Loads, capacitors and shapes¶
This page is the conversion reference for the OpenDSS classes that draw power or switch a shunt: Load,
Capacitor, CapControl and LoadShape. For each one it says what the importer writes, what the exporter reads
back and what raises. The field classes (copied, mapped, structural, derived, untranscribed) and the conventions
every section follows are on the reference index. The getters the exporter reads through are on the
core site's loads, shunts and compensators page.
| DSS class | CIM classes | .cimtbl artifact and shape |
Importer | Exporter |
|---|---|---|---|---|
Load |
EnergyConsumer, or ConformLoad with a yearly shape; LoadResponseCharacteristic |
load.cimtbl, shape load |
importer/cimtbl/load.py |
exporter/load.py |
Capacitor |
LinearShuntCompensator |
capacitor.cimtbl, shape shunt |
importer/cimtbl/capacitor.py |
exporter/capacitor.py |
CapControl |
RegulatingControl, and an update of its LinearShuntCompensator |
capcontrol.cimtbl, shape shunt |
importer/cimtbl/capcontrol.py |
exporter/capcontrol.py |
LoadShape |
ConformLoadGroup, ConformLoadSchedule, and RegularTimePoint rows in a Parquet sidecar |
loadshape.cimtbl, shape load_schedule |
importer/cimtbl/loadshape.py |
exporter/loadshape.py |
The table shapes are on the core site's shapes page.
The master imports loadshape.cimtbl before load.cimtbl, and capcontrol.cimtbl after capacitor.cimtbl, so
each reference resolves. Source paths are under
cimhub_opendss/src/cimhub_opendss/.
Load, capacitor, PV, battery and generator share one terminal rule, in importer/cimtbl/injection.py
(device_terminal, rated_phase_kv, line_kv) and, inverted, in exporter/injection.py (device_connection,
device_kv, rated_kv). CapControl and RegControl share exporter/controls.py (pt_phase, control_enabled).
The examples run from the repository root with uv run python. They convert the public test atoms in
cimhub_opendss/tests/atoms to CIM and
back. This helper is shared by all of them:
from pathlib import Path
from cimhub_opendss import DssExporter, DssImporter, DssReader, DssWriter
from cimhub_opendss.schema import opendss_schema as schema
ATOMS = Path("cimhub_opendss/tests/atoms")
def round_trip(atom: str, *classes):
"""Import an atom deck to CIM, export it, and return the DSS lines of `classes`."""
path = ATOMS / atom
time_points = {}
network = DssImporter(path.stem, time_points=time_points).to_cim(DssReader(path).read_all())
model = DssExporter(time_points).to_model(network, name_source="name")
writer = DssWriter()
return [writer.serialize(record) for cls in classes for record in model.list_by_class(cls)]
name_source="name" writes each object under its CIM name, which the importer set to the deck's name. The default
is the mRID (ld_cvr1, cap_c1).
Load¶
One EnergyConsumer per Load, mRID ld_ + the name, lowercased. A load that names a yearly shape is a
ConformLoad of that shape's group (see LoadShape). On export an EnergyConsumer, ConformLoad,
NonConformLoad or StationSupply each becomes a Load. CIM gives a load no rated voltage: p and q are
at the BaseVoltage of the bus.
Power. The last of kW, kvar and kVA picks the pair the engine computes from: (kW, pf), (kW,
kvar) or (kVA, pf); pf never changes it, so kvar wins over pf in either order. (kW, pf) gives
q = kW x tan(acos abs(pf)) with the sign of pf (default 0.88); (kVA, pf) gives p = kVA x abs(pf).
At the end of each command the engine recomputes the other values from the pair, so the mapper replays the deck
command by command: kVA=100 kvar=30 is 10 kW in one command and 88 kW with kvar in a later Edit. The values
are in kW and kVAr, as the column headers say.
Phases and connection. The bus's node numbers give the phases: 1, 2, 3 are A, B, C, and on a split-phase
island 1 and 2 are s1 and s2. A node list left out is the DSS default (conductor k on node k). conn=wye is
phaseConnection Y and grounded true; conn=delta is D and not grounded. A 2-phase delta load raises. On
export, a wye load needs grounded true (DSS puts its neutral on node 0), and a delta load across two phases is
written as phases=1 in branch order (.1.2, .2.3, .3.1).
Voltage response. The model property picks a LoadResponseCharacteristic:
DSS model |
Import: EnergyConsumer.LoadResponse |
Export |
|---|---|---|
| 1, constant PQ | zip_constant_pq |
the power fractions of get_load_response are 1 |
| 2, constant Z | zip_constant_z |
the impedance fractions are 1 |
| 5, constant I | zip_constant_i |
the current fractions are 1 |
| 4, CVR | exp_<CVRwatts>_<CVRvars>, one row per pair in load.cimtbl, exponentModel true |
exponential: model=4 with CVRwatts, CVRvars from the exponents |
| 3, 6, 7, 8 | raises | not produced |
| any other mix of fractions | not produced | raises |
The three zip_ rows come from the fixed zip_fractions.cimtbl that every distribution converter imports.
Load properties¶
| Property | Import | Export |
|---|---|---|
name |
EnergyConsumer.name; mRID ld_ + name, lowercased |
the CIM name or mRID (name_source); one load per phase is <name>_<phase> |
bus1, phases |
node, phases (structural, see above) |
bus1 is the bus on the phase conductors; phases counts them |
kV |
not written: raises when the phase voltage it gives is more than 1 % off the bus's | the bus's BaseVoltage: line to line for delta and for 2 or 3 phases, line to neutral for 1-phase wye |
kW |
EnergyConsumer.p (kW) |
get_phase_loads total p, in kW |
kvar |
EnergyConsumer.q (kVAr) |
get_phase_loads total q, in kVAr |
pf |
derived into q |
not written |
kVA |
derived into p and q when it is the last of kW, kvar and kVA |
not written |
model |
LoadResponse (table above); default 1 |
get_load_response |
CVRwatts, CVRvars |
LoadResponseCharacteristic.pVoltageExponent, qVoltageExponent; model 4 only; defaults 1 and 2 |
model 4 only, from the response's exponents |
conn |
phaseConnection and grounded; default wye |
Y and Yn are wye, D is delta; another kind raises |
NumCust |
EnergyConsumer.customerCount; default 1 |
customerCount; unset: not written |
enabled |
EnergyConsumer.normallyInService; default true |
get_in_service(which='normal'); unset: not written |
yearly |
ConformLoad.LoadGroup = lg_<shape>; a shape the deck does not define raises |
the group's LoadShape when its schedule has points; otherwise the load is static |
daily, duty, growth, CVRcurve |
untranscribed: a ConformLoad has one group, its yearly shape's |
not written |
status, Vminpu, Vmaxpu, Vminnorm, Vminemerg, Vlowpu |
untranscribed: solver settings with no CIM home | not written, so the engine's defaults |
Rneut, Xneut |
raises when set (a Rneut below 0, no neutral, is allowed) |
not written |
xfkVA, allocationfactor |
raises: with kW the engine takes whichever comes last |
not written |
ZIPV |
untranscribed: only model 8 uses it, and model 8 raises | model 8 is never produced |
kwh, kwhdays, Cfactor, load_class, pct_mean, pct_stddev, RelWeight, pct_SeriesRL, puXharm, XRharm, spectrum, basefreq, like |
untranscribed (like is resolved by the reader first) |
not written |
An untranscribed value that a deck sets is listed in a # untranscribed: comment on the row, so nothing disappears
silently.
Load fail-fast rules¶
| Rule | Message |
|---|---|
kV more than 1 % off its bus |
Load a: kV=12.47 on bus b1, whose ABC Y phase voltage is 4.16 kV; CIM has no load rating, so p would be at the wrong voltage |
model 3, 6, 7 or 8 |
Load a: model ConstantPQuadQ is not mapped (models 1, 2, 4 and 5 are) |
yearly names no LoadShape |
Load a: yearly=nope names no LoadShape of the deck |
Rneut of 0 or more, or Xneut |
Load a: Rneut not mapped yet (no deck in the sweep sets them) |
xfkVA or allocationfactor |
Load a: xfkVA/allocationfactor not mapped (with kW the engine takes whichever comes last, and the record keeps no order) |
| export: unequal phases on a delta load | a delta load with unequal phases; a CIM phase on a delta load names no branch (E8) |
| export: ZIP fractions of no one model | ZIP fractions {...} are no one DSS model (1, 2, 5) |
Load round trip¶
| What | Why |
|---|---|
kV comes back as the bus's phase voltage (2.4 on a 4.16 kV bus is 2.40178) |
CIM has no load rating. A constant-PQ load solves to the same power; a Z, I or CVR load's power follows the voltage ratio, by 0.15 % for a constant-Z load here |
pf and kVA come back as kW and kvar |
p and q carry the power |
unequal per-phase values come back as one 1-phase Load per phase, <name>_<phase>, the first carrying NumCust and the others 0 |
a load from another CIM source can carry EnergyConsumerPhase values; a DSS deck never does |
daily, duty and the untranscribed settings come back at the engine's defaults |
no CIM home |
| a load whose shape has no points comes back static, with one warning that lists the groups | see LoadShape |
A disabled load stays in the model with normallyInService false and comes back enabled=No.
Load excerpt¶
From tests/atoms/load/loads.cimtbl.
The comments name the defaults the deck relied on:
# model 4 (CVR): p = p0 (V/V0)^CVRwatts, q = q0 (V/V0)^CVRvars
Table LoadResponseCharacteristic: mRID, exponentModel, pVoltageExponent, qVoltageExponent
exp_0.8_3, true, 0.8, 3.0
exp_1_2, true, 1.0, 2.0
Table EnergyConsumer: mRID, name, node, phases, phaseConnection, grounded, p (kW), q (kVAr), customerCount, LoadResponse, normallyInService, BaseVoltage, EquipmentContainer=fdr_atom
# defaulted: NumCust=1, enabled=true
ld_ca, ca, b1, CA, D, false, 170.0, 82.33475782243494, 1, zip_constant_i, true, bv_4p16kv
# defaulted: conn=wye, NumCust=1, enabled=true
ld_cvr1, cvr1, b1, A, Y, true, 100.0, 32.86841051788632, 1, exp_0.8_3, true, bv_4p16kv
Round trip two of the atom's loads (cvr1 is model 4, house is a 2-phase split-phase load):
for line in round_trip("load/loads.dss", schema.Load):
if " Load.cvr1 " in line or " Load.house " in line:
print(line)
new Load.cvr1 phases=1 bus1=b1.1 kV=2.40177711982884 kW=100 model=4 conn=wye kvar=32.8684105178863 CVRwatts=0.8 CVRvars=3 NumCust=1 enabled=Yes
new Load.house phases=2 bus1=house.1.2 kV=0.207846096908265 kW=5 model=1 conn=wye kvar=3.09872169201551 NumCust=1 enabled=Yes
The deck's kV=2.40177711982884 for cvr1 is already the bus's phase voltage. house had kV=0.208 and comes back
as the leg pair's 0.2078.
Capacitor¶
One LinearShuntCompensator per Capacitor, mRID cap_ + the name, lowercased. Only a one-section bank maps.
nomQ is kvar (the total over the phases) and nomU is kv, both as the deck rates them. bPerSection is
nomQ / nomU^2: kVAr over kV squared is millisiemens, so the column is bPerSection (mS) and no factor appears. maximumSections is 1, and sections
and normalSections are the steps states closes. A bank whose kv differs
from its bus's keeps its rated kv (13.8 kV on a 13.2 kV bus stays).
Capacitor properties¶
| Property | Import | Export |
|---|---|---|
name |
LinearShuntCompensator.name; mRID cap_ + name, lowercased |
the CIM name or mRID (name_source) |
bus1, phases, conn |
node, phases, phaseConnection and grounded, as for a load; default 3 phases, wye |
the same connection rule as a load |
kvar |
nomQ (kVAr), the total over the phases; default 1200; more than one step raises |
kvar=[x] from get_shunt_reactive_power(sections='maximum', voltage='nominal'), in kVAr; maximumSections other than 1 raises |
kv |
nomU (kV), and bPerSection (mS); line to neutral for a 1-phase wye bank, else line to line; default 12.47 |
nomU, the voltage bPerSection was derived on |
Numsteps |
maximumSections; more than 1 raises (unequal steps would need a NonlinearShuntCompensator) |
not written; maximumSections above 1 raises |
states |
sections = normalSections = the steps closed; default all closed |
states=[sections]; sections other than 0 or 1 raises; normalSections is not written |
enabled |
normallyInService; default true |
get_in_service(which='normal'); unset: not written |
bus2, cmatrix, cuf, normamps, emergamps |
raises when set | not written |
R, XL |
0 is untranscribed, any other value raises | not written |
Harm, faultrate, pctperm, repair, basefreq, like |
untranscribed | not written |
Capacitor fail-fast rules¶
| Rule | Message |
|---|---|
| more than one step | Capacitor c: 2 steps; only one section is mapped |
bus2, cmatrix, cuf, nonzero R or XL, normamps, emergamps |
Capacitor c: R not mapped yet (no deck in the sweep sets them) |
export: maximumSections other than 1 |
maximumSections 2; one section is mapped, as on import |
export: sections other than 0 or 1 |
sections 2; a one-section bank has 0 or 1 |
Capacitor round trip¶
| What | Why |
|---|---|
normalSections is lost |
DSS has no normal state for a capacitor; states carries sections |
R=0 and the reliability settings come back at the engine's defaults |
untranscribed |
Capacitor excerpt¶
From tests/atoms/capacitor/caps.cimtbl:
# derived: bPerSection = nomQ / nomU^2 (b_per_section); sections = normalSections = the steps states closes
Table LinearShuntCompensator: mRID, name, node, phases, phaseConnection, grounded, nomQ (kVAr), nomU (kV), bPerSection (mS), maximumSections, normalSections, sections, normallyInService, BaseVoltage, EquipmentContainer=fdr_atom
# defaulted: conn=wye, Numsteps=1, enabled=true
cap_c1, c1, b2, C, Y, true, 100.0, 2.4, 17.36111111111111, 1, 1, 1, true, bv_4p16kv
CapControl¶
One RegulatingControl per CapControl, mRID cc_ + the name, lowercased. The control is in capcontrol.cimtbl,
and an update of the LinearShuntCompensator it regulates gives that bank its RegulatingControl, aVRDelay (s)
and controlEnabled. So the capacitor mapper knows nothing of controls, and a control on its own capacitor makes no
reference cycle.
The control's Terminal is the monitored element's: ln_<line>_T<n> for a line, sw_<switch>_T<n> for a switch
line, cap_<capacitor>_T<n> for a capacitor. An element of another class raises.
ON and OFF. CIM has a target and a deadband in primary units, and DSS has ON and OFF settings on the relay's
side. The importer writes targetValue = (ON + OFF) / 2 and targetDeadband = abs(OFF - ON), after scaling by
PTratio (voltage) or CTratio (current). A kvar control's values stay in kvar, and the row says so with
targetValueUnitMultiplier=k. The exporter inverts it and divides by the same ratio.
DSS type |
RegulatingControl.mode |
ON is | targetValue and targetDeadband are in |
|---|---|---|---|
voltage |
voltage |
below OFF | V: ON and OFF x PTratio |
current |
currentFlow |
above OFF | A: ON and OFF x CTratio |
kvar |
reactivePower |
above OFF | kvar, with targetValueUnitMultiplier=k |
time |
timeScheduled |
below OFF | hours from midnight |
pf, follow |
raises |
The type is read by a unique prefix, as the engine reads it (volt is voltage); the default is current. A control
with ON on the wrong side of OFF for its type raises, so the exporter can rebuild the pair from the mode.
CapControl properties¶
| Property | Import | Export |
|---|---|---|
name |
RegulatingControl.name; mRID cc_ + name, lowercased |
the CIM name or mRID (name_source) |
element, terminal |
RegulatingControl.Terminal; terminal defaults to 1; a Line, switch or Capacitor that no New defines raises |
Line.<line or switch> or Capacitor.<shunt> of the monitored Terminal's equipment, and its sequenceNumber; other equipment raises |
capacitor |
the update row names cap_<capacitor>; one that no New defines raises, and so do two controls on one capacitor |
the one LinearShuntCompensator the control regulates; anything else regulated raises |
type |
RegulatingControl.mode (table above); default current |
voltage, currentFlow, reactivePower, timeScheduled give voltage, current, kvar, time; another mode raises |
PTratio, CTratio |
ptRatio, ctRatio; default 60 |
written when set; a voltage control needs ptRatio and a current control needs ctRatio, else it raises |
ONsetting, OFFsetting |
targetValue, targetDeadband (derived); defaults 300 and 200 |
ON and OFF = target -+ deadband / 2 (on_off_from_band), then divided by the ratio; an unset targetDeadband raises |
Delay |
LinearShuntCompensator.aVRDelay (s) on the update row; default 15 |
the shunt's aVRDelay; unset: not written |
PTPhase |
monitoredPhase: the phase of the monitored terminal's conductor PTPhase (default 1); a number past the conductors raises, and AVG, MAX and MIN raise ValueError in the mapper |
the 1-based place of monitoredPhase among the monitored equipment's phase conductors |
enabled |
RegulatingControl.enabled, and controlEnabled on the update row; default true |
the control's enabled; the shunt's controlEnabled must agree |
VoltOverride, Vmax, Vmin, DelayOFF, DeadTime |
untranscribed: no CIM home | not written, so the engine's defaults |
CTPhase, VBus, UserModel, UserData, ControlSignal |
raises when set | not written |
EventLog, pctMinkvar, Reset, basefreq, like |
untranscribed | not written |
CapControl fail-fast rules¶
| Rule | Message |
|---|---|
type=pf or follow |
CapControl cc: type=pf is not mapped |
| ON on the wrong side of OFF | CapControl cc: ON -300.0 is not above OFF 150.0 for a reactivePower control |
export: another mode |
mode ...; a CapControl is voltage, current, kvar or time |
export: targetDeadband unset |
targetDeadband is unset; a CapControl needs ON and OFF |
| export: an allowed range or a reverse setting | [...] have no CapControl slot |
| export: a control that does not regulate exactly one capacitor | regulates [...]; a CapControl has one LinearShuntCompensator |
A RegulatingControl that regulates a SynchronousMachine is the machine's own and is written by its Generator
(see DER and machines). A TapChangerControl is a RegControl, on the
transformers page.
CapControl round trip¶
| What | Why |
|---|---|
VoltOverride, Vmax, Vmin, DelayOFF, DeadTime come back at the defaults |
untranscribed. A kvar control that used VoltOverride acts differently when the engine solves it |
type=volt comes back voltage |
the type is written out in full |
CapControl excerpt¶
From tests/atoms/capacitor/caps_capcontrol.cimtbl.
A kvar control on a switch line (ON 150, OFF -225 kvar), then the update of its capacitor:
Table RegulatingControl: mRID, name, mode, discrete=true, enabled, monitoredPhase, ptRatio, ctRatio, targetValue, targetDeadband, targetValueUnitMultiplier, Terminal
# derived from ON=150.0, OFF=-225.0
# defaulted: PTPhase=1, enabled=true
# untranscribed: VoltOverride=true, Vmax=7740.0, Vmin=7110.0, DelayOFF=90.0
cc_kvar, kvar, reactivePower, true, A, 1.0, 1.0, -37.5, 375.0, k, sw_capsw_T1
# the compensator's control, delay (Delay) and controlEnabled
Update Table LinearShuntCompensator: mRID, RegulatingControl, aVRDelay (s), controlEnabled
cap_c3, cc_kvar, 100.0, true
The same atom round trips. c1 is a 1-phase bank that a voltage control on line l2 switches:
for line in round_trip("capacitor/caps.dss", schema.Capacitor, schema.Capcontrol):
if " Capacitor.c1 " in line or " Capcontrol.volt " in line:
print(line)
new Capacitor.c1 phases=1 bus1=b2.3 kvar=[100] kv=2.4 conn=wye states=[1] enabled=Yes
new Capcontrol.volt element=Line.l2 terminal=2 capacitor=c1 type=voltage PTratio=20 CTratio=60 on=115 off=125 Delay=15 PTPhase=1 enabled=Yes
LoadShape¶
A LoadShape that a Load names as yearly is a curve of multipliers on that load's kW and kvar. It maps to
a ConformLoadGroup lg_<name> with one ConformLoadSchedule ls_<name>, and every load that names it is a
ConformLoad of the group. The points are not in the .cimtbl: they go to the RegularTimePoint table of a
Parquet sidecar, one row per sample, as the core site's
time series guide describes. Pass the dict that
receives them to the converters:
| Direction | How the points travel |
|---|---|
| import | DssImporter(name, time_points={}) (or dss_to_cim(..., time_points=)) fills the dict. Without it the points are dropped with one warning |
| export | DssExporter(time_points) (or cim_to_dss(..., time_points=)) reads the dict. Without it the loads are written static |
A shape that a PVSystem, Storage or Generator names as yearly is not a load group. It is that device's own
EnergyConnectionSchedule, described on DER and machines. A shape that nothing names is not mapped, and
the master's comment counts it (not mapped: Loadshape 1).
Time. DSS has no date. Sample k (from 1) is in force from k x interval, so startTime is 2020-01-01T00:00Z plus
one interval, and sequenceNumber counts from 0. The timeStep keeps the unit of the interval slot the deck
assigned last, with one ConformLoadSchedule table per unit (h, min, s). The engine wraps a shape around, and
CIM has no repeat, so the wrap is lost.
No npts. The engine reads none of mult without npts (a bare mult=1), so the load stays constant. Such a
shape becomes a ConformLoadGroup with no schedule, its name kept.
LoadShape properties¶
| Property | Import | Export |
|---|---|---|
name |
ConformLoadGroup.name and ConformLoadSchedule.name; mRIDs lg_ and ls_ + name, lowercased |
a LoadShape named after the group (the Loadshape namespace) |
npts |
structural: unset means no schedule; otherwise it must equal the number of mult values |
the number of points |
mult |
RegularTimePoint.value1 in the sidecar, value1Unit none |
mult = value1 of each point, in sequence order |
qmult |
RegularTimePoint.value2, value2Unit none; unset: Q follows mult, as in the engine |
qmult = value2; not written when value2 is unset |
interval, minterval, sinterval |
ConformLoadSchedule.timeStep in h, min or s, from the slot assigned last; none is 1 h; 0 or less (0 is an hour array) raises |
always sinterval = timeStep in seconds; a timeStep that is not positive raises |
action |
normalize divides mult and qmult each by its largest magnitude, as the engine does; an array assigned after it raises; DblSave and SngSave are untranscribed; any other raises |
not written |
UseActual |
raises when yes: whether a load takes the shape's peak as its kW depends on command order | a NonConformLoad is written static |
hour, csvfile, sngfile, dblfile, PQCSVFile, Pmult, Pbase, Qbase |
raises when set | not written |
mean, stddev, Pmax, Qmax, MemoryMapping, Mode, Interpolation, like |
untranscribed | not written |
On export, a schedule whose values have a unit other than none raises, because a conform schedule holds
multipliers. Owners whose name, interval and multipliers agree share one LoadShape; another with that name and
other points takes a suffix (sun, sun_2).
A ConformLoad is written static, with one warning that lists its group, when the group has no schedule, the
schedule has no points, the group holds days by season and day type (a GridLAB-D schedule's, which DSS has no
calendar for), or the load is a NonConformLoad.
LoadShape fail-fast rules¶
| Rule | Message |
|---|---|
UseActual=yes |
LoadShape s: UseActual=Yes; a Load naming it takes the shape's peak as its kW or keeps its own by command order, which the record does not keep |
npts is not the number of mult values |
LoadShape s: npts=3 but mult has 2 values |
| an interval of 0 | LoadShape s: interval=0.0; an hour array (interval 0) is not mapped |
qmult of another length, no mult, a file or hour array, an unknown action |
LoadShape s: ... naming the property |
LoadShape round trip¶
| What | Why |
|---|---|
interval= and minterval= come back as sinterval= |
one written form; the interval is equal |
a shape that no load names, and a load's daily and duty |
not imported |
a bare mult=1 shape is not written, and its loads have no yearly |
the engine reads no points from it, so the loads are constant either way |
| the wrap-around, and a GridLAB-D player's date | CIM has no repeat, DSS has no date |
LoadShape excerpt¶
From tests/atoms/loadshape/loadshapes.loadshape.cimtbl:
Table ConformLoadGroup: mRID, name
lg_com, com
# npts unset: the engine reads none of mult (S8), so no schedule
lg_flat, flat
lg_ind, ind
lg_res, res
Table ConformLoadSchedule: mRID, name, startTime, timeStep (h), value1Unit, value2Unit, ConformLoadGroup
ls_res, res, 2020-01-01T01:00:00+00:00, 1.0, none, none, lg_res
Import the atom, look at the sidecar, and export the shape and one of the loads that names it:
path = ATOMS / "loadshape/loadshapes.dss"
time_points = {}
DssImporter(path.stem, time_points=time_points).to_cim(DssReader(path).read_all())
print(sorted(time_points))
rows = time_points["RegularTimePoint"].to_pylist()
print(len(rows), [row["value1"] for row in rows[:4]])
for line in round_trip("loadshape/loadshapes.dss", schema.Loadshape, schema.Load):
if " Loadshape.res " in line or " Load.r1 " in line:
print(line)
['RegularTimePoint']
11 [0.25, 0.5, 1.0, 0.75]
new Loadshape.res npts=4 mult=[0.5 0.75 1 0.8] qmult=[0.4 0.6 0.9 0.7] sinterval=3600
new Load.r1 phases=1 bus1=b1.1 kV=2.40177711982884 kW=100 model=1 yearly=res conn=wye kvar=40 NumCust=1 enabled=Yes
The 11 points are res (4), com (4) and ind (3); the first four are com after action=normalize
(2 4 8 6 over 8). The export also logs a warning that the group flat, a shape with no npts, is written static.