Skip to content

Class: Regcontrol

A Regcontrol object in OpenDSS representing a voltage regulator control that monitors a transformer winding and adjusts its tap to regulate voltage.

URI: dss:Regcontrol

 classDiagram
    class Regcontrol
    click Regcontrol href "../Regcontrol/"
      Regcontrol : band

      Regcontrol : basefreq

      Regcontrol : bus

      Regcontrol : Cogen

      Regcontrol : CTprim

      Regcontrol : debugtrace

      Regcontrol : delay

      Regcontrol : enabled

      Regcontrol : EventLog

      Regcontrol : idle

      Regcontrol : idleForward

      Regcontrol : idleReverse

      Regcontrol : inversetime

      Regcontrol : LDC_Z

      Regcontrol : like

      Regcontrol : maxtapchange

      Regcontrol : name

      Regcontrol : PTphase

      Regcontrol : ptratio

      Regcontrol : R

      Regcontrol : RemotePTRatio

      Regcontrol : Reset

      Regcontrol : rev_Z

      Regcontrol : revband

      Regcontrol : revDelay

      Regcontrol : reversible

      Regcontrol : revNeutral

      Regcontrol : revR

      Regcontrol : revThreshold

      Regcontrol : revvreg

      Regcontrol : revX

      Regcontrol : tapdelay

      Regcontrol : TapNum

      Regcontrol : tapwinding

      Regcontrol : transformer

      Regcontrol : vlimit

      Regcontrol : vreg

      Regcontrol : winding

      Regcontrol : X

Class Properties

Property Value
Class URI dss:Regcontrol

Slots

Name Cardinality and Range Description Inheritance
name 1
String
Object name direct
transformer 0..1
String
Name of Transformer or AutoTrans element to which the RegControl is connected direct
winding 0..1
Integer
Number of the winding of the transformer element that the RegControl is monit... direct
vreg 0..1
Float
Voltage regulator setting, in VOLTS, for the winding being controlled direct
band 0..1
Float
Bandwidth in VOLTS for the controlled bus (full bandwidth) direct
ptratio 0..1
Float
Ratio of the PT that converts the controlled winding voltage to the regulator... direct
CTprim 0..1
Float
Rating, in Amperes, of the primary CT rating for which the line amps convert ... direct
R 0..1
Float
R setting on the line drop compensator in the regulator, expressed in VOLTS direct
X 0..1
Float
X setting on the line drop compensator in the regulator, expressed in VOLTS direct
bus 0..1
String
Name of a bus (busname direct
delay 0..1
Float
Time delay, in seconds, from when the voltage goes out of band to when tap ch... direct
reversible 0..1
Boolean
{Yes No*} Indicates whether the regulator has a reverse operation mode
revvreg 0..1
Float
Voltage setting in volts for operation in the reverse direction direct
revband 0..1
Float
Bandwidth for operating in the reverse direction direct
revR 0..1
Float
R line drop compensator setting for reverse direction direct
revX 0..1
Float
X line drop compensator setting for reverse direction direct
tapdelay 0..1
Float
Delay in sec between tap changes direct
debugtrace 0..1
Boolean
{Yes No* } Default is no
maxtapchange 0..1
Integer
Maximum allowable tap change per control iteration in STATIC control mode direct
inversetime 0..1
Boolean
{Yes No* } Default is no
tapwinding 0..1
Integer
Winding containing the actual taps, if different than the WINDING property direct
vlimit 0..1
Float
Voltage Limit for bus to which regulated winding is connected direct
PTphase 0..1
String
For multi-phase transformers, the number of the phase being monitored or one ... direct
revThreshold 0..1
Float
kW reverse power threshold for reversing the direction of the regulator direct
revDelay 0..1
Float
Time Delay in seconds for executing the reversing action once the threshold f... direct
revNeutral 0..1
Boolean
{Yes No*} Default is no
EventLog 0..1
Boolean
{Yes/True* No/False} Default is YES for regulator control
RemotePTRatio 0..1
Float
PT ratio required to convert actual voltage at the remote bus to control volt... direct
TapNum 0..1
Integer
An integer number indicating the tap position that the controlled transformer... direct
Reset 0..1
Boolean
{Yes No} If Yes, forces Reset of this RegControl
LDC_Z 0..1
Float
Z value for Beckwith LDC_Z control option direct
rev_Z 0..1
Float
Reverse Z value for Beckwith LDC_Z control option direct
Cogen 0..1
Boolean
{Yes No*} Default is No
idle 0..1
Boolean
{Yes No*} Default is No
idleReverse 0..1
Boolean
{Yes No*} Default is No
idleForward 0..1
Boolean
{Yes No*} Default is No
basefreq 0..1
Float
Base Frequency for ratings direct
enabled 0..1
Boolean
{Yes No or True
like 0..1
String
Make like another object, e direct

Comments

  • Import: one TapChangerControl rc_ + name and one RatioTapChanger rc_ + name + _tap (regcontrol.cimtbl) on the controlled end of the transformer it names (a VoltageRegulator's AutoTransformerEnd, or an LTC's PowerTransformerEnd). Export: one RegControl per TapChangerControl; another mode raises.

Identifier and Mapping Information

Schema Source

  • from schema: https://gridappsd.github.io/dss-graph/opendss

Mappings

Mapping Type Mapped Value
self dss:Regcontrol
native dss:Regcontrol
exact cim:TapChangerControl
close cim:RatioTapChanger

LinkML Source

Direct

name: Regcontrol
description: A Regcontrol object in OpenDSS representing a voltage regulator control
  that monitors a transformer winding and adjusts its tap to regulate voltage.
comments:
- 'Import: one TapChangerControl rc_ + name and one RatioTapChanger rc_ + name + _tap
  (regcontrol.cimtbl) on the controlled end of the transformer it names (a VoltageRegulator''s
  AutoTransformerEnd, or an LTC''s PowerTransformerEnd). Export: one RegControl per
  TapChangerControl; another mode raises.'
from_schema: https://gridappsd.github.io/dss-graph/opendss
exact_mappings:
- cim:TapChangerControl
close_mappings:
- cim:RatioTapChanger
attributes:
  name:
    name: name
    description: Object name. Must be unique per object type.
    comments:
    - 'Import: TapChangerControl.name and RatioTapChanger.name. Export: Names, the
      RegControl namespace.'
    from_schema: https://gridappsd.github.io/dss-graph/controls/regcontrol
    exact_mappings:
    - cim:IdentifiedObject.name
    identifier: true
    domain_of:
    - Load
    - Generator
    - Generic5
    - Gicline
    - Indmach012
    - Pvsystem
    - Storage
    - Upfc
    - Vccs
    - Vsconverter
    - Windgen
    - Autotrans
    - Capacitor
    - Gictransformer
    - Line
    - Reactor
    - Transformer
    - Capcontrol
    - Espvlcontrol
    - Expcontrol
    - Fuse
    - Gendispatcher
    - Invcontrol
    - Pycontrol
    - Recloser
    - Regcontrol
    - Relay
    - Storagecontroller
    - Swtcontrol
    - Upfccontrol
    - Buscoords
    - Cndata
    - Dynamicexp
    - Growthshape
    - Linecode
    - Linegeometry
    - Linespacing
    - Loadshape
    - Priceshape
    - Spectrum
    - TccCurve
    - Tsdata
    - Tshape
    - Wiredata
    - Xfmrcode
    - Xycurve
    - Energymeter
    - Fmonitor
    - Monitor
    - Sensor
    - Fault
    - Gicsource
    - Isource
    - Options
    - Vsource
    range: string
    required: true
  transformer:
    name: transformer
    annotations:
      order:
        tag: order
        value: 1
    description: Name of Transformer or AutoTrans element to which the RegControl
      is connected.
    comments:
    - 'Import: structural; the regulator or LTC, a Transformer no New defines or two
      RegControls name raises. Export: the DSS Transformer of the tap''s unit.'
    from_schema: https://gridappsd.github.io/dss-graph/controls/regcontrol
    close_mappings:
    - cim:RatioTapChanger.TransformerEnd
    rank: 1000
    domain_of:
    - Regcontrol
    range: string
    required: false
  winding:
    name: winding
    annotations:
      order:
        tag: order
        value: 2
      dss_default:
        tag: dss_default
        value: int(1)
    description: Number of the winding of the transformer element that the RegControl
      is monitoring. Default is 1.
    comments:
    - 'Import: the end xf_<transformer>_<winding> holds the tap changer and its Terminal
      is monitored; default 1. Export: the winding whose end holds the RatioTapChanger.'
    from_schema: https://gridappsd.github.io/dss-graph/controls/regcontrol
    close_mappings:
    - cim:RatioTapChanger.TransformerEnd
    - cim:RegulatingControl.Terminal
    rank: 1000
    domain_of:
    - Regcontrol
    range: integer
    required: false
  vreg:
    name: vreg
    annotations:
      order:
        tag: order
        value: 3
      dss_default:
        tag: dss_default
        value: float(120.0)
    description: Voltage regulator setting, in VOLTS, for the winding being controlled.
      Default is 120 V.
    comments:
    - 'Import: derived; targetValue (V) = vreg x ptratio (secondary_to_primary); default
      120. Export: targetValue / ptRatio.'
    from_schema: https://gridappsd.github.io/dss-graph/controls/regcontrol
    close_mappings:
    - cim:RegulatingControl.targetValue
    rank: 1000
    domain_of:
    - Regcontrol
    range: float
    required: false
  band:
    name: band
    annotations:
      order:
        tag: order
        value: 4
      dss_default:
        tag: dss_default
        value: float(3.0)
    description: Bandwidth in VOLTS for the controlled bus (full bandwidth). Default
      is 3 V.
    comments:
    - 'Import: derived; targetDeadband (V) = band x ptratio; default 3. Export: targetDeadband
      / ptRatio.'
    from_schema: https://gridappsd.github.io/dss-graph/controls/regcontrol
    close_mappings:
    - cim:RegulatingControl.targetDeadband
    rank: 1000
    domain_of:
    - Regcontrol
    range: float
    required: false
  ptratio:
    name: ptratio
    annotations:
      order:
        tag: order
        value: 5
      dss_default:
        tag: dss_default
        value: float(60.0)
    description: Ratio of the PT that converts the controlled winding voltage to the
      regulator control voltage. Default is 60.
    comments:
    - 'Import: ptRatio on the control and the tap changer; default 60. Export: ptRatio
      (the two must agree; unset raises).'
    from_schema: https://gridappsd.github.io/dss-graph/controls/regcontrol
    exact_mappings:
    - cim:RegulatingControl.ptRatio
    - cim:TapChanger.ptRatio
    rank: 1000
    domain_of:
    - Regcontrol
    range: float
    required: false
    minimum_value: 0.0
  CTprim:
    name: CTprim
    annotations:
      order:
        tag: order
        value: 6
      dss_default:
        tag: dss_default
        value: float(300.0)
    description: Rating, in Amperes, of the primary CT rating for which the line amps
      convert to control rated amps. Default is 300 A.
    comments:
    - 'Import: ctRating (A) = CTprim, ctRatio = CTprim / 0.2 (the DSS CT secondary);
      default 300. Export: ctRating (A); ctRatio is not read.'
    from_schema: https://gridappsd.github.io/dss-graph/controls/regcontrol
    close_mappings:
    - cim:TapChanger.ctRating
    - cim:TapChanger.ctRatio
    rank: 1000
    domain_of:
    - Regcontrol
    range: float
    required: false
  R:
    name: R
    annotations:
      order:
        tag: order
        value: 7
      dss_default:
        tag: dss_default
        value: float(0.0)
    description: R setting on the line drop compensator in the regulator, expressed
      in VOLTS.
    comments:
    - 'Import: derived; lineDropR (ohm) = R x ptratio / CTprim, compensation on when
      R or X is nonzero. Export: lineDropR x CTprim / ptRatio.'
    from_schema: https://gridappsd.github.io/dss-graph/controls/regcontrol
    close_mappings:
    - cim:TapChangerControl.lineDropR
    - cim:TapChangerControl.lineDropCompensation
    domain_of:
    - Gicline
    - Capacitor
    - Reactor
    - Regcontrol
    range: float
    required: false
  X:
    name: X
    annotations:
      order:
        tag: order
        value: 8
      dss_default:
        tag: dss_default
        value: float(0.0)
    description: X setting on the line drop compensator in the regulator, expressed
      in VOLTS.
    comments:
    - 'Import: derived; lineDropX (ohm) = X x ptratio / CTprim. Export: lineDropX
      x CTprim / ptRatio.'
    from_schema: https://gridappsd.github.io/dss-graph/controls/regcontrol
    close_mappings:
    - cim:TapChangerControl.lineDropX
    domain_of:
    - Gicline
    - Reactor
    - Regcontrol
    range: float
    required: false
  bus:
    name: bus
    annotations:
      order:
        tag: order
        value: 9
    description: Name of a bus (busname.nn.nn.nn) for remote voltage sensing. When
      set, the regulator monitors this bus instead of the transformer winding.
    comments:
    - 'Import: raises when set (remote sensing); no deck in the sweep sets it, so
      a mapping waits for one. Export: unset.'
    from_schema: https://gridappsd.github.io/dss-graph/controls/regcontrol
    domain_of:
    - Autotrans
    - Transformer
    - Regcontrol
    range: string
    required: false
  delay:
    name: delay
    annotations:
      order:
        tag: order
        value: 10
      dss_default:
        tag: dss_default
        value: float(15.0)
    description: Time delay, in seconds, from when the voltage goes out of band to
      when tap changing begins. Default is 15 s.
    comments:
    - 'Import: initialDelay (s); default 15. Export: initialDelay; unset -> not written.'
    from_schema: https://gridappsd.github.io/dss-graph/controls/regcontrol
    exact_mappings:
    - cim:TapChanger.initialDelay
    rank: 1000
    domain_of:
    - Regcontrol
    range: float
    required: false
  reversible:
    name: reversible
    annotations:
      order:
        tag: order
        value: 11
      dss_default:
        tag: dss_default
        value: 'false'
    description: '{Yes |No*} Indicates whether the regulator has a reverse operation
      mode.'
    comments:
    - 'Import: reversible; default false. Export: reversible.'
    from_schema: https://gridappsd.github.io/dss-graph/controls/regcontrol
    exact_mappings:
    - cim:TapChangerControl.reversible
    rank: 1000
    domain_of:
    - Regcontrol
    range: boolean
    required: false
  revvreg:
    name: revvreg
    annotations:
      order:
        tag: order
        value: 12
      dss_default:
        tag: dss_default
        value: float(120.0)
    description: Voltage setting in volts for operation in the reverse direction.
      Default is 120 V.
    comments:
    - 'Import: derived; reverseTargetValue (V) = revvreg x ptratio; default 120. Export:
      reverseTargetValue / ptRatio.'
    from_schema: https://gridappsd.github.io/dss-graph/controls/regcontrol
    close_mappings:
    - cim:RegulatingControl.reverseTargetValue
    rank: 1000
    domain_of:
    - Regcontrol
    range: float
    required: false
  revband:
    name: revband
    annotations:
      order:
        tag: order
        value: 13
      dss_default:
        tag: dss_default
        value: float(3.0)
    description: Bandwidth for operating in the reverse direction. Default is 3 V.
    comments:
    - 'Import: derived; reverseTargetDeadband (V) = revband x ptratio; default 3.
      Export: reverseTargetDeadband / ptRatio.'
    from_schema: https://gridappsd.github.io/dss-graph/controls/regcontrol
    close_mappings:
    - cim:RegulatingControl.reverseTargetDeadband
    rank: 1000
    domain_of:
    - Regcontrol
    range: float
    required: false
  revR:
    name: revR
    annotations:
      order:
        tag: order
        value: 14
      dss_default:
        tag: dss_default
        value: float(0.0)
    description: R line drop compensator setting for reverse direction.
    comments:
    - 'Import: derived; reverseLineDropR (ohm) = revR x ptratio / CTprim. Export:
      reverseLineDropR x CTprim / ptRatio.'
    from_schema: https://gridappsd.github.io/dss-graph/controls/regcontrol
    close_mappings:
    - cim:TapChangerControl.reverseLineDropR
    rank: 1000
    domain_of:
    - Regcontrol
    range: float
    required: false
  revX:
    name: revX
    annotations:
      order:
        tag: order
        value: 15
      dss_default:
        tag: dss_default
        value: float(0.0)
    description: X line drop compensator setting for reverse direction.
    comments:
    - 'Import: derived; reverseLineDropX (ohm) = revX x ptratio / CTprim. Export:
      reverseLineDropX x CTprim / ptRatio.'
    from_schema: https://gridappsd.github.io/dss-graph/controls/regcontrol
    close_mappings:
    - cim:TapChangerControl.reverseLineDropX
    rank: 1000
    domain_of:
    - Regcontrol
    range: float
    required: false
  tapdelay:
    name: tapdelay
    annotations:
      order:
        tag: order
        value: 16
      dss_default:
        tag: dss_default
        value: float(2.0)
    description: Delay in sec between tap changes. Default is 2 s.
    comments:
    - 'Import: subsequentDelay (s); default 2. Export: subsequentDelay; unset -> not
      written.'
    from_schema: https://gridappsd.github.io/dss-graph/controls/regcontrol
    exact_mappings:
    - cim:TapChanger.subsequentDelay
    rank: 1000
    domain_of:
    - Regcontrol
    range: float
    required: false
  debugtrace:
    name: debugtrace
    annotations:
      order:
        tag: order
        value: 17
    description: '{Yes | No* }  Default is no. If true, writes debug trace to file.'
    comments:
    - 'Import: untranscribed (DSS report flag). Export: unset.'
    from_schema: https://gridappsd.github.io/dss-graph/controls/regcontrol
    domain_of:
    - Generator
    - Pvsystem
    - Storage
    - Windgen
    - Regcontrol
    range: boolean
    required: false
  maxtapchange:
    name: maxtapchange
    annotations:
      order:
        tag: order
        value: 18
    description: Maximum allowable tap change per control iteration in STATIC control
      mode. Default is 16.
    comments:
    - 'Import: untranscribed (DSS solution control; no home in the network profile
      parts). Export: unset.'
    from_schema: https://gridappsd.github.io/dss-graph/controls/regcontrol
    rank: 1000
    domain_of:
    - Regcontrol
    range: integer
    required: false
  inversetime:
    name: inversetime
    annotations:
      order:
        tag: order
        value: 19
    description: '{Yes | No* } Default is no. If yes, time delays decrease inversely
      with magnitude of voltage excursion.'
    comments:
    - 'Import: untranscribed (DSS solution control; no home in the network profile
      parts). Export: unset.'
    from_schema: https://gridappsd.github.io/dss-graph/controls/regcontrol
    rank: 1000
    domain_of:
    - Regcontrol
    range: boolean
    required: false
  tapwinding:
    name: tapwinding
    annotations:
      order:
        tag: order
        value: 20
    description: Winding containing the actual taps, if different than the WINDING
      property.
    comments:
    - 'Import: raises when set (a tap winding other than the monitored one); no deck
      in the sweep sets it, so a mapping waits for one. Export: unset.'
    from_schema: https://gridappsd.github.io/dss-graph/controls/regcontrol
    rank: 1000
    domain_of:
    - Regcontrol
    range: integer
    required: false
  vlimit:
    name: vlimit
    annotations:
      order:
        tag: order
        value: 21
      dss_default:
        tag: dss_default
        value: float(0.0)
    description: Voltage Limit for bus to which regulated winding is connected. Default
      is 0 (no limit).
    todos:
    - 'Converter bug: uses tcc.limitVoltage (not a real TapChangerControl field) instead
      of tcc.maxLimitVoltage on both import and export.'
    comments:
    - 'Import: raises when set to anything but its default 0 (no limit); no deck in
      the sweep sets it, so a mapping waits for one. Export: a control with a voltage
      limit raises.'
    from_schema: https://gridappsd.github.io/dss-graph/controls/regcontrol
    close_mappings:
    - cim:TapChangerControl.maxLimitVoltage
    rank: 1000
    domain_of:
    - Regcontrol
    range: float
    required: false
  PTphase:
    name: PTphase
    annotations:
      order:
        tag: order
        value: 22
      dss_default:
        tag: dss_default
        value: int(1)
    description: For multi-phase transformers, the number of the phase being monitored
      or one of {MAX | MIN} for all phases. Default is 1.
    comments:
    - 'Import: monitoredPhase = the phase of the winding''s conductor PTphase (default
      1); MAX and MIN raise. Export: the 1-based place of monitoredPhase among the
      winding''s phase conductors.'
    from_schema: https://gridappsd.github.io/dss-graph/controls/regcontrol
    close_mappings:
    - cim:RegulatingControl.monitoredPhase
    rank: 1000
    domain_of:
    - Regcontrol
    range: string
    required: false
  revThreshold:
    name: revThreshold
    annotations:
      order:
        tag: order
        value: 23
      dss_default:
        tag: dss_default
        value: float(100.0)
    description: kW reverse power threshold for reversing the direction of the regulator.
      Default is 100 kW.
    comments:
    - 'Import: reversingPowerThreshold (kW); default 100. Export: reversingPowerThreshold
      (kW).'
    from_schema: https://gridappsd.github.io/dss-graph/controls/regcontrol
    exact_mappings:
    - cim:TapChangerControl.reversingPowerThreshold
    rank: 1000
    domain_of:
    - Regcontrol
    range: float
    required: false
  revDelay:
    name: revDelay
    annotations:
      order:
        tag: order
        value: 24
      dss_default:
        tag: dss_default
        value: float(60.0)
    description: Time Delay in seconds for executing the reversing action once the
      threshold for reversing has been exceeded. Default is 60 s.
    comments:
    - 'Import: reversingDelay (s); default 60. Export: reversingDelay (s).'
    from_schema: https://gridappsd.github.io/dss-graph/controls/regcontrol
    exact_mappings:
    - cim:TapChangerControl.reversingDelay
    rank: 1000
    domain_of:
    - Regcontrol
    range: float
    required: false
  revNeutral:
    name: revNeutral
    annotations:
      order:
        tag: order
        value: 25
      dss_default:
        tag: dss_default
        value: 'false'
    description: '{Yes | No*} Default is no. If yes, regulator goes to neutral tap
      in reverse direction.'
    comments:
    - 'Import: reverseToNeutral; default false. Export: reverseToNeutral.'
    from_schema: https://gridappsd.github.io/dss-graph/controls/regcontrol
    exact_mappings:
    - cim:TapChangerControl.reverseToNeutral
    rank: 1000
    domain_of:
    - Regcontrol
    range: boolean
    required: false
  EventLog:
    name: EventLog
    annotations:
      order:
        tag: order
        value: 26
    description: '{Yes/True* | No/False} Default is YES for regulator control.'
    comments:
    - 'Import: untranscribed (DSS report flag). Export: unset.'
    from_schema: https://gridappsd.github.io/dss-graph/controls/regcontrol
    domain_of:
    - Capcontrol
    - Expcontrol
    - Invcontrol
    - Regcontrol
    - Relay
    - Storagecontroller
    range: boolean
    required: false
  RemotePTRatio:
    name: RemotePTRatio
    annotations:
      order:
        tag: order
        value: 27
    description: PT ratio required to convert actual voltage at the remote bus to
      control voltage when regulating a remote bus.
    comments:
    - 'Import: raises when set (remote sensing); no deck in the sweep sets it, so
      a mapping waits for one. Export: unset.'
    from_schema: https://gridappsd.github.io/dss-graph/controls/regcontrol
    rank: 1000
    domain_of:
    - Regcontrol
    range: float
    required: false
  TapNum:
    name: TapNum
    annotations:
      order:
        tag: order
        value: 28
    description: An integer number indicating the tap position that the controlled
      transformer winding tap position is currently at.
    comments:
    - 'Import: raises when set, even to 0 (a tap position that overrides the transformer''s
      tap: setting it moves the tap, so it has no default); no deck in the sweep sets
      it. Export: unset.'
    from_schema: https://gridappsd.github.io/dss-graph/controls/regcontrol
    close_mappings:
    - cim:TapChanger.step
    rank: 1000
    domain_of:
    - Regcontrol
    range: integer
    required: false
  Reset:
    name: Reset
    annotations:
      order:
        tag: order
        value: 29
    description: '{Yes | No} If Yes, forces Reset of this RegControl.'
    comments:
    - 'Import: untranscribed (a command, not a setting). Export: unset.'
    from_schema: https://gridappsd.github.io/dss-graph/controls/regcontrol
    domain_of:
    - Capcontrol
    - Recloser
    - Regcontrol
    - Relay
    - Swtcontrol
    range: boolean
    required: false
  LDC_Z:
    name: LDC_Z
    annotations:
      order:
        tag: order
        value: 30
      dss_default:
        tag: dss_default
        value: float(0.0)
    description: Z value for Beckwith LDC_Z control option. Complex impedance in ohms.
    comments:
    - 'Import: raises when set to anything but its default 0 (a line-drop impedance);
      no deck in the sweep sets it, so a mapping waits for one. Export: unset.'
    from_schema: https://gridappsd.github.io/dss-graph/controls/regcontrol
    rank: 1000
    domain_of:
    - Regcontrol
    range: float
    required: false
  rev_Z:
    name: rev_Z
    annotations:
      order:
        tag: order
        value: 31
      dss_default:
        tag: dss_default
        value: float(0.0)
    description: Reverse Z value for Beckwith LDC_Z control option.
    comments:
    - 'Import: raises when set to anything but its default 0 (a reverse line-drop
      impedance); no deck in the sweep sets it, so a mapping waits for one. Export:
      unset.'
    from_schema: https://gridappsd.github.io/dss-graph/controls/regcontrol
    rank: 1000
    domain_of:
    - Regcontrol
    range: float
    required: false
  Cogen:
    name: Cogen
    annotations:
      order:
        tag: order
        value: 32
      dss_default:
        tag: dss_default
        value: 'false'
    description: '{Yes|No*} Default is No. Cogen mode — sets direction of power flow
      sensing for reverse operation.'
    comments:
    - 'Import: raises when set to anything but its default No (cogeneration); no deck
      in the sweep sets it, so a mapping waits for one. Export: unset.'
    from_schema: https://gridappsd.github.io/dss-graph/controls/regcontrol
    rank: 1000
    domain_of:
    - Regcontrol
    range: boolean
    required: false
  idle:
    name: idle
    annotations:
      order:
        tag: order
        value: 33
    description: '{Yes|No*} Default is No. If Yes, disables tap changing.'
    comments:
    - 'Import: raises when set (idle mode); no deck in the sweep sets it, so a mapping
      waits for one. Export: unset.'
    from_schema: https://gridappsd.github.io/dss-graph/controls/regcontrol
    rank: 1000
    domain_of:
    - Regcontrol
    range: boolean
    required: false
  idleReverse:
    name: idleReverse
    annotations:
      order:
        tag: order
        value: 34
    description: '{Yes|No*} Default is No. If Yes, disables tap changing in reverse
      mode.'
    comments:
    - 'Import: raises when set (idle mode); no deck in the sweep sets it, so a mapping
      waits for one. Export: unset.'
    from_schema: https://gridappsd.github.io/dss-graph/controls/regcontrol
    rank: 1000
    domain_of:
    - Regcontrol
    range: boolean
    required: false
  idleForward:
    name: idleForward
    annotations:
      order:
        tag: order
        value: 35
    description: '{Yes|No*} Default is No. If Yes, disables tap changing in forward
      mode.'
    comments:
    - 'Import: raises when set (idle mode); no deck in the sweep sets it, so a mapping
      waits for one. Export: unset.'
    from_schema: https://gridappsd.github.io/dss-graph/controls/regcontrol
    rank: 1000
    domain_of:
    - Regcontrol
    range: boolean
    required: false
  basefreq:
    name: basefreq
    annotations:
      order:
        tag: order
        value: 36
    description: Base Frequency for ratings.
    comments:
    - 'Import: untranscribed (no home on a control). Export: unset.'
    from_schema: https://gridappsd.github.io/dss-graph/controls/regcontrol
    domain_of:
    - Load
    - Generator
    - Generic5
    - Gicline
    - Indmach012
    - Pvsystem
    - Storage
    - Upfc
    - Vccs
    - Vsconverter
    - Windgen
    - Autotrans
    - Capacitor
    - Gictransformer
    - Line
    - Reactor
    - Transformer
    - Capcontrol
    - Espvlcontrol
    - Expcontrol
    - Fuse
    - Gendispatcher
    - Invcontrol
    - Pycontrol
    - Recloser
    - Regcontrol
    - Relay
    - Storagecontroller
    - Swtcontrol
    - Upfccontrol
    - Energymeter
    - Fmonitor
    - Monitor
    - Sensor
    - Fault
    - Gicsource
    - Isource
    - Vsource
    range: float
    required: false
  enabled:
    name: enabled
    annotations:
      order:
        tag: order
        value: 37
      dss_default:
        tag: dss_default
        value: 'true'
    description: '{Yes|No or True|False} Indicates whether this element is enabled.'
    comments:
    - 'Import: the control''s enabled and the tap''s controlEnabled; default true.
      Export: the control''s enabled; the tap''s must agree.'
    from_schema: https://gridappsd.github.io/dss-graph/controls/regcontrol
    exact_mappings:
    - cim:RegulatingControl.enabled
    - cim:TapChanger.controlEnabled
    domain_of:
    - Load
    - Generator
    - Generic5
    - Gicline
    - Indmach012
    - Pvsystem
    - Storage
    - Upfc
    - Vccs
    - Vsconverter
    - Windgen
    - Autotrans
    - Capacitor
    - Gictransformer
    - Line
    - Reactor
    - Transformer
    - Capcontrol
    - Espvlcontrol
    - Expcontrol
    - Fuse
    - Gendispatcher
    - Invcontrol
    - Pycontrol
    - Recloser
    - Regcontrol
    - Relay
    - Storagecontroller
    - Swtcontrol
    - Upfccontrol
    - Energymeter
    - Fmonitor
    - Monitor
    - Sensor
    - Fault
    - Gicsource
    - Isource
    - Vsource
    range: boolean
    required: false
  like:
    name: like
    annotations:
      order:
        tag: order
        value: 38
    description: 'Make like another object, e.g.: New Regcontrol.RC2 like=RC1 ...'
    comments:
    - 'Import: untranscribed; the reader resolves like= before mapping. Export: never
      written.'
    from_schema: https://gridappsd.github.io/dss-graph/controls/regcontrol
    domain_of:
    - Load
    - Generator
    - Generic5
    - Gicline
    - Indmach012
    - Pvsystem
    - Storage
    - Upfc
    - Vccs
    - Vsconverter
    - Windgen
    - Autotrans
    - Capacitor
    - Gictransformer
    - Line
    - Reactor
    - Transformer
    - Capcontrol
    - Espvlcontrol
    - Expcontrol
    - Fuse
    - Gendispatcher
    - Invcontrol
    - Pycontrol
    - Recloser
    - Regcontrol
    - Relay
    - Storagecontroller
    - Swtcontrol
    - Upfccontrol
    - Cndata
    - Dynamicexp
    - Growthshape
    - Linecode
    - Linegeometry
    - Linespacing
    - Loadshape
    - Priceshape
    - Spectrum
    - TccCurve
    - Tsdata
    - Tshape
    - Wiredata
    - Xfmrcode
    - Xycurve
    - Energymeter
    - Fmonitor
    - Monitor
    - Sensor
    - Fault
    - Gicsource
    - Isource
    - Vsource
    range: string
    required: false
class_uri: dss:Regcontrol

Induced

name: Regcontrol
description: A Regcontrol object in OpenDSS representing a voltage regulator control
  that monitors a transformer winding and adjusts its tap to regulate voltage.
comments:
- 'Import: one TapChangerControl rc_ + name and one RatioTapChanger rc_ + name + _tap
  (regcontrol.cimtbl) on the controlled end of the transformer it names (a VoltageRegulator''s
  AutoTransformerEnd, or an LTC''s PowerTransformerEnd). Export: one RegControl per
  TapChangerControl; another mode raises.'
from_schema: https://gridappsd.github.io/dss-graph/opendss
exact_mappings:
- cim:TapChangerControl
close_mappings:
- cim:RatioTapChanger
attributes:
  name:
    name: name
    description: Object name. Must be unique per object type.
    comments:
    - 'Import: TapChangerControl.name and RatioTapChanger.name. Export: Names, the
      RegControl namespace.'
    from_schema: https://gridappsd.github.io/dss-graph/controls/regcontrol
    exact_mappings:
    - cim:IdentifiedObject.name
    identifier: true
    owner: Regcontrol
    domain_of:
    - Load
    - Generator
    - Generic5
    - Gicline
    - Indmach012
    - Pvsystem
    - Storage
    - Upfc
    - Vccs
    - Vsconverter
    - Windgen
    - Autotrans
    - Capacitor
    - Gictransformer
    - Line
    - Reactor
    - Transformer
    - Capcontrol
    - Espvlcontrol
    - Expcontrol
    - Fuse
    - Gendispatcher
    - Invcontrol
    - Pycontrol
    - Recloser
    - Regcontrol
    - Relay
    - Storagecontroller
    - Swtcontrol
    - Upfccontrol
    - Buscoords
    - Cndata
    - Dynamicexp
    - Growthshape
    - Linecode
    - Linegeometry
    - Linespacing
    - Loadshape
    - Priceshape
    - Spectrum
    - TccCurve
    - Tsdata
    - Tshape
    - Wiredata
    - Xfmrcode
    - Xycurve
    - Energymeter
    - Fmonitor
    - Monitor
    - Sensor
    - Fault
    - Gicsource
    - Isource
    - Options
    - Vsource
    range: string
    required: true
  transformer:
    name: transformer
    annotations:
      order:
        tag: order
        value: 1
    description: Name of Transformer or AutoTrans element to which the RegControl
      is connected.
    comments:
    - 'Import: structural; the regulator or LTC, a Transformer no New defines or two
      RegControls name raises. Export: the DSS Transformer of the tap''s unit.'
    from_schema: https://gridappsd.github.io/dss-graph/controls/regcontrol
    close_mappings:
    - cim:RatioTapChanger.TransformerEnd
    rank: 1000
    owner: Regcontrol
    domain_of:
    - Regcontrol
    range: string
    required: false
  winding:
    name: winding
    annotations:
      order:
        tag: order
        value: 2
      dss_default:
        tag: dss_default
        value: int(1)
    description: Number of the winding of the transformer element that the RegControl
      is monitoring. Default is 1.
    comments:
    - 'Import: the end xf_<transformer>_<winding> holds the tap changer and its Terminal
      is monitored; default 1. Export: the winding whose end holds the RatioTapChanger.'
    from_schema: https://gridappsd.github.io/dss-graph/controls/regcontrol
    close_mappings:
    - cim:RatioTapChanger.TransformerEnd
    - cim:RegulatingControl.Terminal
    rank: 1000
    owner: Regcontrol
    domain_of:
    - Regcontrol
    range: integer
    required: false
  vreg:
    name: vreg
    annotations:
      order:
        tag: order
        value: 3
      dss_default:
        tag: dss_default
        value: float(120.0)
    description: Voltage regulator setting, in VOLTS, for the winding being controlled.
      Default is 120 V.
    comments:
    - 'Import: derived; targetValue (V) = vreg x ptratio (secondary_to_primary); default
      120. Export: targetValue / ptRatio.'
    from_schema: https://gridappsd.github.io/dss-graph/controls/regcontrol
    close_mappings:
    - cim:RegulatingControl.targetValue
    rank: 1000
    owner: Regcontrol
    domain_of:
    - Regcontrol
    range: float
    required: false
  band:
    name: band
    annotations:
      order:
        tag: order
        value: 4
      dss_default:
        tag: dss_default
        value: float(3.0)
    description: Bandwidth in VOLTS for the controlled bus (full bandwidth). Default
      is 3 V.
    comments:
    - 'Import: derived; targetDeadband (V) = band x ptratio; default 3. Export: targetDeadband
      / ptRatio.'
    from_schema: https://gridappsd.github.io/dss-graph/controls/regcontrol
    close_mappings:
    - cim:RegulatingControl.targetDeadband
    rank: 1000
    owner: Regcontrol
    domain_of:
    - Regcontrol
    range: float
    required: false
  ptratio:
    name: ptratio
    annotations:
      order:
        tag: order
        value: 5
      dss_default:
        tag: dss_default
        value: float(60.0)
    description: Ratio of the PT that converts the controlled winding voltage to the
      regulator control voltage. Default is 60.
    comments:
    - 'Import: ptRatio on the control and the tap changer; default 60. Export: ptRatio
      (the two must agree; unset raises).'
    from_schema: https://gridappsd.github.io/dss-graph/controls/regcontrol
    exact_mappings:
    - cim:RegulatingControl.ptRatio
    - cim:TapChanger.ptRatio
    rank: 1000
    owner: Regcontrol
    domain_of:
    - Regcontrol
    range: float
    required: false
    minimum_value: 0.0
  CTprim:
    name: CTprim
    annotations:
      order:
        tag: order
        value: 6
      dss_default:
        tag: dss_default
        value: float(300.0)
    description: Rating, in Amperes, of the primary CT rating for which the line amps
      convert to control rated amps. Default is 300 A.
    comments:
    - 'Import: ctRating (A) = CTprim, ctRatio = CTprim / 0.2 (the DSS CT secondary);
      default 300. Export: ctRating (A); ctRatio is not read.'
    from_schema: https://gridappsd.github.io/dss-graph/controls/regcontrol
    close_mappings:
    - cim:TapChanger.ctRating
    - cim:TapChanger.ctRatio
    rank: 1000
    owner: Regcontrol
    domain_of:
    - Regcontrol
    range: float
    required: false
  R:
    name: R
    annotations:
      order:
        tag: order
        value: 7
      dss_default:
        tag: dss_default
        value: float(0.0)
    description: R setting on the line drop compensator in the regulator, expressed
      in VOLTS.
    comments:
    - 'Import: derived; lineDropR (ohm) = R x ptratio / CTprim, compensation on when
      R or X is nonzero. Export: lineDropR x CTprim / ptRatio.'
    from_schema: https://gridappsd.github.io/dss-graph/controls/regcontrol
    close_mappings:
    - cim:TapChangerControl.lineDropR
    - cim:TapChangerControl.lineDropCompensation
    owner: Regcontrol
    domain_of:
    - Gicline
    - Capacitor
    - Reactor
    - Regcontrol
    range: float
    required: false
  X:
    name: X
    annotations:
      order:
        tag: order
        value: 8
      dss_default:
        tag: dss_default
        value: float(0.0)
    description: X setting on the line drop compensator in the regulator, expressed
      in VOLTS.
    comments:
    - 'Import: derived; lineDropX (ohm) = X x ptratio / CTprim. Export: lineDropX
      x CTprim / ptRatio.'
    from_schema: https://gridappsd.github.io/dss-graph/controls/regcontrol
    close_mappings:
    - cim:TapChangerControl.lineDropX
    owner: Regcontrol
    domain_of:
    - Gicline
    - Reactor
    - Regcontrol
    range: float
    required: false
  bus:
    name: bus
    annotations:
      order:
        tag: order
        value: 9
    description: Name of a bus (busname.nn.nn.nn) for remote voltage sensing. When
      set, the regulator monitors this bus instead of the transformer winding.
    comments:
    - 'Import: raises when set (remote sensing); no deck in the sweep sets it, so
      a mapping waits for one. Export: unset.'
    from_schema: https://gridappsd.github.io/dss-graph/controls/regcontrol
    owner: Regcontrol
    domain_of:
    - Autotrans
    - Transformer
    - Regcontrol
    range: string
    required: false
  delay:
    name: delay
    annotations:
      order:
        tag: order
        value: 10
      dss_default:
        tag: dss_default
        value: float(15.0)
    description: Time delay, in seconds, from when the voltage goes out of band to
      when tap changing begins. Default is 15 s.
    comments:
    - 'Import: initialDelay (s); default 15. Export: initialDelay; unset -> not written.'
    from_schema: https://gridappsd.github.io/dss-graph/controls/regcontrol
    exact_mappings:
    - cim:TapChanger.initialDelay
    rank: 1000
    owner: Regcontrol
    domain_of:
    - Regcontrol
    range: float
    required: false
  reversible:
    name: reversible
    annotations:
      order:
        tag: order
        value: 11
      dss_default:
        tag: dss_default
        value: 'false'
    description: '{Yes |No*} Indicates whether the regulator has a reverse operation
      mode.'
    comments:
    - 'Import: reversible; default false. Export: reversible.'
    from_schema: https://gridappsd.github.io/dss-graph/controls/regcontrol
    exact_mappings:
    - cim:TapChangerControl.reversible
    rank: 1000
    owner: Regcontrol
    domain_of:
    - Regcontrol
    range: boolean
    required: false
  revvreg:
    name: revvreg
    annotations:
      order:
        tag: order
        value: 12
      dss_default:
        tag: dss_default
        value: float(120.0)
    description: Voltage setting in volts for operation in the reverse direction.
      Default is 120 V.
    comments:
    - 'Import: derived; reverseTargetValue (V) = revvreg x ptratio; default 120. Export:
      reverseTargetValue / ptRatio.'
    from_schema: https://gridappsd.github.io/dss-graph/controls/regcontrol
    close_mappings:
    - cim:RegulatingControl.reverseTargetValue
    rank: 1000
    owner: Regcontrol
    domain_of:
    - Regcontrol
    range: float
    required: false
  revband:
    name: revband
    annotations:
      order:
        tag: order
        value: 13
      dss_default:
        tag: dss_default
        value: float(3.0)
    description: Bandwidth for operating in the reverse direction. Default is 3 V.
    comments:
    - 'Import: derived; reverseTargetDeadband (V) = revband x ptratio; default 3.
      Export: reverseTargetDeadband / ptRatio.'
    from_schema: https://gridappsd.github.io/dss-graph/controls/regcontrol
    close_mappings:
    - cim:RegulatingControl.reverseTargetDeadband
    rank: 1000
    owner: Regcontrol
    domain_of:
    - Regcontrol
    range: float
    required: false
  revR:
    name: revR
    annotations:
      order:
        tag: order
        value: 14
      dss_default:
        tag: dss_default
        value: float(0.0)
    description: R line drop compensator setting for reverse direction.
    comments:
    - 'Import: derived; reverseLineDropR (ohm) = revR x ptratio / CTprim. Export:
      reverseLineDropR x CTprim / ptRatio.'
    from_schema: https://gridappsd.github.io/dss-graph/controls/regcontrol
    close_mappings:
    - cim:TapChangerControl.reverseLineDropR
    rank: 1000
    owner: Regcontrol
    domain_of:
    - Regcontrol
    range: float
    required: false
  revX:
    name: revX
    annotations:
      order:
        tag: order
        value: 15
      dss_default:
        tag: dss_default
        value: float(0.0)
    description: X line drop compensator setting for reverse direction.
    comments:
    - 'Import: derived; reverseLineDropX (ohm) = revX x ptratio / CTprim. Export:
      reverseLineDropX x CTprim / ptRatio.'
    from_schema: https://gridappsd.github.io/dss-graph/controls/regcontrol
    close_mappings:
    - cim:TapChangerControl.reverseLineDropX
    rank: 1000
    owner: Regcontrol
    domain_of:
    - Regcontrol
    range: float
    required: false
  tapdelay:
    name: tapdelay
    annotations:
      order:
        tag: order
        value: 16
      dss_default:
        tag: dss_default
        value: float(2.0)
    description: Delay in sec between tap changes. Default is 2 s.
    comments:
    - 'Import: subsequentDelay (s); default 2. Export: subsequentDelay; unset -> not
      written.'
    from_schema: https://gridappsd.github.io/dss-graph/controls/regcontrol
    exact_mappings:
    - cim:TapChanger.subsequentDelay
    rank: 1000
    owner: Regcontrol
    domain_of:
    - Regcontrol
    range: float
    required: false
  debugtrace:
    name: debugtrace
    annotations:
      order:
        tag: order
        value: 17
    description: '{Yes | No* }  Default is no. If true, writes debug trace to file.'
    comments:
    - 'Import: untranscribed (DSS report flag). Export: unset.'
    from_schema: https://gridappsd.github.io/dss-graph/controls/regcontrol
    owner: Regcontrol
    domain_of:
    - Generator
    - Pvsystem
    - Storage
    - Windgen
    - Regcontrol
    range: boolean
    required: false
  maxtapchange:
    name: maxtapchange
    annotations:
      order:
        tag: order
        value: 18
    description: Maximum allowable tap change per control iteration in STATIC control
      mode. Default is 16.
    comments:
    - 'Import: untranscribed (DSS solution control; no home in the network profile
      parts). Export: unset.'
    from_schema: https://gridappsd.github.io/dss-graph/controls/regcontrol
    rank: 1000
    owner: Regcontrol
    domain_of:
    - Regcontrol
    range: integer
    required: false
  inversetime:
    name: inversetime
    annotations:
      order:
        tag: order
        value: 19
    description: '{Yes | No* } Default is no. If yes, time delays decrease inversely
      with magnitude of voltage excursion.'
    comments:
    - 'Import: untranscribed (DSS solution control; no home in the network profile
      parts). Export: unset.'
    from_schema: https://gridappsd.github.io/dss-graph/controls/regcontrol
    rank: 1000
    owner: Regcontrol
    domain_of:
    - Regcontrol
    range: boolean
    required: false
  tapwinding:
    name: tapwinding
    annotations:
      order:
        tag: order
        value: 20
    description: Winding containing the actual taps, if different than the WINDING
      property.
    comments:
    - 'Import: raises when set (a tap winding other than the monitored one); no deck
      in the sweep sets it, so a mapping waits for one. Export: unset.'
    from_schema: https://gridappsd.github.io/dss-graph/controls/regcontrol
    rank: 1000
    owner: Regcontrol
    domain_of:
    - Regcontrol
    range: integer
    required: false
  vlimit:
    name: vlimit
    annotations:
      order:
        tag: order
        value: 21
      dss_default:
        tag: dss_default
        value: float(0.0)
    description: Voltage Limit for bus to which regulated winding is connected. Default
      is 0 (no limit).
    todos:
    - 'Converter bug: uses tcc.limitVoltage (not a real TapChangerControl field) instead
      of tcc.maxLimitVoltage on both import and export.'
    comments:
    - 'Import: raises when set to anything but its default 0 (no limit); no deck in
      the sweep sets it, so a mapping waits for one. Export: a control with a voltage
      limit raises.'
    from_schema: https://gridappsd.github.io/dss-graph/controls/regcontrol
    close_mappings:
    - cim:TapChangerControl.maxLimitVoltage
    rank: 1000
    owner: Regcontrol
    domain_of:
    - Regcontrol
    range: float
    required: false
  PTphase:
    name: PTphase
    annotations:
      order:
        tag: order
        value: 22
      dss_default:
        tag: dss_default
        value: int(1)
    description: For multi-phase transformers, the number of the phase being monitored
      or one of {MAX | MIN} for all phases. Default is 1.
    comments:
    - 'Import: monitoredPhase = the phase of the winding''s conductor PTphase (default
      1); MAX and MIN raise. Export: the 1-based place of monitoredPhase among the
      winding''s phase conductors.'
    from_schema: https://gridappsd.github.io/dss-graph/controls/regcontrol
    close_mappings:
    - cim:RegulatingControl.monitoredPhase
    rank: 1000
    owner: Regcontrol
    domain_of:
    - Regcontrol
    range: string
    required: false
  revThreshold:
    name: revThreshold
    annotations:
      order:
        tag: order
        value: 23
      dss_default:
        tag: dss_default
        value: float(100.0)
    description: kW reverse power threshold for reversing the direction of the regulator.
      Default is 100 kW.
    comments:
    - 'Import: reversingPowerThreshold (kW); default 100. Export: reversingPowerThreshold
      (kW).'
    from_schema: https://gridappsd.github.io/dss-graph/controls/regcontrol
    exact_mappings:
    - cim:TapChangerControl.reversingPowerThreshold
    rank: 1000
    owner: Regcontrol
    domain_of:
    - Regcontrol
    range: float
    required: false
  revDelay:
    name: revDelay
    annotations:
      order:
        tag: order
        value: 24
      dss_default:
        tag: dss_default
        value: float(60.0)
    description: Time Delay in seconds for executing the reversing action once the
      threshold for reversing has been exceeded. Default is 60 s.
    comments:
    - 'Import: reversingDelay (s); default 60. Export: reversingDelay (s).'
    from_schema: https://gridappsd.github.io/dss-graph/controls/regcontrol
    exact_mappings:
    - cim:TapChangerControl.reversingDelay
    rank: 1000
    owner: Regcontrol
    domain_of:
    - Regcontrol
    range: float
    required: false
  revNeutral:
    name: revNeutral
    annotations:
      order:
        tag: order
        value: 25
      dss_default:
        tag: dss_default
        value: 'false'
    description: '{Yes | No*} Default is no. If yes, regulator goes to neutral tap
      in reverse direction.'
    comments:
    - 'Import: reverseToNeutral; default false. Export: reverseToNeutral.'
    from_schema: https://gridappsd.github.io/dss-graph/controls/regcontrol
    exact_mappings:
    - cim:TapChangerControl.reverseToNeutral
    rank: 1000
    owner: Regcontrol
    domain_of:
    - Regcontrol
    range: boolean
    required: false
  EventLog:
    name: EventLog
    annotations:
      order:
        tag: order
        value: 26
    description: '{Yes/True* | No/False} Default is YES for regulator control.'
    comments:
    - 'Import: untranscribed (DSS report flag). Export: unset.'
    from_schema: https://gridappsd.github.io/dss-graph/controls/regcontrol
    owner: Regcontrol
    domain_of:
    - Capcontrol
    - Expcontrol
    - Invcontrol
    - Regcontrol
    - Relay
    - Storagecontroller
    range: boolean
    required: false
  RemotePTRatio:
    name: RemotePTRatio
    annotations:
      order:
        tag: order
        value: 27
    description: PT ratio required to convert actual voltage at the remote bus to
      control voltage when regulating a remote bus.
    comments:
    - 'Import: raises when set (remote sensing); no deck in the sweep sets it, so
      a mapping waits for one. Export: unset.'
    from_schema: https://gridappsd.github.io/dss-graph/controls/regcontrol
    rank: 1000
    owner: Regcontrol
    domain_of:
    - Regcontrol
    range: float
    required: false
  TapNum:
    name: TapNum
    annotations:
      order:
        tag: order
        value: 28
    description: An integer number indicating the tap position that the controlled
      transformer winding tap position is currently at.
    comments:
    - 'Import: raises when set, even to 0 (a tap position that overrides the transformer''s
      tap: setting it moves the tap, so it has no default); no deck in the sweep sets
      it. Export: unset.'
    from_schema: https://gridappsd.github.io/dss-graph/controls/regcontrol
    close_mappings:
    - cim:TapChanger.step
    rank: 1000
    owner: Regcontrol
    domain_of:
    - Regcontrol
    range: integer
    required: false
  Reset:
    name: Reset
    annotations:
      order:
        tag: order
        value: 29
    description: '{Yes | No} If Yes, forces Reset of this RegControl.'
    comments:
    - 'Import: untranscribed (a command, not a setting). Export: unset.'
    from_schema: https://gridappsd.github.io/dss-graph/controls/regcontrol
    owner: Regcontrol
    domain_of:
    - Capcontrol
    - Recloser
    - Regcontrol
    - Relay
    - Swtcontrol
    range: boolean
    required: false
  LDC_Z:
    name: LDC_Z
    annotations:
      order:
        tag: order
        value: 30
      dss_default:
        tag: dss_default
        value: float(0.0)
    description: Z value for Beckwith LDC_Z control option. Complex impedance in ohms.
    comments:
    - 'Import: raises when set to anything but its default 0 (a line-drop impedance);
      no deck in the sweep sets it, so a mapping waits for one. Export: unset.'
    from_schema: https://gridappsd.github.io/dss-graph/controls/regcontrol
    rank: 1000
    owner: Regcontrol
    domain_of:
    - Regcontrol
    range: float
    required: false
  rev_Z:
    name: rev_Z
    annotations:
      order:
        tag: order
        value: 31
      dss_default:
        tag: dss_default
        value: float(0.0)
    description: Reverse Z value for Beckwith LDC_Z control option.
    comments:
    - 'Import: raises when set to anything but its default 0 (a reverse line-drop
      impedance); no deck in the sweep sets it, so a mapping waits for one. Export:
      unset.'
    from_schema: https://gridappsd.github.io/dss-graph/controls/regcontrol
    rank: 1000
    owner: Regcontrol
    domain_of:
    - Regcontrol
    range: float
    required: false
  Cogen:
    name: Cogen
    annotations:
      order:
        tag: order
        value: 32
      dss_default:
        tag: dss_default
        value: 'false'
    description: '{Yes|No*} Default is No. Cogen mode — sets direction of power flow
      sensing for reverse operation.'
    comments:
    - 'Import: raises when set to anything but its default No (cogeneration); no deck
      in the sweep sets it, so a mapping waits for one. Export: unset.'
    from_schema: https://gridappsd.github.io/dss-graph/controls/regcontrol
    rank: 1000
    owner: Regcontrol
    domain_of:
    - Regcontrol
    range: boolean
    required: false
  idle:
    name: idle
    annotations:
      order:
        tag: order
        value: 33
    description: '{Yes|No*} Default is No. If Yes, disables tap changing.'
    comments:
    - 'Import: raises when set (idle mode); no deck in the sweep sets it, so a mapping
      waits for one. Export: unset.'
    from_schema: https://gridappsd.github.io/dss-graph/controls/regcontrol
    rank: 1000
    owner: Regcontrol
    domain_of:
    - Regcontrol
    range: boolean
    required: false
  idleReverse:
    name: idleReverse
    annotations:
      order:
        tag: order
        value: 34
    description: '{Yes|No*} Default is No. If Yes, disables tap changing in reverse
      mode.'
    comments:
    - 'Import: raises when set (idle mode); no deck in the sweep sets it, so a mapping
      waits for one. Export: unset.'
    from_schema: https://gridappsd.github.io/dss-graph/controls/regcontrol
    rank: 1000
    owner: Regcontrol
    domain_of:
    - Regcontrol
    range: boolean
    required: false
  idleForward:
    name: idleForward
    annotations:
      order:
        tag: order
        value: 35
    description: '{Yes|No*} Default is No. If Yes, disables tap changing in forward
      mode.'
    comments:
    - 'Import: raises when set (idle mode); no deck in the sweep sets it, so a mapping
      waits for one. Export: unset.'
    from_schema: https://gridappsd.github.io/dss-graph/controls/regcontrol
    rank: 1000
    owner: Regcontrol
    domain_of:
    - Regcontrol
    range: boolean
    required: false
  basefreq:
    name: basefreq
    annotations:
      order:
        tag: order
        value: 36
    description: Base Frequency for ratings.
    comments:
    - 'Import: untranscribed (no home on a control). Export: unset.'
    from_schema: https://gridappsd.github.io/dss-graph/controls/regcontrol
    owner: Regcontrol
    domain_of:
    - Load
    - Generator
    - Generic5
    - Gicline
    - Indmach012
    - Pvsystem
    - Storage
    - Upfc
    - Vccs
    - Vsconverter
    - Windgen
    - Autotrans
    - Capacitor
    - Gictransformer
    - Line
    - Reactor
    - Transformer
    - Capcontrol
    - Espvlcontrol
    - Expcontrol
    - Fuse
    - Gendispatcher
    - Invcontrol
    - Pycontrol
    - Recloser
    - Regcontrol
    - Relay
    - Storagecontroller
    - Swtcontrol
    - Upfccontrol
    - Energymeter
    - Fmonitor
    - Monitor
    - Sensor
    - Fault
    - Gicsource
    - Isource
    - Vsource
    range: float
    required: false
  enabled:
    name: enabled
    annotations:
      order:
        tag: order
        value: 37
      dss_default:
        tag: dss_default
        value: 'true'
    description: '{Yes|No or True|False} Indicates whether this element is enabled.'
    comments:
    - 'Import: the control''s enabled and the tap''s controlEnabled; default true.
      Export: the control''s enabled; the tap''s must agree.'
    from_schema: https://gridappsd.github.io/dss-graph/controls/regcontrol
    exact_mappings:
    - cim:RegulatingControl.enabled
    - cim:TapChanger.controlEnabled
    owner: Regcontrol
    domain_of:
    - Load
    - Generator
    - Generic5
    - Gicline
    - Indmach012
    - Pvsystem
    - Storage
    - Upfc
    - Vccs
    - Vsconverter
    - Windgen
    - Autotrans
    - Capacitor
    - Gictransformer
    - Line
    - Reactor
    - Transformer
    - Capcontrol
    - Espvlcontrol
    - Expcontrol
    - Fuse
    - Gendispatcher
    - Invcontrol
    - Pycontrol
    - Recloser
    - Regcontrol
    - Relay
    - Storagecontroller
    - Swtcontrol
    - Upfccontrol
    - Energymeter
    - Fmonitor
    - Monitor
    - Sensor
    - Fault
    - Gicsource
    - Isource
    - Vsource
    range: boolean
    required: false
  like:
    name: like
    annotations:
      order:
        tag: order
        value: 38
    description: 'Make like another object, e.g.: New Regcontrol.RC2 like=RC1 ...'
    comments:
    - 'Import: untranscribed; the reader resolves like= before mapping. Export: never
      written.'
    from_schema: https://gridappsd.github.io/dss-graph/controls/regcontrol
    owner: Regcontrol
    domain_of:
    - Load
    - Generator
    - Generic5
    - Gicline
    - Indmach012
    - Pvsystem
    - Storage
    - Upfc
    - Vccs
    - Vsconverter
    - Windgen
    - Autotrans
    - Capacitor
    - Gictransformer
    - Line
    - Reactor
    - Transformer
    - Capcontrol
    - Espvlcontrol
    - Expcontrol
    - Fuse
    - Gendispatcher
    - Invcontrol
    - Pycontrol
    - Recloser
    - Regcontrol
    - Relay
    - Storagecontroller
    - Swtcontrol
    - Upfccontrol
    - Cndata
    - Dynamicexp
    - Growthshape
    - Linecode
    - Linegeometry
    - Linespacing
    - Loadshape
    - Priceshape
    - Spectrum
    - TccCurve
    - Tsdata
    - Tshape
    - Wiredata
    - Xfmrcode
    - Xycurve
    - Energymeter
    - Fmonitor
    - Monitor
    - Sensor
    - Fault
    - Gicsource
    - Isource
    - Vsource
    range: string
    required: false
class_uri: dss:Regcontrol