Sources, options and coordinates

The deck's circuit, its Set options, its buses and its bus coordinates. These are the parts of a DSS deck that are not a piece of equipment, plus the one source every deck has. How to read the tables is on the reference landing page.

DSS CIM (cim18v17) Import Export
New Circuit, Vsource EnergySource vsource.cimtbl (shape source) Vsource; the circuit's is New Circuit
New Circuit name, Set defaultbasefreq, Set voltagebases Substation, Feeder, BaseFrequency, BaseVoltage the master .cimtbl the deck's Options record
Set earthmodel EarthResistivity linegeometry.cimtbl, when the deck has geometry or sets earthmodel Set earthmodel
Open, Close Switch.open line.cimtbl Open Line.<name> 1
the walk's buses ConnectivityNode with a BaseVoltage bus.cimtbl bus names <bus>.<node>...
BusCoords, LatLongCoords CoordinateSystem, Location buscoords.cimtbl (shape location) Buscoords rows and a CSV beside the deck

The shapes are described on the core site's shapes page.

Circuit and Vsource

New Circuit.<name> is New Vsource.source with the circuit's name kept on the deck's Options, so the circuit and every Vsource map alike: one EnergySource per source, in the Substation. The mRID is src_ plus the name, lowercased. The three ways DSS gives a source's Thevenin impedance map as follows, and a source that sets two of them raises, because DSS keeps the one set last and the reader does not record the order.

Impedance group Import Export
R1 X1 R0 X0 (ohm) copied to r, x, r0, x0; all four must be set written for a 3-phase source
MVAsc3 MVAsc1 with x1r1, x0r0 derived by thevenin_from_short_circuit; an unset value takes its DSS default (2000, 2100, 4, 3) and is listed as defaulted written for a 1-phase source, by the exact inverse short_circuit_from_thevenin
Isc3 Isc1 (A) the short-circuit power in kVA by kvasc_from_isc (kV x A), then as above; kV squared over kVA is kohm, so these rows have their own table with r (kohm) ... x0 (kohm) never written
none set all four MVAsc defaults, as the engine does not applicable
property import export
name copied to EnergySource.name; mRID = src_ + name, lowercased written: Names; the circuit's source is always source
bus1 structural: node, and phases from its conductors; default sourcebus written: bus_ref(get_terminal_nodes, get_source.phases)
basekv copied to EnergySource.nominalVoltage (kV) written: get_source.nominal_u (kV)
pu derived: voltageMagnitude (kV) = basekv x pu written: get_source.magnitude_pu
angle copied to EnergySource.voltageAngle (deg) written by rule: get_source.angle (deg); unset -> 0, the reference angle
phases structural: 3 = ABC, 1 = the phase of bus1's conductor written: the phase conductors: 3 or 1, any other count raises
MVAsc3 derived: r, x (thevenin_from_short_circuit) written: 1-phase: kV^2 / abs (short_circuit_from_thevenin)
MVAsc1 derived: r0, x0 (thevenin_from_short_circuit) written: 1-phase: 3 kV^2 / abs(2 Z1 + Z0)
x1r1 derived: r, x (thevenin_from_short_circuit) written: 1-phase: x / r; r = 0 raises
x0r0 derived: r0, x0 (thevenin_from_short_circuit) written: 1-phase: x0 / r0; r0 = 0 raises
Isc3 derived: the 3-phase short-circuit kVA (kvasc_from_isc), then as MVAsc3; r, x in kohm not written: the ohms or the MVAsc group carries the same impedance
Isc1 derived: the 1-phase short-circuit kVA (kvasc_from_isc), then as MVAsc1; r0, x0 in kohm not written: the ohms or the MVAsc group carries the same impedance
R1 copied to EnergySource.r (ohm) written: 3-phase: get_source.impedance.r (ohm); r, x, r0, x0 unset raises (DSS takes one group)
X1 copied to EnergySource.x (ohm) written: 3-phase: get_source.impedance.x (ohm)
R0 copied to EnergySource.r0 (ohm) written: 3-phase: get_source.impedance.r0 (ohm)
X0 copied to EnergySource.x0 (ohm) written: 3-phase: get_source.impedance.x0 (ohm)
bus2 raises when set: an ungrounded (series) source has no source-shape home not written: an EnergySource has one terminal
Z1, Z0 raises when set (not mapped yet) not written: the ohms or the MVAsc group carries the same impedance
Z2 raises when set (not mapped yet) not written: r2/x2 set and different from r/x raises: the Z2 group is not mapped (nor imported)
puZ1, puZ0, puZ2 raises when set (not mapped yet) not written: the ohms or the MVAsc group carries the same impedance
baseMVA raises when set (not mapped yet) (the base of puZ1/puZ0/puZ2) not written: the ohms or the MVAsc group carries the same impedance
enabled copied to EnergySource.normallyInService written: get_in_service(which='normal'); unset -> not written
like untranscribed: the reader resolves like= before mapping not written: the writer never writes like=
frequency, ScanType, Sequence, Yearly, Daily, Duty, Model, puZideal, spectrum, basefreq untranscribed (listed in the table comment) not written

Fail fast.

  • bus2, Z1, Z0, Z2, puZ1, puZ0, puZ2 and baseMVA raise when set: Vsource source: Z1 not mapped yet (no deck in the sweep sets them).
  • Two impedance groups raise: Vsource source: sets the ohms and MVAsc impedance groups; DSS keeps whichever was set last, which the reader does not record. So does a partial R1 X1 R0 X0.
  • A source with phases other than 1 or 3 raises (only 1- and 3-phase sources are walked), as does a bus whose nodes do not fit the phase count.
  • On export, an EnergySource with r, x, r0 or x0 unset raises, as does a 1-phase source with r = 0 or r0 = 0 (no X/R ratio). With several EnergySources, circuit_source= (default "source") names the one exported as New Circuit; unless exactly one is exported under that name, the export raises.

Expected differences after a round trip.

  • A 3-phase source given by MVAsc or Isc comes back as R1 X1 R0 X0; a 1-phase source given by ohms comes back as MVAsc3 MVAsc1 x1r1 x0r0. The impedance is the same in the engine.
  • The circuit's source is always named source; the circuit name is the Feeder's.
  • angle unset is written 0. Floats are written to 15 significant digits.
  • frequency, basefreq, the harmonic and time-series slots are not in CIM and are not written.

Excerpt from cimhub_opendss/tests/atoms/vsource/mvasc.cimtbl (the defaulted comment lists what the deck left unset):

Table EnergySource: mRID, name, node, phases, nominalVoltage (kV), voltageMagnitude (kV), voltageAngle (deg), r (ohm), x (ohm), r0 (ohm), x0 (ohm), normallyInService, BaseVoltage, EquipmentContainer=sub_atom
    # derived from MVAsc3=20000.0, MVAsc1=21000.0; defaulted: x1r1=4.0, x0r0=3.0
    src_source, source, sourcebus, , 115.0, 115.0, 30.0, 0.16037668205527517, 0.6415067282211007, 0.17960358301233556, 0.5388107490370067, , bv_115kv

A blank phases cell is a balanced three-phase source (ABC).

Set options, containers and open switches

The reader keeps three Set options and the Open/Close commands on one Options record. Every other Set option (mode, controlmode, tolerance, and so on) is a solution setting, not part of the model, and is dropped.

DSS Import Export
New Circuit.<name> Substation sub_<name> and Feeder fdr_<name> (lowercased), both named <name>; the Substation holds the EnergySources, the Feeder everything else. A deck with no New Circuit raises the deck has no New Circuit; a second one raises at read time. Options.circuit is the one Feeder's name. Several Feeders that share one NormalEnergizingSubstation are one circuit, named by the Substation; a Feeder with no equipment is not counted. Otherwise it raises.
Set defaultbasefreq BaseFrequency bf_<f>hz, frequency (Hz). Unset is the DSS default, 60, listed as defaulted. It is also the frequency that turns a LineCode's C into b when the code has no baseFreq. Set defaultbasefreq=<network base frequency>, written before New Circuit.
Set voltagebases Mapped. The BaseVoltages are one per distinct bus voltage of the topology walk and one per voltagebases value, highest first. A base on no bus is kept, because it is what the engine's CalcVoltageBases snaps bus bases to; buses still take the walk's voltage. The master's comment lists the deck's voltagebases, those on no bus, and walk voltages the list lacks. Set voltagebases=[...] and CalcVoltageBases: every BaseVoltage.nominalVoltage in kV, ascending, so the deck's bases come back. A BaseVoltage with no nominalVoltage raises.
Set earthmodel One EarthResistivity earth (earthModelType carson or deri, rho) that every geometry WireConfiguration names, when the deck has a LineGeometry or a Line with spacing=. Unset is the engine's Deri and 100 ohm-m, listed as defaulted. A deck without geometry that sets earthmodel gets the same earth, which no line names (rho the default 100 ohm-m, listed as defaulted); a deck with neither gets none. FullCarson raises: earthmodel=FullCarson: EarthModelKind has ['carson', 'deri']. The geometry lines' rho must all agree. Set earthmodel=Carson or Deri, written after New Circuit. The geometry WireConfigurations' models must agree, and one without an EarthResistivity beside one with raises. With no geometry at all, the network's one EarthResistivity, which no line names. None at all: not written.
Open Class.name n, Close An open Line becomes an open switch (Line). An Open of anything but a Line raises: Open Transformer.t 1: only a Line's terminal is mapped (as an open switch). Open Line.<name> 1 for each switch open in the chosen state (switch_state).

The master's Authority and Model come from the caller (DssImporter(name, authority=...)). A DSS class no mapper reads is counted in the master's not mapped: comment.

Buses and BaseVoltages

A DSS bus is a name, and a Line or Reactor has no voltage of its own. The importer runs the topology walk (cimtopology.core.walk, the same one every importer uses) once, from the Vsources, and writes one ConnectivityNode per bus the walk reaches, with its BaseVoltage, in bus.cimtbl. The master carries the BaseVoltages. Equipment keeps its own BaseVoltage column too, which cimtables needs as the base of a per-unit column.

What the walk follows:

DSS Walk
Vsource A source: basekv is phase to phase on 3 phases, the source voltage on 1 phase.
Line A branch, switches too: an open switch keeps its voltage. A Line with bus1 or bus2 unset raises.
Reactor, Capacitor A branch only when bus2 is on another bus (a series element).
Transformer Coils with phases, windings, kVs and conns from the instance, else its XfmrCode. A polyphase winding's kV is phase to phase; a split-phase secondary is windings 2 and 3 on one bus.

Bus names are lowercased, and a ConnectivityNode's mRID and name are the bus name, so a node= column in any other part binds to it. A bus the walk does not reach has no row, and the equipment on it raises: Line l: bus nowhere has no voltage (the topology walk did not reach it).

Export reads the bus from each Terminal's ConnectivityNode (Names.bus; a . in the name becomes _, because it is DSS's node delimiter). A bus reference is <bus>.<n>... with the conductors in order, A/B/C as 1/2/3 and s1/s2 as 1/2, never bare. A BusbarSection is its node's bus and writes no record. Two buses that land on one name raise.

BusCoords and LatLongCoords

A ConnectivityNode is not a PowerSystemResource, so a bus cannot hold a Location. The importer places the equipment as a GIS does, through the wkt column of the location shape, once every other part has bound its Terminals (bound_parts, so buscoords.cimtbl is imported last).

Equipment Geometry on import
a Line (ACLineSegment) a LINESTRING through its Terminals' buses, in Terminal order
anything else with one Terminal a POINT at its bus
anything else with several a POINT at the centroid of its buses: a switch, fuse or transformer midway between its buses
a two-terminal device with device_geometry="linestring" a LINESTRING from bus to bus, like a line (DssImporter(..., device_geometry=...); the default is "point")
property import export
name structural: picks the bus: every Terminal on it takes its coordinates; a name the circuit has no bus for is ignored, as in the engine (counted in the file comment) written: the bus (Names.bus) of each Terminal of located equipment
x derived: geometry: a line's LINESTRING vertex at each Terminal bus, verbatim; other equipment's POINT at its Terminal buses' centroid (the bus itself for one Terminal) written: the Terminal's PositionPoint xPosition (get_location_coordinates); a bus only a device point touches is solved from it as the centroid of the device's buses
y derived: as x written: as x, from yPosition
geographic mapped: the directive (LatLongCoords -> true) picks the CoordinateSystem: COORDINATE_SYSTEMS written: crsUrn CRS84 -> true (LatLongCoords), OpenDSSLocalBusCoordinates -> false; others raise

Fail fast.

  • A deck that gives both BusCoords and LatLongCoords raises: one coordinate system per model.
  • An unknown device_geometry raises.
  • On export, two Locations that put one bus at different points raise (a DSS bus has one position), as do Locations in two coordinate systems, a crsUrn other than the two below, and a Location with a point count that fits no Terminal pairing.

What is not an error. Equipment with a Terminal bus that has no coordinates gets no Location, and coordinates for a bus the circuit does not have are ignored, as the engine ignores them. Both are counted in the file's comment.

The CoordinateSystem picks the file: BusCoords is crs_bus with the URN OpenDSSLocalBusCoordinates (the deck's own projection, which it does not name); LatLongCoords is crs_latlong, urn:ogc:def:crs:OGC:1.3:CRS84, with x the longitude. Export inverts it and writes <stem>_buscoords.csv or <stem>_latlongcoords.csv beside the deck, which DssWriter names in a BusCoords or LatLongCoords command.

Expected differences. A bus no located equipment touches has no coordinates after export. A single POINT on a switch, fuse or transformer is its buses' centroid, so it places only the buses nothing else placed: next to one placed bus it reflects it across the point, which gives back the importer's midpoint to float noise; with none placed every bus goes at the point. An import under device_geometry="linestring" has no device points and comes back exactly.

Excerpt from cimhub_opendss/tests/atoms/buscoords/local.cimtbl (a line, a switch, a regulator, a load and a PV; the line far has a bus with no coordinates, so it is not located):

Object CoordinateSystem: mRID=crs_bus, name=BusCoords, crsUrn=OpenDSSLocalBusCoordinates

# a line's LINESTRING through its Terminal buses; other equipment a POINT at their centroid
Update Table PowerSystemResource: mRID, wkt
    src_source, "POINT (0.0 0.0)"
    ln_l1,      "LINESTRING (0.0 0.0, 50.0 0.0)"
    sw_sw1,     "POINT (75.0 0.0)"
    xf_reg,     "POINT (102.5 2.5)"

Run it

This imports a 1-phase source on phase B and exports it. It runs from the repository root.

from pathlib import Path

from cimhub_opendss import DssReader, cim_to_dss, dss_to_cim

deck = Path("cimhub_opendss/tests/atoms/vsource/single_phase.dss")
network = dss_to_cim(DssReader(deck).read_all(), name="single_phase", artifact_dir="/tmp/ref-sources")

text = Path("/tmp/ref-sources/vsource.cimtbl").read_text()
print(text[text.index("Table EnergySource"):])

cim_to_dss(network, "/tmp/ref-sources/back.dss", name_source="name")
print(Path("/tmp/ref-sources/back.dss").read_text())
Table EnergySource: mRID, name, node, phases, nominalVoltage (kV), voltageMagnitude (kV), voltageAngle (deg), r (ohm), x (ohm), r0 (ohm), x0 (ohm), normallyInService, BaseVoltage, EquipmentContainer=sub_lateral
    # derived from MVAsc3=100.0, MVAsc1=90.0; defaulted: angle=0.0, x1r1=4.0, x0r0=3.0
    src_source, source, tap, B, 7.2, 7.344, 0.0, 0.12573046801883503, 0.5029218720753401, 0.21896347099154312, 0.6568904129746294, , bv_7p2kv

Clear
Set defaultbasefreq=60
New Circuit.lateral phases=1 bus1=tap.2 basekv=7.2 pu=1.02 angle=0 MVAsc3=100 MVAsc1=90 x1r1=4 x0r0=3
Set voltagebases=[7.2]
CalcVoltageBases

name_source="name" names the exported objects by their CIM name. The default is mrid (or $CIMHUB_NAME_SOURCE), which would name this circuit fdr_lateral.

See the core site for the source and location shapes, the getters the exporter reads through, and the topology reference.