DER and machines

This page is the conversion reference for the OpenDSS classes that inject power: PVSystem, Storage and Generator. For each one it says what the importer writes, what the exporter reads back and what raises. The field classes (copied, mapped, structural, derived, untranscribed) and the conventions every section follows are on the reference index. The getters the exporter reads through are on the core site's sources, DER and machines page.

DSS class CIM classes .cimtbl artifact and shape Importer Exporter
PVSystem PowerElectronicsConnection and its PhotoVoltaicUnit pvsystem.cimtbl, shape der importer/cimtbl/pvsystem.py exporter/pvsystem.py
Storage PowerElectronicsConnection and its BatteryUnit storage.cimtbl, shape der importer/cimtbl/storage.py exporter/storage.py
Generator SynchronousMachine, and a RegulatingControl for model 3 generator.cimtbl, shape synchronous_machine importer/cimtbl/generator.py exporter/generator.py
InvControl not converted none none none

InvControl has no mapper. The master's comment counts it (not mapped: Invcontrol 1), so a deck's inverter control is not silently lost, but nothing of it reaches CIM. A PV's or battery's own setpoints are converted without it. A battery's VarFollowInverter acts only with one, so it is untranscribed; a PV's is used in the snapshot (see PVSystem). The reader keeps Mode and CombiMode as the names the deck gives (VOLTVAR, VV_VW).

A yearly LoadShape on a device is the device's own EnergyConnectionSchedule, which the section of each class covers. The load-side shapes are on Loads, capacitors and shapes. The table shapes are on the core site's shapes page. Source paths are under cimhub_opendss/src/cimhub_opendss/.

PVSystem and Storage share importer/cimtbl/inverter.py (the connection row) and exporter/inverter.py (inverter_pieces, the chop below). All five classes share the terminal rule in importer/cimtbl/injection.py and exporter/injection.py.

The examples run from the repository root with uv run python. They convert the public test atoms in cimhub_opendss/tests/atoms to CIM and back. This helper is shared by all of them:

from pathlib import Path

from cimhub_opendss import DssExporter, DssImporter, DssReader, DssWriter
from cimhub_opendss.schema import opendss_schema as schema

ATOMS = Path("cimhub_opendss/tests/atoms")


def round_trip(atom: str, *classes):
    """Import an atom deck to CIM, export it, and return the DSS lines of `classes`."""
    path = ATOMS / atom
    time_points = {}
    network = DssImporter(path.stem, time_points=time_points).to_cim(DssReader(path).read_all())
    model = DssExporter(time_points).to_model(network, name_source="name")
    writer = DssWriter()
    return [writer.serialize(record) for cls in classes for record in model.list_by_class(cls)]

name_source="name" writes each object under its CIM name, which the importer set to the deck's name. The default is the mRID (pv_dim, storage_capped, gen_steam).

Sign convention

CIM's terminal sign is the load's: p and q are positive into the equipment. A PV array, a generator and a discharging battery therefore carry negative p. The importer writes p = -(the output) and q = -kvar, and the exporter asks the core getters for the generation sign (sign='generation'), so DSS kW and kvar come back positive for output. The rule and its limit pairs are on the core DER reference.

Rules shared by PVSystem, Storage and Generator

Terminal. The importer's phase rule is the load's: the bus's nodes give the phases (1, 2, 3 are A, B, C; 1 and 2 are s1 and s2 on a split-phase island), a wye device's neutral is ground and a delta device has none. The exporter puts the phase conductors on bus1; a delta across two conductors is phases=1.

Rated voltage. ratedU (kV, line to line) is kv, times the square root of 3 for a 1-phase wye device. The exporter divides it back. It is the device's own rating and is not checked against the bus, unlike a load's kV: a 240 V inverter on 120 V legs stays 240 V.

The inverter row. A PVSystem and a Storage share one PowerElectronicsConnection row:

Column Import Export
ratedS (kVA) kVA ratedS, times the unit's share
maxQ (kVAr) kvarMax; default kVA kvarMax, times the share; unset: not written
minQ (kVAr) -kvarMaxAbs; default kVA kvarMaxAbs = -minQ, times the share; unset: not written
maxIFault 1 / Vminpu; default Vminpu 0.9 Vminpu = 1 / maxIFault; unset: not written
normallyInService enabled; default true get_in_service(which='normal'); unset: not written
p (kW), q (kVAr) the dispatch, in the load sign the unit's output, in the generation sign

The unit is <connection mRID>_unit: a PhotoVoltaicUnit for a PV, a BatteryUnit for a battery.

The chop on export. A DSS PVSystem or Storage is one inverter with one DC device, and CIM lets several units share a connection. The exporter writes one DSS device per unit of the right class:

Case Result
one unit the device keeps the connection's name
several units each takes its unit's name, and a share of ratedS, maxQ and minQ equal to its maxP over the units' total
unequal phases, one unit one 1-phase device per phase, <name>_<phase>, each a 1/n share of the connection and of the unit's own ratings
unequal phases, several units, or a delta inverter raises
a device's output above its share of ratedS raises, because the engine would cut it (a DC-coupled PV feeding its battery can do this)
a PowerElectronicsWindUnit a model 1 Generator at the unit's output, as a Generator
any other unit class raises

Units, shares and the getters behind them are get_inverter_units, get_der_output and get_inverter_rating, on the core DER reference.

PVSystem

One PowerElectronicsConnection pv_<name> (lowercased) and one PhotoVoltaicUnit pv_<name>_unit. The p is the engine's snapshot dispatch at rated voltage, worked out by the importer:

  1. The panel gives Pmpp x irradiance. Below %Cutout of kVA the inverter is off and p is 0 (the row comment says off: below %Cutout of kVA).
  2. Otherwise the power is capped at Pmpp x %Pmpp / 100, then cut to fit kVA with kvar kept (var priority).
  3. q is kvar, or the power after the %Pmpp cap and before the cut to kVA, x tan(acos abs(pf)) with the sign of pf, whichever the deck assigned last (default pf 1). An inverter that is off still gives a set kvar, unless VarFollowInverter is yes.

irradiance is also copied to PhotoVoltaicUnit.irradiance (kW/m2), a property that cim18v17 carries for it.

PVSystem properties

Property Import Export
name PowerElectronicsConnection.name; mRID pv_ + name, lowercased the CIM name or mRID; the connection's for one unit, the unit's for several, <name>_<phase> per phase
phases, bus1, conn node, phases, phaseConnection (Y or D); default 3 phases, wye as the shared terminal rule
kv ratedU (kV), line to line (derived); default 12.47 kv from ratedU
irradiance PhotoVoltaicUnit.irradiance (kW/m2), and p; default 1 the unit's irradiance; unset: the unit's output over Pmpp, so the panel gives exactly the output
Pmpp PhotoVoltaicUnit.maxP (kW) with minP 0, and p; default 500 maxP times the share; unset or 0 raises, and so does a minP other than 0
pct_Pmpp derived into p; default 100 100 x output / Pmpp when the output is below the panel's power; not written otherwise; an output above the panel raises
kVA ratedS (kVA), and caps p; default 500 ratedS times the share
kvar, pf derived into q (the later of the two wins) kvar is the unit's q; pf only with a yearly shape whose q follows p
pct_Cutout derived: p is 0 below it; default 20 0 when the output is above 0 and the panel is below 20 % of kVA, or with a yearly shape; else not written
pct_Cutin structural: acts only after the inverter turns off; default 20 0 with a yearly shape; else not written
VarFollowInverter derived into q when the inverter is off; default no not written
kvarMax, kvarMaxAbs, Vminpu inverter row (table above) inverter row
model structural: only 1 maps, any other raises not written, so the engine's 1
yearly the PV's EnergyConnectionSchedule <mRID>_yearly (see below) a LoadShape; see below
enabled normallyInService inverter row
EffCurve, P_TCurve, UserModel, UserData raises when set: they change the snapshot power or have no home not written
Balanced, LimitCurrent, WattPriority, PFPriority raises when yes not written
pct_PminNoVars, pct_PminkvarMax raises when nonzero not written
ControlMode GFL maps; GFM raises not written
Temperature, Vmaxpu, daily, duty, Tyearly, Tdaily, Tduty, DutyStart, class_class, debugtrace, spectrum, basefreq, like untranscribed not written
pct_R, pct_X, kVDC, Kp, PITol, SafeVoltage, SafeMode, DynamicEq, DynOut, AmpLimit, AmpLimitGain untranscribed: dynamics settings with no home in the network profile not written

Yearly shape. A yearly LoadShape scales the irradiance. The importer writes an EnergyConnectionSchedule <mRID>_yearly in pvsystem.cimtbl, and its points (p and q at each sample, in the load sign, SI units) go to the EnergyConnectionTimePoint table of the sidecar, each sample solved as above at irradiance x mult. A qmult on the shape raises. A sample whose panel power falls between %Cutout and %Cutin of kVA raises: the engine keeps the inverter on or off as it was, which depends on the earlier samples.

The exporter turns the schedule back into a LoadShape with mult = p / (Pmpp x irradiance) at each point, and writes %Cutin=0 %Cutout=0 so that the engine gives every point's p, the low ones too. It writes q as kvar when every point's q is the written kvar, as pf when q is in proportion to p, and otherwise raises.

PVSystem fail-fast rules

Rule Message
model other than 1 PVSystem p: model=2 is not mapped (model 1 is; the engine rejects anything but 1, 2 and 3)
a curve, Balanced, WattPriority, ... set PVSystem p: ... not mapped yet (no deck in the sweep sets them)
kvar above kVA PVSystem p: ... kvar is above its ... kVA
a yearly sample between %Cutout and %Cutin PVSystem p: sample 1 of yearly=s puts the panel at 25 kW, between %Cutout (20) and %Cutin (30); the engine keeps the inverter as it was, which is not mapped
export: output above Pmpp x irradiance p ... kW is above the panel's ... kW (maxP x irradiance ...)
export: p into the PV p ... kW into the PV; a PVSystem only generates
export: a yearly q that is neither the kvar nor in proportion to p its q is neither the PV's ... kvar nor in proportion to p; a PVSystem gives one or the other

PVSystem round trip

What Why
%Pmpp is written when the output is below the panel's power (a PV cut to fit kVA, or held back) the engine gives CIM's p; a PV that was off comes back %Pmpp=0
%Cutout=0 is written for a running PV whose panel is below 20 % of kVA the engine would switch it off at its default cut-out
with a yearly shape, %Cutin and %Cutout come back 0 and q as kvar or pf the engine then gives the points' p and q
devices that shared a shape but whose multipliers differ get their own, sun, sun_2 one shape scales one way
irradiance is the unit's when set, else the output over Pmpp a CIM PV need not have one

PVSystem excerpt

From tests/atoms/der/pvsystem.cimtbl. pmppcap has irradiance=0.9, Pmpp=10 and %Pmpp=60, so the panel's 9 kW is capped at 6:

Table PowerElectronicsConnection: mRID, name, node, phases, phaseConnection, ratedS (kVA), ratedU (kV), p (kW), q (kVAr), maxQ (kVAr), minQ (kVAr), maxIFault, normallyInService, BaseVoltage, EquipmentContainer=fdr_atom
    # defaulted: phases=3, pf=1.0, conn=wye, pct_Cutin=20.0, pct_Cutout=20.0, model=1, Vminpu=0.9, enabled=true
    pv_pmppcap,  pmppcap,  b2,    ,     Y, 12.0,   0.48,                -6.0,    0.0,                12.0,   -12.0,   1.1111111111111112, true, bv_480v

Table PhotoVoltaicUnit: mRID, maxP (kW), minP (kW), irradiance (kW/m2), PowerElectronicsConnection, EquipmentContainer=fdr_atom
    pv_pmppcap_unit,  10.0,   0.0, 0.9, pv_pmppcap

(The two rows are from different tables of the file, with the other devices' rows between them left out.)

Storage

One PowerElectronicsConnection storage_<name> (lowercased) and one BatteryUnit storage_<name>_unit. The engine keeps a discharge setpoint and a charge setpoint, and State picks the one that runs. The importer replays the deck's assignments in order and gets the snapshot state and p:

  • kW > 0 sets the discharge setpoint and the state discharging; kW < 0 sets the charge setpoint and charging; kW = 0 idles. So state=charge kW=150 discharges at 150 kW.
  • %Discharge or %Charge puts its setpoint back to that percent of kWrated; State is read by its first letter (charge is charging).
  • The output is capped at kVA (default kWrated). A battery that waits draws its idling loss, %IdlingkW x kWrated / 100, which is its p. q is 0.

The load sign applies: discharge is negative p, charging positive.

Storage properties

Property Import Export
name PowerElectronicsConnection.name; mRID storage_ + name, lowercased as for a PV
phases, bus1, conn, kv as for a PV as for a PV
kW derived: replayed with State into p not written: %Discharge and %Charge carry the output, because the engine turns kW into a percent of the kWrated of that moment and kWrated is written after it
State BatteryUnit.batteryState: charging, discharging, idling become charging, discharging, waiting; default idling batteryState charging, discharging, waiting give State; another state raises, and so does an output of the wrong sign
kWrated BatteryUnit.maxP (kW) and minP = -kWrated; default 25 maxP times the share; unset raises, and a minP other than -maxP raises
kWhrated BatteryUnit.ratedE (kWh); default 50 ratedE; unset: not written
kWhstored, pct_stored BatteryUnit.storedE (kWh): kWhstored, or %stored x kWhrated / 100, whichever the deck assigned last; default %stored 100 kWhstored = storedE
pct_reserve BatteryUnit.minimumE (kWh) = %reserve x kWhrated / 100; default 20 %reserve = minimumE / ratedE x 100; either unset: not written
pct_Discharge, pct_Charge derived into p; default 100 the output over kWrated x 100, for the matching state
pct_EffCharge, pct_EffDischarge chargingEfficiency, dischargingEfficiency (percent); default 90 the efficiencies; unset: not written
pct_IdlingkW BatteryUnit.idlingP (kW) = %IdlingkW x kWrated / 100, also the p when waiting; default 1 idlingP / kWrated x 100; a waiting battery's p must equal idlingP when both are set
kVA, kvarMax, kvarMaxAbs, Vminpu, enabled inverter row; kVA defaults to kWrated inverter row
kvar raises when nonzero not written; a q other than 0 raises
pf 1 only; any other raises not written
model 1 only; any other raises not written
DispMode default, or follow with a yearly shape; any other raises follow with a yearly shape; else not written
yearly DispMode=follow: the battery's EnergyConnectionSchedule <mRID>_yearly (see below); with another DispMode, a shape raises a LoadShape (see below)
EffCurve, DynaDLL, DynaData, UserModel, UserData raises when set not written
Balanced, LimitCurrent, WattPriority, PFPriority raises when yes not written
pct_PminNoVars, pct_PminkvarMax raises when nonzero not written
ControlMode GFL maps; GFM raises not written
pct_Cutin, pct_Cutout, VarFollowInverter, pct_kWrated, pct_Idlingkvar, DischargeTrigger, ChargeTrigger, TimeChargeTrig, Vmaxpu, daily, duty, class_class, debugtrace, spectrum, basefreq, like untranscribed not written
pct_R, pct_X, kVDC, Kp, PITol, SafeVoltage, SafeMode, DynamicEq, DynOut, AmpLimit, AmpLimitGain untranscribed: dynamics settings not written

Energy checks. The engine checks the stored energy against full and the reserve when the state is assigned. Charging a full battery, or discharging at or below the reserve, makes it idle, and the mapping cannot say so: both raise on import and on export. An energy assigned after the last State or kW raises on import. The exporter writes the energies before State for the same reason.

Yearly shape. With DispMode=follow, a LoadShape is the battery's output at each sample: it discharges at mult x kWrated when mult > 0, charges at -mult x kWrated when < 0 and idles at 0, capped at kVA. The importer writes the points (p only) to the sidecar, and a kW or State on such a battery raises, because its snapshot idles. A shape in another dispatch mode raises. The exporter writes DispMode=follow and the LoadShape with mult = output / kWrated, 0 where the output is the idling loss, and does not write State (the battery must be waiting). A point above kVA, or a q other than 0, raises.

Storage fail-fast rules

Rule Message
kvar set Storage s: kvar not mapped yet (no deck in the sweep sets them)
DispMode other than default and follow Storage s: DispMode=peakshave not mapped yet (no deck in the sweep sets them)
charging a full battery Storage s: charging with 200 of 200 kWh stored; the engine idles a full battery, which is not mapped
discharging at or below the reserve Storage s: discharging with ... kWh stored, at or below its ... kWh reserve; the engine idles it, which is not mapped
DispMode=follow without a yearly shape, or the reverse Storage s: DispMode=... with yearly=...; only a follow-mode battery's yearly shape is mapped (S9-6)
export: batteryState other than charging, discharging, waiting batteryState ...; a Storage State is charging, discharging or waiting
export: q other than 0 q ... kVAr; a Storage's kvar is not mapped, as on import

Storage round trip

What Why
kW never comes back; the output is %Discharge or %Charge see the kW row
a battery capped by its kVA comes back with the capped percent (80 kVA on 100 kW: %Discharge=80) CIM keeps only the capped output
in follow mode, %Charge, %Discharge and State are not written; a capped sample comes back at the cap (mult 0.8, not 1) follow mode does not use them, and the schedule holds the output
%stored comes back as kWhstored storedE is in kWh

Storage excerpt

From tests/atoms/der/storage.cimtbl. capped has kWrated=100 and kVA=80, so its discharge is capped at 80 kW:

Table PowerElectronicsConnection: mRID, name, node, phases, phaseConnection, ratedS (kVA), ratedU (kV), p (kW), q (kVAr), maxQ (kVAr), minQ (kVAr), maxIFault, normallyInService, BaseVoltage, EquipmentContainer=fdr_atom
    # defaulted: phases=3, conn=wye, pf=1.0, pct_stored=100.0, pct_reserve=20.0, pct_Discharge=100.0, pct_Charge=100.0,
    # pct_EffCharge=90.0, pct_EffDischarge=90.0, pct_IdlingkW=1.0, model=1, Vminpu=0.9, DispMode=default, enabled=true
    storage_capped,   capped,   b2,    ,     Y, 80.0,  0.48,              -80.0,  0.0, 80.0,  -80.0,  1.1111111111111112, true, bv_480v

Table BatteryUnit: mRID, ratedE (kWh), storedE (kWh), minimumE (kWh), maxP (kW), minP (kW), chargingEfficiency (percent), dischargingEfficiency (percent), idlingP (kW), batteryState, PowerElectronicsConnection, EquipmentContainer=fdr_atom
    storage_capped_unit,   200.0, 200.0, 40.0,  100.0, -100.0, 90.0, 90.0, 1.0,  discharging, storage_capped

(The two rows are from different tables of the file, with the other batteries' rows between them left out.)

Round trip the DER atom. dim is a PV whose panel (1 kW) is below 20 % of its 12 kVA, so it is off. pmppcap is capped by %Pmpp, and capped is the battery above:

for line in round_trip("der/der.dss", schema.Pvsystem, schema.Storage):
    if " Pvsystem.dim " in line or " Pvsystem.pmppcap " in line or " Storage.capped " in line:
        print(line)
new Pvsystem.dim phases=3 bus1=b2.1.2.3 kv=0.48 irrad=0.1 Pmpp=10 %Pmpp=0 conn=wye kvar=0 kVA=12 Vminpu=0.9 kvarMax=12 kvarMaxAbs=12 enabled=Yes
new Pvsystem.pmppcap phases=3 bus1=b2.1.2.3 kv=0.48 irrad=0.9 Pmpp=10 %Pmpp=60 conn=wye kvar=0 kVA=12 Vminpu=0.9 kvarMax=12 kvarMaxAbs=12 enabled=Yes
new Storage.capped phases=3 bus1=b2.1.2.3 kv=0.48 conn=wye kVA=80 kvarMax=80 kvarMaxAbs=80 kWrated=100 kWhrated=200 kWhstored=200 %reserve=20 State=discharging %Discharge=80 %EffCharge=90 %EffDischarge=90 %IdlingkW=1 Vminpu=0.9 enabled=Yes

Generator

One SynchronousMachine gen_<name> (lowercased), with type generator and operatingMode generator. p = -kW and q = -kvar, in the load sign. kW defaults to 1000 and kVA to 1.2 x kW.

kvar. The engine keeps kvar as a power factor. Assigning kvar sets the power factor at the kW of that moment; assigning kW or pf recomputes kvar = kW x tan(acos abs(pf)). The importer replays the deck's kW, pf and kvar assignments in order from the engine's start (1000 kW, pf 0.88, 60 kvar), so kW=620 kvar=30 followed by kW=50 is 2.4 kvar, and kvar=30 kW=100 is 3. The exporter writes kW first and kvar after it, so that kvar is the engine's at that kW.

Connection. SynchronousMachine has no phaseConnection: conn=wye is earthing true and conn=delta is false. On export an unset earthing raises.

Models. The mapped model values are:

DSS model Import Export
1, constant PQ a machine at kW and kvar model 1 when the machine has no control, or a disabled one on its own terminal
7, current limited as model 1; below Vminpu the engine limits its current, a power-flow behaviour (noted on the row) comes back as model 1: CIM has no current limit
3, PV bus as model 1, plus a voltage RegulatingControl gen_<name>_ctrl on the machine's own terminal, given to the machine by an update model 3 when an enabled voltage control regulates its own terminal
2, 4, 5, 6 raises not produced

The control has targetValue = Vpu x ratedU, in volts, and targetDeadband 0. The exporter writes Vpu = targetValue / ratedU. A disabled control gives model 1, because DSS has no disabled PV bus.

Generator properties

Property Import Export
name SynchronousMachine.name; mRID gen_ + name, lowercased the CIM name or mRID
phases, bus1 node, phases; default 3 phases as the shared terminal rule
kv ratedU (kV), line to line (derived); default 12.47 kv from ratedU
kW p (kW) = -kW (derived); default 1000 get_der_output total p, generation sign
pf, kvar q (kVAr) = -kvar, replayed (derived); pf default 0.88 kvar = total q, written after kW; pf is not written
kVA ratedS (kVA); default 1.2 x kW ratedS
conn earthing: wye true, delta false earthing true is wye, false is delta; unset raises
model table above table above
Vpu model 3: RegulatingControl.targetValue = Vpu x ratedU in kV, with targetValueUnitMultiplier=k; default 1 model 3: target / ratedU
maxkvar, minkvar maxQ, minQ (kVAr), model 3 only; default 2 x kvar and -2 x kvar, as the engine resets both whenever kW, pf or kvar is set, so a maxkvar or minkvar set before the last of those is the default too; on another model they raise model 3: maxQ, minQ; unset: not written
yearly the machine's EnergyConnectionSchedule <mRID>_yearly (see below) a LoadShape (see below)
enabled normallyInService; default true get_in_service(which='normal'); unset: not written
MVA, UserModel, UserData, ShaftModel, ShaftData raises when set not written
Xd, Xdp, Xdpp, H, D, XRdp untranscribed: dynamics not written: cim18v17 has no machine reactance or inertia, so the engine's defaults
Vminpu, Vmaxpu, pvfactor, Balanced, forceon, gen_class, debugtrace, DutyStart, daily, duty, DynamicEq, DynOut, spectrum, basefreq, like untranscribed not written
dispmode, dispvalue, status, UseFuel, FuelkWh, pct_Fuel, pct_Reserve, Refuel untranscribed: dispatch and fuel settings of a time series; with a yearly shape a dispmode other than default, a dispvalue above 0 or a status of Fixed raises not written

Yearly shape. The engine scales kW and kvar by mult. The importer writes the machine's EnergyConnectionSchedule with p = -kW x mult and q = -kvar x mult at each sample; a model 3 machine's q is its control's, so its schedule carries p only. The exporter writes mult = p / kW, and each point's q must be kvar x mult (a model 3 machine's is not checked); a kW of 0 raises.

Wind turbines. A PowerElectronicsWindUnit behind a PowerElectronicsConnection has no DSS inverter class, so the exporter writes a model 1 Generator at the unit's output, on the inverter's bus, voltage and share of kVA. The inverter's q limits and maxIFault have no home on a model 1 generator and are not written. A schedule on a wind unit raises. The deck reads back as a SynchronousMachine.

Generator fail-fast rules

Rule Message
model 2, 4, 5, 6 Generator g: model ConstantZ is not mapped (models 1, 3 and 7 are)
maxkvar or minkvar on another model Generator g: Maxkvar/Minkvar on model ConstantPQ; only model 3 uses them
MVA, UserModel, UserData, ShaftModel, ShaftData Generator g: ... not mapped yet (no deck in the sweep sets them)
a yearly shape with a dispatch setting Generator g: yearly=... with dispmode=..., ...; only a generator that follows its shape is mapped (S9)
export: a control on another terminal its control monitors another terminal; a Generator regulates its own
export: a control that is not voltage, or has a deadband, an allowed range or a reverse target a ... control; a Generator regulates voltage, or [...] have no Generator slot
export: a yearly q off kvar x mult point 2 has q ... kVAr, not kvar ... x mult ...; the engine scales kvar with kW

Generator round trip

What Why
model 7 comes back as model 1 CIM has no current limit
Xd, Xdp, Xdpp, H come back at the engine's defaults cim18v17 has no machine reactance or inertia. A model 3 machine's admittance depends on Xdp, so a deck that sets it solves slightly differently
pf comes back as kvar q carries it
a machine without a kVA comes back with 1.2 x kW written ratedS carries it

Generator excerpt

From tests/atoms/generator/gens.cimtbl. steam is a model 3 machine with Vpu=1.02 on a 4.16 kV bus, so its control's target is 4.2432 kV, written in kV with targetValueUnitMultiplier=k. Its rows are copied from the file's tables, with each table's header:

Table SynchronousMachine: mRID, name, node, phases, ratedS (kVA), ratedU (kV), p (kW), q (kVAr), maxQ (kVAr), minQ (kVAr), earthing, normallyInService, BaseVoltage, type=generator, operatingMode=generator, EquipmentContainer=fdr_atom
    # model ConstantPV: a PV bus: a voltage RegulatingControl
    # defaulted: phases=3, pf=0.88, conn=wye, enabled=true
    gen_steam,     steam,     b1, ,  4000.0, 4.16,                -1000.0, -539.7428221380871,  1079.4856442761743, -1079.4856442761743, true,  true, bv_4p16kv

# model 3 (PV bus): the machine regulates its own terminal
Table RegulatingControl: mRID, targetValue, Terminal, targetValueUnitMultiplier=k, mode=voltage, discrete=false, enabled=true, targetDeadband=0
    # derived: targetValue (kV) = Vpu=1.02 x ratedU
    gen_steam_ctrl,  4.2432, gen_steam_T1

Update Table SynchronousMachine: mRID, RegulatingControl, controlEnabled=true
    gen_steam,  gen_steam_ctrl

Round trip two of the atom's generators. edited sets kW=620 kvar=30 and then kW=50, and is model 7:

for line in round_trip("generator/gens.dss", schema.Generator):
    if " Generator.steam " in line or " Generator.edited " in line:
        print(line)
new Generator.edited phases=3 bus1=b2.1.2.3 kv=0.48 kW=50 kvar=2.41935483870966 model=1 conn=wye kVA=775 enabled=Yes
new Generator.steam phases=3 bus1=b1.1.2.3 kv=4.16 kW=1000 kvar=539.742822138087 model=3 conn=wye Vpu=1.02 maxkvar=1079.48564427617 minkvar=-1079.48564427617 kVA=4000 enabled=Yes

Device shapes

A yearly LoadShape on a PVSystem, Storage or Generator is that device's own EnergyConnectionSchedule <mRID>_yearly, not a load group. The rows are in the device's .cimtbl; the points (p and q at each sample, in watts and vars, the load sign) are in the EnergyConnectionTimePoint table of the sidecar, with atTime the epoch 2020-01-01T00:00Z plus k x interval for sample k. The sidecar travels as for load shapes, through the time_points dict of DssImporter and DssExporter (see LoadShape), and the core time series guide describes the table.

The exporter writes one LoadShape per schedule, named after the schedule and shared when name, interval and multipliers agree. A schedule with uneven points raises (a LoadShape has one interval), and so does a schedule on a connection written as several DSS objects or with several units: one shape would scale them all by one multiplier, which CIM does not say.

path = ATOMS / "loadshape/devices.dss"
time_points = {}
DssImporter(path.stem, time_points=time_points).to_cim(DssReader(path).read_all())
rows = time_points["EnergyConnectionTimePoint"].to_pylist()
print(len(rows), [(row["atTime"].isoformat(), round(row["p"], 1)) for row in rows[:3]])

for line in round_trip("loadshape/devices.dss", schema.Loadshape, schema.Pvsystem):
    if " Loadshape.sun" in line or " Pvsystem.p2 " in line:
        print(line)
20 [('2020-01-01T00:30:00+00:00', 0.0), ('2020-01-01T01:00:00+00:00', -18000.0), ('2020-01-01T01:30:00+00:00', -54000.0)]
new Loadshape.sun npts=6 mult=[0 0.2 0.6 1 0.5 0] sinterval=1800
new Loadshape.sun_2 npts=6 mult=[0 0.2 0.6 0.816496580927726 0.5 0] sinterval=1800
new Pvsystem.p2 phases=1 bus1=b1.1 kv=2.40177711982884 irrad=1 Pmpp=60 %Pmpp=81.6496580927726 conn=wye kvar=10 kVA=50 %Cutin=0 %Cutout=0 Vminpu=0.9 yearly=sun_2 kvarMax=50 kvarMaxAbs=50 enabled=Yes

Two PVs (p1, p2) name sun in the deck. p2 is cut to fit its 50 kVA, so its multipliers differ and it takes sun_2.