvar (S4a engine rules).
S4b maps the rest of the injections and the series reactor: PVSystem and Storage (shape der), Generator (new
shape synchronous_machine) and Reactor (new shape series_compensator). Its exit is the full IEEE13_CDPSM artifact
directory as the reference golden (D6). The two new shape names are the ones RAW's plan requests from core (its C2),
so the two waves share them. RAW adds its bus-branch variants and GeneratingUnit later.
Census of the 31 sweep decks, 2026-11-08 (30 read; the balanced ieee9500_2025 copy stops in the reader, as in S3):
- PVSystem: 950 in 7 decks. 887 are 2-phase on a split-phase secondary: 356 at kV 0.208 (the IEEE9500 copies)
and 531 at 0.24 (ieee9500_2025). 45 are 1-phase and 13 are 3-phase.
- pf is always 1.0, and no PV sets kvar.
- irradiance is 1.0 or 0.8 (IEEE13_CDPSM). Only ieee9500 sets %Cutin/%Cutout, at 0.1.
- 3 PVs are delta (IEEE9500's M1047PV-3, 3-phase).
- IEEE9500's PVFarm1 has Pmpp 1200 on kVA 1000, so the inverter caps it.
- Storage: 27 in 5 decks.
- States: 22 charge/charging, 3 discharging and 2 idling. pf is 1.0 wherever it is set, and no record
sets kvar.
- 21 set kW, always after state= (IEEE9500: state=charge kW=150; IEEE123: state=charge kW=-0.0).
- 6 are delta. No record sets both kWhstored and %stored.
- Generator: 61 in 3 decks (ACEP_PSIL and the IEEE9500 copies), all 3-phase.
- Models: 41 ConstantPQ, 15 CurrentLimited (7) and 5 ConstantPV (3). 18 are delta.
- Every record sets kVA. Xdp/Xdpp/H are on 45. Maxkvar/Minkvar are never set.
- One IEEE9500 machine sets both pf=0.98 and kvar=0 at kW=0.
- Reactor: 8.
- 7 are IEEE8500/IEEE9500's HVMV_Sub_HSB: series, 3-phase, X 14.798 Ω, R 0, normamps = emergamps = 400.
- 1 is K1's T2_neutral, K_LSB.4 to K_LSB.0 on one bus.
Engine rules (pinned with probes in /tmp; the defaults are the engine's readback of a bare New):
- PVSystem.
- The panel's power is Pmpp × irradiance, and %Pmpp caps it: the available power is min(Pmpp × irradiance,
Pmpp × %Pmpp / 100). Probed 2026-11-10: Pmpp 100 at irradiance 0.5 gives 50 at %Pmpp 60 and 150, and 10 at
%Pmpp 10; at irradiance 1.2 it gives 120 at %Pmpp 150. q comes from pf (q = P·tan(acos |pf|), with pf's sign)
or from kvar.
- Over kVA, P is cut to √(kVA² − q²) (var priority, the default), so Pmpp 1200 on kVA 1000 gives 1000.
- The PV is off (P = 0) when the panel's power, before the %Pmpp cap, is below %Cutout × kVA / 100
(irradiance 0.5 on Pmpp 100 and kVA 100 runs at %Pmpp 10, giving 10 under a 20 % cut-out). The initial state uses
%Cutout, not %Cutin: 25 % with cut-in 30 / cut-out 5 runs, and with cut-in 5 / cut-out 30 it is off.
- pf and kvar override each other in the order given (unlike a load, where kvar always wins).
- Defaults: 3 phases, kV 12.47, irradiance 1, Pmpp 500, %Pmpp 100, pf 1, kVA 500, %Cutin and %Cutout 20,
Vminpu 0.9, wye. kvarMax and kvarMaxAbs default to kVA.
- Storage.
- State and kW override each other in the order given. A kW > 0 discharges, < 0 charges, and 0 (or −0.0)
idles.
- So IEEE9500's state=charge kW=150 discharges at 150 kW, and IEEE123's state=charge kW=-0.0 idles.
- With no kW: charging draws kWrated × %Charge / 100, discharging gives kWrated × %Discharge / 100, and
idling draws %IdlingkW × kWrated / 100 (1 kW on 100). Every |P| is capped at kVA.
- The battery idles instead when it is told to charge while full, or to discharge at or below %reserve.
- kWhstored and %stored override each other in order.
- With pf ≠ 1, the engine caps q at a kvarMax left over from the default kVA (pf 0.9 on 100 kW gives 25 kvar).
- Defaults: kV 12.47, kWrated 25, kVA = kWrated, kWhrated 50, %stored 100, %reserve 20, State idling,
%Charge/%Discharge 100, %EffCharge/%EffDischarge 90, %IdlingkW 1, pf 1, wye.
- Generator.
- q comes from pf or kvar, and the two override each other in order.
- Defaults: kW 1000, pf 0.88, kV 12.47, model 1, Vpu 1, kVA 1.2 × kW, Maxkvar = 2 × kvar, Minkvar = −2 × kvar.
Each kW, pf or kvar assignment resets Maxkvar and Minkvar to ±2 × kvar, so a Maxkvar or Minkvar holds only when
assigned after the last of them (engine-checked 2026-11-24).
- Model 3 regulates its terminal to Vpu within Maxkvar/Minkvar. Model 7 dispatches as model 1.
- 2-phase PV at 0.24 kV on 120 V legs (ieee9500_2025): the engine's base is 0.24/√3 = 138.6 V. The legs sit at
0.866 pu, below Vminpu, so it gives 92.8 % of Pmpp. At 0.208 kV it gives 100 %. This is a power-flow result, not a
setting; the mapping keeps the deck's kV (S4b-4).
- The engine's CIM export disagrees with itself on sign. ExportCIMXML.pas writes PowerElectronicsConnection.p
= −kW but RotatingMachine.p = +kW. cim18v17 documents both as the load sign, so S4b writes −kW for both (S4b-1).
Expected sweep: 22 of 31 decks bind. Besides S3's six, three stop:
- CIMHub_2_0's two ieee9500 copies: PVFarm1 ... Mode=7 reads as model=7, which the engine rejects too
("7" is not a valid value), so those decks do not compile.
- IEEE123_test_harness: Battery5 is phases=1 on 108.1.2.3, which puts its neutral on node 2. The shared phase
rule raises (S4b-6).
Shared rules (S4b)¶
- Terminal: the S4 shared phase rule (
injection.device_terminal) for PVSystem, Storage and Generator. ratedUis line to line (S4b-4): the deck's kV, × √3 for a 1-phase wye device; the exporter inverts it. This matches the engine's CIM export, which is where GridAPPS-D's files come from. CIMHub_2_0 wrote kV unchanged; the round-trip comparison lists that difference. ratedU is not checked against the bus: a 240 V inverter on 120 V legs stays 240 V.- Sign: p and q are the load sign: generation and discharge are negative, q = −kvar (S4b-1).
- pf with kvar: the deck's assignment order decides, as in the engine (S4b-8, which replaced S4b-2's raise).
- Inverter cap (PVSystem and Storage):
inverter_power(available, q, kva), the engine's var-priority cut. enabled=falsegivesnormallyInService=false(S4-9).
PVSystem¶
Mapper importer/cimtbl/pvsystem.py (map_pvsystem). Artifact pvsystem.cimtbl; shape der. Atom
tests/atoms/der/der.dss:
- the IEEE13_CDPSM PVs: 3-phase at irradiance 0.8, and 2-phase s1s2 at 0.208;
- a 1-phase leg, a delta PV, a kVA-capped PV, one below cut-out, one with a negative pf, one with kvar, and one
capped at %Pmpp (irradiance 0.9 at %Pmpp 60 gives 6 kW).
Identity. PowerElectronicsConnection pv_ + name and PhotoVoltaicUnit pv_<name>_unit, lowercased. The
prefix keeps IEEE13_CDPSM's PVSystem.School and Storage.School apart.
Rows.
- Connection:
- node, phases, phaseConnection (cim18v17's PowerElectronicsConnection has no grounded);
- ratedS = kVA, ratedU (S4b-4);
- p = −P and q = −q, by the rules above (derived, pv_power);
- maxQ = kvarMax, minQ = −kvarMaxAbs, maxIFault = 1 / Vminpu (the engine's export convention);
- normallyInService, BaseVoltage, EquipmentContainer.
- Unit: maxP = Pmpp, minP = 0, irradiance = irradiance (kW/m2; the gridappsd extension), and its
connection.
What raises:
- model other than 1;
- EffCurve or P-TCurve (both change the snapshot power);
- WattPriority or PFPriority set to yes; a nonzero %PminNoVars or %PminkvarMax;
- UserModel/UserData; ControlMode=GFM; Balanced or LimitCurrent set to yes;
- a kvar above kVA, on or off (M38, decision 9, 2026-11-27): below %Cutout the engine clamps it to kvarMax
(Pmpp=100 kVA=100 irradiance=0.05 kvar=150 gives 100 kvar), and reactive capability is not modelled yet.
Untranscribed:
- the Yearly/Daily/Duty and T-curves, which are time series that a snapshot does not use;
- %Cutin, which only acts after the inverter turns off;
- %R, %X, kVDC, Kp, PITol, SafeVoltage, SafeMode, DynamicEq, DynOut, AmpLimit, AmpLimitGain
(dynamics);
- Vmaxpu, Temperature (it acts only through a P-TCurve), VarFollowInverter (InvControl), class, spectrum,
basefreq, DutyStart, DebugTrace.
Storage¶
Mapper importer/cimtbl/storage.py (map_storage). Artifact storage.cimtbl; shape der. Atom
tests/atoms/der/der.dss:
- the three IEEE13_CDPSM batteries (charging, discharging, idling);
- state=charge kW=150 (IEEE9500) and state=charge kW=-0.0 (IEEE123);
- a kVA-capped battery, one with %stored, and a delta battery.
Identity. PowerElectronicsConnection storage_ + name, and BatteryUnit storage_<name>_unit.
Rows.
- Connection: as a PV's, with ratedS = kVA (default kWrated). q = 0.
- Unit:
- ratedE = kWhrated;
- storedE = kWhstored, else %stored × kWhrated / 100;
- minimumE = %reserve × kWhrated / 100;
- maxP = kWrated, minP = −kWrated;
- chargingEfficiency = %EffCharge and dischargingEfficiency = %EffDischarge (percent);
- idlingP = %IdlingkW × kWrated / 100.
- State and p (derived, battery_dispatch; S4b-8): the deck's kW, State, %Discharge and %Charge assignments
replayed in order (above). Discharging p = −min(setpoint, kVA), charging p = min(setpoint, kVA), idling waiting
with p = idlingP. A setpoint is the last kW of its sign, else kWrated × %Discharge (or %Charge) / 100.
- The row comment names an override, for example "kW=150 after State=charging: discharging".
What raises:
- a battery that the engine would idle instead: charging when full, or discharging at or below %reserve;
- kWhstored, %stored, kWhrated or %reserve assigned after the last State or kW (above);
- pf ≠ 1 or kvar ≠ 0 (because of the engine's kvarMax quirk above; no deck has one);
- DispMode other than default;
- model other than 1;
- EffCurve, UserModel/UserData, DynaDLL/DynaData;
- WattPriority/PFPriority set to yes, a nonzero %PminNoVars/%PminkvarMax, Balanced/LimitCurrent set to yes;
- a negative %IdlingkW (decision 12, 2026-11-27): the engine takes it and the idling battery generates, but the
exporter raises on a negative idlingP, so the import raises too.
Untranscribed: the curves, DischargeTrigger/ChargeTrigger/TimeChargeTrig (dispatch modes, which raise),
%Idlingkvar (deprecated), %CutIn/%CutOut, %kWRated, Vmaxpu, and the dynamics slots, as for PVSystem.
Generator¶
Mapper importer/cimtbl/generator.py (map_generator). Artifact generator.cimtbl; shape synchronous_machine.
Atom tests/atoms/generator/gens.dss:
- models 1, 3 and 7; wye and delta;
- q from pf, from kvar, and from the default 0.88;
- kW=0 pf=0.98 kvar=0; and a 1-phase machine;
- model 3 with Maxkvar alone (capped), and with Maxkvar and Minkvar before a kW edit (reset).
Identity. SynchronousMachine gen_ + name. A model 3 control is gen_<name>_ctrl: the machine has no
control of its own name, as the shape's <cap>_ctrl had.
Rows.
- node, phases;
- ratedS = kVA (default 1.2 × kW), ratedU (S4b-4);
- p = −kW, q = −q;
- type=generator, operatingMode=generator;
- earthing = not delta (S4b-5);
- normallyInService, BaseVoltage, EquipmentContainer.
Model 3 (PV bus):
- maxQ = Maxkvar and minQ = Minkvar (default ±2 × kvar, reset by each kW, pf or kvar assignment:
reactive_limits);
- a RegulatingControl gen_<name>_ctrl:
- mode=voltage, discrete=false, enabled=true;
- targetValue = Vpu × ratedU in kV with targetValueUnitMultiplier=k, targetDeadband=0;
- Terminal=gen_<name>_T1;
- then Update SynchronousMachine: mRID, RegulatingControl, controlEnabled=true. This is S4a's own-terminal form
(U3).
Model 7 maps as model 1, with a row note: below Vminpu it limits current, which is power-flow behaviour.
What raises:
- models 2, 4, 5 and 6; UserModel/ShaftModel;
- Maxkvar/Minkvar on a model other than 3.
Untranscribed:
- Xd, Xdp, Xdpp, H, D, XRdp (dynamics);
- Vminpu, Vmaxpu, PVFactor (a solver aid), Status, DispMode, DispValue, ForceOn;
- the curves, the fuel slots, class, spectrum, basefreq.
Reactor¶
Mapper importer/cimtbl/reactor.py (map_reactor). Artifact reactor.cimtbl; shape series_compensator. Atom
tests/atoms/reactor/reactors.dss: IEEE8500's HVMV_Sub_HSB and a 1-phase series reactor with R.
Identity. SeriesCompensator rx_ + name.
Rows.
- node1, node2, phases (the line rule, line_phases);
- r = R and x = X (Ω per phase); r0 = R and x0 = X, as in the engine's export (no mutual coupling);
- normallyInService, BaseVoltage (bus1's), EquipmentContainer;
- rx_<name>_limits, an OperationalLimitSet with CurrentLimits _norm/_emerg. These come from the deck's own
normamps/emergamps only (nothing from the engine's kvar-derived defaults), as for a line. Line's ratings code is
shared.
What raises:
- no bus2, or bus2 on the same bus: a shunt or neutral reactor, such as K1's T2_neutral (K1 stops on DSS-10
first);
- X unset, or kvar given (X derived from kvar and kV);
- Rmatrix/Xmatrix, Z/Z1/Z2/Z0, LmH, Rp, Parallel=yes, RCurve/LCurve.
Untranscribed: kV (it acts only with kvar), conn (a series reactor has no neutral), faultrate/pctperm/
repair, basefreq.
Artifact order, schema, shapes (S4b)¶
- Order:
MAPPING_ORDERgains reactor after line (it is a branch, and its limits use the common limit types), then pvsystem, storage and generator after capcontrol. - Schema (DSS-6). The
dss_defaults of the four classes become the engine readback above. This fixes PVSystem'spf0.88 → 1, itsVminpu0 → 0.9, and Generator'sXdp0.27 → 0.28. The derived defaults (kvarMax, Storage kVA, Generator kVA and Maxkvar) stay in the mapper, named. - Core shapes:
der.cimtbl: gainsphaseConnection,maxQ/minQ/maxIFault, a 2-phases1s2PV, and the battery'sminimumE, efficiencies,idlingPandmaxP/minP.- New
synchronous_machine.cimtbl: a model 1 machine, and a PV-bus machine with itsRegulatingControland theUpdate. - New
series_compensator.cimtbl: a reactor between two nodes, with its limit set. - The
cimtbl-shapesskill rows to match.
Engine checks (S4b)¶
On the atoms and the engine decks:
- PVSystem: kVA, kV, Pmpp; p and q against the engine's dispatch (PVSystems.kW()/kvar() after Compile);
- Storage: kWrated, kVA, kWhrated, kWhstored, the state, and the kW/kvar properties;
- Generator: the kW and kvar properties, kVA, kV, delta, and model/Vpu/Maxkvar/Minkvar for model 3;
- Reactor: R, X, both buses, normamps and emergamps.
IEEE13_CDPSM golden directory (D6)¶
tests/goldens/IEEE13_CDPSM/ holds every part to_cimtbl writes (master, bus, zip_fractions, each class's
document), not only the master and bus. The orchestrator test compares the whole directory, and
CIMHUB_UPDATE_GOLDENS=1 rewrites it.
PVSystem, Storage, Generator and Reactor fields¶
Generated from each mapper's FIELDS (samples: the 31 sweep decks).
| Pvsystem field | type | samples | kind | target |
|---|---|---|---|---|
name |
Union[str, PvsystemName] |
House, School, PVFarm1 |
copied | PowerElectronicsConnection.name; mRID = pv_ + name, lowercased; the unit is |
phases |
Optional[int] |
2, 3, 1 |
structural | the conductor count; default 3 |
bus1 |
Optional[str] |
House.1.2, 634, M1047PV-3 |
structural | node and phases, by the S4 shared phase rule |
kv |
Optional[float] |
0.208, 0.48, 12.47 |
derived | ratedU (kV, LL) = kv, x sqrt 3 for 1-phase wye (S4b-4); not checked against the bus; default 12.47 |
irradiance |
Optional[float] |
0.8, 1.0 |
copied | PhotoVoltaicUnit.irradiance (kW/m2); also p (pv_power); default 1 |
Pmpp |
Optional[float] |
5.0, 300.0, 1000.0 |
copied | PhotoVoltaicUnit.maxP (kW); also p (pv_power); default 500 |
pct_Pmpp |
Optional[float] |
derived | p is capped at Pmpp x %Pmpp / 100 (pv_power); default 100 | |
Temperature |
Optional[float] |
untranscribed | acts only through a P-TCurve, which raises | |
pf |
Optional[float] |
1.0 |
derived | q = -kW x tan(acos abs(pf)) x sign(pf), unless kvar was assigned after it (the last of the two wins, S4b-8); default 1 |
conn |
Optional[str] |
wye, delta |
mapped | PowerElectronicsConnection.phaseConnection; wye -> Y, delta -> D; default wye |
kvar |
Optional[float] |
derived | q (kVAr) = -kvar (the load sign), unless pf was assigned after it; above kVA it raises, off or on (the engine clamps it to kvarMax; decision 9) | |
kVA |
Optional[float] |
5.0, 300.0, 1500.0 |
copied | PowerElectronicsConnection.ratedS (kVA); also caps p (var priority); default 500 |
pct_Cutin |
Optional[float] |
0.1 |
structural | acts only after the inverter turns off; the snapshot state uses %Cutout; a yearly sample between %Cutout and %Cutin raises (S9); default 20 |
pct_Cutout |
Optional[float] |
0.1 |
derived | p = 0 when Pmpp x irradiance is below %Cutout of kVA, q too unless kvar is set (VarFollowInverter); default 20 |
EffCurve |
Optional[str] |
structural | raises: an efficiency curve changes the snapshot power | |
P_TCurve |
Optional[str] |
structural | raises: a temperature curve changes the snapshot power | |
pct_R |
Optional[float] |
untranscribed | a dynamics setting; no home in the network profile parts | |
pct_X |
Optional[float] |
untranscribed | a dynamics setting; no home in the network profile parts | |
model |
Optional[int] |
7, 1 |
structural | 1 (constant P, PF) only; any other raises (ieee9500's Mode=7 is model=7, which the engine rejects too); default 1 |
Vminpu |
Optional[float] |
derived | maxIFault = 1 / Vminpu (the engine's CIM export); default 0.9 | |
Vmaxpu |
Optional[float] |
untranscribed | above it the engine models the PV as constant Z; a power-flow setting | |
Balanced |
Union[bool, Bool, NoneType] |
structural | raises when yes: no deck in the sweep sets it, so a mapping waits for one | |
LimitCurrent |
Union[bool, Bool, NoneType] |
structural | raises when yes: no deck in the sweep sets it, so a mapping waits for one | |
yearly |
Optional[str] |
mapped | EnergyConnectionSchedule.name; the PV's EnergyConnectionSchedule |
|
daily |
Optional[str] |
untranscribed | a time-series curve; a snapshot does not use it (DSS-11) | |
duty |
Optional[str] |
untranscribed | a time-series curve; a snapshot does not use it (DSS-11) | |
Tyearly |
Optional[str] |
untranscribed | a time-series curve; a snapshot does not use it (DSS-11) | |
Tdaily |
Optional[str] |
untranscribed | a time-series curve; a snapshot does not use it (DSS-11) | |
Tduty |
Optional[str] |
untranscribed | a time-series curve; a snapshot does not use it (DSS-11) | |
class_class |
Optional[int] |
untranscribed | a DSS report grouping | |
UserModel |
Optional[str] |
structural | raises when set: no deck in the sweep sets it, so a mapping waits for one | |
UserData |
Optional[str] |
structural | raises when set: no deck in the sweep sets it, so a mapping waits for one | |
debugtrace |
Union[bool, Bool, NoneType] |
untranscribed | a DSS debugging switch | |
VarFollowInverter |
Union[bool, Bool, NoneType] |
derived | yes: an inverter that is off gives no kvar either (pv_power, engine-checked); default no | |
DutyStart |
Optional[float] |
untranscribed | a time-series curve; a snapshot does not use it (DSS-11) | |
WattPriority |
Union[bool, Bool, NoneType] |
structural | raises when yes: no deck in the sweep sets it, so a mapping waits for one (var priority is mapped) | |
PFPriority |
Union[bool, Bool, NoneType] |
structural | raises when yes: no deck in the sweep sets it, so a mapping waits for one | |
pct_PminNoVars |
Optional[float] |
structural | raises when nonzero: no deck in the sweep sets it, so a mapping waits for one | |
pct_PminkvarMax |
Optional[float] |
structural | raises when nonzero: no deck in the sweep sets it, so a mapping waits for one | |
kvarMax |
Optional[float] |
copied | PowerElectronicsConnection.maxQ (kVAr); default kVA |
|
kvarMaxAbs |
Optional[float] |
derived | minQ (kVAr) = -kvarMaxAbs; default kVA | |
kVDC |
Optional[float] |
untranscribed | a dynamics setting; no home in the network profile parts | |
Kp |
Optional[float] |
untranscribed | a dynamics setting; no home in the network profile parts | |
PITol |
Optional[float] |
untranscribed | a dynamics setting; no home in the network profile parts | |
SafeVoltage |
Optional[float] |
untranscribed | a dynamics setting; no home in the network profile parts | |
SafeMode |
Union[bool, Bool, NoneType] |
untranscribed | a dynamics setting; no home in the network profile parts | |
DynamicEq |
Optional[str] |
untranscribed | a dynamics setting; no home in the network profile parts | |
DynOut |
Union[str, list[str], NoneType] |
untranscribed | a dynamics setting; no home in the network profile parts | |
ControlMode |
Optional[str] |
structural | GFL only; GFM raises (no deck in the sweep sets it, so a mapping waits for one) | |
AmpLimit |
Optional[float] |
untranscribed | a dynamics setting; no home in the network profile parts | |
AmpLimitGain |
Optional[float] |
untranscribed | a dynamics setting; no home in the network profile parts | |
spectrum |
Optional[str] |
untranscribed | harmonics model; no home in the network profile parts | |
basefreq |
Optional[float] |
untranscribed | no home on an inverter | |
enabled |
Union[bool, Bool, NoneType] |
copied | PowerElectronicsConnection.normallyInService; default true |
|
like |
Optional[str] |
untranscribed | the reader resolves like= before mapping |
| Storage field | type | samples | kind | target |
|---|---|---|---|---|
name |
Union[str, StorageName] |
BatIdle, House, School |
copied | PowerElectronicsConnection.name; mRID = storage_ + name, lowercased; the unit is |
phases |
Optional[int] |
3, 2, 1 |
structural | the conductor count; default 3 |
bus1 |
Optional[str] |
634, House.1.2, m2001-ESS1 |
structural | node and phases, by the S4 shared phase rule |
kv |
Optional[float] |
0.48, 0.208, 2.4 |
derived | ratedU (kV, LL) = kv, x sqrt 3 for 1-phase wye (S4b-4); default 12.47 |
conn |
Optional[str] |
wye, delta |
mapped | PowerElectronicsConnection.phaseConnection; wye -> Y, delta -> D; default wye |
kW |
Optional[float] |
150.0, -0.0, 0.0 |
derived | replayed in deck order (battery_dispatch, S4b-8): > 0 sets the discharge setpoint and discharging, < 0 the charge setpoint and charging, 0 waiting; capped at kVA |
kvar |
Optional[float] |
structural | raises when nonzero: no deck in the sweep sets it, so a mapping waits for one (q = 0) | |
pf |
Optional[float] |
1.0 |
structural | 1 only; another raises (the engine caps q by a kvarMax left from the default kVA); default 1 |
kVA |
Optional[float] |
250.0, 125.0, 200.0 |
copied | PowerElectronicsConnection.ratedS (kVA); also caps p; default kWrated |
pct_Cutin |
Optional[float] |
untranscribed | an inverter cut-in; 0 by default for storage | |
pct_Cutout |
Optional[float] |
untranscribed | an inverter cut-out; 0 by default for storage | |
EffCurve |
Optional[str] |
structural | raises: an efficiency curve changes the snapshot power | |
VarFollowInverter |
Union[bool, Bool, NoneType] |
untranscribed | acts only with an InvControl | |
kvarMax |
Optional[float] |
copied | PowerElectronicsConnection.maxQ (kVAr); default kVA |
|
kvarMaxAbs |
Optional[float] |
derived | minQ (kVAr) = -kvarMaxAbs; default kVA | |
WattPriority |
Union[bool, Bool, NoneType] |
structural | raises when yes: no deck in the sweep sets it, so a mapping waits for one | |
PFPriority |
Union[bool, Bool, NoneType] |
structural | raises when yes: no deck in the sweep sets it, so a mapping waits for one | |
pct_PminNoVars |
Optional[float] |
structural | raises when nonzero: no deck in the sweep sets it, so a mapping waits for one | |
pct_PminkvarMax |
Optional[float] |
structural | raises when nonzero: no deck in the sweep sets it, so a mapping waits for one | |
kWrated |
Optional[float] |
100.0, 5.0, 250.0 |
copied | BatteryUnit.maxP (kW); minP = -kWrated; also p by State; default 25 |
pct_kWrated |
Optional[float] |
untranscribed | the kW limit of the dispatch modes, which raise | |
kWhrated |
Optional[float] |
200.0, 13.5, 500.0 |
copied | BatteryUnit.ratedE (kWh); default 50 |
kWhstored |
Optional[float] |
100.0, 5.0, 135.0 |
copied | BatteryUnit.storedE (kWh); unless %stored was assigned after it (the last wins) |
pct_stored |
Optional[float] |
60.0, 40.0, 35.0 |
derived | storedE (kWh) = %stored x kWhrated / 100 unless kWhstored was assigned after it; default 100 |
pct_reserve |
Optional[float] |
30.0 |
derived | minimumE (kWh) = %reserve x kWhrated / 100; default 20 |
State |
Optional[str] |
idling, charging, discharging |
mapped | BatteryUnit.batteryState; charging, discharging, idling -> waiting (by the first letter, as the engine reads it: the decks' charge); picks the setpoint that runs, replayed with kW (S4b-8); default idling |
pct_Discharge |
Optional[float] |
derived | the discharge setpoint kWrated x %Discharge / 100 until a kW > 0 sets it; default 100 | |
pct_Charge |
Optional[float] |
derived | the charge setpoint kWrated x %Charge / 100 until a kW < 0 sets it; default 100 | |
pct_EffCharge |
Optional[float] |
copied | BatteryUnit.chargingEfficiency (percent); default 90 |
|
pct_EffDischarge |
Optional[float] |
copied | BatteryUnit.dischargingEfficiency (percent); default 90 |
|
pct_IdlingkW |
Optional[float] |
derived | idlingP (kW) = %IdlingkW x kWrated / 100, also p when waiting; default 1; negative raises (decision 12) | |
pct_Idlingkvar |
Optional[float] |
untranscribed | deprecated in the engine | |
pct_R |
Optional[float] |
untranscribed | a dynamics setting; no home in the network profile parts | |
pct_X |
Optional[float] |
untranscribed | a dynamics setting; no home in the network profile parts | |
model |
Optional[int] |
structural | 1 (constant P, PF) only; any other raises; default 1 | |
Vminpu |
Optional[float] |
derived | maxIFault = 1 / Vminpu (the engine's CIM export); default 0.9 | |
Vmaxpu |
Optional[float] |
untranscribed | above it the engine models the battery as constant Z; a power-flow setting | |
Balanced |
Union[bool, Bool, NoneType] |
structural | raises when yes: no deck in the sweep sets it, so a mapping waits for one | |
LimitCurrent |
Union[bool, Bool, NoneType] |
structural | raises when yes: no deck in the sweep sets it, so a mapping waits for one | |
yearly |
Optional[str] |
mapped | EnergyConnectionSchedule.name; DispMode=follow: the battery's EnergyConnectionSchedule |
|
daily |
Optional[str] |
untranscribed | a time-series curve; a snapshot does not use it (DSS-11) | |
duty |
Optional[str] |
untranscribed | a time-series curve; a snapshot does not use it (DSS-11) | |
DispMode |
Optional[str] |
structural | default, or follow with a yearly shape (S9); another dispatch mode raises (no deck in the sweep sets it, so a mapping waits for one) | |
DischargeTrigger |
Optional[float] |
untranscribed | acts only in a dispatch mode, which raises | |
ChargeTrigger |
Optional[float] |
untranscribed | acts only in a dispatch mode, which raises | |
TimeChargeTrig |
Optional[float] |
untranscribed | acts only in a dispatch mode, which raises | |
class_class |
Optional[int] |
untranscribed | a DSS report grouping | |
DynaDLL |
Optional[str] |
structural | raises when set: no deck in the sweep sets it, so a mapping waits for one | |
DynaData |
Optional[str] |
structural | raises when set: no deck in the sweep sets it, so a mapping waits for one | |
UserModel |
Optional[str] |
structural | raises when set: no deck in the sweep sets it, so a mapping waits for one | |
UserData |
Optional[str] |
structural | raises when set: no deck in the sweep sets it, so a mapping waits for one | |
debugtrace |
Union[bool, Bool, NoneType] |
untranscribed | a DSS debugging switch | |
kVDC |
Optional[float] |
untranscribed | a dynamics setting; no home in the network profile parts | |
Kp |
Optional[float] |
untranscribed | a dynamics setting; no home in the network profile parts | |
PITol |
Optional[float] |
untranscribed | a dynamics setting; no home in the network profile parts | |
SafeVoltage |
Optional[float] |
untranscribed | a dynamics setting; no home in the network profile parts | |
SafeMode |
Union[bool, Bool, NoneType] |
untranscribed | a dynamics setting; no home in the network profile parts | |
DynamicEq |
Optional[str] |
untranscribed | a dynamics setting; no home in the network profile parts | |
DynOut |
Union[str, list[str], NoneType] |
untranscribed | a dynamics setting; no home in the network profile parts | |
ControlMode |
Optional[str] |
structural | GFL only; GFM raises (no deck in the sweep sets it, so a mapping waits for one) | |
AmpLimit |
Optional[float] |
untranscribed | a dynamics setting; no home in the network profile parts | |
AmpLimitGain |
Optional[float] |
untranscribed | a dynamics setting; no home in the network profile parts | |
spectrum |
Optional[str] |
untranscribed | harmonics model; no home in the network profile parts | |
basefreq |
Optional[float] |
untranscribed | no home on an inverter | |
enabled |
Union[bool, Bool, NoneType] |
copied | PowerElectronicsConnection.normallyInService; default true |
|
like |
Optional[str] |
untranscribed | the reader resolves like= before mapping |
| Generator field | type | samples | kind | target |
|---|---|---|---|---|
name |
Union[str, GeneratorName] |
Diesel590, Diesel620, LNGengine100 |
copied | SynchronousMachine.name; mRID = gen_ + name, lowercased |
phases |
Optional[int] |
structural | the conductor count; default 3 | |
bus1 |
Optional[str] |
m1089-DIES1, m1209-DIES1, M1142-LNG1 |
structural | node and phases, by the S4 shared phase rule |
kv |
Optional[float] |
0.48, 12.47 |
derived | ratedU (kV, LL) = kv, x sqrt 3 for 1-phase wye (S4b-4); default 12.47 |
kW |
Optional[float] |
0.0, 50.0, 100.0 |
derived | p (kW) = -kW (the load sign); default 1000 |
pf |
Optional[float] |
0.95, 0.98 |
derived | q (kVAr) = -kvar, kvar replayed from the kW, pf and kvar assignments in deck order (dispatched_kvar, S4b-8): each kW or pf recomputes kvar = kW x tan(acos abs(pf)); default 0.88 |
kvar |
Optional[float] |
15.0, 30.0, 5.0 |
derived | sets the pf, kW / kVA with kvar's sign, at the kW of that moment; a pf of 0 (kvar at kW 0) leaves kvar as set (dispatched_kvar, S4b-8) |
model |
Union[str, ForwardRef('GeneratorModel'), NoneType] |
CurrentLimited, ConstantPQ, ConstantPV |
structural | 1 and 7 dispatch kW/kvar; 3 adds a voltage RegulatingControl; 2, 4, 5, 6 raise; default 1 |
Vminpu |
Optional[float] |
untranscribed | below it the engine models the machine as constant Z; a power-flow setting | |
Vmaxpu |
Optional[float] |
untranscribed | above it the engine models the machine as constant Z; a power-flow setting | |
yearly |
Optional[str] |
mapped | EnergyConnectionSchedule.name; the machine's EnergyConnectionSchedule |
|
daily |
Optional[str] |
untranscribed | a time-series curve; a snapshot does not use it (DSS-11) | |
duty |
Optional[str] |
untranscribed | a time-series curve; a snapshot does not use it (DSS-11) | |
dispmode |
Union[str, ForwardRef('DispatchMode'), NoneType] |
untranscribed | a dispatch setting of time-series solutions; a snapshot does not use it; with a yearly shape, another than Default raises | |
dispvalue |
Optional[float] |
untranscribed | a dispatch setting of time-series solutions; a snapshot does not use it; with a yearly shape, above 0 raises | |
conn |
Union[str, ForwardRef('ConnectionType'), NoneType] |
wye, delta |
mapped | SynchronousMachine.earthing; wye -> earthing true, delta -> false (no phaseConnection on a machine, S4b-5); default wye |
status |
Union[str, ForwardRef('GenStatus'), NoneType] |
untranscribed | Fixed/Variable: whether load multipliers scale it; a dispatch setting of time-series solutions; a snapshot does not use it; with a yearly shape, Fixed raises | |
gen_class |
Optional[int] |
untranscribed | a DSS report grouping | |
Vpu |
Optional[float] |
1.0 |
derived | model 3: the control's targetValue = Vpu x ratedU in kV (targetValueUnitMultiplier k); default 1 |
maxkvar |
Optional[float] |
copied | SynchronousMachine.maxQ (kVAr); model 3 only (another model raises); default 2 x kvar (reactive_limits) |
|
minkvar |
Optional[float] |
copied | SynchronousMachine.minQ (kVAr); model 3 only (another model raises); default -2 x kvar (reactive_limits) |
|
pvfactor |
Optional[float] |
untranscribed | a convergence aid of the engine's model 3 | |
forceon |
Union[bool, Bool, NoneType] |
untranscribed | a dispatch setting of time-series solutions; a snapshot does not use it | |
kVA |
Optional[float] |
737.0, 775.0, 125.0 |
copied | SynchronousMachine.ratedS (kVA); default 1.2 x kW |
MVA |
Optional[float] |
structural | raises when set: no deck in the sweep sets it, so a mapping waits for one (kVA is) | |
Xd |
Optional[float] |
untranscribed | a dynamics setting; no home in the network profile parts | |
Xdp |
Optional[float] |
0.27 |
untranscribed | a dynamics setting; no home in the network profile parts |
Xdpp |
Optional[float] |
0.2 |
untranscribed | a dynamics setting; no home in the network profile parts |
H |
Optional[float] |
2.0 |
untranscribed | a dynamics setting; no home in the network profile parts |
D |
Optional[float] |
untranscribed | a dynamics setting; no home in the network profile parts | |
UserModel |
Optional[str] |
structural | raises when set: no deck in the sweep sets it, so a mapping waits for one | |
UserData |
Optional[str] |
structural | raises when set: no deck in the sweep sets it, so a mapping waits for one | |
ShaftModel |
Optional[str] |
structural | raises when set: no deck in the sweep sets it, so a mapping waits for one | |
ShaftData |
Optional[str] |
structural | raises when set: no deck in the sweep sets it, so a mapping waits for one | |
DutyStart |
Optional[float] |
untranscribed | a time-series curve; a snapshot does not use it (DSS-11) | |
debugtrace |
Union[bool, Bool, NoneType] |
untranscribed | a DSS debugging switch | |
Balanced |
Union[bool, Bool, NoneType] |
untranscribed | a power-flow setting of the engine's model | |
XRdp |
Optional[float] |
untranscribed | a dynamics setting; no home in the network profile parts | |
UseFuel |
Union[bool, Bool, NoneType] |
untranscribed | a fuel-limited dispatch setting; a snapshot does not use it | |
FuelkWh |
Optional[float] |
untranscribed | a fuel-limited dispatch setting; a snapshot does not use it | |
pct_Fuel |
Optional[float] |
untranscribed | a fuel-limited dispatch setting; a snapshot does not use it | |
pct_Reserve |
Optional[float] |
untranscribed | a fuel-limited dispatch setting; a snapshot does not use it | |
Refuel |
Union[bool, Bool, NoneType] |
untranscribed | a fuel-limited dispatch setting; a snapshot does not use it | |
DynamicEq |
Optional[str] |
untranscribed | a dynamics setting; no home in the network profile parts | |
DynOut |
Union[str, list[str], NoneType] |
untranscribed | a dynamics setting; no home in the network profile parts | |
spectrum |
Optional[str] |
untranscribed | harmonics model; no home in the network profile parts | |
basefreq |
Optional[float] |
untranscribed | no home on a machine | |
enabled |
Union[bool, Bool, NoneType] |
copied | SynchronousMachine.normallyInService; default true |
|
like |
Optional[str] |
untranscribed | the reader resolves like= before mapping |
| Reactor field | type | samples | kind | target |
|---|---|---|---|---|
name |
Union[str, ReactorName] |
HVMV_Sub_HSB, T2_neutral |
copied | SeriesCompensator.name; mRID = rx_ + name, lowercased |
bus1 |
Optional[str] |
SourceBus, sourcebus, K_LSB.4 |
structural | node1 and the phases (the line rule) |
bus2 |
Optional[str] |
HVMV115_HSB1, hvmv115s1_HSB1, K_LSB.0 |
structural | node2; unset or on bus1's bus (a shunt or neutral reactor) raises |
phases |
Optional[int] |
1 |
structural | the conductor count; default 3 |
kvar |
Optional[float] |
structural | raises when set: no deck in the sweep sets it, so a mapping waits for one (X from kvar and kV) | |
kv |
Optional[float] |
untranscribed | acts only with kvar, which raises | |
conn |
Optional[str] |
untranscribed | a series reactor has no neutral | |
Rmatrix |
Union[float, list[float], NoneType] |
structural | raises when set: no deck in the sweep sets it, so a mapping waits for one | |
Xmatrix |
Union[float, list[float], NoneType] |
structural | raises when set: no deck in the sweep sets it, so a mapping waits for one | |
Parallel |
Union[bool, Bool, NoneType] |
structural | raises when yes: no deck in the sweep sets it, so a mapping waits for one | |
R |
Optional[float] |
0.0 |
copied | SeriesCompensator.r (ohm), SeriesCompensator.r0 (ohm); per phase; r0 = r (no mutual); default 0 |
X |
Optional[float] |
14.798306633595042, 0.5 |
copied | SeriesCompensator.x (ohm), SeriesCompensator.x0 (ohm); per phase; x0 = x (no mutual); unset raises |
Rp |
Optional[float] |
structural | raises when set: no deck in the sweep sets it, so a mapping waits for one (a parallel R) | |
Z1 |
Union[float, list[float], NoneType] |
structural | raises when set: no deck in the sweep sets it, so a mapping waits for one | |
Z2 |
Union[float, list[float], NoneType] |
structural | raises when set: no deck in the sweep sets it, so a mapping waits for one | |
Z0 |
Union[float, list[float], NoneType] |
structural | raises when set: no deck in the sweep sets it, so a mapping waits for one | |
Z |
Union[float, list[float], NoneType] |
structural | raises when set: no deck in the sweep sets it, so a mapping waits for one | |
RCurve |
Optional[str] |
structural | raises when set: no deck in the sweep sets it, so a mapping waits for one | |
LCurve |
Optional[str] |
structural | raises when set: no deck in the sweep sets it, so a mapping waits for one | |
LmH |
Optional[float] |
structural | raises when set: no deck in the sweep sets it, so a mapping waits for one (X from an inductance) | |
normamps |
Optional[float] |
400.0 |
structural | instance OperationalLimitSet rx_ |
emergamps |
Optional[float] |
400.0 |
structural | CurrentLimit emerg (olt_emergency) in rx |
faultrate |
Optional[float] |
untranscribed | a reliability setting; no home in the network profile parts | |
pctperm |
Optional[float] |
untranscribed | a reliability setting; no home in the network profile parts | |
repair |
Optional[float] |
untranscribed | a reliability setting; no home in the network profile parts | |
basefreq |
Optional[float] |
60.0 |
untranscribed | no home on a compensator; x is at the model's frequency |
enabled |
Union[bool, Bool, NoneType] |
copied | SeriesCompensator.normallyInService; default true |
|
like |
Optional[str] |
untranscribed | the reader resolves like= before mapping |
Decisions for S4b (approved 2026-11-08)¶
S4b-1 to S4b-4 were approved as written; S4b-5 to S4b-7 had no objection and stand as proposed. The user
added that cim18v17's RotatingMachinePhase names a 1-phase machine's phase.
- S4b-1: p and q follow the load sign for everything, PowerElectronicsConnection and SynchronousMachine (−kW for generation), as cim18v17 documents. The engine's export writes +kW on machines; the exporter negates.
- S4b-2 (replaced by S4b-8): pf with kvar raised unless both gave the same q.
- S4b-3 (replaced by S4b-8): a Storage's
kWdecided its state when set. The replay gives the same result on every deck (IEEE9500'sstate=charge kW=150still discharges at 150 kW). - S4b-4:
ratedUis line to line, as the engine exports it: the deck's kV, × √3 for 1-phase wye. It is not checked against the bus. - S4b-5: a delta generator is
earthing=false, because SynchronousMachine has nophaseConnection. In DSS a wye machine's neutral is ground (the shared rule raises otherwise), so for DSSearthingis exactly "not delta". A request forRotatingMachine.phaseConnectiongoes toUPSTREAM_REQUESTS.mdas U8. - S4b-6: IEEE123_test_harness's
Battery5(1-phase, neutral on node 2) raises under the shared phase rule. The deck is wrong (it looks like a 3-phase battery written asphases=1), and a guess would put it across A–B. - S4b-7: shape names
synchronous_machineandseries_compensator, shared with RAW (its C2), in place of the DSS plan'smachine. - S4b-9: a balanced three-phase device (phases
ABC) has a blankphasescell, so no per-phase children and noTerminal.phases(above); U10 asks CIM-Tables for the balanced form. - S4b-8 (approved 2026-11-08): the reader keeps each record's assignment history (
DssModel), and the Generator, PVSystem and Storage mappers replay it as the engine does (above). The Load replays it command by command (decision 7, 2026-11-27).
S5 (approved and done 2026-11-08)¶
Result (2026-11-08).
- Every equipment Location equals the engine's bus coordinates on both atoms and the 8 engine decks that bind:
- one point per Terminal where every Terminal bus has Bus.Coorddefined(), and no Location otherwise;
- this includes IEEE8500 and IEEE9500, where the engine's x is the longitude.
- The sweep test passes: 18 of the 24 CIMHUB_DSS_DECKS decks bind and 6 stop as listed. The throwaway 31-deck sweep
is unchanged at 22.
- The reader fix (S5-7) recovers the IEEE123 coordinates: IEEE123_PV 214 rows (was 2), deconfliction 134 and
test_harness 139 (were 0). Every coordinate file in the sweep parses.
- Locations: IEEE9500 unbal 8,072; IEEE8500 6,082; IEEE123_PV 326; IEEE13_CDPSM 46.
- The IEEE13_CDPSM golden directory has 14 files.
- G7 after S5:
| deck | read | map | bind |
|---|---|---|---|
| IEEE9500 unbal | 4.0 s | 1.0 s | 8.2 s: 65,282 rows / 80,238 objects, about 7,900 rows/s |
| IEEE8500 | 0.5 s | 0.7 s | 6.6 s: 47,840 rows, about 7,200 rows/s |
The coordinates cost about 2 s of bind on each deck.
The user's review: keep the CIM17 form, PositionPoint.Location, not cim18v17's Geometry/GeometricElement
form (the catalog lists that as not yet catalogued). The decisions stand as recommended.
Changes from the proposal:
- A center-tap transformer gets two points, not three. Its secondary is one Terminal (s1s2N), because the windings
land on lugs (DSS-2). The engine writes a point for each of its 3 windings, but two of them are the same bus.
- The Terminals come from the bound network, not from the document text (S5-2, revised 2026-11-09 when CIM-Tables
declined U11). So a TransformerEnd's Terminal is whatever binding made of it; no separate end-class check.
S5 adds bus coordinates (buscoords.cimtbl), turns the throwaway deck sweep into a test, and records the G7
numbers. Census through today's reader on the 31 sweep decks: 14 decks have coordinates (about 31,000 rows; IEEE9500
5,305, IEEE8500 4,893, J1 3,441, K1 650; the IEEE13s 16-74). Only PNNL/IEEE9500 uses LatLongCoords; every other
deck uses BusCoords. No deck uses both.
Where the coordinates go (S5-1)¶
In CIM a Location hangs off a PowerSystemResource. A ConnectivityNode is not one, so a bus can't carry
coordinates itself. Proposed: each piece of conducting equipment gets one Location with one PositionPoint per
Terminal, holding the coordinates of that Terminal's bus. So a line is a two-point polyline, a load or capacitor is
one point, and a center-tap transformer has three. This matches the engine's own CIM export (WritePositions in
ExportCIMXML.pas), CIMHub_2_0's importer and GridAPPS-D. A CYME section's polyline also fits it, with more points
per line. The alternative, rejected: a Junction per bus (the CIM note: "to associate ... Location to a
ConnectivityNode"). It is closer to the native table, but it adds about 5,300 one-terminal equipment objects to
IEEE9500, and every consumer and exporter would have to skip them. No tool reads it either.
Revised 2026-11-10 (S5-8): the points are drawn as a GIS draws the equipment, through cimtables' wkt column.
A line (ACLineSegment) is a LINESTRING through its Terminals' buses; any other equipment is one POINT, at its
bus for one Terminal and at its buses' centroid for more. So a switch, fuse or transformer sits midway between its
buses, as a GIS point feature does, rather than as a two-point polyline.
Shape location (added to the catalog first)¶
Profile = cim18v17
Import common.cimtbl
Object CoordinateSystem: mRID=crs_bus, name=BusCoords, crsUrn=OpenDSSLocalBusCoordinates
Update Table PowerSystemResource: mRID, wkt
ln_650632, "LINESTRING (200.0 350.0, 200.0 300.0)"
sw_671692, "POINT (225.0 250.0)"
ld_671, "POINT (200.0 250.0)"
An Update on the abstract PowerSystemResource resolves any subclass. cimtables' wkt binding makes the Location
(<mRID>_loc), one Identity-only PositionPoint per vertex (<mRID>_loc_<n>, sequenceNumber from 0) and points
the Location at the CoordinateSystem declared first.
Buscoords¶
- Mapper:
importer/cimtbl/buscoords.py,map_buscoords(native, network). It isDssImporter.bound_parts: core binds every other part first, calls it with that network, writesbuscoords.cimtblbeside them as the lastImport(DSS_REWRITE_PLAN.md §2, row 16) and binds it onto the same network. - Finding the equipment (S5-2, revised 2026-11-09): the mapper reads each piece of equipment's Terminals from the
bound network (
terminal_buses), not from the DSS records, so no mapper's mRID or bus rules are written twice; the circuit's buses are the network's ConnectivityNodes. The first version re-read the connectivity columns of the written documents (core'sdocument_terminals) and asked CIM-Tables for that inverse (U11). CIM-Tables declined: a.cimtblmeans what binding makes. The hook (CimtblImporter.bound_parts,cimtbl_to_cim(bound_parts=)) is in core because any spoke with coordinates needs it (GLM node latitude/longitude, CYME). The bound Terminals equalled the stand-in's on IEEE13_CDPSM, IEEE8500 and IEEE9500 unbal before it was deleted. - Geometry (S5-8): one
wktcell per equipment, from its Terminal buses in TerminalsequenceNumberorder. AnACLineSegmentisLINESTRING (x1 y1, x2 y2). Anything else isPOINT (x y)at the buses' centroid: the bus itself for a load, capacitor, PV or source, the midpoint for a switch, fuse, regulator or two-terminal transformer. A center-tap transformer has two Terminals (S5-1 above), so it gets the midpoint too. device_geometry(S5-9):DssImporter(..., device_geometry="linestring")(anddss_to_cim) draws every two-terminal equipment as aLINESTRINGfrom bus to bus, like a line: switches, fuses, transformers, regulators, series reactors. Equipment with one Terminal, or three or more, stays aPOINT. The default is"point"; any other value raises when the importer is made. It is a keyword, not an environment variable, so a call's output depends only on its arguments.- Identity: cimtables'
wktbinding names them: - Location:
<equipment mRID>_loc, unnamed (the engine's<name>_Locname is dropped with the Location table); - PositionPoint:
<location>_<n>,sequenceNumber= n, the vertex number from 0 (S5-5 is superseded); - CoordinateSystem:
crs_bus(BusCoords) orcrs_latlong(LatLongCoords), declared first in the file. - Order: equipment in the order its first Terminal binds.
- Values:
xPosition/yPositionare strings in CIM. The reader's floats are written bycell(repr), so a line's vertices and a one-Terminal point read back exactly; a centroid isreprof the float mean. For LatLongCoords the reader has already swapped them (x = longitude, y = latitude). - Partial coordinates (S5-3): equipment gets a Location only if every one of its Terminal buses has
coordinates. The engine writes 0, 0 for a bus without them, which would make a polyline vertex up. The file comment
counts what is left out:
# not located: <n> of <m> equipment (a terminal bus without coordinates). That case is K1 (644 of 1,285 buses have none), plus IEEE123_PV and the deconfliction deck before the reader fix below. - Coordinates for a bus the circuit doesn't have: untranscribed, because the engine ignores them too. The comment
lists the count and the first names:
# no such bus: 17 (0000500000247160_load, ...). That covers IEEE8500's 17_loadbuses, IEEE9500's 8, IEEE13_CDPSM's older copy'stap, and J1's blank-name row. - Coordinate system (S5-4): BusCoords →
crsUrn=OpenDSSLocalBusCoordinates, the engine's value (a local projection the deck does not name). LatLongCoords →urn:ogc:def:crs:OGC:1.3:CRS84: WGS84 longitude/latitude in x, y order. The engine writes its local URN for both, which loses the fact that the values are degrees. - Fail fast: a deck that uses both BusCoords and LatLongCoords raises (none does). A coordinate row that doesn't parse raises with its file and line (the reader fix below).
| Buscoords field | type | samples | kind | target |
|---|---|---|---|---|
name |
Union[str, BuscoordsName] |
611, 632, 190-7361 |
structural | picks the bus: every Terminal on it takes its coordinates; a name the circuit has no bus for is ignored, as in the engine (counted in the file comment) |
x |
Optional[float] |
0.0, 200.0, -119.1650904 |
derived | geometry: a line's LINESTRING vertex at each Terminal bus, verbatim; other equipment's POINT at its Terminal buses' centroid (the bus itself for one Terminal) |
y |
Optional[float] |
100.0, 250.0, 46.65388888 |
derived | as x |
geographic |
Union[bool, Bool, NoneType] |
False, True |
mapped | the directive (LatLongCoords -> true) picks the CoordinateSystem: COORDINATE_SYSTEMS |
Reader fix (S5-7)¶
The reader splits a coordinate row only on commas, and it skips any row it can't parse. The IEEE123 family's files are
whitespace-separated (1 700 1500), so IEEE123_PV keeps 2 of 216 rows and IEEE123_deconfliction and
IEEE123_test_harness keep none, all silently. The engine reads the file with its own command parser, which takes
commas or whitespace. The fix:
- split on either;
- raise on a row whose two coordinates aren't numbers, naming the file and line;
- keep J1's blank-name row (its name is '', which is no bus).
A bus listed twice keeps its last row, as in the engine; the reader's dict already does that.
Deck sweep test (S5-6)¶
tests/test_cimtbl_sweep.py, marked roundtrip, runs every deck under CIMHUB_DSS_DECKS (the 24 in the
test_data/models/feeders/OpenDSS layout). Each deck either binds, with its bus voltages equal to the walk's, or
stops with the error its row in SWEEP_STOPS names. An unlisted stop fails the test, and so does a listed stop
that now binds, so the table stays true. Expected today:
| deck | stop |
|---|---|
| EPRI J1, K1, M1; IEEE13_OCHRE | DSS-10 (line phases ≠ code nphases) |
PNNL IEEE9500 Master-bal-initial-config |
linecode=3PH_H-4_ACSR4_ACSR4_ACSR4_ACSR is no LineCode, which the engine rejects too |
| IEEE123_test_harness | Battery5 (S4b-6) |
So 18 of 24 bind. The other 7 of the throwaway sweep's 31 decks are copies in CIMHub_2_0's private
cimhub_opendss/tests/test_models/: IEEE13_CDPSM, IEEE13_assets plus its _geo variant, and the ieee9500 and
ieee9500_2025 bal/unbal pairs. They are dropped from the sweep, because their findings are already recorded (the
Mode=7 PV, the open of an undefined switch). The per-slice sweep notes above stay as the history; this table is the current one.
Engine checks (S5)¶
On the atom and every engine deck:
- for each line, its PositionPoints equal the engine's coordinates of its Terminals' buses (Circuit.SetActiveBus,
Bus.X(), Bus.Y()); for other equipment, its one PositionPoint equals their centroid (S5-8);
- every equipment whose buses all have Bus.Coorddefined() has a Location, and no other equipment does.
For IEEE9500 the engine's x is the longitude, which also checks the reader's swap.
Atoms, golden, G7¶
- Atoms:
atoms/buscoords/: local.dss+ CSV: a line, a switch, a center-tap transformer, a regulator, a load, a capacitor and a PV. The CSV has a whitespace row, a bus the circuit doesn't have, a bus listed twice, and one bus left without coordinates.latlong.dss: two buses, by LatLongCoords.local_linestring.cimtbl:local.dssunderdevice_geometry="linestring"(S5-9).- Golden: the IEEE13_CDPSM directory (D6) gains
buscoords.cimtbl, so it holds 14 files. - G7 before S5 (2026-11-08):
| deck | read | map | bind |
|---|---|---|---|
| IEEE9500 unbal | 4.4 s | 1.2 s | 6.0 s: 35,747 rows / 58,774 objects, about 6,000 rows/s |
| IEEE8500 | 0.6 s | 0.4 s | 4.9 s: 24,700 rows, about 5,000 rows/s |
That was about 400 rows/s before R12 (G7's first measurement), so G7 is closed. Coordinates add about 13,400 points, 6,000-7,000 Locations and as many Update rows to IEEE9500 (the measurement after S5 is under Result).
Decisions for S5 (approved 2026-11-08)¶
- S5-1: coordinates go on each piece of equipment's Location (one PositionPoint per Terminal), not on a Junction
per bus. The CIM17 form (
PositionPoint.Location) stays, not cim18v17'sGeometry(the user's review). - S5-2: the mapper finds the Terminals on the bound network (
CimtblImporter.bound_parts); revised 2026-11-09 from a re-read of the written documents (document_terminals) when CIM-Tables declined U11. - S5-3: no Location for equipment with a Terminal bus that has no coordinates; the file comment counts them.
- S5-4:
crsUrnisOpenDSSLocalBusCoordinatesfor BusCoords and CRS84 for LatLongCoords. - S5-5:
sequenceNumberis the Terminal number, 1-based. - S5-6: the sweep test covers the 24
CIMHUB_DSS_DECKSdecks; the 7 CIMHub_2_0test_modelscopies are dropped. - S5-7: the reader reads whitespace-separated coordinate rows and raises on a row it can't parse.
- S5-8 (2026-11-10, the user's ask): the coordinates are GIS geometry through cimtables'
wktcolumn: a line is aLINESTRINGthrough its Terminal buses, other equipment onePOINTat their centroid (the midpoint for a switch or transformer). It replaces the Location and PositionPoint tables and S5-5's 1-based Terminal numbering; the Location loses its<name>_Locname. The exporter reads it back by F8 (EXPORT_MAPPING.md). - S5-9 (2026-11-10, the user's ask):
device_geometry="linestring"draws every two-terminal device bus to bus instead of as a midpoint. The exporter needs nothing new: two points on two Terminals pair one per Terminal, so each bus comes back exactly.
S6g: earth model and reclose sequences (2026-11-09)¶
Specified with the export in EXPORT_MAPPING.md#s6g-earth-model-and-reclose-sequences. On import:
- A deck with geometry gets one EarthResistivity (earth), first in linegeometry.cimtbl, from Set earthmodel
and the geometry lines' rho (the engine's Deri and 100 ohm-m when unset, listed). Every WireConfiguration names
it. FullCarson, disagreeing rho, and rho on a line without geometry raise.
- A deck without geometry that sets earthmodel gets the same EarthResistivity earth, floating: no line names
it (# the deck's earthmodel; no line names it), rho the default 100 ohm-m (defaulted: rho=100.0). It keeps
the setting for the export's Set earthmodel, so earthmodel no longer differs in the power-flow parity of such
decks (IEEE13_CDPSM now has a linegeometry.cimtbl). A deck with neither geometry nor earthmodel gets none
(2026-11-24; test_no_geometry_keeps_a_set_earthmodel, test_no_geometry_and_no_earthmodel_has_no_earth).
- A Recloser's Shots - 1 reclosures are RecloseSequence rows <switch>_rs<n> in line.cimtbl, at its
RecloseIntervals (the engine's defaults filling either, listed). Both given and disagreeing raise, and so does
Shots above 4 without intervals.
S8: load shapes (built 2026-11-21 at the user's word)¶
GLM's S8 (cimhub_gridlabd/docs/CIMTBL_MAPPING.md#s8-load-players) maps a player to the
ConformLoadSchedule → ConformLoadGroup ← ConformLoad pattern (the user's call, 2026-11-21: ConformLoad groups,
points in a Parquet sidecar). A DSS LoadShape a Load names as yearly is the same thing: one curve of multipliers
that scales every load naming it. Mapper importer/cimtbl/loadshape.py, artifact loadshape.cimtbl, shape
load_schedule; the loads in load.cimtbl. Atom tests/atoms/loadshape/loadshapes.dss:
- an hourly shape with qmult, shared by two loads (res);
- a 15-minute shape given as minterval and normalized (com, as K1's action=normalize);
- a 900 s shape given as sinterval (ind);
- M1's bare mult=1 with no npts (flat), named in another case;
- a shape no Load names (pv, as K1's PVSystem irradiance shape);
- a load with no shape.
| # | decision |
|---|---|
| S8-1 | A LoadShape a Load names as yearly is a ConformLoadGroup lg_<name> with one ConformLoadSchedule ls_<name> (lowercased); each Load naming it is a ConformLoad whose LoadGroup is the group, its p and q as for any load. Only yearly: a ConformLoad has one group, and every load in the sweep names only yearly (M1, K1, J1). daily and duty are untranscribed (listed on the row) |
| S8-2 | Multipliers: value1 = mult, value1Unit none; value2 = qmult (value2Unit none) when given, else unset: Q follows mult, the engine's rule (engine-checked). action=normalize divides each array by its largest magnitude, as the engine does; an array assigned after it raises (the engine normalizes only what came before) |
| S8-3 | Time: timeStep = the interval slot the deck assigned last (the engine's rule), copied in its unit (interval h, minterval min, sinterval s), one schedule table per unit; none gives the engine's 1 h. DSS has no date: sample k (from 1) is in force from k × interval (engine-checked: yearly mode, hour 1 gives sample 1), so startTime = 2020-01-01T00:00Z (ditto's epoch) + one interval (cimhub_gdm TIMESERIES_NEEDS.md X2). The engine wraps a shape around; CIM has no repeat, so the wrap is lost (X4) |
| S8-4 | Points: RegularTimePoint rows in the Parquet sidecar (cimhub_core.time_points), as GLM's: DssImporter(time_points={}) / dss_to_cim(..., time_points=) fills the caller's dict; without it the points are dropped with one warning |
| S8-5 | npts unset: the engine reads none of mult, inline or from a file (engine-checked with DSS C-API 0.14.5: Npts 0, the load constant), so the group has no schedule, its name kept, as GLM's undefined player (M1's five mult=1 shapes). npts set must equal the number of values |
| S8-6 | UseActual=Yes raises: a Load naming it takes the shape's peak as its kW and kvar, or keeps its own, depending on whether yearly= comes after kW= (engine-checked), which the record does not keep. So no DSS form maps a NonConformLoad yet, either way |
| S8-7 | A shape no Load names as yearly is not a group: one a PVSystem, Storage or Generator names is that device's schedule (S9); one nothing names (a Vsource's, an unused irradiance shape) is not mapped and not checked, and the master's comment counts it (not mapped: Loadshape 1) |
What raises:
- UseActual=Yes;
- hour, csvfile, sngfile, dblfile, PQCSVFile, Pmult, Pbase, Qbase set (no deck sets them);
- an interval of 0 (an hour array);
- npts other than the number of mult values, qmult of another length, no mult;
- an array assigned after action=normalize, or an action other than normalize, DblSave, SngSave;
- a Load whose yearly names no shape of the deck.
Engine checks. test_cimtbl_loadshape.py compiles the atom and reads each shape's PMult, QMult and
HrInterval from the engine, against the mapper's values (the normalized com included, and flat's 0 points).
test_export_loadshape.py runs the original atom and its export in yearly mode every 5 minutes for 6 hours, every
load's power equal at every step (rel 1e-9).
Not mapped: an Hour-array shape and a file the reader does not read (csvfile=, ...). A mult=(file=...)
with no npts is S8-5's case too: the engine reads no points from the file either (engine-checked).
LoadShape fields¶
| Loadshape field | type | samples | kind | target |
|---|---|---|---|---|
name |
Union[str, LoadshapeName] |
com, flat, ind |
copied | ConformLoadGroup.name, ConformLoadSchedule.name; mRID = lg_ / ls_ + name, lowercased |
npts |
Optional[int] |
4, 3, 2 |
structural | the number of points the engine reads: unset, none of mult (inline or from a file; engine-checked), so the group has no schedule; else it must equal the number of mult values |
interval |
Optional[float] |
1.0 |
copied | ConformLoadSchedule.timeStep (h); the interval slot the deck assigned last (the engine's rule); 0 (an hour array) raises; none: 1 h |
mult |
Union[float, list[float], NoneType] |
[2.0, 4.0, 8.0, 6.0], [1.0], [1.0, 0.9, 0.95] |
copied | RegularTimePoint.value1; the points, in the Parquet sidecar (S8-4); action=normalize divides them by their peak |
hour |
Union[float, list[float], NoneType] |
structural | raises when set: no deck in the sweep sets it, so a mapping waits for one (an irregular shape has no RegularIntervalSchedule) | |
mean |
Optional[float] |
untranscribed | a Monte Carlo statistic; the engine computes it from mult | |
stddev |
Optional[float] |
untranscribed | a Monte Carlo statistic; the engine computes it from mult | |
csvfile |
Optional[str] |
structural | raises when set: no deck in the sweep sets it, so a mapping waits for one (the reader reads mult=(file=...)) | |
sngfile |
Optional[str] |
structural | raises when set: no deck in the sweep sets it, so a mapping waits for one (the reader reads mult=(file=...)) | |
dblfile |
Optional[str] |
structural | raises when set: no deck in the sweep sets it, so a mapping waits for one (the reader reads mult=(file=...)) | |
action |
Optional[str] |
normalize |
derived | normalize: mult and qmult each divided by its largest magnitude, as the engine does (one assigned after it raises); DblSave, SngSave write files and are untranscribed; others raise. Every action assigned counts (each acts when assigned), not only the last |
qmult |
Union[float, list[float], NoneType] |
[0.4, 0.6, 0.9, 0.7] |
copied | RegularTimePoint.value2; in the sidecar; unset: Q follows mult (the engine's rule), value2 unset |
UseActual |
Union[bool, Bool, NoneType] |
structural | Yes raises: a Load naming it takes the shape's peak as its kW, or keeps its own, by command order, which the record does not keep (engine-checked); default No | |
Pmax |
Optional[float] |
untranscribed | used only with UseActual | |
Qmax |
Optional[float] |
untranscribed | used only with UseActual | |
sinterval |
Optional[float] |
900 |
copied | ConformLoadSchedule.timeStep (s); the interval slot the deck assigned last (the engine's rule); 0 (an hour array) raises; none: 1 h |
minterval |
Optional[float] |
15 |
copied | ConformLoadSchedule.timeStep (min); the interval slot the deck assigned last (the engine's rule); 0 (an hour array) raises; none: 1 h |
Pbase |
Optional[float] |
structural | raises when set: no deck in the sweep sets it, so a mapping waits for one (a normalize base) | |
Qbase |
Optional[float] |
structural | raises when set: no deck in the sweep sets it, so a mapping waits for one (a normalize base) | |
Pmult |
Union[float, list[float], NoneType] |
structural | raises when set: no deck in the sweep sets it, so a mapping waits for one (a synonym of mult) | |
PQCSVFile |
Optional[str] |
structural | raises when set: no deck in the sweep sets it, so a mapping waits for one (the reader reads mult=(file=...)) | |
MemoryMapping |
Union[bool, Bool, NoneType] |
untranscribed | how the engine stores the points | |
Mode |
Optional[float] |
untranscribed | generator dispatch; no effect on a Load | |
Interpolation |
Optional[str] |
untranscribed | AVG and EDGE agree at the solution steps, which are on the interval grid (TIMESERIES_NEEDS.md X3) | |
like |
Optional[str] |
untranscribed | the reader resolves like= before mapping |
S9: device shapes (built 2026-11-21 at the user's word: "shapes for PV, storage, etc using the nc_schedule profile classes")¶
A yearly LoadShape on a PVSystem, Storage or Generator drives that one device's output, which the engine computes
from the shape and the device's own settings (irradiance, kWrated, kW). So it is nc_schedule's per-device
EnergyConnectionSchedule on the device's PowerElectronicsConnection or SynchronousMachine, its points the
device's p and q at each sample as EnergyConnectionTimePoint rows in the Parquet sidecar (TIME_POINT_SCHEMA, as
GDM's T1 schedules), not a load group. The user chose this over a PowerSchedule on the unit (2026-11-21). Mappers:
pvsystem.py, storage.py, generator.py (schedule_points; the schedule row in their own document), with
loadshape.py's device_shape, point_times and device_schedules. Atom tests/atoms/loadshape/devices.dss:
- sun (30 min) on two PVs: p1 by pf with %Cutin = %Cutout = 10, off at both ends; p2 by kvar, cut to fit
its kVA at the peak, off with its kvar kept at both ends;
- run (hourly) on a model 1 generator by pf, down to 0;
- cycle (hourly) on a follow-mode battery that discharges, charges, idles, and is capped at kVA;
- a PV and a load with no shape.
| # | decision |
|---|---|
| S9-1 | A device's yearly shape is an EnergyConnectionSchedule <connection mRID>_yearly, named after the shape, timeSeriesKind schedule, interpolationKind previous (a sample holds until the next), on the device's EnergyConnection. One per device: devices sharing a shape each get their own, as their outputs differ (a PV's cap). Only yearly, as for loads (S8-1): daily, duty, Tyearly.. are untranscribed. The snapshot p, q are the deck's, as before |
| S9-2 | Times: sample k (from 1) at the epoch 2020-01-01T00:00Z + k intervals, the instant it is in force (S8-3's rule, engine-checked here per device). The wrap is lost (X4) |
| S9-3 | Generator: p = -kW x mult, q = -kvar x mult (engine-checked: the engine scales kvar with kW, pf or kvar alike); a model 3 machine's schedule carries p only (its q is its control's). A shape with dispmode other than Default, dispvalue above 0 or status=Fixed raises (the engine then dispatches by load level, price, or not at all) |
| S9-4 | PVSystem: each sample is pv_power at irradiance x mult (engine-checked: the shape scales the irradiance, so %Pmpp, %Cutout and the kVA cut apply per sample). A sample whose panel power lies between %Cutout and %Cutin raises: the engine keeps the inverter on or off as it was (hysteresis, engine-checked), which depends on the samples before and on a snapshot solved first |
| S9-5 | An inverter that is off still gives a set kvar unless VarFollowInverter (engine-checked, snapshot and yearly alike): pv_power now keeps it. This changes no golden: no atom or sweep deck has an off PV with a kvar |
| S9-6 | Storage: only DispMode=follow with a yearly shape (engine-checked: discharge at mult x kWrated for mult > 0, charge at -mult x kWrated below 0, idle at 0 with the idling loss, capped at kVA; %Charge, %Discharge and %kWrated have no effect); p only. It is the dispatch asked for: a battery that fills or reaches its reserve idles in the engine, which the schedule does not model (the export's deck idles it too, so a round trip agrees). A follow-mode battery with a kW or State raises (the engine's snapshot of one is not that of battery_dispatch); one with neither idles, as the importer has it. A yearly shape in the default (trigger) mode, or follow mode without a shape, raises |
| S9-7 | A shape with qmult raises on a device: its output is scaled by mult alone. A shape with no npts is no schedule (S8-5); a yearly naming no shape raises |
| S9-8 | Points: DssImporter(time_points={}) fills the EnergyConnectionTimePoint table beside the RegularTimePoint one (time_points.add_device_time_points, CIM-Builder's builder converting kW, kVAr to SI); without it they are dropped with the one warning of S8-4 |
What raises: a sample between %Cutout and %Cutin; a generator shape off Default dispatch; a storage shape off
follow mode, follow mode with no shape, with a kW or with a State; a qmult on a device's shape; a yearly naming
no shape.
Engine checks. test_cimtbl_device_shape.py runs the atom in yearly mode at each shape's own interval and
compares every device's kW and kvar at every sample with the schedule's points (rel 1e-6, a tight solver
tolerance). test_export_device_shape.py runs the original atom and its export every 30 minutes for 8 hours, every
device's power equal at every step.
Not mapped: daily and duty shapes; a temperature shape (it acts only through a P-TCurve, which raises); a shape on a Vsource; a battery's trigger dispatch modes.