Loads, capacitors and shapes

This page is the conversion reference for the OpenDSS classes that draw power or switch a shunt: Load, Capacitor, CapControl and LoadShape. For each one it says what the importer writes, what the exporter reads back and what raises. The field classes (copied, mapped, structural, derived, untranscribed) and the conventions every section follows are on the reference index. The getters the exporter reads through are on the core site's loads, shunts and compensators page.

DSS class CIM classes .cimtbl artifact and shape Importer Exporter
Load EnergyConsumer, or ConformLoad with a yearly shape; LoadResponseCharacteristic load.cimtbl, shape load importer/cimtbl/load.py exporter/load.py
Capacitor LinearShuntCompensator capacitor.cimtbl, shape shunt importer/cimtbl/capacitor.py exporter/capacitor.py
CapControl RegulatingControl, and an update of its LinearShuntCompensator capcontrol.cimtbl, shape shunt importer/cimtbl/capcontrol.py exporter/capcontrol.py
LoadShape ConformLoadGroup, ConformLoadSchedule, and RegularTimePoint rows in a Parquet sidecar loadshape.cimtbl, shape load_schedule importer/cimtbl/loadshape.py exporter/loadshape.py

The table shapes are on the core site's shapes page. The master imports loadshape.cimtbl before load.cimtbl, and capcontrol.cimtbl after capacitor.cimtbl, so each reference resolves. Source paths are under cimhub_opendss/src/cimhub_opendss/.

Load, capacitor, PV, battery and generator share one terminal rule, in importer/cimtbl/injection.py (device_terminal, rated_phase_kv, line_kv) and, inverted, in exporter/injection.py (device_connection, device_kv, rated_kv). CapControl and RegControl share exporter/controls.py (pt_phase, control_enabled).

The examples run from the repository root with uv run python. They convert the public test atoms in cimhub_opendss/tests/atoms to CIM and back. This helper is shared by all of them:

from pathlib import Path

from cimhub_opendss import DssExporter, DssImporter, DssReader, DssWriter
from cimhub_opendss.schema import opendss_schema as schema

ATOMS = Path("cimhub_opendss/tests/atoms")


def round_trip(atom: str, *classes):
    """Import an atom deck to CIM, export it, and return the DSS lines of `classes`."""
    path = ATOMS / atom
    time_points = {}
    network = DssImporter(path.stem, time_points=time_points).to_cim(DssReader(path).read_all())
    model = DssExporter(time_points).to_model(network, name_source="name")
    writer = DssWriter()
    return [writer.serialize(record) for cls in classes for record in model.list_by_class(cls)]

name_source="name" writes each object under its CIM name, which the importer set to the deck's name. The default is the mRID (ld_cvr1, cap_c1).

Load

One EnergyConsumer per Load, mRID ld_ + the name, lowercased. A load that names a yearly shape is a ConformLoad of that shape's group (see LoadShape). On export an EnergyConsumer, ConformLoad, NonConformLoad or StationSupply each becomes a Load. CIM gives a load no rated voltage: p and q are at the BaseVoltage of the bus.

Power. The last of kW, kvar and kVA picks the pair the engine computes from: (kW, pf), (kW, kvar) or (kVA, pf); pf never changes it, so kvar wins over pf in either order. (kW, pf) gives q = kW x tan(acos abs(pf)) with the sign of pf (default 0.88); (kVA, pf) gives p = kVA x abs(pf). At the end of each command the engine recomputes the other values from the pair, so the mapper replays the deck command by command: kVA=100 kvar=30 is 10 kW in one command and 88 kW with kvar in a later Edit. The values are in kW and kVAr, as the column headers say.

Phases and connection. The bus's node numbers give the phases: 1, 2, 3 are A, B, C, and on a split-phase island 1 and 2 are s1 and s2. A node list left out is the DSS default (conductor k on node k). conn=wye is phaseConnection Y and grounded true; conn=delta is D and not grounded. A 2-phase delta load raises. On export, a wye load needs grounded true (DSS puts its neutral on node 0), and a delta load across two phases is written as phases=1 in branch order (.1.2, .2.3, .3.1).

Voltage response. The model property picks a LoadResponseCharacteristic:

DSS model Import: EnergyConsumer.LoadResponse Export
1, constant PQ zip_constant_pq the power fractions of get_load_response are 1
2, constant Z zip_constant_z the impedance fractions are 1
5, constant I zip_constant_i the current fractions are 1
4, CVR exp_<CVRwatts>_<CVRvars>, one row per pair in load.cimtbl, exponentModel true exponential: model=4 with CVRwatts, CVRvars from the exponents
3, 6, 7, 8 raises not produced
any other mix of fractions not produced raises

The three zip_ rows come from the fixed zip_fractions.cimtbl that every distribution converter imports.

Load properties

Property Import Export
name EnergyConsumer.name; mRID ld_ + name, lowercased the CIM name or mRID (name_source); one load per phase is <name>_<phase>
bus1, phases node, phases (structural, see above) bus1 is the bus on the phase conductors; phases counts them
kV not written: raises when the phase voltage it gives is more than 1 % off the bus's the bus's BaseVoltage: line to line for delta and for 2 or 3 phases, line to neutral for 1-phase wye
kW EnergyConsumer.p (kW) get_phase_loads total p, in kW
kvar EnergyConsumer.q (kVAr) get_phase_loads total q, in kVAr
pf derived into q not written
kVA derived into p and q when it is the last of kW, kvar and kVA not written
model LoadResponse (table above); default 1 get_load_response
CVRwatts, CVRvars LoadResponseCharacteristic.pVoltageExponent, qVoltageExponent; model 4 only; defaults 1 and 2 model 4 only, from the response's exponents
conn phaseConnection and grounded; default wye Y and Yn are wye, D is delta; another kind raises
NumCust EnergyConsumer.customerCount; default 1 customerCount; unset: not written
enabled EnergyConsumer.normallyInService; default true get_in_service(which='normal'); unset: not written
yearly ConformLoad.LoadGroup = lg_<shape>; a shape the deck does not define raises the group's LoadShape when its schedule has points; otherwise the load is static
daily, duty, growth, CVRcurve untranscribed: a ConformLoad has one group, its yearly shape's not written
status, Vminpu, Vmaxpu, Vminnorm, Vminemerg, Vlowpu untranscribed: solver settings with no CIM home not written, so the engine's defaults
Rneut, Xneut raises when set (a Rneut below 0, no neutral, is allowed) not written
xfkVA, allocationfactor raises: with kW the engine takes whichever comes last not written
ZIPV untranscribed: only model 8 uses it, and model 8 raises model 8 is never produced
kwh, kwhdays, Cfactor, load_class, pct_mean, pct_stddev, RelWeight, pct_SeriesRL, puXharm, XRharm, spectrum, basefreq, like untranscribed (like is resolved by the reader first) not written

An untranscribed value that a deck sets is listed in a # untranscribed: comment on the row, so nothing disappears silently.

Load fail-fast rules

Rule Message
kV more than 1 % off its bus Load a: kV=12.47 on bus b1, whose ABC Y phase voltage is 4.16 kV; CIM has no load rating, so p would be at the wrong voltage
model 3, 6, 7 or 8 Load a: model ConstantPQuadQ is not mapped (models 1, 2, 4 and 5 are)
yearly names no LoadShape Load a: yearly=nope names no LoadShape of the deck
Rneut of 0 or more, or Xneut Load a: Rneut not mapped yet (no deck in the sweep sets them)
xfkVA or allocationfactor Load a: xfkVA/allocationfactor not mapped (with kW the engine takes whichever comes last, and the record keeps no order)
export: unequal phases on a delta load a delta load with unequal phases; a CIM phase on a delta load names no branch (E8)
export: ZIP fractions of no one model ZIP fractions {...} are no one DSS model (1, 2, 5)

Load round trip

What Why
kV comes back as the bus's phase voltage (2.4 on a 4.16 kV bus is 2.40178) CIM has no load rating. A constant-PQ load solves to the same power; a Z, I or CVR load's power follows the voltage ratio, by 0.15 % for a constant-Z load here
pf and kVA come back as kW and kvar p and q carry the power
unequal per-phase values come back as one 1-phase Load per phase, <name>_<phase>, the first carrying NumCust and the others 0 a load from another CIM source can carry EnergyConsumerPhase values; a DSS deck never does
daily, duty and the untranscribed settings come back at the engine's defaults no CIM home
a load whose shape has no points comes back static, with one warning that lists the groups see LoadShape

A disabled load stays in the model with normallyInService false and comes back enabled=No.

Load excerpt

From tests/atoms/load/loads.cimtbl. The comments name the defaults the deck relied on:

# model 4 (CVR): p = p0 (V/V0)^CVRwatts, q = q0 (V/V0)^CVRvars
Table LoadResponseCharacteristic: mRID, exponentModel, pVoltageExponent, qVoltageExponent
    exp_0.8_3, true, 0.8, 3.0
    exp_1_2,   true, 1.0, 2.0

Table EnergyConsumer: mRID, name, node, phases, phaseConnection, grounded, p (kW), q (kVAr), customerCount, LoadResponse, normallyInService, BaseVoltage, EquipmentContainer=fdr_atom
    # defaulted: NumCust=1, enabled=true
    ld_ca,    ca,    b1,    CA,   D, false, 170.0,  82.33475782243494,   1, zip_constant_i,  true,  bv_4p16kv
    # defaulted: conn=wye, NumCust=1, enabled=true
    ld_cvr1,  cvr1,  b1,    A,    Y, true,  100.0,  32.86841051788632,   1, exp_0.8_3,       true,  bv_4p16kv

Round trip two of the atom's loads (cvr1 is model 4, house is a 2-phase split-phase load):

for line in round_trip("load/loads.dss", schema.Load):
    if " Load.cvr1 " in line or " Load.house " in line:
        print(line)
new Load.cvr1 phases=1 bus1=b1.1 kV=2.40177711982884 kW=100 model=4 conn=wye kvar=32.8684105178863 CVRwatts=0.8 CVRvars=3 NumCust=1 enabled=Yes
new Load.house phases=2 bus1=house.1.2 kV=0.207846096908265 kW=5 model=1 conn=wye kvar=3.09872169201551 NumCust=1 enabled=Yes

The deck's kV=2.40177711982884 for cvr1 is already the bus's phase voltage. house had kV=0.208 and comes back as the leg pair's 0.2078.

Capacitor

One LinearShuntCompensator per Capacitor, mRID cap_ + the name, lowercased. Only a one-section bank maps.

nomQ is kvar (the total over the phases) and nomU is kv, both as the deck rates them. bPerSection is nomQ / nomU^2: kVAr over kV squared is millisiemens, so the column is bPerSection (mS) and no factor appears. maximumSections is 1, and sections and normalSections are the steps states closes. A bank whose kv differs from its bus's keeps its rated kv (13.8 kV on a 13.2 kV bus stays).

Capacitor properties

Property Import Export
name LinearShuntCompensator.name; mRID cap_ + name, lowercased the CIM name or mRID (name_source)
bus1, phases, conn node, phases, phaseConnection and grounded, as for a load; default 3 phases, wye the same connection rule as a load
kvar nomQ (kVAr), the total over the phases; default 1200; more than one step raises kvar=[x] from get_shunt_reactive_power(sections='maximum', voltage='nominal'), in kVAr; maximumSections other than 1 raises
kv nomU (kV), and bPerSection (mS); line to neutral for a 1-phase wye bank, else line to line; default 12.47 nomU, the voltage bPerSection was derived on
Numsteps maximumSections; more than 1 raises (unequal steps would need a NonlinearShuntCompensator) not written; maximumSections above 1 raises
states sections = normalSections = the steps closed; default all closed states=[sections]; sections other than 0 or 1 raises; normalSections is not written
enabled normallyInService; default true get_in_service(which='normal'); unset: not written
bus2, cmatrix, cuf, normamps, emergamps raises when set not written
R, XL 0 is untranscribed, any other value raises not written
Harm, faultrate, pctperm, repair, basefreq, like untranscribed not written

Capacitor fail-fast rules

Rule Message
more than one step Capacitor c: 2 steps; only one section is mapped
bus2, cmatrix, cuf, nonzero R or XL, normamps, emergamps Capacitor c: R not mapped yet (no deck in the sweep sets them)
export: maximumSections other than 1 maximumSections 2; one section is mapped, as on import
export: sections other than 0 or 1 sections 2; a one-section bank has 0 or 1

Capacitor round trip

What Why
normalSections is lost DSS has no normal state for a capacitor; states carries sections
R=0 and the reliability settings come back at the engine's defaults untranscribed

Capacitor excerpt

From tests/atoms/capacitor/caps.cimtbl:

# derived: bPerSection = nomQ / nomU^2 (b_per_section); sections = normalSections = the steps states closes
Table LinearShuntCompensator: mRID, name, node, phases, phaseConnection, grounded, nomQ (kVAr), nomU (kV), bPerSection (mS), maximumSections, normalSections, sections, normallyInService, BaseVoltage, EquipmentContainer=fdr_atom
    # defaulted: conn=wye, Numsteps=1, enabled=true
    cap_c1,   c1,   b2, C, Y, true,  100.0, 2.4,  17.36111111111111, 1, 1, 1, true, bv_4p16kv

CapControl

One RegulatingControl per CapControl, mRID cc_ + the name, lowercased. The control is in capcontrol.cimtbl, and an update of the LinearShuntCompensator it regulates gives that bank its RegulatingControl, aVRDelay (s) and controlEnabled. So the capacitor mapper knows nothing of controls, and a control on its own capacitor makes no reference cycle.

The control's Terminal is the monitored element's: ln_<line>_T<n> for a line, sw_<switch>_T<n> for a switch line, cap_<capacitor>_T<n> for a capacitor. An element of another class raises.

ON and OFF. CIM has a target and a deadband in primary units, and DSS has ON and OFF settings on the relay's side. The importer writes targetValue = (ON + OFF) / 2 and targetDeadband = abs(OFF - ON), after scaling by PTratio (voltage) or CTratio (current). A kvar control's values stay in kvar, and the row says so with targetValueUnitMultiplier=k. The exporter inverts it and divides by the same ratio.

DSS type RegulatingControl.mode ON is targetValue and targetDeadband are in
voltage voltage below OFF V: ON and OFF x PTratio
current currentFlow above OFF A: ON and OFF x CTratio
kvar reactivePower above OFF kvar, with targetValueUnitMultiplier=k
time timeScheduled below OFF hours from midnight
pf, follow raises

The type is read by a unique prefix, as the engine reads it (volt is voltage); the default is current. A control with ON on the wrong side of OFF for its type raises, so the exporter can rebuild the pair from the mode.

CapControl properties

Property Import Export
name RegulatingControl.name; mRID cc_ + name, lowercased the CIM name or mRID (name_source)
element, terminal RegulatingControl.Terminal; terminal defaults to 1; a Line, switch or Capacitor that no New defines raises Line.<line or switch> or Capacitor.<shunt> of the monitored Terminal's equipment, and its sequenceNumber; other equipment raises
capacitor the update row names cap_<capacitor>; one that no New defines raises, and so do two controls on one capacitor the one LinearShuntCompensator the control regulates; anything else regulated raises
type RegulatingControl.mode (table above); default current voltage, currentFlow, reactivePower, timeScheduled give voltage, current, kvar, time; another mode raises
PTratio, CTratio ptRatio, ctRatio; default 60 written when set; a voltage control needs ptRatio and a current control needs ctRatio, else it raises
ONsetting, OFFsetting targetValue, targetDeadband (derived); defaults 300 and 200 ON and OFF = target -+ deadband / 2 (on_off_from_band), then divided by the ratio; an unset targetDeadband raises
Delay LinearShuntCompensator.aVRDelay (s) on the update row; default 15 the shunt's aVRDelay; unset: not written
PTPhase monitoredPhase: the phase of the monitored terminal's conductor PTPhase (default 1); a number past the conductors raises, and AVG, MAX and MIN raise ValueError in the mapper the 1-based place of monitoredPhase among the monitored equipment's phase conductors
enabled RegulatingControl.enabled, and controlEnabled on the update row; default true the control's enabled; the shunt's controlEnabled must agree
VoltOverride, Vmax, Vmin, DelayOFF, DeadTime untranscribed: no CIM home not written, so the engine's defaults
CTPhase, VBus, UserModel, UserData, ControlSignal raises when set not written
EventLog, pctMinkvar, Reset, basefreq, like untranscribed not written

CapControl fail-fast rules

Rule Message
type=pf or follow CapControl cc: type=pf is not mapped
ON on the wrong side of OFF CapControl cc: ON -300.0 is not above OFF 150.0 for a reactivePower control
export: another mode mode ...; a CapControl is voltage, current, kvar or time
export: targetDeadband unset targetDeadband is unset; a CapControl needs ON and OFF
export: an allowed range or a reverse setting [...] have no CapControl slot
export: a control that does not regulate exactly one capacitor regulates [...]; a CapControl has one LinearShuntCompensator

A RegulatingControl that regulates a SynchronousMachine is the machine's own and is written by its Generator (see DER and machines). A TapChangerControl is a RegControl, on the transformers page.

CapControl round trip

What Why
VoltOverride, Vmax, Vmin, DelayOFF, DeadTime come back at the defaults untranscribed. A kvar control that used VoltOverride acts differently when the engine solves it
type=volt comes back voltage the type is written out in full

CapControl excerpt

From tests/atoms/capacitor/caps_capcontrol.cimtbl. A kvar control on a switch line (ON 150, OFF -225 kvar), then the update of its capacitor:

Table RegulatingControl: mRID, name, mode, discrete=true, enabled, monitoredPhase, ptRatio, ctRatio, targetValue, targetDeadband, targetValueUnitMultiplier, Terminal
    # derived from ON=150.0, OFF=-225.0
    # defaulted: PTPhase=1, enabled=true
    # untranscribed: VoltOverride=true, Vmax=7740.0, Vmin=7110.0, DelayOFF=90.0
    cc_kvar, kvar, reactivePower, true, A, 1.0,  1.0,  -37.5,  375.0, k, sw_capsw_T1

# the compensator's control, delay (Delay) and controlEnabled
Update Table LinearShuntCompensator: mRID, RegulatingControl, aVRDelay (s), controlEnabled
    cap_c3,  cc_kvar, 100.0, true

The same atom round trips. c1 is a 1-phase bank that a voltage control on line l2 switches:

for line in round_trip("capacitor/caps.dss", schema.Capacitor, schema.Capcontrol):
    if " Capacitor.c1 " in line or " Capcontrol.volt " in line:
        print(line)
new Capacitor.c1 phases=1 bus1=b2.3 kvar=[100] kv=2.4 conn=wye states=[1] enabled=Yes
new Capcontrol.volt element=Line.l2 terminal=2 capacitor=c1 type=voltage PTratio=20 CTratio=60 on=115 off=125 Delay=15 PTPhase=1 enabled=Yes

LoadShape

A LoadShape that a Load names as yearly is a curve of multipliers on that load's kW and kvar. It maps to a ConformLoadGroup lg_<name> with one ConformLoadSchedule ls_<name>, and every load that names it is a ConformLoad of the group. The points are not in the .cimtbl: they go to the RegularTimePoint table of a Parquet sidecar, one row per sample, as the core site's time series guide describes. Pass the dict that receives them to the converters:

Direction How the points travel
import DssImporter(name, time_points={}) (or dss_to_cim(..., time_points=)) fills the dict. Without it the points are dropped with one warning
export DssExporter(time_points) (or cim_to_dss(..., time_points=)) reads the dict. Without it the loads are written static

A shape that a PVSystem, Storage or Generator names as yearly is not a load group. It is that device's own EnergyConnectionSchedule, described on DER and machines. A shape that nothing names is not mapped, and the master's comment counts it (not mapped: Loadshape 1).

Time. DSS has no date. Sample k (from 1) is in force from k x interval, so startTime is 2020-01-01T00:00Z plus one interval, and sequenceNumber counts from 0. The timeStep keeps the unit of the interval slot the deck assigned last, with one ConformLoadSchedule table per unit (h, min, s). The engine wraps a shape around, and CIM has no repeat, so the wrap is lost.

No npts. The engine reads none of mult without npts (a bare mult=1), so the load stays constant. Such a shape becomes a ConformLoadGroup with no schedule, its name kept.

LoadShape properties

Property Import Export
name ConformLoadGroup.name and ConformLoadSchedule.name; mRIDs lg_ and ls_ + name, lowercased a LoadShape named after the group (the Loadshape namespace)
npts structural: unset means no schedule; otherwise it must equal the number of mult values the number of points
mult RegularTimePoint.value1 in the sidecar, value1Unit none mult = value1 of each point, in sequence order
qmult RegularTimePoint.value2, value2Unit none; unset: Q follows mult, as in the engine qmult = value2; not written when value2 is unset
interval, minterval, sinterval ConformLoadSchedule.timeStep in h, min or s, from the slot assigned last; none is 1 h; 0 or less (0 is an hour array) raises always sinterval = timeStep in seconds; a timeStep that is not positive raises
action normalize divides mult and qmult each by its largest magnitude, as the engine does; an array assigned after it raises; DblSave and SngSave are untranscribed; any other raises not written
UseActual raises when yes: whether a load takes the shape's peak as its kW depends on command order a NonConformLoad is written static
hour, csvfile, sngfile, dblfile, PQCSVFile, Pmult, Pbase, Qbase raises when set not written
mean, stddev, Pmax, Qmax, MemoryMapping, Mode, Interpolation, like untranscribed not written

On export, a schedule whose values have a unit other than none raises, because a conform schedule holds multipliers. Owners whose name, interval and multipliers agree share one LoadShape; another with that name and other points takes a suffix (sun, sun_2).

A ConformLoad is written static, with one warning that lists its group, when the group has no schedule, the schedule has no points, the group holds days by season and day type (a GridLAB-D schedule's, which DSS has no calendar for), or the load is a NonConformLoad.

LoadShape fail-fast rules

Rule Message
UseActual=yes LoadShape s: UseActual=Yes; a Load naming it takes the shape's peak as its kW or keeps its own by command order, which the record does not keep
npts is not the number of mult values LoadShape s: npts=3 but mult has 2 values
an interval of 0 LoadShape s: interval=0.0; an hour array (interval 0) is not mapped
qmult of another length, no mult, a file or hour array, an unknown action LoadShape s: ... naming the property

LoadShape round trip

What Why
interval= and minterval= come back as sinterval= one written form; the interval is equal
a shape that no load names, and a load's daily and duty not imported
a bare mult=1 shape is not written, and its loads have no yearly the engine reads no points from it, so the loads are constant either way
the wrap-around, and a GridLAB-D player's date CIM has no repeat, DSS has no date

LoadShape excerpt

From tests/atoms/loadshape/loadshapes.loadshape.cimtbl:

Table ConformLoadGroup: mRID, name
    lg_com,  com
    # npts unset: the engine reads none of mult (S8), so no schedule
    lg_flat, flat
    lg_ind,  ind
    lg_res,  res

Table ConformLoadSchedule: mRID, name, startTime, timeStep (h), value1Unit, value2Unit, ConformLoadGroup
    ls_res, res, 2020-01-01T01:00:00+00:00, 1.0, none, none, lg_res

Import the atom, look at the sidecar, and export the shape and one of the loads that names it:

path = ATOMS / "loadshape/loadshapes.dss"
time_points = {}
DssImporter(path.stem, time_points=time_points).to_cim(DssReader(path).read_all())
print(sorted(time_points))
rows = time_points["RegularTimePoint"].to_pylist()
print(len(rows), [row["value1"] for row in rows[:4]])

for line in round_trip("loadshape/loadshapes.dss", schema.Loadshape, schema.Load):
    if " Loadshape.res " in line or " Load.r1 " in line:
        print(line)
['RegularTimePoint']
11 [0.25, 0.5, 1.0, 0.75]
new Loadshape.res npts=4 mult=[0.5 0.75 1 0.8] qmult=[0.4 0.6 0.9 0.7] sinterval=3600
new Load.r1 phases=1 bus1=b1.1 kV=2.40177711982884 kW=100 model=1 yearly=res conn=wye kvar=40 NumCust=1 enabled=Yes

The 11 points are res (4), com (4) and ind (3); the first four are com after action=normalize (2 4 8 6 over 8). The export also logs a warning that the group flat, a shape with no npts, is written static.