What converts

Which DSS classes import and export today. The source of truth is the code: the importer's mappers are listed in MAPPING_ORDER in importer/dss_to_cimtbl.py and the exporter modules in EXPORT_ORDER in exporter/cim_to_dss.py. The tables below follow those two lists in order. Property-level detail is in the import mapping and the export mapping, where every property is classified. Each class links to the conversion reference page that describes it.

Classes that convert

In MAPPING_ORDER order, which is the order the importer's Imports run: catalogs before the equipment that uses them.

DSS class CIM class (cim18v17) Import Export Reference
WireData OverheadWireInfo yes yes lines
CNData ConcentricNeutralCableInfo yes yes lines
TSData TapeShieldCableInfo yes yes lines
LineSpacing XYSpacing (template) yes inline in LineGeometry lines
LineGeometry WireConfiguration with a WireSpacing yes yes lines
LineCode PerLengthPhaseImpedance (matrix) or PerLengthSequenceImpedance, in a template WireConfiguration yes yes lines
XfmrCode TransformerTankConfiguration yes yes transformers
Vsource EnergySource yes yes sources
Line ACLineSegment, or a switch class when Switch=y yes yes lines
Reactor SeriesCompensator yes yes lines
Transformer PowerTransformer, VoltageRegulator yes yes transformers
RegControl TapChangerControl on a RatioTapChanger yes yes transformers
LoadShape ConformLoadGroup and ConformLoadSchedule, or a device's EnergyConnectionSchedule yes, those named as yearly yes, with time points loads
Load EnergyConsumer or ConformLoad, with a LoadResponseCharacteristic yes yes loads
Capacitor LinearShuntCompensator yes yes loads
CapControl RegulatingControl on the compensator yes yes loads
PVSystem PowerElectronicsConnection with a PhotoVoltaicUnit yes yes DER
Storage PowerElectronicsConnection with a BatteryUnit yes yes DER
Generator SynchronousMachine yes yes DER

The Line mapper also reads the controls that switch a line, so they convert with it:

DSS class CIM class Import Export Reference
Fuse Fuse yes yes lines
Recloser Recloser, with its RecloseSequences yes yes lines
SwtControl the switch's state yes yes lines

And the deck's settings and coordinates:

In the deck CIM Import Export Reference
New Circuit Substation, Feeder and the circuit's EnergySource yes yes sources
Set defaultbasefreq BaseFrequency yes yes sources
Set voltagebases BaseVoltages: one per bus voltage the topology walk reaches and one per voltagebases value, so a base on no bus is kept. On export it is every BaseVoltage. yes yes sources
Set earthmodel EarthResistivity of the geometry WireConfigurations; in a deck without geometry, one that no line names yes yes sources
BusCoords, LatLongCoords files Locations with PositionPoints yes yes sources

The exporter's modules, in EXPORT_ORDER: vsource, wire, linecode, linegeometry, line, switch, xfmrcode, transformer, regcontrol, loadshape, load, capacitor, capcontrol, pvsystem, storage, generator, reactor, buscoords.

Notes:

  • A Line with Switch=y imports as a switch. A Fuse or Recloser that names it as its SwitchedObj sets the class, and any other switch is a LoadBreakSwitch; its SwtControl or Open command gives the state. On export, every switch class other than Fuse and Recloser comes back as a LoadBreakSwitch.
  • A regulated Transformer with equal winding voltages imports as a VoltageRegulator.
  • A Transformer's or XfmrCode's Seasons and Ratings import as one ApparentPowerLimit per season (kVA), and its RdcOhms as each winding's rDC; both export back. normhkVA and emerghkVA are not imported.
  • On export, a CIM AutoTransformer is written as a DSS Transformer.
  • A Line that names a Geometry imports as a WireConfiguration, never as a computed impedance matrix, and exports back as a LineGeometry.
  • A Load that names a yearly shape imports as a ConformLoad of that shape's group. daily and duty are not imported, so a load that names only those imports with its base power and no time series.
  • The shape's points go to the time_points dict (see Import).

Classes that do not convert

The reader parses every class in the schema. These have no mapper and no exporter, so the importer skips them and lists each by count in the master's not mapped: comment:

Group DSS classes
Transformers AutoTrans, GICTransformer
Sources Isource, GICsource, VCCS, VSConverter, UPFC, Generic5
Rotating machines IndMach012, WindGen
Lines GICLine
Controls and dispatch InvControl, ExpControl, StorageController, GenDispatcher, ESPVLControl, UPFCControl, Relay, PyControl, DynamicExp
Meters and faults EnergyMeter, Monitor, Sensor, Fault, FMonitor
Curves and shapes GrowthShape, PriceShape, TShape, XYCurve, TCC_Curve, Spectrum

A LoadShape that no Load, PVSystem, Storage or Generator names as yearly is also not mapped, and the master's comment counts it (not mapped: Loadshape 1).

A deck that uses one of these still imports. What the class would have configured is absent from the CIM network. For example, a Load that names a daily load shape imports with its base power and no daily curve.

Properties that raise

Inside a class that converts, a property can be classified as raising when set. The importer refuses it instead of dropping it. The ones users meet most are in Import. The complete list is the classification table in each section of the import mapping; each raising property says in its row what deck would justify mapping it.

Export limits

Export is the inverse of the same mappings, with these limits:

  • Conducting equipment of a CIM class no exporter module handles raises, naming the class and count.
  • Protection settings with no home in cim18v17's protection function blocks (for example FuseCurve) are written as the engine's default. The export mapping marks them unset.
  • Property-level gaps are marked not mapped in the same tables.
  • A NonConformLoad, a schedule without points and a load group of days by season and day type are written as static loads, with one warning.