Round trip¶
A round trip imports a deck to CIM and exports it back to a new deck. The check that matters is that the engine solves both decks to the same answer.
Run it yourself¶
import tempfile
from pathlib import Path
from cimhub_opendss import DssReader, cim_to_dss, dss_to_cim
original = Path("cimhub_opendss/tests/decks/IEEE/IEEE13_CDPSM/IEEE13_CDPSM.dss")
written = Path(tempfile.mkdtemp()) / "IEEE13_CDPSM.dss"
network = dss_to_cim(DssReader(original).read_all(), name="IEEE13_CDPSM")
cim_to_dss(network, written, name_source="name")
print(len(DssReader(written).read_all().graph)) # the written deck reads back
name_source="name" keeps the deck's own names, so the two decks compare element by element. The default, 'mrid',
also reads back, but a name that the importer lowercased or prefixed (ld_611) is written as it was compiled.
Compare voltages in the engine¶
Compile each deck with OpenDSSDirect.py (installation) and compare the solved node voltages. Turn controls off and tighten the tolerance, so both decks converge to one answer from their different starting points. Measure the difference against the bus's base voltage, because a node near zero (a floating neutral) would make a relative error meaningless.
import tempfile
from pathlib import Path
import opendssdirect as dss
from cimhub_opendss import DssImporter, DssReader, cim_to_dss
dss.Basic.AllowChangeDir(False) # Compile would otherwise change the process's directory
original = Path("cimhub_opendss/tests/decks/IEEE/IEEE13_CDPSM/IEEE13_CDPSM.dss")
written = Path(tempfile.mkdtemp()) / "IEEE13_CDPSM.dss"
network = DssImporter("IEEE13_CDPSM").to_cim(DssReader(original).read_all())
cim_to_dss(network, written, name_source="name")
def solved_voltages(deck):
"""({node: complex volts}, {bus: base volts, line to neutral}) after a no-control solve."""
dss.Text.Command("Clear")
dss.Text.Command(f"Compile [{deck.resolve()}]")
dss.Text.Command("Set controlmode=off tolerance=1e-10 maxiterations=500")
dss.Solution.Solve()
assert dss.Solution.Converged()
values = dss.Circuit.AllBusVolts()
nodes = [name.lower() for name in dss.Circuit.AllNodeNames()]
volts = {node: complex(values[2 * i], values[2 * i + 1]) for i, node in enumerate(nodes)}
bases = {}
for bus in dss.Circuit.AllBusNames():
dss.Circuit.SetActiveBus(bus)
bases[bus.lower()] = dss.Bus.kVBase() * 1000
return volts, bases
before, bases = solved_voltages(original)
after, _ = solved_voltages(written)
assert before.keys() == after.keys()
worst = max(abs(after[node] - before[node]) / bases[node.split(".")[0]] for node in before)
print(f"{len(before)} nodes, largest difference {worst:.2%} of the bus base voltage")
For IEEE 13 this prints 57 nodes, largest difference 0.06% of the bus base voltage. The package's own tests use a
tolerance of 0.1 % of the base voltage.
The difference is not zero because the CIM model does not hold every setting of the deck. In IEEE 13 the loads'
Vminpu and Vmaxpu are not in CIM, and the exporter writes the loads' kV as 2.40178 where the deck says 2.4. The
settings the tests copy from the original into the written deck before solving are:
| Setting | Why it is not in the model |
|---|---|
Load.Vminpu, Load.Vmaxpu |
below Vminpu the engine turns a load into constant impedance |
Transformer.ppm_antifloat |
the engine's 1 ppm default against the deck's setting moves a floating delta |
Transformer.taps, Capacitor.states |
an in-deck Solve moves them, and the importer reads the deck's text |
What the tests check¶
The package's tests run from a checkout (cimhub_opendss/tests/). The engine-based ones need opendssdirect.
| Test file | Checks |
|---|---|
test_export_decks.py |
Whole decks through import and export. Power-flow parity in the engine (engine_compare.assert_same_power_flow), that each deck's bus coordinates come back as the engine had them, and idempotence: exporting the exported deck again gives byte-identical text. |
test_cimtbl_sweep.py |
Every deck either binds, with every equipment's BaseVoltage equal to its nodes', or stops at a named, expected error. An unlisted stop fails, and so does a listed stop that now binds. |
test_dss_to_cimtbl.py |
The IEEE 13-node .cimtbl artifacts match the committed goldens in tests/goldens/. |
test_cimtbl_*.py |
Each mapper against its atoms (tests/atoms/<table>/), many of them also compiled in the engine to check a value. |
test_export_*.py |
Each exporter module from small CIM networks, comparing the engine's state (buses, YPrim, node voltages) of the original and the written atom (engine_compare.assert_same_engine_state). |
tests/cross_format/ (repository root) |
A GridLAB-D deck through CIM to a DSS deck, and the IEEE 13-node feeder in both formats. |
Parity compares against the original deck minus the settings in the table above. Each deck's list is in
test_export_decks.py, so a loss is explicit.
Running the tests¶
From a checkout, one pytest process per package:
scripts/test-all.sh opendss # the package's tests
scripts/test-all.sh opendss -- --roundtrip # also the slow whole-deck tests
Whole-deck tests carry the roundtrip pytest marker and are skipped unless you pass --roundtrip. The vendored decks
(cimhub_opendss/tests/decks/, origins in its README) are the IEEE 4, 13 and 37 node and 123-bus feeders, the EPRI K1
and M1 feeders, and the IEEE 13-node variants with assets. K1 and M1 stop at import (a Line whose phases differ
from its LineCode's), and the engine cannot compile them here, so they are in the sweep only as expected stops.
Larger decks (EPRI J1, IEEE 8500, IEEE 9500) are not vendored. Set CIMHUB_DSS_DECKS to a directory with the same
layout, for example IEEE/IEEE8500/Master.dss, and their tests run; otherwise they skip.
To regenerate a golden after an intended change, set CIMHUB_UPDATE_GOLDENS=1 and review the diff.