cim18v17 → OpenDSS export spec¶
Plan and decisions: .development/DSS_REWRITE_PLAN.md §8 (E1-E10, approved 2026-11-09). One section per
sub-slice, each approved before its code (DSS-12). The exporter reads values only through the core getters (skill
export-getters). The DssModel it returns has the shape DssReader.read_all() returns, so the writer's deck reads
back through the reader and the importer.
S6a: framework, writer, Vsource (spec approved 2026-11-09; done 2026-11-09)¶
Layout¶
cimhub_opendss/src/cimhub_opendss/exporter/
cim_to_dss.py DssExporter(FormatExporter), EXPORT_ORDER, cim_to_dss(network, destination, **opts)
naming.py Names: the E1 switch + dss_safe_name (kept in the writer) + the per-namespace collision check
buses.py bus_ref(node, phases, names) -> "650.1.2.3" (E7)
options.py the Options record: circuit, defaultbasefreq, voltagebases (E10)
(Slot, check_slots, slots_table: cimhub_core/export_slots.py, shared with the RAW exporter)
vsource.py EnergySource -> Vsource (one module per DSS class from here on)
DssExporter().to_model(network, *, name_source=None, circuit_source="source", switch_state="actual") -> DssModel. It runs each module ofEXPORT_ORDERover its CIM classes and adds the records.historystays empty: it is a reader artifact.- Each module has
export(context) -> list[record]andSLOTS, which names each slot of its DSS class aswritten(from which getter),rule(a CIMNoneDSS needs, E4),unset(CIM cannot hold it; engine default) ornot mapped. A test checks thatSLOTScovers every schema slot, ascheck_fieldsdoes on import, and the tables below are generated from it. context(ExportContext) holds the network, theNames, the circuit's EnergySource and theswitch_state. Nothing else is shared between modules.- Conducting equipment of a class no module exports raises, with the counts (
no DSS export yet for {'ACLineSegment': 1, ...}), so nothing is dropped silently while the sub-slices land. - Values the exporter cannot read through an existing getter got one:
getters/in_service.get_in_service(equipment, which='actual'|'normal')(unset is None), the pattern ofget_switch_state. DSSenabledreads'normal', the importer'snormallyInService.
Names (E1)¶
- Core,
cimhub_core/names.py: NAME_SOURCES = ("name", "mrid", "uri")andNAME_SOURCE_ENV = "CIMHUB_NAME_SOURCE";resolve_name_source(source): the argument, else the env var, else"mrid". Any other value raises;export_name(obj, source) -> str:obj.name,obj.mRIDorobj.uri()(the stable UUID: fixed length, which GridLAB-D's name-reference limit needs). Unset or blank raises, naming the class and mRID.
Every exporter (GLM, RAW, ...) uses the same three.
- Spoke, exporter/naming.py, Names(source):
- name(obj, dss_class) returns dss_safe_name(export_name(obj, source)) (the writer's sanitizer, which stays in
the writer: it sanitizes every name it writes, idempotently). bus(node) also replaces ., DSS's node
delimiter.
- It records the name per DSS class, lowercased. A second object on the same name raises, naming both mRIDs.
Buses (ConnectivityNodes) are one namespace of their own.
- The circuit:
- Its name is the one Feeder's, by the same switch. Several Feeders are one circuit (one deck per substation)
when every one has the same NormalEnergizingSubstation, and the Substation names it. No Feeder, or several
without one Substation, raises. Among several, a Feeder that contains no equipment is not counted (H2).
- Its source's Vsource is always named source, whatever the switch: that is DSS's name for New Circuit's
source (the reader's rule).
- The circuit source is the only EnergySource, or the one whose exported name is circuit_source (E2). Several
EnergySources and no match raises.
- E8's per-phase objects are named <name>_<phase> (lowercase phase, ld_x_a) through the same check.
Bus references (E7, S6a part)¶
bus_ref(terminal, names) returns <bus>.<n>...:
- the bus is names.bus(get_terminal_nodes(eq)[i]);
- the nodes are get_terminal_phases in conductor order, A/B/C → 1/2/3 and s1/s2 → 1/2;
- a blank (balanced) PhaseCode is ABC, written .1.2.3, never bare.
S6a needs only phase conductors (Vsource). The neutral cases (.0, .4, Rneut) arrive with the windings in S6c,
and an N before then raises.
Options (E10)¶
One Options(name="options", circuit=..., defaultbasefreq=..., voltagebases=[...]) record:
- defaultbasefreq = network.base_frequency in Hz;
- voltagebases = the distinct BaseVoltage.nominalVoltage values in kV, sorted ascending. Since 2026-11-24 the
importer keeps a deck's voltagebases on no bus as BaseVoltages too, so these are the deck's bases back, which the
engine's CalcVoltageBases snaps bus bases to;
- earthmodel the WireConfigurations' one EarthResistivity model (options.earth_model, S6g). With no geometry at
all, the network's one EarthResistivity, which no line names (the importer keeps a deck's Set earthmodel that
way, 2026-11-24). None -> not set;
- open_terminals filled by S6b's switches.
network.base_frequency follows the graph's BaseFrequency (U14, closed 2026-11-09 in CIM-Graph), so a 50 Hz
model writes defaultbasefreq=50. An atom at 50 Hz pins it.
Vsource¶
One Vsource per EnergySource, through get_source(es, angle_unit="deg", voltage_unit="kV",
impedance_unit="ohm"). The impedance form depends on the phases (found in implementation, engine-checked):
- 3-phase: the ohms group R1 X1 R0 X0, the importer's copied form.
- 1-phase: the engine forces Z0 = Z1 when a 1-phase source is given ohms, so its single impedance is Z1. Given
MVAsc it is (2 Z1 + Z0) / 3. The importer reads a 1-phase source's MVAsc into Z1 and Z0, so the exporter writes
the MVAsc group back: MVAsc3 = kV²/abs(Z1), MVAsc1 = 3 kV²/abs(2 Z1 + Z0), x1r1 = X1/R1, x0r0 = X0/R0.
short_circuit_from_thevenin is the exact inverse of the importer's thevenin_from_short_circuit (tested to
1e-12). A zero r or r0 raises. The atom single_phase showed this: its ohms export had another YPrim.
| DSS slot | kind | from / why |
|---|---|---|
| name | written | Names; the circuit's source is always source |
| bus1 | written | bus_ref(get_terminal_nodes, get_source.phases) |
| basekv | written | get_source.nominal_u (kV) |
| pu | written | get_source.magnitude_pu |
| angle | rule | get_source.angle (deg); unset -> 0, the reference angle |
| phases | written | the phase conductors: 3 or 1, any other count raises |
| R1 | written | 3-phase: get_source.impedance.r (ohm); r, x, r0, x0 unset raises (DSS takes one group) |
| X1 | written | 3-phase: get_source.impedance.x (ohm) |
| R0 | written | 3-phase: get_source.impedance.r0 (ohm) |
| X0 | written | 3-phase: get_source.impedance.x0 (ohm) |
| MVAsc3 | written | 1-phase: kV^2 / abs(Z1) (short_circuit_from_thevenin) |
| MVAsc1 | written | 1-phase: 3 kV^2 / abs(2 Z1 + Z0) |
| x1r1 | written | 1-phase: x / r; r = 0 raises |
| x0r0 | written | 1-phase: x0 / r0; r0 = 0 raises |
| enabled | written | get_in_service(which='normal'); unset -> not written |
| Isc3 | not mapped | not written: the ohms or the MVAsc group carries the same impedance |
| Isc1 | not mapped | not written: the ohms or the MVAsc group carries the same impedance |
| Z1 | not mapped | not written: the ohms or the MVAsc group carries the same impedance |
| Z0 | not mapped | not written: the ohms or the MVAsc group carries the same impedance |
| Z2 | not mapped | r2/x2 set and different from r/x raises: the Z2 group is not mapped (nor imported) |
| puZ1 | not mapped | not written: the ohms or the MVAsc group carries the same impedance |
| puZ0 | not mapped | not written: the ohms or the MVAsc group carries the same impedance |
| puZ2 | not mapped | not written: the ohms or the MVAsc group carries the same impedance |
| baseMVA | not mapped | not written: the ohms or the MVAsc group carries the same impedance |
| frequency | unset | Options.defaultbasefreq is the deck's |
| basefreq | unset | Options.defaultbasefreq is the deck's |
| ScanType | unset | not in CIM (untranscribed on import) |
| Sequence | unset | not in CIM (untranscribed on import) |
| spectrum | unset | not in CIM (untranscribed on import) |
| Yearly | unset | not in CIM (untranscribed on import) |
| Daily | unset | not in CIM (untranscribed on import) |
| Duty | unset | not in CIM (untranscribed on import) |
| Model | unset | not in CIM (untranscribed on import) |
| puZideal | unset | not in CIM (untranscribed on import) |
| bus2 | not mapped | an EnergySource has one terminal |
| like | not mapped | the writer never writes like= |
Writer changes (§8.2)¶
WRITE_ORDER: a class-level list of the DSS classes in definition order. Catalogs (WireData, CNData, TSData, LineSpacing, LineGeometry, LineCode, XfmrCode), Vsource, Line, Fuse, Recloser, SwtControl, Transformer, RegControl, Load, Capacitor, CapControl, PVSystem, Storage, Generator, Reactor. A class in the model that is not on the list raises.write(model, destination)emits, in order:Clear;Set defaultbasefreq=<f>;New Circuit.<circuit>with the slots ofVsource.source;- the records in
WRITE_ORDER(Vsource.sourcenot again); Set voltagebases=[...];CalcVoltageBases;Open <Class>.<name> <terminal>peropen_terminals;Buscoords <stem>_buscoords.csv(LatLongCoordsfor geographic rows), with the CSV written beside the deck.serialize(obj)is unchanged for an ordinary record.OptionsandBuscoordsare not ordinary records, soserializeraises on them, andwritehandles them as above.write(model, destination, per_class=True)(alsocim_to_dss(..., per_class=True)) writes step 4 as one file per class beside the deck (linecode.dss,xfmrcode.dss,line.dss, ...; only classes that have records), and the masterdestinationhasRedirect <file>inWRITE_ORDERin its place. A master named like a class file (Line.dss) raises rather than being overwritten. The default is the single deck.
Found by the round-trip test (atoms and the IEEE13_CDPSM, IEEE123, IEEE4 OYOD decks; each is engine-checked):
- like= is never written. The reader has already copied the other object's values into the record. like=
written after them (schema order) copied reg4a back over IEEE123's reg4b/reg4c (buses, R, X).
- Some slots go first (_LEADING_SLOTS): XfmrCode, linecode, geometry, spacing, phases, Switch. A
template set after buses= re-sizes the windings and resets their buses (IEEE13 Tpoletop's third winding
became tpoletop_3), and Switch=y sets r1=1, x1=1, .... phases goes before Switch, as the decks write it:
the engine's recalculation of a switch line at CalcVoltageBases depends on that order (IEEE13 Sect1).
- Per-winding slots with no array form go last (_PER_WINDING_SLOTS: RdcOhms, 2026-11-24): one
wdg=n RdcOhms=v block per winding, after every other slot, so no other per-winding slot follows a wdg= they
move.
- A LineGeometry with positions is written as cond= blocks, each naming its conductor's kind (wire,
cncable, tscable) from the catalog that defines the name. The reader folds the blocks into
wires/xs/hs (mixed kinds into one cond-ordered wires list) and leaves the last block in the cursor slots.
Only blocks can mix kinds (IEEE13_Assets 607: a TS phase and a bare neutral). serialize raises on one, because
the kinds need the model's catalogs.
- Set earthmodel goes after New Circuit: the engine refuses it before. defaultbasefreq stays before.
- Matrices at full precision; .6g changed every value past 6 digits. Since S6b every float is written at 15
significant digits (FLOAT_DIGITS, see S6b's goldens note).
- A deck without a circuit (a catalog fragment, which the reader also reads) is written without one. Only one
of Options.circuit and Vsource.source raises.
- Relay joins WRITE_ORDER after Line (IEEE13_CDPSM has one).
Tests¶
- Writer round trip (
tests/test_dss_writer.py): every atom deck, plus IEEE13_CDPSM, IEEE123 and IEEE4 OYOD, is read, written and read again, and gives equal records (likedropped;historyexcluded). The three decks are also compared in the engine (tests/engine_compare.py, shared by every export test): - per element, its buses (bus names and
NodeOrder) and YPrim (rel 1e-9); - the node voltages, solved with
controlmode=off tolerance=1e-10(rel 1e-8 + 10 µV). Solution settings are not part of the model, so the reader drops them; the tight tolerance makes both decks converge to one answer. - the three decks are also written
per_classand checked the same way (records and engine). - Names: core precedence (argument > env var >
mrid), a bad value raises, an unset name raises,uriis 36 characters. Spoke: sanitizing, dots in bus names, a collision after sanitizing raises, namespaces are separate, the per-phase suffix. - Framework: options, unexported equipment raises, and
circuit_sourcewith two sources (its collision with the other source's own namesourceraises undername). - Vsource per atom (
mvasc,ohms,isc,defaults,single_phase, and a newfifty_hz), each exported and compared with the original in the engine: - under
name: the source's R1 X1 R0 X0 basekv pu angle phases (rel 1e-9), every element's YPrim, the voltages; - under
mridanduri: the voltages, with the buses renamed underuri. - Goldens:
tests/atoms/vsource/export/<atom>.dss(name_source="mrid").
S6b: lines, wire catalogs, switches (spec approved 2026-11-09 with B3 and B6 amended; done 2026-11-09)¶
Content: WireData/CNData/TSData, LineGeometry, LineCode, Line, and switches (a Switch=y Line plus a Fuse, Recloser
or SwtControl, and Open), with the line ratings. Plan §8.1 row S6b; E3, E5, E6 and E7 apply. Decisions B1-B6
are at the end of this section.
Layout¶
cimhub_opendss/src/cimhub_opendss/exporter/
wire.py OverheadWireInfo and CableInfo / ConcentricNeutralCableInfo / TapeShieldCableInfo -> Wiredata / Cndata / Tsdata
linecode.py PerLengthPhaseImpedance / PerLengthSequenceImpedance -> Linecode
linegeometry.py (WireConfiguration, ySpacingOffset) and spacing lines -> Linegeometry, inline positions (B2)
line.py ACLineSegment -> Line
switch.py Switch subclasses -> Line Switch=y + Fuse / Recloser / Swtcontrol; open_terminals()
EXPORT_ORDER becomes (vsource, wire, linecode, linegeometry, line, switch). The writer's WRITE_ORDER already
puts catalogs before lines and controls after them. options_record fills open_terminals from
switch.open_terminals(context).
Framework change (found in implementation):
- A module exports from the whole network. Its protocol is now export(context) -> list[record], not
export(obj, context), because a LineGeometry is one record per (configuration, offset) among the lines.
ExportContext.objects(*classes) lists a module's CIM objects.
- SLOTS is {DSS class: {slot: Slot}}, for the modules that write several classes (wire, switch).
test_export_framework.test_slots_are_complete checks every module in EXPORT_ORDER.
- A record shared by several objects (a code, a wire, a geometry) is named through one function: wire_name,
linecode_name, geometry_name or switch_name. Names gives an object the same name again, so a Line names
its LineCode exactly as the LineCode record does.
New getters and derived functions (core)¶
getters/wire.py-
get_wire_info(wire, length_unit="m", resistance_unit="ohm/m", current_unit="A") -> WireValues. It readsrDC20,rAC25,rAC50,gmrandradius, and the ratings:ratedCurrent, and theCurrentLimitsof the wire'sAssetInfo.OperationalLimitSet(normal, emergency).ratedCurrentand a normal limit that are both set must agree. A cable also getscable: CableValues:insulationThickness, and the diameters over insulation, jacket, neutral and screen;- CN:
neutralStrandCount,neutralStrandRadius,neutralStrandGmr,neutralStrandRDC20; - TS:
tapeThickness,tapeLap.
Unset is None. Any other WireInfo subclass raises. Only rAC25 (the DSS importer's) and rAC50 (the GLM importer's) are read; a set
rAC75raises until a producer writes one. -get_configuration_wires(configuration) -> tuple[(sequence_number, WireInfo), ...]. These are theWireSequenceConfigurations in sequence-number order. A repeated or missing number raises. -getters/line_impedance.py, code-level getters (B5):get_phase_impedance_code(code, impedance_unit, admittance_unit) -> CodeMatrix(conductor_count, r, x, b, g)andget_sequence_impedance_code(code, ...) -> SequenceImpedance. They read a catalog object on its own, so a code no line uses is still exported. The line phase-matrix getter shares their reading (_matrix_values), with no change in behaviour. -derived/capacitance.py(E5, closes the G3 open point):c_from_b(b, frequency)= b / (2 pi f), with b in nS and f in Hz giving C in nF. Its inverseb_from_cmoved here from the importer'slinecode.py. The units go with the values: the caller reads b withget_qtyinnS/mand gets nF/m. Found in implementation: E5'scim.Capacitance(...).to('nF')gives 0.9999999999999999 nF for 1e-9 F, so the conversion is left toget_qty. -getters/current_limits.py:get_asset_info_current_limits(info)reads a catalog's limits through the same code asget_current_limits.AssetInfo.OperationalLimitSetis single-valued (one set), unlikeEquipment.OperationalLimitSet.
Units (B1)¶
Every length goes into the deck in metres:
- Line units=m, LineCode units=m;
- LineGeometry position units=m;
- WireData/CNData/TSData Runits=m GMRunits=m radunits=m.
Each value is read with get_qty in its metre-based unit (ohm/m, nF/m, m). CIM keeps no record of the
deck's own units, and one fixed unit makes a second export the same text (S6f idempotence).
Wire catalogs¶
One record per WireInfo in the network, used or not (E3). The three DSS classes share one name namespace (wire):
a LineGeometry's conductor list names a wire without saying its catalog, so the writer's _conductor_kinds needs
each name in only one catalog. A plain CableInfo (no neutral or shield) is a WireData, its insulation unmodelled (B7).
| DSS slot | from |
|---|---|
| Rdc / Rac | rDC20 / rAC25, else rAC50 (ohm/m). DSS has one Rac, labelled 25 C, so rAC25 wins when both are set; a GridLAB-D-imported wire has only rAC50 (decision 11). Each is written when set; all unset raises. Rac unset is the engine's 1.02 x Rdc, the importer's rule inverted |
| GMRac | gmr (m). Unset is left unset, and the engine takes 0.7788 x radius (E4) |
| radius | radius (m), required. diam is never written |
| normamps / emergamps | the wire's normal / emergency limit, else ratedCurrent for normamps. emergamps unset is left unset: the engine's 1.5 x normamps |
CN k, DiaStrand, GmrStrand, Rstrand |
neutralStrandCount, 2 x neutralStrandRadius, neutralStrandGmr, neutralStrandRDC20 |
CN DiaCable |
diameterOverNeutral, which the engine uses as the circle of the strands. Unset raises. The importer writes the jacket diameter equal to it |
TS DiaShield |
diameterOverScreen + 2 x tapeThickness (the importer's screen_diameter inverted) |
TS TapeLayer, TapeLap |
tapeThickness, tapeLap |
InsLayer, DiaIns |
insulationThickness, diameterOverInsulation |
TS DiaCable |
diameterOverJacket |
EpsR, Capradius, SemiconLayer, Seasons, Ratings |
unset: not in CIM (the importer's untranscribed or raising fields) |
LineCode¶
One record per template PerLengthImpedance in the network (E3): isTemplate true or unset (unset is the CIM default for a code no producer marked). One with isTemplate=false is a line's own impedance and is written inline on its Line (skill wire-configuration). baseFreq is network.base_frequency. A code whose
calculatedFrequency is set and differs from it raises: C is computed at the deck's frequency.
- Phase code:
- nphases = conductorCount;
- rmatrix / xmatrix = r / x as lower triangles (ohm/m);
- cmatrix = C from b (nF/m). An unset b gives zeros, so the engine's 3.4/1.6 nF default never applies (rule 8).
- Sequence code:
- nphases = 3;
- r1, x1, r0, x0 (ohm/m). An unset r0 or x0 raises: DSS would take its own default;
- C1, C0 from bch, b0ch. Unset gives 0.
The importer stores 1- and 2-phase sequence codes as phase matrices (DSS-4), so they come back as matrix codes.
A line with other than 3 phases on a sequence code raises (DSS-10's mismatch, from the CIM side).
- Raises:
- g, gch or g0ch set and nonzero (DSS lines have no shunt conductance);
- rg/xg set (not mapped on import either);
- a matrix entry with a neutral row: a code-line neutral needs LineCode Kron/neutral, and no producer writes one.
- Not written: normamps and emergamps (no home on PerLengthImpedance, D9), which come from the Line instead.
The reliability, Kron, neutral and Seasons slots stay unset.
LineGeometry (B2)¶
- One record per (WireConfiguration, ySpacingOffset) among the lines (E3). It is named
<configuration>at offset unset or 0, and<configuration>_<offset>motherwise (offset in m rounded to the mm,.written asp:10p363m). Two offsets of one configuration that round to one name raise. - A WireConfiguration no line uses is written once, offset 0 (the CIM default), on the positions of its spacing
that its own WireSequenceConfigurations name: a template spacing may hold several circuits, each its own
configuration (the double circuit's two, one of them unused in a feeder exported alone). A configured sequence
number with no position raises. One with a PerLengthImpedance and no WireSpacing is a template LineCode, not geometry: LineCode writes
its code, and it has no earth (
options.earth_modelskips it). - A spacing line (the EPRI line shape:
ACLineSegment.WireSpacing, no WireConfiguration, a WireInfo on every ACLineSegmentPhase) gets one record per (spacing, ySpacingOffset, conductors), the conductors being each phase's sequence number, WireInfo and whether it is N. It is named<line>_geometryafter the first line that has it. The spacing may hold several circuits (a double circuit, a secondary bundle under a primary): the line takes the positions of its own phases' sequence numbers.circuitNumberis not read, since cim18v17 says a line's need not match its positions'. Lines of oneMultiCircuitGroupat its highest voltage are coupled instead when two or more are in the network (H1, S6h). - Positions:
get_line_conductor_xy(line), orget_spacing_xyon its own sequence numbers for an unused configuration, in m: phase conductors, then neutrals. A bundle (RegularBundlePositiontriplex,BundlePositionquadruplex) is expanded into its sub-conductors. They are written asxs/hswith the conductor names inwires, and the writer emits the cond blocks;- the wires are matched to positions by sequence number from
get_configuration_wires, or a spacing line'sget_line_phase_wires; - a plain CableInfo below grade is written at the same height above it (B7): DSS takes a WireData only above grade.
- The other slots:
- nconds = the positions;
- nphases =
numberOfPhases(required), or a spacing line's phases other than N. Position kinds, where set, must bephasefor 1..nphases andneutralafter; reduce=y: the neutrals are Kron-reduced, i.e. grounded at both ends, as the impedance getters assume (G2; 242 of 243 sweep geometries set it). The import leftreduceuntranscribed for that reason.- The earth of a spacing line. cim18v17 associates an EarthResistivity only with a WireConfiguration or a
PerLengthImpedance, so a spacing line takes the network's one EarthResistivity (
get_network_earth) for itsrhoand the deck's earthmodel. None or several raise. - Raises:
- a spacing line with a phase without a WireInfo, or a phase whose sequence number its spacing has no conductor for; a line with both a WireConfiguration and a phase WireInfo;
- a phase count on the line other than nphases.
- The importer's spacing sharing. The importer shares
spc_500among 601, 602, ...; each geometry now carries its own positions, so a re-import giveswc_<name>_spcper geometry. That is a listed difference, equal in the engine.
Line¶
One record per ACLineSegment (a Switch is not an ACLineSegment; switch.py).
| DSS slot | from |
|---|---|
| bus1 / bus2 | bus_ref over get_terminal_nodes, with the phase conductors of get_conductor_phases in order (645 CB is .3.2). The neutral is not on the bus: it is reduced (B4) |
| phases | the phase conductors' count |
| linecode / geometry | the code's name, or the (configuration, offset) geometry's name, or a spacing line's <line>_geometry. Geometry is a WireConfiguration that names a WireSpacing (get_line_geometry); the code is the line's own PerLengthImpedance or its WireConfiguration's, a template LineCode (get_line_code, DSS-14). Geometry wins when both are set (skill conductor-geometry) |
| rho | the configuration's EarthResistivity, or a spacing line's network EarthResistivity (ohm-m) |
| length, units | required_qty(line, "length", "m"), units=m |
| normamps / emergamps | get_current_limits(line) normal / emergency. Unset is left unset, and the engine copies the code's or geometry's. short_term and seasonal limits are not mapped |
| enabled | get_in_service(which="normal"); unset is not written |
- A lumped-only line (B6, the user's rule):
r/xon the segment and no template. It is written inline: r1 x1 r0 x0= the whole-line values divided by the length, in ohm/km "for better decimal places";C1 C0frombch/b0chthe same way (nF/km);lengthin km withunits=km. A line with no length getslength=1, so the per-km values are the whole-line values. A length of 0 raises: a DSS line's impedance is per length, and the engine cannot solve a zero-length line (probe 2026-11-24:Matrix Inversion Error).
The values come from get_line_sequence_impedance(line, "ohm") (LUMPED). An unset b is C = 0 (rule 8). An
unset r0/x0 raises, as on a sequence code. A set and nonzero gch/g0ch raises.
- A line's own impedance (isTemplate=false, the importer's ln_<line>_lc, DSS-14) is written inline on the
Line, per metre as a LineCode writes it (linecode.code_slots): r1 x1 r0 x0 C1 C0 or rmatrix xmatrix cmatrix.
So a deck's inline line comes back inline. One that two lines use raises: isTemplate=false marks one line's own.
Switches (E6)¶
One Line with Switch=y per Switch subclass:
- bus1/bus2 and phases as a Line; a blank PhaseCode is .1.2.3;
- an open tie between laterals on different phases (terminals B and C, SwitchPhase.phaseSide1 B →
phaseSide2 C, the GLM importer's S6-9) is written side by side from get_switch_sides: bus1=<a>.2 bus2=<b>.3.
The pairs go in side 1's PhaseCode order. A tie that is closed in either state raises, because closed it would
join two phases. So do SwitchPhases that don't pair exactly the two terminals' conductors;
- normamps/emergamps from get_current_limits (the importer writes none);
- enabled;
- a small invented impedance (B3, the user's rule), because CIM has none (DSS-8): r1=1e-3 r0=1e-3 x1=0 x0=0 C1=0
C0=0 length=1 units=m, i.e. 1 mOhm. 1e-3 Ohm is the old exporter's zero-impedance floor (_zero_impedance.py),
and it is resistive only, as the IEEE decks write their switches. The slots come after Switch=y
(_LEADING_SLOTS), so they replace the engine's Switch=y defaults. It is one constant, SWITCH_IMPEDANCE, in
switch.py.
The control depends on the class:
- Fuse: Fuse.<name> MonitoredObj=Line.<name> RatedCurrent=<ratedCurrent A>. Its Normal/State are written
one value per phase ([open open open]). Engine finding: the engine sets a fuse phase by phase, so
State=open on a 3-phase line opens phase 1 only (atom states, first draft: n1.1 at 75 V, n1.2 and n1.3 at
2402 V). Importer fix: a Fuse whose Normal/State give a value count other than its line's phases now
raises. CIM's open is the whole switch's, and the importer had read State=open as all three phases open. No
sweep deck sets a Fuse state.
- Recloser: Recloser.<name> MonitoredObj=Line.<name>. The protection settings are untranscribed on import
(DSS-11).
- Any other class (LoadBreakSwitch, Breaker, Disconnector, Sectionaliser, Jumper):
SwtControl.<name> SwitchedObj=Line.<name>, written only when the switch is open in either state.
The state:
- get_switch_state(which="normal") → the control's Normal=open|closed;
- which="actual" → State=open|closed, plus Open Line.<name> 1 in Options.open_terminals when open (the
importer's rule inverted).
- to_model(..., switch_state="normal") reads which="normal" for State and Open too, for an as-built model
whose Switch.open is unset. The default, "actual", raises on an unset open; there is no silent fallback.
A Fuse or Recloser closed in both states writes neither. A one-terminal switch (GroundDisconnector) raises. The class is lossy on the way back: Breaker, Disconnector, Sectionaliser and Jumper come back as LoadBreakSwitch (DSS-9, listed).
Tests¶
As built (tests/test_export_line.py, 34 tests; core test_getters_wire.py, test_derived_capacitance.py, and
code-level tests in test_getters_line_impedance.py):
- Per atom, in the engine (§8.3, engine_compare): line/codes, line/geometry, and two new atoms:
- line/cables.dss: the IEEE13_Assets CN and TS geometries 606/607 (607 mixes a TS phase and a bare neutral), the
IEEE8500 sequence code, and an unused wire and code;
- line/states.dss: an open Fuse (one state per phase), an open Recloser, and a SwtControl with Normal=open
State=closed.
Each atom is exported under name. Per element it checks buses, NodeOrder and YPrim (rel 1e-9), then the
voltages (rel 1e-8). Under mrid and uri only the voltages are checked. assert_same_engine_state takes the
listed exceptions:
- yprim_differs: every switch, because the deck's stand-in (r1=1e-4, or the Switch=y defaults) is not the
exporter's 1 mOhm (B3). Nothing flows through them in the atoms, so the voltages agree to 1e-9;
- added: the SwtControl of codes' sect (E6). The Recloser settings have no element of their own.
Every line by code, by geometry and by cable has the original's YPrim to rel 1e-9.
- The CIM fixed point for catalog-only atoms is dropped (found in implementation). linecode/mtx601,
linecode/seq_3_1_0c, wire/* and geometry/assets have no New Circuit, so the importer cannot make a
network of them. The cables atom puts every catalog kind on a line instead, so the engine sees each one.
- Engine catalog values (cables): every WireData/CNData/TSData property of the export equals the original's in
the engine, each converted to metres by its own unit selector (rel 1e-9).
- Getters: get_wire_info (the three kinds, ratings agreement, rAC75 raises), get_configuration_wires,
get_asset_info_current_limits, the code-level impedance getters, and c_from_b as the inverse of b_from_c
(1e-12).
- Lumped lines: the codes network with seq2's code replaced by its whole-line lumped values, with and without
a length. Exported, its YPrim equals the original's (rel 1e-9).
- Spoke unit tests:
- the offset geometry name;
- unused codes, wires and configurations are written;
- each raise listed above;
- the switch-control matrix (class x states).
- Deck round trip: IEEE13_CDPSM through import → export → engine, element by element. It is not a gate: its
transformers wait for S6c. So it runs only once S6c lands, and S6b's exit is the atoms.
- Goldens: tests/atoms/line/export/*.dss (mrid).
- Float tails clipped (the user, 2026-11-09). The unit conversions left binary tails
(x0=0.0018000000000000002). Every float the writer writes is now format_float, 15 significant digits in the
shortest form (0.0018, 60, 1e-05). The cost is 1e-15 relative: IEEE8500's X=14.798306633595042 is written
14.798306633595. The writer round-trip test therefore compares records at the writer's precision, and the
engine round trips (IEEE13_CDPSM, IEEE123, IEEE4) are unchanged.
- Test harness fix: Set defaultbasefreq outlives Clear in the engine. After the 50 Hz Vsource atom, a deck
without its own frequency compiled at 50 Hz, and the IEEE13_CDPSM round trip failed when it ran after it.
conftest.compile_deck now sets 60 Hz after Clear.
Decisions for S6b (approved 2026-11-09)¶
| # | question | decision |
|---|---|---|
| B1 | Deck units | Every length in metres (Line/LineCode units=m, geometry units=m, wire Runits/GMRunits/radunits=m); B6's lumped lines are the one exception |
| B2 | Geometry form | Inline positions (cond blocks) per (WireConfiguration, offset), and per (spacing, offset, conductors) for a spacing line (a direct WireSpacing and a WireInfo on each phase, the EPRI shape); no LineSpacing is written |
| B3 | Switch impedance (amended by the user) | A small invented impedance: 1 mOhm resistive, r1=r0=1e-3 x1=x0=0 C1=C0=0 length=1 units=m |
| B4 | Line neutrals (approved by the user 2026-11-09, as recommended and built) | Geometry reduce=y, and the neutral is not written on the bus. Engine probe (2026-11-09, geometry 601 under an unbalanced load): reduce=y gives the same voltages, to 1e-9 V, as reduce=n with the neutral on node 0 at both ends. So reduce=y is exactly a neutral grounded at both ends, and it keeps a 3x3 YPrim. reduce=n on a .1.2.3 bus puts the neutral on node 4, ungrounded: it floats (292 V in the probe), and the phase voltages move by up to 4 %. CIM has no per-conductor neutral grounding to export, so reduce=n has nothing to carry. A code line with a neutral row raises |
| B5 | Code values | Code-level getters; a code no line uses is still exported |
| B6 | Lumped-only lines (amended by the user) | Written inline: the whole-line values divided by the length, r1 x1 r0 x0 in ohm/km and C1 C0 in nF/km, units=km; with no length, length=1 |
| B7 | Unshielded cable (user, 2026-11-12) | A plain CableInfo (insulated, no neutral or shield: an underground secondary's conductors) is a WireData, its insulation not modelled. DSS takes a WireData only above grade, so a buried one is written at the same height above (hs = abs(y)). The series impedance is close: the earth-return depth (about 850 m at 100 ohm-m) dwarfs a few feet |
Slot tables (generated from SLOTS)¶
Wiredata (exporter/wire.py)
| DSS slot | kind | from / why |
|---|---|---|
| name | written | Names, one namespace for the three catalogs |
| Rdc | written | get_wire_info.r_dc20 (ohm/m); Rdc and Rac both unset raises |
| Rac | rule | get_wire_info.r_ac25 (ohm/m), else r_ac50 (a GridLAB-D wire's 50 C value); both unset -> not written, the engine's 1.02 x Rdc |
| Runits | written | m (B1) |
| GMRac | rule | get_wire_info.gmr (m); unset -> not written, the engine's 0.7788 x radius |
| GMRunits | written | m (B1) |
| radius | written | get_wire_info.radius (m); unset raises |
| radunits | written | m (B1) |
| normamps | written | the wire's normal limit, else ratedCurrent (A) |
| emergamps | rule | the wire's emergency limit (A); unset -> not written, the engine's 1.5 x normamps |
| diam | not mapped | radius is written instead |
| Seasons | unset | not in CIM (untranscribed or raising on import) |
| Ratings | unset | not in CIM (untranscribed or raising on import) |
| Capradius | unset | not in CIM (untranscribed or raising on import) |
| like | not mapped | the writer never writes like= |
Cndata (exporter/wire.py)
| DSS slot | kind | from / why |
|---|---|---|
| name | written | Names, one namespace for the three catalogs |
| Rdc | written | get_wire_info.r_dc20 (ohm/m); Rdc and Rac both unset raises |
| Rac | rule | get_wire_info.r_ac25 (ohm/m), else r_ac50 (a GridLAB-D wire's 50 C value); both unset -> not written, the engine's 1.02 x Rdc |
| Runits | written | m (B1) |
| GMRac | rule | get_wire_info.gmr (m); unset -> not written, the engine's 0.7788 x radius |
| GMRunits | written | m (B1) |
| radius | written | get_wire_info.radius (m); unset raises |
| radunits | written | m (B1) |
| normamps | written | the wire's normal limit, else ratedCurrent (A) |
| emergamps | rule | the wire's emergency limit (A); unset -> not written, the engine's 1.5 x normamps |
| diam | not mapped | radius is written instead |
| Seasons | unset | not in CIM (untranscribed or raising on import) |
| Ratings | unset | not in CIM (untranscribed or raising on import) |
| Capradius | unset | not in CIM (untranscribed or raising on import) |
| like | not mapped | the writer never writes like= |
| EpsR | unset | no permittivity on CableInfo; the engine's 2.3 |
| InsLayer | written | cable.insulation_thickness (m) |
| DiaIns | written | cable.diameter_over_insulation (m) |
| k | written | cable.neutral_strand_count |
| DiaStrand | written | 2 x cable.neutral_strand_radius (m) |
| GmrStrand | written | cable.neutral_strand_gmr (m) |
| Rstrand | written | cable.neutral_strand_r_dc20 (ohm/m), CIM's only strand resistance |
| SemiconLayer | unset | not in CIM (untranscribed or raising on import) |
| DiaCable | written | cable.diameter_over_neutral (m), the circle of the strands; unset raises |
Tsdata (exporter/wire.py)
| DSS slot | kind | from / why |
|---|---|---|
| name | written | Names, one namespace for the three catalogs |
| Rdc | written | get_wire_info.r_dc20 (ohm/m); Rdc and Rac both unset raises |
| Rac | rule | get_wire_info.r_ac25 (ohm/m), else r_ac50 (a GridLAB-D wire's 50 C value); both unset -> not written, the engine's 1.02 x Rdc |
| Runits | written | m (B1) |
| GMRac | rule | get_wire_info.gmr (m); unset -> not written, the engine's 0.7788 x radius |
| GMRunits | written | m (B1) |
| radius | written | get_wire_info.radius (m); unset raises |
| radunits | written | m (B1) |
| normamps | written | the wire's normal limit, else ratedCurrent (A) |
| emergamps | rule | the wire's emergency limit (A); unset -> not written, the engine's 1.5 x normamps |
| diam | not mapped | radius is written instead |
| Seasons | unset | not in CIM (untranscribed or raising on import) |
| Ratings | unset | not in CIM (untranscribed or raising on import) |
| Capradius | unset | not in CIM (untranscribed or raising on import) |
| like | not mapped | the writer never writes like= |
| EpsR | unset | no permittivity on CableInfo; the engine's 2.3 |
| InsLayer | written | cable.insulation_thickness (m) |
| DiaIns | written | cable.diameter_over_insulation (m) |
| DiaShield | written | cable.diameter_over_screen + 2 x tape_thickness (m): DSS measures over the tape |
| TapeLayer | written | cable.tape_thickness (m) |
| TapeLap | written | cable.tape_lap (percent) |
| DiaCable | written | cable.diameter_over_jacket (m) |
Linecode (exporter/linecode.py)
| DSS slot | kind | from / why |
|---|---|---|
| name | written | Names |
| nphases | written | phase code: conductorCount; sequence code: 3 |
| r1 | written | sequence code: r (ohm/m) |
| x1 | written | sequence code: x (ohm/m) |
| r0 | written | sequence code: r0 (ohm/m); unset raises |
| x0 | written | sequence code: x0 (ohm/m); unset raises |
| C1 | rule | sequence code: c_from_b(bch) (nF/m); unset -> 0 |
| C0 | rule | sequence code: c_from_b(b0ch) (nF/m); unset -> 0 |
| units | written | m (B1) |
| rmatrix | written | phase code: r, lower triangle (ohm/m) |
| xmatrix | written | phase code: x, lower triangle (ohm/m) |
| cmatrix | rule | phase code: c_from_b(b), lower triangle (nF/m); unset -> zeros |
| baseFreq | written | network.base_frequency (Hz); a calculatedFrequency that differs raises |
| normamps | unset | no rating on a PerLengthImpedance (D9); the Line carries its own |
| emergamps | unset | no rating on a PerLengthImpedance (D9); the Line carries its own |
| faultrate | unset | not in CIM (untranscribed on import) |
| pctperm | unset | not in CIM (untranscribed on import) |
| repair | unset | not in CIM (untranscribed on import) |
| Kron | unset | not in CIM (untranscribed on import) |
| Rg | not mapped | PerLengthImpedance.rg set raises (not imported either) |
| Xg | not mapped | PerLengthImpedance.xg set raises (not imported either) |
| rho | unset | not in CIM (untranscribed on import) |
| neutral | unset | not in CIM (untranscribed on import) |
| B1 | not mapped | C1 carries the susceptance |
| B0 | not mapped | C0 carries the susceptance |
| Seasons | unset | not in CIM (untranscribed on import) |
| Ratings | unset | not in CIM (untranscribed on import) |
| LineType | unset | not in CIM (untranscribed on import) |
| like | not mapped | the writer never writes like= |
Linegeometry (exporter/linegeometry.py)
| DSS slot | kind | from / why |
|---|---|---|
| name | written | Names; |
| nconds | written | the configuration's positions; a spacing line's: its phases' positions; a coupled group's: its lines' positions, a shared neutral once |
| nphases | written | WireConfiguration.numberOfPhases, required; a spacing line's: its phases other than N, a coupled group's: every line's; position kinds phase then neutral |
| cond | not mapped | the writer folds wires/xs/hs into cond= blocks |
| wire | not mapped | the writer folds wires/xs/hs into cond= blocks |
| x | not mapped | the writer folds wires/xs/hs into cond= blocks |
| h | not mapped | the writer folds wires/xs/hs into cond= blocks |
| units | written | m (B1) |
| normamps | unset | no rating on a WireConfiguration (D9); the Line carries its own |
| emergamps | unset | no rating on a WireConfiguration (D9); the Line carries its own |
| reduce | written | y: the neutrals grounded at both ends, as the impedance getters assume (B4) |
| spacing | not mapped | positions are written inline (B2) |
| wires | written | get_configuration_wires, or a spacing line's get_line_phase_wires (line_wires), by sequence number; any of the three catalogs |
| cncable | not mapped | the writer folds wires/xs/hs into cond= blocks |
| tscable | not mapped | the writer folds wires/xs/hs into cond= blocks |
| cncables | not mapped | wires carries every kind (the writer names each block's kind) |
| tscables | not mapped | wires carries every kind (the writer names each block's kind) |
| xs | written | get_line_conductor_xy x (m); an unused configuration: get_spacing_xy on its WireSequenceConfigurations' sequence numbers |
| hs | written | get_line_conductor_xy y, above ground (m); a plain CableInfo's abs(y) (B7) |
| Seasons | unset | not in CIM (untranscribed on import) |
| Ratings | unset | not in CIM (untranscribed on import) |
| LineType | unset | not in CIM (untranscribed on import) |
| conductors | not mapped | wires carries the names |
| like | not mapped | the writer never writes like= |
Line (exporter/line.py)
| DSS slot | kind | from / why |
|---|---|---|
| name | written | Names; a coupled group's: the group's, |
| bus1 | written | bus_ref(get_terminal_nodes[0], the phase conductors of get_conductor_phases); a coupled group's: |
| bus2 | written | bus_ref(get_terminal_nodes[1], the same phases); a coupled group's: |
| linecode | written | the template PerLengthImpedance's LineCode name (get_line_code); a line's own (isTemplate=false) is written inline |
| length | written | required_qty(length, m), <= 0 raises; lumped: km, unset -> 1, <= 0 raises; a coupled group's: its shortest line's (<= 0 raises), a remainder the rest of its line, a jumper 1 m (H4) |
| phases | written | the phase conductors (a neutral is reduced, B4); a coupled group's: every line's |
| r1 | written | the line's own sequence code (isTemplate=false), as a LineCode writes it (ohm/m); lumped only (B6): the whole-line value / length in km (ohm/km); a jumper's: SWITCH_IMPEDANCE (B3, H1) |
| x1 | written | the line's own sequence code (isTemplate=false), as a LineCode writes it (ohm/m); lumped only (B6): the whole-line value / length in km (ohm/km); a jumper's: SWITCH_IMPEDANCE (B3, H1) |
| r0 | written | the line's own sequence code (isTemplate=false), as a LineCode writes it (ohm/m); lumped only (B6): the whole-line value / length in km (ohm/km); unset raises; a jumper's: SWITCH_IMPEDANCE (B3, H1) |
| x0 | written | the line's own sequence code (isTemplate=false), as a LineCode writes it (ohm/m); lumped only (B6): the whole-line value / length in km (ohm/km); unset raises; a jumper's: SWITCH_IMPEDANCE (B3, H1) |
| C1 | rule | the line's own sequence code (isTemplate=false), as a LineCode writes it; lumped only (B6): the whole-line value / length in km, c_from_b(bch) (nF/km); unset -> 0; a jumper's: SWITCH_IMPEDANCE (B3, H1) |
| C0 | rule | the line's own sequence code (isTemplate=false), as a LineCode writes it; lumped only (B6): the whole-line value / length in km, c_from_b(b0ch) (nF/km); unset -> 0; a jumper's: SWITCH_IMPEDANCE (B3, H1) |
| rmatrix | written | the line's own phase code (isTemplate=false), lower triangle per m; a template's is its LineCode's |
| xmatrix | written | the line's own phase code (isTemplate=false), lower triangle per m; a template's is its LineCode's |
| cmatrix | written | the line's own phase code (isTemplate=false), lower triangle per m; a template's is its LineCode's |
| Switch | not mapped | a Switch is exported by switch.py |
| Rg | unset | not in CIM (untranscribed or raising on import) |
| Xg | unset | not in CIM (untranscribed or raising on import) |
| rho | written | line_rho: a geometry line's WireConfiguration EarthResistivity.rho (ohm-m), unset -> not written; a spacing line's: get_network_earth; a coupled group's: its lines' one |
| geometry | written | the (WireConfiguration, ySpacingOffset) LineGeometry name; a spacing line's: spacing_geometry_name of its owner; a coupled group's: |
| units | written | m (B1); lumped: km (B6) |
| spacing | not mapped | positions are written inline in the LineGeometry (B2) |
| cncables | not mapped | the LineGeometry carries the conductors (B2) |
| tscables | not mapped | the LineGeometry carries the conductors (B2) |
| wires | not mapped | the LineGeometry carries the conductors (B2) |
| EarthModel | not mapped | the deck's Set earthmodel carries it (options.py: one model per deck) |
| B1 | not mapped | C1 carries the susceptance |
| B0 | not mapped | C0 carries the susceptance |
| Seasons | unset | not in CIM (untranscribed or raising on import) |
| Ratings | unset | not in CIM (untranscribed or raising on import) |
| LineType | unset | not in CIM (untranscribed or raising on import) |
| EpsRmedium | unset | not in CIM (untranscribed or raising on import) |
| HeightOffset | not mapped | ySpacingOffset goes into the geometry's heights |
| HeightUnit | not mapped | ySpacingOffset goes into the geometry's heights |
| conductors | unset | not in CIM (untranscribed or raising on import) |
| normamps | rule | get_current_limits normal (A); unset -> not written, the engine copies the catalog's |
| emergamps | rule | get_current_limits emergency (A); unset -> not written, as normamps |
| faultrate | unset | not in CIM (untranscribed or raising on import) |
| pct_perm | unset | not in CIM (untranscribed or raising on import) |
| repair | unset | not in CIM (untranscribed or raising on import) |
| basefreq | unset | Options.defaultbasefreq is the deck's |
| enabled | written | get_in_service(which='normal'); unset -> not written |
| like | not mapped | the writer never writes like= |
Line (exporter/switch.py)
| DSS slot | kind | from / why |
|---|---|---|
| name | written | Names, the Line namespace (shared with ACLineSegments) |
| bus1 | written | bus_ref, as a Line |
| bus2 | written | bus_ref, as a Line |
| linecode | unset | a switch has no other line data (DSS-8) |
| length | rule | SWITCH_IMPEDANCE: CIM has no switch impedance (B3, 1 mOhm) |
| phases | written | the phase conductors |
| r1 | rule | SWITCH_IMPEDANCE: CIM has no switch impedance (B3, 1 mOhm) |
| x1 | rule | SWITCH_IMPEDANCE: CIM has no switch impedance (B3, 1 mOhm) |
| r0 | rule | SWITCH_IMPEDANCE: CIM has no switch impedance (B3, 1 mOhm) |
| x0 | rule | SWITCH_IMPEDANCE: CIM has no switch impedance (B3, 1 mOhm) |
| C1 | rule | SWITCH_IMPEDANCE: CIM has no switch impedance (B3, 1 mOhm) |
| C0 | rule | SWITCH_IMPEDANCE: CIM has no switch impedance (B3, 1 mOhm) |
| rmatrix | unset | a switch has no other line data (DSS-8) |
| xmatrix | unset | a switch has no other line data (DSS-8) |
| cmatrix | unset | a switch has no other line data (DSS-8) |
| Switch | written | y |
| Rg | unset | a switch has no other line data (DSS-8) |
| Xg | unset | a switch has no other line data (DSS-8) |
| rho | unset | a switch has no other line data (DSS-8) |
| geometry | unset | a switch has no other line data (DSS-8) |
| units | rule | SWITCH_IMPEDANCE: CIM has no switch impedance (B3, 1 mOhm) |
| spacing | unset | a switch has no other line data (DSS-8) |
| cncables | unset | a switch has no other line data (DSS-8) |
| tscables | unset | a switch has no other line data (DSS-8) |
| wires | unset | a switch has no other line data (DSS-8) |
| EarthModel | unset | a switch has no other line data (DSS-8) |
| B1 | unset | a switch has no other line data (DSS-8) |
| B0 | unset | a switch has no other line data (DSS-8) |
| Seasons | unset | a switch has no other line data (DSS-8) |
| Ratings | unset | a switch has no other line data (DSS-8) |
| LineType | unset | a switch has no other line data (DSS-8) |
| EpsRmedium | unset | a switch has no other line data (DSS-8) |
| HeightOffset | unset | a switch has no other line data (DSS-8) |
| HeightUnit | unset | a switch has no other line data (DSS-8) |
| conductors | unset | a switch has no other line data (DSS-8) |
| normamps | rule | get_current_limits normal (A); unset -> not written |
| emergamps | rule | get_current_limits emergency (A); unset -> not written |
| faultrate | unset | a switch has no other line data (DSS-8) |
| pct_perm | unset | a switch has no other line data (DSS-8) |
| repair | unset | a switch has no other line data (DSS-8) |
| basefreq | unset | a switch has no other line data (DSS-8) |
| enabled | written | get_in_service(which='normal'); unset -> not written |
| like | not mapped | the writer never writes like= |
Fuse (exporter/switch.py)
| DSS slot | kind | from / why |
|---|---|---|
| name | written | Names, the switch's |
| MonitoredObj | written | Line.<the switch's Line name> |
| MonitoredTerm | unset | no home on a Switch (untranscribed on import) |
| SwitchedObj | not mapped | the engine takes MonitoredObj |
| SwitchedTerm | unset | no home on a Switch (untranscribed on import) |
| FuseCurve | unset | protection setting; no home in cim18v17's protection function blocks (DSS-11): the engine's default |
| RatedCurrent | written | Switch.ratedCurrent (A) |
| Delay | unset | no home on a Switch (untranscribed on import) |
| Action | unset | no home on a Switch (untranscribed on import) |
| Normal | written | get_switch_state(which='normal'); written only when open in either state; one value per phase (the engine sets a fuse per phase) |
| State | written | get_switch_state(which='actual'); written only when open in either state; one value per phase (the engine sets a fuse per phase) |
| basefreq | unset | no home on a Switch (untranscribed on import) |
| enabled | rule | no: no trip settings or curve in CIM yet (U15), so the engine's defaults would trip it (V7) |
| like | not mapped | the writer never writes like= |
Recloser (exporter/switch.py)
| DSS slot | kind | from / why |
|---|---|---|
| name | written | Names, the switch's |
| MonitoredObj | written | Line.<the switch's Line name> |
| MonitoredTerm | unset | protection setting; no home in cim18v17's protection function blocks (DSS-11): the engine's default |
| SwitchedObj | not mapped | the engine takes MonitoredObj |
| SwitchedTerm | unset | protection setting; no home in cim18v17's protection function blocks (DSS-11): the engine's default |
| NumFast | unset | protection setting; no home in cim18v17's protection function blocks (DSS-11): the engine's default |
| PhaseFast | unset | protection setting; no home in cim18v17's protection function blocks (DSS-11): the engine's default |
| PhaseDelayed | unset | protection setting; no home in cim18v17's protection function blocks (DSS-11): the engine's default |
| GroundFast | unset | protection setting; no home in cim18v17's protection function blocks (DSS-11): the engine's default |
| GroundDelayed | unset | protection setting; no home in cim18v17's protection function blocks (DSS-11): the engine's default |
| PhaseTrip | unset | protection setting; no home in cim18v17's protection function blocks (DSS-11): the engine's default |
| GroundTrip | unset | protection setting; no home in cim18v17's protection function blocks (DSS-11): the engine's default |
| PhaseInst | unset | protection setting; no home in cim18v17's protection function blocks (DSS-11): the engine's default |
| GroundInst | unset | protection setting; no home in cim18v17's protection function blocks (DSS-11): the engine's default |
| Reset | unset | protection setting; no home in cim18v17's protection function blocks (DSS-11): the engine's default |
| Shots | written | the RecloseSequences + 1 (get_reclose_delays); none -> 1, no reclosure |
| RecloseIntervals | written | each RecloseSequence's recloseDelay (s), in recloseStep order; none -> not written |
| Delay | unset | protection setting; no home in cim18v17's protection function blocks (DSS-11): the engine's default |
| Action | unset | protection setting; no home in cim18v17's protection function blocks (DSS-11): the engine's default |
| TDPhFast | unset | protection setting; no home in cim18v17's protection function blocks (DSS-11): the engine's default |
| TDGrFast | unset | protection setting; no home in cim18v17's protection function blocks (DSS-11): the engine's default |
| TDPhDelayed | unset | protection setting; no home in cim18v17's protection function blocks (DSS-11): the engine's default |
| TDGrDelayed | unset | protection setting; no home in cim18v17's protection function blocks (DSS-11): the engine's default |
| Normal | written | get_switch_state(which='normal'); written only when open in either state |
| State | written | get_switch_state(which='actual'); written only when open in either state |
| basefreq | unset | protection setting; no home in cim18v17's protection function blocks (DSS-11): the engine's default |
| enabled | rule | no: no trip settings or curve in CIM yet (U15), so the engine's defaults would trip it (V7) |
| like | not mapped | the writer never writes like= |
Swtcontrol (exporter/switch.py)
| DSS slot | kind | from / why |
|---|---|---|
| name | written | Names, the switch's |
| SwitchedObj | written | Line.<the switch's Line name> |
| SwitchedTerm | unset | no home on a Switch (untranscribed on import) |
| Action | unset | no home on a Switch (untranscribed on import) |
| Lock | unset | no home on a Switch (untranscribed on import) |
| Delay | unset | no home on a Switch (untranscribed on import) |
| Normal | written | get_switch_state(which='normal'); written only when open in either state |
| State | written | get_switch_state(which='actual'); written only when open in either state |
| Reset | unset | no home on a Switch (untranscribed on import) |
| basefreq | unset | no home on a Switch (untranscribed on import) |
| enabled | unset | no home on a Switch (untranscribed on import) |
| like | not mapped | the writer never writes like= |
S6c: transformers, XfmrCode, regulators, RegControl (spec approved 2026-11-09; done 2026-11-09)¶
Content: every transformer form get_transformer_model reads, written as an inline Transformer or as an XfmrCode and
its instances; regulators and LTCs with their taps; RegControl. Plan §8.1 row S6c; DSS-2, DSS-5, DSS-13, E3 and E7
apply. Decisions T1-T7 are at the end of this section.
Layout¶
cimhub_opendss/src/cimhub_opendss/exporter/
windings.py a unit's DSS winding values (model on winding 1's kVA, buses, taps), shared by the three below
xfmrcode.py TransformerTankConfiguration -> Xfmrcode (T5)
transformer.py PowerTransformer / AutoTransformer (VoltageRegulator) -> Transformer, one per unit (T4), taps
regcontrol.py TapChangerControl -> Regcontrol
switch.py's slot-defaulting helper moved to slots.with_default, which all four modules use.
EXPORT_ORDER becomes (vsource, wire, linecode, linegeometry, line, switch, xfmrcode, transformer, regcontrol).
The writer's WRITE_ORDER already has XfmrCode before Transformer and RegControl after it. A probe (2026-11-09)
showed the writer's slot order wdg=2 Rneut=0 Xneut=0.4 buses=[...] puts the neutral impedance on winding 2, the
same as the deck's ~ wdg=2 ... Rneut=0 Xneut=0.4 (YPrim and voltages equal), and the reader reads it back. A
second probe showed that XfmrCode= must come first: written after buses=, it re-sizes a center tap to 3
windings and resets winding 3's bus to t_3. The writer's _LEADING_SLOTS already puts it first.
Forms¶
One DSS Transformer per unit of get_transformer_units (T4). Every value comes from
get_transformer_model(unit, base_power=<winding 1's DSS kVA>), so every percent is on the base DSS puts it on.
| CIM form | DSS | kV, kVA | |
|---|---|---|---|
BY_ENDS (PowerTransformer, balanced ends) |
inline, phases=3 |
ratedU (LL), ratedS |
%imag/%noloadloss = the core's b/g |
| BY_PHASE_ENDS (a tank's own windings) | inline, phases=1 |
baseU, baseS (the coil) |
the tank's %imag/%noloadloss |
BY_TANK_ENDS, BY_LUGS (a TankConfiguration) |
the configuration's XfmrCode; the instance writes XfmrCode=, buses and enabled |
(on the code) | |
BY_TANK_IMPEDANCE (two ends and each tank's percentImpedance, a GIS's cans) |
inline, phases 1 or 3; a center-tap end (s1s2N, kind I) is two halves on one bus; a bank is one 1-phase Transformer per can (T4), in tank order (GETTERS_PLAN bank rules) |
a coil: ratedU derived to the coil (V2), each half ratedU/2 at the can's kVA; 3-phase ratedU, ratedS |
%Rs and X** from %Z and loadLoss (Hopkinson's split on a center tap); the tank's %imag/%noloadloss |
AUTO (AutoTransformer, VoltageRegulator) |
inline, phases 1 or 3 (DSS has no AutoTrans mapping here, DSS-11) |
baseU (the deck's kV, LL on a 3-phase gang unit: an AutoTransformerEnd has no ratedU), ratedS |
no core |
- kVA on a coil is
baseS. A center-tap half is written at the can's kVA (25 for a 25 kVA can), as every deck writes it. Probe: writing the half at itsratedS(12.5) with its %R moved to that base is not engine-equal (0.27 V on the atom): the engine takes more than %R from each winding's kVA. - %Rs: winding n's r from the getter (on winding 1's kVA) times kVA_n / kVA_1. A regulator's mesh r (DSS-13: %R1
- %R2) is written
%Rs=[r/2 r/2]. Probe: equal to the deck's%LoadLoss=r(YPrim equal). - XHL, XHT, XLT: the mesh x (1,2), (1,3), (2,3), on winding 1's kVA. A missing pair raises. A mesh r on any form but AUTO raises: DSS has no home for it.
- conns:
connectionKindD → delta; Y, Yn, I → wye. An AutoTransformerEnd has none: a coil with a neutral is wye, a coil between two phases delta (IEEE37'sconns=[delta delta]). Probe: on a 1-phase coil, wye and delta differ only in the engine's anti-float conductance (YPrim within 1.5e-8), so a deck's 1-phase LL coil written wye (thecenter_tapatom) comes back delta, a listed YPrim difference. - Windings: 2 or 3; more raise (
Xscarraynot mapped). - Not written:
normhkVA/emerghkVA(untranscribed, D9),bank,LeadLag,ppm_antifloat(an instance'sppm=0comes back at the engine's default, a listed YPrim difference),XRConst, the thermal and reliability slots.
Bus references (E7, the windings' part; T6)¶
A winding's phases in their order (a coil From → To). bus_ref gains the neutral's node:
- A 3-phase wye (the terminal's ABCN):
- grounded solidly → .1.2.3, the engine's neutral on node 0;
- grounded through rground/xground → .1.2.3.4 with wdg=<n> Rneut= Xneut=;
- ungrounded → .1.2.3.4 with no Rneut.
Probe: Rneut on .1.2.3 is shorted by the neutral on node 0 (the same as solid). Two windings with a neutral
impedance raise: the record has one wdg.
- A delta: .1.2.3.
- A 2-phase wye (every winding on the same two phases and N): as a 3-phase wye on its two phase
conductors (p.2.3, .2.3.4 ungrounded), DSS phases=2.
- A coil: its two conductors, N as .0 (feeder.1.0, house.0.2, n1.1.2) when grounded. An ungrounded
coil neutral is .4, as T6 (head.1.4): a bank's cans on one bus share that floating node, the wye primary of a
floating-wye / delta bank. The engine's default antifloat (1 ppm) is enough for it to solve. A coil neutral
with grounded unset raises. The importer has no phase for node 4 on a 1-phase transformer, so it does not read
such a deck back (it raises).
XfmrCode (T5)¶
One per TransformerTankConfiguration that a unit uses. Its values come from the model of the first unit that uses
it, so they follow the same rules as an inline Transformer:
- phases: the polyphase unit's phase conductors, 3 (ABC) or 2 (a 2-phase wye: every winding on the same two
phases and N, GLM's WYE_WYE on two phases, whose per-phase base (kV/√3)² / (kVA/2) is the coil's), else 1 (a
coil); anything else raises;
- windings, conns, kVs, kVAs and %Rs;
- Xhl, Xht and Xlt;
- %imag and %noloadloss;
- Rneut/Xneut from the TankEnd's rground/xground;
- RdcOhms from the template windings' rDC, and Seasons/Ratings from the template's own limit set (below).
MaxTap and the other tap slots are the instance's. Every instance names it XfmrCode=<code> and writes its buses
from its own model.
DC resistance and seasonal ratings (2026-11-24)¶
The importer now maps RdcOhms to TransformerWinding.rDC and Seasons/Ratings to ApparentPowerLimits of
type olt_season<n> (CIMTBL_MAPPING.md, Transformer and XfmrCode), so the exporter writes them back:
- RdcOhms is each winding's rDC (ohm), from the core Winding.r_dc of get_transformer_model, which is
None on an end (BY_ENDS, AUTO): then nothing is written. The writer emits it last, one wdg=n RdcOhms=v block
per winding, since DSS has no array form (_PER_WINDING_SLOTS). Some windings with and some without rDC raise:
DSS would take its default for those.
- Seasons is the number of olt_season<n> limits and Ratings their values (kVA) in season order
(transformer.season_ratings), read with get_limits_by_type(transformer, ApparentPowerLimit, "kVA") on a
PowerTransformer and get_configuration_limits_by_type(configuration, ...) on a template (its
EquipmentConfiguration.OperationalLimitSet). Seasons that are not 1..n raise, since DSS numbers them.
ApparentPowerLimits of other types are not written. Ratings on a transformer of several units raise: DSS rates
each unit's Transformer.
- Atoms: transformer/rated_inline.dss and xfmrcode/rated.dss, goldens export/rated_inline.dss and
export/rated.dss; test_ratings_and_dc_resistance_match_the_engine checks that the exported Seasons,
Ratings and each winding's RdcOhms are what the engine read from the original.
- normhkVA/emerghkVA stay unwritten (untranscribed on import).
Taps¶
Every RatioTapChanger on a unit's end:
- taps = 1 on every winding but the tap's, which gets get_tap_ratio(which='actual') (R2: step is the deck's
tap; normalStep is not read);
- MaxTap/MinTap = the ratio at highStep/lowStep;
- NumTaps = highStep - lowStep.
What raises:
- an unset step;
- a neutralU other than the winding's kV;
- a tap on an end with two windings (a center-tap secondary);
- any other TapChanger class.
A regulator by XfmrCode (IEEE8500 regleg) comes back inline. CIM has no AutoTransformer template, so its code was
never written (S3a), a listed difference that is equal in the engine.
RegControl¶
One per TapChangerControl, from get_tap_changer_control, inverting the importer's secondary_to_primary and
line_drop_ohms. That pair moves to cimhub_core/derived/regulator.py beside its inverses, as b_from_c did.
| DSS slot | from |
|---|---|
transformer, winding |
the tap's unit; the winding whose end holds the tap |
vreg, band |
target, deadband (V) / ptRatio |
revvreg, revband |
the reverse target and deadband / ptRatio |
ptratio |
ptRatio (tap and control agreed) |
CTprim |
ctRating (A) |
R, X, revR, revX |
line drop (ohm) × CTprim / ptratio |
delay, tapdelay |
initialDelay, subsequentDelay (s) |
reversible, revNeutral, revDelay |
as stored |
revThreshold |
reversingPowerThreshold (kW) |
PTphase |
1-based place of the monitoredPhase among the winding's phase conductors |
enabled |
the control's enabled; the tap's controlEnabled must agree |
ctRatio is not read: the engine's CT secondary is fixed at 0.2 A, and R/X go through CTprim.
What raises:
- a mode other than voltage;
- an unset ptRatio;
- a line drop with no ctRating;
- R/X with lineDropCompensation=false;
- a monitored Terminal other than the tap end's (remote sensing, tapwinding);
- maxLimitVoltage (vlimit) or minLimitVoltage;
- several monitored phases.
Core changes¶
get_transformer_model(T2): Y on a template TankEnd and Yn on its instance end agree, and the result is the instance's. Found in the S6c probe: the getter raises on the importer's ownxfmrcode/codes(sub:xf_sub_2Yn,xc_sub_end_2Y), because grounding is the instance's (S3b) while the getter compared the kinds literally.- T3 (polarity), importer and getter. The importer wrote a 1-phase TankEnd instance's LL end as a PhaseCode,
which has no order, so IEEE4 YYD's
tert.3.1came backtert.1.3. Probe: the 3-can bank's voltages move by 1.6 kV. Now: - The importer gives every 1-phase instance by template a
TransformerPhaseEndper terminal conductor, on the end's Terminal. A lug instance keeps terminal order (its lugs name them). A TankEnd instance follows its coil's node order (coil_phase_end_numbers). - BY_TANK_ENDS reads a coil's phases from them, in
sequenceNumberorder (_ordered_phases). Phase ends that are not the terminal's phases raise. - Goldens:
xfmrcode/codes_transformer.cimtbl(the yyd instances' phase ends) andgoldens/IEEE13_CDPSM/transformer.cimtbl(the table comment only). The sweep still binds every deck it bound. derived/regulator.py:secondary_to_primary,line_drop_ohms(moved from the importer) and their inversesprimary_to_secondary,line_drop_volts.bus_ref(..., neutral=): a neutral is written on the node the winding gives (0 for a coil, 4 for T6). Without one it still raises, so a line can never write a neutral.
Tests¶
As built (tests/test_export_transformer.py, 28 tests; core test_derived_regulator.py and three tests in
test_getters_transformer.py):
- Per atom, in the engine (§8.3), exported under name. Per element: buses, NodeOrder and YPrim (rel 1e-9),
then the voltages. Under mrid/uri only the voltages. The atoms:
- xfmrcode/codes: three XfmrCodes and six instances; transformer.t2 (its ppm=0) is the listed YPrim
difference;
- regcontrol/regulators: every regulator and the LTC inline, every RegControl; no difference;
- the new transformer/inline.dss (with a circuit): sub3, xfm1, the LL center tap ct_ab (listed: wye → delta),
the LN center tap ct_bn, the J1 service svc, an ungrounded wye ug on .4, and a delta-delta dd.
- Regulator settings in the engine: every RegControl property the importer maps and every regulator's taps,
MaxTap, MinTap, NumTaps equal the original's (rel 1e-9; text properties exactly).
- Spoke unit tests:
- the T6 nodes (sub3 .1.2.3.4 with wdg=2 Rneut=0 Xneut=0.4; ug .1.2.3.4 with no Rneut);
- a center-tap half at the can's kVA;
- yydc's tert.3.1 (T3);
- an instance holding only XfmrCode= and buses;
- the regulator's %Rs=[r/2 r/2];
- T4's per-tank names on a two-tank PowerTransformer.
The importer names no TransformerTank, so under name a several-tank transformer needs tank names. Without
them it raises, as any unnamed object does.
- Raises:
- two neutral impedances;
- a mesh r on balanced ends;
- an unset ptRatio;
- remote sensing;
- a line drop without ctRating;
- a mode other than voltage.
- Getters: T2 (a template Y with an instance Yn gives Yn), and T3 (a TankEnd coil in its phase-end order, plus
phase ends that are not the terminal's, which raise).
- Deck round trip: IEEE13_CDPSM still cannot run. Its loads and capacitors raise "no DSS export yet"
(_check_exported). (S6d found it also has PVSystems and Storage, so it waits for S6e; S6d's deck check runs on
four other engine decks.)
- Goldens: export/*.dss beside each atom (mrid).
- Suite: 1,090 passed. With the external decks (CIMHUB_DSS_DECKS, --roundtrip), all 607 opendss tests pass,
the sweep included.
Decisions for S6c (approved 2026-11-09, as recommended; T3 the phase-end option)¶
| # | question | recommendation |
|---|---|---|
| T1 | Forms | As the Forms table: an inline Transformer for ends, phase ends and regulators; an XfmrCode plus XfmrCode= instances for a TankConfiguration; a coil's kV/kVA are baseU/baseS, a 3-phase unit's ratedU/ratedS |
| T2 | Y vs Yn, template vs instance | Fix the getter: the kinds agree up to the grounding, and the instance's wins. The importer stays as built |
| T3 | Polarity of a 1-phase TankEnd instance | The importer gives such an instance a TransformerPhaseEnd per terminal conductor in the deck's node order, and BY_TANK_ENDS reads a coil's phases from them when present. Alternatives: the importer writes such an instance inline (BY_PHASE_ENDS, a listed difference), or it raises on a descending LL coil (IEEE4 YYD stops binding) |
| T4 | Several tanks on one PowerTransformer | One DSS Transformer per tank, named by the tank; a PowerTransformer with one tank is named by itself. A tap changer on a several-tank PowerTransformer raises until a producer writes one |
| T5 | An unused TransformerTankConfiguration | No XfmrCode, logged as a warning naming the skipped mRIDs: a template alone does not say its phases. Amended 2026-11-16 (the user's, for clallam_cim): a feeder package carries its utility's whole catalogue, so most of its templates are sibling feeders'; it raised before |
| T6 | Neutral impedance (amends E7) | The neutral goes on .4 with Rneut/Xneut (probe: on .1.2.3 it is shorted); an ungrounded wye, or an ungrounded coil neutral, is .4 with no Rneut; two neutral impedances on one transformer raise |
| T7 | Regulator impedance and range | %Rs=[r/2 r/2] (equal to %LoadLoss=r); MaxTap/MinTap/NumTaps from the step range; an unset step or ptRatio raises |
Slot tables (S6c, generated from SLOTS)¶
Transformer (exporter/transformer.py)
| DSS slot | kind | from / why |
|---|---|---|
| name | written | Names; a one-unit transformer by itself, each tank of several by the tank (T4) |
| phases | written | 3 when every winding has A, B, C, else 1 (a coil); inline units only; a unit on a TankConfiguration takes it from its XfmrCode |
| windings | written | the model's windings, 2 or 3; inline units only; a unit on a TankConfiguration takes it from its XfmrCode |
| wdg | written | the one winding grounded through rground/xground (T6) |
| bus | not mapped | the active-winding form; the arrays carry every winding |
| conn | not mapped | the active-winding form; the arrays carry every winding |
| kV | not mapped | the active-winding form; the arrays carry every winding |
| kVA | not mapped | the active-winding form; the arrays carry every winding |
| tap | not mapped | the active-winding form; the arrays carry every winding |
| pct_R | not mapped | the active-winding form; the arrays carry every winding |
| Rneut | written | rground (ohm) of winding wdg; its neutral on .4 (T6) |
| Xneut | written | xground (ohm) of winding wdg |
| buses | written | bus_ref of each winding's phases: a coil's N on .0; a 3-phase wye solid .1.2.3, else .1.2.3.4 (E7, T6) |
| conns | written | connectionKind D -> delta, Y/Yn/I -> wye; AUTO: wye with a neutral; inline units only; a unit on a TankConfiguration takes it from its XfmrCode |
| kVs | written | a coil's or an AutoTransformerEnd's baseU, a 3-phase winding's ratedU (kV); inline units only; a unit on a TankConfiguration takes it from its XfmrCode |
| kVAs | written | a coil's baseS (AUTO: ratedS), a 3-phase winding's ratedS (kVA); inline units only; a unit on a TankConfiguration takes it from its XfmrCode |
| taps | written | 1, and get_tap_ratio(actual) on the RatioTapChanger's winding |
| XHL | written | mesh (1,2) x, percent on winding 1's kVA; inline units only; a unit on a TankConfiguration takes it from its XfmrCode |
| XHT | written | mesh (1,3) x; inline units only; a unit on a TankConfiguration takes it from its XfmrCode |
| XLT | written | mesh (2,3) x; inline units only; a unit on a TankConfiguration takes it from its XfmrCode |
| Xscarray | not mapped | more than 3 windings raise |
| thermal | unset | untranscribed on import; not in CIM |
| n | unset | untranscribed on import; not in CIM |
| m | unset | untranscribed on import; not in CIM |
| flrise | unset | untranscribed on import; not in CIM |
| hsrise | unset | untranscribed on import; not in CIM |
| pct_loadloss | not mapped | %Rs carries the winding r (AUTO: the mesh r halved, T7) |
| pct_noloadloss | written | the core g (percent on winding 1's kVA); unset -> not written; inline units only; a unit on a TankConfiguration takes it from its XfmrCode |
| normhkVA | unset | untranscribed on import |
| emerghkVA | unset | untranscribed |
| sub | unset | untranscribed on import; not in CIM |
| MaxTap | written | get_tap_ratio(high) |
| MinTap | written | get_tap_ratio(low) |
| NumTaps | written | highStep - lowStep |
| subname | unset | untranscribed on import; not in CIM |
| pct_imag | written | the core b (percent); unset -> not written; inline units only; a unit on a TankConfiguration takes it from its XfmrCode |
| ppm_antifloat | unset | untranscribed on import; not in CIM |
| pct_Rs | rule | winding r x kVA_n / kVA_1 (AUTO: [r/2 r/2], T7); unset -> 0; inline units only; a unit on a TankConfiguration takes it from its XfmrCode |
| bank | unset | each DSS Transformer is its own PowerTransformer (DSS-2) |
| XfmrCode | written | the unit's TankConfiguration (BY_TANK_ENDS, BY_LUGS) |
| XRConst | unset | untranscribed on import; not in CIM |
| X12 | unset | untranscribed on import; not in CIM |
| X13 | unset | untranscribed on import; not in CIM |
| X23 | unset | untranscribed on import; not in CIM |
| LeadLag | unset | untranscribed on import; not in CIM |
| Core | unset | untranscribed on import; not in CIM |
| RdcOhms | rule | each winding's rDC (ohm), written per winding; an end has none -> not written; inline units only; a unit on a TankConfiguration takes it from its XfmrCode |
| Seasons | rule | the number of season ratings (season_ratings); none -> not written |
| Ratings | rule | the PowerTransformer's ApparentPowerLimits of type olt_season |
| normamps | unset | untranscribed on import; not in CIM |
| emergamps | unset | untranscribed on import; not in CIM |
| faultrate | unset | untranscribed on import; not in CIM |
| pct_perm | unset | untranscribed on import; not in CIM |
| repair | unset | untranscribed on import; not in CIM |
| basefreq | unset | untranscribed on import; not in CIM |
| enabled | written | get_in_service(which='normal'); unset -> not written |
| like | not mapped | the writer never writes like= |
Xfmrcode (exporter/xfmrcode.py)
| DSS slot | kind | from / why |
|---|---|---|
| name | written | Names, the XfmrCode namespace |
| phases | written | as the Transformer's (windings.py), read through the first unit; every unit must give the same |
| windings | written | as the Transformer's (windings.py), read through the first unit; every unit must give the same |
| wdg | written | as the Transformer's (windings.py), read through the first unit; every unit must give the same |
| conn | not mapped | the active-winding form; the arrays carry every winding |
| kV | not mapped | the active-winding form; the arrays carry every winding |
| kVA | not mapped | the active-winding form; the arrays carry every winding |
| tap | not mapped | the active-winding form; the arrays carry every winding |
| pct_R | not mapped | the active-winding form; the arrays carry every winding |
| Rneut | written | as the Transformer's (windings.py), read through the first unit; every unit must give the same |
| Xneut | written | as the Transformer's (windings.py), read through the first unit; every unit must give the same |
| conns | written | as the Transformer's (windings.py), read through the first unit; every unit must give the same |
| kVs | written | as the Transformer's (windings.py), read through the first unit; every unit must give the same |
| kVAs | written | as the Transformer's (windings.py), read through the first unit; every unit must give the same |
| taps | not mapped | a tap is the instance's |
| Xhl | written | as the Transformer's (windings.py), read through the first unit; every unit must give the same |
| Xht | written | as the Transformer's (windings.py), read through the first unit; every unit must give the same |
| Xlt | written | as the Transformer's (windings.py), read through the first unit; every unit must give the same |
| Xscarray | not mapped | more than 3 windings raise |
| thermal | unset | untranscribed on import; not in CIM |
| n | unset | untranscribed on import; not in CIM |
| m | unset | untranscribed on import; not in CIM |
| flrise | unset | untranscribed on import; not in CIM |
| hsrise | unset | untranscribed on import; not in CIM |
| pct_loadloss | not mapped | %Rs carries the winding r |
| pct_noloadloss | written | as the Transformer's (windings.py), read through the first unit; every unit must give the same |
| normhkVA | unset | untranscribed on import |
| emerghkVA | unset | untranscribed |
| MaxTap | not mapped | a tap is the instance's |
| MinTap | not mapped | a tap is the instance's |
| NumTaps | not mapped | a tap is the instance's |
| pct_imag | written | as the Transformer's (windings.py), read through the first unit; every unit must give the same |
| ppm_antifloat | unset | untranscribed on import; not in CIM |
| pct_Rs | rule | as the Transformer's (windings.py), read through the first unit; every unit must give the same; unset r -> 0 |
| X12 | unset | untranscribed on import; not in CIM |
| X13 | unset | untranscribed on import; not in CIM |
| X23 | unset | untranscribed on import; not in CIM |
| RdcOhms | written | as the Transformer's (windings.py), read through the first unit; every unit must give the same |
| Seasons | rule | the number of the template's season ratings; none -> not written |
| Ratings | rule | the TransformerTankConfiguration's ApparentPowerLimits of type olt_season |
| like | not mapped | the writer never writes like= |
Regcontrol (exporter/regcontrol.py)
| DSS slot | kind | from / why |
|---|---|---|
| name | written | Names, the RegControl namespace |
| transformer | written | the DSS Transformer of the tap's unit (one unit) |
| winding | written | the winding whose end holds the RatioTapChanger |
| vreg | written | targetValue (V) / ptRatio (primary_to_secondary); unset raises |
| band | written | targetDeadband (V) / ptRatio (primary_to_secondary); unset -> not written, the engine's default |
| ptratio | written | ptRatio, the tap's and the control's agreed; unset or <= 0 raises |
| CTprim | written | ctRating (A); unset -> not written, and a line drop then raises |
| R | written | lineDropR (ohm) x CTprim / ptRatio (line_drop_volts); unset -> not written (0) |
| X | written | lineDropX (ohm) x CTprim / ptRatio (line_drop_volts); unset -> not written (0) |
| bus | not mapped | the control must monitor its tap end's Terminal (remote sensing raises) |
| delay | written | initialDelay (s); unset -> not written |
| reversible | written | TapChangerControl.reversible |
| revvreg | written | reverseTargetValue (V) / ptRatio (primary_to_secondary); unset -> not written, the engine's default |
| revband | written | reverseTargetDeadband (V) / ptRatio (primary_to_secondary); unset -> not written, the engine's default |
| revR | written | reverseLineDropR (ohm) x CTprim / ptRatio (line_drop_volts); unset -> not written (0) |
| revX | written | reverseLineDropX (ohm) x CTprim / ptRatio (line_drop_volts); unset -> not written (0) |
| tapdelay | written | subsequentDelay (s); unset -> not written |
| debugtrace | unset | untranscribed or raising on import; not in CIM |
| maxtapchange | unset | untranscribed or raising on import; not in CIM |
| inversetime | unset | untranscribed or raising on import; not in CIM |
| tapwinding | not mapped | the tap winding is the monitored one |
| vlimit | not mapped | maxLimitVoltage raises (untranscribed on import) |
| PTphase | written | 1-based place of monitoredPhase among the winding's phase conductors; 1 on a 1-phase winding, whichever of its conductors CIM names |
| revThreshold | written | reversingPowerThreshold (kW) |
| revDelay | written | reversingDelay (s) |
| revNeutral | written | reverseToNeutral |
| EventLog | unset | untranscribed or raising on import; not in CIM |
| RemotePTRatio | unset | untranscribed or raising on import; not in CIM |
| TapNum | unset | untranscribed or raising on import; not in CIM |
| Reset | unset | untranscribed or raising on import; not in CIM |
| LDC_Z | unset | untranscribed or raising on import; not in CIM |
| rev_Z | unset | untranscribed or raising on import; not in CIM |
| Cogen | unset | untranscribed or raising on import; not in CIM |
| idle | unset | untranscribed or raising on import; not in CIM |
| idleReverse | unset | untranscribed or raising on import; not in CIM |
| idleForward | unset | untranscribed or raising on import; not in CIM |
| basefreq | unset | untranscribed or raising on import; not in CIM |
| enabled | written | the control's enabled; the tap's controlEnabled must agree |
| like | not mapped | the writer never writes like= |
S6d: loads, capacitors, CapControl (built 2026-11-09 at the user's word, with decisions L1-L7 as recommended)¶
Content: EnergyConsumer → Load, LinearShuntCompensator → Capacitor, the RegulatingControl of a shunt → CapControl. Plan §8.1 row S6d; DSS-5, DSS-7, S4-2, E4, E8 and E9 apply. The user approved S6d together with B4 ("go ahead and implement that and 6d"), so this spec was written alongside the code. Its decisions, L1-L7, are at the end of this section, as recommended; any of them can still be amended.
Layout¶
cimhub_opendss/src/cimhub_opendss/exporter/
injection.py a one-terminal device's bus1, phases, conn and a load's kV (Load, Capacitor; DER in S6e)
controls.py PTPhase and enabled, shared by RegControl and CapControl (moved out of regcontrol.py)
load.py EnergyConsumer (ConformLoad, NonConformLoad, StationSupply) -> Load
capacitor.py LinearShuntCompensator -> Capacitor
capcontrol.py RegulatingControl -> Capcontrol
EXPORT_ORDER gains load, capacitor, capcontrol after regcontrol. The writer's WRITE_ORDER already has
Capacitor before CapControl.
Connection (the importer's shared phase rule inverted)¶
bus1: the phase conductors (no neutral), A/B/C as 1/2/3 and s1/s2 as 1/2.- A wye device's neutral is the engine's node 0, so the device must be
grounded=true. Unset or false raises (an ungrounded or impedance-grounded neutral is not mapped, as on import). phaseConnectionY and Yn are wye and D is delta; I, G and unset raise.- A delta across two conductors is DSS's 1-phase delta, written in branch order A-B, B-C, C-A (L2). Engine
probe: CIM's PhaseCode
ACwritten.1.3gives the same YPrim, but the node order differs from the deck's.3.1. - A delta on another count raises.
Load¶
| DSS slot | from |
|---|---|
kW, kvar |
get_phase_loads total (kW, kVAr) |
kV |
the BaseVoltage (L1) |
model |
get_load_response: pure constant PQ → 1, Z → 2, I → 5; exponential → 4 with CVRwatts/CVRvars |
NumCust |
customerCount; unset → not written |
enabled |
get_in_service(which='normal') |
- kV (L1, E9): CIM gives a load no rating (S4-2), so
kVis the bus's: LL for delta and for 2 or 3 phases, LN for 1-phase wye. On a split-phase secondary the BaseVoltage (240 V) is the whole coil, so a leg is half of it (0.12) and a 2-phase wye leg pair is read by the engine's sqrt 3 rule (0.2078). A deck's rounded kV comes back as the bus's: IEEE13'skV=2.4as 2.40178. Probe: the YPrim moves by (2.4 / 2.40178)^2, 0.15 %. A constant PQ load solves to the same power, but a Z, I or CVR load's power moves by the same ratio. - Model (L3): a mix of fractions raises. ZIPV (model 8) and model 3 raise on import too.
- Per phase (E8, L4): when the
EnergyConsumerPhasevalues differ, each phase becomes a 1-phase wye Load<name>_<phase>. Its kV is LN, and the first carriescustomerCount, the othersNumCust=0, so the deck's total is CIM's. A delta load with unequal phases raises. The importer never writes phase values, so a unit test builds them. - Not written:
pf,kVA,xfkVA(kW and kvar carry the power);Vminpu,Vmaxpu,statusand the other untranscribed slots (L6, the engine's defaults).
Capacitor¶
kvar=get_shunt_reactive_power(sections='maximum', voltage='nominal')(kVAr), that is, bPerSection x nomU^2.maximumSectionsother than 1 raises (L5, as on import).kv=nomU, the voltage bPerSection was derived on.states=[sections], the sections in service. DSS has no normal state for a capacitor, sonormalSectionsis not written (L5). Asectionsother than 0 or 1 raises.conn,bus1andphasesas above, andenabled.
CapControl¶
One per RegulatingControl (a TapChangerControl is another class, RegControl's). It must regulate exactly one
LinearShuntCompensator; anything else raises, because other regulated equipment is not exported yet (L7).
| DSS slot | from |
|---|---|
type |
mode voltage, currentFlow, reactivePower, timeScheduled → voltage, current, kvar, time; others raise |
ONsetting, OFFsetting |
on_off_from_band(target, deadband): ON = target - deadband / 2 for voltage and time, + for current and kvar; then voltage / PTratio, current / CTratio, kvar in kvar, time in hours |
PTratio, CTratio |
ptRatio, ctRatio; unset → not written. A voltage control needs PTratio and a current control needs CTratio: unset raises |
element, terminal |
the monitored Terminal's equipment, as its record is named (Line.<line>, Line.<switch>, Capacitor.<shunt>; others raise), and its sequenceNumber |
capacitor |
the regulated shunt |
Delay |
the shunt's aVRDelay (s) |
PTPhase |
the 1-based place of monitoredPhase among the monitored equipment's phase conductors (controls.pt_phase, shared with RegControl) |
enabled |
the control's enabled; the shunt's controlEnabled must agree (controls.control_enabled) |
What raises:
- an unset targetDeadband (DSS needs both settings);
- minAllowedTargetValue, maxAllowedTargetValue, or a reverse target or deadband (no CapControl slot).
VoltOverride, Vmax, Vmin, DelayOFF and DeadTime are untranscribed on import (S4-5), so they come back at
the engine's defaults (L6).
Core changes¶
derived/control_band.py:band_from_on_off(the importer's midpoint and width, moved out ofon_off_target) and its inverseon_off_from_band, asderived/regulator.pydid for RegControl.- Getters: none new;
get_phase_loads,get_load_response,get_shunt_reactive_power,get_equipment_controlandget_base_voltageas built in G6.
Findings¶
- An XfmrCode that leaves its reactances unset. The engine reports XHL=7, XHT=35, XLT=30, but it builds the
instance with X near 0. Probe: YPrim almost purely resistive, while an inline transformer with the same unset
slots gets 7 %. The importer reads the reported defaults (DSS-6), so it disagrees with the engine on such a code.
No sweep deck has one; only the old
load/loadsatom did, and it now sets them (after CDPSM's CT5). Proposed follow-up: the importer raises on an XfmrCode with unset reactances. - Decks that solve when compiled (IEEE13_original, IEEE37, IEEE13_Assets) run
Solvewith controls on. That moves regulator taps and switches capacitors (IEEE13_Assets' time-controlledcap1is off at hour 0) before a comparison can read the model. A whole-deck YPrim and voltage comparison therefore compares solved states, and belongs to S6f. - IEEE37's
reg1cis a coil C → B, which an AutoTransformerEnd's PhaseCode holds as BC. It comes back.2.3, with its RegControl's node 2. Both windings reverse together, so it is the same coil. It is a listed node order difference; T3's phase ends cover templates only. - The IEEE13_CDPSM round trip waits for S6e: the deck also has PVSystems and Storage.
Tests¶
As built (tests/test_export_injection.py, 24 tests; core test_derived_control_band.py):
- Per atom, in the engine (§8.3), exported under name: per element, buses, NodeOrder and YPrim (rel 1e-9),
then the voltages. Under mrid/uri only the voltages. The atoms:
- load/loads. Changed so that it compares: the CVR loads' kV is now the bus's to full precision, and the
XfmrCode sets its reactances. load.house (0.208 → 0.2078) is the listed YPrim difference.
- capacitor/caps. Its switch now carries B3's 1 mOhm, so the bank behind it solves alike.
The import goldens do not change: kV is not written, and the switch impedance is untranscribed.
- Settings in the engine:
- every Load's phases, conn, kW, kvar, model, CVR exponents, NumCust and enabled (rel 1e-9), and its kV
within 1 %;
- every Capacitor's phases, conn, kvar, kv, states and enabled;
- every CapControl's element, terminal, capacitor, type, ratios, ON, OFF, Delay, PTPhase and enabled.
- Whole decks (IEEE13_original, IEEE123, IEEE37, IEEE13_Assets; vendored, about 1 s each): the same elements,
each on the same buses and node order (listed: IEEE37's reg1c/creg1c), and every Load, Capacitor (states
aside) and CapControl set alike.
- Spoke unit tests:
- the kV rule (LN, LL, a leg, two legs);
- branch order (.3.1);
- E8 per-phase loads, with the customer count;
- an open bank states=[0];
- ON/OFF rebuilt for all four types.
- Raises:
- mixed ZIP fractions;
- an ungrounded wye load;
- two sections;
- an unset deadband;
- an unset ptRatio on a voltage control;
- another mode;
- a control that regulates no shunt.
- Harness: engine_compare records a disabled element as disabled; the engine gives it no nodes.
- Goldens: export/loads.dss and export/caps.dss (mrid).
- Suite: 1,120 passed. With the external decks (CIMHUB_DSS_DECKS, --roundtrip), all 634 opendss tests pass,
the sweep included.
Decisions for S6d (recommended; built at the user's word 2026-11-09)¶
| # | question | recommendation |
|---|---|---|
| L1 | A load's kV | The BaseVoltage by E9 and DSS-5 (a leg half the coil, a 2-phase leg pair x sqrt 3). A deck's rounded kV comes back as the bus's, a listed YPrim difference. A 1-phase source's island (its BaseVoltage is the LN source voltage) is not told apart: no sweep deck has a 1-phase source, so a load there would be written at LN / sqrt 3 |
| L2 | 1-phase delta order | Branch order A-B, B-C, C-A (IEEE13's 692.3.1), since a PhaseCode has none |
| L3 | Load models | A pure ZIP is 1, 2 or 5 and exponential is 4; a mix raises (model 8, as on import) |
| L4 | E8 per-phase loads and NumCust | The first phase's load carries customerCount and the others 0, so the total is kept |
| L5 | Capacitor sections | One section; states=[sections] (actual), and normalSections is not written |
| L6 | Untranscribed settings | Load Vminpu/Vmaxpu/status, CapControl VoltOverride/Vmax/Vmin/DelayOFF/DeadTime: the engine's defaults |
| L7 | Which RegulatingControls | Every plain RegulatingControl is a CapControl on its one LinearShuntCompensator; one regulating anything else raises until S6e exports that equipment |
Slot tables (S6d, generated from SLOTS)¶
Load (exporter/load.py)
| DSS slot | kind | from / why |
|---|---|---|
| name | written | Names; one load per phase is |
| bus1 | written | bus_ref of the phase conductors; a wye's neutral is node 0, so it must be grounded |
| phases | written | the phase conductors; a delta across two is 1 |
| kV | written | the BaseVoltage: LL for delta and 2-3 phases, LN for 1-phase wye; a split-phase leg half the coil, a 2-phase wye leg pair x sqrt 3 (E9, DSS-5) |
| kW | written | get_phase_loads total p (kW); per phase when the phases differ (E8) |
| pf | not mapped | kvar carries q |
| model | written | get_load_response: a pure ZIP 1 (PQ), 2 (Z), 5 (I); exponential 4 (CVR); a mix raises |
| yearly | written | a ConformLoad's group LoadShape (S8); unset otherwise |
| daily | unset | untranscribed or raising on import; not in CIM |
| duty | unset | untranscribed or raising on import; not in CIM |
| growth | unset | untranscribed or raising on import; not in CIM |
| conn | written | phaseConnection Y/Yn -> wye, D -> delta; others raise |
| kvar | written | get_phase_loads total q (kVAr); per phase when the phases differ (E8) |
| Rneut | unset | untranscribed or raising on import; not in CIM |
| Xneut | unset | untranscribed or raising on import; not in CIM |
| status | unset | DSS solution control; untranscribed on import, the engine's default |
| load_class | unset | untranscribed or raising on import; not in CIM |
| Vminpu | unset | DSS solution control; untranscribed on import, the engine's default |
| Vmaxpu | unset | DSS solution control; untranscribed on import, the engine's default |
| Vminnorm | unset | DSS solution control; untranscribed on import, the engine's default |
| Vminemerg | unset | DSS solution control; untranscribed on import, the engine's default |
| xfkVA | not mapped | kW carries p |
| allocationfactor | not mapped | kW carries p |
| kVA | not mapped | kW and kvar carry the power |
| pct_mean | unset | untranscribed or raising on import; not in CIM |
| pct_stddev | unset | untranscribed or raising on import; not in CIM |
| CVRwatts | written | pVoltageExponent; model 4 only |
| CVRvars | written | qVoltageExponent; model 4 only |
| kwh | unset | untranscribed or raising on import; not in CIM |
| kwhdays | unset | untranscribed or raising on import; not in CIM |
| Cfactor | unset | untranscribed or raising on import; not in CIM |
| CVRcurve | unset | untranscribed or raising on import; not in CIM |
| NumCust | written | customerCount; unset -> not written; per phase on the first load, 0 on the others |
| ZIPV | not mapped | model 8 raises, as on import |
| pct_SeriesRL | unset | untranscribed or raising on import; not in CIM |
| RelWeight | unset | untranscribed or raising on import; not in CIM |
| Vlowpu | unset | DSS solution control; untranscribed on import, the engine's default |
| puXharm | unset | untranscribed or raising on import; not in CIM |
| XRharm | unset | untranscribed or raising on import; not in CIM |
| spectrum | unset | untranscribed or raising on import; not in CIM |
| basefreq | unset | untranscribed or raising on import; not in CIM |
| enabled | written | get_in_service(which='normal'); unset -> not written |
| like | not mapped | the writer never writes like= |
Capacitor (exporter/capacitor.py)
| DSS slot | kind | from / why |
|---|---|---|
| name | written | Names, the Capacitor namespace |
| bus1 | written | bus_ref of the phase conductors; a wye's neutral is node 0, so it must be grounded |
| bus2 | not mapped | a shunt has one terminal |
| phases | written | the phase conductors; a delta across two is 1 |
| kvar | written | get_shunt_reactive_power(sections='maximum', voltage='nominal') (kVAr); maximumSections other than 1 raises |
| kv | written | nomU (kV), the voltage bPerSection was derived on |
| conn | written | phaseConnection Y/Yn -> wye, D -> delta; others raise |
| cmatrix | not mapped | kvar carries the susceptance |
| cuf | not mapped | kvar carries the susceptance |
| R | unset | untranscribed or raising on import; not in CIM |
| XL | unset | untranscribed or raising on import; not in CIM |
| Harm | unset | untranscribed or raising on import; not in CIM |
| Numsteps | not mapped | one section; more raise, as on import |
| states | written | [sections], the sections in service (0 or 1); normalSections is not written |
| normamps | unset | untranscribed or raising on import; not in CIM |
| emergamps | unset | untranscribed or raising on import; not in CIM |
| faultrate | unset | untranscribed or raising on import; not in CIM |
| pctperm | unset | untranscribed or raising on import; not in CIM |
| repair | unset | untranscribed or raising on import; not in CIM |
| basefreq | unset | untranscribed or raising on import; not in CIM |
| enabled | written | get_in_service(which='normal'); unset -> not written |
| like | not mapped | the writer never writes like= |
CapControl (exporter/capcontrol.py)
| DSS slot | kind | from / why |
|---|---|---|
| name | written | Names, the CapControl namespace |
| element | written | the monitored Terminal's equipment: Line. |
| terminal | written | the monitored Terminal's sequenceNumber |
| capacitor | written | the one LinearShuntCompensator the control regulates |
| type | written | mode voltage, currentFlow, reactivePower, timeScheduled -> voltage, current, kvar, time; others raise |
| PTratio | written | ptRatio; unset -> not written, and a voltage control raises, as does one <= 0 |
| CTratio | written | ctRatio; unset -> not written, and a current control raises, as does one <= 0 |
| ONsetting | written | targetValue -+ targetDeadband / 2 (on_off_from_band), voltage / PTratio, current / CTratio; ON below OFF for voltage and time |
| OFFsetting | written | targetValue +- targetDeadband / 2 (on_off_from_band), voltage / PTratio, current / CTratio; an unset target or deadband raises |
| Delay | written | the shunt's aVRDelay (s); unset -> not written |
| VoltOverride | unset | untranscribed on import (S4-5); the engine's default |
| Vmax | unset | untranscribed on import (S4-5); the engine's default |
| Vmin | unset | untranscribed on import (S4-5); the engine's default |
| DelayOFF | unset | untranscribed on import (S4-5); the engine's default |
| DeadTime | unset | untranscribed on import (S4-5); the engine's default |
| CTPhase | unset | untranscribed or raising on import; not in CIM |
| PTPhase | written | 1-based place of monitoredPhase among the monitored equipment's phase conductors |
| VBus | unset | untranscribed or raising on import; not in CIM |
| EventLog | unset | untranscribed or raising on import; not in CIM |
| UserModel | unset | untranscribed or raising on import; not in CIM |
| UserData | unset | untranscribed or raising on import; not in CIM |
| pctMinkvar | unset | untranscribed or raising on import; not in CIM |
| Reset | unset | untranscribed or raising on import; not in CIM |
| ControlSignal | unset | untranscribed or raising on import; not in CIM |
| basefreq | unset | untranscribed or raising on import; not in CIM |
| enabled | written | the control's enabled; the shunt's controlEnabled must agree |
| like | not mapped | the writer never writes like= |
S6e: DER and reactors (built 2026-11-09 at the user's word, with decisions P1-P9 as recommended; P2 confirmed by the user)¶
Content: PowerElectronicsConnection → one PVSystem per PhotoVoltaicUnit and one Storage per BatteryUnit,
SynchronousMachine → Generator, SeriesCompensator → series Reactor. Plan §8.1 row S6e; S4b, E4, E8 and E9 apply.
The user asked for S6e with the old GDM code's chop of a shared inverter ("CIM permits multiple DC devices behind
single inverter, so we will need to chop up the inverter same way previous code did"), and with cim18v17's new
unit attributes (PowerElectronicsUnit.p, idlingP). The spec was written alongside the code. Its decisions, P1-P9,
are at the end of this section; the user confirmed P2 (the raise above a unit's share) on 2026-11-09.
Layout¶
cimhub_opendss/src/cimhub_opendss/exporter/
injection.py + rated_kv (a DER's kv from ratedU), equal_phases (E8; shared with load.py)
inverter.py a PowerElectronicsConnection chopped into one InverterPiece per unit (or per phase)
pvsystem.py PhotoVoltaicUnit -> PVSystem
storage.py BatteryUnit -> Storage
generator.py SynchronousMachine -> Generator (model 3 from its own voltage control)
reactor.py SeriesCompensator -> Reactor
EXPORT_ORDER gains pvsystem, storage, generator, reactor after capcontrol. capcontrol skips a
RegulatingControl that regulates one SynchronousMachine: the Generator carries it.
Inverters: the chop (P1-P4)¶
A DSS PVSystem or Storage is one inverter with one DC device. CIM lets several PowerElectronicsUnits share one
PowerElectronicsConnection (a PV array and a battery behind one inverter). get_inverter_units (core) chops the
connection the way the old GDM exporter did:
- Share: each unit's maxP / the units' total maxP (1 for one unit). Each unit takes its share of the
connection's ratedS, q, maxQ and minQ. With several units, every maxP must be above 0.
- p: each unit's own PowerElectronicsUnit.p (new in cim18v17) when every unit has one. Their sum must be the
connection's p (rel SUM_REL_TOL). When no unit has p, each takes its share of the connection's p (the GDM rule).
Some with p and some without raises.
- Names (P3): one unit keeps the connection's name (a round trip of a DSS deck is unchanged); several take their
units' names.
- Above the share (P2): a piece whose output is above its share of ratedS (KVA_REL_TOL 1e-9) raises, because
the engine would cut it. A DC-coupled PV that feeds its battery is the case: hybrid_h1's PV at 80 kW of a
100 kW maxP is inside its 100 kVA share, but the same PV at 300 kW on a 225 kVA share is not. The alternative,
each piece keeping the whole rating, was offered and not taken.
- Per phase (E8, P4): a connection with one unit and unequal phases gives one 1-phase device per phase,
<name>_<phase>. Each is a 1/n share of the connection and of the unit's own ratings (Pmpp, kWrated, the
energies, idlingP). Several units with unequal phases raise, and so does a delta inverter with unequal phases.
- A unit of a class other than PhotoVoltaicUnit, BatteryUnit and PowerElectronicsWindUnit (a Generator, below)
raises: DSS has no class for it.
Each piece's inverter slots:
| DSS slot | from |
|---|---|
bus1, phases, conn |
device_connection; cim18v17's connection has no grounded, so a wye inverter's neutral is node 0, as on import |
kv |
ratedU (kV, LL), / sqrt 3 for a 1-phase wye device (rated_kv, S4b-4 inverted). Not the bus's: a 240 V inverter on 120 V legs stays 240 V |
kVA |
share x ratedS |
kvarMax, kvarMaxAbs |
share x maxQ, share x -minQ; unset → not written |
Vminpu |
1 / maxIFault (the importer's rule inverted) |
enabled |
get_in_service(which='normal') |
PVSystem¶
Pmpp= the unit's maxP x its 1/n share.irradiance= the unit'sPhotoVoltaicUnit.irradiance(kW/m2, the gridappsd extension); unset, it falls back to p / Pmpp, so the panel gives exactly p.kvar= the piece's q (generation sign).%Pmpp= 100 x p / Pmpp when p is below the panel's Pmpp x irradiance (a PV cut to fit kVA, or held back); the engine caps the panel at it (S4b engine rules), so it gives CIM's p at the default P-T curve. Not written when p is the panel's power.%Cutout=0only when p > 0 and Pmpp x irradiance < 20 % of kVA (ENGINE_CUTOUT_PERCENT): the engine would switch the PV off below its default cut-out.- Raises: maxP unset or 0, minP other than 0, p into the PV, p above Pmpp x irradiance.
Storage (P6)¶
Statefrom batteryState: discharging, charging, waiting → idling. full, empty and unset raise. An output of the wrong sign for the state raises (a waiting battery with generation too: it only draws its idling loss), and so do charging a full battery and discharging at or below its reserve (the engine idles both, S4b).- The output is
%Discharge/%Charge= |p| / kWrated x 100, andkWis never written. The engine keeps the setpoint as a percent of the kWrated at the momentkWis assigned, and the writer puts kW before kWrated. Probe:kW=-5thenkWrated=5charges at 1 kW. kWrated= maxP x 1/n; minP must be -maxP (one kWrated both ways).kWhrated,kWhstoredscaled likewise;%reserve= minimumE / ratedE x 100;%EffCharge,%EffDischargefrom the efficiencies.%IdlingkW= idlingP / kWrated x 100 (new in cim18v17). A waiting battery's p must equal its idlingP (scaled) when both are set; otherwise its p is the idling loss. A negative idlingP raises: it is a loss. The engine honours both wrong signs, but the user chose to treat them as a mismatched input (decision 12).- q must be 0, as on import.
- The writer's order puts the energies before
State, which the engine checks when the state is assigned.
Generator (P7)¶
kW= -p andkvar= -q, kW first (S4b-8);kVA= ratedS;connfromearthing(true wye, false delta, unset raises; S4b-5);kvbyrated_kv.- Model 3 when the machine's enabled RegulatingControl is a voltage control on its own terminal:
Vpu= target / ratedU,Maxkvar/Minkvar= maxQ/minQ. A disabled control gives model 1, since DSS has no disabled PV bus. A control on another terminal, another mode, or a nonzero deadband, allowed limit or reverse target raises. Model 7 comes back as model 1 (CIM has no current limit; listed). Xd,Xdp,Xdpp,H,D,XRdpare unset: cim18v17 has no machine reactance or inertia (U13), so they take the engine's defaults (E4).- A PowerElectronicsWindUnit (user, 2026-11-09, for a GIS spoke) is a model 1 Generator at the unit's output:
inverter_piecesgives its name, bus,kv, its share of the inverter'skVA, and its share of p and q. DSS has no inverter wind class, and IEEE 9500 writes its turbines as Generators. The inverter's q limits andmaxIFaulthave no home on a model 1 Generator and are not written. The deck reads back as a SynchronousMachine.
Reactor (P8)¶
R,Xfromget_series_compensator(ohm);bus1/bus2fromline.terminal_buses;normamps/emergampsfromline.ratings.- A DSS Reactor has no mutual coupling: r0 or x0 other than r/x raises. A varistor raises.
Core changes¶
getters/der.py:get_inverter_units(connection, active_unit, reactive_unit, *, sign)→InverterUnitShare(unit, share, p, q)per unit, the chop above.getters/series_compensator.py(new):get_series_compensator→SeriesCompensatorData(r, x, r0, x0, compensator_type, varistor_present, varistor_rated_current, varistor_voltage_threshold), in ohm, A and V; r and x are required. Per unit is not offered: a SeriesCompensator has no base of its own.shapes/der.cimtbl:hybrid_h1, a 150 kVA two-unit inverter (a 100 kW PV at 80 kW and a 50 kW battery charging at 20 kW, net 60 kW out).
Findings¶
- A model 3 Generator's YPrim depends on
Xdp. IEEE8500'sSteamGen1sets 0.27 against the 0.28 default, a listed U13 difference in the solved state (S6f). - IEEE9500's Fuses come back named by the switch line they switch (a CIM Fuse is the switch, S6b), and E6 drops a SwtControl on a switch closed in both states. The deck test maps them.
- IEEE9500's regulator taps are moved by its in-deck
Solve, and the original does not converge with controls off at tolerance 1e-10. Its YPrim and voltages wait for S6f. - IEEE8500's
Master-unbalredirects a file the original does not have; the test usesMaster.dss. - A battery capped by its kVA keeps only the capped output in CIM, so its
%Dischargediffers (listed). - The
deratom's XfmrCodectleft its reactances unset (the S6d finding); it now sets them.
Tests¶
As built (tests/test_export_der.py, 29 tests; core test_getters_der.py, test_getters_series_compensator.py):
- Per atom, in the engine (§8.3), under name: per element, buses, NodeOrder and YPrim, then the voltages.
Under mrid/uri only the voltages. Atoms der/der, generator/gens, reactor/reactors (listed: the reactor
atom's load.l3, kV 2.4 → 2.40178, S6d L1).
- Settings in the engine: every PVSystem, Storage, Generator and Reactor slot the importer maps, and each PV's
dispatch after Compile (PVsystems.kW/kvar; irradiance and pf may come back otherwise for the same output).
- Whole decks (CIMHUB_DSS_DECKS, --roundtrip but CDPSM): IEEE13_CDPSM, IEEE123_PV, IEEE8500, IEEE9500,
ACEP_PSIL. The same elements on the same buses, and every DER and reactor set alike. Listed: classes the importer
does not map (relay.brkr1, the EnergyMeters, DSS-11) and the switch controls above.
- Spoke unit tests: the hybrid inverter (records, then 200 kW PV and 40 kW storage in the engine at its
shares), shares without p, the above-share raise, per phase, a wind unit, a full battery, a battery with q,
idling, a disabled machine control (model 1), a control of another terminal, unset earthing, a coupled reactor.
- Harness: engine_compare.engine_buses (compile only; a disabled element is ("disabled",)),
engine_settings and assert_same_settings, shared with test_export_injection.py.
- Goldens: export/der.dss, export/gens.dss, export/reactors.dss (mrid).
- Suite: 1,157 passed, 80 skipped, 2 xfailed; every binding sweep deck (18) exports with its elements on the
same buses.
Decisions for S6e (recommended; built at the user's word 2026-11-09)¶
| # | question | recommendation |
|---|---|---|
| P1 | Chopping a shared inverter | The GDM rule: share = maxP / the units' total; ratedS, q and the q limits by share; each unit's own p when all have one (summing to the connection's), else its share of the connection's p; a partial set raises |
| P2 | A unit above its share of ratedS (confirmed by the user 2026-11-09) | Raises, naming the unit, its output and its share. Giving each piece the whole rating was the alternative |
| P3 | Names of the pieces | One unit: the connection's; several: the units' |
| P4 | Unequal phases (E8) | One unit: one 1-phase device per phase, each 1/n of the connection and of the unit; several units or delta raise |
| P5 | PV output | irradiance = the unit's (the extension, 2026-11-10), else p / Pmpp, at Pmpp = maxP; %Pmpp holds the output at p below the panel; %Cutout=0 below the engine's 20 % so a running PV keeps running |
| P6 | Storage output | %Discharge/%Charge, never kW (the engine's percent of the kWrated of the moment); waiting is idling at idlingP |
| P7 | Generator model | 3 from an enabled voltage control on its own terminal; disabled → 1; model 7 → 1 (listed); reactances at the engine's defaults (U13) |
| P8 | Reactor coupling | r0/x0 must equal r/x; a varistor raises |
| P9 | DER kv | ratedU (S4b-4 inverted), not the bus's |
Slot tables (S6e, generated from SLOTS)¶
PVSystem (exporter/pvsystem.py)
| DSS slot | kind | from / why |
|---|---|---|
| name | written | Names: the connection's for one unit, the unit's for several, |
| phases | written | the phase conductors; a delta across two is 1 |
| bus1 | written | bus_ref of the phase conductors; a wye inverter's neutral is node 0 |
| kv | written | ratedU (kV, LL), / sqrt 3 for 1-phase wye (S4b-4 inverted) |
| irradiance | written | the unit's irradiance (kW/m2); unset -> the unit's output / Pmpp (get_inverter_units p, generation sign) |
| Pmpp | written | the unit's maxP (kW), x 1/n for one of n phases; unset raises, a minP other than 0 raises |
| pct_Pmpp | rule | 100 x output / Pmpp when the output is below Pmpp x irradiance, else not written; an output above it raises |
| Temperature | unset | untranscribed or raising on import; not in CIM |
| pf | rule | with a yearly shape whose q is in proportion to p: p / hypot(p, q) with the sign of q; else kvar carries q |
| conn | written | phaseConnection Y/Yn -> wye, D -> delta; others raise |
| kvar | written | the unit's share of q (generation sign: -q) |
| kVA | written | ratedS, the connection's, by the unit's share (inverter_pieces) |
| pct_Cutin | rule | 0 with a yearly shape, else not written |
| pct_Cutout | rule | 0 when the output is above 0 and Pmpp x irradiance below the engine's 20 % of kVA, or with a yearly shape; else not written |
| EffCurve | unset | untranscribed or raising on import; not in CIM |
| P_TCurve | unset | untranscribed or raising on import; not in CIM |
| pct_R | unset | untranscribed or raising on import; not in CIM |
| pct_X | unset | untranscribed or raising on import; not in CIM |
| model | not mapped | model 1, the engine's default; others raise on import |
| Vminpu | written | 1 / maxIFault (the importer's rule inverted); unset -> not written |
| Vmaxpu | unset | untranscribed or raising on import; not in CIM |
| Balanced | unset | untranscribed or raising on import; not in CIM |
| LimitCurrent | unset | untranscribed or raising on import; not in CIM |
| yearly | written | the connection's EnergyConnectionSchedule as a LoadShape, mult = p / (Pmpp x irradiance) (S9); %Cutin, %Cutout 0 and q by kvar or pf with it |
| daily | unset | untranscribed or raising on import; not in CIM |
| duty | unset | untranscribed or raising on import; not in CIM |
| Tyearly | unset | untranscribed or raising on import; not in CIM |
| Tdaily | unset | untranscribed or raising on import; not in CIM |
| Tduty | unset | untranscribed or raising on import; not in CIM |
| class_class | unset | untranscribed or raising on import; not in CIM |
| UserModel | unset | untranscribed or raising on import; not in CIM |
| UserData | unset | untranscribed or raising on import; not in CIM |
| debugtrace | unset | untranscribed or raising on import; not in CIM |
| VarFollowInverter | unset | untranscribed or raising on import; not in CIM |
| DutyStart | unset | untranscribed or raising on import; not in CIM |
| WattPriority | unset | untranscribed or raising on import; not in CIM |
| PFPriority | unset | untranscribed or raising on import; not in CIM |
| pct_PminNoVars | unset | untranscribed or raising on import; not in CIM |
| pct_PminkvarMax | unset | untranscribed or raising on import; not in CIM |
| kvarMax | written | maxQ, the connection's, by the unit's share (inverter_pieces); unset -> not written |
| kvarMaxAbs | written | -minQ, the connection's, by the unit's share (inverter_pieces); unset -> not written |
| kVDC | unset | untranscribed or raising on import; not in CIM |
| Kp | unset | untranscribed or raising on import; not in CIM |
| PITol | unset | untranscribed or raising on import; not in CIM |
| SafeVoltage | unset | untranscribed or raising on import; not in CIM |
| SafeMode | unset | untranscribed or raising on import; not in CIM |
| DynamicEq | unset | untranscribed or raising on import; not in CIM |
| DynOut | unset | untranscribed or raising on import; not in CIM |
| ControlMode | unset | untranscribed or raising on import; not in CIM |
| AmpLimit | unset | untranscribed or raising on import; not in CIM |
| AmpLimitGain | unset | untranscribed or raising on import; not in CIM |
| spectrum | unset | untranscribed or raising on import; not in CIM |
| basefreq | unset | untranscribed or raising on import; not in CIM |
| enabled | written | get_in_service(which='normal'); unset -> not written |
| like | not mapped | the writer never writes like= |
Storage (exporter/storage.py)
| DSS slot | kind | from / why |
|---|---|---|
| name | written | Names: the connection's for one unit, the unit's for several, |
| phases | written | the phase conductors; a delta across two is 1 |
| bus1 | written | bus_ref of the phase conductors; a wye inverter's neutral is node 0 |
| kv | written | ratedU (kV, LL), / sqrt 3 for 1-phase wye (S4b-4 inverted) |
| conn | written | phaseConnection Y/Yn -> wye, D -> delta; others raise |
| kW | not mapped | %Discharge/%Charge carry the output: the engine makes kW a percent of the kWrated of the moment, and kWrated is written after kW |
| kvar | not mapped | q must be 0 (it raises on import); another raises |
| pf | not mapped | q is 0 |
| kVA | written | ratedS, the connection's, by the unit's share (inverter_pieces) |
| pct_Cutin | unset | untranscribed or raising on import; not in CIM |
| pct_Cutout | unset | untranscribed or raising on import; not in CIM |
| EffCurve | unset | untranscribed or raising on import; not in CIM |
| VarFollowInverter | unset | untranscribed or raising on import; not in CIM |
| kvarMax | written | maxQ, the connection's, by the unit's share (inverter_pieces); unset -> not written |
| kvarMaxAbs | written | -minQ, the connection's, by the unit's share (inverter_pieces); unset -> not written |
| WattPriority | unset | untranscribed or raising on import; not in CIM |
| PFPriority | unset | untranscribed or raising on import; not in CIM |
| pct_PminNoVars | unset | untranscribed or raising on import; not in CIM |
| pct_PminkvarMax | unset | untranscribed or raising on import; not in CIM |
| kWrated | written | the unit's maxP (kW), x 1/n for one of n phases; unset raises, a minP other than -maxP raises |
| pct_kWrated | unset | untranscribed or raising on import; not in CIM |
| kWhrated | written | ratedE (kWh), x 1/n for one of n phases; unset -> not written |
| kWhstored | written | storedE (kWh), x 1/n for one of n phases; unset -> not written |
| pct_stored | not mapped | kWhstored carries the energy |
| pct_reserve | written | minimumE / ratedE x 100; either unset -> not written |
| State | written | batteryState charging, discharging, waiting -> charging, discharging, idling; others raise, and so does an output of the wrong sign (generation while waiting too) |
| pct_Discharge | written | discharging: the unit's output / kWrated x 100 |
| pct_Charge | written | charging: -(the unit's output) / kWrated x 100 |
| pct_EffCharge | written | chargingEfficiency (percent); unset -> not written |
| pct_EffDischarge | written | dischargingEfficiency (percent); unset -> not written |
| pct_IdlingkW | written | idlingP / kWrated x 100; waiting: its p (which idlingP, when set, must be); a negative idlingP raises |
| pct_Idlingkvar | unset | untranscribed or raising on import; not in CIM |
| pct_R | unset | untranscribed or raising on import; not in CIM |
| pct_X | unset | untranscribed or raising on import; not in CIM |
| model | not mapped | model 1, the engine's default; others raise on import |
| Vminpu | written | 1 / maxIFault (the importer's rule inverted); unset -> not written |
| Vmaxpu | unset | untranscribed or raising on import; not in CIM |
| Balanced | unset | untranscribed or raising on import; not in CIM |
| LimitCurrent | unset | untranscribed or raising on import; not in CIM |
| yearly | written | the connection's EnergyConnectionSchedule as a LoadShape, mult = output / kWrated (S9) |
| daily | unset | untranscribed or raising on import; not in CIM |
| duty | unset | untranscribed or raising on import; not in CIM |
| DispMode | rule | follow with a yearly shape, else not written |
| DischargeTrigger | unset | untranscribed or raising on import; not in CIM |
| ChargeTrigger | unset | untranscribed or raising on import; not in CIM |
| TimeChargeTrig | unset | untranscribed or raising on import; not in CIM |
| class_class | unset | untranscribed or raising on import; not in CIM |
| DynaDLL | unset | untranscribed or raising on import; not in CIM |
| DynaData | unset | untranscribed or raising on import; not in CIM |
| UserModel | unset | untranscribed or raising on import; not in CIM |
| UserData | unset | untranscribed or raising on import; not in CIM |
| debugtrace | unset | untranscribed or raising on import; not in CIM |
| kVDC | unset | untranscribed or raising on import; not in CIM |
| Kp | unset | untranscribed or raising on import; not in CIM |
| PITol | unset | untranscribed or raising on import; not in CIM |
| SafeVoltage | unset | untranscribed or raising on import; not in CIM |
| SafeMode | unset | untranscribed or raising on import; not in CIM |
| DynamicEq | unset | untranscribed or raising on import; not in CIM |
| DynOut | unset | untranscribed or raising on import; not in CIM |
| ControlMode | unset | untranscribed or raising on import; not in CIM |
| AmpLimit | unset | untranscribed or raising on import; not in CIM |
| AmpLimitGain | unset | untranscribed or raising on import; not in CIM |
| spectrum | unset | untranscribed or raising on import; not in CIM |
| basefreq | unset | untranscribed or raising on import; not in CIM |
| enabled | written | get_in_service(which='normal'); unset -> not written |
| like | not mapped | the writer never writes like= |
Generator (exporter/generator.py)
| DSS slot | kind | from / why |
|---|---|---|
| name | written | Names, the Generator namespace; a wind unit as inverter_pieces names it |
| phases | written | the phase conductors; a delta across two is 1 |
| bus1 | written | bus_ref of the phase conductors; a wye machine's neutral is node 0 |
| kv | written | ratedU (kV, LL), / sqrt 3 for 1-phase wye (S4b-4 inverted) |
| kW | written | get_der_output total p (kW, generation sign); a wind unit: its share of the connection's p (inverter_pieces) |
| pf | not mapped | kvar carries q |
| kvar | written | get_der_output total q (kVAr, generation sign), after kW; a wind unit: its share of q |
| model | written | 3 (ConstantPV) when an enabled control regulates its own terminal's voltage, else 1 (ConstantPQ); model 7 comes back as 1 |
| Vminpu | unset | untranscribed or raising on import; not in CIM |
| Vmaxpu | unset | untranscribed or raising on import; not in CIM |
| yearly | written | the machine's EnergyConnectionSchedule as a LoadShape, mult = p / kW (S9) |
| daily | unset | untranscribed or raising on import; not in CIM |
| duty | unset | untranscribed or raising on import; not in CIM |
| dispmode | unset | untranscribed or raising on import; not in CIM |
| dispvalue | unset | untranscribed or raising on import; not in CIM |
| conn | written | earthing true -> wye, false -> delta; unset raises |
| status | unset | untranscribed or raising on import; not in CIM |
| gen_class | unset | untranscribed or raising on import; not in CIM |
| Vpu | written | model 3: the control's target / ratedU |
| maxkvar | written | model 3: maxQ (kVAr); unset -> not written |
| minkvar | written | model 3: minQ (kVAr); unset -> not written |
| pvfactor | unset | untranscribed or raising on import; not in CIM |
| forceon | unset | untranscribed or raising on import; not in CIM |
| kVA | written | ratedS (kVA); a wind unit: its share of the inverter's ratedS |
| MVA | not mapped | kVA carries ratedS |
| Xd | unset | no machine reactance or inertia in cim18v17 (U13); the engine's default |
| Xdp | unset | no machine reactance or inertia in cim18v17 (U13); the engine's default |
| Xdpp | unset | no machine reactance or inertia in cim18v17 (U13); the engine's default |
| H | unset | no machine reactance or inertia in cim18v17 (U13); the engine's default |
| D | unset | no machine reactance or inertia in cim18v17 (U13); the engine's default |
| UserModel | unset | untranscribed or raising on import; not in CIM |
| UserData | unset | untranscribed or raising on import; not in CIM |
| ShaftModel | unset | untranscribed or raising on import; not in CIM |
| ShaftData | unset | untranscribed or raising on import; not in CIM |
| DutyStart | unset | untranscribed or raising on import; not in CIM |
| debugtrace | unset | untranscribed or raising on import; not in CIM |
| Balanced | unset | untranscribed or raising on import; not in CIM |
| XRdp | unset | no machine reactance or inertia in cim18v17 (U13); the engine's default |
| UseFuel | unset | untranscribed or raising on import; not in CIM |
| FuelkWh | unset | untranscribed or raising on import; not in CIM |
| pct_Fuel | unset | untranscribed or raising on import; not in CIM |
| pct_Reserve | unset | untranscribed or raising on import; not in CIM |
| Refuel | unset | untranscribed or raising on import; not in CIM |
| DynamicEq | unset | untranscribed or raising on import; not in CIM |
| DynOut | unset | untranscribed or raising on import; not in CIM |
| spectrum | unset | untranscribed or raising on import; not in CIM |
| basefreq | unset | untranscribed or raising on import; not in CIM |
| enabled | written | get_in_service(which='normal'); unset -> not written |
| like | not mapped | the writer never writes like= |
Reactor (exporter/reactor.py)
| DSS slot | kind | from / why |
|---|---|---|
| name | written | Names, the Reactor namespace |
| bus1 | written | terminal_buses (line.py): the first terminal on the phase conductors |
| bus2 | written | terminal_buses: the second terminal |
| phases | written | the phase conductors |
| kvar | not mapped | R and X carry the impedance; r0/x0 other than r/x raise |
| kv | unset | untranscribed or raising on import; not in CIM |
| conn | unset | untranscribed or raising on import; not in CIM |
| Rmatrix | not mapped | R and X carry the impedance; r0/x0 other than r/x raise |
| Xmatrix | not mapped | R and X carry the impedance; r0/x0 other than r/x raise |
| Parallel | not mapped | R and X carry the impedance; r0/x0 other than r/x raise |
| R | written | get_series_compensator r (ohm) |
| X | written | get_series_compensator x (ohm) |
| Rp | not mapped | R and X carry the impedance; r0/x0 other than r/x raise |
| Z1 | not mapped | R and X carry the impedance; r0/x0 other than r/x raise |
| Z2 | not mapped | R and X carry the impedance; r0/x0 other than r/x raise |
| Z0 | not mapped | R and X carry the impedance; r0/x0 other than r/x raise |
| Z | not mapped | R and X carry the impedance; r0/x0 other than r/x raise |
| RCurve | unset | untranscribed or raising on import; not in CIM |
| LCurve | unset | untranscribed or raising on import; not in CIM |
| LmH | not mapped | R and X carry the impedance; r0/x0 other than r/x raise |
| normamps | written | get_current_limits normal (A); unset -> not written |
| emergamps | written | get_current_limits emergency (A); unset -> not written |
| faultrate | unset | untranscribed or raising on import; not in CIM |
| pctperm | unset | untranscribed or raising on import; not in CIM |
| repair | unset | untranscribed or raising on import; not in CIM |
| basefreq | unset | untranscribed or raising on import; not in CIM |
| enabled | written | get_in_service(which='normal'); unset -> not written |
| like | not mapped | the writer never writes like= |
S6f: bus coordinates, power flow parity, idempotence (built 2026-11-09 at the user's word, with decisions F1-F7 as recommended)¶
Content: equipment Locations → Buscoords rows; whole-deck power flow parity in the engine (plan §5, §8.3); the
idempotence sweep. Plan §8.1 row S6f. The user asked for "the next phase" after confirming S6e's P2, so this spec
was written alongside the code. Its decisions, F1-F7, are at the end of this section; F3 and F5 carry an open
question each.
Layout¶
cimhub_core/src/cimhub_core/getters/location.py get_location_coordinates (new)
cimhub_opendss/src/cimhub_opendss/exporter/
buscoords.py equipment Locations -> Buscoords rows (last in EXPORT_ORDER)
regcontrol.py PTphase 1 on a 1-phase winding (a fix the idempotence sweep found)
cimhub_opendss/tests/
engine_compare.py + assert_same_power_flow, engine_coordinates
test_export_buscoords.py the coordinate atoms
test_export_decks.py parity and coordinates on 16 decks, idempotence on the 18 binding decks
The writer already writes Buscoords <stem>_buscoords.csv or LatLongCoords <stem>_latlongcoords.csv beside the
deck (S6a, §8.2).
Coordinates (F1)¶
The importer's S5-1 inverted. get_location_coordinates(equipment) (core) gives the Location's points in
PositionPoint sequenceNumber order and each Terminal's point:
- one point per Terminal: they pair in order (a one-Terminal POINT, a two-point LINESTRING);
- a two-terminal polyline (more than two points): its ends go to its Terminals (CIM's line route);
- one point on equipment with several Terminals: a device point (F8), which pairs with no Terminal, so terminals
is None;
- any other count raises, and so do a point without a sequenceNumber or a position, and two points with one
number. No Location, or a Location without points, is None. zPosition is not read.
buscoords.export gives each Terminal's bus of located equipment that Terminal's point, one row per bus in the
network's ConnectivityNode order:
- Equipment without a Location gives none, so a bus no located equipment touches has no coordinates, as on import
(S5-3).
- Two points for one bus that differ beyond math.isclose at rel 1e-4 and abs 1e-9 (POINT_REL_TOL,
POINT_ABS_TOL) raise, naming both pieces of equipment.
- Device points (F8, 2026-11-10): the importer puts a switch, fuse or transformer at its buses' centroid (S5-8),
so a device point places only the buses no Terminal point placed. With k of its N buses open, each goes at
(N · point − Σ placed) / k: a two-terminal device next to one placed bus reflects it across the point, which gives
back the importer's bus to float noise (the midpoint rounded a + b once); with none placed, every bus goes at the
point. A device with one open bus goes first, so a chain of switches fills from its placed end. The parity and
atom tests compare coordinates to rel 1e-12 / abs 1e-9 (assert_same_coordinates) for that noise. An import
under device_geometry="linestring" (S5-9) has no device points: each device's buses pair one per Terminal and
come back exactly.
- The CoordinateSystem picks the file: urn:ogc:def:crs:OGC:1.3:CRS84 is LatLongCoords (x = longitude, written
latitude first), OpenDSSLocalBusCoordinates is BusCoords (the importer's COORDINATE_SYSTEMS inverted).
Another URN, or Locations in two systems, raise.
- Non-conducting resources with a Location (a Substation) are skipped: they have no bus.
Power flow parity (F2-F4)¶
engine_compare.assert_same_power_flow(original, written): every node voltage within 0.1 % of its bus's base
(the original's kVBase), both decks solved with controls off at the original's control state and
untranscribed settings. What the written deck had otherwise is returned, and each deck's set is listed in the test
so the list stays true:
| copied from the original | why | decks |
|---|---|---|
Transformer.taps, Capacitor.states |
an in-deck Solve moves them; the importer reads the deck's text (F2) |
IEEE13_original, IEEE37, IEEE13_Assets (caps), IEEE123_PV, IEEE123_deconfliction, IEEE9500 |
earthmodel |
not in CIM (E10); Carson against the engine's Deri moves a geometry line's YPrim by 0.6 % | none since 2026-11-24 (S6g gave geometry decks an EarthResistivity; decks without geometry keep a floating one). It was IEEE13_CDPSM, IEEE13_Assets, IEEE4 Bal (DY, GrdYD, YD, YY), IEEE123_PV, IEEE9500, ACEP_PSIL |
Load.Vminpu/Vmaxpu |
not in CIM (L6); below Vminpu a load turns constant Z | IEEE13_CDPSM, every IEEE4 deck, IEEE8500 (all 1,177 loads Vminpu=.88), IEEE9500 |
Transformer.ppm_antifloat |
not in CIM; ppm=0 against the engine's 1 ppm moves a floating delta's voltage to ground |
IEEE123, 4bus-OYOD-UnBal, IEEE123_PV, IEEE123_deconfliction, IEEE8500, IEEE9500 |
earthmodel goes into a copy of the written deck after New Circuit (after Compile the lines are built); the
others are set after Compile. Results (worst node, % of the bus base):
| deck | nodes | worst |
|---|---|---|
| IEEE13_CDPSM | 57 | 0.056 % (675.3; the loads' kV 2.4 → 2.40178, L1) |
| IEEE13_original | 41 | 0.009 % |
| IEEE13_Assets | 41 | 0.010 % |
| IEEE123 | 278 | 0.015 % |
| IEEE123_PV | 442 | 0.017 % |
| IEEE123_deconfliction | 271 | 0.020 % |
| IEEE37 | 117 | 0.0003 % |
| IEEE4: DY, GrdYD, OYOD, YD, YY (Bal), OYOD-UnBal | 12-13 | 0.003-0.018 % |
| IEEE8500 | 8,531 | 0.072 % (a secondary; not traced further) |
| IEEE9500 | 9,536 | 0.095 % (m2001-mt1: B3's 1 mOhm switch against the original's 1e-6 ohm, 300 A from a 250 kVA microturbine) |
| ACEP_PSIL | 24 | 0.000 % |
Every deck's bus coordinates come back as the engine had them (engine_coordinates, compile only). Not in parity:
YYD-Master (it ends in a fault study with every load disabled, and its Export commands write files beside it)
and IEEE8500 Master-unbal (it redirects a file the original lacks).
Idempotence (F6)¶
export(import(export(import(deck)))) is the same text as export(import(deck)), deck and coordinate files, on all
18 binding sweep decks, under name_source="name". Under mrid it cannot be: the importer compiles an mRID from
the native name, so a second pass prefixes again (ln_ln_632633).
The sweep found one bug: IEEE37's creg1c (coil C → B) comes back .2.3, and the exporter wrote PTphase=2,
the place of C among the coil's conductors. A 1-phase DSS winding has one phase, and the importer raises on 2. The
exporter now writes 1 on a 1-phase winding; the re-import then monitors B, the same coil voltage.
Findings¶
- Protection has no trip settings (F5). Recloser
PhaseTrip/GroundTripand Relay settings are untranscribed (DSS-11's protection TODO). In a controls-on solve of the exported IEEE13_CDPSM,Recloser.Rec1trips at the engine's 1 A default, recloses and locks out after 7 control iterations. Parity runs controls off, so protection does not act there. - Protection controls are written disabled (V7, the user's rule 2026-11-09, until U15). Every Fuse and Recloser
control gets
enabled=no, keepingRatedCurrent,Shots,RecloseIntervalsand its states. Without CIM trip settings or curves, the engine's defaults locked out a GIS spoke's feeders behind their head reclosers on the first snapshot. A fuse blew under backfeed. The switch Line stays as CIM says, and an open switch is still opened by itsOpencommand (E6). The importer reads a disabled control back as the same Fuse or Recloser (itsenabledis untranscribed). The engine comparisons treat the original's controls as disabled (engine_compare.as_exported). Once U15 maps the settings, a device that has them is written enabled (switch.PROTECTION_ENABLED). - Controls on is fragile for parity (F2). From the same starting state, IEEE9500's
vreg3_aends on tap 3 in the original and 4 in the export: the 0.095 % differences tip one band decision. IEEE13_CDPSM's deck itself ends inSet Controlmode=OFFwith taps set by hand. - Untranscribed solution settings move voltages by percent (F3). Without them a plain solve of the exported IEEE8500 is 5.8 % off on its secondaries (Vminpu), the IEEE4 decks 2-9 % (earthmodel, Vminpu), 4bus-OYOD-UnBal 9 % (Vminpu 0.7, ppm).
- YYD-Master writes
YYDTestCase_*result files beside itself whenever the engine compiles it; the tests never compile it.
Tests¶
As built (core test_getters_location.py, 6 tests; opendss test_export_buscoords.py, 7; test_export_decks.py,
34):
- Getter: one point per Terminal, a polyline's ends, no Location, and the raises (a count the Terminals cannot
pair, a repeated number, a missing position).
- Coordinate atoms (buscoords/local, buscoords/latlong): the engine's coordinates equal the original's
(far stays without, ghost is no bus); lat-long written latitude first under LatLongCoords; b1's last row; the
raises (two points for one bus, an unmapped crsUrn, two systems).
- Parity and coordinates on the 16 decks above; idempotence on the 18 binding sweep decks. The external
decks are marked roundtrip.
- Suite: 1,194 passed. With the external decks and --roundtrip, every opendss test passes.
Decisions for S6f (recommended; built at the user's word 2026-11-09)¶
| # | question | recommendation |
|---|---|---|
| F1 | Bus coordinates | Each Terminal's point from its equipment's Location (one per Terminal, or a two-terminal polyline's ends); conflicting points raise; CRS84 → LatLongCoords, the local URN → BusCoords, others raise |
| F2 | Parity solve | Controls off, from the original's compiled taps and capacitor states; control settings are compared one by one (S6c, S6d). Controls on was the alternative: deterministic only when no band decision is near its edge |
| F3 | Untranscribed settings that move voltages (open; earthmodel closed by S6g) | The harness copies earthmodel, load Vminpu/Vmaxpu and transformer ppm_antifloat, listed per deck; the exporter leaves them at the engine's defaults (E4, E10, L6). Open: whether to give them a home (a CIMHub extension, or an exporter option such as load_vminpu=), since IEEE8500's export solves 5.8 % off without Vminpu |
| F4 | Tolerance | 0.1 % of the bus base (plan §5); the largest residual is B3's switch impedance on IEEE9500 (0.095 %) |
| F5 | Protection settings (open; reclosing closed by S6g, trip settings still open, G5) | Untranscribed for now (DSS-11), listed: the exported recloser trips at the engine's 1 A in a controls-on solve. Open: map Recloser PhaseTrip/GroundTrip (and Relay settings) once DSS-11's protection TODO picks the CIM classes |
| F6 | Idempotence | Under name_source="name", deck and coordinate files; mrid re-prefixes by design |
| F7 | Decks out of parity | YYD-Master (a fault study that writes files) and IEEE8500 Master-unbal (a missing redirect): idempotence only |
| F8 | Device points (2026-11-10, the user's pick) | A single POINT on multi-terminal equipment places only open buses, at (N · point − Σ placed) / k: reflection across the point next to a placed bus, the point itself with none. Placing every open bus at the point was the alternative: simpler and closer to real GIS, but a DSS round trip moves a bus only a device touches (a regulator's output) |
Slot table (S6f, generated from SLOTS)¶
Buscoords (exporter/buscoords.py)
| DSS slot | kind | from / why |
|---|---|---|
| name | written | the bus (Names.bus) of each Terminal of located equipment |
| x | written | the Terminal's PositionPoint xPosition (get_location_coordinates); a bus only a device point touches is solved from it as the centroid of the device's buses |
| y | written | as x, from yPosition |
| geographic | written | crsUrn CRS84 -> true (LatLongCoords), OpenDSSLocalBusCoordinates -> false; others raise |
S6g: earth model and reclose sequences (built 2026-11-09 at the user's word, with decisions G1-G5 as recommended)¶
Content: the user added EarthResistivity (WiresEXT) and rebuilt the protection profile with
RecloseSequence.ProtectedSwitch (2026-11-09). That gives two of S6f's open items a home: F3's earthmodel, and
the reclosing part of F5. Both directions are changed here, because each value must come back.
Layout¶
cimhub_core/src/cimhub_core/
getters/earth.py get_earth_resistivity (new): EarthData(model, rho ohm-m, earth_return_gmr m)
getters/switch_state.py + get_reclose_delays: the recloseDelay of each RecloseSequence, in step order
shapes/line_by_wire_configuration.cimtbl + EarthResistivity earth_carson on wc_601
shapes/switch.cimtbl + RecloseSequence sw_r1_rs1, sw_r1_rs2 (0.5 s, 2 s)
cimhub_opendss/src/cimhub_opendss/
schema/linkml/controls/recloser.yaml + dss_default Shots 4, RecloseIntervals [0.5 2 2] (DSS-6)
importer/cimtbl/geometry.py earth_statement: the deck's EarthResistivity, first in linegeometry.cimtbl
importer/cimtbl/line.py RecloseSequence rows; rho on a geometry line; spacing= configurations name the earth
exporter/options.py earthmodel = the configurations' one model
exporter/line.py rho on a geometry line
exporter/switch.py Recloser Shots and RecloseIntervals
Earth model (G1, G2)¶
Import. A deck with geometry (a LineGeometry, or a Line by spacing=) gets one EarthResistivity, mRID
earth, written first in linegeometry.cimtbl. Every WireConfiguration names it, the spacing= lines' synthesized
ones too.
- earthModelType comes from Set earthmodel: Carson → carson, Deri → deri. FullCarson raises, because
EarthModelKind has no member for it.
- rho is the geometry lines' rho, which must all agree.
- Unset values take the engine's defaults, Deri and 100 ohm-m, listed as # defaulted: (DSS-6).
- rho on a line without geometry raises: it computes nothing there.
- A deck without geometry that sets earthmodel gets the same EarthResistivity earth, floating: no line names
it, and rho is the default 100 ohm-m (defaulted: rho=100.0; the comment says no line names it). It keeps the
setting for the export. A deck with neither geometry nor earthmodel gets none, since its earth model computes
nothing (amended 2026-11-24: before, a deck without geometry got none and lost its Set earthmodel, which the
parity harness listed for IEEE13_CDPSM, IEEE123_PV, IEEE9500 and ACEP_PSIL; it no longer does).
Export.
- Set earthmodel is the one model of every WireConfiguration (options.earth_model). DSS's earthmodel is the
deck's, so configurations over different models raise. So does one without an EarthResistivity beside one with,
which would silently take the other's model. With no geometry at all, it is the network's one EarthResistivity,
which no line names (test_a_floating_earth_writes_the_earthmodel).
- Each geometry line writes rho from its configuration's EarthResistivity. DSS's LineGeometry has no rho.
- earthReturnGMR is not written: DSS derives Carson's earth return from rho and the frequency.
- The per-line EarthModel slot is not written; the deck's Set earthmodel carries it.
Profile note: EarthResistivity.rho is typed Resistance (ohm). A resistivity is ohm-m, and the profile has no
CIMUnit for it, so the value is read in ohm and stands for ohm-m (get_earth_resistivity).
Reclose sequences (G3, G4)¶
Import. A Recloser's Shots - 1 reclosures become one RecloseSequence each, <switch>_rs<n>, with
ProtectedSwitch the switch, recloseStep n and recloseDelay = RecloseIntervals[n] (s). The engine's rules,
probed:
- RecloseIntervals defaults to (0.5, 2, 2) and Shots to 4, and the engine keeps the first Shots - 1 intervals.
Unset values are defaulted from the schema's new dss_defaults and listed on the first row.
- Giving the intervals sets Shots to their count + 1, so both given and disagreeing raise: the engine's result
depends on their order.
- Shots above 4 without intervals raises: the engine reads past its three defaults (probe: 5.5e-310).
- Shots=1 gives no sequence.
All 53 IEEE9500 reclosers set Shots=3: two reclosures at 0.5 s and 2 s.
Export. A Recloser writes Shots = its RecloseSequences + 1 and RecloseIntervals their delays in step order
(get_reclose_delays; the steps must be 1..n, each with a delay). A recloser without sequences writes Shots=1: no
reclosure, as CIM says (G4). RecloseSequences on another ProtectedSwitch (a Breaker) raise: in DSS a Relay recloses
a breaker, and Relay is not mapped (DSS-11).
What is still open (G5)¶
- Trip settings. The pickups (
PhaseTrip,GroundTrip,PhaseInst,GroundInst), the curves (PhaseFast/PhaseDelayed/GroundFast/GroundDelayed), the time dials andNumFaststill have no attribute. In cim18v17 the overcurrent function blocks carry onlyoperatingQuantityType. So the exported recloser still trips at the engine's 1 A default in a controls-on solve (S6f F5). CIM17'sRecloserInfohadphaseTripRating,groundTripRatingandrecloseLockoutCount. A pickup (and a time-current curve link) onOverCurrentProtectionFunctionBlock, or an extension on the Recloser, would close it. EarthModelKindhas nofullCarson.- Fuse's minimum-melt association is spelled
MiinimumMeltCurvein the profile.
Findings¶
- The parity harness compared the original's earth model with the engine's Deri, not with the written deck. It now
compiles the written deck and reads its earthmodel. With S6g,
earthmodeldrops from the parity lists of every deck with geometry: IEEE13_Assets and the IEEE4 Bal decks (DY, GrdYD, YD, YY). Since the floating EarthResistivity (2026-11-24) it drops from the rest too: IEEE13_CDPSM, IEEE123_PV, IEEE9500 and ACEP_PSIL.
Tests¶
- Core:
test_getters_earth.py(2) andtest_getters_reclose.py(4): model and rho; no earth; delays in order and in ms; no sequence; a missing step; an unset delay. - Import:
- goldens:
line/codes(sw_rec1's two sequences),line/geometry,geometry/assets_linegeometry(EarthResistivity earth), IEEE13_CDPSM'sline.cimtbl; test_cimtbl_line.py: the four reclose rules, and three new raises (Shots=6 without intervals, Shots and intervals disagreeing, rho without geometry);test_cimtbl_geometry.py: the deck's model and rho, the defaults, FullCarson, disagreeing rho, no geometry.- Export:
- goldens:
line/codes,line/geometry,line/cables,line/states(Set earthmodel=Deri,rho=100,Shots=3 RecloseIntervals=[0.5 2]); test_export_line.py: the engine'sShots/RecloseIntervalsequal the original's oncodesandstates; a recloser without sequences isShots=1; sequences on a Breaker raise; geometry lines write their earth; two earth models raise.- Every atom's YPrim and voltages are still equal in the engine.
Decisions for S6g (recommended; built at the user's word 2026-11-09)¶
| # | question | recommendation |
|---|---|---|
| G1 | Where the earth goes | One EarthResistivity per deck (DSS's earthmodel is global), named by every WireConfiguration; rho from the geometry lines, which must agree; defaults listed (DSS-6) |
| G2 | Earth on export | Set earthmodel from the configurations' one model (several raise); rho on each geometry line |
| G3 | Reclosures on import | Shots - 1 RecloseSequences at RecloseIntervals, the engine's defaults filling either; the cases the engine resolves by order or by reading past its defaults raise |
| G4 | A recloser with no RecloseSequence | Shots=1, no reclosure, as CIM says, rather than the engine's 4 |
| G5 | Trip settings (open, TODO U15) | Still untranscribed: they need an attribute in the profile (see "What is still open"). Tracked as .development/UPSTREAM_REQUESTS.md U15 until the user repairs the FunctionBlock package in the UML |
S6h: multi-circuit lines, empty Feeders, bus sections (built 2026-11-19 at the user's word; H1 with jumpers, H4-H7 as recommended)¶
Found by exporting the CIMTBL-Models boundary_example (feeder s1-f2 alone, and s1-f2 with s1-f3 on their shared
double-circuit first span). H4-H7 came from GIS-derived feeders, whose groups are mostly a primary span with the
secondary underbuilt on the same poles, drawn with lengths that differ (median 6 %, at most 88 times).
Multi-circuit lines (H1, H4-H7)¶
- Which lines are coupled (
linegeometry.coupled_groups, found once per export asExportContext.coupled): the lines of oneMultiCircuitGroupat its highest nominal voltage, when two or more of them are in the network. Each is a spacing line or a line with geometry (a WireConfiguration naming a WireSpacing, as on a template double-circuit spacing with a configuration per circuit), and a group may mix the two. A line's wires are its configuration's WireSequenceConfigurations or its phases' WireInfo (line_wires), by sequence number, and there must be one on each of its phases' sequence numbers. - The group's lines at another voltage (an underbuilt secondary) are written on their own positions, uncoupled (H5). One line would put them on a bus with the primary's voltage base.
- One line of a group alone, as in a feeder exported on its own, is an ordinary line on its own positions (1, 2, 3, 7 for s1-f2).
- A group whose coupled lines name one phase position (series pieces of one circuit, such as a span split at a tap) is written uncoupled, with a warning (H7): one coupled line cannot carry them.
- The geometry
<group>_geometry: every line's phase conductors in circuit order (the lines ordered by their lowest phase sequence number), then the neutrals in sequence-number order. A position several lines name is one conductor, as in the EPRI ConductorPosition model (H6), so a shared neutral is written once, on one wire.SharedPhasesis not needed; where an ACLineSegmentPhase names a MultiCircuitGroup, it must be its line's.nphasesis every coupled line's phases, andreduce=y(B4). - The line
<group>: one Line on the geometry from bus<group>_1to<group>_2, each circuit's phase conductors on the next nodes (.1.2.3, then.4.5.6), over the shortest line's length (to the mm). The lines must agree on spacing, ySpacingOffset, earth, ratings and in-service state, which the one Line carries. Itsrhois every line'sline_rho: a spacing line's network earth, a configuration line's EarthResistivity (unset: none). - The ends. A DSS terminal is on one bus, and the circuits end on different nodes:
- each circuit has a jumper
<line>_jumper1from its node 1 onto its nodes of<group>_1, with the switches' invented 1 mOhm (B3, nowline.SWITCH_IMPEDANCE). It is notSwitch=y: it is a conductor, not a switch; - a line no longer than the group has
<line>_jumper2from<group>_2onto its node 2; - a longer line goes on as
<line>, its own section from its nodes of<group>_2to its node 2, on its own positions, for the rest of its length (H4). Every circuit keeps its exact length.
Terminal 1 of every line of a group is taken to be at the same end of the structure, and the coupled span to start there: CIM does not say which ends meet, or where along the longer line the shorter one runs. - Raises: a coupled line without geometry; a coupled line whose wires are not on its phases' sequence numbers; coupled lines that differ on spacing, offset, earth, ratings or in-service state; a shared position on different wires; a phase naming another group. - Not imported back. The DSS importer raises on the group's Line (nodes 4-6 have no phase), so an exported multi-circuit deck does not round-trip yet. Importing DSS multi-circuit lines into a MultiCircuitGroup is separate work.
Empty Feeders (H2)¶
A frame model declares the Feeders of its whole area (the boundary example's dso_area.cimtbl declares all five,
under two substations), and a deck holds only those whose equipment it has. Among several Feeders, one that
contains no equipment is not counted. A Feeder alone still names the circuit, even when empty: the DSS importer
puts a source-only deck's source in a Substation.
Bus sections (H3)¶
A BusbarSection is its node's bus. DSS has no element for it, so it writes no record
(buses.BUS_CLASSES, counted as exported by _check_exported).
Tests¶
test_export_line.py:- the coupled group's records;
- its YPrim equal to the same structure written by hand in DSS units (rel 1e-9), with the circuits' mutual block nonzero;
- a lone line of a group on its own positions;
- a longer line's remainder (H4), which solves;
- a shared neutral without SharedPhases (H6);
- an underbuilt secondary left uncoupled (H5);
- series pieces left uncoupled, with the warning (H7);
- five raises;
- lines on a template spacing's WireConfigurations, and one of them with a spacing line, coupled to the same records as two spacing lines (frame-boundary-agent, 2026-11-24), and two raises (the earths differ, a wire off its line's phases);
- an unused configuration of that template written on its own four positions, not the spacing's seven.
test_export_circuit.py: an empty Feeder of another substation is not counted.test_export_framework.py: a BusbarSection writes nothing.
Decisions for S6h¶
| # | question | decision |
|---|---|---|
| H1 | A MultiCircuitGroup | One DSS line on the whole structure when two or more of its lines are coupled, with a 1 mOhm jumper at each end of each circuit; a lone line keeps its own positions. A precomputed 6x6 matrix is not an option (skill conductor-geometry) |
| H2 | Feeders in a frame-model assembly | Among several, empty Feeders are not counted |
| H3 | BusbarSection | Its node's bus; no record |
| H4 | Lines of one group with different lengths (user, 2026-11-19) | Coupled over the shortest line's length; the rest of each longer line is its own uncoupled section at its terminal-2 end |
| H5 | An underbuilt secondary in a group (user, 2026-11-19) | Only the lines at the group's highest nominal voltage are coupled; the others stay on their own positions |
| H6 | A shared conductor (user, 2026-11-19) | One position on several lines is one conductor (EPRI ConductorPosition); SharedPhases is not required |
| H7 | Series pieces of one circuit in a group (user, 2026-11-19) | The group is written uncoupled, with a warning |
S8: load shapes (built 2026-11-21 at the user's word)¶
The importer's S8 inverted (CIMTBL_MAPPING.md#s8-load-shapes), as GLM's X29 writes players.
Layout¶
exporter/loadshape.py: eachConformLoadSchedulewith points is aLoadShapenamed after its group (theLoadshapenamespace ofNames);CIM_CLASSES = (), as a schedule is not conducting equipment.exporter/load.py: a ConformLoad whose group's schedule is a shape names it asyearly, on each per-phase load too (E8).DssExporter(time_points)/cim_to_dss(..., time_points=): the caller's time point tables (read_time_points, or the dict an importer filled), read throughcimhub_core.getters.load_schedule(get_schedule_points: the points numbered 0, 1, ... in order, value2 set at all points or none).ExportContext.pointsholds theRegularTimePointrows by schedule uri.- The writer writes
Loadshapefirst (WRITE_ORDER): a Load names its shape when it is defined.
Rules¶
nptsthe number of points;multvalue1;qmultvalue2, not written when value2 is unset (Q followsmult);sintervalthetimeStepin seconds, whatever unit the import read (an hourlyinterval=1comes back assinterval=3600: the engine's interval is the same).startTimeis not written: DSS has no date. The first point is sample 1, in force one interval into the run, which is what the importer'sstartTimesays of a DSS shape (S8-3). A GLM player's date (2009-07-21) is lost.- A value unit other than none (a multiplier) on a ConformLoadSchedule raises.
- Written static, their groups named in one warning: a ConformLoad whose group has no schedule (M1's
npts-less shapes, GLM's undefined players), a schedule with no points (or notime_points), a group of days by season and day type (a GLM schedule's, GLM S9: DSS has no calendar), and a NonConformLoad (its schedule is actual power, which onlyUseActualholds, and a UseActual shape's snapshot depends on command order: S8-6). - Shapes are shared (
ShapeRegistry, also S9's): owners whose export name, interval and multipliers agree name one LoadShape; another of that name with other points takes a suffix_2,_3.
Expected differences (round trip)¶
| what | why |
|---|---|
interval=/minterval= come back as sinterval= |
one written form; the engine's interval is equal |
a shape no Load names, and a Load's daily / duty |
not imported (S8-1, S8-7) |
M1's mult=1 shapes (no npts) are not written; their loads have no yearly |
the engine reads no points from them: the loads are constant either way (S8-5) |
Tests¶
test_export_loadshape.py: the atom's export golden (atoms/loadshape/export/loadshapes.dss); the original and the export in the engine in yearly mode every 5 minutes for 6 hours, every load's kW and kvar equal (rel 1e-9: the intervals, the normalized shape,qmult, the wrap); without points the loads are static with the warning; the loads made NonConform are static; a schedule in W raises.tests/cross_format/test_glm_player_to_dss.py: a GLM player through CIM to a LoadShape, solved in yearly mode at 60 s steps as the deck fixed at each step's value (rel 1e-9, the fifth step wrapping to the first).
Slot tables (S8, generated from SLOTS)¶
LoadShape (exporter/loadshape.py)
| DSS slot | kind | from / why |
|---|---|---|
| name | written | the group's name (Names) |
| npts | written | the number of points |
| interval | unset | not in CIM; the engine's default |
| mult | written | value1 of each point, in sequence order |
| hour | unset | not in CIM; the engine's default |
| mean | unset | not in CIM; the engine's default |
| stddev | unset | not in CIM; the engine's default |
| csvfile | unset | not in CIM; the engine's default |
| sngfile | unset | not in CIM; the engine's default |
| dblfile | unset | not in CIM; the engine's default |
| action | unset | not in CIM; the engine's default |
| qmult | written | value2 of each point; unset when value2 is (Q follows mult) |
| UseActual | unset | not in CIM; the engine's default |
| Pmax | unset | not in CIM; the engine's default |
| Qmax | unset | not in CIM; the engine's default |
| sinterval | written | timeStep (s) |
| minterval | unset | not in CIM; the engine's default |
| Pbase | unset | not in CIM; the engine's default |
| Qbase | unset | not in CIM; the engine's default |
| Pmult | unset | not in CIM; the engine's default |
| PQCSVFile | unset | not in CIM; the engine's default |
| MemoryMapping | unset | not in CIM; the engine's default |
| Mode | unset | not in CIM; the engine's default |
| Interpolation | unset | not in CIM; the engine's default |
| like | not mapped | the writer never writes like= |
S9: device shapes (built 2026-11-21 at the user's word)¶
The importer's S9 inverted (CIMTBL_MAPPING.md#s9-device-shapes): a PV's, battery's or machine's own
EnergyConnectionSchedule with points is its yearly LoadShape.
Layout¶
cimhub_core.getters.device_schedule.get_device_schedule: the equipment's oneEnergyConnectionSchedulewith points, p and q in the caller's units and sign (here kW, kVAr, generation), the step when the points are even; interpolation other than previous, a column null at some points only, and two schedules with points raise.exporter/loadshape.py:device_schedule(uneven points raise; so does a schedule on a connection written as several DSS objects, or with several units: one shape would scale them by one multiplier, which CIM does not say) anddevice_yearly(the sharedShapeRegistry).ExportContext.device_pointsholds theEnergyConnectionTimePointrows by schedule uri.exporter/pvsystem.py,storage.py,generator.py: the multipliers, the device's own slots, and the shape record before the device's when it is new.
Rules¶
- Generator: mult = p / kW (the written kW, generation sign); each point's q must be kvar x mult (the engine scales them together), unless the machine is model 3; a kW of 0 raises.
- PVSystem: mult = p / (Pmpp x irradiance), the irradiance it scales;
%Cutin=0 %Cutout=0, so the engine gives each point's p, low ones too (an off sample has p 0). q:kvarwhen every point's q is the written kvar (an off PV keeps it, S9-5), elsepf= p / hypot(p, q) with q's sign when q is in proportion to p; another q raises, as does a point above the written %Pmpp cap or below 0 kW (the engine reads a negative multiplier as 0). - Storage:
DispMode=follow; mult = output / kWrated, 0 where the output is the idling loss;Stateis not written (the importer raises on a follow-mode battery with one), so its snapshot idles, which batteryState must say (waiting). A point above kVA or a q other than 0 raises. - As for loads,
startTimeis not written: the first point is sample 1, one interval into the run.
Expected differences (round trip)¶
| what | why |
|---|---|
a PV's %Cutin/%Cutout come back 0, its q rule as kvar or pf |
the engine gives the points' p and q with them |
| a battery's capped sample comes back at the cap (80 kVA: mult 0.8, not 1) | the schedule holds the output |
devices sharing a shape whose multipliers differ (a PV cut to fit) get their own shapes, sun_2 |
one shape scales one way |
a battery's %Charge, %Discharge, State |
follow mode does not use them |
Tests¶
test_export_device_shape.py: the atom's export golden (atoms/loadshape/export/devices.dss); the original and the
export in the engine in yearly mode every 30 minutes for 8 hours, every device's kW and kvar equal (rel 1e-6:
both intervals, the PVs off and cut to fit, the battery capped, the wrap); shared shapes; without points the devices
are static; a generator's q off kvar x mult, a PV's q off both rules, a PV point above its cap, a battery's q or a
point above its kVA, and uneven points raise.