Skip to content

Export: CIM to DSS

from cimhub_opendss import DssExporter, DssWriter, cim_to_dss

cim_to_dss(network, "out/IEEE13_CDPSM.dss")                 # export and write in one call

model = DssExporter().to_model(network, name_source="name")  # records only, no files
DssWriter().write(model, "out/IEEE13_CDPSM.dss")

network is any cim18v17 network, for example the result of dss_to_cim. The exporter reads it through the getters in cimhub_core and returns a DssModel, the same shape DssReader.read_all() returns, so the deck the writer produces reads back through the reader and the importer. Only DssWriter touches the filesystem.

Options

DssExporter(time_points=None).to_model(network, *, name_source=None, circuit_source="source", switch_state="actual"). cim_to_dss(network, destination, *, per_class=False, time_points=None, **opts) passes opts to to_model.

Argument Meaning
name_source What a DSS name comes from: 'name', 'mrid' or 'uri'. Without it, $CIMHUB_NAME_SOURCE, else 'mrid'. Any other value raises.
circuit_source Which EnergySource becomes New Circuit when the network has several. Matched, ignoring case, against the exported name. Default "source".
switch_state 'actual' (default) writes each switch's State and Open command from Switch.open. 'normal' reads Switch.normalOpen, for a model whose open is unset. Normal always reads normalOpen. Any other value raises.
time_points The TimePoint tables of the network's schedules (see time points).
per_class cim_to_dss and DssWriter.write only. Write each DSS class to its own file beside the deck (line.dss, load.dss, ...), which the master Redirects.

Names

Every DSS name is the CIM object's name, mRID or uri(), as name_source says, with each run of characters DSS cannot parse (white space, quotes, <>[]{}(),=~|) replaced by _.

name_source Use it when
'mrid' (default) the model came from dss_to_cim: the importer compiled each mRID from the DSS name, so names are unique
'name' you want the names a person gave the objects. A model with duplicate names raises (below)
'uri' names must be stable and of fixed length across tools. mRID is a free-form string in cim18v17, so it is not a safe join key; uri() is

Rules:

  • Two objects of one DSS class that end up with the same name, compared ignoring case as DSS does, raise: ACLineSegment 'ln_b' and 'ln_a' are both named 'a' in DSS Line (name source 'name'). Buses are one namespace of their own, and a . in a bus name becomes _ because . is DSS's node delimiter.
  • An object with no name (or mRID, or uri()) to export it under raises, naming its class and mRID.
  • The circuit is named for the one Feeder. Several Feeders with equipment are one circuit when they share a NormalEnergizingSubstation, and the Substation names it. No Feeder, or several without one Substation, raises. A Feeder with no equipment is not counted when there are several.
  • The circuit's source is always written as Vsource.source, whatever the naming, because that is DSS's name for New Circuit's source.

The circuit source

A deck has one New Circuit. With one EnergySource in the network it is the circuit's source. With several, the one whose exported name matches circuit_source is, and the others become Vsource records:

cim_to_dss(network, "out/feeder.dss", name_source="name", circuit_source="substation_a")

Several EnergySources and no single match raises: 2 EnergySources and 0 exported as 'source' (name source 'name'); pass circuit_source= to name the circuit's.

What is written

The deck is written in this order: Clear, Set defaultbasefreq, New Circuit, Set earthmodel (when the WireConfigurations name one, or, in a model without line geometry, the network's one EarthResistivity), the records, Set voltagebases and CalcVoltageBases, one Open per open switch terminal, then Buscoords or LatLongCoords naming the CSV files written beside the deck (<stem>_buscoords.csv, <stem>_latlongcoords.csv). Records go catalogs first: LoadShape, the wire catalogs, LineSpacing, LineGeometry, LineCode, XfmrCode, then the equipment, each class after what it references. The writer creates the destination's folders.

Quantities are converted with CIMUnit.to() into the unit the DSS property expects. Line lengths and wire dimensions are written in metres (a line with only lumped values is written per km, units=km).

Which CIM class becomes which DSS class, and where each slot comes from, is in the export mapping. What converts lists the classes.

Switches

A CIM switch is written as a Line with Switch=y and a small invented impedance (r1=r0=0.001 ohm over length=1 units=m), because CIM holds none. The control depends on the class: a Fuse and a Recloser get their own control; any other switch class gets a SwtControl, written only when the switch is open in either state (normalOpen or the state switch_state reads). The Fuse and Recloser controls are written with enabled=false, because cim18v17 holds no trip settings or curve and the engine's defaults would trip them. With switch_state='actual', an open switch also gets an Open Line.<name> 1 line. A switch whose open is unset raises under 'actual', since there is no silent fallback; use switch_state='normal' for an as-built model. A switch whose normalOpen is unset raises under both: LoadBreakSwitch 'sw_671692': normalOpen is unset.

Bus coordinates

Each Location of the network's equipment gives its Terminals' buses their coordinates, as the import's inverse. A bus no located equipment touches has none. Two different points for one bus raise, naming both pieces of equipment. The CoordinateSystem picks the file: urn:ogc:def:crs:OGC:1.3:CRS84 is written as LatLongCoords (latitude first, as the engine reads it), and the importer's own OpenDSSLocalBusCoordinates as BusCoords. Another system, or two systems in one model, raises.

Load shapes and time points

A ConformLoadSchedule with points becomes a LoadShape, named for its group, and each load of the group names it as yearly. The same holds for the EnergyConnectionSchedule of a PV, battery or machine. The points are not in the network, so pass the tables the importer filled, or read_time_points:

from pathlib import Path
from cimhub_opendss import DssExporter, DssReader, DssWriter, dss_to_cim

time_points = {}
model = DssReader("cimhub_opendss/tests/atoms/loadshape/loadshapes.dss").read_all()
network = dss_to_cim(model, name="loadshapes", time_points=time_points)

exported = DssExporter(time_points).to_model(network, name_source="name")
DssWriter().write(exported, "/tmp/loadshapes_out/loadshapes.dss")
print([line[:60] for line in Path("/tmp/loadshapes_out/loadshapes.dss").read_text().splitlines() if "Loadshape" in line])

This needs the time-points extra. A schedule with no points, a load group with no schedule, and a NonConformLoad are written as static loads, and one warning names their groups. Shapes with the same name, interval and multipliers are shared; another shape of that name with other points takes a suffix (_2, _3). startTime is not written, because DSS has no date. An hourly interval=1 comes back as sinterval=3600, which is the same interval.

What raises

Cause Message starts
Conducting equipment of a CIM class no exporter module handles no DSS export yet for {'<Class>': <count>}
More than one EnergySource with none exported under circuit_source <n> EnergySources and 0 exported as 'source'
Two objects on one DSS name <Class> '<mRID>' and '<mRID>' are both named '<name>' in DSS <namespace>
An object with no name, mRID or uri() to export <Class> '<mRID>': has no <name_source> to export it under
No Feeder, or several without one Substation the model has <n> Feeders with equipment ...; a DSS deck is one circuit
A bad name_source or switch_state name source must be one of ..., switch_state must be one of ...
A value a DSS property needs that the model does not hold for example a WireConfiguration with no WireSpacing, a wire with neither Rdc nor Rac, or a switch with no state
Two earth models in one network WireConfigurations over earth models ...; a DSS deck has one earthmodel
A BaseVoltage with no nominalVoltage a BaseVoltage has no nominalVoltage
A per_class file that would overwrite the master the master <name> would be overwritten by the <Class> file

What does not survive a round trip

Some DSS and CIM distinctions are lossy by design:

  • Every switch class other than Fuse and Recloser comes back as a LoadBreakSwitch.
  • A DSS protection setting with no home in cim18v17 is written as the engine's default. The export mapping marks each such slot unset or rule.
  • A CIM AutoTransformer is written as a DSS Transformer.
  • Settings the model does not hold come back as the engine's defaults: Load.Vminpu and Vmaxpu, the Transformer.ppm_antifloat setting and the deck's tap and capacitor states that an in-deck Solve moved.

Round trip shows how to see which of these a given deck hit.