OpenDSS → .cimtbl mapping spec

Status: S2 done (2026-11-07): LineCode units, base frequency and short sequence codes; wire catalogs; LineSpacing/LineGeometry. S3a and S3b done 2026-11-08 (lines, switches, transformers, regulators, RegControl, XfmrCode templates). S4a done 2026-11-08 (Load, Capacitor, CapControl); S4b done 2026-11-08 (PVSystem, Storage, Generator, Reactor); S5 done 2026-11-08 (bus coordinates, the deck sweep test). LineCode (Phase 1) and the inline Transformer are seeded from CIMHub_2_0 with their atoms; the master, buses and Vsource are S0/S1's. The other DSS classes follow slice by slice (DSS_REWRITE_PLAN.md), each section approved before its code (DSS-12). Format: the cimtbl-mapping-spec skill. Contract: the cimtbl-import-contract skill.

The classification tables are generated from each mapper's FIELDS with cimhub_core.cimtbl.fields_table(..., fields=FIELDS). The samples come from tests/decks/IEEE/IEEE13_CDPSM/ and the IEEE8500 LineCodes.dss; the S2 tables' samples come from the 31 sweep decks. {length} in a unit is the code's units; {r_length}, {gmr_length}, {radius_length} are a wire's Runits, GMRunits, radunits.

Artifact files and order

native class artifact shape depends on
(the deck) <Model>.cimtbl (master) settings, common rows (Substation, Feeder, BaseFrequency, BaseVoltage), Imports every part
(the topology walk) bus.cimtbl one ConnectivityNode per bus, with its BaseVoltage the master
Vsource vsource.cimtbl source the master, bus.cimtbl
WireData, CNData, TSData wiredata.cimtbl, cndata.cimtbl, tsdata.cimtbl wire_info nothing
LineSpacing linespacing.cimtbl line_by_wire_configuration (XYSpacing) nothing
LineGeometry linegeometry.cimtbl line_by_wire_configuration (WireConfiguration; inline positions get a synthesized XYSpacing) the wire catalogs, linespacing.cimtbl
LineCode linecode.cimtbl matrix code: PerLengthPhaseImpedance + PhaseImpedanceData per lower-triangle element; sequence code: PerLengthSequenceImpedance nothing
Line (+ Fuse, Recloser, SwtControl) line.cimtbl line_by_impedance, line_by_wire_configuration, switch; the line's own impedance ln_<name>_lc (isTemplate=false), synthesized ln_<name>_wc; ratings as OperationalLimitSet + CurrentLimit the master (Feeder, BaseVoltage, OperationalLimitType), bus.cimtbl, the catalogs
XfmrCode xfmrcode.cimtbl transformer_template (3-phase, TankEnd), transformer_template_1ph (1-phase, lugs); seasonal ratings as the template's own OperationalLimitSet + ApparentPowerLimit the instances that use it (their bus systems); the master (OperationalLimitType)
Transformer transformer.cimtbl 3-phase: transformer_by_ends; 1-phase: transformer_by_phase_ends; regulated with equal winding kV: voltage_regulator; seasonal ratings as OperationalLimitSet + ApparentPowerLimit the master (Feeder, BaseVoltage, OperationalLimitType) and the topology walk's bus systems
RegControl regcontrol.cimtbl voltage_regulator / regulator (RatioTapChanger + TapChangerControl) transformer.cimtbl
LoadShape (those a Load names as yearly) loadshape.cimtbl load_schedule (ConformLoadGroup + ConformLoadSchedule; the points in the Parquet sidecar, S8) nothing
a shape a PVSystem, Storage or Generator names as yearly is not here but that device's own EnergyConnectionSchedule, in its document (S9)
Load load.cimtbl load; exp_<CVRwatts>_<CVRvars> response rows; a ConformLoad of its yearly shape's group (S8) the master (Feeder, BaseVoltage, zip_fractions.cimtbl), bus.cimtbl, loadshape.cimtbl
Capacitor capacitor.cimtbl shunt (LinearShuntCompensator) the master, bus.cimtbl
CapControl capcontrol.cimtbl shunt (RegulatingControl + Update of the compensator) line.cimtbl, capacitor.cimtbl
PVSystem, Storage pvsystem.cimtbl, storage.cimtbl der; a yearly shape: nc_schedule EnergyConnectionSchedule <mRID>_yearly (the points in the Parquet sidecar, S9) the master, bus.cimtbl
Generator generator.cimtbl synchronous_machine; a yearly shape as for a PVSystem (S9) the master, bus.cimtbl
Reactor reactor.cimtbl series_compensator the master, bus.cimtbl
Buscoords (BusCoords / LatLongCoords files) buscoords.cimtbl (last) location every equipment part (their bound Terminals: bound_parts, S5-2)

Master

Orchestrator: cimhub_opendss/importer/dss_to_cimtbl.py (DssImporter, map_master, dss_to_cim). Golden: tests/goldens/IEEE13_CDPSM/IEEE13_CDPSM.cimtbl, tested by tests/test_dss_to_cimtbl.py. Approved 2026-11-07 (D7 as written); the common rows approved with S1.

  • File and settings (plan D7): the caller names the model (DssImporter("IEEE13_CDPSM")); it is the master's file stem and Model. Authority is https://github.com/PNNL-CIM-Tools/CIMHub unless the caller passes another. Profile = cim18v17.
  • Imports: one per non-empty part, in MAPPING_ORDER (catalogs before instances, plan section 2). A DSS class with no records writes no part and no Import.
  • Comment: the deck name, this anchor, and not mapped: with the record count of every DSS class no mapper reads yet (DSS-11), so a class never disappears silently. The list shrinks as slices land.
  • common rows (S1). The containers come from New Circuit.<circuit>, which the reader keeps as Options.circuit. A deck with no New Circuit, or with a second one, raises.

Object Substation: mRID=sub_<circuit>, name=<circuit>
Object Feeder: mRID=fdr_<circuit>, name=<circuit>, NormalEnergizingSubstation=sub_<circuit>
Object BaseFrequency: mRID=bf_60hz, frequency (Hz)=60          # defaulted: defaultbasefreq=60.0
# voltagebases: 115.0, 4.16, 13.2, 0.48, 0.208; on no bus: 0.208; not in voltagebases: 0.24
Table BaseVoltage: mRID, nominalVoltage (kV)
    bv_115kv,  115.0
    bv_13p2kv, 13.2
    ...
    bv_240v,   0.24
    bv_208v,   0.208
- mRIDs are lowercased, like every DSS mRID. - BaseFrequency is Set defaultbasefreq, else the DSS default of 60 Hz (DSS-3b). Set basefrequency raises in the reader: the engine applies it only to objects defined after it, so the deck could hold two base frequencies. - The BaseVoltages are one per distinct bus voltage of the topology walk and one per voltagebases value, each through nominal_kv, highest first. A base on no bus is kept (bv_208v above): it is what the engine's CalcVoltageBases snaps bus bases to, so the export writes it back (Set voltagebases is every BaseVoltage). Buses still take the walk's voltage (bus.cimtbl). The comment reconciles the two lists: the deck's voltagebases, those on no bus, and walk voltages missing from voltagebases (a bus the engine would snap, plan section 3.1) as not in voltagebases. This amends DSS-1 ("the walk's, never voltagebases"), on 2026-11-24 at the user's direction (test_voltagebases_on_no_bus_are_kept_for_the_engine). - The OperationalLimitTypes are olt_normal and olt_emergency (the line ratings, R1), then olt_season1 .. olt_season<N> for the most seasons any Transformer or XfmrCode Ratings rate (limit_types(seasons); see Transformer). IEEE13_CDPSM rates none, so it has only the first two. - The Substation holds the EnergySources. The Feeder holds every other piece of equipment and every ConnectivityNode, so it is the container that mappers receive.

Buses

Orchestrator: importer/dss_to_cimtbl.py (map_buses). Golden: tests/goldens/IEEE13_CDPSM/bus.cimtbl. Approved 2026-11-07: equipment keeps its own BaseVoltage (mandatory).

cim18v17 adds ConnectivityNode.BaseVoltage. The CIM text: it "is used only if the ConnectivityNode is not contained in a VoltageLevel", and "it is not required that the BaseVoltage of connected equipment is the same". There are no VoltageLevels here, so the topology walk's result becomes an artifact: one row per bus it reaches.

# Bus voltages from the topology walk (cimtopology.core) from the source buses; 22 buses.
Table ConnectivityNode: mRID, name, BaseVoltage, ConnectivityNodeContainer=fdr_ieee13nodeckt
    sourcebus, sourcebus, bv_115kv
    650z,      650z,      bv_13p2kv
    ...
  • mRID and name are the bus name, lowercased: the walk's key, and the cell every node column writes. cimtables binds a later node=650 to this node instead of creating a new one.
  • Rows are sorted highest voltage first, then by bus name, so the file does not depend on the walk's internals.
  • A bus the walk does not reach has no row. Equipment on such a bus raises in its mapper (no bus voltage), as the transformer mapper already does.

What this solves: - Every bus has a voltage, written once. A DSS Line, switch or reactor has none of its own. A bus between two transformers had a voltage only through the TransformerEnds. An exporter that needs a per-bus base (DSS setkVBase, a GridLAB-D node's nominal_voltage, the MATPOWER and RAW bus tables) reads the node instead of inferring it from the equipment. - The walk is visible. Plan section 3.1's result sits in a diffable file, not only in the mappers' buses argument. - A check on every equipment row. Equipment keeps its own BaseVoltage column, which cimtables needs as the system base of a (pu) column and which consumers of ConductingEquipment.BaseVoltage read. The bind test asserts it equals the BaseVoltage of each of the equipment's nodes. A transformer's ends already carry their own, per end.

Vsource

Mapper: importer/cimtbl/vsource.py (map_vsource). Atoms: tests/atoms/vsource/: mvasc (IEEE13_CDPSM), ohms (IEEE123), isc (IEEE4_xfmrs B1), defaults (New Circuit.x basekv=12.47) and single_phase, with prereq.cimtbl; tested by tests/test_cimtbl_vsource.py. Approved 2026-11-07.

One EnergySource per Vsource, New Circuit included (source shape):

# OpenDSS Vsource -> EnergySource on its bus; 1 Vsource.
Table EnergySource: mRID, name, node, phases, nominalVoltage (kV), voltageMagnitude (kV), voltageAngle (deg), r (ohm), x (ohm), r0 (ohm), x0 (ohm), normallyInService, BaseVoltage, EquipmentContainer=sub_ieee13nodeckt
    src_source, source, sourcebus, ABC, 115, 115, 30, 0.160376682055275, 0.641506728221101, 0.179603583012336, 0.538810749037007, true, bv_115kv  # derived from MVAsc3=20000.0, MVAsc1=21000.0; defaulted: x1r1=4.0, x0r0=3.0
  • Identity: mRID = src_ + name, lowercased.
  • Bus and phases: bus1 (default sourcebus) gives node. phases (default 3) gives ABC or, on a 1-phase source, the phase of the bus's single conductor. Any other phase count raises. A bus2 raises, because an ungrounded (series) source has no source-shape home.
  • Voltage: nominalVoltage = basekv (default 115), copied. voltageMagnitude = basekv × pu (default pu 1), derived. voltageAngle = angle (default 0), copied, in degrees.
  • Impedance. DSS has three ways to give a source's Thevenin impedance, and keeps the one set last (Vsource properties, VSource.pas PropertySideEffects). The reader does not record the order, so, as for LineCode, a Vsource that sets two groups raises:
  • R1 X1 R0 X0 (ohms): copied. All four must be set; a partial set raises.
  • MVAsc3 MVAsc1 (with x1r1, x0r0): derived by vsource.thevenin_from_short_circuit, which follows VSource.pas RecalcElementData:
    • X1 = kV² / MVAsc3 / √(1 + 1/x1r1²) and R1 = X1 / x1r1;
    • R0 is the positive root of (1 + x0r0²)·R0² + 4(R1 + X1·x0r0)·R0 + 4(R1² + X1²) − (3·kV²/MVAsc1)² = 0, and X0 = R0 · x0r0;
    • a negative discriminant raises, and so do kV, MVAsc3, MVAsc1 or x1r1 not above 0, x0r0 below 0 and a negative R0: the engine refuses some and computes a negative, infinite or zero impedance for the rest. A slot left unset takes its DSS default (MVAsc3 2000, MVAsc1 2100, x1r1 4, x0r0 3) under # defaulted. A Vsource that sets no group takes all four defaults, as the engine does. LineCode raises in that case instead, but a bare New Circuit.x basekv=12.47 is the documented minimal deck.
  • Isc3 Isc1 (amps): the short-circuit power, √3·kV·Isc3 and f·kV·Isc1 (f = √3 on 3 phases and 1 on 1 phase; vsource.kvasc_from_isc), then as group 2. kV times A is kVA, and kV² / kVA is kohm, so these rows go in their own table with r (kohm), x (kohm), r0 (kohm), x0 (kohm): the units travel with the values and no factor appears. Both must be set; a partial set raises (Isc3=1000 alone at 12.47 kV gives the engine a negative R0).
  • Checked against the engine (opendssdirect, 9 digits): IEEE13's MVAsc, all defaults, MVAsc3 alone, Isc, and a 1-phase source.
  • Z1 Z0 Z2 puZ1 puZ0 puZ2 baseMVA raise when set: no deck in the sweep uses them, so a mapping waits for one.
  • Group 2 and 3 values are derived numbers, so the row comment names their inputs. The test oracle is the engine: r x r0 x0 must equal ? Vsource.<name>.R1 etc. after compile, on every engine deck.
  • enabled → normallyInService, copied.
  • Untranscribed: frequency and basefreq (the master's BaseFrequency is the deck's), ScanType, Sequence, spectrum (harmonics), Yearly, Daily, Duty (time series), Model, puZideal.
  • Reader and schema changes of this slice: the reader keeps the circuit name on Options.circuit and no longer writes bus1=sourcebus into a New Circuit's parameters; the schema's dss_defaults on Vsource carry the defaults, which importer/topology.py takes through vsource.with_defaults. Clear discards everything before it (the IEEE4 balanced decks build, solve and rebuild). x1r1, x0r0 and frequency are floats, and puZ1/puZ0/puZ2 are [R, X] arrays like Z1.

LineCode

Mapper: cimhub_opendss/importer/cimtbl/linecode.py (map_linecode). Atoms: tests/atoms/linecode/mtx601.{dss,cimtbl} (matrix, IEEE13_CDPSM) and seq_3_1_0c.{dss,cimtbl} (sequence, IEEE8500), tested by tests/test_cimtbl_linecode.py.

Identity. mRID = lc_ + name, lowercased (DSS names are case-insensitive). PhaseImpedanceData has no mRID; its identifier column is <mRID>_<row><column>.

Template (DSS-14, the user's rule 2026-11-21). A LineCode is a template its lines share by name: its impedance has isTemplate=true, and a WireConfiguration <template>_wc (lc_<name>_wc, or lc_<name>_<unit>_wc per DSS-3) holds it as PerLengthImpedance, with no WireSpacing. Lines reference that WireConfiguration, not the impedance. The WireConfiguration is CIM's equivalence route: a configuration with a spacing is geometry, one with only a PerLengthImpedance is a template LineCode, and one with both is geometry with its equivalent impedance. Exporters read it through get_line_geometry and get_line_code (cimhub_core.getters.line_impedance). An impedance only one line uses, the line's own values, is ACLineSegment.PerLengthImpedance with isTemplate=false (Line, below).

Form. A code that sets any of r1 x1 r0 x0 C1 C0 B1 B0 is a sequence code (OpenDSS Line properties); one that sets rmatrix/xmatrix/cmatrix is a matrix code. DSS keeps whichever form was set last, and the reader does not record the order, so a code that sets both raises. So does a code that sets neither (DSS would apply its defaults).

Values. The DSS reader yields floats for most slots (written as repr()), but C1, C0, B1, B0 and baseFreq as the file's text. One table per header: matrix data per length unit, sequence codes per (length unit, bch/b0ch source), because a C-derived bch is in nS and a copied B1 in uS.

Linecode field type samples kind target
name Union[str, LinecodeName] mtx601, mtx602, mtx603 copied PerLengthPhaseImpedance.name, PerLengthSequenceImpedance.name, WireConfiguration.name; mRID = lc_ + name, lowercased; its WireConfiguration's lc__wc (DSS-14)
nphases Optional[int] 3, 2 copied PerLengthPhaseImpedance.conductorCount; the matrix order of rmatrix/xmatrix/cmatrix; a 1- or 2-phase sequence code becomes a phase matrix as the engine builds the line (phase_matrix): 1-phase z = Z1, 2-phase Zs = (2 Z1 + Z0)/3 and Zm = (Z0 - Z1)/3 (DSS-4); unset = the engine's default 3 (defaulted)
r1 Optional[float] 0.769009, 0.3489, 0.535622 copied PerLengthSequenceImpedance.r (ohm/{length})
x1 Optional[float] 0.312115, 0.491691, 0.560725 copied PerLengthSequenceImpedance.x (ohm/{length})
r0 Optional[float] 1.294322, 0.613107, 0.608571 copied PerLengthSequenceImpedance.r0 (ohm/{length})
x0 Optional[float] 0.287695, 1.241561, 1.19452 copied PerLengthSequenceImpedance.x0 (ohm/{length})
C1 Optional[float] 154.240283543118, 8.96939698228171, 9.08509466816236 derived PerLengthSequenceImpedance bch = 2 pi baseFreq C1 (b_from_c): nF -> nS
C0 Optional[float] 154.240283543118, 4.95311934077534, 5.10821052765362 derived PerLengthSequenceImpedance b0ch = 2 pi baseFreq C0 (b_from_c): nF -> nS
units Optional[str] mi, km mapped the length unit of every per-length header via LENGTH_UNIT; unset: the unit of the lines that use the code, else the deck's magnitude gate (DSS-3)
rmatrix Union[float, list[float], NoneType] [0.3465, 0.1535, 0.3375, 0.158, 0.156..., [0.7526, 0.1535, 0.7475, 0.156, 0.158..., [1.3238, 0.2066, 1.3294] structural PhaseImpedanceData r, one row per lower-triangle element
xmatrix Union[float, list[float], NoneType] [1.0179, 0.3849, 1.0478, 0.4236, 0.50..., [1.1814, 0.3849, 1.1983, 0.5017, 0.42..., [1.3569, 0.4591, 1.3471] structural PhaseImpedanceData x, one row per lower-triangle element
cmatrix Union[float, list[float], NoneType] [0.0, 0.0, 0.0, 0.0, 0.0, 0.0], [0.0, 0.0, 0.0] derived PhaseImpedanceData b = 2 pi baseFreq C (b_from_c): nF -> nS
baseFreq Optional[float] 60 copied PerLengthPhaseImpedance.calculatedFrequency (Hz), PerLengthSequenceImpedance.calculatedFrequency (Hz); also the frequency of the derived b; unset with a nonzero C: the deck's base frequency, defaulted (DSS-3b)
normamps Optional[float] 730.0, 340.0, 230.0 untranscribed catalog ratings have no home on PerLengthImpedance; instance limits or untranscribed (plan D9)
emergamps Optional[float] 160.0, 310.0, 260.0 untranscribed catalog ratings have no home on PerLengthImpedance; instance limits or untranscribed (plan D9)
faultrate Optional[float] 0 untranscribed reliability data; no home in the network profile parts
pctperm Optional[float] 20.0 untranscribed reliability data; no home in the network profile parts
repair Optional[float] 3 untranscribed reliability data; no home in the network profile parts
Kron Union[bool, Bool, NoneType] untranscribed input of the matrix calculation; no CIM home
Rg Optional[float] untranscribed Carson earth return per length; home PerLengthImpedance.rg/xg (ohm/), not mapped until a deck sets it (none of the test decks do)
Xg Optional[float] untranscribed Carson earth return per length; home PerLengthImpedance.rg/xg (ohm/), not mapped until a deck sets it (none of the test decks do)
rho Optional[float] untranscribed earth resistivity; home EarthResistivity.rho, an object of its own, not mapped until a deck sets it
neutral Optional[int] untranscribed input of the matrix calculation; no CIM home
B1 Optional[float] copied PerLengthSequenceImpedance.bch (uS/{length}); the alternative to C1
B0 Optional[float] copied PerLengthSequenceImpedance.b0ch (uS/{length}); the alternative to C0
Seasons Optional[int] untranscribed catalog ratings have no home on PerLengthImpedance; instance limits or untranscribed (plan D9)
Ratings Union[float, list[float], NoneType] untranscribed catalog ratings have no home on PerLengthImpedance; instance limits or untranscribed (plan D9)
LineType Optional[str] untranscribed no home in the network profile parts
like Optional[str] untranscribed the reader resolves like= before mapping

Derived. b_from_c(c, f) = 2πfC: C in nF and f in Hz give b in nS. susceptance applies it per value; C = 0 gives b = 0 without a baseFreq (ACEP_PSIL buswork sets none).

Fail fast. A units value with no mapping; a unitless code whose lines give units on some lines only, or a gate median in no band; both C1 and B1 (or C0 and B0); both forms or neither; B1/B0 on a 1- or 2-phase code; C0 without C1 on a 2-phase code (the engine completes it with its default C1); a matrix whose length does not fit nphases. A code with no nphases takes the engine's 3 (with_default_phases, noted defaulted: nphases=3). A switch's linecode gives the code no units (DSS-8).

Deck sweep (2026-11-06). 9 of the 24 decks with line codes map and bind. The rest stop on:

stop decks open point
nonzero cmatrix without baseFreq ieee9500 (both copies), IEEE8500 and K1 triplex DSS takes the circuit's default base frequency. Take it from the deck's Circuit/Set DefaultBaseFrequency, else 60 Hz?
units unset IEEE13_original, IEEE123_deconfliction, EPRI M1 and J1 DSS reads the values per unit of the line's length, so the per-length unit belongs to the instance. Defer the code to the Line mapper, or require units?
1-/2-phase sequence code EPRI J1 (17 codes) The engine (J1, 2026-11-06) builds a 1-phase line from Z1 alone (oh_b13552: R = R1, X = X1, C = C1 per length) and a 2-phase line from Zs = (2Z1 + Z0)/3, Zm = (Z0 − Z1)/3 (oh_b41869). The LineCode object itself reports (2Z1 + Z0)/3 for both, so the code alone does not fix the value. Proposal in DSS_REWRITE_PLAN.md (DSS-4)
two mRIDs give one UUID IEEE8500 (lc_1p_#2acsr_#2n vs lc_1p_#2arv_#2n) CIM-Profiles bug: the mRID seed drops text up to the last # (CIMTABLES_REQUESTS R10)
nphases=4 read as 3 IEEE13_OCHRE reader bug: it limits nphases to [1, 3] and substitutes 3, so the 10-value rmatrix no longer fits

Reader/schema findings (not mapper issues, fixed 2026-11-24): faultrate was typed int, so 0.1 read as 0; LineType was typed float (DSS values are words such as oh); C1/C0/B1/B0/baseFreq were typed str. Every slot now has the engine's property type (test_schema_types_match_the_engine), so baseFreq=60 is the float 60.0 and its calculatedFrequency (Hz) cell is 60.0, as every other float cell is written (repr).

Expected differences from the hand translation (CIMTBL-Models/.../IEEE13_CDPSM): it carries the 2011 corrected off-diagonals; the import keeps the deck's values (mtx601 r21 = 0.1535).

LineCode: units, base frequency, short sequence codes (S2, approved 2026-11-07)

S2 lifts three of the fail-fast stops above (the sweep tables below are the pre-S2 record), as decided in DSS_REWRITE_PLAN.md §6. They are the stops for 16 of the 31 sweep decks.

  • units unset (DSS-3). DSS reads a unitless code per unit of the line's length, so:
  • (a) a code used by lines that give units takes the line's unit (J1: 1,382 lines, all kft). Lines that disagree give one template per unit, lc_<name>_<unit>.
  • (b) code and lines both unitless (M1, IEEE123_deconfliction), or a unitless code no line uses (IEEE13_original): a deck-level magnitude gate on the median positive r1 (or rmatrix diagonal) of the deck's unitless codes. 0.006 to 10 per unit gives km; 1e-5 to 0.006 gives m; anything else raises. length_unit= on the importer overrides the gate.

The row comment states the unit's source: # units from its lines: kft (...), # units inferred: km (median r 0.134 per unit over 17 codes; no units on code or line) (M1), or # units given: ... for length_unit=. Inferred in the sweep: km for M1, IEEE123, IEEE123_deconfliction, IEEE13_original, IEEE37 and J1's 2 unused codes; J1's 4 used codes take kft from their lines. Code and line share the unit, so z·length is exact for any label. A wrong label only scales the physical length. The mapper reads the Lines (their linecode and units) for this; it maps none of them. - A nonzero C without baseFreq (DSS-3b). b_from_c takes the master's base frequency (Set defaultbasefreq, else 60 Hz), and the row says # defaulted: baseFreq=60. - 1- and 2-phase sequence codes (DSS-4; J1, 17 codes). These become a derived PerLengthPhaseImpedance + PhaseImpedanceData, as the engine builds the line. 1-phase: z = Z1, b from C1. 2-phase: Zs = (2 Z1 + Z0)/3 and Zm = (Z0 − Z1)/3, the same for C. The function is cimhub_core.derived.sequence.phase_matrix (closed form, not Carson; a U4 candidate). Atom short_sequence.dss (two J1 codes, one line each): r, x and b equal the engine's line matrices. A 1-phase row lists the r0/x0/C0 the line does not use; B1/B0 on a short code raises. - D9: normamps/emergamps stay untranscribed on a LineCode (no home on PerLengthImpedance).

Wire catalogs

Mapper: cimhub_opendss/importer/cimtbl/wire.py (map_wires(native, native_class, prefix, fields)). Shape: wire_info. Atoms: tests/atoms/wire/assets.dss (IEEE13_Assets: Rdc-only ACSR, Rac-only CU, CN_250, TS_1/0) and metric.dss (one IEEE9500 wire, km/cm), tested by tests/test_cimtbl_wire.py. Approved 2026-11-07, with Rac filled from Rdc and the TS screen diameter = DiaShield − 2 TapeLayer.

Identity. One file per DSS class (D4): wiredata.cimtbl, cndata.cimtbl, tsdata.cimtbl. mRID = wire_, cn_ or ts_ + name, lowercased. Each DSS class is its own namespace, so the prefixes keep a WireData and a CNData of one name apart.

Units. Runits (resistance per length), GMRunits and radunits become header units, values as written. A cable's dimensions (DiaIns, DiaCable, InsLayer, DiaStrand, DiaShield, TapeLayer) are in radunits. GmrStrand is in GMRunits and Rstrand in Runits, as DSS states. The mapper writes one table per unit combination, as LineCode writes one per length unit. IEEE13_Assets gives two tables (kft/in/in and mi/in/in); the IEEE9500 wires give one (km/cm/cm). An unset selector raises; every wire in the sweep sets all three.

Values the engine fills (DSS-6, in the row comment): - Rac unset: rAC25 = 1.02 × Rdc, the engine's rule (ac_from_dc; the 9 IEEE4/IEEE13_Assets ACSR wires). Rdc unset is left unset: the engine only uses Rdc to fill Rac. - diam: radius = diam / 2 (radius_from_diameter). Setting both radius and diam raises (DSS keeps the last, which the reader does not record); so does setting neither. - GMRac unset: raises. The engine would take 0.7788 × radius, but no deck in the sweep omits GMRac.

Cables follow EPRI's ExportCIMXML wherever CIM has no exact twin: - Rac → rAC25 (DSS gives no temperature) and Rstrand → neutralStrandRDC20 (DSS calls it AC; CIM has only the one strand resistance). Only rAC25 is written, never the same value copied to rAC50/rAC75. - CN DiaCable → both diameterOverJacket and diameterOverNeutral: the strands are outermost. CN's diameterOverScreen is not written; it is derivable and no consumer needs it. - TS diameterOverScreen = DiaShield − 2 TapeLayer (screen_diameter). DSS measures over the tape; CIM's screen diameter is the shield's inside. - EpsR is untranscribed: CableInfo has no permittivity. Every cable in the sweep uses the DSS default, 2.3.

Ratings (approved 2026-11-08). A rated wire's normamps is ratedCurrent, as before. It also becomes an OperationalLimitSet <mRID>_limits on the new GridAPPS-D AssetInfo.OperationalLimitSet (the serialized side, so the wire row names its set and the set is written first). The set has two CurrentLimits: - <mRID>_norm = normamps on olt_normal; - <mRID>_emerg = emergamps on olt_emergency. An unset emergamps is 1.5 × normamps, the engine's rule (wire_ratings, # defaulted: emergamps = 1.5 x normamps). An unset normamps with emergamps set is emergamps / 1.5, also the engine's, written to ratedCurrent and <mRID>_norm (# defaulted: normamps = emergamps / 1.5).

The two limit types are the master's. An unrated wire gets no set (DSS's 400/600 A defaults are not written). Seasons/Ratings raise when set, as on a Line. The line mapper uses the same wire_ratings for a geometry line's first conductor.

Example (wiredata.cimtbl, IEEE13_Assets):

Table OperationalLimitSet: mRID
    wire_acsr_1/0_limits
    ...
Table CurrentLimit: mRID, normalValue (A), OperationalLimitType, OperationalLimitSet
    wire_acsr_1/0_norm,    230.0,  olt_normal,    wire_acsr_1/0_limits
    # defaulted: emergamps = 1.5 x normamps
    wire_acsr_1/0_emerg,   345.0,  olt_emergency, wire_acsr_1/0_limits
    ...
Table OverheadWireInfo: mRID, name, rDC20 (ohm/kft), rAC25 (ohm/kft), gmr (in), radius (in), ratedCurrent (A), OperationalLimitSet
    # defaulted: Rac = 1.02 x Rdc
    wire_acsr_1/0,   ACSR_1/0,   0.212121212, 0.21636363624000002, 0.05352, 0.199,  230.0, wire_acsr_1/0_limits
    ...

Fail fast: a unit selector unset; radius and diam both set or neither; GMRac unset; Capradius, SemiconLayer, Seasons or Ratings set (no deck sets them).

Oracle: every written value equals the engine's property in the engine's units (opendssdirect WireData / CNData / TSData), including the filled Rac and the normal and emergency ratings, on the vendored IEEE13_Assets and IEEE4 decks (test_values_match_the_engine).

Wiredata field type samples kind target
name Union[str, WiredataName] ACSR_1/0, ACSR_4/0, ACSR_556_5 copied OverheadWireInfo.name; mRID = prefix + name, lowercased
Rdc Optional[float] 0.212121212, 0.112121212, 0.035227273 copied OverheadWireInfo.rDC20 (ohm/{r_length}); DC resistance (DSS gives no temperature)
Rac Optional[float] 0.607, 1.010411, 0.939016 copied OverheadWireInfo.rAC25 (ohm/{r_length}); DSS: resistance at 60 Hz, temperature unstated; rAC25 as in EPRI's ExportCIMXML. Unset: 1.02 x Rdc, the engine's rule (ac_from_dc), with a defaulted comment
Runits Optional[str] kft, mi, km mapped the unit of Rdc, Rac in the header (LENGTH_UNIT); unset raises (every wire in the sweep sets it)
GMRac Optional[float] 0.05352, 0.09768, 0.3732 copied OverheadWireInfo.gmr ({gmr_length}); unset raises (the engine's 0.7788 x radius default; no deck in the sweep omits it)
GMRunits Optional[str] in, cm, ft mapped the unit of GMRac in the header (LENGTH_UNIT); unset raises (every wire in the sweep sets it)
radius Optional[float] 0.40132, 0.39624, 0.37084 copied OverheadWireInfo.radius ({radius_length}); one of radius and diam; both raise (DSS keeps the last, the reader does not record which), neither raises
radunits Optional[str] in, cm mapped the unit of radius, diam and every cable dimension in the header (LENGTH_UNIT); unset raises (every wire in the sweep sets it)
normamps Optional[float] 230.0, 340.0, 730.0 copied OverheadWireInfo.ratedCurrent (A); also the normal CurrentLimit of the wire's OperationalLimitSet _limits (AssetInfo.OperationalLimitSet); unset with emergamps set: emergamps / 1.5 (wire_ratings, the engine's rule), defaulted
emergamps Optional[float] 200.0, 239.0, 172.0 structural the emergency CurrentLimit of the wire's OperationalLimitSet _limits (AssetInfo.OperationalLimitSet); unset: 1.5 x normamps (wire_ratings, the engine's rule), defaulted
diam Optional[float] 0.398, 0.563, 0.927 derived radius = diam / 2 (radius_from_diameter)
Seasons Optional[int] structural raises when set: no deck in the sweep sets it, so a mapping waits for one (an indexed rating array that names no calendar season; home OperationalLimitType.season)
Ratings Union[float, list[float], NoneType] structural raises when set: no deck in the sweep sets it, so a mapping waits for one (with Seasons)
Capradius Optional[float] structural raises when set: no deck in the sweep sets it, so a mapping waits for one (the radius for capacitance; not WireInfo.coreRadius)
like Optional[str] untranscribed the reader resolves like= before mapping
Cndata field type samples kind target
name Union[str, CndataName] CN_250, 1/0_Al_15kV_1/3 copied ConcentricNeutralCableInfo.name; mRID = prefix + name, lowercased
k Optional[int] 13, 6 copied ConcentricNeutralCableInfo.neutralStrandCount
DiaStrand Optional[float] 0.0641, 0.064 derived neutralStrandRadius = DiaStrand / 2 (radius_from_diameter), radunits
GmrStrand Optional[float] 0.02496 copied ConcentricNeutralCableInfo.neutralStrandGmr ({gmr_length}); in GMRunits, as DSS says
Rstrand Optional[float] 14.8722, 2.55 copied ConcentricNeutralCableInfo.neutralStrandRDC20 (ohm/{r_length}); DSS calls it the strand's AC resistance; neutralStrandRDC20 as in ExportCIMXML, CIM's only strand resistance
SemiconLayer Union[bool, Bool, NoneType] structural raises when set: no deck in the sweep sets it, so a mapping waits for one
EpsR Optional[float] 2.3 untranscribed insulation relative permittivity; no home on CableInfo (InsulationInfo has a material, not a permittivity). DSS default 2.3, which every cable in the sweep uses
InsLayer Optional[float] 0.22, 0.445 copied ConcentricNeutralCableInfo.insulationThickness ({radius_length})
DiaIns Optional[float] 1.06, 2.11 copied ConcentricNeutralCableInfo.diameterOverInsulation ({radius_length})
DiaCable Optional[float] 1.29, 2.74 copied ConcentricNeutralCableInfo.diameterOverJacket ({radius_length}), ConcentricNeutralCableInfo.diameterOverNeutral ({radius_length}); the outer diameter; a CN cable has no jacket over its strands, so it is also the diameter over the neutral (ExportCIMXML)
Rdc Optional[float] copied ConcentricNeutralCableInfo.rDC20 (ohm/{r_length}); DC resistance (DSS gives no temperature)
Rac Optional[float] 0.41, 0.603 copied ConcentricNeutralCableInfo.rAC25 (ohm/{r_length}); DSS: resistance at 60 Hz, temperature unstated; rAC25 as in EPRI's ExportCIMXML. Unset: 1.02 x Rdc, the engine's rule (ac_from_dc), with a defaulted comment
Runits Optional[str] mi, km mapped the unit of Rdc, Rac, Rstrand in the header (LENGTH_UNIT); unset raises (every wire in the sweep sets it)
GMRac Optional[float] 0.2052, 0.338 copied ConcentricNeutralCableInfo.gmr ({gmr_length}); unset raises (the engine's 0.7788 x radius default; no deck in the sweep omits it)
GMRunits Optional[str] in, cm mapped the unit of GMRac, GmrStrand in the header (LENGTH_UNIT); unset raises (every wire in the sweep sets it)
radius Optional[float] copied ConcentricNeutralCableInfo.radius ({radius_length}); one of radius and diam; both raise (DSS keeps the last, the reader does not record which), neither raises
radunits Optional[str] in, cm mapped the unit of radius, diam and every cable dimension in the header (LENGTH_UNIT); unset raises (every wire in the sweep sets it)
normamps Optional[float] 260.0 copied ConcentricNeutralCableInfo.ratedCurrent (A); also the normal CurrentLimit of the wire's OperationalLimitSet _limits (AssetInfo.OperationalLimitSet); unset with emergamps set: emergamps / 1.5 (wire_ratings, the engine's rule), defaulted
emergamps Optional[float] structural the emergency CurrentLimit of the wire's OperationalLimitSet _limits (AssetInfo.OperationalLimitSet); unset: 1.5 x normamps (wire_ratings, the engine's rule), defaulted
diam Optional[float] 0.567, 0.935 derived radius = diam / 2 (radius_from_diameter)
Seasons Optional[int] structural raises when set: no deck in the sweep sets it, so a mapping waits for one (an indexed rating array that names no calendar season; home OperationalLimitType.season)
Ratings Union[float, list[float], NoneType] structural raises when set: no deck in the sweep sets it, so a mapping waits for one (with Seasons)
Capradius Optional[float] structural raises when set: no deck in the sweep sets it, so a mapping waits for one (the radius for capacitance; not WireInfo.coreRadius)
like Optional[str] untranscribed the reader resolves like= before mapping
Tsdata field type samples kind target
name Union[str, TsdataName] TS_1/0 copied TapeShieldCableInfo.name; mRID = prefix + name, lowercased
DiaShield Optional[float] 0.88 derived diameterOverScreen = DiaShield - 2 TapeLayer (screen_diameter): DSS measures over the tape, CIM's screen diameter is the shield's inside (ExportCIMXML)
TapeLayer Optional[float] 0.005 copied TapeShieldCableInfo.tapeThickness ({radius_length})
TapeLap Optional[float] 20.0 copied TapeShieldCableInfo.tapeLap (percent)
EpsR Optional[float] 2.3 untranscribed insulation relative permittivity; no home on CableInfo (InsulationInfo has a material, not a permittivity). DSS default 2.3, which every cable in the sweep uses
InsLayer Optional[float] 0.22 copied TapeShieldCableInfo.insulationThickness ({radius_length})
DiaIns Optional[float] 0.82 copied TapeShieldCableInfo.diameterOverInsulation ({radius_length})
DiaCable Optional[float] 1.06 copied TapeShieldCableInfo.diameterOverJacket ({radius_length}); the outer diameter
Rdc Optional[float] copied TapeShieldCableInfo.rDC20 (ohm/{r_length}); DC resistance (DSS gives no temperature)
Rac Optional[float] 0.97 copied TapeShieldCableInfo.rAC25 (ohm/{r_length}); DSS: resistance at 60 Hz, temperature unstated; rAC25 as in EPRI's ExportCIMXML. Unset: 1.02 x Rdc, the engine's rule (ac_from_dc), with a defaulted comment
Runits Optional[str] mi mapped the unit of Rdc, Rac in the header (LENGTH_UNIT); unset raises (every wire in the sweep sets it)
GMRac Optional[float] 0.1332 copied TapeShieldCableInfo.gmr ({gmr_length}); unset raises (the engine's 0.7788 x radius default; no deck in the sweep omits it)
GMRunits Optional[str] in mapped the unit of GMRac in the header (LENGTH_UNIT); unset raises (every wire in the sweep sets it)
radius Optional[float] copied TapeShieldCableInfo.radius ({radius_length}); one of radius and diam; both raise (DSS keeps the last, the reader does not record which), neither raises
radunits Optional[str] in mapped the unit of radius, diam and every cable dimension in the header (LENGTH_UNIT); unset raises (every wire in the sweep sets it)
normamps Optional[float] 165.0 copied TapeShieldCableInfo.ratedCurrent (A); also the normal CurrentLimit of the wire's OperationalLimitSet _limits (AssetInfo.OperationalLimitSet); unset with emergamps set: emergamps / 1.5 (wire_ratings, the engine's rule), defaulted
emergamps Optional[float] structural the emergency CurrentLimit of the wire's OperationalLimitSet _limits (AssetInfo.OperationalLimitSet); unset: 1.5 x normamps (wire_ratings, the engine's rule), defaulted
diam Optional[float] 0.368 derived radius = diam / 2 (radius_from_diameter)
Seasons Optional[int] structural raises when set: no deck in the sweep sets it, so a mapping waits for one (an indexed rating array that names no calendar season; home OperationalLimitType.season)
Ratings Union[float, list[float], NoneType] structural raises when set: no deck in the sweep sets it, so a mapping waits for one (with Seasons)
Capradius Optional[float] structural raises when set: no deck in the sweep sets it, so a mapping waits for one (the radius for capacitance; not WireInfo.coreRadius)
like Optional[str] untranscribed the reader resolves like= before mapping

LineSpacing and LineGeometry

Mapper: cimhub_opendss/importer/cimtbl/geometry.py (map_linespacing, map_linegeometry). Shape: line_by_wire_configuration. Geometry stays geometry: no impedance is computed (the conductor-geometry skill). Atom: tests/atoms/geometry/assets.dss from IEEE13_Assets: spacing 500 with geometry 601 (the spacing= form), 606 (inline CN positions) and 607 (inline: a TS phase and a bare CU neutral), tested by tests/test_cimtbl_geometry.py. Approved 2026-11-07.

LineSpacing → linespacing.cimtbl. An XYSpacing spc_<name> (isTemplate=true) and one XYConductorPosition per conductor: sequenceNumber 1..nconds, xCoord/yCoord from x/h in the spacing's units, and kind phase for 1..nphases, neutral after (DSS's convention). detailed=Yes is the engine default (LineSpacing.pas:213 sets FEquivalentSpacing := not detailed, FALSE by default at :327) and maps the positions as usual. The equivalent-spacing form, detailed=No, has no positions and raises, and so does EqDistPhPh, EqDistPhN, AvgPhaseHeight or AvgNeutralHeight set at any value: it takes every phase-phase and neutral-neutral distance from EqDistPhPh, every phase-neutral one from EqDistPhN, and the image distances from 2 x AvgPhaseHeight, 2 x AvgNeutralHeight or their sum for a phase-neutral pair (LineConstants.pas:218-297), which no set of XY positions reproduces in general (M19, decision 10, 2026-11-27; rc_2 had detailed inverted). No deck uses it, and opendssdirect 0.9.4 does not know these slots, so the tests check the mapper alone.

LineGeometry → linegeometry.cimtbl. A WireConfiguration wc_<name> (numberOfPhases = nphases) and one WireSequenceConfiguration per conductor, naming its WireInfo. Its WireSpacing is: - spacing= → spc_<spacing> from linespacing.cimtbl. - inline positions (cond=1 x=.. h=..) → a synthesized XYSpacing wc_<name>_spc in linegeometry.cimtbl, under # synthesized, built like a LineSpacing.

Conductor names. The reader gives them in cond order in one of wires, cncables, tscables. A mixed assembly (607) arrives whole in wires, so the array says nothing about the kind. Each name must therefore be in exactly one of WireData, CNData and TSData; a name in two raises.

Example (linegeometry.cimtbl, 607):

# synthesized: the inline positions of LineGeometry 607
Object XYSpacing: mRID=wc_607_spc, name=607, isTemplate=true
Table XYConductorPosition: mRID, XYSpacing=wc_607_spc, sequenceNumber, xCoord (ft), yCoord (ft), kind
    wc_607_spc_1, 1, 0.0,  -4.0, phase
    wc_607_spc_2, 2, 0.25, -4.0, neutral

# untranscribed: reduce=true
Object WireConfiguration: mRID=wc_607, name=607, numberOfPhases=1, WireSpacing=wc_607_spc

Table WireSequenceConfiguration: mRID, WireConfiguration=wc_607, sequenceNumber, WireInfo
    wc_607_1, 1, ts_ts_1/0
    wc_607_2, 2, wire_cu_1/0

Earth. linegeometry.cimtbl opens with the deck's one EarthResistivity earth (Set earthmodel and the geometry lines' rho), which every WireConfiguration names. A deck without geometry that sets earthmodel still gets it, floating (no line names it), so the export can write the setting back; a deck with neither gets none (S6g below).

Untranscribed: reduce (Kron reduction is the consumer's choice from the segment's phases; 242 of 243 set it), ratings (D9), LineType.

Reader fix: the reader kept the last units of the cond= blocks, so conductors in different units were misread. It now raises when the blocks disagree; a block without units takes the last given, else DSS's initial ft. No deck mixes units (engine-checked).

Fail fast: two name arrays; a name count or position count other than nconds; spacing= together with inline positions; inline positions without units; a name in no catalog or in two; the scalar cond/wire/x/h without the arrays.

Oracle: for every geometry the conductor names, coordinates and phase count equal the engine's (LineGeometries.Conductors/Xcoords/Ycoords/Phases; test_geometries_match_the_engine on the vendored IEEE13_Assets and IEEE4 decks). Checked by hand 2026-11-07, all match: IEEE9500 balanced 70 (both copies), YYD 3.

Linespacing field type samples kind target
name Union[str, LinespacingName] 500, 505, 510 copied XYSpacing.name; mRID = spc_ + name, lowercased; isTemplate = true
nconds Optional[int] 4, 3, 2 structural one XYConductorPosition per conductor, sequenceNumber 1..nconds; x and h must have nconds values
nphases Optional[int] 3, 2, 1 structural kind: phase for conductors 1..nphases, neutral after
x Union[float, list[float], NoneType] [-4.0, -1.0, 3.0, 0.0], [-4.0, 3.0, 0.0], [0.5, 0.0] structural XYConductorPosition.xCoord ({length}), one per conductor
h Union[float, list[float], NoneType] [28.0, 28.0, 28.0, 24.0], [28.0, 28.0, 24.0], [29.0, 24.0] structural XYConductorPosition.yCoord ({length}), one per conductor
units Optional[str] ft mapped the length unit of xCoord and yCoord (LENGTH_UNIT); unset raises
detailed Union[bool, Bool, NoneType] structural Yes (the default, LineSpacing.pas:213, :327) maps the positions; No (the equivalent-spacing form) raises: it has no positions
EqDistPhPh Optional[str] structural raises when set, at any value: detailed=No takes phase-phase and neutral-neutral distances from EqDistPhPh, phase-neutral ones from EqDistPhN and the image distances from 2 x AvgPhaseHeight, 2 x AvgNeutralHeight or their sum (LineConstants.pas:218-297), which no XY positions reproduce in general
EqDistPhN Optional[str] structural raises when set, at any value: detailed=No takes phase-phase and neutral-neutral distances from EqDistPhPh, phase-neutral ones from EqDistPhN and the image distances from 2 x AvgPhaseHeight, 2 x AvgNeutralHeight or their sum (LineConstants.pas:218-297), which no XY positions reproduce in general
AvgPhaseHeight Optional[str] structural raises when set, at any value: detailed=No takes phase-phase and neutral-neutral distances from EqDistPhPh, phase-neutral ones from EqDistPhN and the image distances from 2 x AvgPhaseHeight, 2 x AvgNeutralHeight or their sum (LineConstants.pas:218-297), which no XY positions reproduce in general
AvgNeutralHeight Optional[str] structural raises when set, at any value: detailed=No takes phase-phase and neutral-neutral distances from EqDistPhPh, phase-neutral ones from EqDistPhN and the image distances from 2 x AvgPhaseHeight, 2 x AvgNeutralHeight or their sum (LineConstants.pas:218-297), which no XY positions reproduce in general
like Optional[str] untranscribed the reader resolves like= before mapping
Linegeometry field type samples kind target
name Union[str, LinegeometryName] 601, 602, 603 copied WireConfiguration.name; mRID = wc_ + name, lowercased
nconds Optional[int] 4, 3, 2 structural one WireSequenceConfiguration per conductor, sequenceNumber 1..nconds; the conductor names and (inline) positions must have nconds values
nphases Optional[int] 3, 2, 1 copied WireConfiguration.numberOfPhases; also the kind of an inline position: phase for 1..nphases, neutral after
cond Optional[int] 3, 2, 1 structural the reader folds the cond= blocks into the arrays; set alone (no cond=) it raises
wire Optional[str] CU_1/0, 2_ACSR, 1/0_TPX structural the reader folds the cond= blocks into the arrays; set alone (no cond=) it raises
x Optional[float] 0.5, 0.25, 0.1524 structural the reader folds the cond= blocks into the arrays; set alone (no cond=) it raises
h Optional[float] -4.0, 8.2296, -1.22 structural the reader folds the cond= blocks into the arrays; set alone (no cond=) it raises
units Optional[str] ft, m mapped the length unit of the inline positions (LENGTH_UNIT); unset raises. The reader raises when the cond= blocks give different units
normamps Optional[float] untranscribed no home on a WireConfiguration; instance limits or untranscribed (plan D9)
emergamps Optional[float] untranscribed no home on a WireConfiguration; instance limits or untranscribed (plan D9)
reduce Union[bool, Bool, NoneType] True untranscribed Kron reduction of the neutrals; a solver choice the consumer makes from the segment's phases
spacing Optional[str] 500, 505, 510 structural WireConfiguration.WireSpacing = spc_ + spacing; with inline positions it raises
wires Union[str, list[str], NoneType] ['ACSR_556_5', 'ACSR_556_5', 'ACSR_55..., ['ACSR_4/0', 'ACSR_4/0', 'ACSR_4/0', ..., ['ACSR_1/0', 'ACSR_1/0', 'ACSR_1/0'] structural the conductor names in cond order; each resolves to exactly one of WireData, CNData, TSData (a name in two raises) and is the WireSequenceConfiguration.WireInfo. A mixed assembly (607: a TS phase, a bare neutral) arrives here whole, so the array carries no kind
cncable Optional[str] CN_250, 1/0_Al_15kV_1/3 structural the reader folds the cond= blocks into the arrays; set alone (no cond=) it raises
tscable Optional[str] TS_1/0 structural the reader folds the cond= blocks into the arrays; set alone (no cond=) it raises
cncables Union[str, list[str], NoneType] ['CN_250', 'CN_250', 'CN_250'], ['1/0_Al_15kV_1/3'], ['1/0_Al_15kV_1/3', '1/0_Al_15kV_1/3'... structural as wires; only one of wires, cncables, tscables may be set
tscables Union[str, list[str], NoneType] structural as wires; only one of wires, cncables, tscables may be set
xs Union[float, list[float], NoneType] [-0.5, 0.0, 0.5], [0.0, 0.25], [-0.1524, 0.1524] structural inline positions: a synthesized XYSpacing wc__spc, xCoord ({length})
hs Union[float, list[float], NoneType] [-4.0, -4.0, -4.0], [-4.0, -4.0], [10.5156, 8.2296] structural inline positions: the synthesized XYSpacing's yCoord ({length})
Seasons Optional[int] untranscribed no home on a WireConfiguration; instance limits or untranscribed (plan D9)
Ratings Union[float, list[float], NoneType] untranscribed no home on a WireConfiguration; instance limits or untranscribed (plan D9)
LineType Optional[str] untranscribed no home on a WireConfiguration
conductors Union[str, list[str], NoneType] structural raises when set: no deck in the sweep sets it, so a mapping waits for one
like Optional[str] 603 untranscribed the reader resolves like= before mapping

XfmrCode (S3b, approved and done 2026-11-08)

Mapper: cimhub_opendss/importer/cimtbl/xfmrcode.py (map_xfmrcode(native, buses)). Artifact xfmrcode.cimtbl, after the line codes; the instances stay in transformer.cimtbl. Atom tests/atoms/xfmrcode/codes.dss: - ct25: a center tap with two instances on a 3-phase system; - sub: 3-phase delta-wye; - yyd: 1-phase Y-Y-D, three cans; - unused: no instance uses it.

Goldens codes.cimtbl and codes_transformer.cimtbl, tested by tests/test_cimtbl_xfmrcode.py. U2 is closed (2026-11-08).

Result. 25 of 31 sweep decks bind with every S3 part (the S3a stops only). The center-tap templates are 9 in IEEE8500 (1,177 instances), 9 in each IEEE9500 copy, 3 in IEEE123_PV and 1 in IEEE13_CDPSM (Tpoletop). IEEE13_Assets has 2 TankEnd templates, IEEE4 YYD has 1. Every template's winding kV, kVA, %R and mesh x equal the engine's for each instance, on the atom and the engine decks (IEEE13_CDPSM, IEEE13_Assets, IEEE8500, IEEE9500). Multi-can tank templating and lug sequencing across a bank wait until CYME's form is seen; the CIM template class is then updated to match (user, 2026-11-08).

Template forms (the user's model, 2026-11-08; settles D10 and amends DSS-2's "lug to lug" for every code).

Census (the instances that wait for S3b, counting duplicate deck copies):

code kind instances form
center tap: 1-phase, 3 windings, secondary halves equal (7.2/0.12/0.12, 2.4/0.12/0.12, ...) 8,828 (IEEE8500, IEEE9500, IEEE123_PV, IEEE13_OCHRE, IEEE13_CDPSM CT5) lugs
1-phase, 3 windings Y-Y-D (IEEE4 YYD, 39.83/7.62/2.4 kV) 3 lugs (S3b-3; TankEnd before)
3-phase, 2 windings 3 TankEnd
1-phase, 2 windings none outside the regulators (mapped in S3a) lugs (S3b-3)

Every center-tap instance has the split-phase secondary bus2.1.0 + bus2.0.2 and a line-to-neutral primary on one node. No instance overrides its code's values, except ppm_antifloat (untranscribed).

  • TankEnd template (3-phase only, S3b-3): TransformerTankConfiguration xc_<code>. Each DSS winding gives:
  • a TransformerTankEnd xc_<code>_end_<n> (endNumber, connectionKind, rground/xground from Rneut/Xneut; no phases);
  • a TransformerWinding xc_<code>_wdg_<n> (FromTransformerEnd = its tank end), with ratedU (LL), baseU (the coil), ratedS, baseS (per phase on a 3-phase code) and r.

The mesh between windings carries x. The instance's PowerTransformerEnd n is template end n (endNumber); it carries the node, phases and grounded. Shapes: transformer_template, transformer_by_template (xf_t1). - Lug template (every 1-phase code, S3b-3). Any code but a center tap has two lugs per winding, H1 H2, X1 X2, Y1 Y2 (IEEE C57.12.70), numbered in each coil's node order (its direction) over the instance's phase ends, end 1 first, so a 2-winding code's are 1-4 and IEEE4 YYD's 1-6; windings H1→H2, X1→X2, Y1→Y2, baseS each its own kVA. A center tap is a 3-winding tank, as CIMTBL-Models distribution/templates/polemount_1ph_50kva_7200_12470y.cimtbl: - TransformerLugs H1, H2, X1, X3, X2 (sequenceNumber 1-5: the instance phase end each lands on, below); - windings lug to lug from the polarity end: H1→H2, X1→X2 (DSS winding 2, bus2.1.0: s1→N) and X2→X3 (winding 3, bus2.0.2: N→s2); - designation per IEEE C57.12.70 (the profile's text). X1 is the low-side terminal in phase with H1 under either polarity, so s1 (in phase with the primary) is X1 and s2 (at 180°) is X3. Additive polarity (X3, X2, X1: 1-phase, 200 kVA or less, 8,660 V or less) against subtractive (X1, X2, X3) only says where X1 sits on the tank, so the model is the same for both (confirmed by the user, 2026-11-08). Y designations belong to a true 3-winding unit's tertiary (IEEE4 YYD).

The instance has a PowerTransformerEnd per bus (end 1: the primary node and phases; end 2: s1s2N) and, as the inline 1-phase mapper already does, a TransformerPhaseEnd per phase of each end's terminal, not per lug: sequenceNumber unique in the transformer, end 1 first, in terminal phase order, neutral last. A lug's sequenceNumber names the phase end it lands on, so several lugs may share one: three bussed center-tap cans on bus2.1.2.3.0 are 4 phase ends for 12 lugs. Each DSS Transformer is its own PowerTransformer with one tank (DSS-2), so here the numbers line up one to one: - end 1 BN (line to neutral, DSS's default node 0) or AB (line to line) is 1, 2, which H1 and H2 land on; - end 2 s1s2N is s1 = 3, s2 = 4, N = 5, which X1, X3, X2 land on.

The template's lug numbers are therefore those of a one-tank instance. A bank of tanks on one PowerTransformer needs a configuration per tank position (CIMTBL-Models bank_oyod_50_50_7200_12470y.cimtbl), which no DSS deck produces. An instance whose secondary is not bus2.1.0 + bus2.0.2 raises. Shapes: transformer_template_1ph and transformer_by_template (xf_t2), rewritten from today's phase-end template to this lug pattern.

Values. - ratedU is the nameplate: phase to phase. A coil's voltage alone does not fix it, because 7.2 kV is 7200/12470Y on a 3-phase system and 7200 on a single-phase one. So it comes from the bus system its instances sit on (the S3a rule: × √3 for a phase-to-neutral coil on a 3-phase system, × 2 for a split-phase half), and instances that disagree raise. - The rest: baseU = the code's kV, the coil. baseS = winding 1's kVA on every coil. A split-phase half has ratedS = kVA / 2. r = %Rs per winding (or %loadloss / 2 on windings 1 and 2). The mesh 1-2, 1-3, 2-3 x = Xhl, Xht, Xlt in percent on the From winding's baseU and baseS. %imag and %noloadloss go on the configuration. - Defaults (DSS-6, dss_default on XfmrCode): conns wye, %Rs 0.2, Xhl/Xht/Xlt 7/35/30.

Instances (transformer.cimtbl): PowerTransformer xf_<name>, plus TransformerTank xf_<name>_tank with TankConfiguration = xc_<code>, plus the ends above. A lug template's instance phase ends reference their end's generated Terminal (xf_<name>_T<n>), which is their link to the PowerTransformer, since the instance has no windings. Amended 2026-11-09 (DSS S6c, T3): a 1-phase instance of a TankEnd template gets them too, numbered in its coil's node order, end 1 first (since S3b-3 every 1-phase code is a lug template, whose lugs are numbered so). That order is the coil's direction, which a PhaseCode cannot hold. Without it, IEEE4 YYD's tert.3.1 came back tert.1.3, and in the engine the 3-can bank's voltages moved by 1.6 kV. A code no unregulated instance uses is not written; the file's comment names it. An instance that sets a slot its code also sets raises (the template must be the one source), except the untranscribed ones. A regulated instance keeps S3a's rule: it takes its code's values, because CIM has no AutoTransformer template.

Fail fast: a code of other than 1 or 3 phases; windings other than 2 or 3; Rneut on a 1-phase code; a mesh From winding rated other than winding 1; a tap other than 1 on an unregulated code; a center-tap code with an instance that is not a split-phase secondary; instances of one code on different bus systems; Seasons without Ratings, or a Ratings count other than Seasons (see the Transformer section).

DC resistance and seasonal ratings (2026-11-24). Atom tests/atoms/xfmrcode/rated.dss (code sub with each winding's RdcOhms and Seasons=2 Ratings=[22000 25000]), golden rated.cimtbl, test_rated_code_matches_golden_and_binds: - RdcOhms is copied verbatim to each template winding, Update Table TransformerWinding: mRID, rDC (ohm), only when set. - Ratings are the template's own OperationalLimitSet xc_<code>_ratings, written alone (no Equipment), with one ApparentPowerLimit xc_<code>_ratings_<n> (kVA) of type olt_season<n> per season. The template names it with Update Table TransformerTankConfiguration: mRID, OperationalLimitSet (EquipmentConfiguration.OperationalLimitSet, a GridAPPS-D extension of the profile). An instance does not inherit the set: it gets only its own ratings, and one that sets Ratings or Seasons its code also sets raises (the one-source rule above).

Engine checks: each template's ratings, r and x against the engine's transformer of each instance.

Decisions (approved 2026-11-08): - S3b-1: AutoTrans stays unmapped until a deck has one; the master's not-mapped count is the signal. - S3b-2: the Y-Y-D 1-phase 3-winding code (IEEE4 YYD) is a TankEnd template (3 tank ends, D on the third). Superseded by S3b-3. - S3b-3 (the user's, 2026-11-19, via clallam_cim request 10): "TransformerTankEnd is only for three-phase templates, single-phase should use TransformerPhaseEnd / TransformerLug." Every 1-phase code is a lug template (above), the instance's phase ends unchanged; a 2-phase code raises (no deck has one). The engine checks are unchanged.

Xfmrcode field type samples kind target
name Union[str, XfmrcodeName] CT5, FdrXfmr, RegLeg copied TransformerTankConfiguration.name; mRID = xc_ + name, lowercased
phases Optional[int] 1, 3 structural 3: TankEnd template; 1: lug template (a center tap's H1 H2 X1 X3 X2, else two lugs per winding)
windings Optional[int] 3, 2 structural one TransformerWinding each; 2 or 3
wdg Optional[int] structural the winding Rneut/Xneut belong to (the reader's tag); none = the last
conn Union[str, ForwardRef('ConnectionType'), NoneType] structural the active-winding form; the reader folds wdg= blocks and bare values into the arrays
kV Optional[float] structural the active-winding form; the reader folds wdg= blocks and bare values into the arrays
kVA Optional[float] structural the active-winding form; the reader folds wdg= blocks and bare values into the arrays
tap Optional[float] structural the active-winding form; the reader folds wdg= blocks and bare values into the arrays
pct_R Optional[float] structural the active-winding form; the reader folds wdg= blocks and bare values into the arrays
Rneut Optional[float] structural TankEnd rground (ohm) of its winding when >= 0; on a 1-phase code raises
Xneut Optional[float] structural TankEnd xground (ohm) of its winding, with Rneut >= 0
conns Union[str, ForwardRef('ConnectionType'), list[Union[str, ForwardRef('ConnectionType')]], NoneType] [ConnectionType(text='wye', descripti..., [ConnectionType(text='delta', descrip... structural TankEnd connectionKind (D, Y; grounding is the instance's); a center tap's secondary halves are I; default wye
kVs Union[float, list[float], NoneType] [2.4, 0.12, 0.12], [4.16, 0.48], [2.4, 2.4] structural winding baseU (the coil); ratedU phase-to-phase from the instances' common bus system (x sqrt 3 on a 3-phase system, x 2 for a split-phase half), and instances that disagree raise
kVAs Union[float, list[float], NoneType] [5.0, 5.0, 5.0], [500.0, 500.0], [1666.0, 1666.0] structural winding ratedS (a split-phase half: kVA / 2); baseS = winding 1's kVA on every coil (per phase on a 3-phase code)
taps Union[float, list[float], NoneType] structural a tap other than 1 raises (a fixed tap is not mapped yet)
Xhl Optional[float] 2.04, 2.0, 0.01 structural mesh 1-2 x (percent on the From winding's baseU and baseS); default 7
Xht Optional[float] 2.04, 1.632, 36.0 structural mesh 1-3 x; default 35
Xlt Optional[float] 1.36, 1.088, 28.0 structural mesh 2-3 x; default 30
Xscarray Union[float, list[float], NoneType] untranscribed for more than 3 windings, which raise
thermal Optional[float] untranscribed thermal model; no home in the network profile parts
n Optional[float] untranscribed thermal model; no home in the network profile parts
m Optional[float] untranscribed thermal model; no home in the network profile parts
flrise Optional[float] untranscribed thermal model; no home in the network profile parts
hsrise Optional[float] untranscribed thermal model; no home in the network profile parts
pct_loadloss Optional[float] 0.01, 1.1 derived when pct_Rs is unset, r = loadloss / 2 on windings 1 and 2; set with pct_Rs, the two must agree
pct_noloadloss Optional[float] 0.2, 0.6 derived TransformerTankConfiguration.noLoadLoss (kW) = % x winding 1 kVA
normhkVA Optional[float] untranscribed a tank rating; instance OperationalLimitSet or untranscribed
emerghkVA Optional[float] untranscribed a tank rating; instance OperationalLimitSet or untranscribed
MaxTap Optional[float] 1.1 untranscribed tap changer range; a regulated instance takes it (S3a); else untranscribed
MinTap Optional[float] 0.9 untranscribed tap changer range; a regulated instance takes it (S3a); else untranscribed
NumTaps Optional[int] untranscribed tap changer range; a regulated instance takes it (S3a); else untranscribed
pct_imag Optional[float] 0.5, 1.1 copied TransformerTankConfiguration.percentMagnetizingCurrent (percent)
ppm_antifloat Optional[float] untranscribed numerical aid of the DSS solver
pct_Rs Union[float, list[float], NoneType] [0.6, 1.2, 1.2], [0.55, 0.55], [0.0005, 0.0005] structural winding r (percent on its own baseS); default 0.2
X12 Optional[float] structural alias of Xhl
X13 Optional[float] structural alias of Xht
X23 Optional[float] structural alias of Xlt
RdcOhms Union[float, list[float], NoneType] copied TransformerWinding.rDC (ohm); per template winding
Seasons Optional[int] structural the number of Ratings; one by default, and a count other than the Ratings' raises
Ratings Union[float, list[float], NoneType] copied ApparentPowerLimit.normalValue (kVA); one per season n, of type olt_season, in the OperationalLimitSet _ratings on the TransformerTankConfiguration names (EquipmentConfiguration.OperationalLimitSet)
like Optional[str] untranscribed the reader resolves like= before mapping

Transformer

Mapper: cimhub_opendss/importer/cimtbl/transformer.py (map_transformer(native, buses, container)). Atoms: tests/atoms/transformer/ — xfm1 (3-phase, IEEE13), sub3 (3-winding delta-wye-wye, neutral impedance on winding 2), reg1 (1-phase regulator unit), service (EPRI J1 7.2/0.24 kV), center_tap (phase-to-phase primary, s1/s2 secondary), with prereq.cimtbl; tested by tests/test_cimtbl_transformer.py. Regulators and LTCs (S3a): see "Transformer: regulators and LTCs" below. An XfmrCode instance no RegControl names waits for the template (S3b).

Model (the user's, 2026-11-06). Every DSS Transformer is its own PowerTransformer (bank is untranscribed), with one PowerTransformerEnd per distinct bus, numbered in winding order. The end's terminal holds the phases. - 3-phase, balanced ends: ratedU = the DSS kV (phase-to-phase), ratedS, r (percent on the end's own rating) per end. x goes on the end-to-end mesh, in percent on winding 1's kVA at the From end's voltage, so a From end with another kVA raises. pct_imag/pct_noloadloss become end 1 b/g (percent). Wye gives Yn when grounded (neutral on node 0, or Rneut >= 0 on that winding) and Y otherwise; delta gives D. - 1-phase, phase ends: one TransformerTank, one TransformerPhaseEnd per phase conductor on each bus (sequenceNumber unique in the transformer, end 1 first, in terminal phase order), and one TransformerWinding per DSS winding from the phase end of its first conductor to that of its second. Windings 2 and 3 on one bus, both on node 0, with nodes 1 and 2, form a split-phase secondary (s1s2N, I). Otherwise node 1/2/3 is A/B/C, 0 is N, an LN coil's end is Y and an LL coil's is D.

Nameplate ratings (IEEE C57.12.00-2021 Table 7; the catalog rule): - baseU = the DSS kV, i.e. the coil voltage. - ratedU (derived) is phase-to-phase: - an LN coil on a 3-phase system: kV × √3, never rounded (7.2 → 12.4708); - a split-phase half: 2 × kV; - an LL coil, or an LN coil on a single-phase system (the J1 240 V services): kV. - baseS = winding 1's kVA on every coil. A split-phase half has ratedS = kVA / 2. On 1-phase, the kVAs must be equal, because each %R is on its own winding's kVA.

Whether a bus's system is 3-phase comes from the topology walk (cimtopology.core.BusSystem), as does its BaseVoltage.

Defaults (listed in the row comment, # defaulted: ...): phases 3, conns wye, %R 0.2 per winding (pct_loadloss / 2 on windings 1 and 2 when set), XHL/XHT/XLT 7/35/30. Rneut/Xneut belong to the reader's wdg tag, else the last winding (the old importer's rule). Missing buses take DSS's default nodes: conductor k on node k, the neutral on 0.

Fail fast: - phases other than 1 or 3, or windings other than 2 or 3; - an active-winding scalar (kV, kVA, conn, bus, tap, %R) left over after the reader (it resolves them to their winding, S3); - a tap other than 1 on a transformer no RegControl names; - pct_Rs and pct_loadloss that disagree, or XHL and X12 that disagree; - 3-phase nodes other than 1.2.3; - two windings on one bus that are not a split-phase secondary; - a bus missing from the topology result; - RdcOhms on some windings only (the reader), on a 3-phase transformer by balanced ends, or on a regulator; - Seasons without Ratings, or a Ratings count other than Seasons; - Rneut >= 0 on a 1-phase transformer (a coil's neutral impedance has no row yet), as on a 1-phase XfmrCode; - Rneut/Xneut on a second winding (the reader: the schema holds one winding's).

DC resistance and seasonal ratings (2026-11-24). Atom tests/atoms/transformer/rated.dss (the EPRI J1 service with each winding's RdcOhms and Seasons=2 Ratings=[44 52]), golden rated.cimtbl, test_rated_service_binds; the export atom rated_inline.dss is the same record on a circuit of its own. - RdcOhms is per winding. DSS has no array form, so the reader puts each value at the active wdg='s place in the RdcOhms list. Some windings set and others not raises: the engine's default for those (85 % of %R in ohms) is not transcribed. The values are copied verbatim, Update Table TransformerWinding: mRID, rDC (ohm), only when set, on a 1-phase transformer's coils (and on an XfmrCode template's windings). A 3-phase transformer by balanced ends has no TransformerWinding, so it raises (RdcOhms on a 3-phase transformer by balanced ends), and so does a regulator (an AutoTransformerEnd has no rDC). - Ratings (kVA) are one ApparentPowerLimit <owner>_ratings_<n> per season n, of type olt_season<n>, in the OperationalLimitSet <owner>_ratings. An inline Transformer's set is on its PowerTransformer (OperationalLimitSet.Equipment), a regulator's on its VoltageRegulator. The master declares olt_season1 .. olt_season<N> (name season <n>, durationKind normal, isInfiniteDuration true, absoluteValue) for the most seasons any Transformer or XfmrCode rates (limit_types(seasons)). - Seasons is the number of ratings. The engine keeps only Seasons values of Ratings (one by default) and pads a Seasons alone with zeros, so Seasons without Ratings raises, and so does len(Ratings) != Seasons. Known limit: the engine also zeroes the Ratings when Seasons comes after Ratings on the line; the reader does not record that order. - normhkVA and emerghkVA stay untranscribed.

Transformer field type samples kind target
name Union[str, TransformerName] Reg1, Reg2, Reg3 copied PowerTransformer.name; mRID = xf_ + name, lowercased
phases Optional[int] 1, 3 structural 1 = by phase ends, 3 = by balanced ends; default 3
windings Optional[int] 3, 2 structural 2 or 3; must match the buses
wdg Optional[int] 2 structural the winding Rneut/Xneut belong to (the reader's tag); none = the last
bus Optional[str] structural the active-winding form; the reader folds wdg= blocks into the arrays, and a bare value raises
conn Union[str, ForwardRef('ConnectionType'), NoneType] structural the active-winding form; the reader folds wdg= blocks into the arrays, and a bare value raises
kV Optional[float] structural the active-winding form; the reader folds wdg= blocks into the arrays, and a bare value raises
kVA Optional[float] structural the active-winding form; the reader folds wdg= blocks into the arrays, and a bare value raises
tap Optional[float] structural the active-winding form; the reader folds wdg= blocks into the arrays, and a bare value raises
pct_R Optional[float] structural the active-winding form; the reader folds wdg= blocks into the arrays, and a bare value raises
Rneut Optional[float] 0.0 structural rground (ohm) of its winding's end when >= 0; negative = no impedance; >= 0 on a 1-phase transformer raises
Xneut Optional[float] 0.4 structural xground (ohm) of its winding's end, with Rneut >= 0
buses Union[str, list[str], NoneType] ['BRKR.1', 'RG60.1'], ['BRKR.2', 'RG60.2'], ['BRKR.3', 'RG60.3'] structural end node and terminal phases; one end per distinct bus
conns Union[str, ForwardRef('ConnectionType'), list[Union[str, ForwardRef('ConnectionType')]], NoneType] [ConnectionType(text='delta', descrip..., [ConnectionType(text='wye', descripti... structural connectionKind, grounded, default nodes; default wye
kVs Union[float, list[float], NoneType] [2.4, 2.4], [115.0, 4.16, 13.2], [4.16, 0.48] structural 3-phase: end ratedU; 1-phase: winding baseU, ratedU derived (x sqrt 3, x 2)
kVAs Union[float, list[float], NoneType] [1666.0, 1666.0], [5000.0, 5000.0, 1000.0], [500.0, 500.0] structural end ratedS / winding ratedS (halves / 2); winding 1's kVA is every baseS
taps Union[float, list[float], NoneType] [1.0, 1.0625], [1.0, 1.05], [1.0, 1.06875] structural the regulated winding's tap is RatioTapChanger.step (regcontrol.cimtbl); any other tap other than 1 raises; values past the winding count are ignored and missing ones are 1, as in the engine (winding_taps)
XHL Optional[float] 0.01, 2.0, 5.75 structural mesh 1-2 x (percent on winding 1's kVA); default 7
XHT Optional[float] 0.025 structural mesh 1-3 x; default 35
XLT Optional[float] 0.025 structural mesh 2-3 x; default 30
Xscarray Union[float, list[float], NoneType] untranscribed for more than 3 windings, which raise
thermal Optional[float] untranscribed thermal model; no home in the network profile parts
n Optional[float] untranscribed thermal model; no home in the network profile parts
m Optional[float] untranscribed thermal model; no home in the network profile parts
flrise Optional[float] untranscribed thermal model; no home in the network profile parts
hsrise Optional[float] untranscribed thermal model; no home in the network profile parts
pct_loadloss Optional[float] 0.01, 0.001, 0.7639 derived when pct_Rs is unset, r = loadloss / 2 on windings 1 and 2; set with pct_Rs, the two must agree
pct_noloadloss Optional[float] 0.0851, 0.34, 0.1348 derived 3-phase: end 1 g (percent); 1-phase: tank noLoadLoss = % x kVA; a regulator has no home for it (row comment)
normhkVA Optional[float] 25.0, 15.0, 75.0 untranscribed instance OperationalLimitSet or untranscribed
emerghkVA Optional[float] 35.0, 21.0, 105.0 untranscribed instance OperationalLimitSet or untranscribed
sub Union[bool, Bool, NoneType] True untranscribed DSS report flag
MaxTap Optional[float] 1.1, 1.05 structural the RatioTapChanger range of a regulated transformer (regcontrol.cimtbl); else untranscribed; default 1.1
MinTap Optional[float] 0.9, 0.95 structural the RatioTapChanger range of a regulated transformer (regcontrol.cimtbl); else untranscribed; default 0.9
NumTaps Optional[int] 16, 32 structural the RatioTapChanger range of a regulated transformer (regcontrol.cimtbl); else untranscribed; default 32
subname Optional[str] M1, HVMV_Sub untranscribed DSS report label
pct_imag Optional[float] 0.0001, 0.5 structural 3-phase: end 1 b (percent); 1-phase: tank percentMagnetizingCurrent; a regulator has no home for it (row comment)
ppm_antifloat Optional[float] 0.0, 5.0 untranscribed numerical aid of the DSS solver
pct_Rs Union[float, list[float], NoneType] [0.0005, 0.0005, 0.0005], [0.55, 0.55], [0.67, 0.67] structural 3-phase: end r (percent); 1-phase: winding r (percent); default 0.2
bank Optional[str] Reg, FEEDER1_REG1, FEEDER2_REG2 untranscribed each DSS Transformer is its own PowerTransformer
XfmrCode Optional[str] CT5, RegLeg, SubXfmr structural a regulated instance takes the code's values (with_code); any other waits for the template (S3b) and is counted on the master
XRConst Union[bool, Bool, NoneType] untranscribed harmonics option
X12 Optional[float] structural alias of XHL
X13 Optional[float] structural alias of XHT
X23 Optional[float] structural alias of XLT
LeadLag Union[str, ForwardRef('LeadLagType'), NoneType] Lag untranscribed PowerTransformer.vectorGroup clock; vectorGroup not mapped yet
Core Union[str, ForwardRef('CoreType'), NoneType] untranscribed core type; no home in the network profile parts
RdcOhms Union[float, list[float], NoneType] copied TransformerWinding.rDC (ohm); per winding, on a 1-phase transformer's coils; by balanced ends (no TransformerWinding) it raises
Seasons Optional[int] structural the number of Ratings; one by default, and a count other than the Ratings' raises
Ratings Union[float, list[float], NoneType] copied ApparentPowerLimit.normalValue (kVA); one per season n, of type olt_season, in the OperationalLimitSet _ratings on the PowerTransformer (seasonal_ratings)
normamps Optional[float] untranscribed instance OperationalLimitSet or untranscribed
emergamps Optional[float] untranscribed instance OperationalLimitSet or untranscribed
faultrate Optional[float] untranscribed reliability data; no home in the network profile parts
pct_perm Optional[float] untranscribed reliability data; no home in the network profile parts
repair Optional[float] untranscribed reliability data; no home in the network profile parts
basefreq Optional[float] untranscribed no home on a transformer
enabled Union[bool, Bool, NoneType] True copied PowerTransformer.normallyInService
like Optional[str] reg3a, reg4a, reg1a untranscribed the reader resolves like= before mapping

Deck sweep (2026-11-06, placeholder bus systems). 1,365 of the 1,378 inline transformers in 11 decks map. Stops:

stop count next
taps ≠ 1 6 (IEEE13_original regulators) lifted in S3a: regulators
kVA=750 with no wdg= 8 (ieee9500 *-DIES1) lifted in S3a: the reader's active-winding rule (2-winding kVA sets both)
%R=0.1 with no wdg= 2 (J1 ExistingSite*) lifted in S3a: winding 2 gets 0.1, winding 1 the default 0.2, as the engine

Reader fixes this slice needed: numeric bus and wire names stayed floats (634 → 634.0, i.e. node 0); quoted arrays (conns='delta delta', IEEE37) failed to build, and the reader dropped reg1a with only a log line. A failed build now raises.

S3 (S3a approved and done 2026-11-08)

S3 maps the network: lines and switches, the transformers into the orchestrator, regulators and LTCs, and their RegControls. Census of the 31 sweep decks, 2026-11-07: - Lines: 34,254 in all. By linecode 27,679; by geometry 5,294; inline sequence values 1,162 (678 of them switches); inline matrix 4 (1 a switch); spacing + wires 3; switches with no impedance 112. - Switch controls: 98 Fuses, 161 Reclosers, 336 SwtControls. - Regulators: 176 RegControls.

Scope split (approved, R3). A non-regulator Transformer by XfmrCode waits for U2. In the sweep that is IEEE8500 1,177, IEEE9500 1,275, IEEE123_PV 82, IEEE13_OCHRE 16, IEEE13_CDPSM 1 (Tpoletop). So S3 splits: - S3a (done): lines, switches, transformers in MAPPING_ORDER, VoltageRegulators and LTCs (a regulator by XfmrCode included), RegControl. - S3b (done 2026-11-08): XfmrCode templates and their instances (section XfmrCode). AutoTrans stays unmapped until a deck has one (S3b-1).

Until S3b a Transformer by XfmrCode that no RegControl names was counted on the master's # not mapped: line; S3b maps it by template.

Result (2026-11-08). The S3a exit is met: - IEEE13_CDPSM, IEEE123 and IEEE8500 bind with every line, switch, transformer and regulator. Their XfmrCode transformers are counted on the master. - 25 of the 31 sweep decks bind with every S3a part. The six stops: - DSS-10, a line's phases ≠ its code's nphases: J1, K1, M1, IEEE13_OCHRE; - the ieee9500_2025 balanced copy (an Open of a line it never defines; the engine fails too); - the PNNL balanced IEEE9500 deck, whose lines name LineCodes it never loads (the engine fails too). - Engine checks, on the atoms and the 8 engine decks (IEEE13 ×3, IEEE123, IEEE37, IEEE4, IEEE8500, IEEE9500): - every line's ratings, and the z and b totals of every line by code or by inline values; - every switch state; - every RegControl setting, the tap range and the regulator nameplate and mesh; - the tap position, on the atom (a deck that solves when compiled moves its taps).

Engine rules found in S3 (each pinned with a probe and kept in a test): - Ratings. A line copies each of normamps/emergamps it leaves unset from its LineCode, or from its LineGeometry. A geometry rating left unset is its first conductor's. A wire with normamps and no emergamps is rated 1.5 × normamps, and one with emergamps and no normamps has normamps = emergamps / 1.5. A spacing + wires line takes its first wire's. - Default C. A matrix LineCode without cmatrix keeps the engine's default C matrix: self (2 C1 + C0)/3 and mutual (C0 − C1)/3 from C1 = 3.4, C0 = 1.6 nF per unit length, on any number of phases (cimhub_core.derived.sequence.balanced_matrix). IEEE13_original's codes are this case (an amendment to the S2 LineCode mapper; the row says # defaulted: cmatrix from C1=3.4, C0=1.6). - Inline defaults. A sequence line leaves some of r1, x1, r0, x0, C1, C0 unset; they take the DSS defaults. r and x stay per unit length as they are. The engine keeps C1 and C0 per kft whatever the line's units, so a line with units writes them as given, in bch (nS/kft)/b0ch (nS/kft) (or b (nS/kft) on a 1- or 2-phase line) beside its r (ohm/<units>). A line with no units has no length to be per, and its defaults go in its gated unit. A line that sets one of C1/C0 (of those it uses: a 1-phase line uses C1 only) and leaves the other to the per-kft default, in units other than kft, raises: its C would be in two length units. - Unitless geometry line. Its length is in metres.

Reader fixes in S3 (§3.4 of the plan; each checked against the engine): - A value with no name goes to the property after the last one named, in the schema's order. {...} is RPN. The decks use this as Normamps=156 {156 1.25 *}: emergamps = 195 on the J1, K1, M1, IEEE8500 and IEEE9500 triplex codes, which the reader used to drop silently. A positional value on a class the reader rewrites by blocks (Transformer, XfmrCode, AutoTrans, LineGeometry) raises. - A bare per-winding property (bus kV kVA conn tap %R) goes to the active winding: the last wdg=, else the last winding an array set (an array sets every winding), else winding 1. On a 2-winding transformer, kVA sets both windings, even inside a wdg= block (wdg=1 kva=500 wdg=2 kva=300 is [300, 300] in the engine). - This lifts the old kVA=750 stop on the ieee9500 *-DIES1/-ESS/-MT transformers. - A winding no property sets takes the per-winding default (dss_default on Transformer/XfmrCode kV kVA conn tap %R, as the engine does), with a warning. J1's ExistingSite* %R=0.1 was this case. An unset bus raises.

Line and switches

Mapper: cimhub_opendss/importer/cimtbl/line.py (map_line; CONTROLS for Fuse, Recloser, SwtControl). Artifact line.cimtbl; shapes line_by_impedance, line_by_wire_configuration, switch. Atoms in tests/atoms/line/, tested by tests/test_cimtbl_line.py: - codes.dss (after IEEE13_CDPSM): lines by code (one code without cmatrix), inline sequence lines (one with defaults, one unitless 1-phase), and a LoadBreakSwitch, Fuse, Recloser, an open SwtControl tie and an Open section; - geometry.dss (after IEEE13_Assets): geometry lines (one unitless), a spacing + wires line, ratings from the first wire.

Identity. An ACLineSegment is ln_ + name and a switch sw_ + name, lowercased. Every Switch subclass shares sw_, so the switch's class can change without changing its mRID.

Class (DSS-9). A Line with Switch=y is a switch: - a Fuse whose SwitchedObj (else MonitoredObj, the DSS default) is that line makes it a Fuse, and its RatedCurrent becomes ratedCurrent; - a Recloser makes it a Recloser; - otherwise (a SwtControl, or no control) it is a LoadBreakSwitch.

What raises: a Fuse or Recloser on a line without Switch=y; two controls of different classes on one line; a control or an Open command whose line no New defines, also in a deck with no Line at all. In the sweep, every Fuse and Recloser switches the line it monitors.

Switch state. - open: an Open command on either terminal (Options.open_terminals), or a SwtControl with State=Open. - normalOpen: the SwtControl's Normal, else the same as open.

An Open command and a SwtControl State that disagree raise. A Fuse whose Normal/State give a value count other than its line's phases raises (found by the S6b export, 2026-11-09). The engine sets a fuse phase by phase, so State=open on a 3-phase line opens phase 1 only, and CIM's open is the whole switch's. No sweep deck sets a Fuse state. So does an Open on a line that is not a switch: Terminal.connected would be its home, but no deck needs it. - Sweep: 33 SwtControls are Open with Normal = State on every one. ieee9500 has 9 Open commands and IEEE123_test_harness 2, all on switch lines. - Dropped from switches: a switch's impedance, length and ratings stay untranscribed (DSS-8). DSS needs them only as numerical stand-ins: r1=1e-4, or the Switch=y defaults.

Template (ACLineSegment). Exactly one of the following; a line that combines two raises: - linecode= → WireConfiguration = the WireConfiguration of the code's template for the line's unit (lc_<code>_wc, or lc_<code>_<unit>_wc when the code's lines disagree, DSS-3, DSS-14); - geometry= → WireConfiguration = wc_<geometry>; - spacing= + wires=/cncables=/tscables= → a synthesized WireConfiguration ln_<name>_wc on spc_<spacing>, conductors in order (IEEE13_Assets 684652). This is the counterpart of S2's synthesized spacing; - inline r1…B0 or rmatrix/xmatrix/cmatrix → PerLengthImpedance = a synthesized PerLengthSequenceImpedance or PerLengthPhaseImpedance ln_<name>_lc of the line's own, isTemplate=false (DSS-14), under # synthesized in line.cimtbl (DSS-8). It goes through the LineCode mapper's own functions, so DSS-3 (units, gate), DSS-3b and DSS-4 apply unchanged. - Naming: DSS-8 said lc_<line>. A line and a code may share a name, so this proposes ln_<name>_lc. - Units: a unitless inline line goes through the same magnitude gate, over the deck's unitless inline lines (its own group, so its inference is stated on its own rows). Sweep: 432 in M1, 8 in IEEE123, 1 in IEEE37. - Unset sequence values take the engine's defaults (above).

Length and units. length (default 1, defaulted) is in the line's units. A unitless line by code takes the code's template unit: the code's units, else the gate (DSS-3). A unitless line by geometry (M1, 2 lines) takes metres, as the engine reads it (# defaulted: units=m).

Phases. They come from bus1's nodes: - 1/2/3 → A/B/C, in bus order (645.3.2 → CB, the matrix row order); - on a split-phase island (the walk, DSS-5): 1/2 → s1/s2; - no nodes → 1..phases; - a geometry with neutral conductors adds N (601: ABCN).

What raises: - bus2's phase nodes differing from bus1's (a transposition); - phases ≠ the code's nphases (DSS-10, deferred). That leaves J1 (1,381 lines), K1 (743), M1 (1,949) and IEEE13_OCHRE (50) in the sweep table. IEEE8500 and IEEE9500 have no mismatch: their lines take phases from the code.

Ratings (R1, approved). A line's normamps and emergamps go on an OperationalLimitSet ln_<name>_limits (Equipment = the segment) with one CurrentLimit (normalValue, A) each: - ln_<name>_norm on OperationalLimitType olt_normal: durationKind=normal, isInfiniteDuration=true, direction=absoluteValue; - ln_<name>_emerg on olt_emergency: durationKind=emergency, isInfiniteDuration=false, direction=absoluteValue.

The two types (GridAPPS-D LimitDurationKind, added to cim18v17 2026-11-07) are written once in the master, so later slices (transformers, catalogs) share them. season (CalendarSeasonKind) stays unset. DSS's Seasons and Ratings are an indexed array that a SeasonSignal loadshape selects, and they name no calendar season. No deck in the sweep sets them, so they raise until a deck shows the index-to-season convention. Values: - the line's own value, else what the engine copies: its code's, else its geometry's, else the geometry's first conductor's, with a wire's emergency rating defaulting to 1.5 × normamps (# ratings: normamps from LineCode mtx601). DSS keeps the last value set, and the reader does not record the order. Decks give a line's ratings after its linecode=, and the engine check agrees on every engine deck; - nothing from DSS's 400/600 A defaults.

Defaults (from the dss_default annotations, filled for Line, Fuse, Recloser and SwtControl in this slice, DSS-6): length 1, phases 3, units none.

Expected differences from the hand translation: IEEE13_CDPSM Brkr1 becomes a LoadBreakSwitch, not a Breaker: DSS has no breaker class, and DSS-9 decides by control.

Line field type samples kind target
name Union[str, LineName] 632633, 632645, 632670 copied ACLineSegment.name, Switch.name; mRID = ln_ + name (segment) or sw_ + name (switch), lowercased
bus1 str 632.1.2.3, 632.3.2, MID.1.2.3 structural node1, and the phases from its nodes: 1/2/3 = A/B/C, s1/s2 on a split-phase island (DSS-5); no nodes = 1..phases
bus2 Optional[str] 633.1.2.3, 645.3.2, 670.1.2.3 structural node2; its phase nodes must equal bus1's (a transposition raises)
linecode Optional[str] mtx602, mtx603, mtx601 structural ACLineSegment.WireConfiguration = the WireConfiguration of the code's template for the line's unit (lc_wc or lc__wc, DSS-3, DSS-14)
length Optional[float] 500.0, 667.0, 300.0 copied ACLineSegment.length ({length}); default 1 (defaulted); none on a switch
phases Optional[int] 3, 2, 1 structural the phase count; unset = the code's, geometry's or spacing's nphases, else 3 (line_phase_count; a switch has no template); one that differs from the code's nphases raises (DSS-10)
r1 Optional[float] 0.0001, 0.001, 1.0 structural the line's own PerLengthImpedance ln__lc (isTemplate=false) in line.cimtbl, values per length as written, through the LineCode mapper's rules (DSS-3 units, DSS-3b, DSS-4, DSS-14); on a switch untranscribed
x1 Optional[float] 0.0, 0.001, 1.0 structural the line's own PerLengthImpedance ln__lc (isTemplate=false) in line.cimtbl, values per length as written, through the LineCode mapper's rules (DSS-3 units, DSS-3b, DSS-4, DSS-14); on a switch untranscribed
r0 Optional[float] 0.0001, 0.001, 1.0 structural the line's own PerLengthImpedance ln__lc (isTemplate=false) in line.cimtbl, values per length as written, through the LineCode mapper's rules (DSS-3 units, DSS-3b, DSS-4, DSS-14); on a switch untranscribed
x0 Optional[float] 0.0, 0.001, 1.0 structural the line's own PerLengthImpedance ln__lc (isTemplate=false) in line.cimtbl, values per length as written, through the LineCode mapper's rules (DSS-3 units, DSS-3b, DSS-4, DSS-14); on a switch untranscribed
C1 Optional[float] 0.0, 0.000212206590789194, 0.000450939005427037 structural the line's own PerLengthImpedance ln__lc (isTemplate=false) in line.cimtbl, values per length as written, through the LineCode mapper's rules (DSS-3 units, DSS-3b, DSS-4, DSS-14); on a switch untranscribed
C0 Optional[float] 0.0, 0.000636619772367581, 0.00135281701628111 structural the line's own PerLengthImpedance ln__lc (isTemplate=false) in line.cimtbl, values per length as written, through the LineCode mapper's rules (DSS-3 units, DSS-3b, DSS-4, DSS-14); on a switch untranscribed
rmatrix Union[float, list[float], NoneType] [1.3238, 0.2066, 1.3294], [0.0001] structural the line's own PerLengthImpedance ln__lc (isTemplate=false) in line.cimtbl, values per length as written, through the LineCode mapper's rules (DSS-3 units, DSS-3b, DSS-4, DSS-14); on a switch untranscribed
xmatrix Union[float, list[float], NoneType] [1.3569, 0.4591, 1.3471], [0.0] structural the line's own PerLengthImpedance ln__lc (isTemplate=false) in line.cimtbl, values per length as written, through the LineCode mapper's rules (DSS-3 units, DSS-3b, DSS-4, DSS-14); on a switch untranscribed
cmatrix Union[float, list[float], NoneType] [0.0] structural the line's own PerLengthImpedance ln__lc (isTemplate=false) in line.cimtbl, values per length as written, through the LineCode mapper's rules (DSS-3 units, DSS-3b, DSS-4, DSS-14); on a switch untranscribed
Switch Union[bool, Bool, NoneType] True structural a Switch (sw_) instead of an ACLineSegment; class from its control (DSS-9)
Rg Optional[float] structural raises when set: no deck in the sweep sets it, so a mapping waits for one (Carson earth return; the consumer's choice for geometry)
Xg Optional[float] structural raises when set: no deck in the sweep sets it, so a mapping waits for one (Carson earth return; the consumer's choice for geometry)
rho Optional[float] structural the deck's EarthResistivity.rho (ohm-m), which every geometry line must agree on (geometry.earth_statement); on another line it raises; a switch lists it untranscribed
geometry Optional[str] 602, 603, 601 structural ACLineSegment.WireConfiguration = wc_
units Union[str, ForwardRef('LengthUnit'), NoneType] Ft, mi, km mapped the length unit (LENGTH_UNIT); unset: the template's unit (DSS-3)
spacing Optional[str] 510 structural with spacing=: a synthesized WireConfiguration ln_wc on spc, conductors in order
cncables Union[str, list[str], NoneType] structural with spacing=: a synthesized WireConfiguration ln_wc on spc, conductors in order
tscables Union[str, list[str], NoneType] structural with spacing=: a synthesized WireConfiguration ln_wc on spc, conductors in order
wires Union[str, list[str], NoneType] ['ACSR_1/0', 'ACSR_1/0'] structural with spacing=: a synthesized WireConfiguration ln_wc on spc, conductors in order
EarthModel Union[str, ForwardRef('EarthModelType'), NoneType] untranscribed the earth model of the impedance calculation; the consumer's choice
B1 Optional[float] structural the line's own PerLengthImpedance ln__lc (isTemplate=false) in line.cimtbl, values per length as written, through the LineCode mapper's rules (DSS-3 units, DSS-3b, DSS-4, DSS-14); on a switch untranscribed
B0 Optional[float] structural the line's own PerLengthImpedance ln__lc (isTemplate=false) in line.cimtbl, values per length as written, through the LineCode mapper's rules (DSS-3 units, DSS-3b, DSS-4, DSS-14); on a switch untranscribed
Seasons Optional[int] structural raises when set: no deck in the sweep sets it, so a mapping waits for one (an indexed rating array that names no calendar season; home OperationalLimitType.season)
Ratings Union[float, list[float], NoneType] structural raises when set: no deck in the sweep sets it, so a mapping waits for one (with Seasons)
LineType Union[str, ForwardRef('LineTypeCode'), NoneType] untranscribed no home in the network profile parts
EpsRmedium Optional[float] structural raises when set: no deck in the sweep sets it, so a mapping waits for one
HeightOffset Optional[float] structural raises when set: no deck in the sweep sets it, so a mapping waits for one
HeightUnit Union[str, ForwardRef('LengthUnit'), NoneType] structural raises when set: no deck in the sweep sets it, so a mapping waits for one
conductors Union[str, list[str], NoneType] structural raises when set: no deck in the sweep sets it, so a mapping waits for one
normamps Optional[float] 230.0, 90.0, 450.0 structural instance OperationalLimitSet ln__limits (see Ratings); on a switch untranscribed
emergamps Optional[float] 130.0, 600.0, 300.0 structural instance OperationalLimitSet ln__limits (see Ratings); on a switch untranscribed
faultrate Optional[float] untranscribed reliability data; no home in the network profile parts
pct_perm Optional[float] untranscribed reliability data; no home in the network profile parts
repair Optional[float] untranscribed reliability data; no home in the network profile parts
basefreq Optional[float] structural the line's own impedance's calculatedFrequency and the frequency of its b; unset: the deck's (DSS-3b)
enabled Union[bool, Bool, NoneType] True, False copied ACLineSegment.normallyInService, Switch.normallyInService
like Optional[str] untranscribed the reader resolves like= before mapping
Fuse field type samples kind target
name Union[str, FuseName] Fuse1, 2002200004641085, 2002200004868472 untranscribed the switch takes the Line's name; the Fuse names no CIM object
MonitoredObj Optional[str] Line.Fuse1, Line.2002200004641085_sw, Line.2002200004868472_sw structural the Line it switches: SwitchedObj, else MonitoredObj (the DSS default); not a Switch=y line raises
MonitoredTerm Optional[int] untranscribed the switch opens both terminals in CIM; DSS's terminal choice has no home
SwitchedObj Optional[str] Line.2002200004641085_sw, Line.2002200004868472_sw, Line.200220000499_sw structural the Line it switches: SwitchedObj, else MonitoredObj (the DSS default); not a Switch=y line raises
SwitchedTerm Optional[int] untranscribed the switch opens both terminals in CIM; DSS's terminal choice has no home
FuseCurve Optional[str] untranscribed protection setting; no home in cim18v17's protection function blocks (DSS-11)
RatedCurrent Optional[float] 100.0, 65.0, 15.0 copied Fuse.ratedCurrent (A)
Delay Optional[float] untranscribed control timing; no home on a Switch
Action Optional[str] structural raises when set: no deck in the sweep sets it, so a mapping waits for one (the deprecated form of State)
Normal Union[str, list[str], NoneType] structural Normal -> normalOpen, State -> open on the switch; with an Open command on the line they must agree
State Union[str, list[str], NoneType] structural Normal -> normalOpen, State -> open on the switch; with an Open command on the line they must agree
basefreq Optional[float] untranscribed no home on a switch
enabled Union[bool, Bool, NoneType] untranscribed a disabled control leaves its switch in place; no home
like Optional[str] untranscribed the reader resolves like= before mapping
Recloser field type samples kind target
name Union[str, RecloserName] Rec1, A333_48332, G9343_48332 untranscribed the switch takes the Line's name; the Recloser names no CIM object
MonitoredObj Optional[str] Line.Rec1, Line.A333_48332_sw, Line.G9343_48332_sw structural the Line it switches: SwitchedObj, else MonitoredObj (the DSS default); not a Switch=y line raises
MonitoredTerm Optional[int] untranscribed the switch opens both terminals in CIM; DSS's terminal choice has no home
SwitchedObj Optional[str] Line.A333_48332_sw, Line.G9343_48332_sw, Line.L5397_48332_sw structural the Line it switches: SwitchedObj, else MonitoredObj (the DSS default); not a Switch=y line raises
SwitchedTerm Optional[int] untranscribed the switch opens both terminals in CIM; DSS's terminal choice has no home
NumFast Optional[int] untranscribed protection setting; no home in cim18v17's protection function blocks (DSS-11)
PhaseFast Optional[str] untranscribed protection setting; no home in cim18v17's protection function blocks (DSS-11)
PhaseDelayed Optional[str] untranscribed protection setting; no home in cim18v17's protection function blocks (DSS-11)
GroundFast Optional[str] untranscribed protection setting; no home in cim18v17's protection function blocks (DSS-11)
GroundDelayed Optional[str] untranscribed protection setting; no home in cim18v17's protection function blocks (DSS-11)
PhaseTrip Optional[float] 1200.0, 200 untranscribed protection setting; no home in cim18v17's protection function blocks (DSS-11)
GroundTrip Optional[float] 400.0, 40 untranscribed protection setting; no home in cim18v17's protection function blocks (DSS-11)
PhaseInst Optional[float] untranscribed protection setting; no home in cim18v17's protection function blocks (DSS-11)
GroundInst Optional[float] untranscribed protection setting; no home in cim18v17's protection function blocks (DSS-11)
Reset Optional[float] untranscribed protection setting; no home in cim18v17's protection function blocks (DSS-11)
Shots Optional[int] 3 structural one RecloseSequence _rs per reclosure, Shots - 1 of them, recloseDelay = RecloseIntervals[n] (s); unset: the engine's Shots 4, intervals 0.5 2 2 (defaulted). Both given and disagreeing raise, and so does Shots above 4 without intervals (the engine reads past its defaults) or below 1 (the engine refuses it)
RecloseIntervals Union[float, list[float], NoneType] structural one RecloseSequence _rs per reclosure, Shots - 1 of them, recloseDelay = RecloseIntervals[n] (s); unset: the engine's Shots 4, intervals 0.5 2 2 (defaulted). Both given and disagreeing raise, and so does Shots above 4 without intervals (the engine reads past its defaults) or below 1 (the engine refuses it)
Delay Optional[float] untranscribed control timing; no home on a Switch
Action Optional[str] structural raises when set: no deck in the sweep sets it, so a mapping waits for one (the deprecated form of State)
TDPhFast Optional[float] untranscribed protection setting; no home in cim18v17's protection function blocks (DSS-11)
TDGrFast Optional[float] untranscribed protection setting; no home in cim18v17's protection function blocks (DSS-11)
TDPhDelayed Optional[float] untranscribed protection setting; no home in cim18v17's protection function blocks (DSS-11)
TDGrDelayed Optional[float] untranscribed protection setting; no home in cim18v17's protection function blocks (DSS-11)
Normal Optional[str] structural Normal -> normalOpen, State -> open on the switch; with an Open command on the line they must agree
State Optional[str] structural Normal -> normalOpen, State -> open on the switch; with an Open command on the line they must agree
basefreq Optional[float] untranscribed no home on a switch
enabled Union[bool, Bool, NoneType] untranscribed a disabled control leaves its switch in place; no home
like Optional[str] untranscribed the reader resolves like= before mapping
Swtcontrol field type samples kind target
name Union[str, SwtcontrolName] 2002200004641085, 2002200004868472, 200220000499 untranscribed the switch takes the Line's name; the SwtControl names no CIM object
SwitchedObj Optional[str] Line.2002200004641085_sw, Line.2002200004868472_sw, Line.200220000499_sw structural the Line it switches: SwitchedObj, else MonitoredObj (the DSS default); not a Switch=y line raises
SwitchedTerm Optional[int] untranscribed the switch opens both terminals in CIM; DSS's terminal choice has no home
Action Optional[str] structural raises when set: no deck in the sweep sets it, so a mapping waits for one (the deprecated form of State)
Lock Union[bool, Bool, NoneType] True untranscribed control lock; no home on a Switch
Delay Optional[float] untranscribed control timing; no home on a Switch
Normal Optional[str] Closed, Open structural Normal -> normalOpen, State -> open on the switch; with an Open command on the line they must agree
State Optional[str] Closed, Open structural Normal -> normalOpen, State -> open on the switch; with an Open command on the line they must agree
Reset Union[bool, Bool, NoneType] untranscribed a command, not a setting
basefreq Optional[float] untranscribed no home on a switch
enabled Union[bool, Bool, NoneType] untranscribed a disabled control leaves its switch in place; no home
like Optional[str] untranscribed the reader resolves like= before mapping

Transformer: regulators and LTCs

transformer.py (seeded) joins MAPPING_ORDER. A Transformer named by a RegControl changes as follows (DSS-13): - Regulator (equal winding kV; 133 single-phase, 4 three-phase gang in the sweep): a VoltageRegulator xf_<name> (same prefix, since it is the same DSS object) with two AutoTransformerEnds xf_<name>_1, xf_<name>_2. - Each end carries node, endNumber, grounded, baseU (kV, the coil voltage), ratedS (kVA) and BaseVoltage. Its phase is a PhaseCode: AN for a line-to-neutral unit, AB for a line-to-line unit (IEEE37), ABCN for a 3-phase gang unit. grounded when the coil ends on node 0: a wye 1-phase coil with 0 among its nodes, a 3-phase gang unit with its star point (the last node) on 0; a star point on node 4 floats in the engine. - Impedance (the user's model, 2026-11-07): one TransformerMeshImpedance xf_<name>_mesh_12 from end 1 to end 2, with x = XHL and r = %R1 + %R2 (percent). Their base is end 1's baseU/ratedS, the base CIM-Tables' z_base gives an AutoTransformerEnd. The row comment says it is the engine's stand-in impedance: a regulator's nameplate has no %Z, and OpenDSS needs XHL only because it has no real autotransformer. - What raises: unequal kVAs, a delta winding, more than 2 windings. %imag and %noloadloss have no home on an AutoTransformerEnd, so they are untranscribed. - LTC (unequal kV: J1 SubXfmr, M1 M1_XFMR, one 66/13.8 kV): stays a PowerTransformer (DSS-2); the tap changer goes on the controlled PowerTransformerEnd. - Taps (the RegControl's winding only; a tap ≠ 1 on any other winding, or on a transformer no RegControl names, still raises): - The deck's taps[winding] becomes RatioTapChanger.step = (tap − 1) / increment, where increment = (MaxTap − MinTap) / NumTaps (defaults 1.1, 0.9, 32). A step that is not whole within 1e-6 raises. - The range: highStep = (MaxTap − 1) / increment, lowStep = −(1 − MinTap) / increment, neutralStep 0, stepVoltageIncrement = increment × 100 (percent), neutralU = the winding kV. - These sit in the RegControl's rows, because they belong to the tap changer. - A taps list is read as the engine reads it (M46, decision 7, transformer.winding_taps): values past the winding count are ignored (windings=2 taps=[1.05 1.02 0.98] is 1.05, 1.02), and a shorter list leaves the other windings at 1.0 (windings=3 taps=[1.05]). - A regulator by XfmrCode (the 36 coded RegControls in the sweep) takes the code's values, as the engine copies them; the row comment names the code. CIM has no template for an AutoTransformer, so this needs neither U2 nor S3b.

The core shape voltage_regulator.cimtbl (added in S3a) holds the pattern: VoltageRegulator + AutoTransformerEnds + mesh + RatioTapChanger + TapChangerControl. The regulator shape (PowerTransformer + tap) is the LTC pattern. Atom: tests/atoms/regcontrol/regulators.dss (goldens regulators_transformer.cimtbl, regulators.cimtbl), tested by tests/test_cimtbl_regcontrol.py.

RegControl

Mapper: cimhub_opendss/importer/cimtbl/regcontrol.py (map_regcontrol). Artifact regcontrol.cimtbl, after transformer.cimtbl. Atom tests/atoms/regcontrol/regulators.dss: - reg1: 1-phase line-to-neutral, LDC (after IEEE13_CDPSM); - vr_ll: 1-phase line-to-line (after IEEE37); - gang: 3-phase gang-operated, PTphase 2; - coded: by XfmrCode, reversible (after IEEE8500); - ltc: a step-down LTC (after M1).

Values: targetValue, targetDeadband, the reverse ones and ctRating are plain floats in cim18v17, so their headers carry no unit (primary volts, amps).

  • TapChangerControl rc_<name>: mode=voltage, discrete=true, Terminal = xf_<transformer>_T<winding>, monitoredPhase from PTphase.
  • RatioTapChanger rc_<name>_tap: TransformerEnd = xf_<transformer>_<winding>, ltcFlag=true, ctRatio = CTprim / 0.2.
  • Secondary to primary (derived, named functions):
  • targetValue (V) = vreg × ptratio (Reg1: 122 × 20 = 2440 V); the deadband and the reverse settings the same way;
  • line drop (ohm) = R × ptratio / CTprim (Reg1: 3 × 20 / 700 = 0.0857 Ω), and X likewise.
  • Defaults (dss_default annotations, filled for RegControl from the EPRI property page in this slice): vreg 120, band 3, ptratio 60, CTprim 300, delay 15, tapdelay 2, winding 1, revThreshold 100, revDelay 60.
  • Fail fast: remote sensing (bus=; 1 in the sweep), tapwinding, vlimit, TapNum, LDC_Z, any of the idle/cogen modes; two RegControls on one transformer; a transformer no New defines; a tap range the engine takes but no tap changer has (NumTaps < 1, MaxTap ≤ MinTap, a tap outside them); a tap other than 1 on a winding the control does not move (the engine keeps it fixed; a fixed tap is not mapped yet).
  • Unset means unset or at its default (decision 14, 2026-11-27): an unmapped slot equal to its dss_default counts as unset, because the engine default changes nothing: vlimit 0, LDC_Z 0, rev_Z 0, Cogen No (engine readback; RegControl.pas:606, 624, 635, 656). Any other value raises. A slot with no default raises at any value: TapNum=0 too, because setting TapNum moves the tap (RegControl.pas:1469, Set_TapNum; taps=[1 1.025] with TapNum=0 is tap 1.0 in the engine). rc_2 dropped every falsy value (TapNum=0, idle=No).
Regcontrol field type samples kind target
name Union[str, RegcontrolName] Reg1, Reg2, Reg3 copied TapChangerControl.name, RatioTapChanger.name; mRID = rc_ + name (control) and rc_ + name + _tap (tap changer), lowercased
transformer Optional[str] Reg1, Reg2, Reg3 structural the regulator or LTC (DSS-13); a Transformer no New defines, or one two RegControls name, raises
winding Optional[int] 2 structural RatioTapChanger.TransformerEnd = xf_; TapChangerControl.Terminal = xf_T; default 1
vreg Optional[float] 122.0, 123.0, 125.0 derived targetValue (V) = vreg x ptratio (secondary_to_primary); default 120
band Optional[float] 2.0, 3.0, 1.0 derived targetDeadband (V) = band x ptratio (secondary_to_primary); default 3
ptratio Optional[float] 20.0, 60.0, 63.50852961 copied TapChangerControl.ptRatio, RatioTapChanger.ptRatio; default 60
CTprim Optional[float] 700.0, 50.0, 300.0 copied RatioTapChanger.ctRating (A); default 300; also ctRatio = CTprim / 0.2 (the DSS CT secondary, 0.2 A) and the LDC base
R Optional[float] 3.0, 0.4, 0.6 derived lineDropR (ohm) = R x ptratio / CTprim (line_drop_ohms); default 0; lineDropCompensation = R or X nonzero
X Optional[float] 9.0, 7.5, 0.4 derived lineDropX (ohm) = X x ptratio / CTprim (line_drop_ohms); default 0
bus Optional[str] temp structural raises when set: no deck in the sweep sets it, so a mapping waits for one (remote sensing; 1 RegControl in the sweep, which raises)
delay Optional[float] 90.0, 47.0, 50.0 copied RatioTapChanger.initialDelay (s); default 15
reversible Union[bool, Bool, NoneType] True copied TapChangerControl.reversible; default false
revvreg Optional[float] 125.0 derived reverseTargetValue (V) = revvreg x ptratio (secondary_to_primary); default 120
revband Optional[float] 2.0 derived reverseTargetDeadband (V) = revband x ptratio (secondary_to_primary); default 3
revR Optional[float] derived reverseLineDropR (ohm) = revR x ptratio / CTprim (line_drop_ohms); default 0
revX Optional[float] derived reverseLineDropX (ohm) = revX x ptratio / CTprim (line_drop_ohms); default 0
tapdelay Optional[float] 30.0, 45.0 copied RatioTapChanger.subsequentDelay (s); default 2
debugtrace Union[bool, Bool, NoneType] untranscribed DSS report flag
maxtapchange Optional[int] untranscribed DSS solution control; no home in the network profile parts
inversetime Union[bool, Bool, NoneType] untranscribed DSS solution control; no home in the network profile parts
tapwinding Optional[int] structural raises when set: no deck in the sweep sets it, so a mapping waits for one (a tap winding other than the monitored one)
vlimit Optional[float] structural raises when set: no deck in the sweep sets it, so a mapping waits for one (home TapChangerControl.maxLimitVoltage)
PTphase Optional[str] structural TapChangerControl.monitoredPhase = the phase of the winding's conductor PTphase (default 1); MAX/MIN raise
revThreshold Optional[float] 50.0 copied TapChangerControl.reversingPowerThreshold (kW); default 100
revDelay Optional[float] copied TapChangerControl.reversingDelay (s); default 60
revNeutral Union[bool, Bool, NoneType] copied TapChangerControl.reverseToNeutral; default false
EventLog Union[bool, Bool, NoneType] untranscribed DSS report flag
RemotePTRatio Optional[float] structural raises when set: no deck in the sweep sets it, so a mapping waits for one
TapNum Optional[int] structural raises when set: no deck in the sweep sets it, so a mapping waits for one (a tap position that overrides the transformer's tap); even 0 raises: setting it moves the tap, so it has no default
Reset Union[bool, Bool, NoneType] untranscribed a command, not a setting
LDC_Z Optional[float] structural raises when set: no deck in the sweep sets it, so a mapping waits for one
rev_Z Optional[float] structural raises when set: no deck in the sweep sets it, so a mapping waits for one
Cogen Union[bool, Bool, NoneType] structural raises when set: no deck in the sweep sets it, so a mapping waits for one
idle Union[bool, Bool, NoneType] structural raises when set: no deck in the sweep sets it, so a mapping waits for one
idleReverse Union[bool, Bool, NoneType] structural raises when set: no deck in the sweep sets it, so a mapping waits for one
idleForward Union[bool, Bool, NoneType] structural raises when set: no deck in the sweep sets it, so a mapping waits for one
basefreq Optional[float] untranscribed no home on a control
enabled Union[bool, Bool, NoneType] True copied TapChangerControl.enabled, RatioTapChanger.controlEnabled; default true
like Optional[str] creg3a, creg4a, creg1a untranscribed the reader resolves like= before mapping

Decisions for S3a (approved 2026-11-08)

  • R1: line ratings are mapped as above. The season goes on the OperationalLimitType when a deck gives one.
  • R2: RatioTapChanger.normalStep is not written. The converter writes step (the deck's tap position) only.
  • R3: S3a/S3b as proposed.
  • R4: synthesized templates are ln_<name>_lc and ln_<name>_wc.

S4 (S4a approved and done 2026-11-08)

S4 maps the injections.

Result (S4a, 2026-11-08). - 25 of the 31 sweep decks bind with every load, capacitor and CapControl; the stops are S3's six (DSS-10 in J1, K1, M1, IEEE13_OCHRE; the two balanced IEEE9500 copies). - Engine checks pass on the atoms and the 8 engine decks: every load's kW, kvar, model, CVR exponents, connection and customer count; every capacitor's kvar, kV, connection and steps (states on the atom); every CapControl's mode, ON and OFF (rebuilt from target and deadband), ratios, delay, element and terminal. IEEE8500 and IEEE9500's kvar controls monitor switches (sw_<name>_T1). - Each equipment's BaseVoltage is its bus's (the walk's, as ConnectivityNode.BaseVoltage in bus.cimtbl). - Found on the way: pce/capacitor.yaml was an orphan copy of pde/capacitor.yaml that hid its dss_defaults from the reader; removed.

Census of the 31 sweep decks, 2026-11-08 (throwaway scripts; the counts include the repeated IEEE8500/IEEE9500 copies): - Loads: 17,447 in 19 decks. Model 1 (ConstantPQ) 14,060; 4 (CVR) 3,184; 5 (ConstantI) 112; 2 (ConstantZ) 86. q from pf 15,535 (13,356 at 0.97), from kvar 3,381; no load sets both. Two ACEP_PSIL loads give kVA and pf without kW. 320 K1 loads set xfkVA (and allocationfactor) besides kW. 4 are disabled. - Capacitors: 106 in 11 decks, every one a single step; 78 single-phase, all wye. CapControls: 59. 48 are kvar (IEEE8500, IEEE9500, M1), 5 voltage (IEEE13_Assets ×2, IEEE13_OCHRE), 3 J1 volt and 3 time (IEEE13_Assets ×2 + _geo). - S4b classes: 950 PVSystems (887 of them 2-phase on a split-phase secondary), 27 Storage, 61 Generators (ACEP_PSIL and the IEEE9500 copies; models 1, 3, 7) and 8 Reactors (7 series HVMV_Sub_HSB in IEEE8500/IEEE9500, and K1's neutral reactor T2_neutral, node 4 to node 0 on one bus).

Scope split (approved, S4-1). S4a uses only shapes that exist; S4b needs two new ones. - S4a: Load, Capacitor, CapControl (shapes load, shunt; the core zip_fractions.cimtbl, DSS-7). - S4b: PVSystem and Storage (der), Generator (new machine shape: SynchronousMachine), Reactor (new series_compensator shape), and the full IEEE13_CDPSM artifact directory as the reference golden (D6). Its spec section follows S4a, as S3b's followed S3a.

Findings that change the plan: - U3 is closed. IEEE13_OCHRE's two voltage controls and IEEE13_Assets' time control monitor their own capacitor, so the plan's "all CapControls monitor a line" is wrong. CIM-Tables' Update form breaks the reference cycle: the compensator row comes first, then the control (naming the compensator's generated cap_<name>_T1), then Update LinearShuntCompensator: mRID=cap_<name>, RegulatingControl=cc_<name>. Checked: this binds, and RegulatingControl.RegulatingCondEq is the compensator. - A 2-phase wye load on a split-phase secondary is two legs to neutral, not one 240 V load. The engine reads its kV as line-to-line by the √3 rule: 0.208 = 0.120 × √3. So IEEE13_CDPSM's House is phases s1s2, wye, grounded, with each leg at 120 V. A 240 V load across s1 and s2 would be a 1-phase load on .1.2; no deck has one. - Every load's kV agrees with its bus within 1 % (17,447 of 17,447; the nearest misses are 2.4 kV against 4.16/√3, 0.07 %). CIM gives a load no rated voltage: EnergyConsumer.p is at the BaseVoltage. So kV is checked and not written. - Engine rules (pinned with probes; 13 engine decks, every load's kW and kvar equal the engine's): - kvar wins over pf in either order; - pf alone gives q = kW·tan(acos |pf|)·sign(pf) (so a negative kW flips q), and the default pf is 0.88; a pf of 0 or above 1 in magnitude gives a NaN or infinite kvar, so the mapper raises (any device); - kVA without kW gives kW = kVA·|pf|; - the load spec type (M4, decision 7, 2026-11-27): the last of kW, kvar and kVA the deck assigns picks the pair the engine computes from: (kW, pf), (kW, kvar) or (kVA, pf); pf never changes it. kVA=100 kW=50 is 50 kW at pf 0.88, kW=50 kVA=100 is 88 kW, kVA=100 kW=50 kvar=30 is 50 kW and 30 kvar; - at the end of each command the engine recomputes the other values from the pair (Load.pas:681, 1138-1160): (kVA, pf) sets kW = kVA·|pf|, and (kW, kvar) sets pf = kW / √(kW² + kvar²) with the sign of kW·kvar. A later pair can read one of them, so the value depends on where the commands end: kVA=100 kvar=30 is 10 kW in one command and 88 kW with kvar in a later Edit; kW=50 kvar=30 kW=100 is 53.97 kvar in one command and 60 across two. A ~ line is a command of its own. The mapper replays the history command by command (load.load_power over DssModel.commands), so every order maps as the engine gives it; - kW and xfkVA override each other in the order given: kW=10 pf=0.9 xfkVA=20 allocationfactor=0.5 is 9 kW, but with kW last it is 10 kW. xfkVA is not mapped. - CapControl defaults: type current, ON 300, OFF 200, PTratio 60, CTratio 60, Delay 15; a Capacitor's are 1200 kvar at 12.47 kV.

Shared phase rule (one helper for every S4 mapper): a 1-terminal device's nodes give its phases. - Nodes 1/2/3 are A/B/C, and s1/s2 on a split-phase island (DSS-5). An omitted node is the DSS default. - Wye: phaseConnection=Y, grounded=true. A neutral on node 0, or none, is ground; a neutral on another node raises. - Delta: D, grounded=false. A 1-phase delta device needs its two nodes: .3.1 is AC (cimtables names its phase child C, CIM's delta convention). - A 3-phase device on a split-phase island raises.

Artifact order. MAPPING_ORDER grows by load, capacitor and capcontrol, after regcontrol. A control references a line's or its capacitor's Terminal, so it comes after both.

Load

Mapper: cimhub_opendss/importer/cimtbl/load.py (map_load). Artifact load.cimtbl; shape load. Atom tests/atoms/load/loads.dss (after IEEE13_CDPSM): - models 1, 2, 4 (two CVR pairs) and 5; - q from pf, from kvar, and from neither (pf 0.88), plus kVA-only; - a 1-phase delta on .3.1, s1 and s2 legs, a 2-phase s1s2 load and a disabled load.

Identity. EnergyConsumer ld_ + name, lowercased.

Voltage response (DSS-7). - The master imports the fixed zip_fractions.cimtbl that core writes: zip_constant_pq, zip_constant_z and zip_constant_i, exponentModel=false. - Model 1, 2 or 5 names one of them. - Model 4 names exp_<CVRwatts>_<CVRvars> (exp_0.8_3, exp_1_2). That is one LoadResponseCharacteristic row per distinct pair, first in load.cimtbl, with exponentModel=true and pVoltageExponent/qVoltageExponent. Its constant fractions are unset. - Models 3, 6, 7 and 8 raise.

What raises: - kV more than 1 % off its bus's phase voltage (LL for delta and 2-3 phases, LN for 1-phase wye); - xfkVA (K1, which stops earlier on DSS-10); - Rneut ≥ 0; - the unmapped models.

enabled=false gives normallyInService=false and the row is written, as for a line. EPRI's ExportCIMXML skips disabled loads.

Capacitor

Mapper: cimhub_opendss/importer/cimtbl/capacitor.py (map_capacitor). Artifact capacitor.cimtbl; shape shunt. Atom tests/atoms/capacitor/caps.dss (after IEEE13_Assets and IEEE13_OCHRE): a 3-phase and a 1-phase wye bank, a delta bank, and a bank whose states=[0]. The same atom carries the CapControls below.

Identity. LinearShuntCompensator cap_ + name, lowercased.

One section. - nomQ = kvar (the total over the phases) and nomU = kv, as rated. K1's 10548920-1 is 13.8 kV on a 13.2 kV bus, and that stays. - bPerSection (mS) = nomQ / nomU² (b_per_section): kVAr over kV² is mS, so no factor appears. Every CIM consumer reads b. - maximumSections=1. sections = normalSections = the steps states closes (M1's Cap1 and Cap2 are 0), as a switch's normalOpen follows open when nothing else is given.

What raises: more than one step; bus2; cmatrix or cuf; a nonzero R or XL (IEEE4's Stabilizer writes R=0, which is untranscribed); normamps/emergamps.

CapControl

Mapper: cimhub_opendss/importer/cimtbl/capcontrol.py (map_capcontrol). Artifact capcontrol.cimtbl; shape shunt. Atom: caps.dss, with controls of four kinds: - kvar on a line (after IEEE8500); - voltage on a line with PTratio 20 and PTPhase 1 (after IEEE13_Assets Cap2); - voltage on its own capacitor (after IEEE13_OCHRE); - time (after IEEE13_Assets Cap1).

Identity. RegulatingControl cc_ + name, lowercased. The shape had <cap>_ctrl; a DSS control has a name of its own, and rc_<name> is the RegControl precedent (S4-8).

Rows. - RegulatingControl with discrete=true, enabled, mode, monitoredPhase, ptRatio, ctRatio, targetValue, targetDeadband, and targetValueUnitMultiplier=k on a kvar control. - Terminal = ln_<line>_T<terminal> or cap_<capacitor>_T<terminal>. Any other element raises. - monitoredPhase is the phase of the monitored terminal's conductor PTPhase (EPRI's rule). - Then Update LinearShuntCompensator: mRID=cap_<capacitor>, RegulatingControl=cc_<name>, aVRDelay (s)=<Delay>, controlEnabled=<enabled>. So the capacitor mapper knows nothing of controls, and the own-terminal cycle is broken (U3).

ON/OFF to target and deadband (derived, on_off_target; EPRI ExportCIMXML's convention, made positive): - targetValue = (ON + OFF) / 2, targetDeadband = |OFF − ON|. Both are plain floats in cim18v17 (S3a), in primary units by mode: - voltage: × PTratio, in V; - current: × CTratio, in A; - kvar: in kvar, as the deck gives it, with targetValueUnitMultiplier=k (the core getter reads it in var); - time: hours from midnight. - The type fixes which side ON is on: below OFF for voltage and time, above it for kvar and current. A control with ON on the wrong side raises, so the exporter can invert the pair without a sign (EPRI writes a negative deadband for kvar).

control ON / OFF ratio targetValue targetDeadband
IEEE8500 CAPBank0A_Ctrl (kvar) 200 / −300 kvar — −50 kvar (k) 500 kvar (k)
IEEE13_Assets Cap2 (voltage) 115 / 125 V PT 20 2,400 V 200 V
IEEE13_OCHRE CAP1_ctrl (voltage, own terminal) 1,950 / 2,500 V PT 1 2,225 V 550 V
IEEE13_Assets Cap1 (time) 8 / 19 h — 13.5 h 11 h

Untranscribed, with no CIM home: VoltOverride, Vmax, Vmin (45 IEEE8500/IEEE9500 kvar controls) and DelayOFF, DeadTime. maxAllowedTargetValue limits the target, not the bus voltage, so it is not a stand-in. This changes how those controls act when the engine solves (S4-5).

What raises: PF and Follow types; CTPhase, VBus, UserModel, ControlSignal; PTPhase AVG/MAX/MIN; a capacitor or element that no New defines.

Schema (DSS-6): - dss_defaults for CapControl and Capacitor (the defaults listed above); - OFFsetting, Delay, DelayOFF and DeadTime ranges → float (they are strings today); - type stays a string read by unique prefix, as the engine reads J1's volt.

Engine checks (S4a)

On the atoms and the engine decks, as in S3: - every load's kW and kvar (already equal on 13 decks with the rule above) and its model; - every capacitor's kvar, kV, connection and step count; the states on the atom (a deck that solves when compiled switches them); - every CapControl's mode, ON and OFF (back from target and deadband), PTratio, CTratio, Delay and monitored element and terminal.

Core and shape changes (S4a)

  • cimhub_core: a zip_fractions() document (zip_constant_pq, _z, _i). The common shape gains zip_constant_i from it, and a test keeps the two equal.
  • shunt.cimtbl: replace the R11 note with the own-terminal form (control, then Update). Drop the (V) on targetValue/targetDeadband here and in voltage_regulator.cimtbl (plain floats, S3a).
  • load.cimtbl: an exp_0.8_3 row and a model-4 consumer.
  • The cimtbl-shapes skill rows to match. UPSTREAM_REQUESTS.md: U3 closed.

Load, Capacitor and CapControl fields

Load

Load field type samples kind target
name Union[str, LoadName] 611, 634a, 634b copied EnergyConsumer.name; mRID = ld_ + name, lowercased
bus1 str 611.3, 634.1, 634.2 structural node; the nodes give the phases: 1/2/3 are A/B/C, and s1/s2 on a split-phase island (DSS-5); an omitted node is the DSS default (conductor k on node k)
phases Optional[int] 1, 3, 2 structural the conductor count; default 3. On a split-phase island 2 wye phases on 1.2 are two legs to neutral (s1s2, kV is LL by the sqrt 3 rule)
kV Optional[float] 2.4, 0.277, 4.16 structural checked, not written: the phase voltage it gives (LL for delta and 2-3 phases, LN for 1-phase wye) must be within 1 % of the bus's, else it raises; CIM p is at the BaseVoltage
kW Optional[float] 170.0, 160.0, 120.0 copied EnergyConsumer.p (kW); consumption is positive p; the last of kW, kvar and kVA picks the pair: (kW, pf), (kW, kvar) or (kVA, pf); each command's end recomputes the rest from it, so the history is replayed command by command (load_power); default 10
pf Optional[float] 0.85, 0.97, 0.87 derived q (kVAr) = kW x tan(acos abs(pf)) x sign(pf) with kW last (kVA last: see kVA); pf never changes the pair, so kvar wins in either order (engine-checked); raises unless 0 < |pf| <= 1; default 0.88
model Union[str, ForwardRef('LoadModel'), NoneType] ConstantI, ConstantPQ, ConstantZ mapped EnergyConsumer.LoadResponse; 1 zip_constant_pq, 2 zip_constant_z, 5 zip_constant_i, 4 exp__; 3, 6, 7, 8 raise; default 1
yearly Optional[str] Other, Commercial, AggLoadProfile mapped ConformLoad.LoadGroup; the shape's group lg_: the load is a ConformLoad (S8); a shape the deck does not define raises
daily Optional[str] com untranscribed a second shape has no home: a ConformLoad has one LoadGroup, its yearly shape's (S8)
duty Optional[str] untranscribed a second shape has no home: a ConformLoad has one LoadGroup, its yearly shape's (S8)
growth Optional[str] untranscribed a GrowthShape reference; not mapped (DSS-11)
conn Union[str, ForwardRef('ConnectionType'), NoneType] wye, delta mapped EnergyConsumer.phaseConnection, EnergyConsumer.grounded; wye -> Y, grounded; delta -> D, not grounded; default wye
kvar Optional[float] 80.0, 110.0, 90.0 copied EnergyConsumer.q (kVAr); with kvar last: p = kW, q = kvar; the last of kW, kvar and kVA picks the pair: (kW, pf), (kW, kvar) or (kVA, pf); each command's end recomputes the rest from it, so the history is replayed command by command (load_power)
Rneut Optional[float] structural raises when set: no deck in the sweep sets it, so a mapping waits for one (>= 0: a wye neutral impedance)
Xneut Optional[float] structural raises when set: no deck in the sweep sets it, so a mapping waits for one
status Union[str, ForwardRef('LoadStatus'), NoneType] Variable, Fixed untranscribed Fixed/Exempt: whether load multipliers scale it; DSS solution control; no home in the network profile parts
load_class Optional[int] 1, 2 untranscribed a DSS report grouping
Vminpu Optional[float] 0.88, 0.85, 0.75 untranscribed below it the engine models the load as constant Z; DSS solution control; no home in the network profile parts
Vmaxpu Optional[float] 1.15 untranscribed above it the engine models the load as constant Z; DSS solution control; no home in the network profile parts
Vminnorm Optional[float] untranscribed an EnergyMeter UE threshold; DSS solution control; no home in the network profile parts
Vminemerg Optional[float] untranscribed an EnergyMeter EEN threshold; DSS solution control; no home in the network profile parts
xfkVA Optional[float] 1.70148, 397.465666666668, 25.1736633333333 structural raises: not mapped, and with kW the engine takes whichever comes last (K1 only, behind DSS-10)
allocationfactor Optional[float] 1.2136, 1.2096, 1.2172 structural raises: it scales xfkVA
kVA Optional[float] 313.0 derived with kVA last: p = kVA x abs(pf), q = kVA x sin(acos abs(pf)) with the sign of pf (ACEP_PSIL); the last of kW, kvar and kVA picks the pair: (kW, pf), (kW, kvar) or (kVA, pf); each command's end recomputes the rest from it, so the history is replayed command by command (load_power)
pct_mean Optional[float] untranscribed a Monte Carlo setting; DSS solution control; no home in the network profile parts
pct_stddev Optional[float] untranscribed a Monte Carlo setting; DSS solution control; no home in the network profile parts
CVRwatts Optional[float] 0.8, 0.7 copied LoadResponseCharacteristic.pVoltageExponent; model 4 only (the exp_ row); default 1; unused by other models
CVRvars Optional[float] 3.0 copied LoadResponseCharacteristic.qVoltageExponent; model 4 only (the exp_ row); default 2; unused by other models
kwh Optional[float] untranscribed sizes the load only in the AllocateLoads command
kwhdays Optional[float] untranscribed sizes the load only in the AllocateLoads command
Cfactor Optional[float] untranscribed sizes the load only in the AllocateLoads command
CVRcurve Optional[str] untranscribed a LoadShape reference; LoadShape is not mapped (DSS-11)
NumCust Optional[int] 1, 2, 6 copied EnergyConsumer.customerCount; default 1
ZIPV Union[float, list[float], NoneType] untranscribed used only by model 8, which raises
pct_SeriesRL Optional[float] untranscribed harmonics model; no home in the network profile parts
RelWeight Optional[float] untranscribed a reliability weighting
Vlowpu Optional[float] untranscribed below it the engine models the load as open; DSS solution control; no home in the network profile parts
puXharm Optional[float] untranscribed harmonics model; no home in the network profile parts
XRharm Optional[float] untranscribed harmonics model; no home in the network profile parts
spectrum Optional[str] untranscribed harmonics model; no home in the network profile parts
basefreq Optional[float] untranscribed no home on a load
enabled Union[bool, Bool, NoneType] False copied EnergyConsumer.normallyInService; default true
like Optional[str] untranscribed the reader resolves like= before mapping

Capacitor

Capacitor field type samples kind target
name Union[str, CapacitorName] Cap1, Cap2, CAPBank1A copied LinearShuntCompensator.name; mRID = cap_ + name, lowercased
bus1 Optional[str] 675, 611.3, R20185.1 structural node and phases, as a load's (1/2/3 are A/B/C)
bus2 Optional[str] structural raises when set: no deck in the sweep sets it, so a mapping waits for one (an ungrounded wye or a series capacitor)
phases Optional[int] 3, 1 structural the conductor count; default 3
kvar Union[float, list[float], NoneType] [600.0], [100.0], [300.0] copied LinearShuntCompensator.nomQ (kVAr); the total over the phases; more than one step raises; default 1200
kv Optional[float] 4.16, 2.4, 7.2 copied LinearShuntCompensator.nomU (kV); as rated (LN for 1-phase wye, else LL); also bPerSection (mS) = nomQ / nomU^2 (b_per_section); default 12.47
conn Union[str, ForwardRef('ConnectionType'), NoneType] wye mapped LinearShuntCompensator.phaseConnection, LinearShuntCompensator.grounded; wye -> Y, grounded; delta -> D, not grounded; default wye
cmatrix Union[float, list[float], NoneType] structural raises when set: no deck in the sweep sets it, so a mapping waits for one (a capacitance matrix instead of kvar)
cuf Union[float, list[float], NoneType] structural raises when set: no deck in the sweep sets it, so a mapping waits for one (microfarads instead of kvar)
R Union[float, list[float], NoneType] [0.0] structural 0 is untranscribed; nonzero raises (a series R is not mapped)
XL Union[float, list[float], NoneType] structural 0 is untranscribed; nonzero raises (a series reactor is not mapped)
Harm Union[float, list[float], NoneType] untranscribed the tuning harmonic of the R/XL filter
Numsteps Optional[int] structural maximumSections; more than 1 raises (unequal steps would need a NonlinearShuntCompensator), and so does 0 (the engine refuses it); default 1
states Union[int, list[int], NoneType] [0], [1] structural sections = normalSections = the step's state, 0 or 1 (a switch's normalOpen = open rule); anything but one 0/1 value raises; default closed
normamps Optional[float] structural raises when set: no deck in the sweep sets it, so a mapping waits for one (an OperationalLimitSet, as a line's)
emergamps Optional[float] structural raises when set: no deck in the sweep sets it, so a mapping waits for one
faultrate Optional[float] untranscribed a reliability setting; no home in the network profile parts
pctperm Optional[float] untranscribed a reliability setting; no home in the network profile parts
repair Optional[float] untranscribed a reliability setting; no home in the network profile parts
basefreq Optional[float] untranscribed no home on a compensator; bPerSection is at the model's frequency
enabled Union[bool, Bool, NoneType] True copied LinearShuntCompensator.normallyInService; default true
like Optional[str] untranscribed the reader resolves like= before mapping

CapControl

Capcontrol field type samples kind target
name Union[str, CapcontrolName] Cap1, Cap2, CAPBank1A_Ctrl copied RegulatingControl.name; mRID = cc_ + name, lowercased
element Optional[str] capacitor.cap1, line.684611, line.CAP_1A structural Terminal = ln_T (sw for a switch) or cap__T; another element class raises
terminal Optional[int] 2, 1 structural the element's terminal: 1 or 2 on a Line (the engine refuses 3), 1 on a Capacitor (a LinearShuntCompensator has one); others raise; default 1
capacitor Optional[str] cap1, cap2, CAPBank1A structural the Update row: LinearShuntCompensator cap_ gets RegulatingControl; a capacitor no New defines raises
type Optional[str] time, voltage, kvar mapped RegulatingControl.mode; voltage -> voltage, current -> currentFlow, kvar -> reactivePower, time -> timeScheduled (a unique prefix, as the engine reads it: J1's volt); PF and Follow raise; default current
PTratio Optional[float] 20.0, 1.0, 60.0 copied RegulatingControl.ptRatio; default 60
CTratio Optional[float] 1.0 copied RegulatingControl.ctRatio; default 60
ONsetting Optional[float] 8.0, 115.0, 150.0 derived targetValue = (ON + OFF) / 2 (on_off_target); voltage x PTratio (V), current x CTratio (A), kvar in kvar (targetValueUnitMultiplier k), time in hours; ON on the wrong side of OFF for the type raises; default 300
OFFsetting Optional[float] 19.0, 125.0, -225.0 derived targetDeadband = abs(OFF - ON) (on_off_target); voltage x PTratio (V), current x CTratio (A), kvar in kvar (targetValueUnitMultiplier k), time in hours; default 200
Delay Optional[float] 100.0, 101.0, 102.0 copied LinearShuntCompensator.aVRDelay (s); on the Update row; default 15
VoltOverride Union[bool, Bool, NoneType] True, False untranscribed a voltage override band of a kvar/current control; no home (maxAllowedTargetValue limits the target, not the voltage)
Vmax Optional[float] 7740.0, 126.0 untranscribed the VoltOverride band (V on the PT secondary)
Vmin Optional[float] 7110.0, 114.0 untranscribed the VoltOverride band (V on the PT secondary)
DelayOFF Optional[float] 100.0, 101.0, 102.0 untranscribed CIM has one aVRDelay (Delay); DSS solution control; no home in the network profile parts
DeadTime Optional[float] 0.0 untranscribed DSS solution control; no home in the network profile parts
CTPhase Optional[str] structural raises when set: no deck in the sweep sets it, so a mapping waits for one
PTPhase Optional[str] 1, 2 structural monitoredPhase = the phase of the monitored terminal's conductor PTPhase (default 1); AVG/MAX/MIN raise
VBus Optional[str] structural raises when set: no deck in the sweep sets it, so a mapping waits for one (remote voltage sensing)
EventLog Union[bool, Bool, NoneType] untranscribed DSS report flag
UserModel Optional[str] structural raises when set: no deck in the sweep sets it, so a mapping waits for one
UserData Optional[str] structural raises when set: no deck in the sweep sets it, so a mapping waits for one
pctMinkvar Optional[float] untranscribed used only by PF control, which raises
Reset Union[bool, Bool, NoneType] untranscribed a command, not a setting
ControlSignal Optional[str] structural raises when set: no deck in the sweep sets it, so a mapping waits for one
basefreq Optional[float] untranscribed no home on a control
enabled Union[bool, Bool, NoneType] copied RegulatingControl.enabled, LinearShuntCompensator.controlEnabled; default true; controlEnabled on the Update row
like Optional[str] untranscribed the reader resolves like= before mapping

S4b

The S4b spec is its own section below, S4b.

Decisions for S4 (approved 2026-11-08)

  • S4-1: split S4a / S4b as above.
  • S4-2: a load's kV is checked against its bus (1 %) and not written; off by more, it raises. The alternative is to rescale p and q to the bus voltage by the model's exponent. No deck needs that.
  • S4-3: kW with kVA or xfkVA raises, because the order decides the value and the record keeps none. kVA without kW is derived (ACEP_PSIL). Superseded for kVA by decision 7 (2026-11-27): the history's last of kW, kvar and kVA picks the pair (S4a engine rules, above); xfkVA still raises. The alternative is the reader keeping the last of the three; K1 is the only user, and it stops on DSS-10 first.
  • S4-4: CapControl target/deadband by EPRI's midpoint and width, deadband positive, in primary units by mode (V, A, var, hours). The side of ON is checked per type.
  • S4-5: VoltOverride/Vmax/Vmin, DelayOFF and DeadTime untranscribed. A GridAPPS-D extension (RegulatingControl voltage override limits, an off delay) is the candidate if power-flow parity on IEEE8500 needs it.
  • S4-6: one-step capacitors only. sections = normalSections from states. bPerSection is written (derived).
  • S4-7: the CapControl writes the compensator's RegulatingControl, aVRDelay and controlEnabled by Update (closes U3).
  • S4-8: cc_<name> for a CapControl.
  • S4-9: disabled loads and capacitors are written with normallyInService=false, as lines are.

S4b (approved and done 2026-11-08)

Result (2026-11-08). - 22 of 31 sweep decks bind, as expected: S3's six stops, the two ieee9500 copies (Mode=7) and IEEE123_test_harness (Battery5). - Engine checks pass on the three atoms and the engine decks for every PV (kW, kvar, kVA, Pmpp, kV), every battery (kW, state, kVA, kWrated, kWhrated, kWhstored, kV), every series reactor (R, X, buses, ratings) and every machine's kW, kvar, ratings and PV-bus settings, including PNNL IEEE9500's Diesel620 and LNGengine100, whose kW is edited after their kvar (S4b-8). - The IEEE13_CDPSM artifact directory is the golden (D6), all 13 files.

Changes from the proposal, found while building it: - The engine reads a Storage State by its first letter. charge is not a prefix of charging, but the engine takes it, so the mapper matches on the first letter as well. - No voltage window in the PV check. Right after Compile, with no solve, PVSystems.kW()/kvar() already give the dispatch: cut to fit kVA, off below %Cutout, and independent of voltage. The check compares against those. - The generator check reads the kW/kvar properties, not Generators.kvar(). After a solve, the latter is the PV bus's solved kvar (SteamGen1: −1000 at Minkvar). - RotatingMachinePhase comes from the phases column. cimtables writes one per phase for every machine (a 1-phase motor's too); the mapper adds nothing. - SeriesCompensator has no per-phase class, so cimtables refuses a phases column on it. The mapper writes Update Table Terminal: mRID, phases for the generated rx_<name>_T1/_T2. A request for the shorthand (set Terminal.phases only, as a TransformerEnd's) is U9 in UPSTREAM_REQUESTS.md. - A balanced three-phase device leaves phases blank (S4b-9, the user's review): cimtables writes a <Class>Phase child per token, but in CIM, and in the engine's export (if NPhases = 3 then exit), per-phase children mean a per-phase device. cimhub_core.cimtbl.phases_cell blanks ABC for loads, capacitors, sources, switches, PVs, batteries, machines and series reactors. This also changes the S1, S3 and S4a artifacts. Lines keep phases (their ACLineSegmentPhases are the conductor order), and the engine writes them for 3-phase lines too. The Terminals of a balanced device lose phases=ABC until CIM-Tables can tell balanced from three single phases (U10). - Line's ratings code is now line.rating_rows/rating_tables, shared with the reactor. line_phases takes a label for its errors. - Wrong schema ranges fixed in passing: the curve references (EffCurve, P-TCurve) → string, and the WattPriority/PFPriority/LimitCurrent switches → boolean, so yes reads as true.

S4b-8: the deck's assignment order is replayed (approved 2026-11-08). For some properties the engine's value depends on the order of assignment, and a record keeps only each slot's last value. The engine rules, pinned with probes: - Generator: the engine keeps kvar as a power factor. Assigning kvar sets pf = kW / √(kW² + kvar²), with kvar's sign, at the kW of that moment; assigning kW or pf recomputes kvar = kW·tan(acos |pf|). A pf of 0 (kvar at kW 0) leaves kvar as assigned. So kW=620 kvar=30 then kW=0 is 0 kvar (IEEE9500's Diesel620), kvar=30 kW=100 is 3 (the pf came from the default kW of 1000), and kW=100 kvar=30 then kW=50 is 15. A bare New is kW 1000, pf 0.88, kvar 60. - PVSystem: pf and kvar: the last assigned wins; kvar stays absolute. - Storage: the engine keeps a discharge and a charge setpoint. A kW > 0 sets the first and discharges, a kW < 0 the second and charges, 0 idles; State picks which runs (kW=40, State=idling, State=discharging discharges at 40); %Discharge/%Charge put the setpoint back to the rating's share. kWhstored and %stored: the last wins. - The engine checks a battery's stored energy when its state is assigned, with the energy of that moment: a %stored assigned after State=discharging does not wake a battery that idled at its reserve. No deck in the sweep assigns the energy after the state, so that order raises.

How: DssReader.read_all() returns a DssModel, a GraphModel that also keeps each record's assignment history: every (slot, value) in deck order, from New, edits, BatchEdit, and the slots like= copies (first). DssModel.assignments(record) and last_of(record, *slots) read it, and the mappers replay it (generator.dispatched_kvar, storage.battery_dispatch, PVSystem's last_of(pf, kvar)). Only the history replaces order guesses; the records stay verbatim.

A Load replays its history command by command (load.load_power over DssModel.commands, decision 7). kVA in a later command takes the pf that kvar implied (kW=10 kvar=3 then kVA=20 is 19.2 kW), but in the same command the pf before kvar (S4a engine rules).

S4b maps the rest of the injections and the series reactor: PVSystem and Storage (shape der), Generator (new shape synchronous_machine) and Reactor (new shape series_compensator). Its exit is the full IEEE13_CDPSM artifact directory as the reference golden (D6). The two new shape names are the ones RAW's plan requests from core (its C2), so the two waves share them. RAW adds its bus-branch variants and GeneratingUnit later.

Census of the 31 sweep decks, 2026-11-08 (30 read; the balanced ieee9500_2025 copy stops in the reader, as in S3): - PVSystem: 950 in 7 decks. 887 are 2-phase on a split-phase secondary: 356 at kV 0.208 (the IEEE9500 copies) and 531 at 0.24 (ieee9500_2025). 45 are 1-phase and 13 are 3-phase. - pf is always 1.0, and no PV sets kvar. - irradiance is 1.0 or 0.8 (IEEE13_CDPSM). Only ieee9500 sets %Cutin/%Cutout, at 0.1. - 3 PVs are delta (IEEE9500's M1047PV-3, 3-phase). - IEEE9500's PVFarm1 has Pmpp 1200 on kVA 1000, so the inverter caps it. - Storage: 27 in 5 decks. - States: 22 charge/charging, 3 discharging and 2 idling. pf is 1.0 wherever it is set, and no record sets kvar. - 21 set kW, always after state= (IEEE9500: state=charge kW=150; IEEE123: state=charge kW=-0.0). - 6 are delta. No record sets both kWhstored and %stored. - Generator: 61 in 3 decks (ACEP_PSIL and the IEEE9500 copies), all 3-phase. - Models: 41 ConstantPQ, 15 CurrentLimited (7) and 5 ConstantPV (3). 18 are delta. - Every record sets kVA. Xdp/Xdpp/H are on 45. Maxkvar/Minkvar are never set. - One IEEE9500 machine sets both pf=0.98 and kvar=0 at kW=0. - Reactor: 8. - 7 are IEEE8500/IEEE9500's HVMV_Sub_HSB: series, 3-phase, X 14.798 Ω, R 0, normamps = emergamps = 400. - 1 is K1's T2_neutral, K_LSB.4 to K_LSB.0 on one bus.

Engine rules (pinned with probes in /tmp; the defaults are the engine's readback of a bare New): - PVSystem. - The panel's power is Pmpp × irradiance, and %Pmpp caps it: the available power is min(Pmpp × irradiance, Pmpp × %Pmpp / 100). Probed 2026-11-10: Pmpp 100 at irradiance 0.5 gives 50 at %Pmpp 60 and 150, and 10 at %Pmpp 10; at irradiance 1.2 it gives 120 at %Pmpp 150. q comes from pf (q = P·tan(acos |pf|), with pf's sign) or from kvar. - Over kVA, P is cut to √(kVA² − q²) (var priority, the default), so Pmpp 1200 on kVA 1000 gives 1000. - The PV is off (P = 0) when the panel's power, before the %Pmpp cap, is below %Cutout × kVA / 100 (irradiance 0.5 on Pmpp 100 and kVA 100 runs at %Pmpp 10, giving 10 under a 20 % cut-out). The initial state uses %Cutout, not %Cutin: 25 % with cut-in 30 / cut-out 5 runs, and with cut-in 5 / cut-out 30 it is off. - pf and kvar override each other in the order given (unlike a load, where kvar always wins). - Defaults: 3 phases, kV 12.47, irradiance 1, Pmpp 500, %Pmpp 100, pf 1, kVA 500, %Cutin and %Cutout 20, Vminpu 0.9, wye. kvarMax and kvarMaxAbs default to kVA. - Storage. - State and kW override each other in the order given. A kW > 0 discharges, < 0 charges, and 0 (or −0.0) idles. - So IEEE9500's state=charge kW=150 discharges at 150 kW, and IEEE123's state=charge kW=-0.0 idles. - With no kW: charging draws kWrated × %Charge / 100, discharging gives kWrated × %Discharge / 100, and idling draws %IdlingkW × kWrated / 100 (1 kW on 100). Every |P| is capped at kVA. - The battery idles instead when it is told to charge while full, or to discharge at or below %reserve. - kWhstored and %stored override each other in order. - With pf ≠ 1, the engine caps q at a kvarMax left over from the default kVA (pf 0.9 on 100 kW gives 25 kvar). - Defaults: kV 12.47, kWrated 25, kVA = kWrated, kWhrated 50, %stored 100, %reserve 20, State idling, %Charge/%Discharge 100, %EffCharge/%EffDischarge 90, %IdlingkW 1, pf 1, wye. - Generator. - q comes from pf or kvar, and the two override each other in order. - Defaults: kW 1000, pf 0.88, kV 12.47, model 1, Vpu 1, kVA 1.2 × kW, Maxkvar = 2 × kvar, Minkvar = −2 × kvar. Each kW, pf or kvar assignment resets Maxkvar and Minkvar to ±2 × kvar, so a Maxkvar or Minkvar holds only when assigned after the last of them (engine-checked 2026-11-24). - Model 3 regulates its terminal to Vpu within Maxkvar/Minkvar. Model 7 dispatches as model 1. - 2-phase PV at 0.24 kV on 120 V legs (ieee9500_2025): the engine's base is 0.24/√3 = 138.6 V. The legs sit at 0.866 pu, below Vminpu, so it gives 92.8 % of Pmpp. At 0.208 kV it gives 100 %. This is a power-flow result, not a setting; the mapping keeps the deck's kV (S4b-4). - The engine's CIM export disagrees with itself on sign. ExportCIMXML.pas writes PowerElectronicsConnection.p = −kW but RotatingMachine.p = +kW. cim18v17 documents both as the load sign, so S4b writes −kW for both (S4b-1).

Expected sweep: 22 of 31 decks bind. Besides S3's six, three stop: - CIMHub_2_0's two ieee9500 copies: PVFarm1 ... Mode=7 reads as model=7, which the engine rejects too ("7" is not a valid value), so those decks do not compile. - IEEE123_test_harness: Battery5 is phases=1 on 108.1.2.3, which puts its neutral on node 2. The shared phase rule raises (S4b-6).

Shared rules (S4b)

  • Terminal: the S4 shared phase rule (injection.device_terminal) for PVSystem, Storage and Generator.
  • ratedU is line to line (S4b-4): the deck's kV, × √3 for a 1-phase wye device; the exporter inverts it. This matches the engine's CIM export, which is where GridAPPS-D's files come from. CIMHub_2_0 wrote kV unchanged; the round-trip comparison lists that difference. ratedU is not checked against the bus: a 240 V inverter on 120 V legs stays 240 V.
  • Sign: p and q are the load sign: generation and discharge are negative, q = −kvar (S4b-1).
  • pf with kvar: the deck's assignment order decides, as in the engine (S4b-8, which replaced S4b-2's raise).
  • Inverter cap (PVSystem and Storage): inverter_power(available, q, kva), the engine's var-priority cut.
  • enabled=false gives normallyInService=false (S4-9).

PVSystem

Mapper importer/cimtbl/pvsystem.py (map_pvsystem). Artifact pvsystem.cimtbl; shape der. Atom tests/atoms/der/der.dss: - the IEEE13_CDPSM PVs: 3-phase at irradiance 0.8, and 2-phase s1s2 at 0.208; - a 1-phase leg, a delta PV, a kVA-capped PV, one below cut-out, one with a negative pf, one with kvar, and one capped at %Pmpp (irradiance 0.9 at %Pmpp 60 gives 6 kW).

Identity. PowerElectronicsConnection pv_ + name and PhotoVoltaicUnit pv_<name>_unit, lowercased. The prefix keeps IEEE13_CDPSM's PVSystem.School and Storage.School apart.

Rows. - Connection: - node, phases, phaseConnection (cim18v17's PowerElectronicsConnection has no grounded); - ratedS = kVA, ratedU (S4b-4); - p = −P and q = −q, by the rules above (derived, pv_power); - maxQ = kvarMax, minQ = −kvarMaxAbs, maxIFault = 1 / Vminpu (the engine's export convention); - normallyInService, BaseVoltage, EquipmentContainer. - Unit: maxP = Pmpp, minP = 0, irradiance = irradiance (kW/m2; the gridappsd extension), and its connection.

What raises: - model other than 1; - EffCurve or P-TCurve (both change the snapshot power); - WattPriority or PFPriority set to yes; a nonzero %PminNoVars or %PminkvarMax; - UserModel/UserData; ControlMode=GFM; Balanced or LimitCurrent set to yes; - a kvar above kVA, on or off (M38, decision 9, 2026-11-27): below %Cutout the engine clamps it to kvarMax (Pmpp=100 kVA=100 irradiance=0.05 kvar=150 gives 100 kvar), and reactive capability is not modelled yet.

Untranscribed: - the Yearly/Daily/Duty and T-curves, which are time series that a snapshot does not use; - %Cutin, which only acts after the inverter turns off; - %R, %X, kVDC, Kp, PITol, SafeVoltage, SafeMode, DynamicEq, DynOut, AmpLimit, AmpLimitGain (dynamics); - Vmaxpu, Temperature (it acts only through a P-TCurve), VarFollowInverter (InvControl), class, spectrum, basefreq, DutyStart, DebugTrace.

Storage

Mapper importer/cimtbl/storage.py (map_storage). Artifact storage.cimtbl; shape der. Atom tests/atoms/der/der.dss: - the three IEEE13_CDPSM batteries (charging, discharging, idling); - state=charge kW=150 (IEEE9500) and state=charge kW=-0.0 (IEEE123); - a kVA-capped battery, one with %stored, and a delta battery.

Identity. PowerElectronicsConnection storage_ + name, and BatteryUnit storage_<name>_unit.

Rows. - Connection: as a PV's, with ratedS = kVA (default kWrated). q = 0. - Unit: - ratedE = kWhrated; - storedE = kWhstored, else %stored × kWhrated / 100; - minimumE = %reserve × kWhrated / 100; - maxP = kWrated, minP = −kWrated; - chargingEfficiency = %EffCharge and dischargingEfficiency = %EffDischarge (percent); - idlingP = %IdlingkW × kWrated / 100. - State and p (derived, battery_dispatch; S4b-8): the deck's kW, State, %Discharge and %Charge assignments replayed in order (above). Discharging p = −min(setpoint, kVA), charging p = min(setpoint, kVA), idling waiting with p = idlingP. A setpoint is the last kW of its sign, else kWrated × %Discharge (or %Charge) / 100. - The row comment names an override, for example "kW=150 after State=charging: discharging".

What raises: - a battery that the engine would idle instead: charging when full, or discharging at or below %reserve; - kWhstored, %stored, kWhrated or %reserve assigned after the last State or kW (above); - pf ≠ 1 or kvar ≠ 0 (because of the engine's kvarMax quirk above; no deck has one); - DispMode other than default; - model other than 1; - EffCurve, UserModel/UserData, DynaDLL/DynaData; - WattPriority/PFPriority set to yes, a nonzero %PminNoVars/%PminkvarMax, Balanced/LimitCurrent set to yes; - a negative %IdlingkW (decision 12, 2026-11-27): the engine takes it and the idling battery generates, but the exporter raises on a negative idlingP, so the import raises too.

Untranscribed: the curves, DischargeTrigger/ChargeTrigger/TimeChargeTrig (dispatch modes, which raise), %Idlingkvar (deprecated), %CutIn/%CutOut, %kWRated, Vmaxpu, and the dynamics slots, as for PVSystem.

Generator

Mapper importer/cimtbl/generator.py (map_generator). Artifact generator.cimtbl; shape synchronous_machine. Atom tests/atoms/generator/gens.dss: - models 1, 3 and 7; wye and delta; - q from pf, from kvar, and from the default 0.88; - kW=0 pf=0.98 kvar=0; and a 1-phase machine; - model 3 with Maxkvar alone (capped), and with Maxkvar and Minkvar before a kW edit (reset).

Identity. SynchronousMachine gen_ + name. A model 3 control is gen_<name>_ctrl: the machine has no control of its own name, as the shape's <cap>_ctrl had.

Rows. - node, phases; - ratedS = kVA (default 1.2 × kW), ratedU (S4b-4); - p = −kW, q = −q; - type=generator, operatingMode=generator; - earthing = not delta (S4b-5); - normallyInService, BaseVoltage, EquipmentContainer.

Model 3 (PV bus): - maxQ = Maxkvar and minQ = Minkvar (default ±2 × kvar, reset by each kW, pf or kvar assignment: reactive_limits); - a RegulatingControl gen_<name>_ctrl: - mode=voltage, discrete=false, enabled=true; - targetValue = Vpu × ratedU in kV with targetValueUnitMultiplier=k, targetDeadband=0; - Terminal=gen_<name>_T1; - then Update SynchronousMachine: mRID, RegulatingControl, controlEnabled=true. This is S4a's own-terminal form (U3).

Model 7 maps as model 1, with a row note: below Vminpu it limits current, which is power-flow behaviour.

What raises: - models 2, 4, 5 and 6; UserModel/ShaftModel; - Maxkvar/Minkvar on a model other than 3.

Untranscribed: - Xd, Xdp, Xdpp, H, D, XRdp (dynamics); - Vminpu, Vmaxpu, PVFactor (a solver aid), Status, DispMode, DispValue, ForceOn; - the curves, the fuel slots, class, spectrum, basefreq.

Reactor

Mapper importer/cimtbl/reactor.py (map_reactor). Artifact reactor.cimtbl; shape series_compensator. Atom tests/atoms/reactor/reactors.dss: IEEE8500's HVMV_Sub_HSB and a 1-phase series reactor with R.

Identity. SeriesCompensator rx_ + name.

Rows. - node1, node2, phases (the line rule, line_phases); - r = R and x = X (Ω per phase); r0 = R and x0 = X, as in the engine's export (no mutual coupling); - normallyInService, BaseVoltage (bus1's), EquipmentContainer; - rx_<name>_limits, an OperationalLimitSet with CurrentLimits _norm/_emerg. These come from the deck's own normamps/emergamps only (nothing from the engine's kvar-derived defaults), as for a line. Line's ratings code is shared.

What raises: - no bus2, or bus2 on the same bus: a shunt or neutral reactor, such as K1's T2_neutral (K1 stops on DSS-10 first); - X unset, or kvar given (X derived from kvar and kV); - Rmatrix/Xmatrix, Z/Z1/Z2/Z0, LmH, Rp, Parallel=yes, RCurve/LCurve.

Untranscribed: kV (it acts only with kvar), conn (a series reactor has no neutral), faultrate/pctperm/ repair, basefreq.

Artifact order, schema, shapes (S4b)

  • Order: MAPPING_ORDER gains reactor after line (it is a branch, and its limits use the common limit types), then pvsystem, storage and generator after capcontrol.
  • Schema (DSS-6). The dss_defaults of the four classes become the engine readback above. This fixes PVSystem's pf 0.88 → 1, its Vminpu 0 → 0.9, and Generator's Xdp 0.27 → 0.28. The derived defaults (kvarMax, Storage kVA, Generator kVA and Maxkvar) stay in the mapper, named.
  • Core shapes:
  • der.cimtbl: gains phaseConnection, maxQ/minQ/maxIFault, a 2-phase s1s2 PV, and the battery's minimumE, efficiencies, idlingP and maxP/minP.
  • New synchronous_machine.cimtbl: a model 1 machine, and a PV-bus machine with its RegulatingControl and the Update.
  • New series_compensator.cimtbl: a reactor between two nodes, with its limit set.
  • The cimtbl-shapes skill rows to match.

Engine checks (S4b)

On the atoms and the engine decks: - PVSystem: kVA, kV, Pmpp; p and q against the engine's dispatch (PVSystems.kW()/kvar() after Compile); - Storage: kWrated, kVA, kWhrated, kWhstored, the state, and the kW/kvar properties; - Generator: the kW and kvar properties, kVA, kV, delta, and model/Vpu/Maxkvar/Minkvar for model 3; - Reactor: R, X, both buses, normamps and emergamps.

IEEE13_CDPSM golden directory (D6)

tests/goldens/IEEE13_CDPSM/ holds every part to_cimtbl writes (master, bus, zip_fractions, each class's document), not only the master and bus. The orchestrator test compares the whole directory, and CIMHUB_UPDATE_GOLDENS=1 rewrites it.

PVSystem, Storage, Generator and Reactor fields

Generated from each mapper's FIELDS (samples: the 31 sweep decks).

Pvsystem field type samples kind target
name Union[str, PvsystemName] House, School, PVFarm1 copied PowerElectronicsConnection.name; mRID = pv_ + name, lowercased; the unit is _unit
phases Optional[int] 2, 3, 1 structural the conductor count; default 3
bus1 Optional[str] House.1.2, 634, M1047PV-3 structural node and phases, by the S4 shared phase rule
kv Optional[float] 0.208, 0.48, 12.47 derived ratedU (kV, LL) = kv, x sqrt 3 for 1-phase wye (S4b-4); not checked against the bus; default 12.47
irradiance Optional[float] 0.8, 1.0 copied PhotoVoltaicUnit.irradiance (kW/m2); also p (pv_power); default 1
Pmpp Optional[float] 5.0, 300.0, 1000.0 copied PhotoVoltaicUnit.maxP (kW); also p (pv_power); default 500
pct_Pmpp Optional[float] derived p is capped at Pmpp x %Pmpp / 100 (pv_power); default 100
Temperature Optional[float] untranscribed acts only through a P-TCurve, which raises
pf Optional[float] 1.0 derived q = -kW x tan(acos abs(pf)) x sign(pf), unless kvar was assigned after it (the last of the two wins, S4b-8); default 1
conn Optional[str] wye, delta mapped PowerElectronicsConnection.phaseConnection; wye -> Y, delta -> D; default wye
kvar Optional[float] derived q (kVAr) = -kvar (the load sign), unless pf was assigned after it; above kVA it raises, off or on (the engine clamps it to kvarMax; decision 9)
kVA Optional[float] 5.0, 300.0, 1500.0 copied PowerElectronicsConnection.ratedS (kVA); also caps p (var priority); default 500
pct_Cutin Optional[float] 0.1 structural acts only after the inverter turns off; the snapshot state uses %Cutout; a yearly sample between %Cutout and %Cutin raises (S9); default 20
pct_Cutout Optional[float] 0.1 derived p = 0 when Pmpp x irradiance is below %Cutout of kVA, q too unless kvar is set (VarFollowInverter); default 20
EffCurve Optional[str] structural raises: an efficiency curve changes the snapshot power
P_TCurve Optional[str] structural raises: a temperature curve changes the snapshot power
pct_R Optional[float] untranscribed a dynamics setting; no home in the network profile parts
pct_X Optional[float] untranscribed a dynamics setting; no home in the network profile parts
model Optional[int] 7, 1 structural 1 (constant P, PF) only; any other raises (ieee9500's Mode=7 is model=7, which the engine rejects too); default 1
Vminpu Optional[float] derived maxIFault = 1 / Vminpu (the engine's CIM export); default 0.9
Vmaxpu Optional[float] untranscribed above it the engine models the PV as constant Z; a power-flow setting
Balanced Union[bool, Bool, NoneType] structural raises when yes: no deck in the sweep sets it, so a mapping waits for one
LimitCurrent Union[bool, Bool, NoneType] structural raises when yes: no deck in the sweep sets it, so a mapping waits for one
yearly Optional[str] mapped EnergyConnectionSchedule.name; the PV's EnergyConnectionSchedule _yearly: pv_power at irradiance x mult per sample (S9)
daily Optional[str] untranscribed a time-series curve; a snapshot does not use it (DSS-11)
duty Optional[str] untranscribed a time-series curve; a snapshot does not use it (DSS-11)
Tyearly Optional[str] untranscribed a time-series curve; a snapshot does not use it (DSS-11)
Tdaily Optional[str] untranscribed a time-series curve; a snapshot does not use it (DSS-11)
Tduty Optional[str] untranscribed a time-series curve; a snapshot does not use it (DSS-11)
class_class Optional[int] untranscribed a DSS report grouping
UserModel Optional[str] structural raises when set: no deck in the sweep sets it, so a mapping waits for one
UserData Optional[str] structural raises when set: no deck in the sweep sets it, so a mapping waits for one
debugtrace Union[bool, Bool, NoneType] untranscribed a DSS debugging switch
VarFollowInverter Union[bool, Bool, NoneType] derived yes: an inverter that is off gives no kvar either (pv_power, engine-checked); default no
DutyStart Optional[float] untranscribed a time-series curve; a snapshot does not use it (DSS-11)
WattPriority Union[bool, Bool, NoneType] structural raises when yes: no deck in the sweep sets it, so a mapping waits for one (var priority is mapped)
PFPriority Union[bool, Bool, NoneType] structural raises when yes: no deck in the sweep sets it, so a mapping waits for one
pct_PminNoVars Optional[float] structural raises when nonzero: no deck in the sweep sets it, so a mapping waits for one
pct_PminkvarMax Optional[float] structural raises when nonzero: no deck in the sweep sets it, so a mapping waits for one
kvarMax Optional[float] copied PowerElectronicsConnection.maxQ (kVAr); default kVA
kvarMaxAbs Optional[float] derived minQ (kVAr) = -kvarMaxAbs; default kVA
kVDC Optional[float] untranscribed a dynamics setting; no home in the network profile parts
Kp Optional[float] untranscribed a dynamics setting; no home in the network profile parts
PITol Optional[float] untranscribed a dynamics setting; no home in the network profile parts
SafeVoltage Optional[float] untranscribed a dynamics setting; no home in the network profile parts
SafeMode Union[bool, Bool, NoneType] untranscribed a dynamics setting; no home in the network profile parts
DynamicEq Optional[str] untranscribed a dynamics setting; no home in the network profile parts
DynOut Union[str, list[str], NoneType] untranscribed a dynamics setting; no home in the network profile parts
ControlMode Optional[str] structural GFL only; GFM raises (no deck in the sweep sets it, so a mapping waits for one)
AmpLimit Optional[float] untranscribed a dynamics setting; no home in the network profile parts
AmpLimitGain Optional[float] untranscribed a dynamics setting; no home in the network profile parts
spectrum Optional[str] untranscribed harmonics model; no home in the network profile parts
basefreq Optional[float] untranscribed no home on an inverter
enabled Union[bool, Bool, NoneType] copied PowerElectronicsConnection.normallyInService; default true
like Optional[str] untranscribed the reader resolves like= before mapping
Storage field type samples kind target
name Union[str, StorageName] BatIdle, House, School copied PowerElectronicsConnection.name; mRID = storage_ + name, lowercased; the unit is _unit
phases Optional[int] 3, 2, 1 structural the conductor count; default 3
bus1 Optional[str] 634, House.1.2, m2001-ESS1 structural node and phases, by the S4 shared phase rule
kv Optional[float] 0.48, 0.208, 2.4 derived ratedU (kV, LL) = kv, x sqrt 3 for 1-phase wye (S4b-4); default 12.47
conn Optional[str] wye, delta mapped PowerElectronicsConnection.phaseConnection; wye -> Y, delta -> D; default wye
kW Optional[float] 150.0, -0.0, 0.0 derived replayed in deck order (battery_dispatch, S4b-8): > 0 sets the discharge setpoint and discharging, < 0 the charge setpoint and charging, 0 waiting; capped at kVA
kvar Optional[float] structural raises when nonzero: no deck in the sweep sets it, so a mapping waits for one (q = 0)
pf Optional[float] 1.0 structural 1 only; another raises (the engine caps q by a kvarMax left from the default kVA); default 1
kVA Optional[float] 250.0, 125.0, 200.0 copied PowerElectronicsConnection.ratedS (kVA); also caps p; default kWrated
pct_Cutin Optional[float] untranscribed an inverter cut-in; 0 by default for storage
pct_Cutout Optional[float] untranscribed an inverter cut-out; 0 by default for storage
EffCurve Optional[str] structural raises: an efficiency curve changes the snapshot power
VarFollowInverter Union[bool, Bool, NoneType] untranscribed acts only with an InvControl
kvarMax Optional[float] copied PowerElectronicsConnection.maxQ (kVAr); default kVA
kvarMaxAbs Optional[float] derived minQ (kVAr) = -kvarMaxAbs; default kVA
WattPriority Union[bool, Bool, NoneType] structural raises when yes: no deck in the sweep sets it, so a mapping waits for one
PFPriority Union[bool, Bool, NoneType] structural raises when yes: no deck in the sweep sets it, so a mapping waits for one
pct_PminNoVars Optional[float] structural raises when nonzero: no deck in the sweep sets it, so a mapping waits for one
pct_PminkvarMax Optional[float] structural raises when nonzero: no deck in the sweep sets it, so a mapping waits for one
kWrated Optional[float] 100.0, 5.0, 250.0 copied BatteryUnit.maxP (kW); minP = -kWrated; also p by State; default 25
pct_kWrated Optional[float] untranscribed the kW limit of the dispatch modes, which raise
kWhrated Optional[float] 200.0, 13.5, 500.0 copied BatteryUnit.ratedE (kWh); default 50
kWhstored Optional[float] 100.0, 5.0, 135.0 copied BatteryUnit.storedE (kWh); unless %stored was assigned after it (the last wins)
pct_stored Optional[float] 60.0, 40.0, 35.0 derived storedE (kWh) = %stored x kWhrated / 100 unless kWhstored was assigned after it; default 100
pct_reserve Optional[float] 30.0 derived minimumE (kWh) = %reserve x kWhrated / 100; default 20
State Optional[str] idling, charging, discharging mapped BatteryUnit.batteryState; charging, discharging, idling -> waiting (by the first letter, as the engine reads it: the decks' charge); picks the setpoint that runs, replayed with kW (S4b-8); default idling
pct_Discharge Optional[float] derived the discharge setpoint kWrated x %Discharge / 100 until a kW > 0 sets it; default 100
pct_Charge Optional[float] derived the charge setpoint kWrated x %Charge / 100 until a kW < 0 sets it; default 100
pct_EffCharge Optional[float] copied BatteryUnit.chargingEfficiency (percent); default 90
pct_EffDischarge Optional[float] copied BatteryUnit.dischargingEfficiency (percent); default 90
pct_IdlingkW Optional[float] derived idlingP (kW) = %IdlingkW x kWrated / 100, also p when waiting; default 1; negative raises (decision 12)
pct_Idlingkvar Optional[float] untranscribed deprecated in the engine
pct_R Optional[float] untranscribed a dynamics setting; no home in the network profile parts
pct_X Optional[float] untranscribed a dynamics setting; no home in the network profile parts
model Optional[int] structural 1 (constant P, PF) only; any other raises; default 1
Vminpu Optional[float] derived maxIFault = 1 / Vminpu (the engine's CIM export); default 0.9
Vmaxpu Optional[float] untranscribed above it the engine models the battery as constant Z; a power-flow setting
Balanced Union[bool, Bool, NoneType] structural raises when yes: no deck in the sweep sets it, so a mapping waits for one
LimitCurrent Union[bool, Bool, NoneType] structural raises when yes: no deck in the sweep sets it, so a mapping waits for one
yearly Optional[str] mapped EnergyConnectionSchedule.name; DispMode=follow: the battery's EnergyConnectionSchedule _yearly, mult x kWrated per sample (S9); with another DispMode raises
daily Optional[str] untranscribed a time-series curve; a snapshot does not use it (DSS-11)
duty Optional[str] untranscribed a time-series curve; a snapshot does not use it (DSS-11)
DispMode Optional[str] structural default, or follow with a yearly shape (S9); another dispatch mode raises (no deck in the sweep sets it, so a mapping waits for one)
DischargeTrigger Optional[float] untranscribed acts only in a dispatch mode, which raises
ChargeTrigger Optional[float] untranscribed acts only in a dispatch mode, which raises
TimeChargeTrig Optional[float] untranscribed acts only in a dispatch mode, which raises
class_class Optional[int] untranscribed a DSS report grouping
DynaDLL Optional[str] structural raises when set: no deck in the sweep sets it, so a mapping waits for one
DynaData Optional[str] structural raises when set: no deck in the sweep sets it, so a mapping waits for one
UserModel Optional[str] structural raises when set: no deck in the sweep sets it, so a mapping waits for one
UserData Optional[str] structural raises when set: no deck in the sweep sets it, so a mapping waits for one
debugtrace Union[bool, Bool, NoneType] untranscribed a DSS debugging switch
kVDC Optional[float] untranscribed a dynamics setting; no home in the network profile parts
Kp Optional[float] untranscribed a dynamics setting; no home in the network profile parts
PITol Optional[float] untranscribed a dynamics setting; no home in the network profile parts
SafeVoltage Optional[float] untranscribed a dynamics setting; no home in the network profile parts
SafeMode Union[bool, Bool, NoneType] untranscribed a dynamics setting; no home in the network profile parts
DynamicEq Optional[str] untranscribed a dynamics setting; no home in the network profile parts
DynOut Union[str, list[str], NoneType] untranscribed a dynamics setting; no home in the network profile parts
ControlMode Optional[str] structural GFL only; GFM raises (no deck in the sweep sets it, so a mapping waits for one)
AmpLimit Optional[float] untranscribed a dynamics setting; no home in the network profile parts
AmpLimitGain Optional[float] untranscribed a dynamics setting; no home in the network profile parts
spectrum Optional[str] untranscribed harmonics model; no home in the network profile parts
basefreq Optional[float] untranscribed no home on an inverter
enabled Union[bool, Bool, NoneType] copied PowerElectronicsConnection.normallyInService; default true
like Optional[str] untranscribed the reader resolves like= before mapping
Generator field type samples kind target
name Union[str, GeneratorName] Diesel590, Diesel620, LNGengine100 copied SynchronousMachine.name; mRID = gen_ + name, lowercased
phases Optional[int] structural the conductor count; default 3
bus1 Optional[str] m1089-DIES1, m1209-DIES1, M1142-LNG1 structural node and phases, by the S4 shared phase rule
kv Optional[float] 0.48, 12.47 derived ratedU (kV, LL) = kv, x sqrt 3 for 1-phase wye (S4b-4); default 12.47
kW Optional[float] 0.0, 50.0, 100.0 derived p (kW) = -kW (the load sign); default 1000
pf Optional[float] 0.95, 0.98 derived q (kVAr) = -kvar, kvar replayed from the kW, pf and kvar assignments in deck order (dispatched_kvar, S4b-8): each kW or pf recomputes kvar = kW x tan(acos abs(pf)); default 0.88
kvar Optional[float] 15.0, 30.0, 5.0 derived sets the pf, kW / kVA with kvar's sign, at the kW of that moment; a pf of 0 (kvar at kW 0) leaves kvar as set (dispatched_kvar, S4b-8)
model Union[str, ForwardRef('GeneratorModel'), NoneType] CurrentLimited, ConstantPQ, ConstantPV structural 1 and 7 dispatch kW/kvar; 3 adds a voltage RegulatingControl; 2, 4, 5, 6 raise; default 1
Vminpu Optional[float] untranscribed below it the engine models the machine as constant Z; a power-flow setting
Vmaxpu Optional[float] untranscribed above it the engine models the machine as constant Z; a power-flow setting
yearly Optional[str] mapped EnergyConnectionSchedule.name; the machine's EnergyConnectionSchedule _yearly: -kW x mult, -kvar x mult per sample (S9)
daily Optional[str] untranscribed a time-series curve; a snapshot does not use it (DSS-11)
duty Optional[str] untranscribed a time-series curve; a snapshot does not use it (DSS-11)
dispmode Union[str, ForwardRef('DispatchMode'), NoneType] untranscribed a dispatch setting of time-series solutions; a snapshot does not use it; with a yearly shape, another than Default raises
dispvalue Optional[float] untranscribed a dispatch setting of time-series solutions; a snapshot does not use it; with a yearly shape, above 0 raises
conn Union[str, ForwardRef('ConnectionType'), NoneType] wye, delta mapped SynchronousMachine.earthing; wye -> earthing true, delta -> false (no phaseConnection on a machine, S4b-5); default wye
status Union[str, ForwardRef('GenStatus'), NoneType] untranscribed Fixed/Variable: whether load multipliers scale it; a dispatch setting of time-series solutions; a snapshot does not use it; with a yearly shape, Fixed raises
gen_class Optional[int] untranscribed a DSS report grouping
Vpu Optional[float] 1.0 derived model 3: the control's targetValue = Vpu x ratedU in kV (targetValueUnitMultiplier k); default 1
maxkvar Optional[float] copied SynchronousMachine.maxQ (kVAr); model 3 only (another model raises); default 2 x kvar (reactive_limits)
minkvar Optional[float] copied SynchronousMachine.minQ (kVAr); model 3 only (another model raises); default -2 x kvar (reactive_limits)
pvfactor Optional[float] untranscribed a convergence aid of the engine's model 3
forceon Union[bool, Bool, NoneType] untranscribed a dispatch setting of time-series solutions; a snapshot does not use it
kVA Optional[float] 737.0, 775.0, 125.0 copied SynchronousMachine.ratedS (kVA); default 1.2 x kW
MVA Optional[float] structural raises when set: no deck in the sweep sets it, so a mapping waits for one (kVA is)
Xd Optional[float] untranscribed a dynamics setting; no home in the network profile parts
Xdp Optional[float] 0.27 untranscribed a dynamics setting; no home in the network profile parts
Xdpp Optional[float] 0.2 untranscribed a dynamics setting; no home in the network profile parts
H Optional[float] 2.0 untranscribed a dynamics setting; no home in the network profile parts
D Optional[float] untranscribed a dynamics setting; no home in the network profile parts
UserModel Optional[str] structural raises when set: no deck in the sweep sets it, so a mapping waits for one
UserData Optional[str] structural raises when set: no deck in the sweep sets it, so a mapping waits for one
ShaftModel Optional[str] structural raises when set: no deck in the sweep sets it, so a mapping waits for one
ShaftData Optional[str] structural raises when set: no deck in the sweep sets it, so a mapping waits for one
DutyStart Optional[float] untranscribed a time-series curve; a snapshot does not use it (DSS-11)
debugtrace Union[bool, Bool, NoneType] untranscribed a DSS debugging switch
Balanced Union[bool, Bool, NoneType] untranscribed a power-flow setting of the engine's model
XRdp Optional[float] untranscribed a dynamics setting; no home in the network profile parts
UseFuel Union[bool, Bool, NoneType] untranscribed a fuel-limited dispatch setting; a snapshot does not use it
FuelkWh Optional[float] untranscribed a fuel-limited dispatch setting; a snapshot does not use it
pct_Fuel Optional[float] untranscribed a fuel-limited dispatch setting; a snapshot does not use it
pct_Reserve Optional[float] untranscribed a fuel-limited dispatch setting; a snapshot does not use it
Refuel Union[bool, Bool, NoneType] untranscribed a fuel-limited dispatch setting; a snapshot does not use it
DynamicEq Optional[str] untranscribed a dynamics setting; no home in the network profile parts
DynOut Union[str, list[str], NoneType] untranscribed a dynamics setting; no home in the network profile parts
spectrum Optional[str] untranscribed harmonics model; no home in the network profile parts
basefreq Optional[float] untranscribed no home on a machine
enabled Union[bool, Bool, NoneType] copied SynchronousMachine.normallyInService; default true
like Optional[str] untranscribed the reader resolves like= before mapping
Reactor field type samples kind target
name Union[str, ReactorName] HVMV_Sub_HSB, T2_neutral copied SeriesCompensator.name; mRID = rx_ + name, lowercased
bus1 Optional[str] SourceBus, sourcebus, K_LSB.4 structural node1 and the phases (the line rule)
bus2 Optional[str] HVMV115_HSB1, hvmv115s1_HSB1, K_LSB.0 structural node2; unset or on bus1's bus (a shunt or neutral reactor) raises
phases Optional[int] 1 structural the conductor count; default 3
kvar Optional[float] structural raises when set: no deck in the sweep sets it, so a mapping waits for one (X from kvar and kV)
kv Optional[float] untranscribed acts only with kvar, which raises
conn Optional[str] untranscribed a series reactor has no neutral
Rmatrix Union[float, list[float], NoneType] structural raises when set: no deck in the sweep sets it, so a mapping waits for one
Xmatrix Union[float, list[float], NoneType] structural raises when set: no deck in the sweep sets it, so a mapping waits for one
Parallel Union[bool, Bool, NoneType] structural raises when yes: no deck in the sweep sets it, so a mapping waits for one
R Optional[float] 0.0 copied SeriesCompensator.r (ohm), SeriesCompensator.r0 (ohm); per phase; r0 = r (no mutual); default 0
X Optional[float] 14.798306633595042, 0.5 copied SeriesCompensator.x (ohm), SeriesCompensator.x0 (ohm); per phase; x0 = x (no mutual); unset raises
Rp Optional[float] structural raises when set: no deck in the sweep sets it, so a mapping waits for one (a parallel R)
Z1 Union[float, list[float], NoneType] structural raises when set: no deck in the sweep sets it, so a mapping waits for one
Z2 Union[float, list[float], NoneType] structural raises when set: no deck in the sweep sets it, so a mapping waits for one
Z0 Union[float, list[float], NoneType] structural raises when set: no deck in the sweep sets it, so a mapping waits for one
Z Union[float, list[float], NoneType] structural raises when set: no deck in the sweep sets it, so a mapping waits for one
RCurve Optional[str] structural raises when set: no deck in the sweep sets it, so a mapping waits for one
LCurve Optional[str] structural raises when set: no deck in the sweep sets it, so a mapping waits for one
LmH Optional[float] structural raises when set: no deck in the sweep sets it, so a mapping waits for one (X from an inductance)
normamps Optional[float] 400.0 structural instance OperationalLimitSet rx__limits: CurrentLimit _norm (olt_normal); nothing from the engine's kvar-derived default
emergamps Optional[float] 400.0 structural CurrentLimit emerg (olt_emergency) in rx_limits
faultrate Optional[float] untranscribed a reliability setting; no home in the network profile parts
pctperm Optional[float] untranscribed a reliability setting; no home in the network profile parts
repair Optional[float] untranscribed a reliability setting; no home in the network profile parts
basefreq Optional[float] 60.0 untranscribed no home on a compensator; x is at the model's frequency
enabled Union[bool, Bool, NoneType] copied SeriesCompensator.normallyInService; default true
like Optional[str] untranscribed the reader resolves like= before mapping

Decisions for S4b (approved 2026-11-08)

S4b-1 to S4b-4 were approved as written; S4b-5 to S4b-7 had no objection and stand as proposed. The user added that cim18v17's RotatingMachinePhase names a 1-phase machine's phase.

  • S4b-1: p and q follow the load sign for everything, PowerElectronicsConnection and SynchronousMachine (−kW for generation), as cim18v17 documents. The engine's export writes +kW on machines; the exporter negates.
  • S4b-2 (replaced by S4b-8): pf with kvar raised unless both gave the same q.
  • S4b-3 (replaced by S4b-8): a Storage's kW decided its state when set. The replay gives the same result on every deck (IEEE9500's state=charge kW=150 still discharges at 150 kW).
  • S4b-4: ratedU is line to line, as the engine exports it: the deck's kV, × √3 for 1-phase wye. It is not checked against the bus.
  • S4b-5: a delta generator is earthing=false, because SynchronousMachine has no phaseConnection. In DSS a wye machine's neutral is ground (the shared rule raises otherwise), so for DSS earthing is exactly "not delta". A request for RotatingMachine.phaseConnection goes to UPSTREAM_REQUESTS.md as U8.
  • S4b-6: IEEE123_test_harness's Battery5 (1-phase, neutral on node 2) raises under the shared phase rule. The deck is wrong (it looks like a 3-phase battery written as phases=1), and a guess would put it across A–B.
  • S4b-7: shape names synchronous_machine and series_compensator, shared with RAW (its C2), in place of the DSS plan's machine.
  • S4b-9: a balanced three-phase device (phases ABC) has a blank phases cell, so no per-phase children and no Terminal.phases (above); U10 asks CIM-Tables for the balanced form.
  • S4b-8 (approved 2026-11-08): the reader keeps each record's assignment history (DssModel), and the Generator, PVSystem and Storage mappers replay it as the engine does (above). The Load replays it command by command (decision 7, 2026-11-27).

S5 (approved and done 2026-11-08)

Result (2026-11-08). - Every equipment Location equals the engine's bus coordinates on both atoms and the 8 engine decks that bind: - one point per Terminal where every Terminal bus has Bus.Coorddefined(), and no Location otherwise; - this includes IEEE8500 and IEEE9500, where the engine's x is the longitude. - The sweep test passes: 18 of the 24 CIMHUB_DSS_DECKS decks bind and 6 stop as listed. The throwaway 31-deck sweep is unchanged at 22. - The reader fix (S5-7) recovers the IEEE123 coordinates: IEEE123_PV 214 rows (was 2), deconfliction 134 and test_harness 139 (were 0). Every coordinate file in the sweep parses. - Locations: IEEE9500 unbal 8,072; IEEE8500 6,082; IEEE123_PV 326; IEEE13_CDPSM 46. - The IEEE13_CDPSM golden directory has 14 files. - G7 after S5:

deck read map bind
IEEE9500 unbal 4.0 s 1.0 s 8.2 s: 65,282 rows / 80,238 objects, about 7,900 rows/s
IEEE8500 0.5 s 0.7 s 6.6 s: 47,840 rows, about 7,200 rows/s

The coordinates cost about 2 s of bind on each deck.

The user's review: keep the CIM17 form, PositionPoint.Location, not cim18v17's Geometry/GeometricElement form (the catalog lists that as not yet catalogued). The decisions stand as recommended.

Changes from the proposal: - A center-tap transformer gets two points, not three. Its secondary is one Terminal (s1s2N), because the windings land on lugs (DSS-2). The engine writes a point for each of its 3 windings, but two of them are the same bus. - The Terminals come from the bound network, not from the document text (S5-2, revised 2026-11-09 when CIM-Tables declined U11). So a TransformerEnd's Terminal is whatever binding made of it; no separate end-class check.

S5 adds bus coordinates (buscoords.cimtbl), turns the throwaway deck sweep into a test, and records the G7 numbers. Census through today's reader on the 31 sweep decks: 14 decks have coordinates (about 31,000 rows; IEEE9500 5,305, IEEE8500 4,893, J1 3,441, K1 650; the IEEE13s 16-74). Only PNNL/IEEE9500 uses LatLongCoords; every other deck uses BusCoords. No deck uses both.

Where the coordinates go (S5-1)

In CIM a Location hangs off a PowerSystemResource. A ConnectivityNode is not one, so a bus can't carry coordinates itself. Proposed: each piece of conducting equipment gets one Location with one PositionPoint per Terminal, holding the coordinates of that Terminal's bus. So a line is a two-point polyline, a load or capacitor is one point, and a center-tap transformer has three. This matches the engine's own CIM export (WritePositions in ExportCIMXML.pas), CIMHub_2_0's importer and GridAPPS-D. A CYME section's polyline also fits it, with more points per line. The alternative, rejected: a Junction per bus (the CIM note: "to associate ... Location to a ConnectivityNode"). It is closer to the native table, but it adds about 5,300 one-terminal equipment objects to IEEE9500, and every consumer and exporter would have to skip them. No tool reads it either.

Revised 2026-11-10 (S5-8): the points are drawn as a GIS draws the equipment, through cimtables' wkt column. A line (ACLineSegment) is a LINESTRING through its Terminals' buses; any other equipment is one POINT, at its bus for one Terminal and at its buses' centroid for more. So a switch, fuse or transformer sits midway between its buses, as a GIS point feature does, rather than as a two-point polyline.

Shape location (added to the catalog first)

Profile = cim18v17
Import common.cimtbl

Object CoordinateSystem: mRID=crs_bus, name=BusCoords, crsUrn=OpenDSSLocalBusCoordinates

Update Table PowerSystemResource: mRID, wkt
    ln_650632,  "LINESTRING (200.0 350.0, 200.0 300.0)"
    sw_671692,  "POINT (225.0 250.0)"
    ld_671,     "POINT (200.0 250.0)"

An Update on the abstract PowerSystemResource resolves any subclass. cimtables' wkt binding makes the Location (<mRID>_loc), one Identity-only PositionPoint per vertex (<mRID>_loc_<n>, sequenceNumber from 0) and points the Location at the CoordinateSystem declared first.

Buscoords

  • Mapper: importer/cimtbl/buscoords.py, map_buscoords(native, network). It is DssImporter.bound_parts: core binds every other part first, calls it with that network, writes buscoords.cimtbl beside them as the last Import (DSS_REWRITE_PLAN.md §2, row 16) and binds it onto the same network.
  • Finding the equipment (S5-2, revised 2026-11-09): the mapper reads each piece of equipment's Terminals from the bound network (terminal_buses), not from the DSS records, so no mapper's mRID or bus rules are written twice; the circuit's buses are the network's ConnectivityNodes. The first version re-read the connectivity columns of the written documents (core's document_terminals) and asked CIM-Tables for that inverse (U11). CIM-Tables declined: a .cimtbl means what binding makes. The hook (CimtblImporter.bound_parts, cimtbl_to_cim(bound_parts=)) is in core because any spoke with coordinates needs it (GLM node latitude/longitude, CYME). The bound Terminals equalled the stand-in's on IEEE13_CDPSM, IEEE8500 and IEEE9500 unbal before it was deleted.
  • Geometry (S5-8): one wkt cell per equipment, from its Terminal buses in Terminal sequenceNumber order. An ACLineSegment is LINESTRING (x1 y1, x2 y2). Anything else is POINT (x y) at the buses' centroid: the bus itself for a load, capacitor, PV or source, the midpoint for a switch, fuse, regulator or two-terminal transformer. A center-tap transformer has two Terminals (S5-1 above), so it gets the midpoint too.
  • device_geometry (S5-9): DssImporter(..., device_geometry="linestring") (and dss_to_cim) draws every two-terminal equipment as a LINESTRING from bus to bus, like a line: switches, fuses, transformers, regulators, series reactors. Equipment with one Terminal, or three or more, stays a POINT. The default is "point"; any other value raises when the importer is made. It is a keyword, not an environment variable, so a call's output depends only on its arguments.
  • Identity: cimtables' wkt binding names them:
  • Location: <equipment mRID>_loc, unnamed (the engine's <name>_Loc name is dropped with the Location table);
  • PositionPoint: <location>_<n>, sequenceNumber = n, the vertex number from 0 (S5-5 is superseded);
  • CoordinateSystem: crs_bus (BusCoords) or crs_latlong (LatLongCoords), declared first in the file.
  • Order: equipment in the order its first Terminal binds.
  • Values: xPosition/yPosition are strings in CIM. The reader's floats are written by cell (repr), so a line's vertices and a one-Terminal point read back exactly; a centroid is repr of the float mean. For LatLongCoords the reader has already swapped them (x = longitude, y = latitude).
  • Partial coordinates (S5-3): equipment gets a Location only if every one of its Terminal buses has coordinates. The engine writes 0, 0 for a bus without them, which would make a polyline vertex up. The file comment counts what is left out: # not located: <n> of <m> equipment (a terminal bus without coordinates). That case is K1 (644 of 1,285 buses have none), plus IEEE123_PV and the deconfliction deck before the reader fix below.
  • Coordinates for a bus the circuit doesn't have: untranscribed, because the engine ignores them too. The comment lists the count and the first names: # no such bus: 17 (0000500000247160_load, ...). That covers IEEE8500's 17 _load buses, IEEE9500's 8, IEEE13_CDPSM's older copy's tap, and J1's blank-name row.
  • Coordinate system (S5-4): BusCoords → crsUrn=OpenDSSLocalBusCoordinates, the engine's value (a local projection the deck does not name). LatLongCoords → urn:ogc:def:crs:OGC:1.3:CRS84: WGS84 longitude/latitude in x, y order. The engine writes its local URN for both, which loses the fact that the values are degrees.
  • Fail fast: a deck that uses both BusCoords and LatLongCoords raises (none does). A coordinate row that doesn't parse raises with its file and line (the reader fix below).
Buscoords field type samples kind target
name Union[str, BuscoordsName] 611, 632, 190-7361 structural picks the bus: every Terminal on it takes its coordinates; a name the circuit has no bus for is ignored, as in the engine (counted in the file comment)
x Optional[float] 0.0, 200.0, -119.1650904 derived geometry: a line's LINESTRING vertex at each Terminal bus, verbatim; other equipment's POINT at its Terminal buses' centroid (the bus itself for one Terminal)
y Optional[float] 100.0, 250.0, 46.65388888 derived as x
geographic Union[bool, Bool, NoneType] False, True mapped the directive (LatLongCoords -> true) picks the CoordinateSystem: COORDINATE_SYSTEMS

Reader fix (S5-7)

The reader splits a coordinate row only on commas, and it skips any row it can't parse. The IEEE123 family's files are whitespace-separated (1 700 1500), so IEEE123_PV keeps 2 of 216 rows and IEEE123_deconfliction and IEEE123_test_harness keep none, all silently. The engine reads the file with its own command parser, which takes commas or whitespace. The fix: - split on either; - raise on a row whose two coordinates aren't numbers, naming the file and line; - keep J1's blank-name row (its name is '', which is no bus).

A bus listed twice keeps its last row, as in the engine; the reader's dict already does that.

Deck sweep test (S5-6)

tests/test_cimtbl_sweep.py, marked roundtrip, runs every deck under CIMHUB_DSS_DECKS (the 24 in the test_data/models/feeders/OpenDSS layout). Each deck either binds, with its bus voltages equal to the walk's, or stops with the error its row in SWEEP_STOPS names. An unlisted stop fails the test, and so does a listed stop that now binds, so the table stays true. Expected today:

deck stop
EPRI J1, K1, M1; IEEE13_OCHRE DSS-10 (line phases ≠ code nphases)
PNNL IEEE9500 Master-bal-initial-config linecode=3PH_H-4_ACSR4_ACSR4_ACSR4_ACSR is no LineCode, which the engine rejects too
IEEE123_test_harness Battery5 (S4b-6)

So 18 of 24 bind. The other 7 of the throwaway sweep's 31 decks are copies in CIMHub_2_0's private cimhub_opendss/tests/test_models/: IEEE13_CDPSM, IEEE13_assets plus its _geo variant, and the ieee9500 and ieee9500_2025 bal/unbal pairs. They are dropped from the sweep, because their findings are already recorded (the Mode=7 PV, the open of an undefined switch). The per-slice sweep notes above stay as the history; this table is the current one.

Engine checks (S5)

On the atom and every engine deck: - for each line, its PositionPoints equal the engine's coordinates of its Terminals' buses (Circuit.SetActiveBus, Bus.X(), Bus.Y()); for other equipment, its one PositionPoint equals their centroid (S5-8); - every equipment whose buses all have Bus.Coorddefined() has a Location, and no other equipment does.

For IEEE9500 the engine's x is the longitude, which also checks the reader's swap.

Atoms, golden, G7

  • Atoms: atoms/buscoords/:
  • local.dss + CSV: a line, a switch, a center-tap transformer, a regulator, a load, a capacitor and a PV. The CSV has a whitespace row, a bus the circuit doesn't have, a bus listed twice, and one bus left without coordinates.
  • latlong.dss: two buses, by LatLongCoords.
  • local_linestring.cimtbl: local.dss under device_geometry="linestring" (S5-9).
  • Golden: the IEEE13_CDPSM directory (D6) gains buscoords.cimtbl, so it holds 14 files.
  • G7 before S5 (2026-11-08):
deck read map bind
IEEE9500 unbal 4.4 s 1.2 s 6.0 s: 35,747 rows / 58,774 objects, about 6,000 rows/s
IEEE8500 0.6 s 0.4 s 4.9 s: 24,700 rows, about 5,000 rows/s

That was about 400 rows/s before R12 (G7's first measurement), so G7 is closed. Coordinates add about 13,400 points, 6,000-7,000 Locations and as many Update rows to IEEE9500 (the measurement after S5 is under Result).

Decisions for S5 (approved 2026-11-08)

  • S5-1: coordinates go on each piece of equipment's Location (one PositionPoint per Terminal), not on a Junction per bus. The CIM17 form (PositionPoint.Location) stays, not cim18v17's Geometry (the user's review).
  • S5-2: the mapper finds the Terminals on the bound network (CimtblImporter.bound_parts); revised 2026-11-09 from a re-read of the written documents (document_terminals) when CIM-Tables declined U11.
  • S5-3: no Location for equipment with a Terminal bus that has no coordinates; the file comment counts them.
  • S5-4: crsUrn is OpenDSSLocalBusCoordinates for BusCoords and CRS84 for LatLongCoords.
  • S5-5: sequenceNumber is the Terminal number, 1-based.
  • S5-6: the sweep test covers the 24 CIMHUB_DSS_DECKS decks; the 7 CIMHub_2_0 test_models copies are dropped.
  • S5-7: the reader reads whitespace-separated coordinate rows and raises on a row it can't parse.
  • S5-8 (2026-11-10, the user's ask): the coordinates are GIS geometry through cimtables' wkt column: a line is a LINESTRING through its Terminal buses, other equipment one POINT at their centroid (the midpoint for a switch or transformer). It replaces the Location and PositionPoint tables and S5-5's 1-based Terminal numbering; the Location loses its <name>_Loc name. The exporter reads it back by F8 (EXPORT_MAPPING.md).
  • S5-9 (2026-11-10, the user's ask): device_geometry="linestring" draws every two-terminal device bus to bus instead of as a midpoint. The exporter needs nothing new: two points on two Terminals pair one per Terminal, so each bus comes back exactly.

S6g: earth model and reclose sequences (2026-11-09)

Specified with the export in EXPORT_MAPPING.md#s6g-earth-model-and-reclose-sequences. On import: - A deck with geometry gets one EarthResistivity (earth), first in linegeometry.cimtbl, from Set earthmodel and the geometry lines' rho (the engine's Deri and 100 ohm-m when unset, listed). Every WireConfiguration names it. FullCarson, disagreeing rho, and rho on a line without geometry raise. - A deck without geometry that sets earthmodel gets the same EarthResistivity earth, floating: no line names it (# the deck's earthmodel; no line names it), rho the default 100 ohm-m (defaulted: rho=100.0). It keeps the setting for the export's Set earthmodel, so earthmodel no longer differs in the power-flow parity of such decks (IEEE13_CDPSM now has a linegeometry.cimtbl). A deck with neither geometry nor earthmodel gets none (2026-11-24; test_no_geometry_keeps_a_set_earthmodel, test_no_geometry_and_no_earthmodel_has_no_earth). - A Recloser's Shots - 1 reclosures are RecloseSequence rows <switch>_rs<n> in line.cimtbl, at its RecloseIntervals (the engine's defaults filling either, listed). Both given and disagreeing raise, and so does Shots above 4 without intervals.

S8: load shapes (built 2026-11-21 at the user's word)

GLM's S8 (cimhub_gridlabd/docs/CIMTBL_MAPPING.md#s8-load-players) maps a player to the ConformLoadSchedule → ConformLoadGroup ← ConformLoad pattern (the user's call, 2026-11-21: ConformLoad groups, points in a Parquet sidecar). A DSS LoadShape a Load names as yearly is the same thing: one curve of multipliers that scales every load naming it. Mapper importer/cimtbl/loadshape.py, artifact loadshape.cimtbl, shape load_schedule; the loads in load.cimtbl. Atom tests/atoms/loadshape/loadshapes.dss: - an hourly shape with qmult, shared by two loads (res); - a 15-minute shape given as minterval and normalized (com, as K1's action=normalize); - a 900 s shape given as sinterval (ind); - M1's bare mult=1 with no npts (flat), named in another case; - a shape no Load names (pv, as K1's PVSystem irradiance shape); - a load with no shape.

# decision
S8-1 A LoadShape a Load names as yearly is a ConformLoadGroup lg_<name> with one ConformLoadSchedule ls_<name> (lowercased); each Load naming it is a ConformLoad whose LoadGroup is the group, its p and q as for any load. Only yearly: a ConformLoad has one group, and every load in the sweep names only yearly (M1, K1, J1). daily and duty are untranscribed (listed on the row)
S8-2 Multipliers: value1 = mult, value1Unit none; value2 = qmult (value2Unit none) when given, else unset: Q follows mult, the engine's rule (engine-checked). action=normalize divides each array by its largest magnitude, as the engine does; an array assigned after it raises (the engine normalizes only what came before)
S8-3 Time: timeStep = the interval slot the deck assigned last (the engine's rule), copied in its unit (interval h, minterval min, sinterval s), one schedule table per unit; none gives the engine's 1 h. DSS has no date: sample k (from 1) is in force from k × interval (engine-checked: yearly mode, hour 1 gives sample 1), so startTime = 2020-01-01T00:00Z (ditto's epoch) + one interval (cimhub_gdm TIMESERIES_NEEDS.md X2). The engine wraps a shape around; CIM has no repeat, so the wrap is lost (X4)
S8-4 Points: RegularTimePoint rows in the Parquet sidecar (cimhub_core.time_points), as GLM's: DssImporter(time_points={}) / dss_to_cim(..., time_points=) fills the caller's dict; without it the points are dropped with one warning
S8-5 npts unset: the engine reads none of mult, inline or from a file (engine-checked with DSS C-API 0.14.5: Npts 0, the load constant), so the group has no schedule, its name kept, as GLM's undefined player (M1's five mult=1 shapes). npts set must equal the number of values
S8-6 UseActual=Yes raises: a Load naming it takes the shape's peak as its kW and kvar, or keeps its own, depending on whether yearly= comes after kW= (engine-checked), which the record does not keep. So no DSS form maps a NonConformLoad yet, either way
S8-7 A shape no Load names as yearly is not a group: one a PVSystem, Storage or Generator names is that device's schedule (S9); one nothing names (a Vsource's, an unused irradiance shape) is not mapped and not checked, and the master's comment counts it (not mapped: Loadshape 1)

What raises: - UseActual=Yes; - hour, csvfile, sngfile, dblfile, PQCSVFile, Pmult, Pbase, Qbase set (no deck sets them); - an interval of 0 (an hour array); - npts other than the number of mult values, qmult of another length, no mult; - an array assigned after action=normalize, or an action other than normalize, DblSave, SngSave; - a Load whose yearly names no shape of the deck.

Engine checks. test_cimtbl_loadshape.py compiles the atom and reads each shape's PMult, QMult and HrInterval from the engine, against the mapper's values (the normalized com included, and flat's 0 points). test_export_loadshape.py runs the original atom and its export in yearly mode every 5 minutes for 6 hours, every load's power equal at every step (rel 1e-9).

Not mapped: an Hour-array shape and a file the reader does not read (csvfile=, ...). A mult=(file=...) with no npts is S8-5's case too: the engine reads no points from the file either (engine-checked).

LoadShape fields

Loadshape field type samples kind target
name Union[str, LoadshapeName] com, flat, ind copied ConformLoadGroup.name, ConformLoadSchedule.name; mRID = lg_ / ls_ + name, lowercased
npts Optional[int] 4, 3, 2 structural the number of points the engine reads: unset, none of mult (inline or from a file; engine-checked), so the group has no schedule; else it must equal the number of mult values
interval Optional[float] 1.0 copied ConformLoadSchedule.timeStep (h); the interval slot the deck assigned last (the engine's rule); 0 (an hour array) raises; none: 1 h
mult Union[float, list[float], NoneType] [2.0, 4.0, 8.0, 6.0], [1.0], [1.0, 0.9, 0.95] copied RegularTimePoint.value1; the points, in the Parquet sidecar (S8-4); action=normalize divides them by their peak
hour Union[float, list[float], NoneType] structural raises when set: no deck in the sweep sets it, so a mapping waits for one (an irregular shape has no RegularIntervalSchedule)
mean Optional[float] untranscribed a Monte Carlo statistic; the engine computes it from mult
stddev Optional[float] untranscribed a Monte Carlo statistic; the engine computes it from mult
csvfile Optional[str] structural raises when set: no deck in the sweep sets it, so a mapping waits for one (the reader reads mult=(file=...))
sngfile Optional[str] structural raises when set: no deck in the sweep sets it, so a mapping waits for one (the reader reads mult=(file=...))
dblfile Optional[str] structural raises when set: no deck in the sweep sets it, so a mapping waits for one (the reader reads mult=(file=...))
action Optional[str] normalize derived normalize: mult and qmult each divided by its largest magnitude, as the engine does (one assigned after it raises); DblSave, SngSave write files and are untranscribed; others raise. Every action assigned counts (each acts when assigned), not only the last
qmult Union[float, list[float], NoneType] [0.4, 0.6, 0.9, 0.7] copied RegularTimePoint.value2; in the sidecar; unset: Q follows mult (the engine's rule), value2 unset
UseActual Union[bool, Bool, NoneType] structural Yes raises: a Load naming it takes the shape's peak as its kW, or keeps its own, by command order, which the record does not keep (engine-checked); default No
Pmax Optional[float] untranscribed used only with UseActual
Qmax Optional[float] untranscribed used only with UseActual
sinterval Optional[float] 900 copied ConformLoadSchedule.timeStep (s); the interval slot the deck assigned last (the engine's rule); 0 (an hour array) raises; none: 1 h
minterval Optional[float] 15 copied ConformLoadSchedule.timeStep (min); the interval slot the deck assigned last (the engine's rule); 0 (an hour array) raises; none: 1 h
Pbase Optional[float] structural raises when set: no deck in the sweep sets it, so a mapping waits for one (a normalize base)
Qbase Optional[float] structural raises when set: no deck in the sweep sets it, so a mapping waits for one (a normalize base)
Pmult Union[float, list[float], NoneType] structural raises when set: no deck in the sweep sets it, so a mapping waits for one (a synonym of mult)
PQCSVFile Optional[str] structural raises when set: no deck in the sweep sets it, so a mapping waits for one (the reader reads mult=(file=...))
MemoryMapping Union[bool, Bool, NoneType] untranscribed how the engine stores the points
Mode Optional[float] untranscribed generator dispatch; no effect on a Load
Interpolation Optional[str] untranscribed AVG and EDGE agree at the solution steps, which are on the interval grid (TIMESERIES_NEEDS.md X3)
like Optional[str] untranscribed the reader resolves like= before mapping

S9: device shapes (built 2026-11-21 at the user's word: "shapes for PV, storage, etc using the nc_schedule profile classes")

A yearly LoadShape on a PVSystem, Storage or Generator drives that one device's output, which the engine computes from the shape and the device's own settings (irradiance, kWrated, kW). So it is nc_schedule's per-device EnergyConnectionSchedule on the device's PowerElectronicsConnection or SynchronousMachine, its points the device's p and q at each sample as EnergyConnectionTimePoint rows in the Parquet sidecar (TIME_POINT_SCHEMA, as GDM's T1 schedules), not a load group. The user chose this over a PowerSchedule on the unit (2026-11-21). Mappers: pvsystem.py, storage.py, generator.py (schedule_points; the schedule row in their own document), with loadshape.py's device_shape, point_times and device_schedules. Atom tests/atoms/loadshape/devices.dss: - sun (30 min) on two PVs: p1 by pf with %Cutin = %Cutout = 10, off at both ends; p2 by kvar, cut to fit its kVA at the peak, off with its kvar kept at both ends; - run (hourly) on a model 1 generator by pf, down to 0; - cycle (hourly) on a follow-mode battery that discharges, charges, idles, and is capped at kVA; - a PV and a load with no shape.

# decision
S9-1 A device's yearly shape is an EnergyConnectionSchedule <connection mRID>_yearly, named after the shape, timeSeriesKind schedule, interpolationKind previous (a sample holds until the next), on the device's EnergyConnection. One per device: devices sharing a shape each get their own, as their outputs differ (a PV's cap). Only yearly, as for loads (S8-1): daily, duty, Tyearly.. are untranscribed. The snapshot p, q are the deck's, as before
S9-2 Times: sample k (from 1) at the epoch 2020-01-01T00:00Z + k intervals, the instant it is in force (S8-3's rule, engine-checked here per device). The wrap is lost (X4)
S9-3 Generator: p = -kW x mult, q = -kvar x mult (engine-checked: the engine scales kvar with kW, pf or kvar alike); a model 3 machine's schedule carries p only (its q is its control's). A shape with dispmode other than Default, dispvalue above 0 or status=Fixed raises (the engine then dispatches by load level, price, or not at all)
S9-4 PVSystem: each sample is pv_power at irradiance x mult (engine-checked: the shape scales the irradiance, so %Pmpp, %Cutout and the kVA cut apply per sample). A sample whose panel power lies between %Cutout and %Cutin raises: the engine keeps the inverter on or off as it was (hysteresis, engine-checked), which depends on the samples before and on a snapshot solved first
S9-5 An inverter that is off still gives a set kvar unless VarFollowInverter (engine-checked, snapshot and yearly alike): pv_power now keeps it. This changes no golden: no atom or sweep deck has an off PV with a kvar
S9-6 Storage: only DispMode=follow with a yearly shape (engine-checked: discharge at mult x kWrated for mult > 0, charge at -mult x kWrated below 0, idle at 0 with the idling loss, capped at kVA; %Charge, %Discharge and %kWrated have no effect); p only. It is the dispatch asked for: a battery that fills or reaches its reserve idles in the engine, which the schedule does not model (the export's deck idles it too, so a round trip agrees). A follow-mode battery with a kW or State raises (the engine's snapshot of one is not that of battery_dispatch); one with neither idles, as the importer has it. A yearly shape in the default (trigger) mode, or follow mode without a shape, raises
S9-7 A shape with qmult raises on a device: its output is scaled by mult alone. A shape with no npts is no schedule (S8-5); a yearly naming no shape raises
S9-8 Points: DssImporter(time_points={}) fills the EnergyConnectionTimePoint table beside the RegularTimePoint one (time_points.add_device_time_points, CIM-Builder's builder converting kW, kVAr to SI); without it they are dropped with the one warning of S8-4

What raises: a sample between %Cutout and %Cutin; a generator shape off Default dispatch; a storage shape off follow mode, follow mode with no shape, with a kW or with a State; a qmult on a device's shape; a yearly naming no shape.

Engine checks. test_cimtbl_device_shape.py runs the atom in yearly mode at each shape's own interval and compares every device's kW and kvar at every sample with the schedule's points (rel 1e-6, a tight solver tolerance). test_export_device_shape.py runs the original atom and its export every 30 minutes for 8 hours, every device's power equal at every step.

Not mapped: daily and duty shapes; a temperature shape (it acts only through a P-TCurve, which raises); a shape on a Vsource; a battery's trigger dispatch modes.