Class: Node

Copyright (C) 2008 Battelle Memorial Institute

@file node.cpp

@addtogroup powerflow_node Node

@ingroup powerflow_object

The node is one of the major components of the method used for solving a

powerflow network. In essense the distribution network can be seen as a

series of nodes and links. Nodes primary responsibility is to act as an

aggregation point for the links that are attached to it, and to hold the

current and voltage values that will be used in the matrix calculations

done in the link.

Three types of nodes are defined in this file. Nodes are simply a basic

object that exports the voltages for each phase. Triplex nodes export

voltages for 3 lines; line1_voltage, line2_voltage, lineN_voltage.

@par Voltage control

When the global variable require_voltage_control is set to @p true,

the bus type is used to determine how voltage control is implemented.

Voltage control is only performed when the bus has no link that

considers it a to node. When the flag #NF_HASSOURCE is cleared, then

the following is in effect:

- #SWING buses are considered infinite sources and the voltage will

remain fixed regardless of conditions.

- #PV buses are considered constrained sources and the voltage will

fall to zero if there is insufficient voltage support at the bus.

A generator object is required to provide the voltage support explicitly.

The voltage will be set to zero if the generator does not provide

sufficient support.

- #PQ buses will always go to zero voltage.

@par Fault support

The following conditions are used to describe a fault impedance @e X (e.g., 1e-6),

between phase @e x and neutral or group, or between phases @e x and @e y, and leaving

phase @e z unaffected at iteration @e t:

- @e phase-to-phase contact at the node

- @e Forward-sweep: @f$ V_x(t) = V_y(t) = @frac{V_x(t-1) + V_y(t-1)}{2} @f$

- @e Back-sweep: @f$ I_x(t+1) = -I_y(t+1) = @frac{V_x(t)-V_y(t)}{X} @f$;

- @e phase-to-ground/neutral contact at the node

- @e Forward-sweep: @f$ V_x(t) = @frac{1}{2} V_x(t-1) @f$

- @e Back-sweep: @f$ I_x(t+1) = @frac{V_x(t)}{X} @f$;

@{

__

Inherits from: powerflow_object

__

Type: Instance (network topology element)

URI: glm:Node

 classDiagram
    class Node
    click Node href "../Node/"
      PowerflowObject <|-- Node
        click PowerflowObject href "../PowerflowObject/"


      Node <|-- Capacitor
        click Capacitor href "../Capacitor/"
      Node <|-- Load
        click Load href "../Load/"
      Node <|-- Meter
        click Meter href "../Meter/"
      Node <|-- Motor
        click Motor href "../Motor/"
      Node <|-- PerformanceMotor
        click PerformanceMotor href "../PerformanceMotor/"
      Node <|-- Substation
        click Substation href "../Substation/"


      Node : behaving_as_swing

      Node : busflags

      Node : bustype

      Node : condition

      Node : current_A





        Node --> "0..1" Complex : current_A
        click Complex href "../Complex/"



      Node : current_AB





        Node --> "0..1" Complex : current_AB
        click Complex href "../Complex/"



      Node : current_AN





        Node --> "0..1" Complex : current_AN
        click Complex href "../Complex/"



      Node : current_B





        Node --> "0..1" Complex : current_B
        click Complex href "../Complex/"



      Node : current_BC





        Node --> "0..1" Complex : current_BC
        click Complex href "../Complex/"



      Node : current_BN





        Node --> "0..1" Complex : current_BN
        click Complex href "../Complex/"



      Node : current_C





        Node --> "0..1" Complex : current_C
        click Complex href "../Complex/"



      Node : current_CA





        Node --> "0..1" Complex : current_CA
        click Complex href "../Complex/"



      Node : current_CN





        Node --> "0..1" Complex : current_CN
        click Complex href "../Complex/"



      Node : current_inj_A





        Node --> "0..1" Complex : current_inj_A
        click Complex href "../Complex/"



      Node : current_inj_B





        Node --> "0..1" Complex : current_inj_B
        click Complex href "../Complex/"



      Node : current_inj_C





        Node --> "0..1" Complex : current_inj_C
        click Complex href "../Complex/"



      Node : current_uptime

      Node : deltamode_full_Y_all_matrix

      Node : deltamode_full_Y_matrix

      Node : deltamode_generator_current_A





        Node --> "0..1" Complex : deltamode_generator_current_A
        click Complex href "../Complex/"



      Node : deltamode_generator_current_B





        Node --> "0..1" Complex : deltamode_generator_current_B
        click Complex href "../Complex/"



      Node : deltamode_generator_current_C





        Node --> "0..1" Complex : deltamode_generator_current_C
        click Complex href "../Complex/"



      Node : deltamode_PGenTotal





        Node --> "0..1" Complex : deltamode_PGenTotal
        click Complex href "../Complex/"



      Node : flags

      Node : frequency_measure_type

      Node : generator_dynamic

      Node : GFA_enable

      Node : GFA_freq_disconnect_time

      Node : GFA_freq_high_trip

      Node : GFA_freq_low_trip

      Node : GFA_reconnect_time

      Node : GFA_status

      Node : GFA_trip_method

      Node : GFA_volt_disconnect_time

      Node : GFA_volt_high_trip

      Node : GFA_volt_low_trip

      Node : groupid

      Node : house_present

      Node : in_svc

      Node : inrush_integration_method

      Node : latitude

      Node : longitude

      Node : maximum_voltage_error

      Node : mean_repair_time

      Node : measured_angle_A

      Node : measured_angle_B

      Node : measured_angle_C

      Node : measured_frequency

      Node : measured_frequency_A

      Node : measured_frequency_B

      Node : measured_frequency_C

      Node : name

      Node : nominal_voltage

      Node : Norton_dynamic

      Node : Norton_dynamic_child

      Node : NR_powerflow_parent

      Node : out_svc

      Node : parent

      Node : phases

      Node : pll_Ki

      Node : pll_Kp

      Node : power_A





        Node --> "0..1" Complex : power_A
        click Complex href "../Complex/"



      Node : power_AB





        Node --> "0..1" Complex : power_AB
        click Complex href "../Complex/"



      Node : power_AN





        Node --> "0..1" Complex : power_AN
        click Complex href "../Complex/"



      Node : power_B





        Node --> "0..1" Complex : power_B
        click Complex href "../Complex/"



      Node : power_BC





        Node --> "0..1" Complex : power_BC
        click Complex href "../Complex/"



      Node : power_BN





        Node --> "0..1" Complex : power_BN
        click Complex href "../Complex/"



      Node : power_C





        Node --> "0..1" Complex : power_C
        click Complex href "../Complex/"



      Node : power_CA





        Node --> "0..1" Complex : power_CA
        click Complex href "../Complex/"



      Node : power_CN





        Node --> "0..1" Complex : power_CN
        click Complex href "../Complex/"



      Node : prerotated_current_A





        Node --> "0..1" Complex : prerotated_current_A
        click Complex href "../Complex/"



      Node : prerotated_current_B





        Node --> "0..1" Complex : prerotated_current_B
        click Complex href "../Complex/"



      Node : prerotated_current_C





        Node --> "0..1" Complex : prerotated_current_C
        click Complex href "../Complex/"



      Node : previous_uptime

      Node : rank

      Node : reference_bus

      Node : reset_disabled_island_state

      Node : residential_nominal_current_A





        Node --> "0..1" Complex : residential_nominal_current_A
        click Complex href "../Complex/"



      Node : residential_nominal_current_A_imag

      Node : residential_nominal_current_A_real

      Node : residential_nominal_current_B





        Node --> "0..1" Complex : residential_nominal_current_B
        click Complex href "../Complex/"



      Node : residential_nominal_current_B_imag

      Node : residential_nominal_current_B_real

      Node : residential_nominal_current_C





        Node --> "0..1" Complex : residential_nominal_current_C
        click Complex href "../Complex/"



      Node : residential_nominal_current_C_imag

      Node : residential_nominal_current_C_real

      Node : service_status

      Node : service_status_double

      Node : sfm_Tf

      Node : shunt_A





        Node --> "0..1" Complex : shunt_A
        click Complex href "../Complex/"



      Node : shunt_AB





        Node --> "0..1" Complex : shunt_AB
        click Complex href "../Complex/"



      Node : shunt_AN





        Node --> "0..1" Complex : shunt_AN
        click Complex href "../Complex/"



      Node : shunt_B





        Node --> "0..1" Complex : shunt_B
        click Complex href "../Complex/"



      Node : shunt_BC





        Node --> "0..1" Complex : shunt_BC
        click Complex href "../Complex/"



      Node : shunt_BN





        Node --> "0..1" Complex : shunt_BN
        click Complex href "../Complex/"



      Node : shunt_C





        Node --> "0..1" Complex : shunt_C
        click Complex href "../Complex/"



      Node : shunt_CA





        Node --> "0..1" Complex : shunt_CA
        click Complex href "../Complex/"



      Node : shunt_CN





        Node --> "0..1" Complex : shunt_CN
        click Complex href "../Complex/"



      Node : solution

      Node : topological_parent

      Node : voltage_A





        Node --> "0..1" Complex : voltage_A
        click Complex href "../Complex/"



      Node : voltage_AB





        Node --> "0..1" Complex : voltage_AB
        click Complex href "../Complex/"



      Node : voltage_B





        Node --> "0..1" Complex : voltage_B
        click Complex href "../Complex/"



      Node : voltage_BC





        Node --> "0..1" Complex : voltage_BC
        click Complex href "../Complex/"



      Node : voltage_C





        Node --> "0..1" Complex : voltage_C
        click Complex href "../Complex/"



      Node : voltage_CA





        Node --> "0..1" Complex : voltage_CA
        click Complex href "../Complex/"



Inheritance

Slots

Name Cardinality and Range Description Inheritance
bustype 0..1
String
defines whether the node is a PQ, PV, or SWING node direct
busflags 0..1
String
flag indicates node has a source for voltage, i direct
reference_bus 0..1
String
reference bus from which frequency is defined direct
maximum_voltage_error 0..1
Float
convergence voltage limit or convergence criteria direct
voltage_A 0..1
Complex
bus voltage, Phase A to ground direct
voltage_B 0..1
Complex
bus voltage, Phase B to ground direct
voltage_C 0..1
Complex
bus voltage, Phase C to ground direct
voltage_AB 0..1
Complex
line voltages, Phase AB direct
voltage_BC 0..1
Complex
line voltages, Phase BC direct
voltage_CA 0..1
Complex
line voltages, Phase CA direct
current_A 0..1
Complex
bus current injection (in = positive), this an accumulator only, not a output... direct
current_B 0..1
Complex
bus current injection (in = positive), this an accumulator only, not a output... direct
current_C 0..1
Complex
bus current injection (in = positive), this an accumulator only, not a output... direct
power_A 0..1
Complex
bus power injection (in = positive), this an accumulator only, not a output o... direct
power_B 0..1
Complex
bus power injection (in = positive), this an accumulator only, not a output o... direct
power_C 0..1
Complex
bus power injection (in = positive), this an accumulator only, not a output o... direct
shunt_A 0..1
Complex
bus shunt admittance, this an accumulator only, not a output or input variabl... direct
shunt_B 0..1
Complex
bus shunt admittance, this an accumulator only, not a output or input variabl... direct
shunt_C 0..1
Complex
bus shunt admittance, this an accumulator only, not a output or input variabl... direct
prerotated_current_A 0..1
Complex
deltamode-functionality - bus current injection (in = positive), but will not... direct
prerotated_current_B 0..1
Complex
deltamode-functionality - bus current injection (in = positive), but will not... direct
prerotated_current_C 0..1
Complex
deltamode-functionality - bus current injection (in = positive), but will not... direct
deltamode_generator_current_A 0..1
Complex
deltamode-functionality - bus current injection (in = positive), direct gener... direct
deltamode_generator_current_B 0..1
Complex
deltamode-functionality - bus current injection (in = positive), direct gener... direct
deltamode_generator_current_C 0..1
Complex
deltamode-functionality - bus current injection (in = positive), direct gener... direct
deltamode_PGenTotal 0..1
Complex
deltamode-functionality - power value for a diesel generator -- accumulator o... direct
deltamode_full_Y_matrix 0..1
String
deltamode-functionality full_Y matrix exposes so generator objects can intera... direct
deltamode_full_Y_all_matrix 0..1
String
deltamode-functionality full_Y_all matrix exposes so generator objects can in... direct
NR_powerflow_parent 0..1
String
NR powerflow - actual powerflow parent - used by generators accessing child o... direct
current_inj_A 0..1
Complex
bus current injection (in = positive), but will not be rotated by powerflow f... direct
current_inj_B 0..1
Complex
bus current injection (in = positive), but will not be rotated by powerflow f... direct
current_inj_C 0..1
Complex
bus current injection (in = positive), but will not be rotated by powerflow f... direct
current_AB 0..1
Complex
bus current delta-connected injection (in = positive), this an accumulator on... direct
current_BC 0..1
Complex
bus current delta-connected injection (in = positive), this an accumulator on... direct
current_CA 0..1
Complex
bus current delta-connected injection (in = positive), this an accumulator on... direct
current_AN 0..1
Complex
bus current wye-connected injection (in = positive), this an accumulator only... direct
current_BN 0..1
Complex
bus current wye-connected injection (in = positive), this an accumulator only... direct
current_CN 0..1
Complex
bus current wye-connected injection (in = positive), this an accumulator only... direct
power_AB 0..1
Complex
bus power delta-connected injection (in = positive), this an accumulator only... direct
power_BC 0..1
Complex
bus power delta-connected injection (in = positive), this an accumulator only... direct
power_CA 0..1
Complex
bus power delta-connected injection (in = positive), this an accumulator only... direct
power_AN 0..1
Complex
bus power wye-connected injection (in = positive), this an accumulator only, ... direct
power_BN 0..1
Complex
bus power wye-connected injection (in = positive), this an accumulator only, ... direct
power_CN 0..1
Complex
bus power wye-connected injection (in = positive), this an accumulator only, ... direct
shunt_AB 0..1
Complex
bus shunt delta-connected admittance, this an accumulator only, not a output ... direct
shunt_BC 0..1
Complex
bus shunt delta-connected admittance, this an accumulator only, not a output ... direct
shunt_CA 0..1
Complex
bus shunt delta-connected admittance, this an accumulator only, not a output ... direct
shunt_AN 0..1
Complex
bus shunt wye-connected admittance, this an accumulator only, not a output or... direct
shunt_BN 0..1
Complex
bus shunt wye-connected admittance, this an accumulator only, not a output or... direct
shunt_CN 0..1
Complex
bus shunt wye-connected admittance, this an accumulator only, not a output or... direct
residential_nominal_current_A 0..1
Complex
posted current on phase A from a residential object, if attached direct
residential_nominal_current_B 0..1
Complex
posted current on phase B from a residential object, if attached direct
residential_nominal_current_C 0..1
Complex
posted current on phase C from a residential object, if attached direct
residential_nominal_current_A_real 0..1
Float
posted current on phase A, real, from a residential object, if attached direct
residential_nominal_current_A_imag 0..1
Float
posted current on phase A, imag, from a residential object, if attached direct
residential_nominal_current_B_real 0..1
Float
posted current on phase B, real, from a residential object, if attached direct
residential_nominal_current_B_imag 0..1
Float
posted current on phase B, imag, from a residential object, if attached direct
residential_nominal_current_C_real 0..1
Float
posted current on phase C, real, from a residential object, if attached direct
residential_nominal_current_C_imag 0..1
Float
posted current on phase C, imag, from a residential object, if attached direct
house_present 0..1
Boolean
boolean for detecting whether a house is attached, not an input direct
mean_repair_time 0..1
Float
Time after a fault clears for the object to be back in service direct
frequency_measure_type 0..1
String
PLL frequency measurement direct
sfm_Tf 0..1
Float
Transducer time constant for simplified frequency measurement (seconds) direct
pll_Kp 0..1
Float
Proportional gain of PLL frequency measurement direct
pll_Ki 0..1
Float
Integration gain of PLL frequency measurement direct
measured_angle_A 0..1
Float
bus angle measurement, phase A direct
measured_frequency_A 0..1
Float
frequency measurement, phase A direct
measured_angle_B 0..1
Float
bus angle measurement, phase B direct
measured_frequency_B 0..1
Float
frequency measurement, phase B direct
measured_angle_C 0..1
Float
bus angle measurement, phase C direct
measured_frequency_C 0..1
Float
frequency measurement, phase C direct
measured_frequency 0..1
Float
frequency measurement - average of present phases direct
service_status 0..1
String
In and out of service flag direct
service_status_double 0..1
Float
In and out of service flag - type double - will indiscriminately override ser... direct
previous_uptime 0..1
Float
Previous time between disconnects of node in minutes direct
current_uptime 0..1
Float
Current time since last disconnect of node in minutes direct
Norton_dynamic 0..1
Boolean
Flag to indicate a Norton-equivalent connection -- used for generators and de... direct
Norton_dynamic_child 0..1
Boolean
Flag to indicate a Norton-equivalent connection is made by a childed node obj... direct
generator_dynamic 0..1
Boolean
Flag to indicate a voltage-sourcing or swing-type generator is present -- use... direct
reset_disabled_island_state 0..1
Boolean
Deltamode/multi-island flag -- used to reset disabled status (and reform an i... direct
GFA_enable 0..1
Boolean
Disable/Enable Grid Friendly Appliance(TM)-type functionality direct
GFA_freq_low_trip 0..1
Float
Low frequency trip point for Grid Friendly Appliance(TM)-type functionality direct
GFA_freq_high_trip 0..1
Float
High frequency trip point for Grid Friendly Appliance(TM)-type functionality direct
GFA_volt_low_trip 0..1
Float
Low voltage trip point for Grid Friendly Appliance(TM)-type functionality direct
GFA_volt_high_trip 0..1
Float
High voltage trip point for Grid Friendly Appliance(TM)-type functionality direct
GFA_reconnect_time 0..1
Float
Reconnect time for Grid Friendly Appliance(TM)-type functionality direct
GFA_freq_disconnect_time 0..1
Float
Frequency violation disconnect time for Grid Friendly Appliance(TM)-type func... direct
GFA_volt_disconnect_time 0..1
Float
Voltage violation disconnect time for Grid Friendly Appliance(TM)-type functi... direct
GFA_status 0..1
Boolean
Grid Friendly Appliance(TM)-type functionality - whether it is in service (no... direct
GFA_trip_method 0..1
String
GFA trip for over-voltage direct
topological_parent 0..1
String
topological parent as per GLM configuration direct
behaving_as_swing 0..1
Boolean
Indicator flag for if a bus is behaving as a reference voltage source - valid... direct
phases 0..1
String
PowerflowObject
nominal_voltage 0..1
Float
PowerflowObject
inrush_integration_method 0..1
String
Integration method for in-rush PowerflowObject
condition 0..1
String
PowerflowObject
solution 0..1
String
PowerflowObject
name 1
String
The object's name; unique across the model GlmObject
parent 0..1
String
The parent object's name GlmObject
groupid 0..1
String
Free-text group label GlmObject
latitude 0..1
String
Latitude, as written (decimal degrees or GridLAB-D's 37N26:12 form) GlmObject
longitude 0..1
String
Longitude, as written GlmObject
in_svc 0..1
String
Timestamp the object enters service GlmObject
out_svc 0..1
String
Timestamp the object leaves service GlmObject
rank 0..1
String
Solver rank GlmObject
flags 0..1
String
Core object flags GlmObject

Comments

  • Import: ConnectivityNode, mRID = name (bus.cimtbl), one per root bus; a node, meter or substation with its own power_X, current_X or shunt_X set raises; a bustype SWING node also gives EnergySource, mRID src_ + name (source.cimtbl). Export: every ConnectivityNode without an EnergySource on a three- or single-phase zone.

Identifier and Mapping Information

Schema Source

  • from schema: https://gridlabd.org/schema/glm

Mappings

Mapping Type Mapped Value
self glm:Node
native glm:Node
exact cim:ConnectivityNode
close cim:EnergySource

LinkML Source

Direct

name: node
description: 'Copyright (C) 2008 Battelle Memorial Institute

  @file node.cpp

  @addtogroup powerflow_node Node

  @ingroup powerflow_object

  The node is one of the major components of the method used for solving a

  powerflow network.  In essense the distribution network can be seen as a

  series of nodes and links.  Nodes primary responsibility is to act as an

  aggregation point for the links that are attached to it, and to hold the

  current and voltage values that will be used in the matrix calculations

  done in the link.

  Three types of nodes are defined in this file.  Nodes are simply a basic

  object that exports the voltages for each phase.  Triplex nodes export

  voltages for 3 lines; line1_voltage, line2_voltage, lineN_voltage.

  @par Voltage control

  When the global variable require_voltage_control is set to @p true,

  the bus type is used to determine how voltage control is implemented.

  Voltage control is only performed when the bus has no link that

  considers it a to node.  When the flag #NF_HASSOURCE is cleared, then

  the following is in effect:

  - #SWING buses are considered infinite sources and the voltage will

  remain fixed regardless of conditions.

  - #PV buses are considered constrained sources and the voltage will

  fall to zero if there is insufficient voltage support at the bus.

  A generator object is required to provide the voltage support explicitly.

  The voltage will be set to zero if the generator does not provide

  sufficient support.

  - #PQ buses will always go to zero voltage.

  @par Fault support

  The following conditions are used to describe a fault impedance @e X (e.g., 1e-6),

  between phase @e x and neutral or group, or between phases @e x and @e y, and leaving

  phase @e z unaffected at iteration @e t:

  - @e phase-to-phase contact at the node

  - @e Forward-sweep: @f$ V_x(t) = V_y(t) = @frac{V_x(t-1) + V_y(t-1)}{2} @f$

  - @e Back-sweep: @f$ I_x(t+1) = -I_y(t+1) = @frac{V_x(t)-V_y(t)}{X} @f$;

  - @e phase-to-ground/neutral contact at the node

  - @e Forward-sweep: @f$ V_x(t) = @frac{1}{2} V_x(t-1)  @f$

  - @e Back-sweep: @f$ I_x(t+1) = @frac{V_x(t)}{X} @f$;

  @{


  Inherits from: powerflow_object


  Type: Instance (network topology element)'
comments:
- 'Import: ConnectivityNode, mRID = name (bus.cimtbl), one per root bus; a node, meter
  or substation with its own power_X, current_X or shunt_X set raises; a bustype SWING
  node also gives EnergySource, mRID src_ + name (source.cimtbl). Export: every ConnectivityNode
  without an EnergySource on a three- or single-phase zone.'
from_schema: https://gridlabd.org/schema/glm
exact_mappings:
- cim:ConnectivityNode
close_mappings:
- cim:EnergySource
is_a: powerflow_object
attributes:
  bustype:
    name: bustype
    annotations:
      order:
        tag: order
        value: 1
      value_type:
        tag: value_type
        value: string
      native_name:
        tag: native_name
        value: bustype
    description: defines whether the node is a PQ, PV, or SWING node
    comments:
    - 'Import: SWING makes an EnergySource; PQ, PV and SWING_PQ are a plain bus (SWING_PQ
      is a swing only when islanded). Export: SWING on the substation only.'
    from_schema: https://gridlabd.org/schema/glm/powerflow/node
    related_mappings:
    - cim:EnergySource
    rank: 1000
    domain_of:
    - node
    - triplex_node
    range: string
    required: false
  busflags:
    name: busflags
    annotations:
      order:
        tag: order
        value: 2
      value_type:
        tag: value_type
        value: string
      native_name:
        tag: native_name
        value: busflags
    description: flag indicates node has a source for voltage, i.e. connects to the
      swing node
    from_schema: https://gridlabd.org/schema/glm/powerflow/node
    rank: 1000
    domain_of:
    - node
    - triplex_node
    range: string
    required: false
  reference_bus:
    name: reference_bus
    annotations:
      order:
        tag: order
        value: 3
      value_type:
        tag: value_type
        value: string
      native_name:
        tag: native_name
        value: reference_bus
    description: reference bus from which frequency is defined
    from_schema: https://gridlabd.org/schema/glm/powerflow/node
    rank: 1000
    domain_of:
    - node
    - triplex_node
    range: string
    required: false
  maximum_voltage_error:
    name: maximum_voltage_error
    annotations:
      order:
        tag: order
        value: 4
      value_type:
        tag: value_type
        value: float
      precision:
        tag: precision
        value: 6
      native_name:
        tag: native_name
        value: maximum_voltage_error[V]
    description: convergence voltage limit or convergence criteria
    from_schema: https://gridlabd.org/schema/glm/powerflow/node
    rank: 1000
    domain_of:
    - node
    - triplex_node
    range: float
    required: false
    unit:
      ucum_code: V
  voltage_A:
    name: voltage_A
    annotations:
      order:
        tag: order
        value: 5
      value_type:
        tag: value_type
        value: complex
      native_name:
        tag: native_name
        value: voltage_A[V]
    description: bus voltage, Phase A to ground
    comments:
    - 'Import: on a SWING bus only: EnergySource.voltageMagnitude (line to line) and
      voltageAngle (deg) from |V| and arg(V); elsewhere the solver guess, not converted.
      Export: not written.'
    from_schema: https://gridlabd.org/schema/glm/powerflow/node
    close_mappings:
    - cim:EnergySource.voltageMagnitude
    - cim:EnergySource.voltageAngle
    rank: 1000
    domain_of:
    - node
    - rectifier
    - windturb_dg
    range: Complex
    required: false
    unit:
      ucum_code: V
  voltage_B:
    name: voltage_B
    annotations:
      order:
        tag: order
        value: 6
      value_type:
        tag: value_type
        value: complex
      native_name:
        tag: native_name
        value: voltage_B[V]
    description: bus voltage, Phase B to ground
    from_schema: https://gridlabd.org/schema/glm/powerflow/node
    rank: 1000
    domain_of:
    - node
    - rectifier
    - windturb_dg
    range: Complex
    required: false
    unit:
      ucum_code: V
  voltage_C:
    name: voltage_C
    annotations:
      order:
        tag: order
        value: 7
      value_type:
        tag: value_type
        value: complex
      native_name:
        tag: native_name
        value: voltage_C[V]
    description: bus voltage, Phase C to ground
    from_schema: https://gridlabd.org/schema/glm/powerflow/node
    rank: 1000
    domain_of:
    - node
    - rectifier
    - windturb_dg
    range: Complex
    required: false
    unit:
      ucum_code: V
  voltage_AB:
    name: voltage_AB
    annotations:
      order:
        tag: order
        value: 8
      value_type:
        tag: value_type
        value: complex
      native_name:
        tag: native_name
        value: voltage_AB[V]
    description: line voltages, Phase AB
    from_schema: https://gridlabd.org/schema/glm/powerflow/node
    rank: 1000
    domain_of:
    - node
    range: Complex
    required: false
    unit:
      ucum_code: V
  voltage_BC:
    name: voltage_BC
    annotations:
      order:
        tag: order
        value: 9
      value_type:
        tag: value_type
        value: complex
      native_name:
        tag: native_name
        value: voltage_BC[V]
    description: line voltages, Phase BC
    from_schema: https://gridlabd.org/schema/glm/powerflow/node
    rank: 1000
    domain_of:
    - node
    range: Complex
    required: false
    unit:
      ucum_code: V
  voltage_CA:
    name: voltage_CA
    annotations:
      order:
        tag: order
        value: 10
      value_type:
        tag: value_type
        value: complex
      native_name:
        tag: native_name
        value: voltage_CA[V]
    description: line voltages, Phase CA
    from_schema: https://gridlabd.org/schema/glm/powerflow/node
    rank: 1000
    domain_of:
    - node
    range: Complex
    required: false
    unit:
      ucum_code: V
  current_A:
    name: current_A
    annotations:
      order:
        tag: order
        value: 11
      value_type:
        tag: value_type
        value: complex
      native_name:
        tag: native_name
        value: current_A[A]
    description: bus current injection (in = positive), this an accumulator only,
      not a output or input variable
    from_schema: https://gridlabd.org/schema/glm/powerflow/node
    rank: 1000
    domain_of:
    - node
    - rectifier
    - windturb_dg
    range: Complex
    required: false
    unit:
      ucum_code: A
  current_B:
    name: current_B
    annotations:
      order:
        tag: order
        value: 12
      value_type:
        tag: value_type
        value: complex
      native_name:
        tag: native_name
        value: current_B[A]
    description: bus current injection (in = positive), this an accumulator only,
      not a output or input variable
    from_schema: https://gridlabd.org/schema/glm/powerflow/node
    rank: 1000
    domain_of:
    - node
    - rectifier
    - windturb_dg
    range: Complex
    required: false
    unit:
      ucum_code: A
  current_C:
    name: current_C
    annotations:
      order:
        tag: order
        value: 13
      value_type:
        tag: value_type
        value: complex
      native_name:
        tag: native_name
        value: current_C[A]
    description: bus current injection (in = positive), this an accumulator only,
      not a output or input variable
    from_schema: https://gridlabd.org/schema/glm/powerflow/node
    rank: 1000
    domain_of:
    - node
    - rectifier
    - windturb_dg
    range: Complex
    required: false
    unit:
      ucum_code: A
  power_A:
    name: power_A
    annotations:
      order:
        tag: order
        value: 14
      value_type:
        tag: value_type
        value: complex
      native_name:
        tag: native_name
        value: power_A[VA]
    description: bus power injection (in = positive), this an accumulator only, not
      a output or input variable
    from_schema: https://gridlabd.org/schema/glm/powerflow/node
    rank: 1000
    domain_of:
    - node
    - inverter
    - inverter_dyn
    - windturb_dg
    range: Complex
    required: false
    unit:
      ucum_code: VA
  power_B:
    name: power_B
    annotations:
      order:
        tag: order
        value: 15
      value_type:
        tag: value_type
        value: complex
      native_name:
        tag: native_name
        value: power_B[VA]
    description: bus power injection (in = positive), this an accumulator only, not
      a output or input variable
    from_schema: https://gridlabd.org/schema/glm/powerflow/node
    rank: 1000
    domain_of:
    - node
    - inverter
    - inverter_dyn
    - windturb_dg
    range: Complex
    required: false
    unit:
      ucum_code: VA
  power_C:
    name: power_C
    annotations:
      order:
        tag: order
        value: 16
      value_type:
        tag: value_type
        value: complex
      native_name:
        tag: native_name
        value: power_C[VA]
    description: bus power injection (in = positive), this an accumulator only, not
      a output or input variable
    from_schema: https://gridlabd.org/schema/glm/powerflow/node
    rank: 1000
    domain_of:
    - node
    - inverter
    - inverter_dyn
    - windturb_dg
    range: Complex
    required: false
    unit:
      ucum_code: VA
  shunt_A:
    name: shunt_A
    annotations:
      order:
        tag: order
        value: 17
      value_type:
        tag: value_type
        value: complex
      native_name:
        tag: native_name
        value: shunt_A[S]
    description: bus shunt admittance, this an accumulator only, not a output or input
      variable
    from_schema: https://gridlabd.org/schema/glm/powerflow/node
    rank: 1000
    domain_of:
    - node
    range: Complex
    required: false
    unit:
      ucum_code: S
  shunt_B:
    name: shunt_B
    annotations:
      order:
        tag: order
        value: 18
      value_type:
        tag: value_type
        value: complex
      native_name:
        tag: native_name
        value: shunt_B[S]
    description: bus shunt admittance, this an accumulator only, not a output or input
      variable
    from_schema: https://gridlabd.org/schema/glm/powerflow/node
    rank: 1000
    domain_of:
    - node
    range: Complex
    required: false
    unit:
      ucum_code: S
  shunt_C:
    name: shunt_C
    annotations:
      order:
        tag: order
        value: 19
      value_type:
        tag: value_type
        value: complex
      native_name:
        tag: native_name
        value: shunt_C[S]
    description: bus shunt admittance, this an accumulator only, not a output or input
      variable
    from_schema: https://gridlabd.org/schema/glm/powerflow/node
    rank: 1000
    domain_of:
    - node
    range: Complex
    required: false
    unit:
      ucum_code: S
  prerotated_current_A:
    name: prerotated_current_A
    annotations:
      order:
        tag: order
        value: 20
      value_type:
        tag: value_type
        value: complex
      native_name:
        tag: native_name
        value: prerotated_current_A[A]
    description: deltamode-functionality - bus current injection (in = positive),
      but will not be rotated by powerflow for off-nominal frequency, this an accumulator
      only, not a output or input variable
    from_schema: https://gridlabd.org/schema/glm/powerflow/node
    rank: 1000
    domain_of:
    - node
    range: Complex
    required: false
    unit:
      ucum_code: A
  prerotated_current_B:
    name: prerotated_current_B
    annotations:
      order:
        tag: order
        value: 21
      value_type:
        tag: value_type
        value: complex
      native_name:
        tag: native_name
        value: prerotated_current_B[A]
    description: deltamode-functionality - bus current injection (in = positive),
      but will not be rotated by powerflow for off-nominal frequency, this an accumulator
      only, not a output or input variable
    from_schema: https://gridlabd.org/schema/glm/powerflow/node
    rank: 1000
    domain_of:
    - node
    range: Complex
    required: false
    unit:
      ucum_code: A
  prerotated_current_C:
    name: prerotated_current_C
    annotations:
      order:
        tag: order
        value: 22
      value_type:
        tag: value_type
        value: complex
      native_name:
        tag: native_name
        value: prerotated_current_C[A]
    description: deltamode-functionality - bus current injection (in = positive),
      but will not be rotated by powerflow for off-nominal frequency, this an accumulator
      only, not a output or input variable
    from_schema: https://gridlabd.org/schema/glm/powerflow/node
    rank: 1000
    domain_of:
    - node
    range: Complex
    required: false
    unit:
      ucum_code: A
  deltamode_generator_current_A:
    name: deltamode_generator_current_A
    annotations:
      order:
        tag: order
        value: 23
      value_type:
        tag: value_type
        value: complex
      native_name:
        tag: native_name
        value: deltamode_generator_current_A[A]
    description: deltamode-functionality - bus current injection (in = positive),
      direct generator injection (so may be overwritten internally), this an accumulator
      only, not a output or input variable
    from_schema: https://gridlabd.org/schema/glm/powerflow/node
    rank: 1000
    domain_of:
    - node
    range: Complex
    required: false
    unit:
      ucum_code: A
  deltamode_generator_current_B:
    name: deltamode_generator_current_B
    annotations:
      order:
        tag: order
        value: 24
      value_type:
        tag: value_type
        value: complex
      native_name:
        tag: native_name
        value: deltamode_generator_current_B[A]
    description: deltamode-functionality - bus current injection (in = positive),
      direct generator injection (so may be overwritten internally), this an accumulator
      only, not a output or input variable
    from_schema: https://gridlabd.org/schema/glm/powerflow/node
    rank: 1000
    domain_of:
    - node
    range: Complex
    required: false
    unit:
      ucum_code: A
  deltamode_generator_current_C:
    name: deltamode_generator_current_C
    annotations:
      order:
        tag: order
        value: 25
      value_type:
        tag: value_type
        value: complex
      native_name:
        tag: native_name
        value: deltamode_generator_current_C[A]
    description: deltamode-functionality - bus current injection (in = positive),
      direct generator injection (so may be overwritten internally), this an accumulator
      only, not a output or input variable
    from_schema: https://gridlabd.org/schema/glm/powerflow/node
    rank: 1000
    domain_of:
    - node
    range: Complex
    required: false
    unit:
      ucum_code: A
  deltamode_PGenTotal:
    name: deltamode_PGenTotal
    annotations:
      order:
        tag: order
        value: 26
      value_type:
        tag: value_type
        value: complex
      native_name:
        tag: native_name
        value: deltamode_PGenTotal
    description: deltamode-functionality - power value for a diesel generator -- accumulator
      only, not an output or input
    from_schema: https://gridlabd.org/schema/glm/powerflow/node
    rank: 1000
    domain_of:
    - node
    - triplex_node
    range: Complex
    required: false
  deltamode_full_Y_matrix:
    name: deltamode_full_Y_matrix
    annotations:
      order:
        tag: order
        value: 27
      value_type:
        tag: value_type
        value: string
      native_name:
        tag: native_name
        value: deltamode_full_Y_matrix
    description: deltamode-functionality full_Y matrix exposes so generator objects
      can interact for Norton equivalents
    from_schema: https://gridlabd.org/schema/glm/powerflow/node
    rank: 1000
    domain_of:
    - node
    - triplex_node
    range: string
    required: false
  deltamode_full_Y_all_matrix:
    name: deltamode_full_Y_all_matrix
    annotations:
      order:
        tag: order
        value: 28
      value_type:
        tag: value_type
        value: string
      native_name:
        tag: native_name
        value: deltamode_full_Y_all_matrix
    description: deltamode-functionality full_Y_all matrix exposes so generator objects
      can interact for Norton equivalents
    from_schema: https://gridlabd.org/schema/glm/powerflow/node
    rank: 1000
    domain_of:
    - node
    - triplex_node
    range: string
    required: false
  NR_powerflow_parent:
    name: NR_powerflow_parent
    annotations:
      order:
        tag: order
        value: 29
      value_type:
        tag: value_type
        value: string
      native_name:
        tag: native_name
        value: NR_powerflow_parent
    description: NR powerflow - actual powerflow parent - used by generators accessing
      child objects
    from_schema: https://gridlabd.org/schema/glm/powerflow/node
    rank: 1000
    domain_of:
    - node
    - triplex_node
    range: string
    required: false
  current_inj_A:
    name: current_inj_A
    annotations:
      order:
        tag: order
        value: 30
      value_type:
        tag: value_type
        value: complex
      native_name:
        tag: native_name
        value: current_inj_A[A]
    description: bus current injection (in = positive), but will not be rotated by
      powerflow for off-nominal frequency, this an accumulator only, not a output
      or input variable
    from_schema: https://gridlabd.org/schema/glm/powerflow/node
    rank: 1000
    domain_of:
    - node
    range: Complex
    required: false
    unit:
      ucum_code: A
  current_inj_B:
    name: current_inj_B
    annotations:
      order:
        tag: order
        value: 31
      value_type:
        tag: value_type
        value: complex
      native_name:
        tag: native_name
        value: current_inj_B[A]
    description: bus current injection (in = positive), but will not be rotated by
      powerflow for off-nominal frequency, this an accumulator only, not a output
      or input variable
    from_schema: https://gridlabd.org/schema/glm/powerflow/node
    rank: 1000
    domain_of:
    - node
    range: Complex
    required: false
    unit:
      ucum_code: A
  current_inj_C:
    name: current_inj_C
    annotations:
      order:
        tag: order
        value: 32
      value_type:
        tag: value_type
        value: complex
      native_name:
        tag: native_name
        value: current_inj_C[A]
    description: bus current injection (in = positive), but will not be rotated by
      powerflow for off-nominal frequency, this an accumulator only, not a output
      or input variable
    from_schema: https://gridlabd.org/schema/glm/powerflow/node
    rank: 1000
    domain_of:
    - node
    range: Complex
    required: false
    unit:
      ucum_code: A
  current_AB:
    name: current_AB
    annotations:
      order:
        tag: order
        value: 33
      value_type:
        tag: value_type
        value: complex
      native_name:
        tag: native_name
        value: current_AB[A]
    description: bus current delta-connected injection (in = positive), this an accumulator
      only, not a output or input variable
    from_schema: https://gridlabd.org/schema/glm/powerflow/node
    rank: 1000
    domain_of:
    - node
    range: Complex
    required: false
    unit:
      ucum_code: A
  current_BC:
    name: current_BC
    annotations:
      order:
        tag: order
        value: 34
      value_type:
        tag: value_type
        value: complex
      native_name:
        tag: native_name
        value: current_BC[A]
    description: bus current delta-connected injection (in = positive), this an accumulator
      only, not a output or input variable
    from_schema: https://gridlabd.org/schema/glm/powerflow/node
    rank: 1000
    domain_of:
    - node
    range: Complex
    required: false
    unit:
      ucum_code: A
  current_CA:
    name: current_CA
    annotations:
      order:
        tag: order
        value: 35
      value_type:
        tag: value_type
        value: complex
      native_name:
        tag: native_name
        value: current_CA[A]
    description: bus current delta-connected injection (in = positive), this an accumulator
      only, not a output or input variable
    from_schema: https://gridlabd.org/schema/glm/powerflow/node
    rank: 1000
    domain_of:
    - node
    range: Complex
    required: false
    unit:
      ucum_code: A
  current_AN:
    name: current_AN
    annotations:
      order:
        tag: order
        value: 36
      value_type:
        tag: value_type
        value: complex
      native_name:
        tag: native_name
        value: current_AN[A]
    description: bus current wye-connected injection (in = positive), this an accumulator
      only, not a output or input variable
    from_schema: https://gridlabd.org/schema/glm/powerflow/node
    rank: 1000
    domain_of:
    - node
    range: Complex
    required: false
    unit:
      ucum_code: A
  current_BN:
    name: current_BN
    annotations:
      order:
        tag: order
        value: 37
      value_type:
        tag: value_type
        value: complex
      native_name:
        tag: native_name
        value: current_BN[A]
    description: bus current wye-connected injection (in = positive), this an accumulator
      only, not a output or input variable
    from_schema: https://gridlabd.org/schema/glm/powerflow/node
    rank: 1000
    domain_of:
    - node
    range: Complex
    required: false
    unit:
      ucum_code: A
  current_CN:
    name: current_CN
    annotations:
      order:
        tag: order
        value: 38
      value_type:
        tag: value_type
        value: complex
      native_name:
        tag: native_name
        value: current_CN[A]
    description: bus current wye-connected injection (in = positive), this an accumulator
      only, not a output or input variable
    from_schema: https://gridlabd.org/schema/glm/powerflow/node
    rank: 1000
    domain_of:
    - node
    range: Complex
    required: false
    unit:
      ucum_code: A
  power_AB:
    name: power_AB
    annotations:
      order:
        tag: order
        value: 39
      value_type:
        tag: value_type
        value: complex
      native_name:
        tag: native_name
        value: power_AB[VA]
    description: bus power delta-connected injection (in = positive), this an accumulator
      only, not a output or input variable
    from_schema: https://gridlabd.org/schema/glm/powerflow/node
    rank: 1000
    domain_of:
    - node
    range: Complex
    required: false
    unit:
      ucum_code: VA
  power_BC:
    name: power_BC
    annotations:
      order:
        tag: order
        value: 40
      value_type:
        tag: value_type
        value: complex
      native_name:
        tag: native_name
        value: power_BC[VA]
    description: bus power delta-connected injection (in = positive), this an accumulator
      only, not a output or input variable
    from_schema: https://gridlabd.org/schema/glm/powerflow/node
    rank: 1000
    domain_of:
    - node
    range: Complex
    required: false
    unit:
      ucum_code: VA
  power_CA:
    name: power_CA
    annotations:
      order:
        tag: order
        value: 41
      value_type:
        tag: value_type
        value: complex
      native_name:
        tag: native_name
        value: power_CA[VA]
    description: bus power delta-connected injection (in = positive), this an accumulator
      only, not a output or input variable
    from_schema: https://gridlabd.org/schema/glm/powerflow/node
    rank: 1000
    domain_of:
    - node
    range: Complex
    required: false
    unit:
      ucum_code: VA
  power_AN:
    name: power_AN
    annotations:
      order:
        tag: order
        value: 42
      value_type:
        tag: value_type
        value: complex
      native_name:
        tag: native_name
        value: power_AN[VA]
    description: bus power wye-connected injection (in = positive), this an accumulator
      only, not a output or input variable
    from_schema: https://gridlabd.org/schema/glm/powerflow/node
    rank: 1000
    domain_of:
    - node
    range: Complex
    required: false
    unit:
      ucum_code: VA
  power_BN:
    name: power_BN
    annotations:
      order:
        tag: order
        value: 43
      value_type:
        tag: value_type
        value: complex
      native_name:
        tag: native_name
        value: power_BN[VA]
    description: bus power wye-connected injection (in = positive), this an accumulator
      only, not a output or input variable
    from_schema: https://gridlabd.org/schema/glm/powerflow/node
    rank: 1000
    domain_of:
    - node
    range: Complex
    required: false
    unit:
      ucum_code: VA
  power_CN:
    name: power_CN
    annotations:
      order:
        tag: order
        value: 44
      value_type:
        tag: value_type
        value: complex
      native_name:
        tag: native_name
        value: power_CN[VA]
    description: bus power wye-connected injection (in = positive), this an accumulator
      only, not a output or input variable
    from_schema: https://gridlabd.org/schema/glm/powerflow/node
    rank: 1000
    domain_of:
    - node
    range: Complex
    required: false
    unit:
      ucum_code: VA
  shunt_AB:
    name: shunt_AB
    annotations:
      order:
        tag: order
        value: 45
      value_type:
        tag: value_type
        value: complex
      native_name:
        tag: native_name
        value: shunt_AB[S]
    description: bus shunt delta-connected admittance, this an accumulator only, not
      a output or input variable
    from_schema: https://gridlabd.org/schema/glm/powerflow/node
    rank: 1000
    domain_of:
    - node
    range: Complex
    required: false
    unit:
      ucum_code: S
  shunt_BC:
    name: shunt_BC
    annotations:
      order:
        tag: order
        value: 46
      value_type:
        tag: value_type
        value: complex
      native_name:
        tag: native_name
        value: shunt_BC[S]
    description: bus shunt delta-connected admittance, this an accumulator only, not
      a output or input variable
    from_schema: https://gridlabd.org/schema/glm/powerflow/node
    rank: 1000
    domain_of:
    - node
    range: Complex
    required: false
    unit:
      ucum_code: S
  shunt_CA:
    name: shunt_CA
    annotations:
      order:
        tag: order
        value: 47
      value_type:
        tag: value_type
        value: complex
      native_name:
        tag: native_name
        value: shunt_CA[S]
    description: bus shunt delta-connected admittance, this an accumulator only, not
      a output or input variable
    from_schema: https://gridlabd.org/schema/glm/powerflow/node
    rank: 1000
    domain_of:
    - node
    range: Complex
    required: false
    unit:
      ucum_code: S
  shunt_AN:
    name: shunt_AN
    annotations:
      order:
        tag: order
        value: 48
      value_type:
        tag: value_type
        value: complex
      native_name:
        tag: native_name
        value: shunt_AN[S]
    description: bus shunt wye-connected admittance, this an accumulator only, not
      a output or input variable
    from_schema: https://gridlabd.org/schema/glm/powerflow/node
    rank: 1000
    domain_of:
    - node
    range: Complex
    required: false
    unit:
      ucum_code: S
  shunt_BN:
    name: shunt_BN
    annotations:
      order:
        tag: order
        value: 49
      value_type:
        tag: value_type
        value: complex
      native_name:
        tag: native_name
        value: shunt_BN[S]
    description: bus shunt wye-connected admittance, this an accumulator only, not
      a output or input variable
    from_schema: https://gridlabd.org/schema/glm/powerflow/node
    rank: 1000
    domain_of:
    - node
    range: Complex
    required: false
    unit:
      ucum_code: S
  shunt_CN:
    name: shunt_CN
    annotations:
      order:
        tag: order
        value: 50
      value_type:
        tag: value_type
        value: complex
      native_name:
        tag: native_name
        value: shunt_CN[S]
    description: bus shunt wye-connected admittance, this an accumulator only, not
      a output or input variable
    from_schema: https://gridlabd.org/schema/glm/powerflow/node
    rank: 1000
    domain_of:
    - node
    range: Complex
    required: false
    unit:
      ucum_code: S
  residential_nominal_current_A:
    name: residential_nominal_current_A
    annotations:
      order:
        tag: order
        value: 51
      value_type:
        tag: value_type
        value: complex
      native_name:
        tag: native_name
        value: residential_nominal_current_A[A]
    description: posted current on phase A from a residential object, if attached
    from_schema: https://gridlabd.org/schema/glm/powerflow/node
    rank: 1000
    domain_of:
    - node
    range: Complex
    required: false
    unit:
      ucum_code: A
  residential_nominal_current_B:
    name: residential_nominal_current_B
    annotations:
      order:
        tag: order
        value: 52
      value_type:
        tag: value_type
        value: complex
      native_name:
        tag: native_name
        value: residential_nominal_current_B[A]
    description: posted current on phase B from a residential object, if attached
    from_schema: https://gridlabd.org/schema/glm/powerflow/node
    rank: 1000
    domain_of:
    - node
    range: Complex
    required: false
    unit:
      ucum_code: A
  residential_nominal_current_C:
    name: residential_nominal_current_C
    annotations:
      order:
        tag: order
        value: 53
      value_type:
        tag: value_type
        value: complex
      native_name:
        tag: native_name
        value: residential_nominal_current_C[A]
    description: posted current on phase C from a residential object, if attached
    from_schema: https://gridlabd.org/schema/glm/powerflow/node
    rank: 1000
    domain_of:
    - node
    range: Complex
    required: false
    unit:
      ucum_code: A
  residential_nominal_current_A_real:
    name: residential_nominal_current_A_real
    annotations:
      order:
        tag: order
        value: 54
      value_type:
        tag: value_type
        value: float
      precision:
        tag: precision
        value: 6
      native_name:
        tag: native_name
        value: residential_nominal_current_A_real[A]
    description: posted current on phase A, real, from a residential object, if attached
    from_schema: https://gridlabd.org/schema/glm/powerflow/node
    rank: 1000
    domain_of:
    - node
    range: float
    required: false
    unit:
      ucum_code: A
  residential_nominal_current_A_imag:
    name: residential_nominal_current_A_imag
    annotations:
      order:
        tag: order
        value: 55
      value_type:
        tag: value_type
        value: float
      precision:
        tag: precision
        value: 6
      native_name:
        tag: native_name
        value: residential_nominal_current_A_imag[A]
    description: posted current on phase A, imag, from a residential object, if attached
    from_schema: https://gridlabd.org/schema/glm/powerflow/node
    rank: 1000
    domain_of:
    - node
    range: float
    required: false
    unit:
      ucum_code: A
  residential_nominal_current_B_real:
    name: residential_nominal_current_B_real
    annotations:
      order:
        tag: order
        value: 56
      value_type:
        tag: value_type
        value: float
      precision:
        tag: precision
        value: 6
      native_name:
        tag: native_name
        value: residential_nominal_current_B_real[A]
    description: posted current on phase B, real, from a residential object, if attached
    from_schema: https://gridlabd.org/schema/glm/powerflow/node
    rank: 1000
    domain_of:
    - node
    range: float
    required: false
    unit:
      ucum_code: A
  residential_nominal_current_B_imag:
    name: residential_nominal_current_B_imag
    annotations:
      order:
        tag: order
        value: 57
      value_type:
        tag: value_type
        value: float
      precision:
        tag: precision
        value: 6
      native_name:
        tag: native_name
        value: residential_nominal_current_B_imag[A]
    description: posted current on phase B, imag, from a residential object, if attached
    from_schema: https://gridlabd.org/schema/glm/powerflow/node
    rank: 1000
    domain_of:
    - node
    range: float
    required: false
    unit:
      ucum_code: A
  residential_nominal_current_C_real:
    name: residential_nominal_current_C_real
    annotations:
      order:
        tag: order
        value: 58
      value_type:
        tag: value_type
        value: float
      precision:
        tag: precision
        value: 6
      native_name:
        tag: native_name
        value: residential_nominal_current_C_real[A]
    description: posted current on phase C, real, from a residential object, if attached
    from_schema: https://gridlabd.org/schema/glm/powerflow/node
    rank: 1000
    domain_of:
    - node
    range: float
    required: false
    unit:
      ucum_code: A
  residential_nominal_current_C_imag:
    name: residential_nominal_current_C_imag
    annotations:
      order:
        tag: order
        value: 59
      value_type:
        tag: value_type
        value: float
      precision:
        tag: precision
        value: 6
      native_name:
        tag: native_name
        value: residential_nominal_current_C_imag[A]
    description: posted current on phase C, imag, from a residential object, if attached
    from_schema: https://gridlabd.org/schema/glm/powerflow/node
    rank: 1000
    domain_of:
    - node
    range: float
    required: false
    unit:
      ucum_code: A
  house_present:
    name: house_present
    annotations:
      order:
        tag: order
        value: 60
      value_type:
        tag: value_type
        value: bool
      native_name:
        tag: native_name
        value: house_present
    description: boolean for detecting whether a house is attached, not an input
    from_schema: https://gridlabd.org/schema/glm/powerflow/node
    rank: 1000
    domain_of:
    - node
    - triplex_node
    range: boolean
    required: false
  mean_repair_time:
    name: mean_repair_time
    annotations:
      order:
        tag: order
        value: 61
      value_type:
        tag: value_type
        value: float
      precision:
        tag: precision
        value: 6
      native_name:
        tag: native_name
        value: mean_repair_time[s]
    description: Time after a fault clears for the object to be back in service
    from_schema: https://gridlabd.org/schema/glm/powerflow/node
    domain_of:
    - link
    - node
    range: float
    required: false
    unit:
      ucum_code: s
  frequency_measure_type:
    name: frequency_measure_type
    annotations:
      order:
        tag: order
        value: 62
      value_type:
        tag: value_type
        value: string
      native_name:
        tag: native_name
        value: frequency_measure_type
    description: PLL frequency measurement
    from_schema: https://gridlabd.org/schema/glm/powerflow/node
    rank: 1000
    domain_of:
    - node
    - triplex_node
    range: string
    required: false
  sfm_Tf:
    name: sfm_Tf
    annotations:
      order:
        tag: order
        value: 63
      value_type:
        tag: value_type
        value: float
      precision:
        tag: precision
        value: 6
      native_name:
        tag: native_name
        value: sfm_Tf[s]
    description: Transducer time constant for simplified frequency measurement (seconds)
    from_schema: https://gridlabd.org/schema/glm/powerflow/node
    rank: 1000
    domain_of:
    - node
    - triplex_node
    range: float
    required: false
    unit:
      ucum_code: s
  pll_Kp:
    name: pll_Kp
    annotations:
      order:
        tag: order
        value: 64
      value_type:
        tag: value_type
        value: float
      precision:
        tag: precision
        value: 6
      native_name:
        tag: native_name
        value: pll_Kp[pu]
    description: Proportional gain of PLL frequency measurement
    from_schema: https://gridlabd.org/schema/glm/powerflow/node
    rank: 1000
    domain_of:
    - node
    - triplex_node
    range: float
    required: false
    unit:
      ucum_code: pu
  pll_Ki:
    name: pll_Ki
    annotations:
      order:
        tag: order
        value: 65
      value_type:
        tag: value_type
        value: float
      precision:
        tag: precision
        value: 6
      native_name:
        tag: native_name
        value: pll_Ki[pu]
    description: Integration gain of PLL frequency measurement
    from_schema: https://gridlabd.org/schema/glm/powerflow/node
    rank: 1000
    domain_of:
    - node
    - triplex_node
    range: float
    required: false
    unit:
      ucum_code: pu
  measured_angle_A:
    name: measured_angle_A
    annotations:
      order:
        tag: order
        value: 66
      value_type:
        tag: value_type
        value: float
      precision:
        tag: precision
        value: 6
      native_name:
        tag: native_name
        value: measured_angle_A[rad]
    description: bus angle measurement, phase A
    from_schema: https://gridlabd.org/schema/glm/powerflow/node
    rank: 1000
    domain_of:
    - node
    range: float
    required: false
    unit:
      ucum_code: rad
  measured_frequency_A:
    name: measured_frequency_A
    annotations:
      order:
        tag: order
        value: 67
      value_type:
        tag: value_type
        value: float
      precision:
        tag: precision
        value: 6
      native_name:
        tag: native_name
        value: measured_frequency_A[Hz]
    description: frequency measurement, phase A
    from_schema: https://gridlabd.org/schema/glm/powerflow/node
    rank: 1000
    domain_of:
    - node
    range: float
    required: false
    unit:
      ucum_code: Hz
  measured_angle_B:
    name: measured_angle_B
    annotations:
      order:
        tag: order
        value: 68
      value_type:
        tag: value_type
        value: float
      precision:
        tag: precision
        value: 6
      native_name:
        tag: native_name
        value: measured_angle_B[rad]
    description: bus angle measurement, phase B
    from_schema: https://gridlabd.org/schema/glm/powerflow/node
    rank: 1000
    domain_of:
    - node
    range: float
    required: false
    unit:
      ucum_code: rad
  measured_frequency_B:
    name: measured_frequency_B
    annotations:
      order:
        tag: order
        value: 69
      value_type:
        tag: value_type
        value: float
      precision:
        tag: precision
        value: 6
      native_name:
        tag: native_name
        value: measured_frequency_B[Hz]
    description: frequency measurement, phase B
    from_schema: https://gridlabd.org/schema/glm/powerflow/node
    rank: 1000
    domain_of:
    - node
    range: float
    required: false
    unit:
      ucum_code: Hz
  measured_angle_C:
    name: measured_angle_C
    annotations:
      order:
        tag: order
        value: 70
      value_type:
        tag: value_type
        value: float
      precision:
        tag: precision
        value: 6
      native_name:
        tag: native_name
        value: measured_angle_C[rad]
    description: bus angle measurement, phase C
    from_schema: https://gridlabd.org/schema/glm/powerflow/node
    rank: 1000
    domain_of:
    - node
    range: float
    required: false
    unit:
      ucum_code: rad
  measured_frequency_C:
    name: measured_frequency_C
    annotations:
      order:
        tag: order
        value: 71
      value_type:
        tag: value_type
        value: float
      precision:
        tag: precision
        value: 6
      native_name:
        tag: native_name
        value: measured_frequency_C[Hz]
    description: frequency measurement, phase C
    from_schema: https://gridlabd.org/schema/glm/powerflow/node
    rank: 1000
    domain_of:
    - node
    range: float
    required: false
    unit:
      ucum_code: Hz
  measured_frequency:
    name: measured_frequency
    annotations:
      order:
        tag: order
        value: 72
      value_type:
        tag: value_type
        value: float
      precision:
        tag: precision
        value: 6
      native_name:
        tag: native_name
        value: measured_frequency[Hz]
    description: frequency measurement - average of present phases
    from_schema: https://gridlabd.org/schema/glm/powerflow/node
    rank: 1000
    domain_of:
    - node
    - triplex_node
    range: float
    required: false
    unit:
      ucum_code: Hz
  service_status:
    name: service_status
    annotations:
      order:
        tag: order
        value: 73
      value_type:
        tag: value_type
        value: string
      native_name:
        tag: native_name
        value: service_status
    description: In and out of service flag
    from_schema: https://gridlabd.org/schema/glm/powerflow/node
    rank: 1000
    domain_of:
    - node
    - triplex_node
    range: string
    required: false
  service_status_double:
    name: service_status_double
    annotations:
      order:
        tag: order
        value: 74
      value_type:
        tag: value_type
        value: float
      precision:
        tag: precision
        value: 6
      native_name:
        tag: native_name
        value: service_status_double
    description: In and out of service flag - type double - will indiscriminately
      override service_status - useful for schedules
    from_schema: https://gridlabd.org/schema/glm/powerflow/node
    rank: 1000
    domain_of:
    - node
    - triplex_node
    range: float
    required: false
  previous_uptime:
    name: previous_uptime
    annotations:
      order:
        tag: order
        value: 75
      value_type:
        tag: value_type
        value: float
      precision:
        tag: precision
        value: 6
      native_name:
        tag: native_name
        value: previous_uptime[min]
    description: Previous time between disconnects of node in minutes
    from_schema: https://gridlabd.org/schema/glm/powerflow/node
    rank: 1000
    domain_of:
    - node
    - triplex_node
    range: float
    required: false
    unit:
      ucum_code: min
  current_uptime:
    name: current_uptime
    annotations:
      order:
        tag: order
        value: 76
      value_type:
        tag: value_type
        value: float
      precision:
        tag: precision
        value: 6
      native_name:
        tag: native_name
        value: current_uptime[min]
    description: Current time since last disconnect of node in minutes
    from_schema: https://gridlabd.org/schema/glm/powerflow/node
    rank: 1000
    domain_of:
    - node
    - triplex_node
    range: float
    required: false
    unit:
      ucum_code: min
  Norton_dynamic:
    name: Norton_dynamic
    annotations:
      order:
        tag: order
        value: 77
      value_type:
        tag: value_type
        value: bool
      native_name:
        tag: native_name
        value: Norton_dynamic
    description: Flag to indicate a Norton-equivalent connection -- used for generators
      and deltamode
    from_schema: https://gridlabd.org/schema/glm/powerflow/node
    rank: 1000
    domain_of:
    - node
    - triplex_node
    range: boolean
    required: false
  Norton_dynamic_child:
    name: Norton_dynamic_child
    annotations:
      order:
        tag: order
        value: 78
      value_type:
        tag: value_type
        value: bool
      native_name:
        tag: native_name
        value: Norton_dynamic_child
    description: Flag to indicate a Norton-equivalent connection is made by a childed
      node object -- used for generators and deltamode
    from_schema: https://gridlabd.org/schema/glm/powerflow/node
    rank: 1000
    domain_of:
    - node
    - triplex_node
    range: boolean
    required: false
  generator_dynamic:
    name: generator_dynamic
    annotations:
      order:
        tag: order
        value: 79
      value_type:
        tag: value_type
        value: bool
      native_name:
        tag: native_name
        value: generator_dynamic
    description: Flag to indicate a voltage-sourcing or swing-type generator is present
      -- used for generators and deltamode
    from_schema: https://gridlabd.org/schema/glm/powerflow/node
    rank: 1000
    domain_of:
    - node
    - triplex_node
    range: boolean
    required: false
  reset_disabled_island_state:
    name: reset_disabled_island_state
    annotations:
      order:
        tag: order
        value: 80
      value_type:
        tag: value_type
        value: bool
      native_name:
        tag: native_name
        value: reset_disabled_island_state
    description: Deltamode/multi-island flag -- used to reset disabled status (and
      reform an island)
    from_schema: https://gridlabd.org/schema/glm/powerflow/node
    rank: 1000
    domain_of:
    - node
    - triplex_node
    range: boolean
    required: false
  GFA_enable:
    name: GFA_enable
    annotations:
      order:
        tag: order
        value: 81
      value_type:
        tag: value_type
        value: bool
      native_name:
        tag: native_name
        value: GFA_enable
    description: Disable/Enable Grid Friendly Appliance(TM)-type functionality
    from_schema: https://gridlabd.org/schema/glm/powerflow/node
    rank: 1000
    domain_of:
    - node
    - triplex_node
    range: boolean
    required: false
  GFA_freq_low_trip:
    name: GFA_freq_low_trip
    annotations:
      order:
        tag: order
        value: 82
      value_type:
        tag: value_type
        value: float
      precision:
        tag: precision
        value: 6
      native_name:
        tag: native_name
        value: GFA_freq_low_trip[Hz]
    description: Low frequency trip point for Grid Friendly Appliance(TM)-type functionality
    from_schema: https://gridlabd.org/schema/glm/powerflow/node
    rank: 1000
    domain_of:
    - node
    - triplex_node
    range: float
    required: false
    unit:
      ucum_code: Hz
  GFA_freq_high_trip:
    name: GFA_freq_high_trip
    annotations:
      order:
        tag: order
        value: 83
      value_type:
        tag: value_type
        value: float
      precision:
        tag: precision
        value: 6
      native_name:
        tag: native_name
        value: GFA_freq_high_trip[Hz]
    description: High frequency trip point for Grid Friendly Appliance(TM)-type functionality
    from_schema: https://gridlabd.org/schema/glm/powerflow/node
    rank: 1000
    domain_of:
    - node
    - triplex_node
    range: float
    required: false
    unit:
      ucum_code: Hz
  GFA_volt_low_trip:
    name: GFA_volt_low_trip
    annotations:
      order:
        tag: order
        value: 84
      value_type:
        tag: value_type
        value: float
      precision:
        tag: precision
        value: 6
      native_name:
        tag: native_name
        value: GFA_volt_low_trip[pu]
    description: Low voltage trip point for Grid Friendly Appliance(TM)-type functionality
    from_schema: https://gridlabd.org/schema/glm/powerflow/node
    rank: 1000
    domain_of:
    - node
    - triplex_node
    range: float
    required: false
    unit:
      ucum_code: pu
  GFA_volt_high_trip:
    name: GFA_volt_high_trip
    annotations:
      order:
        tag: order
        value: 85
      value_type:
        tag: value_type
        value: float
      precision:
        tag: precision
        value: 6
      native_name:
        tag: native_name
        value: GFA_volt_high_trip[pu]
    description: High voltage trip point for Grid Friendly Appliance(TM)-type functionality
    from_schema: https://gridlabd.org/schema/glm/powerflow/node
    rank: 1000
    domain_of:
    - node
    - triplex_node
    range: float
    required: false
    unit:
      ucum_code: pu
  GFA_reconnect_time:
    name: GFA_reconnect_time
    annotations:
      order:
        tag: order
        value: 86
      value_type:
        tag: value_type
        value: float
      precision:
        tag: precision
        value: 6
      native_name:
        tag: native_name
        value: GFA_reconnect_time[s]
    description: Reconnect time for Grid Friendly Appliance(TM)-type functionality
    from_schema: https://gridlabd.org/schema/glm/powerflow/node
    rank: 1000
    domain_of:
    - node
    - triplex_node
    range: float
    required: false
    unit:
      ucum_code: s
  GFA_freq_disconnect_time:
    name: GFA_freq_disconnect_time
    annotations:
      order:
        tag: order
        value: 87
      value_type:
        tag: value_type
        value: float
      precision:
        tag: precision
        value: 6
      native_name:
        tag: native_name
        value: GFA_freq_disconnect_time[s]
    description: Frequency violation disconnect time for Grid Friendly Appliance(TM)-type
      functionality
    from_schema: https://gridlabd.org/schema/glm/powerflow/node
    rank: 1000
    domain_of:
    - node
    - triplex_node
    range: float
    required: false
    unit:
      ucum_code: s
  GFA_volt_disconnect_time:
    name: GFA_volt_disconnect_time
    annotations:
      order:
        tag: order
        value: 88
      value_type:
        tag: value_type
        value: float
      precision:
        tag: precision
        value: 6
      native_name:
        tag: native_name
        value: GFA_volt_disconnect_time[s]
    description: Voltage violation disconnect time for Grid Friendly Appliance(TM)-type
      functionality
    from_schema: https://gridlabd.org/schema/glm/powerflow/node
    rank: 1000
    domain_of:
    - node
    - triplex_node
    range: float
    required: false
    unit:
      ucum_code: s
  GFA_status:
    name: GFA_status
    annotations:
      order:
        tag: order
        value: 89
      value_type:
        tag: value_type
        value: bool
      native_name:
        tag: native_name
        value: GFA_status
    description: Grid Friendly Appliance(TM)-type functionality - whether it is in
      service (not tripped) or not
    from_schema: https://gridlabd.org/schema/glm/powerflow/node
    rank: 1000
    domain_of:
    - node
    - triplex_node
    range: boolean
    required: false
  GFA_trip_method:
    name: GFA_trip_method
    annotations:
      order:
        tag: order
        value: 90
      value_type:
        tag: value_type
        value: string
      native_name:
        tag: native_name
        value: GFA_trip_method
    description: GFA trip for over-voltage
    from_schema: https://gridlabd.org/schema/glm/powerflow/node
    rank: 1000
    domain_of:
    - node
    - triplex_node
    range: string
    required: false
  topological_parent:
    name: topological_parent
    annotations:
      order:
        tag: order
        value: 91
      value_type:
        tag: value_type
        value: string
      native_name:
        tag: native_name
        value: topological_parent
    description: topological parent as per GLM configuration
    from_schema: https://gridlabd.org/schema/glm/powerflow/node
    rank: 1000
    domain_of:
    - node
    - triplex_node
    range: string
    required: false
  behaving_as_swing:
    name: behaving_as_swing
    annotations:
      order:
        tag: order
        value: 92
      value_type:
        tag: value_type
        value: bool
      native_name:
        tag: native_name
        value: behaving_as_swing
    description: Indicator flag for if a bus is behaving as a reference voltage source
      - valid for a SWING or SWING_PQ
    from_schema: https://gridlabd.org/schema/glm/powerflow/node
    rank: 1000
    domain_of:
    - node
    - triplex_node
    range: boolean
    required: false

Induced

name: node
description: 'Copyright (C) 2008 Battelle Memorial Institute

  @file node.cpp

  @addtogroup powerflow_node Node

  @ingroup powerflow_object

  The node is one of the major components of the method used for solving a

  powerflow network.  In essense the distribution network can be seen as a

  series of nodes and links.  Nodes primary responsibility is to act as an

  aggregation point for the links that are attached to it, and to hold the

  current and voltage values that will be used in the matrix calculations

  done in the link.

  Three types of nodes are defined in this file.  Nodes are simply a basic

  object that exports the voltages for each phase.  Triplex nodes export

  voltages for 3 lines; line1_voltage, line2_voltage, lineN_voltage.

  @par Voltage control

  When the global variable require_voltage_control is set to @p true,

  the bus type is used to determine how voltage control is implemented.

  Voltage control is only performed when the bus has no link that

  considers it a to node.  When the flag #NF_HASSOURCE is cleared, then

  the following is in effect:

  - #SWING buses are considered infinite sources and the voltage will

  remain fixed regardless of conditions.

  - #PV buses are considered constrained sources and the voltage will

  fall to zero if there is insufficient voltage support at the bus.

  A generator object is required to provide the voltage support explicitly.

  The voltage will be set to zero if the generator does not provide

  sufficient support.

  - #PQ buses will always go to zero voltage.

  @par Fault support

  The following conditions are used to describe a fault impedance @e X (e.g., 1e-6),

  between phase @e x and neutral or group, or between phases @e x and @e y, and leaving

  phase @e z unaffected at iteration @e t:

  - @e phase-to-phase contact at the node

  - @e Forward-sweep: @f$ V_x(t) = V_y(t) = @frac{V_x(t-1) + V_y(t-1)}{2} @f$

  - @e Back-sweep: @f$ I_x(t+1) = -I_y(t+1) = @frac{V_x(t)-V_y(t)}{X} @f$;

  - @e phase-to-ground/neutral contact at the node

  - @e Forward-sweep: @f$ V_x(t) = @frac{1}{2} V_x(t-1)  @f$

  - @e Back-sweep: @f$ I_x(t+1) = @frac{V_x(t)}{X} @f$;

  @{


  Inherits from: powerflow_object


  Type: Instance (network topology element)'
comments:
- 'Import: ConnectivityNode, mRID = name (bus.cimtbl), one per root bus; a node, meter
  or substation with its own power_X, current_X or shunt_X set raises; a bustype SWING
  node also gives EnergySource, mRID src_ + name (source.cimtbl). Export: every ConnectivityNode
  without an EnergySource on a three- or single-phase zone.'
from_schema: https://gridlabd.org/schema/glm
exact_mappings:
- cim:ConnectivityNode
close_mappings:
- cim:EnergySource
is_a: powerflow_object
attributes:
  bustype:
    name: bustype
    annotations:
      order:
        tag: order
        value: 1
      value_type:
        tag: value_type
        value: string
      native_name:
        tag: native_name
        value: bustype
    description: defines whether the node is a PQ, PV, or SWING node
    comments:
    - 'Import: SWING makes an EnergySource; PQ, PV and SWING_PQ are a plain bus (SWING_PQ
      is a swing only when islanded). Export: SWING on the substation only.'
    from_schema: https://gridlabd.org/schema/glm/powerflow/node
    related_mappings:
    - cim:EnergySource
    rank: 1000
    owner: node
    domain_of:
    - node
    - triplex_node
    range: string
    required: false
  busflags:
    name: busflags
    annotations:
      order:
        tag: order
        value: 2
      value_type:
        tag: value_type
        value: string
      native_name:
        tag: native_name
        value: busflags
    description: flag indicates node has a source for voltage, i.e. connects to the
      swing node
    from_schema: https://gridlabd.org/schema/glm/powerflow/node
    rank: 1000
    owner: node
    domain_of:
    - node
    - triplex_node
    range: string
    required: false
  reference_bus:
    name: reference_bus
    annotations:
      order:
        tag: order
        value: 3
      value_type:
        tag: value_type
        value: string
      native_name:
        tag: native_name
        value: reference_bus
    description: reference bus from which frequency is defined
    from_schema: https://gridlabd.org/schema/glm/powerflow/node
    rank: 1000
    owner: node
    domain_of:
    - node
    - triplex_node
    range: string
    required: false
  maximum_voltage_error:
    name: maximum_voltage_error
    annotations:
      order:
        tag: order
        value: 4
      value_type:
        tag: value_type
        value: float
      precision:
        tag: precision
        value: 6
      native_name:
        tag: native_name
        value: maximum_voltage_error[V]
    description: convergence voltage limit or convergence criteria
    from_schema: https://gridlabd.org/schema/glm/powerflow/node
    rank: 1000
    owner: node
    domain_of:
    - node
    - triplex_node
    range: float
    required: false
    unit:
      ucum_code: V
  voltage_A:
    name: voltage_A
    annotations:
      order:
        tag: order
        value: 5
      value_type:
        tag: value_type
        value: complex
      native_name:
        tag: native_name
        value: voltage_A[V]
    description: bus voltage, Phase A to ground
    comments:
    - 'Import: on a SWING bus only: EnergySource.voltageMagnitude (line to line) and
      voltageAngle (deg) from |V| and arg(V); elsewhere the solver guess, not converted.
      Export: not written.'
    from_schema: https://gridlabd.org/schema/glm/powerflow/node
    close_mappings:
    - cim:EnergySource.voltageMagnitude
    - cim:EnergySource.voltageAngle
    rank: 1000
    owner: node
    domain_of:
    - node
    - rectifier
    - windturb_dg
    range: Complex
    required: false
    unit:
      ucum_code: V
  voltage_B:
    name: voltage_B
    annotations:
      order:
        tag: order
        value: 6
      value_type:
        tag: value_type
        value: complex
      native_name:
        tag: native_name
        value: voltage_B[V]
    description: bus voltage, Phase B to ground
    from_schema: https://gridlabd.org/schema/glm/powerflow/node
    rank: 1000
    owner: node
    domain_of:
    - node
    - rectifier
    - windturb_dg
    range: Complex
    required: false
    unit:
      ucum_code: V
  voltage_C:
    name: voltage_C
    annotations:
      order:
        tag: order
        value: 7
      value_type:
        tag: value_type
        value: complex
      native_name:
        tag: native_name
        value: voltage_C[V]
    description: bus voltage, Phase C to ground
    from_schema: https://gridlabd.org/schema/glm/powerflow/node
    rank: 1000
    owner: node
    domain_of:
    - node
    - rectifier
    - windturb_dg
    range: Complex
    required: false
    unit:
      ucum_code: V
  voltage_AB:
    name: voltage_AB
    annotations:
      order:
        tag: order
        value: 8
      value_type:
        tag: value_type
        value: complex
      native_name:
        tag: native_name
        value: voltage_AB[V]
    description: line voltages, Phase AB
    from_schema: https://gridlabd.org/schema/glm/powerflow/node
    rank: 1000
    owner: node
    domain_of:
    - node
    range: Complex
    required: false
    unit:
      ucum_code: V
  voltage_BC:
    name: voltage_BC
    annotations:
      order:
        tag: order
        value: 9
      value_type:
        tag: value_type
        value: complex
      native_name:
        tag: native_name
        value: voltage_BC[V]
    description: line voltages, Phase BC
    from_schema: https://gridlabd.org/schema/glm/powerflow/node
    rank: 1000
    owner: node
    domain_of:
    - node
    range: Complex
    required: false
    unit:
      ucum_code: V
  voltage_CA:
    name: voltage_CA
    annotations:
      order:
        tag: order
        value: 10
      value_type:
        tag: value_type
        value: complex
      native_name:
        tag: native_name
        value: voltage_CA[V]
    description: line voltages, Phase CA
    from_schema: https://gridlabd.org/schema/glm/powerflow/node
    rank: 1000
    owner: node
    domain_of:
    - node
    range: Complex
    required: false
    unit:
      ucum_code: V
  current_A:
    name: current_A
    annotations:
      order:
        tag: order
        value: 11
      value_type:
        tag: value_type
        value: complex
      native_name:
        tag: native_name
        value: current_A[A]
    description: bus current injection (in = positive), this an accumulator only,
      not a output or input variable
    from_schema: https://gridlabd.org/schema/glm/powerflow/node
    rank: 1000
    owner: node
    domain_of:
    - node
    - rectifier
    - windturb_dg
    range: Complex
    required: false
    unit:
      ucum_code: A
  current_B:
    name: current_B
    annotations:
      order:
        tag: order
        value: 12
      value_type:
        tag: value_type
        value: complex
      native_name:
        tag: native_name
        value: current_B[A]
    description: bus current injection (in = positive), this an accumulator only,
      not a output or input variable
    from_schema: https://gridlabd.org/schema/glm/powerflow/node
    rank: 1000
    owner: node
    domain_of:
    - node
    - rectifier
    - windturb_dg
    range: Complex
    required: false
    unit:
      ucum_code: A
  current_C:
    name: current_C
    annotations:
      order:
        tag: order
        value: 13
      value_type:
        tag: value_type
        value: complex
      native_name:
        tag: native_name
        value: current_C[A]
    description: bus current injection (in = positive), this an accumulator only,
      not a output or input variable
    from_schema: https://gridlabd.org/schema/glm/powerflow/node
    rank: 1000
    owner: node
    domain_of:
    - node
    - rectifier
    - windturb_dg
    range: Complex
    required: false
    unit:
      ucum_code: A
  power_A:
    name: power_A
    annotations:
      order:
        tag: order
        value: 14
      value_type:
        tag: value_type
        value: complex
      native_name:
        tag: native_name
        value: power_A[VA]
    description: bus power injection (in = positive), this an accumulator only, not
      a output or input variable
    from_schema: https://gridlabd.org/schema/glm/powerflow/node
    rank: 1000
    owner: node
    domain_of:
    - node
    - inverter
    - inverter_dyn
    - windturb_dg
    range: Complex
    required: false
    unit:
      ucum_code: VA
  power_B:
    name: power_B
    annotations:
      order:
        tag: order
        value: 15
      value_type:
        tag: value_type
        value: complex
      native_name:
        tag: native_name
        value: power_B[VA]
    description: bus power injection (in = positive), this an accumulator only, not
      a output or input variable
    from_schema: https://gridlabd.org/schema/glm/powerflow/node
    rank: 1000
    owner: node
    domain_of:
    - node
    - inverter
    - inverter_dyn
    - windturb_dg
    range: Complex
    required: false
    unit:
      ucum_code: VA
  power_C:
    name: power_C
    annotations:
      order:
        tag: order
        value: 16
      value_type:
        tag: value_type
        value: complex
      native_name:
        tag: native_name
        value: power_C[VA]
    description: bus power injection (in = positive), this an accumulator only, not
      a output or input variable
    from_schema: https://gridlabd.org/schema/glm/powerflow/node
    rank: 1000
    owner: node
    domain_of:
    - node
    - inverter
    - inverter_dyn
    - windturb_dg
    range: Complex
    required: false
    unit:
      ucum_code: VA
  shunt_A:
    name: shunt_A
    annotations:
      order:
        tag: order
        value: 17
      value_type:
        tag: value_type
        value: complex
      native_name:
        tag: native_name
        value: shunt_A[S]
    description: bus shunt admittance, this an accumulator only, not a output or input
      variable
    from_schema: https://gridlabd.org/schema/glm/powerflow/node
    rank: 1000
    owner: node
    domain_of:
    - node
    range: Complex
    required: false
    unit:
      ucum_code: S
  shunt_B:
    name: shunt_B
    annotations:
      order:
        tag: order
        value: 18
      value_type:
        tag: value_type
        value: complex
      native_name:
        tag: native_name
        value: shunt_B[S]
    description: bus shunt admittance, this an accumulator only, not a output or input
      variable
    from_schema: https://gridlabd.org/schema/glm/powerflow/node
    rank: 1000
    owner: node
    domain_of:
    - node
    range: Complex
    required: false
    unit:
      ucum_code: S
  shunt_C:
    name: shunt_C
    annotations:
      order:
        tag: order
        value: 19
      value_type:
        tag: value_type
        value: complex
      native_name:
        tag: native_name
        value: shunt_C[S]
    description: bus shunt admittance, this an accumulator only, not a output or input
      variable
    from_schema: https://gridlabd.org/schema/glm/powerflow/node
    rank: 1000
    owner: node
    domain_of:
    - node
    range: Complex
    required: false
    unit:
      ucum_code: S
  prerotated_current_A:
    name: prerotated_current_A
    annotations:
      order:
        tag: order
        value: 20
      value_type:
        tag: value_type
        value: complex
      native_name:
        tag: native_name
        value: prerotated_current_A[A]
    description: deltamode-functionality - bus current injection (in = positive),
      but will not be rotated by powerflow for off-nominal frequency, this an accumulator
      only, not a output or input variable
    from_schema: https://gridlabd.org/schema/glm/powerflow/node
    rank: 1000
    owner: node
    domain_of:
    - node
    range: Complex
    required: false
    unit:
      ucum_code: A
  prerotated_current_B:
    name: prerotated_current_B
    annotations:
      order:
        tag: order
        value: 21
      value_type:
        tag: value_type
        value: complex
      native_name:
        tag: native_name
        value: prerotated_current_B[A]
    description: deltamode-functionality - bus current injection (in = positive),
      but will not be rotated by powerflow for off-nominal frequency, this an accumulator
      only, not a output or input variable
    from_schema: https://gridlabd.org/schema/glm/powerflow/node
    rank: 1000
    owner: node
    domain_of:
    - node
    range: Complex
    required: false
    unit:
      ucum_code: A
  prerotated_current_C:
    name: prerotated_current_C
    annotations:
      order:
        tag: order
        value: 22
      value_type:
        tag: value_type
        value: complex
      native_name:
        tag: native_name
        value: prerotated_current_C[A]
    description: deltamode-functionality - bus current injection (in = positive),
      but will not be rotated by powerflow for off-nominal frequency, this an accumulator
      only, not a output or input variable
    from_schema: https://gridlabd.org/schema/glm/powerflow/node
    rank: 1000
    owner: node
    domain_of:
    - node
    range: Complex
    required: false
    unit:
      ucum_code: A
  deltamode_generator_current_A:
    name: deltamode_generator_current_A
    annotations:
      order:
        tag: order
        value: 23
      value_type:
        tag: value_type
        value: complex
      native_name:
        tag: native_name
        value: deltamode_generator_current_A[A]
    description: deltamode-functionality - bus current injection (in = positive),
      direct generator injection (so may be overwritten internally), this an accumulator
      only, not a output or input variable
    from_schema: https://gridlabd.org/schema/glm/powerflow/node
    rank: 1000
    owner: node
    domain_of:
    - node
    range: Complex
    required: false
    unit:
      ucum_code: A
  deltamode_generator_current_B:
    name: deltamode_generator_current_B
    annotations:
      order:
        tag: order
        value: 24
      value_type:
        tag: value_type
        value: complex
      native_name:
        tag: native_name
        value: deltamode_generator_current_B[A]
    description: deltamode-functionality - bus current injection (in = positive),
      direct generator injection (so may be overwritten internally), this an accumulator
      only, not a output or input variable
    from_schema: https://gridlabd.org/schema/glm/powerflow/node
    rank: 1000
    owner: node
    domain_of:
    - node
    range: Complex
    required: false
    unit:
      ucum_code: A
  deltamode_generator_current_C:
    name: deltamode_generator_current_C
    annotations:
      order:
        tag: order
        value: 25
      value_type:
        tag: value_type
        value: complex
      native_name:
        tag: native_name
        value: deltamode_generator_current_C[A]
    description: deltamode-functionality - bus current injection (in = positive),
      direct generator injection (so may be overwritten internally), this an accumulator
      only, not a output or input variable
    from_schema: https://gridlabd.org/schema/glm/powerflow/node
    rank: 1000
    owner: node
    domain_of:
    - node
    range: Complex
    required: false
    unit:
      ucum_code: A
  deltamode_PGenTotal:
    name: deltamode_PGenTotal
    annotations:
      order:
        tag: order
        value: 26
      value_type:
        tag: value_type
        value: complex
      native_name:
        tag: native_name
        value: deltamode_PGenTotal
    description: deltamode-functionality - power value for a diesel generator -- accumulator
      only, not an output or input
    from_schema: https://gridlabd.org/schema/glm/powerflow/node
    rank: 1000
    owner: node
    domain_of:
    - node
    - triplex_node
    range: Complex
    required: false
  deltamode_full_Y_matrix:
    name: deltamode_full_Y_matrix
    annotations:
      order:
        tag: order
        value: 27
      value_type:
        tag: value_type
        value: string
      native_name:
        tag: native_name
        value: deltamode_full_Y_matrix
    description: deltamode-functionality full_Y matrix exposes so generator objects
      can interact for Norton equivalents
    from_schema: https://gridlabd.org/schema/glm/powerflow/node
    rank: 1000
    owner: node
    domain_of:
    - node
    - triplex_node
    range: string
    required: false
  deltamode_full_Y_all_matrix:
    name: deltamode_full_Y_all_matrix
    annotations:
      order:
        tag: order
        value: 28
      value_type:
        tag: value_type
        value: string
      native_name:
        tag: native_name
        value: deltamode_full_Y_all_matrix
    description: deltamode-functionality full_Y_all matrix exposes so generator objects
      can interact for Norton equivalents
    from_schema: https://gridlabd.org/schema/glm/powerflow/node
    rank: 1000
    owner: node
    domain_of:
    - node
    - triplex_node
    range: string
    required: false
  NR_powerflow_parent:
    name: NR_powerflow_parent
    annotations:
      order:
        tag: order
        value: 29
      value_type:
        tag: value_type
        value: string
      native_name:
        tag: native_name
        value: NR_powerflow_parent
    description: NR powerflow - actual powerflow parent - used by generators accessing
      child objects
    from_schema: https://gridlabd.org/schema/glm/powerflow/node
    rank: 1000
    owner: node
    domain_of:
    - node
    - triplex_node
    range: string
    required: false
  current_inj_A:
    name: current_inj_A
    annotations:
      order:
        tag: order
        value: 30
      value_type:
        tag: value_type
        value: complex
      native_name:
        tag: native_name
        value: current_inj_A[A]
    description: bus current injection (in = positive), but will not be rotated by
      powerflow for off-nominal frequency, this an accumulator only, not a output
      or input variable
    from_schema: https://gridlabd.org/schema/glm/powerflow/node
    rank: 1000
    owner: node
    domain_of:
    - node
    range: Complex
    required: false
    unit:
      ucum_code: A
  current_inj_B:
    name: current_inj_B
    annotations:
      order:
        tag: order
        value: 31
      value_type:
        tag: value_type
        value: complex
      native_name:
        tag: native_name
        value: current_inj_B[A]
    description: bus current injection (in = positive), but will not be rotated by
      powerflow for off-nominal frequency, this an accumulator only, not a output
      or input variable
    from_schema: https://gridlabd.org/schema/glm/powerflow/node
    rank: 1000
    owner: node
    domain_of:
    - node
    range: Complex
    required: false
    unit:
      ucum_code: A
  current_inj_C:
    name: current_inj_C
    annotations:
      order:
        tag: order
        value: 32
      value_type:
        tag: value_type
        value: complex
      native_name:
        tag: native_name
        value: current_inj_C[A]
    description: bus current injection (in = positive), but will not be rotated by
      powerflow for off-nominal frequency, this an accumulator only, not a output
      or input variable
    from_schema: https://gridlabd.org/schema/glm/powerflow/node
    rank: 1000
    owner: node
    domain_of:
    - node
    range: Complex
    required: false
    unit:
      ucum_code: A
  current_AB:
    name: current_AB
    annotations:
      order:
        tag: order
        value: 33
      value_type:
        tag: value_type
        value: complex
      native_name:
        tag: native_name
        value: current_AB[A]
    description: bus current delta-connected injection (in = positive), this an accumulator
      only, not a output or input variable
    from_schema: https://gridlabd.org/schema/glm/powerflow/node
    rank: 1000
    owner: node
    domain_of:
    - node
    range: Complex
    required: false
    unit:
      ucum_code: A
  current_BC:
    name: current_BC
    annotations:
      order:
        tag: order
        value: 34
      value_type:
        tag: value_type
        value: complex
      native_name:
        tag: native_name
        value: current_BC[A]
    description: bus current delta-connected injection (in = positive), this an accumulator
      only, not a output or input variable
    from_schema: https://gridlabd.org/schema/glm/powerflow/node
    rank: 1000
    owner: node
    domain_of:
    - node
    range: Complex
    required: false
    unit:
      ucum_code: A
  current_CA:
    name: current_CA
    annotations:
      order:
        tag: order
        value: 35
      value_type:
        tag: value_type
        value: complex
      native_name:
        tag: native_name
        value: current_CA[A]
    description: bus current delta-connected injection (in = positive), this an accumulator
      only, not a output or input variable
    from_schema: https://gridlabd.org/schema/glm/powerflow/node
    rank: 1000
    owner: node
    domain_of:
    - node
    range: Complex
    required: false
    unit:
      ucum_code: A
  current_AN:
    name: current_AN
    annotations:
      order:
        tag: order
        value: 36
      value_type:
        tag: value_type
        value: complex
      native_name:
        tag: native_name
        value: current_AN[A]
    description: bus current wye-connected injection (in = positive), this an accumulator
      only, not a output or input variable
    from_schema: https://gridlabd.org/schema/glm/powerflow/node
    rank: 1000
    owner: node
    domain_of:
    - node
    range: Complex
    required: false
    unit:
      ucum_code: A
  current_BN:
    name: current_BN
    annotations:
      order:
        tag: order
        value: 37
      value_type:
        tag: value_type
        value: complex
      native_name:
        tag: native_name
        value: current_BN[A]
    description: bus current wye-connected injection (in = positive), this an accumulator
      only, not a output or input variable
    from_schema: https://gridlabd.org/schema/glm/powerflow/node
    rank: 1000
    owner: node
    domain_of:
    - node
    range: Complex
    required: false
    unit:
      ucum_code: A
  current_CN:
    name: current_CN
    annotations:
      order:
        tag: order
        value: 38
      value_type:
        tag: value_type
        value: complex
      native_name:
        tag: native_name
        value: current_CN[A]
    description: bus current wye-connected injection (in = positive), this an accumulator
      only, not a output or input variable
    from_schema: https://gridlabd.org/schema/glm/powerflow/node
    rank: 1000
    owner: node
    domain_of:
    - node
    range: Complex
    required: false
    unit:
      ucum_code: A
  power_AB:
    name: power_AB
    annotations:
      order:
        tag: order
        value: 39
      value_type:
        tag: value_type
        value: complex
      native_name:
        tag: native_name
        value: power_AB[VA]
    description: bus power delta-connected injection (in = positive), this an accumulator
      only, not a output or input variable
    from_schema: https://gridlabd.org/schema/glm/powerflow/node
    rank: 1000
    owner: node
    domain_of:
    - node
    range: Complex
    required: false
    unit:
      ucum_code: VA
  power_BC:
    name: power_BC
    annotations:
      order:
        tag: order
        value: 40
      value_type:
        tag: value_type
        value: complex
      native_name:
        tag: native_name
        value: power_BC[VA]
    description: bus power delta-connected injection (in = positive), this an accumulator
      only, not a output or input variable
    from_schema: https://gridlabd.org/schema/glm/powerflow/node
    rank: 1000
    owner: node
    domain_of:
    - node
    range: Complex
    required: false
    unit:
      ucum_code: VA
  power_CA:
    name: power_CA
    annotations:
      order:
        tag: order
        value: 41
      value_type:
        tag: value_type
        value: complex
      native_name:
        tag: native_name
        value: power_CA[VA]
    description: bus power delta-connected injection (in = positive), this an accumulator
      only, not a output or input variable
    from_schema: https://gridlabd.org/schema/glm/powerflow/node
    rank: 1000
    owner: node
    domain_of:
    - node
    range: Complex
    required: false
    unit:
      ucum_code: VA
  power_AN:
    name: power_AN
    annotations:
      order:
        tag: order
        value: 42
      value_type:
        tag: value_type
        value: complex
      native_name:
        tag: native_name
        value: power_AN[VA]
    description: bus power wye-connected injection (in = positive), this an accumulator
      only, not a output or input variable
    from_schema: https://gridlabd.org/schema/glm/powerflow/node
    rank: 1000
    owner: node
    domain_of:
    - node
    range: Complex
    required: false
    unit:
      ucum_code: VA
  power_BN:
    name: power_BN
    annotations:
      order:
        tag: order
        value: 43
      value_type:
        tag: value_type
        value: complex
      native_name:
        tag: native_name
        value: power_BN[VA]
    description: bus power wye-connected injection (in = positive), this an accumulator
      only, not a output or input variable
    from_schema: https://gridlabd.org/schema/glm/powerflow/node
    rank: 1000
    owner: node
    domain_of:
    - node
    range: Complex
    required: false
    unit:
      ucum_code: VA
  power_CN:
    name: power_CN
    annotations:
      order:
        tag: order
        value: 44
      value_type:
        tag: value_type
        value: complex
      native_name:
        tag: native_name
        value: power_CN[VA]
    description: bus power wye-connected injection (in = positive), this an accumulator
      only, not a output or input variable
    from_schema: https://gridlabd.org/schema/glm/powerflow/node
    rank: 1000
    owner: node
    domain_of:
    - node
    range: Complex
    required: false
    unit:
      ucum_code: VA
  shunt_AB:
    name: shunt_AB
    annotations:
      order:
        tag: order
        value: 45
      value_type:
        tag: value_type
        value: complex
      native_name:
        tag: native_name
        value: shunt_AB[S]
    description: bus shunt delta-connected admittance, this an accumulator only, not
      a output or input variable
    from_schema: https://gridlabd.org/schema/glm/powerflow/node
    rank: 1000
    owner: node
    domain_of:
    - node
    range: Complex
    required: false
    unit:
      ucum_code: S
  shunt_BC:
    name: shunt_BC
    annotations:
      order:
        tag: order
        value: 46
      value_type:
        tag: value_type
        value: complex
      native_name:
        tag: native_name
        value: shunt_BC[S]
    description: bus shunt delta-connected admittance, this an accumulator only, not
      a output or input variable
    from_schema: https://gridlabd.org/schema/glm/powerflow/node
    rank: 1000
    owner: node
    domain_of:
    - node
    range: Complex
    required: false
    unit:
      ucum_code: S
  shunt_CA:
    name: shunt_CA
    annotations:
      order:
        tag: order
        value: 47
      value_type:
        tag: value_type
        value: complex
      native_name:
        tag: native_name
        value: shunt_CA[S]
    description: bus shunt delta-connected admittance, this an accumulator only, not
      a output or input variable
    from_schema: https://gridlabd.org/schema/glm/powerflow/node
    rank: 1000
    owner: node
    domain_of:
    - node
    range: Complex
    required: false
    unit:
      ucum_code: S
  shunt_AN:
    name: shunt_AN
    annotations:
      order:
        tag: order
        value: 48
      value_type:
        tag: value_type
        value: complex
      native_name:
        tag: native_name
        value: shunt_AN[S]
    description: bus shunt wye-connected admittance, this an accumulator only, not
      a output or input variable
    from_schema: https://gridlabd.org/schema/glm/powerflow/node
    rank: 1000
    owner: node
    domain_of:
    - node
    range: Complex
    required: false
    unit:
      ucum_code: S
  shunt_BN:
    name: shunt_BN
    annotations:
      order:
        tag: order
        value: 49
      value_type:
        tag: value_type
        value: complex
      native_name:
        tag: native_name
        value: shunt_BN[S]
    description: bus shunt wye-connected admittance, this an accumulator only, not
      a output or input variable
    from_schema: https://gridlabd.org/schema/glm/powerflow/node
    rank: 1000
    owner: node
    domain_of:
    - node
    range: Complex
    required: false
    unit:
      ucum_code: S
  shunt_CN:
    name: shunt_CN
    annotations:
      order:
        tag: order
        value: 50
      value_type:
        tag: value_type
        value: complex
      native_name:
        tag: native_name
        value: shunt_CN[S]
    description: bus shunt wye-connected admittance, this an accumulator only, not
      a output or input variable
    from_schema: https://gridlabd.org/schema/glm/powerflow/node
    rank: 1000
    owner: node
    domain_of:
    - node
    range: Complex
    required: false
    unit:
      ucum_code: S
  residential_nominal_current_A:
    name: residential_nominal_current_A
    annotations:
      order:
        tag: order
        value: 51
      value_type:
        tag: value_type
        value: complex
      native_name:
        tag: native_name
        value: residential_nominal_current_A[A]
    description: posted current on phase A from a residential object, if attached
    from_schema: https://gridlabd.org/schema/glm/powerflow/node
    rank: 1000
    owner: node
    domain_of:
    - node
    range: Complex
    required: false
    unit:
      ucum_code: A
  residential_nominal_current_B:
    name: residential_nominal_current_B
    annotations:
      order:
        tag: order
        value: 52
      value_type:
        tag: value_type
        value: complex
      native_name:
        tag: native_name
        value: residential_nominal_current_B[A]
    description: posted current on phase B from a residential object, if attached
    from_schema: https://gridlabd.org/schema/glm/powerflow/node
    rank: 1000
    owner: node
    domain_of:
    - node
    range: Complex
    required: false
    unit:
      ucum_code: A
  residential_nominal_current_C:
    name: residential_nominal_current_C
    annotations:
      order:
        tag: order
        value: 53
      value_type:
        tag: value_type
        value: complex
      native_name:
        tag: native_name
        value: residential_nominal_current_C[A]
    description: posted current on phase C from a residential object, if attached
    from_schema: https://gridlabd.org/schema/glm/powerflow/node
    rank: 1000
    owner: node
    domain_of:
    - node
    range: Complex
    required: false
    unit:
      ucum_code: A
  residential_nominal_current_A_real:
    name: residential_nominal_current_A_real
    annotations:
      order:
        tag: order
        value: 54
      value_type:
        tag: value_type
        value: float
      precision:
        tag: precision
        value: 6
      native_name:
        tag: native_name
        value: residential_nominal_current_A_real[A]
    description: posted current on phase A, real, from a residential object, if attached
    from_schema: https://gridlabd.org/schema/glm/powerflow/node
    rank: 1000
    owner: node
    domain_of:
    - node
    range: float
    required: false
    unit:
      ucum_code: A
  residential_nominal_current_A_imag:
    name: residential_nominal_current_A_imag
    annotations:
      order:
        tag: order
        value: 55
      value_type:
        tag: value_type
        value: float
      precision:
        tag: precision
        value: 6
      native_name:
        tag: native_name
        value: residential_nominal_current_A_imag[A]
    description: posted current on phase A, imag, from a residential object, if attached
    from_schema: https://gridlabd.org/schema/glm/powerflow/node
    rank: 1000
    owner: node
    domain_of:
    - node
    range: float
    required: false
    unit:
      ucum_code: A
  residential_nominal_current_B_real:
    name: residential_nominal_current_B_real
    annotations:
      order:
        tag: order
        value: 56
      value_type:
        tag: value_type
        value: float
      precision:
        tag: precision
        value: 6
      native_name:
        tag: native_name
        value: residential_nominal_current_B_real[A]
    description: posted current on phase B, real, from a residential object, if attached
    from_schema: https://gridlabd.org/schema/glm/powerflow/node
    rank: 1000
    owner: node
    domain_of:
    - node
    range: float
    required: false
    unit:
      ucum_code: A
  residential_nominal_current_B_imag:
    name: residential_nominal_current_B_imag
    annotations:
      order:
        tag: order
        value: 57
      value_type:
        tag: value_type
        value: float
      precision:
        tag: precision
        value: 6
      native_name:
        tag: native_name
        value: residential_nominal_current_B_imag[A]
    description: posted current on phase B, imag, from a residential object, if attached
    from_schema: https://gridlabd.org/schema/glm/powerflow/node
    rank: 1000
    owner: node
    domain_of:
    - node
    range: float
    required: false
    unit:
      ucum_code: A
  residential_nominal_current_C_real:
    name: residential_nominal_current_C_real
    annotations:
      order:
        tag: order
        value: 58
      value_type:
        tag: value_type
        value: float
      precision:
        tag: precision
        value: 6
      native_name:
        tag: native_name
        value: residential_nominal_current_C_real[A]
    description: posted current on phase C, real, from a residential object, if attached
    from_schema: https://gridlabd.org/schema/glm/powerflow/node
    rank: 1000
    owner: node
    domain_of:
    - node
    range: float
    required: false
    unit:
      ucum_code: A
  residential_nominal_current_C_imag:
    name: residential_nominal_current_C_imag
    annotations:
      order:
        tag: order
        value: 59
      value_type:
        tag: value_type
        value: float
      precision:
        tag: precision
        value: 6
      native_name:
        tag: native_name
        value: residential_nominal_current_C_imag[A]
    description: posted current on phase C, imag, from a residential object, if attached
    from_schema: https://gridlabd.org/schema/glm/powerflow/node
    rank: 1000
    owner: node
    domain_of:
    - node
    range: float
    required: false
    unit:
      ucum_code: A
  house_present:
    name: house_present
    annotations:
      order:
        tag: order
        value: 60
      value_type:
        tag: value_type
        value: bool
      native_name:
        tag: native_name
        value: house_present
    description: boolean for detecting whether a house is attached, not an input
    from_schema: https://gridlabd.org/schema/glm/powerflow/node
    rank: 1000
    owner: node
    domain_of:
    - node
    - triplex_node
    range: boolean
    required: false
  mean_repair_time:
    name: mean_repair_time
    annotations:
      order:
        tag: order
        value: 61
      value_type:
        tag: value_type
        value: float
      precision:
        tag: precision
        value: 6
      native_name:
        tag: native_name
        value: mean_repair_time[s]
    description: Time after a fault clears for the object to be back in service
    from_schema: https://gridlabd.org/schema/glm/powerflow/node
    owner: node
    domain_of:
    - link
    - node
    range: float
    required: false
    unit:
      ucum_code: s
  frequency_measure_type:
    name: frequency_measure_type
    annotations:
      order:
        tag: order
        value: 62
      value_type:
        tag: value_type
        value: string
      native_name:
        tag: native_name
        value: frequency_measure_type
    description: PLL frequency measurement
    from_schema: https://gridlabd.org/schema/glm/powerflow/node
    rank: 1000
    owner: node
    domain_of:
    - node
    - triplex_node
    range: string
    required: false
  sfm_Tf:
    name: sfm_Tf
    annotations:
      order:
        tag: order
        value: 63
      value_type:
        tag: value_type
        value: float
      precision:
        tag: precision
        value: 6
      native_name:
        tag: native_name
        value: sfm_Tf[s]
    description: Transducer time constant for simplified frequency measurement (seconds)
    from_schema: https://gridlabd.org/schema/glm/powerflow/node
    rank: 1000
    owner: node
    domain_of:
    - node
    - triplex_node
    range: float
    required: false
    unit:
      ucum_code: s
  pll_Kp:
    name: pll_Kp
    annotations:
      order:
        tag: order
        value: 64
      value_type:
        tag: value_type
        value: float
      precision:
        tag: precision
        value: 6
      native_name:
        tag: native_name
        value: pll_Kp[pu]
    description: Proportional gain of PLL frequency measurement
    from_schema: https://gridlabd.org/schema/glm/powerflow/node
    rank: 1000
    owner: node
    domain_of:
    - node
    - triplex_node
    range: float
    required: false
    unit:
      ucum_code: pu
  pll_Ki:
    name: pll_Ki
    annotations:
      order:
        tag: order
        value: 65
      value_type:
        tag: value_type
        value: float
      precision:
        tag: precision
        value: 6
      native_name:
        tag: native_name
        value: pll_Ki[pu]
    description: Integration gain of PLL frequency measurement
    from_schema: https://gridlabd.org/schema/glm/powerflow/node
    rank: 1000
    owner: node
    domain_of:
    - node
    - triplex_node
    range: float
    required: false
    unit:
      ucum_code: pu
  measured_angle_A:
    name: measured_angle_A
    annotations:
      order:
        tag: order
        value: 66
      value_type:
        tag: value_type
        value: float
      precision:
        tag: precision
        value: 6
      native_name:
        tag: native_name
        value: measured_angle_A[rad]
    description: bus angle measurement, phase A
    from_schema: https://gridlabd.org/schema/glm/powerflow/node
    rank: 1000
    owner: node
    domain_of:
    - node
    range: float
    required: false
    unit:
      ucum_code: rad
  measured_frequency_A:
    name: measured_frequency_A
    annotations:
      order:
        tag: order
        value: 67
      value_type:
        tag: value_type
        value: float
      precision:
        tag: precision
        value: 6
      native_name:
        tag: native_name
        value: measured_frequency_A[Hz]
    description: frequency measurement, phase A
    from_schema: https://gridlabd.org/schema/glm/powerflow/node
    rank: 1000
    owner: node
    domain_of:
    - node
    range: float
    required: false
    unit:
      ucum_code: Hz
  measured_angle_B:
    name: measured_angle_B
    annotations:
      order:
        tag: order
        value: 68
      value_type:
        tag: value_type
        value: float
      precision:
        tag: precision
        value: 6
      native_name:
        tag: native_name
        value: measured_angle_B[rad]
    description: bus angle measurement, phase B
    from_schema: https://gridlabd.org/schema/glm/powerflow/node
    rank: 1000
    owner: node
    domain_of:
    - node
    range: float
    required: false
    unit:
      ucum_code: rad
  measured_frequency_B:
    name: measured_frequency_B
    annotations:
      order:
        tag: order
        value: 69
      value_type:
        tag: value_type
        value: float
      precision:
        tag: precision
        value: 6
      native_name:
        tag: native_name
        value: measured_frequency_B[Hz]
    description: frequency measurement, phase B
    from_schema: https://gridlabd.org/schema/glm/powerflow/node
    rank: 1000
    owner: node
    domain_of:
    - node
    range: float
    required: false
    unit:
      ucum_code: Hz
  measured_angle_C:
    name: measured_angle_C
    annotations:
      order:
        tag: order
        value: 70
      value_type:
        tag: value_type
        value: float
      precision:
        tag: precision
        value: 6
      native_name:
        tag: native_name
        value: measured_angle_C[rad]
    description: bus angle measurement, phase C
    from_schema: https://gridlabd.org/schema/glm/powerflow/node
    rank: 1000
    owner: node
    domain_of:
    - node
    range: float
    required: false
    unit:
      ucum_code: rad
  measured_frequency_C:
    name: measured_frequency_C
    annotations:
      order:
        tag: order
        value: 71
      value_type:
        tag: value_type
        value: float
      precision:
        tag: precision
        value: 6
      native_name:
        tag: native_name
        value: measured_frequency_C[Hz]
    description: frequency measurement, phase C
    from_schema: https://gridlabd.org/schema/glm/powerflow/node
    rank: 1000
    owner: node
    domain_of:
    - node
    range: float
    required: false
    unit:
      ucum_code: Hz
  measured_frequency:
    name: measured_frequency
    annotations:
      order:
        tag: order
        value: 72
      value_type:
        tag: value_type
        value: float
      precision:
        tag: precision
        value: 6
      native_name:
        tag: native_name
        value: measured_frequency[Hz]
    description: frequency measurement - average of present phases
    from_schema: https://gridlabd.org/schema/glm/powerflow/node
    rank: 1000
    owner: node
    domain_of:
    - node
    - triplex_node
    range: float
    required: false
    unit:
      ucum_code: Hz
  service_status:
    name: service_status
    annotations:
      order:
        tag: order
        value: 73
      value_type:
        tag: value_type
        value: string
      native_name:
        tag: native_name
        value: service_status
    description: In and out of service flag
    from_schema: https://gridlabd.org/schema/glm/powerflow/node
    rank: 1000
    owner: node
    domain_of:
    - node
    - triplex_node
    range: string
    required: false
  service_status_double:
    name: service_status_double
    annotations:
      order:
        tag: order
        value: 74
      value_type:
        tag: value_type
        value: float
      precision:
        tag: precision
        value: 6
      native_name:
        tag: native_name
        value: service_status_double
    description: In and out of service flag - type double - will indiscriminately
      override service_status - useful for schedules
    from_schema: https://gridlabd.org/schema/glm/powerflow/node
    rank: 1000
    owner: node
    domain_of:
    - node
    - triplex_node
    range: float
    required: false
  previous_uptime:
    name: previous_uptime
    annotations:
      order:
        tag: order
        value: 75
      value_type:
        tag: value_type
        value: float
      precision:
        tag: precision
        value: 6
      native_name:
        tag: native_name
        value: previous_uptime[min]
    description: Previous time between disconnects of node in minutes
    from_schema: https://gridlabd.org/schema/glm/powerflow/node
    rank: 1000
    owner: node
    domain_of:
    - node
    - triplex_node
    range: float
    required: false
    unit:
      ucum_code: min
  current_uptime:
    name: current_uptime
    annotations:
      order:
        tag: order
        value: 76
      value_type:
        tag: value_type
        value: float
      precision:
        tag: precision
        value: 6
      native_name:
        tag: native_name
        value: current_uptime[min]
    description: Current time since last disconnect of node in minutes
    from_schema: https://gridlabd.org/schema/glm/powerflow/node
    rank: 1000
    owner: node
    domain_of:
    - node
    - triplex_node
    range: float
    required: false
    unit:
      ucum_code: min
  Norton_dynamic:
    name: Norton_dynamic
    annotations:
      order:
        tag: order
        value: 77
      value_type:
        tag: value_type
        value: bool
      native_name:
        tag: native_name
        value: Norton_dynamic
    description: Flag to indicate a Norton-equivalent connection -- used for generators
      and deltamode
    from_schema: https://gridlabd.org/schema/glm/powerflow/node
    rank: 1000
    owner: node
    domain_of:
    - node
    - triplex_node
    range: boolean
    required: false
  Norton_dynamic_child:
    name: Norton_dynamic_child
    annotations:
      order:
        tag: order
        value: 78
      value_type:
        tag: value_type
        value: bool
      native_name:
        tag: native_name
        value: Norton_dynamic_child
    description: Flag to indicate a Norton-equivalent connection is made by a childed
      node object -- used for generators and deltamode
    from_schema: https://gridlabd.org/schema/glm/powerflow/node
    rank: 1000
    owner: node
    domain_of:
    - node
    - triplex_node
    range: boolean
    required: false
  generator_dynamic:
    name: generator_dynamic
    annotations:
      order:
        tag: order
        value: 79
      value_type:
        tag: value_type
        value: bool
      native_name:
        tag: native_name
        value: generator_dynamic
    description: Flag to indicate a voltage-sourcing or swing-type generator is present
      -- used for generators and deltamode
    from_schema: https://gridlabd.org/schema/glm/powerflow/node
    rank: 1000
    owner: node
    domain_of:
    - node
    - triplex_node
    range: boolean
    required: false
  reset_disabled_island_state:
    name: reset_disabled_island_state
    annotations:
      order:
        tag: order
        value: 80
      value_type:
        tag: value_type
        value: bool
      native_name:
        tag: native_name
        value: reset_disabled_island_state
    description: Deltamode/multi-island flag -- used to reset disabled status (and
      reform an island)
    from_schema: https://gridlabd.org/schema/glm/powerflow/node
    rank: 1000
    owner: node
    domain_of:
    - node
    - triplex_node
    range: boolean
    required: false
  GFA_enable:
    name: GFA_enable
    annotations:
      order:
        tag: order
        value: 81
      value_type:
        tag: value_type
        value: bool
      native_name:
        tag: native_name
        value: GFA_enable
    description: Disable/Enable Grid Friendly Appliance(TM)-type functionality
    from_schema: https://gridlabd.org/schema/glm/powerflow/node
    rank: 1000
    owner: node
    domain_of:
    - node
    - triplex_node
    range: boolean
    required: false
  GFA_freq_low_trip:
    name: GFA_freq_low_trip
    annotations:
      order:
        tag: order
        value: 82
      value_type:
        tag: value_type
        value: float
      precision:
        tag: precision
        value: 6
      native_name:
        tag: native_name
        value: GFA_freq_low_trip[Hz]
    description: Low frequency trip point for Grid Friendly Appliance(TM)-type functionality
    from_schema: https://gridlabd.org/schema/glm/powerflow/node
    rank: 1000
    owner: node
    domain_of:
    - node
    - triplex_node
    range: float
    required: false
    unit:
      ucum_code: Hz
  GFA_freq_high_trip:
    name: GFA_freq_high_trip
    annotations:
      order:
        tag: order
        value: 83
      value_type:
        tag: value_type
        value: float
      precision:
        tag: precision
        value: 6
      native_name:
        tag: native_name
        value: GFA_freq_high_trip[Hz]
    description: High frequency trip point for Grid Friendly Appliance(TM)-type functionality
    from_schema: https://gridlabd.org/schema/glm/powerflow/node
    rank: 1000
    owner: node
    domain_of:
    - node
    - triplex_node
    range: float
    required: false
    unit:
      ucum_code: Hz
  GFA_volt_low_trip:
    name: GFA_volt_low_trip
    annotations:
      order:
        tag: order
        value: 84
      value_type:
        tag: value_type
        value: float
      precision:
        tag: precision
        value: 6
      native_name:
        tag: native_name
        value: GFA_volt_low_trip[pu]
    description: Low voltage trip point for Grid Friendly Appliance(TM)-type functionality
    from_schema: https://gridlabd.org/schema/glm/powerflow/node
    rank: 1000
    owner: node
    domain_of:
    - node
    - triplex_node
    range: float
    required: false
    unit:
      ucum_code: pu
  GFA_volt_high_trip:
    name: GFA_volt_high_trip
    annotations:
      order:
        tag: order
        value: 85
      value_type:
        tag: value_type
        value: float
      precision:
        tag: precision
        value: 6
      native_name:
        tag: native_name
        value: GFA_volt_high_trip[pu]
    description: High voltage trip point for Grid Friendly Appliance(TM)-type functionality
    from_schema: https://gridlabd.org/schema/glm/powerflow/node
    rank: 1000
    owner: node
    domain_of:
    - node
    - triplex_node
    range: float
    required: false
    unit:
      ucum_code: pu
  GFA_reconnect_time:
    name: GFA_reconnect_time
    annotations:
      order:
        tag: order
        value: 86
      value_type:
        tag: value_type
        value: float
      precision:
        tag: precision
        value: 6
      native_name:
        tag: native_name
        value: GFA_reconnect_time[s]
    description: Reconnect time for Grid Friendly Appliance(TM)-type functionality
    from_schema: https://gridlabd.org/schema/glm/powerflow/node
    rank: 1000
    owner: node
    domain_of:
    - node
    - triplex_node
    range: float
    required: false
    unit:
      ucum_code: s
  GFA_freq_disconnect_time:
    name: GFA_freq_disconnect_time
    annotations:
      order:
        tag: order
        value: 87
      value_type:
        tag: value_type
        value: float
      precision:
        tag: precision
        value: 6
      native_name:
        tag: native_name
        value: GFA_freq_disconnect_time[s]
    description: Frequency violation disconnect time for Grid Friendly Appliance(TM)-type
      functionality
    from_schema: https://gridlabd.org/schema/glm/powerflow/node
    rank: 1000
    owner: node
    domain_of:
    - node
    - triplex_node
    range: float
    required: false
    unit:
      ucum_code: s
  GFA_volt_disconnect_time:
    name: GFA_volt_disconnect_time
    annotations:
      order:
        tag: order
        value: 88
      value_type:
        tag: value_type
        value: float
      precision:
        tag: precision
        value: 6
      native_name:
        tag: native_name
        value: GFA_volt_disconnect_time[s]
    description: Voltage violation disconnect time for Grid Friendly Appliance(TM)-type
      functionality
    from_schema: https://gridlabd.org/schema/glm/powerflow/node
    rank: 1000
    owner: node
    domain_of:
    - node
    - triplex_node
    range: float
    required: false
    unit:
      ucum_code: s
  GFA_status:
    name: GFA_status
    annotations:
      order:
        tag: order
        value: 89
      value_type:
        tag: value_type
        value: bool
      native_name:
        tag: native_name
        value: GFA_status
    description: Grid Friendly Appliance(TM)-type functionality - whether it is in
      service (not tripped) or not
    from_schema: https://gridlabd.org/schema/glm/powerflow/node
    rank: 1000
    owner: node
    domain_of:
    - node
    - triplex_node
    range: boolean
    required: false
  GFA_trip_method:
    name: GFA_trip_method
    annotations:
      order:
        tag: order
        value: 90
      value_type:
        tag: value_type
        value: string
      native_name:
        tag: native_name
        value: GFA_trip_method
    description: GFA trip for over-voltage
    from_schema: https://gridlabd.org/schema/glm/powerflow/node
    rank: 1000
    owner: node
    domain_of:
    - node
    - triplex_node
    range: string
    required: false
  topological_parent:
    name: topological_parent
    annotations:
      order:
        tag: order
        value: 91
      value_type:
        tag: value_type
        value: string
      native_name:
        tag: native_name
        value: topological_parent
    description: topological parent as per GLM configuration
    from_schema: https://gridlabd.org/schema/glm/powerflow/node
    rank: 1000
    owner: node
    domain_of:
    - node
    - triplex_node
    range: string
    required: false
  behaving_as_swing:
    name: behaving_as_swing
    annotations:
      order:
        tag: order
        value: 92
      value_type:
        tag: value_type
        value: bool
      native_name:
        tag: native_name
        value: behaving_as_swing
    description: Indicator flag for if a bus is behaving as a reference voltage source
      - valid for a SWING or SWING_PQ
    from_schema: https://gridlabd.org/schema/glm/powerflow/node
    rank: 1000
    owner: node
    domain_of:
    - node
    - triplex_node
    range: boolean
    required: false
  phases:
    name: phases
    annotations:
      order:
        tag: order
        value: 1
      value_type:
        tag: value_type
        value: string
      native_name:
        tag: native_name
        value: phases
    comments:
    - 'Import: structural. Bus: a child''s conductors must be a subset of its root''s.
      Switch: Terminal phases, A B C with N dropped, blank when ABC. Series_reactor:
      Terminal.phases when fewer than three. Swing bus: EnergySource.phases, blank
      when ABC. Export: the A, B, C of the terminals on the bus, then N (S on a split-phase
      bus); a switch or reactor side 1''s A, B, C.'
    from_schema: https://gridlabd.org/schema/glm/powerflow/powerflow_object
    related_mappings:
    - cim:Terminal.phases
    rank: 1000
    owner: node
    domain_of:
    - powerflow_object
    - inverter
    - rectifier
    - windturb_dg
    range: string
    required: false
  nominal_voltage:
    name: nominal_voltage
    annotations:
      order:
        tag: order
        value: 2
      value_type:
        tag: value_type
        value: float
      precision:
        tag: precision
        value: 6
      native_name:
        tag: native_name
        value: nominal_voltage[V]
    comments:
    - 'Import: not copied; the topology walk gives the BaseVoltage, and a bus value
      over 10 percent off it is listed in bus.cimtbl. On a swing bus: EnergySource.nominalVoltage
      (V as written), line to line. Export: BaseVoltage LL / sqrt 3 (three phase),
      LL (single phase), LL / 2 (split phase leg); a substation: EnergySource.nominalVoltage
      / sqrt 3.'
    from_schema: https://gridlabd.org/schema/glm/powerflow/powerflow_object
    close_mappings:
    - cim:BaseVoltage.nominalVoltage
    - cim:EnergySource.nominalVoltage
    rank: 1000
    owner: node
    domain_of:
    - powerflow_object
    - battery
    - waterheater
    range: float
    required: false
    unit:
      ucum_code: V
  inrush_integration_method:
    name: inrush_integration_method
    annotations:
      order:
        tag: order
        value: 3
      value_type:
        tag: value_type
        value: string
      native_name:
        tag: native_name
        value: inrush_integration_method
    description: Integration method for in-rush
    from_schema: https://gridlabd.org/schema/glm/powerflow/powerflow_object
    rank: 1000
    owner: node
    domain_of:
    - powerflow_object
    range: string
    required: false
  condition:
    name: condition
    annotations:
      order:
        tag: order
        value: 4
      value_type:
        tag: value_type
        value: string
      native_name:
        tag: native_name
        value: condition
    from_schema: https://gridlabd.org/schema/glm/powerflow/powerflow_object
    rank: 1000
    owner: node
    domain_of:
    - powerflow_object
    range: string
    required: false
  solution:
    name: solution
    annotations:
      order:
        tag: order
        value: 5
      value_type:
        tag: value_type
        value: string
      native_name:
        tag: native_name
        value: solution
    from_schema: https://gridlabd.org/schema/glm/powerflow/powerflow_object
    rank: 1000
    owner: node
    domain_of:
    - powerflow_object
    range: string
    required: false
  name:
    name: name
    annotations:
      order:
        tag: order
        value: 0
      value_type:
        tag: value_type
        value: string
      native_name:
        tag: native_name
        value: name
    description: The object's name; unique across the model.
    comments:
    - 'Import: <CIM class>.name, copied as written; mRID = the class''s prefix + name
      (none on a bus). Export: Names, sanitized for GridLAB-D; a name two objects
      share raises.'
    from_schema: https://gridlabd.org/schema/glm/types/common
    exact_mappings:
    - cim:IdentifiedObject.name
    rank: 1000
    identifier: true
    owner: node
    domain_of:
    - glm_object
    range: string
    required: true
  parent:
    name: parent
    annotations:
      order:
        tag: order
        value: 0
      value_type:
        tag: value_type
        value: string
      native_name:
        tag: native_name
        value: parent
    description: The parent object's name. A child node is solved as its parent's
      bus; a nested object block sets it to the enclosing object.
    comments:
    - 'Import: a bus whose parent is a bus is its root bus''s ConnectivityNode, named
      on the root''s row; no object of its own. On a link it is not mapped.'
    from_schema: https://gridlabd.org/schema/glm/types/common
    rank: 1000
    owner: node
    domain_of:
    - glm_object
    range: string
  groupid:
    name: groupid
    annotations:
      order:
        tag: order
        value: 0
      value_type:
        tag: value_type
        value: string
      native_name:
        tag: native_name
        value: groupid
    description: Free-text group label.
    from_schema: https://gridlabd.org/schema/glm/types/common
    rank: 1000
    owner: node
    domain_of:
    - glm_object
    range: string
  latitude:
    name: latitude
    annotations:
      order:
        tag: order
        value: 0
      value_type:
        tag: value_type
        value: string
      native_name:
        tag: native_name
        value: latitude
    description: Latitude, as written (decimal degrees or GridLAB-D's 37N26:12 form).
    comments:
    - Not converted. Home is the EquipmentLocation shape.
    from_schema: https://gridlabd.org/schema/glm/types/common
    rank: 1000
    owner: node
    domain_of:
    - glm_object
    range: string
  longitude:
    name: longitude
    annotations:
      order:
        tag: order
        value: 0
      value_type:
        tag: value_type
        value: string
      native_name:
        tag: native_name
        value: longitude
    description: Longitude, as written.
    comments:
    - Not converted. Home is the EquipmentLocation shape.
    from_schema: https://gridlabd.org/schema/glm/types/common
    rank: 1000
    owner: node
    domain_of:
    - glm_object
    range: string
  in_svc:
    name: in_svc
    annotations:
      order:
        tag: order
        value: 0
      value_type:
        tag: value_type
        value: string
      native_name:
        tag: native_name
        value: in_svc
    description: Timestamp the object enters service.
    from_schema: https://gridlabd.org/schema/glm/types/common
    rank: 1000
    owner: node
    domain_of:
    - glm_object
    range: string
  out_svc:
    name: out_svc
    annotations:
      order:
        tag: order
        value: 0
      value_type:
        tag: value_type
        value: string
      native_name:
        tag: native_name
        value: out_svc
    description: Timestamp the object leaves service.
    from_schema: https://gridlabd.org/schema/glm/types/common
    rank: 1000
    owner: node
    domain_of:
    - glm_object
    range: string
  rank:
    name: rank
    annotations:
      order:
        tag: order
        value: 0
      value_type:
        tag: value_type
        value: string
      native_name:
        tag: native_name
        value: rank
    description: Solver rank.
    from_schema: https://gridlabd.org/schema/glm/types/common
    rank: 1000
    owner: node
    domain_of:
    - glm_object
    range: string
  flags:
    name: flags
    annotations:
      order:
        tag: order
        value: 0
      value_type:
        tag: value_type
        value: string
      native_name:
        tag: native_name
        value: flags
    description: Core object flags.
    from_schema: https://gridlabd.org/schema/glm/types/common
    rank: 1000
    owner: node
    domain_of:
    - glm_object
    range: string