Transformers and regulators

XfmrCode, Transformer and RegControl: how each becomes CIM templates, power transformers, voltage regulators and tap changers, and how they come back. How to read the tables is on the reference landing page.

DSS CIM (cim18v17) Import (shape) Export
XfmrCode TransformerTankConfiguration and its ends, lugs, windings and mesh xfmrcode.cimtbl (transformer_template, transformer_template_1ph) XfmrCode, one per configuration a unit uses
Transformer, 3 phases PowerTransformer, PowerTransformerEnd per bus, TransformerMeshImpedance transformer.cimtbl (transformer_by_ends) Transformer
Transformer, 1 phase PowerTransformer, TransformerTank, TransformerPhaseEnd, TransformerWinding, mesh transformer.cimtbl (transformer_by_phase_ends) Transformer
Transformer by XfmrCode PowerTransformer with a TransformerTank on the template transformer.cimtbl (transformer_by_template) Transformer with XfmrCode=
Transformer a RegControl names, equal winding kV VoltageRegulator, AutoTransformerEnd, TransformerMeshImpedance transformer.cimtbl (voltage_regulator) Transformer, inline
Transformer a RegControl names, step-down (an LTC) PowerTransformer as above, with a tap changer on the controlled end transformer.cimtbl Transformer
RegControl TapChangerControl and RatioTapChanger regcontrol.cimtbl RegControl
(CIM only) AutoTransformer AutoTransformer not produced a Transformer, inline

The shapes are on the core site's shapes page, and the getters the exporter reads through (get_transformer_model, get_tap_changer_control) are on its transformers reference.

The rating rule. A winding's baseU is the DSS kV (the coil voltage), ratedU is phase to phase, and baseS is winding 1's kVA on every coil, because DSS puts every x on winding 1's kVA. A split-phase half is rated kVA / 2. The mesh x is in percent on the From winding's baseU and baseS. A 3-phase transformer is by balanced ends: ratedU is the DSS kV, ratedS the kVA, r is percent on the end's own rating, and x is on the mesh between ends.

XfmrCode

A code is a template its transformers share by name, built from the instances that use it because ratedU (phase to phase) is not fixed by the coil voltage alone: 7.2 kV is 7200/12470Y on a 3-phase system. Every unregulated instance must give the same template, else it raises. A code that no unregulated Transformer uses is not written; its regulators take its values directly.

Code Template
3 phases a TransformerTankEnd per winding (connectionKind, rground, xground) and a TransformerWinding each; instance end n is template end n
1 phase, center tap (3 windings, windings 2 and 3 a split-phase secondary on bus.1.0 and bus.0.2) TransformerLugs H1 H2 X1 X3 X2 and windings H1 to H2, X1 to X2 (s1 to N), X2 to X3 (N to s2)
1 phase, any other two lugs per winding, H1 H2, X1 X2, Y1 Y2, numbered in each coil's node order (its direction)
property import export
name copied to TransformerTankConfiguration.name; mRID = xc_ + name, lowercased written: Names, the XfmrCode namespace
phases structural: 3: TankEnd template; 1: lug template (a center tap's H1 H2 X1 X3 X2, else two lugs per winding) written: as the Transformer's (windings.py), read through the first unit; every unit must give the same
windings structural: one TransformerWinding each; 2 or 3 written: as the Transformer's (windings.py), read through the first unit; every unit must give the same
wdg structural: the winding Rneut/Xneut belong to (the reader's tag); none = the last written: as the Transformer's (windings.py), read through the first unit; every unit must give the same
conn structural: the active-winding form; the reader folds wdg= blocks and bare values into the arrays not written: the active-winding form; the arrays carry every winding
kV structural: the active-winding form; the reader folds wdg= blocks and bare values into the arrays not written: the active-winding form; the arrays carry every winding
kVA structural: the active-winding form; the reader folds wdg= blocks and bare values into the arrays not written: the active-winding form; the arrays carry every winding
tap structural: the active-winding form; the reader folds wdg= blocks and bare values into the arrays not written: the active-winding form; the arrays carry every winding
pct_R structural: the active-winding form; the reader folds wdg= blocks and bare values into the arrays not written: the active-winding form; the arrays carry every winding
Rneut structural: TankEnd rground (ohm) of its winding when >= 0; on a 1-phase code raises written: as the Transformer's (windings.py), read through the first unit; every unit must give the same
Xneut structural: TankEnd xground (ohm) of its winding, with Rneut >= 0 written: as the Transformer's (windings.py), read through the first unit; every unit must give the same
conns structural: TankEnd connectionKind (D, Y; grounding is the instance's); a center tap's secondary halves are I; default wye written: as the Transformer's (windings.py), read through the first unit; every unit must give the same
kVs structural: winding baseU (the coil); ratedU phase-to-phase from the instances' common bus system (x sqrt 3 on a 3-phase system, x 2 for a split-phase half), and instances that disagree raise written: as the Transformer's (windings.py), read through the first unit; every unit must give the same
kVAs structural: winding ratedS (a split-phase half: kVA / 2); baseS = winding 1's kVA on every coil (per phase on a 3-phase code) written: as the Transformer's (windings.py), read through the first unit; every unit must give the same
taps structural: a tap other than 1 raises (a fixed tap is not mapped yet) not written: a tap is the instance's
Xhl structural: mesh 1-2 x (percent on the From winding's baseU and baseS); default 7 written: as the Transformer's (windings.py), read through the first unit; every unit must give the same
Xht structural: mesh 1-3 x; default 35 written: as the Transformer's (windings.py), read through the first unit; every unit must give the same
Xlt structural: mesh 2-3 x; default 30 written: as the Transformer's (windings.py), read through the first unit; every unit must give the same
X12 structural: alias of Xhl not written: untranscribed on import; not in CIM
X13 structural: alias of Xht not written: untranscribed on import; not in CIM
X23 structural: alias of Xlt not written: untranscribed on import; not in CIM
Xscarray untranscribed: for more than 3 windings, which raise not written: more than 3 windings raise
pct_Rs structural: winding r (percent on its own baseS); default 0.2 written by rule: as the Transformer's (windings.py), read through the first unit; every unit must give the same; unset r -> 0
pct_loadloss derived: when pct_Rs is unset, r = loadloss / 2 on windings 1 and 2; set with pct_Rs, the two must agree not written: %Rs carries the winding r
pct_noloadloss derived: TransformerTankConfiguration.noLoadLoss (kW) = % x winding 1 kVA written: as the Transformer's (windings.py), read through the first unit; every unit must give the same
pct_imag copied to TransformerTankConfiguration.percentMagnetizingCurrent (percent) written: as the Transformer's (windings.py), read through the first unit; every unit must give the same
MaxTap untranscribed: tap changer range; a regulated instance takes it; else untranscribed not written: a tap is the instance's
MinTap untranscribed: tap changer range; a regulated instance takes it; else untranscribed not written: a tap is the instance's
NumTaps untranscribed: tap changer range; a regulated instance takes it; else untranscribed not written: a tap is the instance's
RdcOhms copied to TransformerWinding.rDC (ohm), per template winding, only when set written: each template winding's rDC (ohm), one wdg=n RdcOhms=v block per winding, last on the line
Seasons structural: the number of Ratings; one by default, and a count other than the Ratings' raises written by rule: the number of the template's season ratings; none -> not written
Ratings copied to ApparentPowerLimit.normalValue (kVA): one per season n, of type olt_season<n>, in the template's own OperationalLimitSet xc_<name>_ratings, which the template names written by rule: the template's ApparentPowerLimits of type olt_season (kVA), in season order; none -> not written
like untranscribed: the reader resolves like= before mapping not written: the writer never writes like=
ppm_antifloat, thermal, n, m, flrise, hsrise, normhkVA, emerghkVA untranscribed (listed in the table comment) not written

Fail fast. More than 3 windings; phases other than 1 or 3; Rneut on a 1-phase code; a fixed taps other than 1; two instances that give the code different templates (for example on different bus systems); a center tap whose secondary is not on bus.1.0 and bus.0.2; kVAs that differ where a base is shared; RdcOhms on some windings only; Seasons without Ratings, or a Ratings count other than Seasons.

Seasonal ratings. A code's Ratings are its template's own limits: an OperationalLimitSet written alone, with one ApparentPowerLimit per season, and an Update of the TransformerTankConfiguration that names it (EquipmentConfiguration.OperationalLimitSet, a GridAPPS-D extension of the profile). The instances do not inherit them. The season types olt_season1, olt_season2, ... are declared once in the master. Excerpt from cimhub_opendss/tests/atoms/xfmrcode/rated.cimtbl (code sub with RdcOhms on each winding and Seasons=2 Ratings=[22000 25000]):

# RdcOhms: the winding's dc resistance, copied
Update Table TransformerWinding: mRID, rDC (ohm)
    xc_sub_wdg_1, 2.8103125
    xc_sub_wdg_2, 0.011014647

# the seasonal ratings: Ratings, one ApparentPowerLimit per season
Table OperationalLimitSet: mRID
    xc_sub_ratings

Table ApparentPowerLimit: mRID, normalValue (kVA), OperationalLimitType, OperationalLimitSet
    xc_sub_ratings_1, 22000.0, olt_season1, xc_sub_ratings
    xc_sub_ratings_2, 25000.0, olt_season2, xc_sub_ratings

Update Table TransformerTankConfiguration: mRID, OperationalLimitSet
    xc_sub, xc_sub_ratings

Expected differences. A regulator by XfmrCode comes back inline: CIM has no AutoTransformer template. A configuration no unit uses has no XfmrCode on export (logged), because a template alone does not say its phases. An instance with a tap changer gets MaxTap, MinTap and NumTaps of its own, since the tap range is the instance's, not the code's.

Excerpt from cimhub_opendss/tests/atoms/xfmrcode/codes.cimtbl (the center-tap code ct25 and the 3-phase code sub):

Table TransformerTankConfiguration: mRID, name, percentMagnetizingCurrent (percent), noLoadLoss (kW)
    # defaulted: conns=wye
    # built from 2 instances (t1, ...)
    xc_ct25, ct25, 0.5, 0.05
    # built from 1 instance (sub, ...)
    xc_sub,  sub,  0.4, 20.0

Table TransformerTankEnd: mRID, TankConfiguration, endNumber, connectionKind, rground (ohm), xground (ohm)
    xc_sub_end_1, xc_sub, 1, D, ,
    xc_sub_end_2, xc_sub, 2, Y, ,

Transformer

An instance becomes one PowerTransformer with one PowerTransformerEnd per distinct bus, and the end's Terminal carries its phases (ABCN, AN, AB, s1s2N). A 1-phase transformer adds a TransformerTank, a TransformerPhaseEnd per phase of each terminal and a TransformerWinding per DSS winding, between the phase ends of its two conductors.

Defaults. Each default is listed in the row comment: conns wye, %Rs 0.2 (or %LoadLoss split over windings 1 and 2), XHL 7, XHT 35, XLT 30, phases 3. %noloadloss is end 1's g (3 phases) or the tank's noLoadLoss (= percent x winding 1's kVA); %imag is end 1's b or the tank's percentMagnetizingCurrent.

Regulators. A Transformer named by a RegControl whose windings have equal kV is a VoltageRegulator: two AutoTransformerEnds with the nameplate (baseU, ratedS, a PhaseCode: AN, AB, or ABCN for a 3-phase wye) and the engine's stand-in mesh impedance, r = %R1 + %R2 and x = XHL. A regulator has no home for %imag or %noloadloss, which the row comment lists. A regulator takes its code's values when it names an XfmrCode. A step-down regulated transformer (an LTC) stays a PowerTransformer.

DC resistance and seasonal ratings. RdcOhms is per winding; DSS has no array form, so the reader puts each value at the active wdg='s place. The values are copied verbatim to the 1-phase transformer's TransformerWinding.rDC (ohm), as an Update of the windings. Ratings (kVA) become one ApparentPowerLimit xf_<name>_ratings_<n> per season n, of type olt_season<n>, in the OperationalLimitSet xf_<name>_ratings on the PowerTransformer (a regulator's on its VoltageRegulator). The master declares the season types, as many as the most seasons any Transformer or XfmrCode rates. An instance by XfmrCode gets only its own ratings; the code's stay on the template (a regulator takes its code's, as it takes every other value). normhkVA and emerghkVA stay untranscribed. Excerpt from cimhub_opendss/tests/atoms/transformer/rated.cimtbl (the EPRI J1 service with RdcOhms on each winding and Seasons=2 Ratings=[44 52]):

# RdcOhms: the winding's dc resistance, copied
Update Table TransformerWinding: mRID, rDC (ohm)
    xf_b13552-1a_wdg_1, 3.9773268
    xf_b13552-1a_wdg_2, 0.004419252

# the seasonal ratings: Ratings, one ApparentPowerLimit per season
Table OperationalLimitSet: mRID, Equipment
    xf_b13552-1a_ratings, xf_b13552-1a

Table ApparentPowerLimit: mRID, normalValue (kVA), OperationalLimitType, OperationalLimitSet
    xf_b13552-1a_ratings_1, 44.0, olt_season1, xf_b13552-1a_ratings
    xf_b13552-1a_ratings_2, 52.0, olt_season2, xf_b13552-1a_ratings
property import export
name copied to PowerTransformer.name; mRID = xf_ + name, lowercased written: Names; a one-unit transformer by itself, each tank of several by the tank
phases structural: 1 = by phase ends, 3 = by balanced ends; default 3 written: 3 when every winding has A, B, C, else 1 (a coil); inline units only; a unit on a TankConfiguration takes it from its XfmrCode
windings structural: 2 or 3; must match the buses written: the model's windings, 2 or 3; inline units only; a unit on a TankConfiguration takes it from its XfmrCode
wdg structural: the winding Rneut/Xneut belong to (the reader's tag); none = the last written: the one winding grounded through rground/xground
bus structural: the active-winding form; the reader folds wdg= blocks into the arrays, and a bare value raises not written: the active-winding form; the arrays carry every winding
conn structural: the active-winding form; the reader folds wdg= blocks into the arrays, and a bare value raises not written: the active-winding form; the arrays carry every winding
kV structural: the active-winding form; the reader folds wdg= blocks into the arrays, and a bare value raises not written: the active-winding form; the arrays carry every winding
kVA structural: the active-winding form; the reader folds wdg= blocks into the arrays, and a bare value raises not written: the active-winding form; the arrays carry every winding
tap structural: the active-winding form; the reader folds wdg= blocks into the arrays, and a bare value raises not written: the active-winding form; the arrays carry every winding
pct_R structural: the active-winding form; the reader folds wdg= blocks into the arrays, and a bare value raises not written: the active-winding form; the arrays carry every winding
Rneut structural: rground (ohm) of its winding's end when >= 0; negative = no impedance; >= 0 on a 1-phase transformer raises written: rground (ohm) of winding wdg; its neutral on .4
Xneut structural: xground (ohm) of its winding's end, with Rneut >= 0 written: xground (ohm) of winding wdg
buses structural: end node and terminal phases; one end per distinct bus written: bus_ref of each winding's phases: a coil's N on .0; a 3-phase wye solid .1.2.3, else .1.2.3.4
conns structural: connectionKind, grounded, default nodes; default wye written: connectionKind D -> delta, Y/Yn/I -> wye; AUTO: wye with a neutral; inline units only; a unit on a TankConfiguration takes it from its XfmrCode
kVs structural: 3-phase: end ratedU; 1-phase: winding baseU, ratedU derived (x sqrt 3, x 2) written: a coil's or an AutoTransformerEnd's baseU, a 3-phase winding's ratedU (kV); inline units only; a unit on a TankConfiguration takes it from its XfmrCode
kVAs structural: end ratedS / winding ratedS (halves / 2); winding 1's kVA is every baseS written: a coil's baseS (AUTO: ratedS), a 3-phase winding's ratedS (kVA); inline units only; a unit on a TankConfiguration takes it from its XfmrCode
taps structural: the regulated winding's tap is RatioTapChanger.step (regcontrol.cimtbl); any other tap other than 1 raises written: 1, and get_tap_ratio(actual) on the RatioTapChanger's winding
XHL structural: mesh 1-2 x (percent on winding 1's kVA); default 7 written: mesh (1,2) x, percent on winding 1's kVA; inline units only; a unit on a TankConfiguration takes it from its XfmrCode
XHT structural: mesh 1-3 x; default 35 written: mesh (1,3) x; inline units only; a unit on a TankConfiguration takes it from its XfmrCode
XLT structural: mesh 2-3 x; default 30 written: mesh (2,3) x; inline units only; a unit on a TankConfiguration takes it from its XfmrCode
X12 structural: alias of XHL not written: untranscribed on import; not in CIM
X13 structural: alias of XHT not written: untranscribed on import; not in CIM
X23 structural: alias of XLT not written: untranscribed on import; not in CIM
Xscarray untranscribed: for more than 3 windings, which raise not written: more than 3 windings raise
pct_Rs structural: 3-phase: end r (percent); 1-phase: winding r (percent); default 0.2 written by rule: winding r x kVA_n / kVA_1; unset -> 0; inline units only; a unit on a TankConfiguration takes it from its XfmrCode
pct_loadloss derived: when pct_Rs is unset, r = loadloss / 2 on windings 1 and 2; set with pct_Rs, the two must agree not written: %Rs carries the winding r
pct_noloadloss derived: 3-phase: end 1 g (percent); 1-phase: tank noLoadLoss = % x kVA; a regulator has no home for it (row comment) written: the core g (percent on winding 1's kVA); unset -> not written; inline units only; a unit on a TankConfiguration takes it from its XfmrCode
pct_imag structural: 3-phase: end 1 b (percent); 1-phase: tank percentMagnetizingCurrent; a regulator has no home for it (row comment) written: the core b (percent); unset -> not written; inline units only; a unit on a TankConfiguration takes it from its XfmrCode
MaxTap structural: the RatioTapChanger range of a regulated transformer (regcontrol.cimtbl); else untranscribed; default 1.1 written: get_tap_ratio(high)
MinTap structural: the RatioTapChanger range of a regulated transformer (regcontrol.cimtbl); else untranscribed; default 0.9 written: get_tap_ratio(low)
NumTaps structural: the RatioTapChanger range of a regulated transformer (regcontrol.cimtbl); else untranscribed; default 32 written: highStep - lowStep
RdcOhms copied to TransformerWinding.rDC (ohm), per winding, only when set, on a 1-phase transformer's coils; on a 3-phase transformer by balanced ends (no TransformerWinding) or a regulator it raises written by rule: each winding's rDC (ohm), one wdg=n RdcOhms=v block per winding, last on the line; an end has none -> not written; inline units only; a unit on a TankConfiguration takes it from its XfmrCode
Seasons structural: the number of Ratings; one by default, and a count other than the Ratings' raises written by rule: the number of season ratings; none -> not written
Ratings copied to ApparentPowerLimit.normalValue (kVA): one per season n, of type olt_season<n>, in the OperationalLimitSet xf_<name>_ratings on the PowerTransformer (a regulator's on its VoltageRegulator) written by rule: the PowerTransformer's ApparentPowerLimits of type olt_season (kVA), in season order; other types are not written; none -> not written
XfmrCode structural: a regulated instance takes the code's values (with_code); any other waits for the template and is counted on the master written: the unit's TankConfiguration (BY_TANK_ENDS, BY_LUGS)
enabled copied to PowerTransformer.normallyInService written: get_in_service(which='normal'); unset -> not written
like untranscribed: the reader resolves like= before mapping not written: the writer never writes like=
thermal, n, m, flrise, hsrise, normhkVA, emerghkVA, normamps, emergamps, sub, subname, ppm_antifloat, bank, XRConst, LeadLag, Core, faultrate, pct_perm, repair, basefreq untranscribed (listed in the table comment) not written

Fail fast.

  • A bare bus, conn, kV, kVA, tap or pct_R without wdg= or an array: the winding it belongs to is not recorded.
  • windings not 2 or 3, or not one bus each; kVs, kVAs, conns or pct_Rs with the wrong count.
  • Transformer t: taps=[1.0, 1.05] with no RegControl; a fixed tap is not mapped yet.
  • pct_Rs and pct_loadloss that disagree; XHL and X12 (and the other aliases) that disagree.
  • A 3-phase end that is not on nodes 1.2.3; windings that share a bus without being a split-phase secondary.
  • A mesh whose From winding does not carry winding 1's kVA; a 1-phase transformer whose windings differ in kVA.
  • An XfmrCode that is undefined, or a slot set on both the instance and its code.
  • A transformer named by two RegControls; a regulator with other than two windings on two buses, with unequal kVA, or with a neutral impedance.
  • Rneut of 0 or more on a 1-phase transformer, and Rneut or Xneut on a second winding (the reader keeps one winding's neutral impedance).
  • A bus the topology walk did not reach.
  • RdcOhms on some windings and not others (the engine's default for the rest, 85 % of %R in ohms, is not transcribed); RdcOhms on a 3-phase transformer by balanced ends; RdcOhms on a regulator; an AutoTransformerEnd has no rDC.
  • Seasons without Ratings (the engine pads its default rating with zeros), and Ratings with a count other than Seasons (the engine keeps only Seasons of them, one by default). The engine also zeroes the Ratings when Seasons comes after Ratings on the line; the reader does not record that order, so this case is not caught.
  • On export, rDC on some windings only, season ratings that are not seasons 1..n, ratings on a transformer of several units, a winding with connectionKind or grounded unset, a tap changer on a several-tank transformer, tap changers on two windings, a PhaseTapChanger, a neutralU that is not the winding's kV, a mesh r outside an AutoTransformer, a missing mesh pair, a neutral impedance on more than one winding, more than 3 windings, an AutoTransformer whose two windings differ in kVA, and a delta winding with a neutral.

Export. One DSS Transformer per unit (a tank, or a transformer without tanks). A unit on a TransformerTankConfiguration writes XfmrCode=, its buses, taps and enabled; every other form is inline. The forms are:

CIM form DSS kVs, kVAs
balanced ends (PowerTransformerEnd data) inline, phases=3 ratedU (line to line), ratedS; %imag, %noloadloss from the core's b, g
a tank's own windings inline, phases=1 baseU, baseS (the coil)
a tank on a template XfmrCode= on the code
AutoTransformer, VoltageRegulator inline, phases 1 or 3 baseU (line to line on a 3-phase unit), ratedS; the mesh r is written %Rs=[r/2 r/2]

connectionKind D is delta; Y, Yn and I are wye; an AutoTransformerEnd has no kind, so a coil with a neutral is wye and one between two phases is delta. A 3-phase wye grounded solidly is .1.2.3, grounded through rground/xground is .1.2.3.4 with wdg, Rneut and Xneut, and ungrounded is .1.2.3.4 with no Rneut. A coil's grounded neutral is .0 and an ungrounded one is .4. A tap is taps=[1 <ratio>] with MaxTap, MinTap and NumTaps from the step range. Seasons and Ratings come from the olt_season<n> limits in season order; RdcOhms from each winding's rDC, written last as one wdg=n RdcOhms=v block per winding (... Seasons=2 Ratings=[44 52] wdg=1 RdcOhms=3.9773268 wdg=2 RdcOhms=0.004419252).

Expected differences.

  • %LoadLoss comes back as %Rs; defaulted XHL, %Rs and conns come back explicit.
  • A 1-phase line-to-line coil written wye comes back delta: the two differ only in the engine's anti-float conductance.
  • ppm_antifloat, bank, normhkVA, emerghkVA, LeadLag, XRConst, the thermal and reliability slots are not in CIM; an instance's ppm=0 comes back at the engine's default.
  • A regulator by XfmrCode comes back inline. A kVA on a center-tap half is the can's, as decks write it.
  • taps come back as a tap ratio on the one regulated winding and 1 on the rest.

Excerpt from cimhub_opendss/tests/atoms/transformer/xfm1.cimtbl (the 3-phase wdg= form from IEEE13_CDPSM):

Table PowerTransformerEnd: mRID, PowerTransformer, node, phases, endNumber, connectionKind, grounded, rground (ohm), xground (ohm), ratedU (kV), ratedS (kVA), r (percent), b (percent), g (percent), BaseVoltage
    xf_xfm1_1, xf_xfm1, xf1, ABCN, 1, Yn, true, , , 4.16, 500.0, 0.55, , , bv_4p16kv
    xf_xfm1_2, xf_xfm1, 634, ABCN, 2, Yn, true, , , 0.48, 500.0, 0.55, , , bv_480v

# x in percent on winding 1's kVA at the From end's voltage
Table TransformerMeshImpedance: mRID, FromTransformerEnd, ToTransformerEnd, x (percent)
    xf_xfm1_mesh_12, xf_xfm1_1, xf_xfm1_2, 2.0

RegControl

A RegControl becomes a TapChangerControl and a RatioTapChanger on the controlled winding's end of the transformer it names: an AutoTransformerEnd of a regulator, or a PowerTransformerEnd of an LTC. The control monitors that end's Terminal. Settings DSS gives on the 120 V PT secondary become primary volts (x ptratio), and line-drop volts become ohms (x ptratio / CTprim). step is a tap position, never a ratio: with increment = (MaxTap - MinTap) / NumTaps, step = (tap - 1) / increment, lowStep = -(1 - MinTap) / increment and highStep = (MaxTap - 1) / increment, each of which must be a whole number of steps. MaxTap, MinTap and NumTaps are the transformer's (defaults 1.1, 0.9 and 32, listed as defaulted). ctRatio is CTprim / 0.2, because DSS's CT secondary is 0.2 A.

property import export
name copied to TapChangerControl.name; RatioTapChanger.name; mRID = rc_ + name (control) and rc_ + name + _tap (tap changer), lowercased written: Names, the RegControl namespace
transformer structural: the regulator or LTC; a Transformer no New defines, or one two RegControls name, raises written: the DSS Transformer of the tap's unit (one unit)
winding structural: RatioTapChanger.TransformerEnd = xf_<transformer><end>; TapChangerControl.Terminal = xf<transformer>_T<end>, where the end is the winding itself on a regulator and its bus's end otherwise; default 1 written: the winding whose end holds the RatioTapChanger
tapwinding raises when set (not mapped yet) (a tap winding other than the monitored one) not written: the tap winding is the monitored one
bus raises when set (not mapped yet) (remote sensing) not written: the control must monitor its tap end's Terminal (remote sensing raises)
PTphase structural: TapChangerControl.monitoredPhase = the phase of the winding's conductor PTphase (default 1); MAX/MIN raise written: 1-based place of monitoredPhase among the winding's phase conductors; 1 on a 1-phase winding, whichever of its conductors CIM names
vreg derived: targetValue (V) = vreg x ptratio (secondary_to_primary); default 120 written: targetValue (V) / ptRatio (primary_to_secondary)
band derived: targetDeadband (V) = band x ptratio (secondary_to_primary); default 3 written: targetDeadband (V) / ptRatio (primary_to_secondary); unset -> not written, the engine's default
ptratio copied to TapChangerControl.ptRatio; RatioTapChanger.ptRatio; default 60 written: ptRatio, the tap's and the control's agreed; unset raises
CTprim copied to RatioTapChanger.ctRating (A); default 300; also ctRatio = CTprim / 0.2 (the DSS CT secondary, 0.2 A) and the LDC base written: ctRating (A); unset -> not written, and a line drop then raises
R derived: lineDropR (ohm) = R x ptratio / CTprim (line_drop_ohms); default 0; lineDropCompensation = R or X nonzero written: lineDropR (ohm) x CTprim / ptRatio (line_drop_volts); unset -> not written (0)
X derived: lineDropX (ohm) = X x ptratio / CTprim (line_drop_ohms); default 0 written: lineDropX (ohm) x CTprim / ptRatio (line_drop_volts); unset -> not written (0)
delay copied to RatioTapChanger.initialDelay (s); default 15 written: initialDelay (s); unset -> not written
tapdelay copied to RatioTapChanger.subsequentDelay (s); default 2 written: subsequentDelay (s); unset -> not written
reversible copied to TapChangerControl.reversible; default false written: TapChangerControl.reversible
revvreg derived: reverseTargetValue (V) = revvreg x ptratio (secondary_to_primary); default 120 written: reverseTargetValue (V) / ptRatio (primary_to_secondary); unset -> not written, the engine's default
revband derived: reverseTargetDeadband (V) = revband x ptratio (secondary_to_primary); default 3 written: reverseTargetDeadband (V) / ptRatio (primary_to_secondary); unset -> not written, the engine's default
revR derived: reverseLineDropR (ohm) = revR x ptratio / CTprim (line_drop_ohms); default 0 written: reverseLineDropR (ohm) x CTprim / ptRatio (line_drop_volts); unset -> not written (0)
revX derived: reverseLineDropX (ohm) = revX x ptratio / CTprim (line_drop_ohms); default 0 written: reverseLineDropX (ohm) x CTprim / ptRatio (line_drop_volts); unset -> not written (0)
revThreshold copied to TapChangerControl.reversingPowerThreshold (kW); default 100 written: reversingPowerThreshold (kW)
revDelay copied to TapChangerControl.reversingDelay (s); default 60 written: reversingDelay (s)
revNeutral copied to TapChangerControl.reverseToNeutral; default false written: reverseToNeutral
vlimit raises when set (not mapped yet) (home TapChangerControl.maxLimitVoltage) not written: maxLimitVoltage raises (untranscribed on import)
TapNum raises when set (not mapped yet) (a tap position that overrides the transformer's tap) not written: untranscribed or raising on import; not in CIM
RemotePTRatio, LDC_Z, rev_Z, Cogen, idle, idleReverse, idleForward raises when set (not mapped yet) not written: untranscribed or raising on import; not in CIM
enabled copied to TapChangerControl.enabled; RatioTapChanger.controlEnabled; default true written: the control's enabled; the tap's controlEnabled must agree
like untranscribed: the reader resolves like= before mapping not written: the writer never writes like=
maxtapchange, inversetime, debugtrace, EventLog, Reset, basefreq untranscribed (listed in the table comment) not written

Fail fast. tapwinding, bus (remote sensing), vlimit, TapNum, RemotePTRatio, LDC_Z, rev_Z, Cogen, idle, idleReverse and idleForward set; a transformer that no New defines or that two RegControls name; winding outside the transformer's windings; PTphase of MAX or MIN, or other than 1 on a 1-phase winding; a tap range that is not a whole number of steps. On export, a control whose mode is not voltage, an unset ptRatio, a line drop with no ctRating or with lineDropCompensation false, a monitored Terminal other than the tap end's, maxLimitVoltage or minLimitVoltage, and several monitored phases.

Expected differences. The control's enabled and the tap changer's controlEnabled must agree on export. A 1-phase winding's PTphase comes back 1, whichever of its conductors CIM names. Defaulted CTprim, delay, tapdelay, and the reverse settings come back explicit. ctRatio is not read.

Excerpt from cimhub_opendss/tests/atoms/regcontrol/regulators.cimtbl (reg1: 700 A CT, R=3 X=9, tap 1.0625 on a 0.625 % step, 10 steps up):

Table TapChangerControl: mRID, name, mode=voltage, discrete=true, enabled, monitoredPhase, ptRatio, targetValue, targetDeadband, lineDropCompensation, lineDropR (ohm), lineDropX (ohm), reversible, reverseTargetValue, reverseTargetDeadband, reverseLineDropR (ohm), reverseLineDropX (ohm), reversingPowerThreshold (kW), reversingDelay (s), reverseToNeutral, Terminal
    rc_reg1,  reg1,  true, A, 60.0,  7320.0,  120.0, true,  0.2571428571428571,  0.7714285714285715,  false, 7200.0,  180.0, 0.0, 0.0, 100.0, 60.0, false, xf_reg1_T2

Table RatioTapChanger: mRID, name, TransformerEnd, TapChangerControl, lowStep, highStep, neutralStep=0, step, stepVoltageIncrement (percent), neutralU (kV), ltcFlag=true, controlEnabled, ptRatio, ctRating, ctRatio, initialDelay (s), subsequentDelay (s)
    rc_reg1_tap,  reg1,  xf_reg1_2, rc_reg1,  -16, 16, 10, 0.625, 7.2,   true, 60.0,  700.0, 3500.0, 15.0, 2.0

Run it

This imports regulators and an LTC with their controls, and exports them. It runs from the repository root.

from pathlib import Path

from cimhub_opendss import DssReader, cim_to_dss, dss_to_cim

deck = Path("cimhub_opendss/tests/atoms/regcontrol/regulators.dss")
network = dss_to_cim(DssReader(deck).read_all(), name="regulators", artifact_dir="/tmp/ref-transformers")
cim_to_dss(network, "/tmp/ref-transformers/back.dss", name_source="name")

for line in Path("/tmp/ref-transformers/back.dss").read_text().splitlines():
    if line.lower().startswith(("new transformer.reg1", "new regcontrol.reg1")):
        print(line)
new Transformer.reg1 phases=1 windings=2 buses=[sub.1.0 rg.1.0] conns=[wye wye] kVs=[7.2 7.2] kVAs=[1666 1666] taps=[1 1.0625] XHL=0.01 MaxTap=1.1 MinTap=0.9 NumTaps=32 %Rs=[0.005 0.005]
new Regcontrol.reg1 transformer=reg1 winding=2 vreg=122 band=2 ptratio=60 CTprim=700 R=3 X=9 delay=15 reversible=No revvreg=120 revband=3 revR=0 revX=0 tapdelay=2 PTphase=1 revThreshold=100 revDelay=60 revNeutral=No enabled=Yes

The deck's %LoadLoss=0.01 is now %Rs=[0.005 0.005], the tap is taps=[1 1.0625] with the range written out, and the control's defaults (delay, revThreshold, ...) are explicit.