Transformers and regulators¶
XfmrCode, Transformer and RegControl: how each becomes CIM templates, power transformers, voltage regulators and tap
changers, and how they come back. How to read the tables is on the reference landing page.
| DSS | CIM (cim18v17) | Import (shape) | Export |
|---|---|---|---|
XfmrCode |
TransformerTankConfiguration and its ends, lugs, windings and mesh |
xfmrcode.cimtbl (transformer_template, transformer_template_1ph) |
XfmrCode, one per configuration a unit uses |
Transformer, 3 phases |
PowerTransformer, PowerTransformerEnd per bus, TransformerMeshImpedance |
transformer.cimtbl (transformer_by_ends) |
Transformer |
Transformer, 1 phase |
PowerTransformer, TransformerTank, TransformerPhaseEnd, TransformerWinding, mesh |
transformer.cimtbl (transformer_by_phase_ends) |
Transformer |
Transformer by XfmrCode |
PowerTransformer with a TransformerTank on the template |
transformer.cimtbl (transformer_by_template) |
Transformer with XfmrCode= |
Transformer a RegControl names, equal winding kV |
VoltageRegulator, AutoTransformerEnd, TransformerMeshImpedance |
transformer.cimtbl (voltage_regulator) |
Transformer, inline |
Transformer a RegControl names, step-down (an LTC) |
PowerTransformer as above, with a tap changer on the controlled end |
transformer.cimtbl |
Transformer |
RegControl |
TapChangerControl and RatioTapChanger |
regcontrol.cimtbl |
RegControl |
(CIM only) AutoTransformer |
AutoTransformer |
not produced | a Transformer, inline |
The shapes are on the core site's shapes page, and the
getters the exporter reads through (get_transformer_model, get_tap_changer_control) are on its
transformers reference.
The rating rule. A winding's baseU is the DSS kV (the coil voltage), ratedU is phase to phase, and baseS is
winding 1's kVA on every coil, because DSS puts every x on winding 1's kVA. A split-phase half is rated kVA / 2.
The mesh x is in percent on the From winding's baseU and baseS. A 3-phase transformer is by balanced ends: ratedU
is the DSS kV, ratedS the kVA, r is percent on the end's own rating, and x is on the mesh between ends.
XfmrCode¶
A code is a template its transformers share by name, built from the instances that use it because ratedU (phase to
phase) is not fixed by the coil voltage alone: 7.2 kV is 7200/12470Y on a 3-phase system. Every unregulated instance must
give the same template, else it raises. A code that no unregulated Transformer uses is not written; its regulators
take its values directly.
| Code | Template |
|---|---|
| 3 phases | a TransformerTankEnd per winding (connectionKind, rground, xground) and a TransformerWinding each; instance end n is template end n |
1 phase, center tap (3 windings, windings 2 and 3 a split-phase secondary on bus.1.0 and bus.0.2) |
TransformerLugs H1 H2 X1 X3 X2 and windings H1 to H2, X1 to X2 (s1 to N), X2 to X3 (N to s2) |
| 1 phase, any other | two lugs per winding, H1 H2, X1 X2, Y1 Y2, numbered in each coil's node order (its direction) |
| property | import | export |
|---|---|---|
name |
copied to TransformerTankConfiguration.name; mRID = xc_ + name, lowercased |
written: Names, the XfmrCode namespace |
phases |
structural: 3: TankEnd template; 1: lug template (a center tap's H1 H2 X1 X3 X2, else two lugs per winding) | written: as the Transformer's (windings.py), read through the first unit; every unit must give the same |
windings |
structural: one TransformerWinding each; 2 or 3 | written: as the Transformer's (windings.py), read through the first unit; every unit must give the same |
wdg |
structural: the winding Rneut/Xneut belong to (the reader's tag); none = the last | written: as the Transformer's (windings.py), read through the first unit; every unit must give the same |
conn |
structural: the active-winding form; the reader folds wdg= blocks and bare values into the arrays | not written: the active-winding form; the arrays carry every winding |
kV |
structural: the active-winding form; the reader folds wdg= blocks and bare values into the arrays | not written: the active-winding form; the arrays carry every winding |
kVA |
structural: the active-winding form; the reader folds wdg= blocks and bare values into the arrays | not written: the active-winding form; the arrays carry every winding |
tap |
structural: the active-winding form; the reader folds wdg= blocks and bare values into the arrays | not written: the active-winding form; the arrays carry every winding |
pct_R |
structural: the active-winding form; the reader folds wdg= blocks and bare values into the arrays | not written: the active-winding form; the arrays carry every winding |
Rneut |
structural: TankEnd rground (ohm) of its winding when >= 0; on a 1-phase code raises | written: as the Transformer's (windings.py), read through the first unit; every unit must give the same |
Xneut |
structural: TankEnd xground (ohm) of its winding, with Rneut >= 0 | written: as the Transformer's (windings.py), read through the first unit; every unit must give the same |
conns |
structural: TankEnd connectionKind (D, Y; grounding is the instance's); a center tap's secondary halves are I; default wye | written: as the Transformer's (windings.py), read through the first unit; every unit must give the same |
kVs |
structural: winding baseU (the coil); ratedU phase-to-phase from the instances' common bus system (x sqrt 3 on a 3-phase system, x 2 for a split-phase half), and instances that disagree raise | written: as the Transformer's (windings.py), read through the first unit; every unit must give the same |
kVAs |
structural: winding ratedS (a split-phase half: kVA / 2); baseS = winding 1's kVA on every coil (per phase on a 3-phase code) | written: as the Transformer's (windings.py), read through the first unit; every unit must give the same |
taps |
structural: a tap other than 1 raises (a fixed tap is not mapped yet) | not written: a tap is the instance's |
Xhl |
structural: mesh 1-2 x (percent on the From winding's baseU and baseS); default 7 | written: as the Transformer's (windings.py), read through the first unit; every unit must give the same |
Xht |
structural: mesh 1-3 x; default 35 | written: as the Transformer's (windings.py), read through the first unit; every unit must give the same |
Xlt |
structural: mesh 2-3 x; default 30 | written: as the Transformer's (windings.py), read through the first unit; every unit must give the same |
X12 |
structural: alias of Xhl | not written: untranscribed on import; not in CIM |
X13 |
structural: alias of Xht | not written: untranscribed on import; not in CIM |
X23 |
structural: alias of Xlt | not written: untranscribed on import; not in CIM |
Xscarray |
untranscribed: for more than 3 windings, which raise | not written: more than 3 windings raise |
pct_Rs |
structural: winding r (percent on its own baseS); default 0.2 | written by rule: as the Transformer's (windings.py), read through the first unit; every unit must give the same; unset r -> 0 |
pct_loadloss |
derived: when pct_Rs is unset, r = loadloss / 2 on windings 1 and 2; set with pct_Rs, the two must agree | not written: %Rs carries the winding r |
pct_noloadloss |
derived: TransformerTankConfiguration.noLoadLoss (kW) = % x winding 1 kVA | written: as the Transformer's (windings.py), read through the first unit; every unit must give the same |
pct_imag |
copied to TransformerTankConfiguration.percentMagnetizingCurrent (percent) |
written: as the Transformer's (windings.py), read through the first unit; every unit must give the same |
MaxTap |
untranscribed: tap changer range; a regulated instance takes it; else untranscribed | not written: a tap is the instance's |
MinTap |
untranscribed: tap changer range; a regulated instance takes it; else untranscribed | not written: a tap is the instance's |
NumTaps |
untranscribed: tap changer range; a regulated instance takes it; else untranscribed | not written: a tap is the instance's |
RdcOhms |
copied to TransformerWinding.rDC (ohm), per template winding, only when set |
written: each template winding's rDC (ohm), one wdg=n RdcOhms=v block per winding, last on the line |
Seasons |
structural: the number of Ratings; one by default, and a count other than the Ratings' raises |
written by rule: the number of the template's season ratings; none -> not written |
Ratings |
copied to ApparentPowerLimit.normalValue (kVA): one per season n, of type olt_season<n>, in the template's own OperationalLimitSet xc_<name>_ratings, which the template names |
written by rule: the template's ApparentPowerLimits of type olt_season |
like |
untranscribed: the reader resolves like= before mapping | not written: the writer never writes like= |
ppm_antifloat, thermal, n, m, flrise, hsrise, normhkVA, emerghkVA |
untranscribed (listed in the table comment) | not written |
Fail fast. More than 3 windings; phases other than 1 or 3; Rneut on a 1-phase code; a fixed taps other than 1; two
instances that give the code different templates (for example on different bus systems); a center tap whose secondary is not on
bus.1.0 and bus.0.2; kVAs that differ where a base is shared; RdcOhms on some windings only; Seasons without
Ratings, or a Ratings count other than Seasons.
Seasonal ratings. A code's Ratings are its template's own limits: an OperationalLimitSet written alone, with one
ApparentPowerLimit per season, and an Update of the TransformerTankConfiguration that names it
(EquipmentConfiguration.OperationalLimitSet, a GridAPPS-D extension of the profile). The instances do not inherit them.
The season types olt_season1, olt_season2, ... are declared once in the master. Excerpt from
cimhub_opendss/tests/atoms/xfmrcode/rated.cimtbl (code sub with RdcOhms on each winding and Seasons=2
Ratings=[22000 25000]):
# RdcOhms: the winding's dc resistance, copied
Update Table TransformerWinding: mRID, rDC (ohm)
xc_sub_wdg_1, 2.8103125
xc_sub_wdg_2, 0.011014647
# the seasonal ratings: Ratings, one ApparentPowerLimit per season
Table OperationalLimitSet: mRID
xc_sub_ratings
Table ApparentPowerLimit: mRID, normalValue (kVA), OperationalLimitType, OperationalLimitSet
xc_sub_ratings_1, 22000.0, olt_season1, xc_sub_ratings
xc_sub_ratings_2, 25000.0, olt_season2, xc_sub_ratings
Update Table TransformerTankConfiguration: mRID, OperationalLimitSet
xc_sub, xc_sub_ratings
Expected differences. A regulator by XfmrCode comes back inline: CIM has no AutoTransformer template. A configuration
no unit uses has no XfmrCode on export (logged), because a template alone does not say its phases. An instance with a tap changer gets
MaxTap, MinTap and NumTaps of its own, since the tap range is the instance's, not the code's.
Excerpt from cimhub_opendss/tests/atoms/xfmrcode/codes.cimtbl (the center-tap code ct25 and the 3-phase code sub):
Table TransformerTankConfiguration: mRID, name, percentMagnetizingCurrent (percent), noLoadLoss (kW)
# defaulted: conns=wye
# built from 2 instances (t1, ...)
xc_ct25, ct25, 0.5, 0.05
# built from 1 instance (sub, ...)
xc_sub, sub, 0.4, 20.0
Table TransformerTankEnd: mRID, TankConfiguration, endNumber, connectionKind, rground (ohm), xground (ohm)
xc_sub_end_1, xc_sub, 1, D, ,
xc_sub_end_2, xc_sub, 2, Y, ,
Transformer¶
An instance becomes one PowerTransformer with one PowerTransformerEnd per distinct bus, and the end's Terminal carries
its phases (ABCN, AN, AB, s1s2N). A 1-phase transformer adds a TransformerTank, a TransformerPhaseEnd per phase of
each terminal and a TransformerWinding per DSS winding, between the phase ends of its two conductors.
Defaults. Each default is listed in the row comment: conns wye, %Rs 0.2 (or %LoadLoss split over windings 1 and 2),
XHL 7, XHT 35, XLT 30, phases 3. %noloadloss is end 1's g (3 phases) or the tank's noLoadLoss
(= percent x winding 1's kVA); %imag is end 1's b or the tank's percentMagnetizingCurrent.
Regulators. A Transformer named by a RegControl whose windings have equal kV is a VoltageRegulator: two
AutoTransformerEnds with the nameplate (baseU, ratedS, a PhaseCode: AN, AB, or ABCN for a 3-phase wye) and the
engine's stand-in mesh impedance, r = %R1 + %R2 and x = XHL. A regulator has no home for %imag or %noloadloss,
which the row comment lists. A regulator takes its code's values when it names an XfmrCode. A step-down regulated
transformer (an LTC) stays a PowerTransformer.
DC resistance and seasonal ratings. RdcOhms is per winding; DSS has no array form, so the reader puts each value
at the active wdg='s place. The values are copied verbatim to the 1-phase transformer's TransformerWinding.rDC
(ohm), as an Update of the windings. Ratings (kVA) become one ApparentPowerLimit xf_<name>_ratings_<n> per
season n, of type olt_season<n>, in the OperationalLimitSet xf_<name>_ratings on the PowerTransformer (a
regulator's on its VoltageRegulator). The master declares the season types, as many as the most seasons any
Transformer or XfmrCode rates. An instance by XfmrCode gets only its own ratings; the code's stay on the template
(a regulator takes its code's, as it takes every other value).
normhkVA and emerghkVA stay untranscribed. Excerpt from cimhub_opendss/tests/atoms/transformer/rated.cimtbl (the
EPRI J1 service with RdcOhms on each winding and Seasons=2 Ratings=[44 52]):
# RdcOhms: the winding's dc resistance, copied
Update Table TransformerWinding: mRID, rDC (ohm)
xf_b13552-1a_wdg_1, 3.9773268
xf_b13552-1a_wdg_2, 0.004419252
# the seasonal ratings: Ratings, one ApparentPowerLimit per season
Table OperationalLimitSet: mRID, Equipment
xf_b13552-1a_ratings, xf_b13552-1a
Table ApparentPowerLimit: mRID, normalValue (kVA), OperationalLimitType, OperationalLimitSet
xf_b13552-1a_ratings_1, 44.0, olt_season1, xf_b13552-1a_ratings
xf_b13552-1a_ratings_2, 52.0, olt_season2, xf_b13552-1a_ratings
| property | import | export |
|---|---|---|
name |
copied to PowerTransformer.name; mRID = xf_ + name, lowercased |
written: Names; a one-unit transformer by itself, each tank of several by the tank |
phases |
structural: 1 = by phase ends, 3 = by balanced ends; default 3 | written: 3 when every winding has A, B, C, else 1 (a coil); inline units only; a unit on a TankConfiguration takes it from its XfmrCode |
windings |
structural: 2 or 3; must match the buses | written: the model's windings, 2 or 3; inline units only; a unit on a TankConfiguration takes it from its XfmrCode |
wdg |
structural: the winding Rneut/Xneut belong to (the reader's tag); none = the last | written: the one winding grounded through rground/xground |
bus |
structural: the active-winding form; the reader folds wdg= blocks into the arrays, and a bare value raises | not written: the active-winding form; the arrays carry every winding |
conn |
structural: the active-winding form; the reader folds wdg= blocks into the arrays, and a bare value raises | not written: the active-winding form; the arrays carry every winding |
kV |
structural: the active-winding form; the reader folds wdg= blocks into the arrays, and a bare value raises | not written: the active-winding form; the arrays carry every winding |
kVA |
structural: the active-winding form; the reader folds wdg= blocks into the arrays, and a bare value raises | not written: the active-winding form; the arrays carry every winding |
tap |
structural: the active-winding form; the reader folds wdg= blocks into the arrays, and a bare value raises | not written: the active-winding form; the arrays carry every winding |
pct_R |
structural: the active-winding form; the reader folds wdg= blocks into the arrays, and a bare value raises | not written: the active-winding form; the arrays carry every winding |
Rneut |
structural: rground (ohm) of its winding's end when >= 0; negative = no impedance; >= 0 on a 1-phase transformer raises | written: rground (ohm) of winding wdg; its neutral on .4 |
Xneut |
structural: xground (ohm) of its winding's end, with Rneut >= 0 | written: xground (ohm) of winding wdg |
buses |
structural: end node and terminal phases; one end per distinct bus | written: bus_ref of each winding's phases: a coil's N on .0; a 3-phase wye solid .1.2.3, else .1.2.3.4 |
conns |
structural: connectionKind, grounded, default nodes; default wye | written: connectionKind D -> delta, Y/Yn/I -> wye; AUTO: wye with a neutral; inline units only; a unit on a TankConfiguration takes it from its XfmrCode |
kVs |
structural: 3-phase: end ratedU; 1-phase: winding baseU, ratedU derived (x sqrt 3, x 2) | written: a coil's or an AutoTransformerEnd's baseU, a 3-phase winding's ratedU (kV); inline units only; a unit on a TankConfiguration takes it from its XfmrCode |
kVAs |
structural: end ratedS / winding ratedS (halves / 2); winding 1's kVA is every baseS | written: a coil's baseS (AUTO: ratedS), a 3-phase winding's ratedS (kVA); inline units only; a unit on a TankConfiguration takes it from its XfmrCode |
taps |
structural: the regulated winding's tap is RatioTapChanger.step (regcontrol.cimtbl); any other tap other than 1 raises | written: 1, and get_tap_ratio(actual) on the RatioTapChanger's winding |
XHL |
structural: mesh 1-2 x (percent on winding 1's kVA); default 7 | written: mesh (1,2) x, percent on winding 1's kVA; inline units only; a unit on a TankConfiguration takes it from its XfmrCode |
XHT |
structural: mesh 1-3 x; default 35 | written: mesh (1,3) x; inline units only; a unit on a TankConfiguration takes it from its XfmrCode |
XLT |
structural: mesh 2-3 x; default 30 | written: mesh (2,3) x; inline units only; a unit on a TankConfiguration takes it from its XfmrCode |
X12 |
structural: alias of XHL | not written: untranscribed on import; not in CIM |
X13 |
structural: alias of XHT | not written: untranscribed on import; not in CIM |
X23 |
structural: alias of XLT | not written: untranscribed on import; not in CIM |
Xscarray |
untranscribed: for more than 3 windings, which raise | not written: more than 3 windings raise |
pct_Rs |
structural: 3-phase: end r (percent); 1-phase: winding r (percent); default 0.2 | written by rule: winding r x kVA_n / kVA_1; unset -> 0; inline units only; a unit on a TankConfiguration takes it from its XfmrCode |
pct_loadloss |
derived: when pct_Rs is unset, r = loadloss / 2 on windings 1 and 2; set with pct_Rs, the two must agree | not written: %Rs carries the winding r |
pct_noloadloss |
derived: 3-phase: end 1 g (percent); 1-phase: tank noLoadLoss = % x kVA; a regulator has no home for it (row comment) | written: the core g (percent on winding 1's kVA); unset -> not written; inline units only; a unit on a TankConfiguration takes it from its XfmrCode |
pct_imag |
structural: 3-phase: end 1 b (percent); 1-phase: tank percentMagnetizingCurrent; a regulator has no home for it (row comment) | written: the core b (percent); unset -> not written; inline units only; a unit on a TankConfiguration takes it from its XfmrCode |
MaxTap |
structural: the RatioTapChanger range of a regulated transformer (regcontrol.cimtbl); else untranscribed; default 1.1 | written: get_tap_ratio(high) |
MinTap |
structural: the RatioTapChanger range of a regulated transformer (regcontrol.cimtbl); else untranscribed; default 0.9 | written: get_tap_ratio(low) |
NumTaps |
structural: the RatioTapChanger range of a regulated transformer (regcontrol.cimtbl); else untranscribed; default 32 | written: highStep - lowStep |
RdcOhms |
copied to TransformerWinding.rDC (ohm), per winding, only when set, on a 1-phase transformer's coils; on a 3-phase transformer by balanced ends (no TransformerWinding) or a regulator it raises |
written by rule: each winding's rDC (ohm), one wdg=n RdcOhms=v block per winding, last on the line; an end has none -> not written; inline units only; a unit on a TankConfiguration takes it from its XfmrCode |
Seasons |
structural: the number of Ratings; one by default, and a count other than the Ratings' raises |
written by rule: the number of season ratings; none -> not written |
Ratings |
copied to ApparentPowerLimit.normalValue (kVA): one per season n, of type olt_season<n>, in the OperationalLimitSet xf_<name>_ratings on the PowerTransformer (a regulator's on its VoltageRegulator) |
written by rule: the PowerTransformer's ApparentPowerLimits of type olt_season |
XfmrCode |
structural: a regulated instance takes the code's values (with_code); any other waits for the template and is counted on the master | written: the unit's TankConfiguration (BY_TANK_ENDS, BY_LUGS) |
enabled |
copied to PowerTransformer.normallyInService |
written: get_in_service(which='normal'); unset -> not written |
like |
untranscribed: the reader resolves like= before mapping | not written: the writer never writes like= |
thermal, n, m, flrise, hsrise, normhkVA, emerghkVA, normamps, emergamps, sub, subname, ppm_antifloat, bank, XRConst, LeadLag, Core, faultrate, pct_perm, repair, basefreq |
untranscribed (listed in the table comment) | not written |
Fail fast.
- A bare
bus,conn,kV,kVA,taporpct_Rwithoutwdg=or an array: the winding it belongs to is not recorded. windingsnot 2 or 3, or not one bus each;kVs,kVAs,connsorpct_Rswith the wrong count.Transformer t: taps=[1.0, 1.05] with no RegControl; a fixed tap is not mapped yet.pct_Rsandpct_loadlossthat disagree;XHLandX12(and the other aliases) that disagree.- A 3-phase end that is not on nodes 1.2.3; windings that share a bus without being a split-phase secondary.
- A mesh whose From winding does not carry winding 1's
kVA; a 1-phase transformer whose windings differ inkVA. - An
XfmrCodethat is undefined, or a slot set on both the instance and its code. - A transformer named by two
RegControls; a regulator with other than two windings on two buses, with unequalkVA, or with a neutral impedance. Rneutof 0 or more on a 1-phase transformer, andRneutorXneuton a second winding (the reader keeps one winding's neutral impedance).- A bus the topology walk did not reach.
RdcOhmson some windings and not others (the engine's default for the rest, 85 % of %R in ohms, is not transcribed);RdcOhms on a 3-phase transformer by balanced ends;RdcOhms on a regulator; an AutoTransformerEnd has no rDC.SeasonswithoutRatings(the engine pads its default rating with zeros), andRatingswith a count other thanSeasons(the engine keeps onlySeasonsof them, one by default). The engine also zeroes the Ratings whenSeasonscomes afterRatingson the line; the reader does not record that order, so this case is not caught.- On export,
rDCon some windings only, season ratings that are not seasons 1..n, ratings on a transformer of several units, a winding withconnectionKindorgroundedunset, a tap changer on a several-tank transformer, tap changers on two windings, aPhaseTapChanger, aneutralUthat is not the winding's kV, a meshroutside anAutoTransformer, a missing mesh pair, a neutral impedance on more than one winding, more than 3 windings, anAutoTransformerwhose two windings differ in kVA, and a delta winding with a neutral.
Export. One DSS Transformer per unit (a tank, or a transformer without tanks). A unit on a TransformerTankConfiguration
writes XfmrCode=, its buses, taps and enabled; every other form is inline. The forms are:
| CIM form | DSS | kVs, kVAs |
|---|---|---|
balanced ends (PowerTransformerEnd data) |
inline, phases=3 |
ratedU (line to line), ratedS; %imag, %noloadloss from the core's b, g |
| a tank's own windings | inline, phases=1 |
baseU, baseS (the coil) |
| a tank on a template | XfmrCode= |
on the code |
AutoTransformer, VoltageRegulator |
inline, phases 1 or 3 |
baseU (line to line on a 3-phase unit), ratedS; the mesh r is written %Rs=[r/2 r/2] |
connectionKind D is delta; Y, Yn and I are wye; an AutoTransformerEnd has no kind, so a coil with a neutral is wye
and one between two phases is delta. A 3-phase wye grounded solidly is .1.2.3, grounded through rground/xground is
.1.2.3.4 with wdg, Rneut and Xneut, and ungrounded is .1.2.3.4 with no Rneut. A coil's grounded neutral is
.0 and an ungrounded one is .4. A tap is taps=[1 <ratio>] with MaxTap, MinTap and NumTaps from the step range.
Seasons and Ratings come from the olt_season<n> limits in season order; RdcOhms from each winding's rDC, written
last as one wdg=n RdcOhms=v block per winding (... Seasons=2 Ratings=[44 52] wdg=1 RdcOhms=3.9773268 wdg=2
RdcOhms=0.004419252).
Expected differences.
%LoadLosscomes back as%Rs; defaultedXHL,%Rsandconnscome back explicit.- A 1-phase line-to-line coil written wye comes back delta: the two differ only in the engine's anti-float conductance.
ppm_antifloat,bank,normhkVA,emerghkVA,LeadLag,XRConst, the thermal and reliability slots are not in CIM; an instance'sppm=0comes back at the engine's default.- A regulator by
XfmrCodecomes back inline. AkVAon a center-tap half is the can's, as decks write it. tapscome back as a tap ratio on the one regulated winding and 1 on the rest.
Excerpt from cimhub_opendss/tests/atoms/transformer/xfm1.cimtbl (the 3-phase wdg= form from IEEE13_CDPSM):
Table PowerTransformerEnd: mRID, PowerTransformer, node, phases, endNumber, connectionKind, grounded, rground (ohm), xground (ohm), ratedU (kV), ratedS (kVA), r (percent), b (percent), g (percent), BaseVoltage
xf_xfm1_1, xf_xfm1, xf1, ABCN, 1, Yn, true, , , 4.16, 500.0, 0.55, , , bv_4p16kv
xf_xfm1_2, xf_xfm1, 634, ABCN, 2, Yn, true, , , 0.48, 500.0, 0.55, , , bv_480v
# x in percent on winding 1's kVA at the From end's voltage
Table TransformerMeshImpedance: mRID, FromTransformerEnd, ToTransformerEnd, x (percent)
xf_xfm1_mesh_12, xf_xfm1_1, xf_xfm1_2, 2.0
RegControl¶
A RegControl becomes a TapChangerControl and a RatioTapChanger on the controlled winding's end of the transformer it
names: an AutoTransformerEnd of a regulator, or a PowerTransformerEnd of an LTC. The control monitors that end's
Terminal. Settings DSS gives on the 120 V PT secondary become primary volts (x ptratio), and line-drop volts become
ohms (x ptratio / CTprim). step is a tap position, never a ratio: with increment = (MaxTap - MinTap) / NumTaps,
step = (tap - 1) / increment, lowStep = -(1 - MinTap) / increment and highStep = (MaxTap - 1) / increment, each of
which must be a whole number of steps. MaxTap, MinTap and NumTaps are the transformer's (defaults 1.1, 0.9 and
32, listed as defaulted). ctRatio is CTprim / 0.2, because DSS's CT secondary is 0.2 A.
| property | import | export |
|---|---|---|
name |
copied to TapChangerControl.name; RatioTapChanger.name; mRID = rc_ + name (control) and rc_ + name + _tap (tap changer), lowercased |
written: Names, the RegControl namespace |
transformer |
structural: the regulator or LTC; a Transformer no New defines, or one two RegControls name, raises | written: the DSS Transformer of the tap's unit (one unit) |
winding |
structural: RatioTapChanger.TransformerEnd = xf_<transformer><end>; TapChangerControl.Terminal = xf<transformer>_T<end>, where the end is the winding itself on a regulator and its bus's end otherwise; default 1 | written: the winding whose end holds the RatioTapChanger |
tapwinding |
raises when set (not mapped yet) (a tap winding other than the monitored one) | not written: the tap winding is the monitored one |
bus |
raises when set (not mapped yet) (remote sensing) | not written: the control must monitor its tap end's Terminal (remote sensing raises) |
PTphase |
structural: TapChangerControl.monitoredPhase = the phase of the winding's conductor PTphase (default 1); MAX/MIN raise | written: 1-based place of monitoredPhase among the winding's phase conductors; 1 on a 1-phase winding, whichever of its conductors CIM names |
vreg |
derived: targetValue (V) = vreg x ptratio (secondary_to_primary); default 120 | written: targetValue (V) / ptRatio (primary_to_secondary) |
band |
derived: targetDeadband (V) = band x ptratio (secondary_to_primary); default 3 | written: targetDeadband (V) / ptRatio (primary_to_secondary); unset -> not written, the engine's default |
ptratio |
copied to TapChangerControl.ptRatio; RatioTapChanger.ptRatio; default 60 |
written: ptRatio, the tap's and the control's agreed; unset raises |
CTprim |
copied to RatioTapChanger.ctRating (A); default 300; also ctRatio = CTprim / 0.2 (the DSS CT secondary, 0.2 A) and the LDC base |
written: ctRating (A); unset -> not written, and a line drop then raises |
R |
derived: lineDropR (ohm) = R x ptratio / CTprim (line_drop_ohms); default 0; lineDropCompensation = R or X nonzero | written: lineDropR (ohm) x CTprim / ptRatio (line_drop_volts); unset -> not written (0) |
X |
derived: lineDropX (ohm) = X x ptratio / CTprim (line_drop_ohms); default 0 | written: lineDropX (ohm) x CTprim / ptRatio (line_drop_volts); unset -> not written (0) |
delay |
copied to RatioTapChanger.initialDelay (s); default 15 |
written: initialDelay (s); unset -> not written |
tapdelay |
copied to RatioTapChanger.subsequentDelay (s); default 2 |
written: subsequentDelay (s); unset -> not written |
reversible |
copied to TapChangerControl.reversible; default false |
written: TapChangerControl.reversible |
revvreg |
derived: reverseTargetValue (V) = revvreg x ptratio (secondary_to_primary); default 120 | written: reverseTargetValue (V) / ptRatio (primary_to_secondary); unset -> not written, the engine's default |
revband |
derived: reverseTargetDeadband (V) = revband x ptratio (secondary_to_primary); default 3 | written: reverseTargetDeadband (V) / ptRatio (primary_to_secondary); unset -> not written, the engine's default |
revR |
derived: reverseLineDropR (ohm) = revR x ptratio / CTprim (line_drop_ohms); default 0 | written: reverseLineDropR (ohm) x CTprim / ptRatio (line_drop_volts); unset -> not written (0) |
revX |
derived: reverseLineDropX (ohm) = revX x ptratio / CTprim (line_drop_ohms); default 0 | written: reverseLineDropX (ohm) x CTprim / ptRatio (line_drop_volts); unset -> not written (0) |
revThreshold |
copied to TapChangerControl.reversingPowerThreshold (kW); default 100 |
written: reversingPowerThreshold (kW) |
revDelay |
copied to TapChangerControl.reversingDelay (s); default 60 |
written: reversingDelay (s) |
revNeutral |
copied to TapChangerControl.reverseToNeutral; default false |
written: reverseToNeutral |
vlimit |
raises when set (not mapped yet) (home TapChangerControl.maxLimitVoltage) | not written: maxLimitVoltage raises (untranscribed on import) |
TapNum |
raises when set (not mapped yet) (a tap position that overrides the transformer's tap) | not written: untranscribed or raising on import; not in CIM |
RemotePTRatio, LDC_Z, rev_Z, Cogen, idle, idleReverse, idleForward |
raises when set (not mapped yet) | not written: untranscribed or raising on import; not in CIM |
enabled |
copied to TapChangerControl.enabled; RatioTapChanger.controlEnabled; default true |
written: the control's enabled; the tap's controlEnabled must agree |
like |
untranscribed: the reader resolves like= before mapping | not written: the writer never writes like= |
maxtapchange, inversetime, debugtrace, EventLog, Reset, basefreq |
untranscribed (listed in the table comment) | not written |
Fail fast. tapwinding, bus (remote sensing), vlimit, TapNum, RemotePTRatio, LDC_Z, rev_Z, Cogen, idle,
idleReverse and idleForward set; a transformer that no New defines or that two RegControls name; winding outside
the transformer's windings; PTphase of MAX or MIN, or other than 1 on a 1-phase winding; a tap range that is not a
whole number of steps. On export, a control whose mode is not voltage, an unset ptRatio, a line drop with no ctRating
or with lineDropCompensation false, a monitored Terminal other than the tap end's, maxLimitVoltage or
minLimitVoltage, and several monitored phases.
Expected differences. The control's enabled and the tap changer's controlEnabled must agree on export. A 1-phase
winding's PTphase comes back 1, whichever of its conductors CIM names. Defaulted CTprim, delay, tapdelay, and the
reverse settings come back explicit. ctRatio is not read.
Excerpt from cimhub_opendss/tests/atoms/regcontrol/regulators.cimtbl (reg1: 700 A CT, R=3 X=9, tap 1.0625 on a 0.625 %
step, 10 steps up):
Table TapChangerControl: mRID, name, mode=voltage, discrete=true, enabled, monitoredPhase, ptRatio, targetValue, targetDeadband, lineDropCompensation, lineDropR (ohm), lineDropX (ohm), reversible, reverseTargetValue, reverseTargetDeadband, reverseLineDropR (ohm), reverseLineDropX (ohm), reversingPowerThreshold (kW), reversingDelay (s), reverseToNeutral, Terminal
rc_reg1, reg1, true, A, 60.0, 7320.0, 120.0, true, 0.2571428571428571, 0.7714285714285715, false, 7200.0, 180.0, 0.0, 0.0, 100.0, 60.0, false, xf_reg1_T2
Table RatioTapChanger: mRID, name, TransformerEnd, TapChangerControl, lowStep, highStep, neutralStep=0, step, stepVoltageIncrement (percent), neutralU (kV), ltcFlag=true, controlEnabled, ptRatio, ctRating, ctRatio, initialDelay (s), subsequentDelay (s)
rc_reg1_tap, reg1, xf_reg1_2, rc_reg1, -16, 16, 10, 0.625, 7.2, true, 60.0, 700.0, 3500.0, 15.0, 2.0
Run it¶
This imports regulators and an LTC with their controls, and exports them. It runs from the repository root.
from pathlib import Path
from cimhub_opendss import DssReader, cim_to_dss, dss_to_cim
deck = Path("cimhub_opendss/tests/atoms/regcontrol/regulators.dss")
network = dss_to_cim(DssReader(deck).read_all(), name="regulators", artifact_dir="/tmp/ref-transformers")
cim_to_dss(network, "/tmp/ref-transformers/back.dss", name_source="name")
for line in Path("/tmp/ref-transformers/back.dss").read_text().splitlines():
if line.lower().startswith(("new transformer.reg1", "new regcontrol.reg1")):
print(line)
new Transformer.reg1 phases=1 windings=2 buses=[sub.1.0 rg.1.0] conns=[wye wye] kVs=[7.2 7.2] kVAs=[1666 1666] taps=[1 1.0625] XHL=0.01 MaxTap=1.1 MinTap=0.9 NumTaps=32 %Rs=[0.005 0.005]
new Regcontrol.reg1 transformer=reg1 winding=2 vreg=122 band=2 ptratio=60 CTprim=700 R=3 X=9 delay=15 reversible=No revvreg=120 revband=3 revR=0 revX=0 tapdelay=2 PTphase=1 revThreshold=100 revDelay=60 revNeutral=No enabled=Yes
The deck's %LoadLoss=0.01 is now %Rs=[0.005 0.005], the tap is taps=[1 1.0625] with the range written out, and the
control's defaults (delay, revThreshold, ...) are explicit.