Class: PowerflowObject

Copyright (C) 2008 Battelle Memorial Institute

@file powerflow_object.cpp

@addtogroup powerflow_object Powerflow objects (abstract)

@ingroup powerflow

The powerflow_object class is an abstract class that implements

basic elements of powerflow solutions. There are two critical

pieces of information:

-# @p phases indicates the phases which are connected by this object.

This may be any feasible combination of the phase flags

- @p PHASE_A for phase A connections

- @p PHASE_B for phase B connections

- @p PHASE_C for phase C connections

- @p PHASE_N for neutral connections

- @p PHASE_D for delta connections (implies A, B, C);

- @p PHASE_A for split connections (requires one of A, B, or C);

- @p PHASE_ABC for three phase connections

- @p PHASE_ABCN for three phase connections with separate

neutral

-# @p reference_bus indicates the bus for the reference frequency and

voltage at which the solution is to be computed. The current solution method

does not change the frequency nor does it consider the frequency in the

powerflow calculated. The parameter is only to be used to adjust

frequency-sensitive loads, such as Grid-FriendlyTM devices.

In addition, each powerflow_object defined must specify what it's parent

object is for the purposes of establishing the evaluation order through the

ranks. The reference bus is also propagated using the rank order.

The powerflow_object provides optional support for outage conditions

when compiled with the SUPPORT_OUTAGES flag is defined in powerflow_object.h.

When enabled the following parameters are also defined

-# @p condition indicates the device's operating condition with respect

to abnormal phase configuration that would require special

consideration during the powerflow solution. This can be any combination of

two of the following

- @p OC_NORMAL for no abnormal configuration (excludes all

others)

- @p OC_PHASE_A_CONTACT phase A in contact

- @p OC_PHASE_B_CONTACT phase B in contact

- @p OC_PHASE_C_CONTACT phase C in contact

- @p OC_NEUTRAL_CONTACT neutral in contact

- @p OC_SPLIT_1_CONTACT split line 1 in contact

- @p OC_SPLIT_2_CONTACT split line 2 in contact

- @p OC_SPLIT_N_CONTACT split line N in contact

- @p OC_GROUND_CONTACT ground in contact

- @p OC_PHASE_A_OPEN phase A is open

- @p OC_PHASE_B_OPEN phase B is open

- @p OC_PHASE_C_OPEN phase C is open

- @p OC_NEUTRAL_OPEN neutral is open

- @p OC_SPLIT_1_OPEN split line 1 is open

- @p OC_SPLIT_2_OPEN split line 2 is open

- @p OC_SPLIT_N_OPEN split neutral is open

- @p OC_GROUND_OPEN ground connection is open

-# @p solution indicates whether special solution methods are required.

The base powerflow_object only recognized the normal solution method

(#PS_NORMAL), but each object may add its own identifiers, so long as it does

not conflict any identifiers in the object inheritance hierarchy. When

#SUPPORT_OUTAGES is defined, the flag #PS_OUTAGE is also defined and can be

used to engage an alternate solution method.

@par Outage support

When SUPPORT_OUTAGES is defined, the @p postsync pass will

examine whether

@p condition and @p solution are matched. If there is an inconsistency

(i.e., @p condition != OC_NORMAL && @p solution ==

PS_NORMAL or

@p condition == OC_NORMAL && @p solution !=

PS_NORMAL), then they will be reconciled and the solver will iterate

again. Object derived from powerflow_object can inspect the value of @p

condition to determine whether they can use the normal powerflow solution

method, or an alternative method that is appropriate for abnormal conditions.

Be aware that this may result in a change of state in some other object

that may cause the solver to reiterate. It is highly recommended that

state changes to OC_NORMAL have a non-zero delay built in (i.e., allow the

clock to advanced). Failure to do so may result in non-convergence

of the solver.

@{

__

Inherits from: gld_object

__

Type: Instance (network topology element)

__

Note: Inherits from gld_object (not in powerflow module)

URI: glm:PowerflowObject

 classDiagram
    class PowerflowObject
    click PowerflowObject href "../PowerflowObject/"
      GlmObject <|-- PowerflowObject
        click GlmObject href "../GlmObject/"


      PowerflowObject <|-- Emissions
        click Emissions href "../Emissions/"
      PowerflowObject <|-- FaultCheck
        click FaultCheck href "../FaultCheck/"
      PowerflowObject <|-- Link
        click Link href "../Link/"
      PowerflowObject <|-- Node
        click Node href "../Node/"
      PowerflowObject <|-- SyncCheck
        click SyncCheck href "../SyncCheck/"
      PowerflowObject <|-- TriplexNode
        click TriplexNode href "../TriplexNode/"
      PowerflowObject <|-- VoltVarControl
        click VoltVarControl href "../VoltVarControl/"


      PowerflowObject : condition

      PowerflowObject : flags

      PowerflowObject : groupid

      PowerflowObject : in_svc

      PowerflowObject : inrush_integration_method

      PowerflowObject : latitude

      PowerflowObject : longitude

      PowerflowObject : name

      PowerflowObject : nominal_voltage

      PowerflowObject : out_svc

      PowerflowObject : parent

      PowerflowObject : phases

      PowerflowObject : rank

      PowerflowObject : solution

Inheritance

Slots

Name Cardinality and Range Description Inheritance
phases 0..1
String
direct
nominal_voltage 0..1
Float
direct
inrush_integration_method 0..1
String
Integration method for in-rush direct
condition 0..1
String
direct
solution 0..1
String
direct
name 1
String
The object's name; unique across the model GlmObject
parent 0..1
String
The parent object's name GlmObject
groupid 0..1
String
Free-text group label GlmObject
latitude 0..1
String
Latitude, as written (decimal degrees or GridLAB-D's 37N26:12 form) GlmObject
longitude 0..1
String
Longitude, as written GlmObject
in_svc 0..1
String
Timestamp the object enters service GlmObject
out_svc 0..1
String
Timestamp the object leaves service GlmObject
rank 0..1
String
Solver rank GlmObject
flags 0..1
String
Core object flags GlmObject

Identifier and Mapping Information

Schema Source

  • from schema: https://gridlabd.org/schema/glm

Mappings

Mapping Type Mapped Value
self glm:PowerflowObject
native glm:PowerflowObject

LinkML Source

Direct

name: powerflow_object
description: "Copyright (C) 2008 Battelle Memorial Institute\n@file powerflow_object.cpp\n\
  @addtogroup powerflow_object Powerflow objects (abstract)\n@ingroup powerflow\n\
  The powerflow_object class is an abstract class that implements\nbasic elements\
  \ of powerflow solutions.  There are two critical\npieces of information:\n-# @p\
  \ phases indicates the phases which are connected by this object.\nThis may be any\
  \ feasible combination of the phase flags\n- @p PHASE_A for phase A connections\n\
  - @p PHASE_B for phase B connections\n- @p PHASE_C for phase C connections\n- @p\
  \ PHASE_N for neutral connections\n- @p PHASE_D for delta connections (implies A,\
  \ B, C);\n- @p PHASE_A for split connections (requires one of A, B, or C);\n- @p\
  \ PHASE_ABC for three phase connections\n- @p PHASE_ABCN for three phase connections\
  \ with separate\nneutral\n-# @p reference_bus indicates the bus for the reference\
  \ frequency and\nvoltage at which the solution is to be computed.  The current solution\
  \ method\ndoes not change the frequency nor does it consider the frequency in the\n\
  powerflow calculated.  The parameter is only to be used to adjust\nfrequency-sensitive\
  \ loads, such as Grid-Friendly<sup>TM</sup> devices.\nIn addition, each powerflow_object\
  \ defined must specify what it's parent\nobject is for the purposes of establishing\
  \ the evaluation order through the\nranks. The reference bus is also propagated\
  \ using the rank order.\nThe powerflow_object provides optional support for outage\
  \ conditions\nwhen compiled with the SUPPORT_OUTAGES flag is defined in powerflow_object.h.\n\
  When enabled the following parameters are also defined\n-# @p condition indicates\
  \ the device's operating condition with respect\nto abnormal phase configuration\
  \ that would require special\nconsideration during the powerflow solution.  This\
  \ can be any combination of\ntwo of the following\n- @p OC_NORMAL for no abnormal\
  \ configuration (excludes all\nothers)\n- @p OC_PHASE_A_CONTACT phase A in contact\n\
  - @p OC_PHASE_B_CONTACT phase B in contact\n- @p OC_PHASE_C_CONTACT phase C in contact\n\
  - @p OC_NEUTRAL_CONTACT neutral in contact\n- @p OC_SPLIT_1_CONTACT split line 1\
  \ in contact\n- @p OC_SPLIT_2_CONTACT split line 2 in contact\n- @p OC_SPLIT_N_CONTACT\
  \ split line N in contact\n- @p OC_GROUND_CONTACT ground in contact\n- @p OC_PHASE_A_OPEN\
  \ phase A is open\n- @p OC_PHASE_B_OPEN phase B is open\n- @p OC_PHASE_C_OPEN phase\
  \ C is open\n- @p OC_NEUTRAL_OPEN neutral is open\n- @p OC_SPLIT_1_OPEN split line\
  \ 1 is open\n- @p OC_SPLIT_2_OPEN split line 2 is open\n- @p OC_SPLIT_N_OPEN split\
  \ neutral is open\n- @p OC_GROUND_OPEN ground connection is open\n-# @p solution\
  \ indicates whether special solution methods are required.\nThe base powerflow_object\
  \ only recognized the normal solution method\n(#PS_NORMAL), but each object may\
  \ add its own identifiers, so long as it does\nnot conflict any identifiers in the\
  \ object inheritance hierarchy.  When\n#SUPPORT_OUTAGES is defined, the flag #PS_OUTAGE\
  \ is also defined and can be\nused to engage an alternate solution method.\n@par\
  \ Outage support\nWhen <code>SUPPORT_OUTAGES</code> is defined, the @p postsync\
  \ pass will\nexamine whether\n@p condition and @p solution are matched.  If there\
  \ is an inconsistency\n(i.e., @p <code>condition != OC_NORMAL &&</code> @p <code>solution\
  \ ==\nPS_NORMAL</code> or\n@p <code>condition == OC_NORMAL &&</code> @p <code>solution\
  \ !=\nPS_NORMAL</code>), then they will be reconciled and the solver will iterate\n\
  again. Object derived from powerflow_object can inspect the value of @p\ncondition\
  \ to determine whether they can use the normal powerflow solution\nmethod, or an\
  \ alternative method that is appropriate for abnormal conditions.\nBe aware that\
  \ this may result in a change of state in some other object\nthat may cause the\
  \ solver to reiterate. It is highly recommended that\nstate changes to OC_NORMAL\
  \ have a non-zero delay built in (i.e., allow the\nclock to advanced).\tFailure\
  \ to do so may result in non-convergence\nof the solver.\n@{\n\nInherits from: gld_object\n\
  \nType: Instance (network topology element)\n\nNote: Inherits from gld_object (not\
  \ in powerflow module)"
from_schema: https://gridlabd.org/schema/glm
is_a: glm_object
attributes:
  phases:
    name: phases
    annotations:
      order:
        tag: order
        value: 1
      value_type:
        tag: value_type
        value: string
      native_name:
        tag: native_name
        value: phases
    comments:
    - 'Import: structural. Bus: a child''s conductors must be a subset of its root''s.
      Switch: Terminal phases, A B C with N dropped, blank when ABC. Series_reactor:
      Terminal.phases when fewer than three. Swing bus: EnergySource.phases, blank
      when ABC. Export: the A, B, C of the terminals on the bus, then N (S on a split-phase
      bus); a switch or reactor side 1''s A, B, C.'
    from_schema: https://gridlabd.org/schema/glm/powerflow/powerflow_object
    related_mappings:
    - cim:Terminal.phases
    rank: 1000
    domain_of:
    - powerflow_object
    - inverter
    - rectifier
    - windturb_dg
    range: string
    required: false
  nominal_voltage:
    name: nominal_voltage
    annotations:
      order:
        tag: order
        value: 2
      value_type:
        tag: value_type
        value: float
      precision:
        tag: precision
        value: 6
      native_name:
        tag: native_name
        value: nominal_voltage[V]
    comments:
    - 'Import: not copied; the topology walk gives the BaseVoltage, and a bus value
      over 10 percent off it is listed in bus.cimtbl. On a swing bus: EnergySource.nominalVoltage
      (V as written), line to line. Export: BaseVoltage LL / sqrt 3 (three phase),
      LL (single phase), LL / 2 (split phase leg); a substation: EnergySource.nominalVoltage
      / sqrt 3.'
    from_schema: https://gridlabd.org/schema/glm/powerflow/powerflow_object
    close_mappings:
    - cim:BaseVoltage.nominalVoltage
    - cim:EnergySource.nominalVoltage
    rank: 1000
    domain_of:
    - powerflow_object
    - battery
    - waterheater
    range: float
    required: false
    unit:
      ucum_code: V
  inrush_integration_method:
    name: inrush_integration_method
    annotations:
      order:
        tag: order
        value: 3
      value_type:
        tag: value_type
        value: string
      native_name:
        tag: native_name
        value: inrush_integration_method
    description: Integration method for in-rush
    from_schema: https://gridlabd.org/schema/glm/powerflow/powerflow_object
    rank: 1000
    domain_of:
    - powerflow_object
    range: string
    required: false
  condition:
    name: condition
    annotations:
      order:
        tag: order
        value: 4
      value_type:
        tag: value_type
        value: string
      native_name:
        tag: native_name
        value: condition
    from_schema: https://gridlabd.org/schema/glm/powerflow/powerflow_object
    rank: 1000
    domain_of:
    - powerflow_object
    range: string
    required: false
  solution:
    name: solution
    annotations:
      order:
        tag: order
        value: 5
      value_type:
        tag: value_type
        value: string
      native_name:
        tag: native_name
        value: solution
    from_schema: https://gridlabd.org/schema/glm/powerflow/powerflow_object
    rank: 1000
    domain_of:
    - powerflow_object
    range: string
    required: false

Induced

name: powerflow_object
description: "Copyright (C) 2008 Battelle Memorial Institute\n@file powerflow_object.cpp\n\
  @addtogroup powerflow_object Powerflow objects (abstract)\n@ingroup powerflow\n\
  The powerflow_object class is an abstract class that implements\nbasic elements\
  \ of powerflow solutions.  There are two critical\npieces of information:\n-# @p\
  \ phases indicates the phases which are connected by this object.\nThis may be any\
  \ feasible combination of the phase flags\n- @p PHASE_A for phase A connections\n\
  - @p PHASE_B for phase B connections\n- @p PHASE_C for phase C connections\n- @p\
  \ PHASE_N for neutral connections\n- @p PHASE_D for delta connections (implies A,\
  \ B, C);\n- @p PHASE_A for split connections (requires one of A, B, or C);\n- @p\
  \ PHASE_ABC for three phase connections\n- @p PHASE_ABCN for three phase connections\
  \ with separate\nneutral\n-# @p reference_bus indicates the bus for the reference\
  \ frequency and\nvoltage at which the solution is to be computed.  The current solution\
  \ method\ndoes not change the frequency nor does it consider the frequency in the\n\
  powerflow calculated.  The parameter is only to be used to adjust\nfrequency-sensitive\
  \ loads, such as Grid-Friendly<sup>TM</sup> devices.\nIn addition, each powerflow_object\
  \ defined must specify what it's parent\nobject is for the purposes of establishing\
  \ the evaluation order through the\nranks. The reference bus is also propagated\
  \ using the rank order.\nThe powerflow_object provides optional support for outage\
  \ conditions\nwhen compiled with the SUPPORT_OUTAGES flag is defined in powerflow_object.h.\n\
  When enabled the following parameters are also defined\n-# @p condition indicates\
  \ the device's operating condition with respect\nto abnormal phase configuration\
  \ that would require special\nconsideration during the powerflow solution.  This\
  \ can be any combination of\ntwo of the following\n- @p OC_NORMAL for no abnormal\
  \ configuration (excludes all\nothers)\n- @p OC_PHASE_A_CONTACT phase A in contact\n\
  - @p OC_PHASE_B_CONTACT phase B in contact\n- @p OC_PHASE_C_CONTACT phase C in contact\n\
  - @p OC_NEUTRAL_CONTACT neutral in contact\n- @p OC_SPLIT_1_CONTACT split line 1\
  \ in contact\n- @p OC_SPLIT_2_CONTACT split line 2 in contact\n- @p OC_SPLIT_N_CONTACT\
  \ split line N in contact\n- @p OC_GROUND_CONTACT ground in contact\n- @p OC_PHASE_A_OPEN\
  \ phase A is open\n- @p OC_PHASE_B_OPEN phase B is open\n- @p OC_PHASE_C_OPEN phase\
  \ C is open\n- @p OC_NEUTRAL_OPEN neutral is open\n- @p OC_SPLIT_1_OPEN split line\
  \ 1 is open\n- @p OC_SPLIT_2_OPEN split line 2 is open\n- @p OC_SPLIT_N_OPEN split\
  \ neutral is open\n- @p OC_GROUND_OPEN ground connection is open\n-# @p solution\
  \ indicates whether special solution methods are required.\nThe base powerflow_object\
  \ only recognized the normal solution method\n(#PS_NORMAL), but each object may\
  \ add its own identifiers, so long as it does\nnot conflict any identifiers in the\
  \ object inheritance hierarchy.  When\n#SUPPORT_OUTAGES is defined, the flag #PS_OUTAGE\
  \ is also defined and can be\nused to engage an alternate solution method.\n@par\
  \ Outage support\nWhen <code>SUPPORT_OUTAGES</code> is defined, the @p postsync\
  \ pass will\nexamine whether\n@p condition and @p solution are matched.  If there\
  \ is an inconsistency\n(i.e., @p <code>condition != OC_NORMAL &&</code> @p <code>solution\
  \ ==\nPS_NORMAL</code> or\n@p <code>condition == OC_NORMAL &&</code> @p <code>solution\
  \ !=\nPS_NORMAL</code>), then they will be reconciled and the solver will iterate\n\
  again. Object derived from powerflow_object can inspect the value of @p\ncondition\
  \ to determine whether they can use the normal powerflow solution\nmethod, or an\
  \ alternative method that is appropriate for abnormal conditions.\nBe aware that\
  \ this may result in a change of state in some other object\nthat may cause the\
  \ solver to reiterate. It is highly recommended that\nstate changes to OC_NORMAL\
  \ have a non-zero delay built in (i.e., allow the\nclock to advanced).\tFailure\
  \ to do so may result in non-convergence\nof the solver.\n@{\n\nInherits from: gld_object\n\
  \nType: Instance (network topology element)\n\nNote: Inherits from gld_object (not\
  \ in powerflow module)"
from_schema: https://gridlabd.org/schema/glm
is_a: glm_object
attributes:
  phases:
    name: phases
    annotations:
      order:
        tag: order
        value: 1
      value_type:
        tag: value_type
        value: string
      native_name:
        tag: native_name
        value: phases
    comments:
    - 'Import: structural. Bus: a child''s conductors must be a subset of its root''s.
      Switch: Terminal phases, A B C with N dropped, blank when ABC. Series_reactor:
      Terminal.phases when fewer than three. Swing bus: EnergySource.phases, blank
      when ABC. Export: the A, B, C of the terminals on the bus, then N (S on a split-phase
      bus); a switch or reactor side 1''s A, B, C.'
    from_schema: https://gridlabd.org/schema/glm/powerflow/powerflow_object
    related_mappings:
    - cim:Terminal.phases
    rank: 1000
    owner: powerflow_object
    domain_of:
    - powerflow_object
    - inverter
    - rectifier
    - windturb_dg
    range: string
    required: false
  nominal_voltage:
    name: nominal_voltage
    annotations:
      order:
        tag: order
        value: 2
      value_type:
        tag: value_type
        value: float
      precision:
        tag: precision
        value: 6
      native_name:
        tag: native_name
        value: nominal_voltage[V]
    comments:
    - 'Import: not copied; the topology walk gives the BaseVoltage, and a bus value
      over 10 percent off it is listed in bus.cimtbl. On a swing bus: EnergySource.nominalVoltage
      (V as written), line to line. Export: BaseVoltage LL / sqrt 3 (three phase),
      LL (single phase), LL / 2 (split phase leg); a substation: EnergySource.nominalVoltage
      / sqrt 3.'
    from_schema: https://gridlabd.org/schema/glm/powerflow/powerflow_object
    close_mappings:
    - cim:BaseVoltage.nominalVoltage
    - cim:EnergySource.nominalVoltage
    rank: 1000
    owner: powerflow_object
    domain_of:
    - powerflow_object
    - battery
    - waterheater
    range: float
    required: false
    unit:
      ucum_code: V
  inrush_integration_method:
    name: inrush_integration_method
    annotations:
      order:
        tag: order
        value: 3
      value_type:
        tag: value_type
        value: string
      native_name:
        tag: native_name
        value: inrush_integration_method
    description: Integration method for in-rush
    from_schema: https://gridlabd.org/schema/glm/powerflow/powerflow_object
    rank: 1000
    owner: powerflow_object
    domain_of:
    - powerflow_object
    range: string
    required: false
  condition:
    name: condition
    annotations:
      order:
        tag: order
        value: 4
      value_type:
        tag: value_type
        value: string
      native_name:
        tag: native_name
        value: condition
    from_schema: https://gridlabd.org/schema/glm/powerflow/powerflow_object
    rank: 1000
    owner: powerflow_object
    domain_of:
    - powerflow_object
    range: string
    required: false
  solution:
    name: solution
    annotations:
      order:
        tag: order
        value: 5
      value_type:
        tag: value_type
        value: string
      native_name:
        tag: native_name
        value: solution
    from_schema: https://gridlabd.org/schema/glm/powerflow/powerflow_object
    rank: 1000
    owner: powerflow_object
    domain_of:
    - powerflow_object
    range: string
    required: false
  name:
    name: name
    annotations:
      order:
        tag: order
        value: 0
      value_type:
        tag: value_type
        value: string
      native_name:
        tag: native_name
        value: name
    description: The object's name; unique across the model.
    comments:
    - 'Import: <CIM class>.name, copied as written; mRID = the class''s prefix + name
      (none on a bus). Export: Names, sanitized for GridLAB-D; a name two objects
      share raises.'
    from_schema: https://gridlabd.org/schema/glm/types/common
    exact_mappings:
    - cim:IdentifiedObject.name
    rank: 1000
    identifier: true
    owner: powerflow_object
    domain_of:
    - glm_object
    range: string
    required: true
  parent:
    name: parent
    annotations:
      order:
        tag: order
        value: 0
      value_type:
        tag: value_type
        value: string
      native_name:
        tag: native_name
        value: parent
    description: The parent object's name. A child node is solved as its parent's
      bus; a nested object block sets it to the enclosing object.
    comments:
    - 'Import: a bus whose parent is a bus is its root bus''s ConnectivityNode, named
      on the root''s row; no object of its own. On a link it is not mapped.'
    from_schema: https://gridlabd.org/schema/glm/types/common
    rank: 1000
    owner: powerflow_object
    domain_of:
    - glm_object
    range: string
  groupid:
    name: groupid
    annotations:
      order:
        tag: order
        value: 0
      value_type:
        tag: value_type
        value: string
      native_name:
        tag: native_name
        value: groupid
    description: Free-text group label.
    from_schema: https://gridlabd.org/schema/glm/types/common
    rank: 1000
    owner: powerflow_object
    domain_of:
    - glm_object
    range: string
  latitude:
    name: latitude
    annotations:
      order:
        tag: order
        value: 0
      value_type:
        tag: value_type
        value: string
      native_name:
        tag: native_name
        value: latitude
    description: Latitude, as written (decimal degrees or GridLAB-D's 37N26:12 form).
    comments:
    - Not converted. Home is the EquipmentLocation shape.
    from_schema: https://gridlabd.org/schema/glm/types/common
    rank: 1000
    owner: powerflow_object
    domain_of:
    - glm_object
    range: string
  longitude:
    name: longitude
    annotations:
      order:
        tag: order
        value: 0
      value_type:
        tag: value_type
        value: string
      native_name:
        tag: native_name
        value: longitude
    description: Longitude, as written.
    comments:
    - Not converted. Home is the EquipmentLocation shape.
    from_schema: https://gridlabd.org/schema/glm/types/common
    rank: 1000
    owner: powerflow_object
    domain_of:
    - glm_object
    range: string
  in_svc:
    name: in_svc
    annotations:
      order:
        tag: order
        value: 0
      value_type:
        tag: value_type
        value: string
      native_name:
        tag: native_name
        value: in_svc
    description: Timestamp the object enters service.
    from_schema: https://gridlabd.org/schema/glm/types/common
    rank: 1000
    owner: powerflow_object
    domain_of:
    - glm_object
    range: string
  out_svc:
    name: out_svc
    annotations:
      order:
        tag: order
        value: 0
      value_type:
        tag: value_type
        value: string
      native_name:
        tag: native_name
        value: out_svc
    description: Timestamp the object leaves service.
    from_schema: https://gridlabd.org/schema/glm/types/common
    rank: 1000
    owner: powerflow_object
    domain_of:
    - glm_object
    range: string
  rank:
    name: rank
    annotations:
      order:
        tag: order
        value: 0
      value_type:
        tag: value_type
        value: string
      native_name:
        tag: native_name
        value: rank
    description: Solver rank.
    from_schema: https://gridlabd.org/schema/glm/types/common
    rank: 1000
    owner: powerflow_object
    domain_of:
    - glm_object
    range: string
  flags:
    name: flags
    annotations:
      order:
        tag: order
        value: 0
      value_type:
        tag: value_type
        value: string
      native_name:
        tag: native_name
        value: flags
    description: Core object flags.
    from_schema: https://gridlabd.org/schema/glm/types/common
    rank: 1000
    owner: powerflow_object
    domain_of:
    - glm_object
    range: string