Conversion reference¶
What happens to each DSS class when a deck becomes CIM and when CIM becomes a deck. The pages are lookup tables, one section per DSS class. For the steps of a conversion see the user guide; for the code behind it, the developer docs; for the complete design records, the import mapping and the export mapping.
The core site documents what the spoke is built on: the getters,
the .cimtbl contract, the
canonical shapes and its
reference. All CIM names here are cim18v17.
Which classes convert¶
Import is the MAPPING_ORDER of the importer; export is the EXPORT_ORDER of the exporter. A DSS class that is in
neither is read by DssReader and never converted: the importer counts it in the master's not mapped: comment, and
the exporter has nothing to write it from.
| DSS class | CIM classes | Import | Export | Page |
|---|---|---|---|---|
Vsource, New Circuit |
EnergySource |
yes | yes | sources |
Set options, Open, Close |
BaseFrequency, BaseVoltage, EarthResistivity, Switch.open |
some | some | sources |
| buses | ConnectivityNode, BaseVoltage |
yes | yes | sources |
BusCoords, LatLongCoords |
CoordinateSystem, Location |
yes | yes | sources |
WireData |
OverheadWireInfo |
yes | yes | lines |
CNData |
ConcentricNeutralCableInfo |
yes | yes | lines |
TSData |
TapeShieldCableInfo |
yes | yes | lines |
LineSpacing |
XYSpacing, XYConductorPosition |
yes | no (inline in LineGeometry) |
lines |
LineGeometry |
WireConfiguration, WireSequenceConfiguration |
yes | yes | lines |
LineCode |
PerLengthPhaseImpedance, PhaseImpedanceData, PerLengthSequenceImpedance, WireConfiguration |
yes | yes | lines |
Line |
ACLineSegment, OperationalLimitSet, CurrentLimit |
yes | yes | lines |
Line with Switch=y, Fuse, Recloser, SwtControl |
LoadBreakSwitch, Fuse, Recloser, RecloseSequence |
yes | yes | lines |
Reactor (series) |
SeriesCompensator |
yes | yes | lines |
XfmrCode |
TransformerTankConfiguration |
yes | yes | transformers |
Transformer |
PowerTransformer, PowerTransformerEnd, TransformerTank, VoltageRegulator, AutoTransformerEnd |
yes | yes | transformers |
RegControl |
TapChangerControl, RatioTapChanger |
yes | yes | transformers |
LoadShape |
ConformLoadGroup, ConformLoadSchedule, EnergyConnectionSchedule |
yes (a shape a Load, PVSystem, Storage or Generator names as yearly) |
yes, with time_points |
loads |
Load |
EnergyConsumer, ConformLoad, LoadResponseCharacteristic |
yes | yes | loads |
Capacitor |
LinearShuntCompensator |
yes | yes | loads |
CapControl |
RegulatingControl |
yes | yes | loads |
PVSystem |
PowerElectronicsConnection, PhotoVoltaicUnit |
yes | yes | der |
Storage |
PowerElectronicsConnection, BatteryUnit |
yes | yes | der |
Generator |
SynchronousMachine, RegulatingControl |
yes | yes | der |
InvControl, Relay, meters, faults, other DSS classes |
none | no | no |
A Fuse, Recloser or SwtControl is read by the Line mapper, which takes its switch class and state from it, so it
has no part of its own. On export a CIM AutoTransformer is written as a Transformer, and a switch class other than
Fuse and Recloser as a LoadBreakSwitch. Conducting equipment of a class no exporter module writes raises
(no DSS export yet for {...}), so nothing is dropped silently.
How to read a section¶
Each section starts with the CIM classes and the .cimtbl shape a DSS class becomes, then a table of its DSS properties,
its fail-fast rules, what a round trip changes, and a short excerpt copied from a golden file in
cimhub_opendss/tests/atoms/. A property row has three columns:
| Column | Says |
|---|---|
| property | the DSS property, as the schema names it (DSS names are case-insensitive) |
| import | what the importer does with it: the field class, and for a copied value the CIM Class.attribute and the unit in the .cimtbl header |
| export | what the exporter does: how it is written back and which getter it reads |
Properties the mapper does not read, and the exporter does not write, are grouped in one row at the foot of the table.
The five field classes (import)¶
Every property of a mapped DSS class has exactly one of these, and a test checks that the classification covers every slot of the schema.
| Class | Means |
|---|---|
| copied | the value lands unchanged in a column, with its source unit in the header (r (ohm/mi), length (ft)) |
| mapped | the value goes through a code table, such as a DSS units word to a header unit |
| structural | the value decides rows: one record becomes several rows, or a value sits on one specific row, or it names another object |
| derived | the value is computed by a named, tested function, because CIM has no attribute for the source quantity (thevenin_from_short_circuit, b_from_c) |
| untranscribed | CIM has no home for it; it is recorded in a comment on the artifact, never dropped silently |
Export slot kinds¶
Every slot of a DSS class is listed by the exporter, so nothing is dropped unnoticed. The export column shows one of three:
| Kind | Means |
|---|---|
| written | the value comes from a getter and is written |
| written by rule | CIM leaves the value unset and DSS needs one; the rule is stated (an unset C1 is written 0, so the engine's default capacitance never applies) |
| not written | CIM cannot hold it, so the engine's default applies, or another form of the same data is written instead (C1 for B1) |
Units and fail-fast¶
Values are copied in the deck's own units and the unit is in the .cimtbl column header; cimtables converts them when it
builds the model. A header such as ohm/{length} stands for the unit the row states (ohm/mi). On export the
getters convert once, through get_qty, to the unit DSS expects: lengths in metres, per-length values per metre, voltages
in kV. See Units, bases and signs on the core site.
"Raises" means fail fast: the mapper stops with a ValueError that names the class, the object and the rule, and nothing
is guessed. Unknown fields, unmapped enumerations and unresolved references all raise. IDs are quoted, never sanitized,
on import; on export dss_safe_name sanitizes a name and two objects that land on one name raise.
Names on export¶
Exported objects are named by name_source: "name" (the CIM name), "mrid" or "uri"; else $CIMHUB_NAME_SOURCE,
else "mrid". The tables say "Names" where a name is written. Under mrid a deck's Line.l1 comes back as ln_l1.
Pages¶
| Page | Covers |
|---|---|
| Sources, options and coordinates | New Circuit and Vsource; Set defaultbasefreq, voltagebases, earthmodel; Open; buses and BaseVoltages; BusCoords and LatLongCoords |
| Lines, wires and switches | LineCode; WireData, CNData, TSData; LineSpacing; LineGeometry; Line; switches with Fuse, Recloser, SwtControl; series Reactor |
| Transformers and regulators | XfmrCode; Transformer, including regulators, LTCs and the export of autotransformers; RegControl |
| Loads, capacitors and shapes | Load; Capacitor; CapControl; LoadShape |
| DER and machines | PVSystem; Storage; Generator |