PSS/E RAW v34 → .cimtbl mapping spec

Status: R0 approved 2026-11-08 and implemented (master, zone, area, bus with substations, busbars, voltage limits and solved voltages; owner). R1 (branch, system switching device, multi-section line, rating sets) approved and implemented 2026-11-08; atoms in tests/atoms/branch/. R2 (load, fixed shunt, switched shunt) approved and implemented 2026-11-08; atoms in tests/atoms/load/, tests/atoms/shunt/. R3 (generator) approved and implemented 2026-11-08; atom in tests/atoms/generator/. R4 (transformer) approved and implemented 2026-11-08; atom in tests/atoms/transformer/. R5 (tie flows, a bus's AREA, inter-area transfer, the netInterchange sign) approved and implemented 2026-11-08; atom in tests/atoms/area/. R6 (node-breaker substations: nodes, substation switching devices, equipment terminals, regulated nodes) approved and implemented 2026-11-09; case tests/cases/IEEE118/, atoms in tests/atoms/substation/. R4b (the transformer forms R4 raised on: fixed phase shifts, phase shifters, impedance correction tables, fixed ratios, one winding out, CONT 0 and negative, load-drop compensation) approved and implemented 2026-11-09; atom tests/atoms/transformer/forms_r4b.raw. P2a (shunt FACTS devices, VSC DC lines) and P2b (two-terminal DC lines) approved and implemented 2026-11-09; atoms in tests/atoms/dc/. R3b's implicit step-up transformers approved and implemented 2026-11-09; atom tests/atoms/generator/step_up.raw. R1b / R2b (a branch between two base voltages, a series capacitor with a length, a multi-section line holding one; switched shunts with MODSW 3 and 6) approved and implemented 2026-11-09; atoms tests/atoms/branch/mixed_base.raw, tests/atoms/shunt/plant_and_facts.raw. R3c (generators with WMOD 2 and 3) approved and implemented 2026-11-09; atom tests/atoms/generator/renewables.raw. Goldens: tests/goldens/IEEE14/, tests/goldens/IEEE118/; tests: tests/test_raw_to_cimtbl.py. Plan: RAW_REWRITE_PLAN.md. Format: the cimtbl-mapping-spec skill; contract: the cimtbl-import-contract skill; shapes: the cimtbl-shapes skill.

The classification tables are generated with cimhub_core.cimtbl.fields_table(..., fields=FIELDS) from the mapper's FIELDS, and check_fields checks them against the schema. Samples come from the committed cases, IEEE14 and WECC240. Field names are the LinkML slots; the RAW names (I, BASKV, ...) start each note.

Reader conventions the mappers rely on (raw34_reader.py): - A blank or missing field is None. The mapper fills it from the schema's raw_default with cimhub_core.cimtbl.fill_defaults, and lists it on the row comment (# defaulted: ...). - Every bus reference is a bus number: extended names are resolved by the reader. - Strings are trimmed of trailing blanks.

Artifact files and order

# native class artifact shape depends on
0 case identification + system-wide data <Model>.cimtbl (master) common + line_bus_branch's BasePower: BasePower, BaseFrequency, GeographicalRegion, BaseVoltage
1 Zone zone.cimtbl SubGeographicalRegion (srgn_<I>) the master
2 Area area_interchange.cimtbl ControlArea (ca_<I>; new, C2/C3); the inter-area transfers listed on its comment (R5) the master
3 Bus bus.cimtbl line_bus_branch: Substations (synthesized, §bus; a SUBSTATION block's sub_s<IS>, R6), TopologicalNodes, one BusbarSection per bus 0, 1
3a Substation (nodes, switching devices) substation.cimtbl a node-breaker substation (new, C2): ConnectivityNodes in their buses' TopologicalNodes, Switch / Breaker / Disconnector with node1/node2 + bus1/bus2, a located block's Location, a BusbarSection per regulated node (R6) 3
4 Branch branch.cimtbl line_bus_branch: ACLineSegment (ln_), SeriesCompensator (sc_, X < 0), ratings on terminals, line shunts (R1), TieFlows of ties (R5) 3
5 System switching device switch.cimtbl switch with bus1/bus2 (R1), TieFlows of ties (R5) 3
6 Multi-section line multi_section_line.cimtbl Line + Update rows on its sections (R1) 4
7 Load load.cimtbl load with bus: LoadArea ⊃ SubLoadArea ⊃ load groups, ZIP LoadResponseCharacteristics, ConformLoad / NonConformLoad (R2) 2, 3
8 Fixed shunt fixed_shunt.cimtbl shunt with bus: LinearShuntCompensator (R2) 3
10 Generator generator.cimtbl synchronous_machine (bus-branch, new, C2) and der with bus: a RegulatingControl per plant; SynchronousMachine + GeneratingUnit (WMOD 0) or PowerElectronicsConnection + PowerElectronicsUnit (WMOD 1, 2, 3), each with its control-area membership (R3); a WMOD 3 plant's control is powerFactor (R3c) 2, 3
11 Transformer transformer.cimtbl transformer_by_ends with bus (2-winding r/x/g/b on end 1, cim18v17; C2) + the regulator shape's RatioTapChanger / TapChangerControl: PowerTransformer, an end per winding, a 3-winding unit's TransformerMeshImpedances, ratings per winding (R4), TieFlows of ties (R5) 3
12 Equipment terminal equipment_terminal.cimtbl Update Table Terminal: mRID, ConnectivityNode (R6) 3a and every equipment artifact
– Owner none untranscribed (CIM 18 gap)

Inter-area transfer has no artifact (R5: listed on area_interchange.cimtbl). After 11 come vsc_dc.cimtbl (DCLine, DCLineSegment, DCTopologicalNodes, VsConverters, their capability curves, ratings and the TieFlows of ties) and facts_device.cimtbl (StaticSynchronousCompensator + RegulatingControl), both P2a, and before them two_terminal_dc.cimtbl (P2b: the same DC rows, CsConverters behind their converter transformers on internal TopologicalNodes, whose BaseVoltages the master writes). Impedance correction comes before 11 (R4b). The remaining phase-2 stubs (multi-terminal DC, GNE, induction machine) write nothing yet. switched_shunt.cimtbl (9: shunt with bus: a RegulatingControl, a LinearShuntCompensator per block, R2, or a StaticVarCompensator, R2c) follows facts_device.cimtbl, because a MODSW 3 or 6 control's Terminal is a machine's or a FACTS device's (R2b); it keeps its number. equipment_terminal.cimtbl (12) comes after them all.

Master

Orchestrator: importer/raw_to_cimtbl.py (RawImporter(CimtblImporter), model_cls = BusBranchModel, MAPPING_ORDER, map_master, raw_to_cim).

# PSS/E RAW case IEEE14: 08/19/93 UW ARCHIVE           100.0  1962 W IEEE 14 BUS TES
# Mapping: cimhub_raw/docs/CIMTBL_MAPPING.md#master
# untranscribed: GAUSS, NEWTON, ADJUST, TYSL, SOLVER (solution options)
Profile = cim18v17
Authority = https://github.com/PNNL-CIM-Tools/CIMHub
Model = IEEE14

Object BasePower: mRID=sbase, basePower (MVA)=100.0
Object BaseFrequency: mRID=bf_60hz, frequency (Hz)=60.0
Object GeographicalRegion: mRID=rgn_ieee14, name=IEEE14
Table BaseVoltage: mRID, nominalVoltage (kV)
    bv_138kv, 138.0
Table OperationalLimitType: mRID, name, durationKind, isInfiniteDuration, direction
    olt_normal_high,    normal high,    normal,    true,  high
    olt_normal_low,     normal low,     normal,    true,  low
    olt_emergency_high, emergency high, emergency, false, high
    olt_emergency_low,  emergency low,  emergency, false, low
Import zone
Import area_interchange
Import bus
  • Model and Authority (plan D7): the caller names the model (RawImporter("IEEE14")). It is the master's file stem, its Model, and the GeographicalRegion's name. rgn_ + the name, lowercased, is that region's mRID. Authority is the CIMHub one unless the caller passes another.
  • BasePower comes first (G13), so every later (pu system) column converts on SBASE.
  • BaseFrequency: BASFRQ. It is blank in WECC240; a blank becomes 60 Hz, marked # defaulted: BASFRQ=60 (RAW-17: the spec's default is "the present option setting", and PSS/E ships 60).
  • OperationalLimitType: the four bus voltage-limit types (RAW-19). R1 adds one per RATING record (RAW-9).
  • BaseVoltage: one row per distinct BASKV, highest first. The mRID comes from cimtopology.core.voltage.base_voltage_mrid (bv_345kv, bv_13p8kv), as DSS uses, so two spokes name a voltage the same way. nominalVoltage (kV) is BASKV copied.
  • Comment: the case name and its first title line, the untranscribed system-wide records, and not mapped: with the record count of every RAW class no mapper reads yet, so a class never disappears silently.
  • Fail fast: IC ≠ 0 (a change case); a model with no buses; a BASKV that is blank or ≤ 0 (the spec defaults it to 0.0, which is no base).
CaseIdentificationRecord field type samples kind target
new_case_flag Union[int, CaseIdentificationRecordNewCaseFlag] 0 structural IC: 0 (base case) maps; 1 (add to the working case) raises, a change case is not a model
system_base_mva Optional[float] 100.0 copied BasePower.basePower (MVA); SBASE; blank: 100 (defaulted)
revision Optional[float] 34.0 structural REV: the reader reads 34 only
transformer_ratings_units Optional[int] 0 mapped XFRRAT: selects what transformer RATEn-k are (<= 0 MVA; > 0 current as MVA at 1 pu voltage); read by R4
branch_ratings_units Optional[int] 0 mapped NXFRAT: what branch and switch RATEn are: <= 0 MVA (ApparentPowerLimit), > 0 current as MVA (CurrentLimit, kA); blank: MVA (defaulted; the spec's 'present option setting')
system_base_frequency Optional[float] 60.0 copied BaseFrequency.frequency (Hz); BASFRQ; blank: 60 (defaulted; the spec's 'present option setting', RAW-17)
titles Union[str, list[str], NoneType] [' 08/19/93 UW ARCHIVE 100...., ['This is a reduced WECC 240-bus powe... untranscribed the two title lines go on the master's comment; no CIM home
general Optional[str] GENERAL, THRSHZ=0.0001, PQBRAK=0.7, B... structural GENERAL: its THRSHZ is the zero-impedance threshold of the substation merge (plan 3.2; default 0.0001); the record itself is a solution option
gauss Optional[str] GAUSS, ITMX=100, ACCP=1.6, ACCQ=1.6, ... untranscribed solution options; no home in the network profile parts
newton Optional[str] NEWTON, ITMXN=20, ACCN=1.0, TOLN=0.1,... untranscribed solution options; no home in the network profile parts
adjust Optional[str] ADJUST, ADJTHR=0.005, ACCTAP=1.0, TAP... untranscribed solution options; no home in the network profile parts
tysl Optional[str] TYSL, ITMXTY=20, ACCTY=1.0, TOLTY=0.0... untranscribed solution options; no home in the network profile parts
solver Optional[str] SOLVER, , ACTAPS=0, AREAIN=0, PHS... untranscribed solution options; no home in the network profile parts
ratings Union[dict[Union[int, RatingRecordRatingSetNumber], Union[dict, ForwardRef('RatingRecord')]], list[Union[dict, ForwardRef('RatingRecord')]], NoneType] [RatingRecord({'rating_set_number': 1... structural RATING records: the names of the twelve OperationalLimitTypes olt_rate in the master (RAW-9; mapping in importer/cimtbl/ratings.py)

Rating sets (R1; RAW-9). The master adds one OperationalLimitType per rating set, all twelve whether used or not: olt_rate<n>, with name/description from the RATING record (else RATEn / RATING SET n) and direction = absoluteValue. durationKind is left unset, because a PSS/E rating set has no fixed meaning.

# rating sets RATE1..RATE12 (RAW-9)
Table OperationalLimitType: mRID, name, description, direction=absoluteValue
    olt_rate1,  RATE1,  RATING SET 1
    ...

Zone

Mapper: importer/cimtbl/zone.py (map_zone). One SubGeographicalRegion per zone, in the case's region:

Table SubGeographicalRegion: mRID, name, Region=rgn_ieee14
    srgn_1, IEEE 14
  • A bus whose ZONE has no Zone record (RAW allows it; the Zone section is optional) gets a synthesized srgn_<zone> named by the number, under # synthesized: zones that buses name but the Zone data does not.
  • A Zone record that no bus uses is still written.
ZoneRecord field type samples kind target
zone_number Union[int, ZoneRecordZoneNumber] 1, 10, 11 structural I: mRID = srgn_ + I, Region = the case's rgn_; the name when ZONAME is blank
zone_name Optional[str] IEEE 14, ALBERTA, NEW MEXI copied SubGeographicalRegion.name; ZONAME; blank: the zone number

Area interchange

Mapper: importer/cimtbl/area_interchange.py (map_area_interchange). One ControlArea per area:

# untranscribed: bus_number
# derived: netInterchange = -PDES (net_import)
Table ControlArea: mRID, name, netInterchange (MW), pTolerance (MW)
    ca_1, IEEE14, 0.0, 999.99
  • Members come from the equipment (cim18v17 profile of 2026-11-08): generating units through ControlAreaGeneratingUnit (R3), loads through ConformLoadGroup → SubLoadArea → ControlArea (R2), and the metered terminals of ties through TieFlow (R5). A bus's own AREA is traced from them on export, and the slack bus ISW has no home (CIM 18 gap; R5).
  • netInterchange = -PDES (R5): PDES is an export, netInterchange an import.
  • type (ControlAreaTypeKind) is left unset: RAW does not say whether an area is used for AGC or for interchange.
  • The ca_ prefix and a control_area shape are requests C2/C3. Until then this section is the shape.
AreaInterchangeRecord field type samples kind target
area_number Union[int, AreaInterchangeRecordAreaNumber] 1, 2, 3 structural I: mRID = ca_ + I (prefix requested, C3); the name when ARNAME is blank
bus_number Optional[int] 2, 0 untranscribed ISW, the area slack bus: no ControlArea slack association (CIM 18 gap)
pdes Optional[float] 0.0 derived PDES (MW, the desired net export): ControlArea.netInterchange (MW, positive into the area) = -PDES (net_import, R5); blank: 0 (defaulted)
ptol Optional[float] 999.99, 5.0 copied ControlArea.pTolerance (MW); PTOL; blank: 10 (defaulted)
name Optional[str] IEEE14, SOUTH, CALIFORNIA copied ControlArea.name; ARNAME; blank: the area number

Bus

Mapper: importer/cimtbl/bus.py (map_bus(native, merge_threshold)). It writes the substations, then one TopologicalNode per bus.

Substations (plan §3.2, RAW-2)

Every bus lands in a Substation. Buses joined by equipment that sits inside a substation share one, but never across a zone boundary: - Merge equipment: - every system switching device; - a zero-impedance branch: R = 0 and |X| ≤ THRSHZ (from GENERAL, default 0.0001); - a branch whose CKT starts with @ or *; - a series capacitor (X < 0; RAW-15, R1); - every transformer, all of its windings' buses. - Zone boundary: a merge edge between two zones is skipped, so the equipment sits on the substation boundary. This is the interim form of the zone gap (§CIM 18 gaps). - Grouping: cimtopology.core.Topology(Network(branches=<one Branch per merge edge>, nodes=<every bus>)).islands(). No local union-find. - Identity: sub_ + the lowest bus number of the group. Its name is that bus's NAME, and its Region is its zone's srgn_. The row comment lists the group's buses and the equipment that merged them.

# synthesized: substations, buses merged across switching devices, zero-impedance branches (|X| <= THRSHZ 0.0001),
# series capacitors and transformers, within a zone (11 substations)
Table Substation: mRID, name, Region
    sub_1, BUS 1, srgn_1
    sub_4, BUS 4, srgn_1  # buses 4, 7, 9; xf_4_7_0_1, xf_4_9_0_1
    sub_5, BUS 5, srgn_1  # buses 5, 6; xf_5_6_0_1
    ...

The result on the committed cases is 11 substations for IEEE14 (two of several buses: {4, 7, 9}, {5, 6}) and 134 for WECC240 (79 of several buses, the largest 7). Without the zone boundary, WECC240 would have 131.

Nodes and busbars

The tables after the substations, in file order: TopologicalNode, BusbarSection, OperationalLimitSet, VoltageLimit, SvVoltage.

Table TopologicalNode: mRID, name, busNumber, BaseVoltage, ConnectivityNodeContainer
    1, BUS 1, 1, bv_138kv, sub_1
    ...
# IDE 4 (isolated): none

# one BusbarSection per bus: its terminal holds the bus's voltage limits and any regulation of the bus
Table BusbarSection: mRID, name, bus, BaseVoltage, EquipmentContainer
    bb_1, BUS 1, 1, bv_138kv, sub_1
    ...
  • BusbarSection (RAW-19, RAW-11): bb_ + I (prefix requested, C3), on the bus's node, in its substation. cimtables generates its terminal bb_<I>_T1. That terminal is where every limit and control of the bus goes:
  • Voltage limits: an OperationalLimitSet bb_<I>_limits (Terminal = bb_<I>_T1) with VoltageLimits bb_<I>_nvhi, _nvlo, _evhi, _evlo. The limit types (in the master) are olt_normal_high, olt_normal_low, olt_emergency_high and olt_emergency_low: direction high/low, durationKind normal/emergency. A blank limit takes its spec default (1.1 / 0.9), listed as defaulted. normalValue (kV) = pu × BASKV is derived by kv_from_per_unit (user, 2026-11-08). A pu cell would need cimtables to reach the base through Terminal.ConductingEquipment.BaseVoltage, one hop too many.
  • Solved voltage (RAW-14): one SvVoltage per node (identity-only: identifier = <I>_sv). v (kV) = VM × BASKV (kv_from_per_unit) and angle (deg) = VA.
  • Regulation (R2, R3): a generator, switched shunt or transformer that regulates bus I names bb_<I>_T1 as its control's Terminal.

  • Identity (RAW-18): the bare bus number. The cimtbl-translate prefix table gives nodes no prefix. The core shape example (line_bus_branch.cimtbl) writes bus_1; that example should follow the table (request to the core owner).

  • name = NAME, else the bus number. busNumber = I.
  • Rows in bus-number order.
BusRecord field type samples kind target
bus_number Union[int, BusRecordBusNumber] 1, 10, 11 copied TopologicalNode.busNumber; I; node mRID = I (bare, the cimtbl-translate rule for nodes; RAW-18); BusbarSection mRID = bb_ + I (RAW-19)
name Optional[str] BUS 1, BUS 10, BUS 11 copied TopologicalNode.name, BusbarSection.name; NAME; blank: the bus number
base_voltage Optional[float] 138.0, 500.0, 345.0 structural BASKV: the node's and the busbar's BaseVoltage bv_; the master writes one BaseVoltage per distinct BASKV, nominalVoltage (kV) copied; the base of every pu voltage of the bus
bus_type Optional[int] 3, 1, 2 structural IDE: 1 and 2 add nothing (the equipment says it); 3 (swing) is the angle reference, written with R3 (SynchronousMachine.referencePriority); 4 (isolated) is listed on the table comment
area Optional[int] 1, 4, 2 untranscribed AREA: a node or BusbarSection has no ControlArea association (CIM 18 gap); the export traces it from generating units and tie flows across devices inside one area (R5); a bus the trace cannot reach (untraced_area_buses) lists untranscribed: area=AREA on its TopologicalNode row
zone Optional[int] 1, 3, 10 structural ZONE: the Region of the node's Substation (srgn_), and a substation boundary (plan 3.2)
owner Optional[int] 1 untranscribed OWNER: ownership is an asset concept (CIM 18 gap)
voltage_magnitude Optional[float] 1.06, 1.05099, 1.05691 derived VM (pu): SvVoltage.v (kV) = VM x BASKV (kv_from_per_unit; RAW-14)
voltage_angle Optional[float] 0.0, -15.0972, -14.7906 copied SvVoltage.angle (deg); VA (RAW-14)
normal_voltage_magnitude_high_limit Optional[float] 1.1 derived NVHI (pu): home VoltageLimit bb_nvhi on the BusbarSection terminal's set bb_limits (RAW-19); normalValue (kV) = pu x BASKV (kv_from_per_unit)
normal_voltage_magnitude_low_limit Optional[float] 0.9 derived NVLO (pu): home VoltageLimit bb_nvlo on the BusbarSection terminal's set bb_limits (RAW-19); normalValue (kV) = pu x BASKV (kv_from_per_unit)
emergency_voltage_magnitude_high_limit Optional[float] 1.1 derived EVHI (pu): home VoltageLimit bb_evhi on the BusbarSection terminal's set bb_limits (RAW-19); normalValue (kV) = pu x BASKV (kv_from_per_unit)
emergency_voltage_magnitude_low_limit Optional[float] 0.9 derived EVLO (pu): home VoltageLimit bb_evlo on the BusbarSection terminal's set bb_limits (RAW-19); normalValue (kV) = pu x BASKV (kv_from_per_unit)

Branch (R1)

Mapper: importer/cimtbl/branch.py (map_branch). Shape: line_bus_branch (r/x/bch (pu system) on bus I's BaseVoltage and the master's BasePower). One row per branch, in key order:

# untranscribed: o1, f1, o2, f2, o3, f3, o4, f4
# untranscribed off a tie: MET (a tie's TieFlows record it; CIM 18 gap, RAW-22)
Table ACLineSegment: mRID, name, bus1, bus2, r (pu system), x (pu system), bch (pu system), length (km), inService, BaseVoltage, EquipmentContainer
    ln_1_2_1,   1_2_1,   1,  2,  0.01938, 0.05917, 0.0528, , true, bv_138kv,
    ...
    ln_7_9_1,   7_9_1,   7,  9,  -0.0,    0.11001, 0.0,    , true, bv_138kv, sub_4
    ...
# series capacitors: X < 0 (RAW-15)
Table SeriesCompensator: mRID, name, bus1, bus2, compensatorType, r (pu system), x (pu system), inService, BaseVoltage, EquipmentContainer
    sc_2404_3893_1, 2404_3893_1, 2404, 3893, capacitor, 1e-07, -0.00935, true, bv_500kv, sub_2404
    ...
  • Class: X < 0 → SeriesCompensator (sc_, compensatorType = capacitor, r/x verbatim; RAW-15). A series capacitor with B ≠ 0 raises: SeriesCompensator has no bch (no case has one). Every other branch is an ACLineSegment (ln_). gch is not written (RAW has no line conductance).
  • BaseVoltage: bus I's, the base of every (pu system) value and of a CurrentLimit. A branch whose bus J has another BASKV lists it on its row (# BASKV <kV> at bus J; R1b-1).
  • Container: the substation, when both buses are in one (a zero-impedance branch, a @/* circuit, a series capacitor, or a parallel path inside a merged substation). Otherwise none, or the multi-section Line (below).
  • Status: inService = ST == 1, written on every row. WECC240 has 4 branches out of service.
  • Ratings (RAW-9, RAW-20): each nonzero RATEn is an ApparentPowerLimit in one OperationalLimitSet on the branch's first terminal (sequenceNumber 1, bus I; user 2026-11-08):
Table OperationalLimitSet: mRID, Terminal
    ln_2000_2202_1_ratings, ln_2000_2202_1_T1
Table ApparentPowerLimit: mRID, OperationalLimitSet, OperationalLimitType, normalValue (MVA)
    ln_2000_2202_1_rate2, ln_2000_2202_1_ratings, olt_rate2, 986.0
    ln_2000_2202_1_rate3, ln_2000_2202_1_ratings, olt_rate3, 888.0
    ...

A zero RATEn is "no limit" in PSS/E, so it writes no row, and a branch with no nonzero rating has no set (IEEE14 has none; WECC240 has 281 nonzero ratings on 192 branches). When NXFRAT > 0 the ratings are a current "expressed as MVA" at the bus's base voltage. They become a CurrentLimit with normalValue (kA) = RATEn / (√3 × BASKV), derived by ka_from_rating. A blank NXFRAT ("the present option setting", as for BASFRQ) is MVA, marked # defaulted: NXFRAT=0 on the master. - Line shunts (RAW-13): GI + jBI ≠ 0 gives a LinearShuntCompensator cap_<I>_<J>_<CKT>_i on bus I, and GJ + jBJ ≠ 0 gives _j on bus J. Each has gPerSection/bPerSection (pu system), nomU (kV) and the BaseVoltage of its own bus (R1b-1), one section, inService = the branch's ST, and the end bus's substation as its container: an ordinary shunt (user 2026-11-08). "Switched with its line" has no CIM association in a bus-branch model, so it is carried by the mRID only (CIM 18 gap; in a node-breaker model the shunt would sit on the line's side of the breaker). Neither public case sets a line shunt; the atom tests/atoms/branch/line_shunts.raw covers it. - LEN (RAW-21): Conductor.length (km), copied: RAW's "user-selected units" are taken as km (user 2026-11-08). LEN = 0 (the default, "not given") writes no length. A series capacitor's LEN ≠ 0 is listed on its row (untranscribed: length=…): SeriesCompensator is no Conductor (R1b-2). - MET (RAW-22): untranscribed, a CIM 18 gap (user 2026-11-08: power flow only, no interchange balancing). WECC240 has 81 branches with MET = 2, written back as MET = 1 (expected difference). - Owners: untranscribed (CIM 18 gap). - Name: NAME, else the key I_J_CKT.

BranchRecord field type samples kind target
from_bus_number int 1001, 1002, 1004 structural I: bus1; BaseVoltage = bus I's bv_, the base of every (pu system) value and of a CurrentLimit; J with another BASKV is listed on the row (R1b-1)
to_bus_number int 1201, 1202, 1004 structural J: bus2
r float 0.00177, 0.0108, 0.0005 copied ACLineSegment.r (pu system), SeriesCompensator.r (pu system); R
x float 0.03169, 0.0965, 0.0053 copied ACLineSegment.x (pu system), SeriesCompensator.x (pu system); X; X < 0: a SeriesCompensator, compensatorType = capacitor, x verbatim (RAW-15)
circuit Optional[str] 1, 9, 2 structural CKT: with I and J the key, mRID ln_ (X < 0: sc_); a first character @ or * is a substation merge edge (plan 3.2)
b Optional[float] 3.3446, 0.3296, 0.0882 copied ACLineSegment.bch (pu system); B; blank: 0 (defaulted); a series capacitor with B != 0 raises (SeriesCompensator has no bch; no case)
name Optional[str] copied ACLineSegment.name, SeriesCompensator.name; NAME; blank: the key I_J_CKT
ratings Union[float, list[float], NoneType] [0.0, 0.0, 0.0, 0.0, 0.0, 0.0, 0.0, 0..., [0.0, 0.0, 1630.0, 0.0, 0.0, 0.0, 0.0..., [0.0, 0.0, 1800.0, 0.0, 0.0, 0.0, 0.0... structural RATE1..RATE12: each nonzero RATEn an ApparentPowerLimit _rate (normalValue (MVA)) in the set _ratings on terminal _T1, type olt_rate (RAW-9, RAW-20); NXFRAT > 0: a CurrentLimit, normalValue (kA) = RATEn / (sqrt(3) x BASKV) (ka_from_rating); 0 is no limit, no row
g_from Optional[float] 0.0 structural GI: with BI, a LinearShuntCompensator cap__i on bus I when either is nonzero (RAW-13): gPerSection (pu system), nomU (kV) and BaseVoltage = bus I's BASKV, one section, inService = ST, the bus's substation
b_from Optional[float] 0.0 structural BI: with GI, a LinearShuntCompensator cap__i on bus I when either is nonzero (RAW-13): bPerSection (pu system), nomU (kV) and BaseVoltage = bus I's BASKV, one section, inService = ST, the bus's substation
g_to Optional[float] 0.0 structural GJ: with BJ, a LinearShuntCompensator cap__j on bus J when either is nonzero (RAW-13): gPerSection (pu system), nomU (kV) and BaseVoltage = bus J's BASKV, one section, inService = ST, the bus's substation
b_to Optional[float] 0.0 structural BJ: with GJ, a LinearShuntCompensator cap__j on bus J when either is nonzero (RAW-13): bPerSection (pu system), nomU (kV) and BaseVoltage = bus J's BASKV, one section, inService = ST, the bus's substation
status Optional[int] 1, 0 mapped ST: inService = (ST == 1), also on the line shunts; blank: 1 (defaulted)
metered_end Optional[int] 1, 2 structural MET: on a tie (I and J in two AREAs) the home end is the non-metered one (1: J, 2: I), and both TieFlows sit on the metered terminal (R5); another code on a tie raises; elsewhere untranscribed, the loss-allocation end has no CIM home (CIM 18 gap, RAW-22); blank: 1 (defaulted)
length Optional[float] 0.0 copied ACLineSegment.length (km); LEN, 'user-selected units' taken as km (RAW-21); 0 (the default): no length; a series capacitor's LEN != 0 is listed on its row (SeriesCompensator is no Conductor, R1b-2)
o1 Optional[int] 1 untranscribed ownership is an asset concept (CIM 18 gap)
f1 Optional[float] 1.0 untranscribed ownership is an asset concept (CIM 18 gap)
o2 Optional[int] untranscribed ownership is an asset concept (CIM 18 gap)
f2 Optional[float] untranscribed ownership is an asset concept (CIM 18 gap)
o3 Optional[int] untranscribed ownership is an asset concept (CIM 18 gap)
f3 Optional[float] untranscribed ownership is an asset concept (CIM 18 gap)
o4 Optional[int] untranscribed ownership is an asset concept (CIM 18 gap)
f4 Optional[float] untranscribed ownership is an asset concept (CIM 18 gap)

System switching device (R1)

Mapper: importer/cimtbl/switch.py (map_switch). Shape: switch with bus1/bus2. Every switch merges its buses into one substation (§3.2), which is its container. Neither public case has one; the atom tests/atoms/branch/switches.raw has one of each STYPE, one open and one normally open.

# untranscribed: x
# untranscribed off a tie: METERED (a tie's TieFlows record it; CIM 18 gap, RAW-22)
Table Switch: mRID, name, bus1, bus2, open, normalOpen, BaseVoltage, EquipmentContainer
    sw_101_102_1, CONNECTOR, 101, 102, false, false, bv_138kv, sub_101

Table Breaker: mRID, name, bus1, bus2, open, normalOpen, BaseVoltage, EquipmentContainer
    sw_102_103_1, BREAKER, 102, 103, true, false, bv_138kv, sub_101

Table Disconnector: mRID, name, bus1, bus2, open, normalOpen, BaseVoltage, EquipmentContainer
    sw_103_104_1, DISCONNECT, 103, 104, false, true, bv_138kv, sub_101

# NXFRAT > 0: derived, normalValue = RATEn / (sqrt(3) x BASKV) (ka_from_rating)
Table CurrentLimit: mRID, OperationalLimitSet, OperationalLimitType, normalValue (kA)
    sw_101_102_1_rate1, sw_101_102_1_ratings, olt_rate1, 0.836739520564675
  • Class by STYPE: 1 (generic connector) → Switch, 2 → Breaker, 3 → Disconnector. The sw_ prefix is shared, so a change of class keeps the mRID. A blank or unknown STYPE raises: the spec gives no default.
  • Status: open = STATUS == 0 and normalOpen = NSTATUS == 0.
  • X is untranscribed: it is the solver's stand-in for zero impedance (X < THRSHZ), and a Switch has none. The exporter writes 0.0001, since the format gives X no default (EXPORT_MAPPING.md E1).
  • Ratings as for branches (sw_<key>_ratings on sw_<key>_T1).
  • A switch across a zone boundary is not a merge edge (§3.2). Its container is bus I's substation.
SwitchRecord field type samples kind target
from_bus_number int 101, 102, 103 structural I: bus1; BaseVoltage = bus I's bv_; EquipmentContainer = bus I's substation
to_bus_number int 102, 103, 104 structural J: bus2
circuit Optional[str] 1 structural CKT: with I and J the key, mRID sw_
x Optional[float] 0.0001 untranscribed X: the solver's stand-in for zero impedance (X < THRSHZ); a Switch has none; the exporter writes 0.0001 (the format gives X no default)
ratings Union[float, list[float], NoneType] [200.0, 0.0, 0.0, 0.0, 0.0, 0.0, 0.0,..., [0.0, 0.0, 0.0, 0.0, 0.0, 0.0, 0.0, 0... structural RATE1..RATE12: as a branch's, the set sw_ratings on sw_T1 (RAW-9, RAW-20)
status Optional[int] 1, 0 mapped STATUS: open = (STATUS == 0); blank: 1 (defaulted)
nstat Optional[int] 1, 0 mapped NSTATUS: normalOpen = (NSTATUS == 0); blank: 1 (defaulted)
metered_end Optional[int] 1, 2 structural METERED: as a branch's MET, the TieFlows of a tie on its metered terminal (R5); elsewhere untranscribed (CIM 18 gap, RAW-22); blank: 1 (defaulted)
stype Optional[int] 1, 2, 3 mapped STYPE: the class, 1 Switch (generic connector), 2 Breaker, 3 Disconnector; blank or another code raises (the spec gives no default)
name Optional[str] CONNECTOR, BREAKER, DISCONNECT copied Switch.name, Breaker.name, Disconnector.name; NAME; blank: the key I_J_CKT

Multi-section line (R1)

Mapper: importer/cimtbl/multi_section_line.py (map_multi_section_line), after branch.cimtbl (RAW-12). The sections stay ordinary branches and the dummy buses stay nodes. The record becomes a Line container, and each section is moved into it by an Update row:

# untranscribed: met
Table Line: mRID, name, Region
    # path 1, 2, 3, 4
    msl_1_4_&1, &1, srgn_1

Update Table ACLineSegment: mRID, EquipmentContainer
    ln_1_2_1, msl_1_4_&1
    ln_2_3_1, msl_1_4_&1
    ln_4_3_1, msl_1_4_&1
  • Members: the path I, DUM1, …, J. Each consecutive pair must be joined by exactly one branch not already used, in either direction, and each dummy bus must have exactly two branches. Anything else raises with the record. A member with both buses in one substation (a series capacitor merges its buses) stays contained there and joins the Line as additional grouped equipment (Update Table …: mRID, AdditionalEquipmentContainer), and the Line's row lists it (# path …; in substations: sc_…; R1b-3).
  • Region: bus I's zone. Name: ID.
  • The msl_ prefix is requested from the translate-table owners (C3).
  • Neither public case has one; the atom tests/atoms/branch/multi_section_line.raw covers it.
MultiSectionLineRecord field type samples kind target
i int 1 structural I: the path's first bus; with J and ID the key, mRID msl_; the Line's Region is bus I's zone
j int 4 structural J: the path's last bus
dum1 int 2 structural DUM1: the path I, DUM1, .., J names the sections, one branch per step; each section's EquipmentContainer becomes the Line (an Update row), except a section in one substation, which stays there, listed on the Line's row (R1b-3)
line_id Optional[str] &1 copied Line.name; ID: the key
met Optional[int] 1 untranscribed MET: the loss-allocation end has no CIM home (CIM 18 gap, RAW-22)
dum2 Optional[int] 3 structural as DUM1
dum3 Optional[int] structural as DUM1
dum4 Optional[int] structural as DUM1
dum5 Optional[int] structural as DUM1
dum6 Optional[int] structural as DUM1
dum7 Optional[int] structural as DUM1
dum8 Optional[int] structural as DUM1
dum9 Optional[int] structural as DUM1

Load (R2)

Mapper: importer/cimtbl/load.py (map_load). Shape: load with bus in place of node (C2). One row per load, in key order, after the area hierarchy and the ZIP models it names (IEEE14):

Table LoadArea: mRID, name, ControlArea
    la_1, 1, ca_1
Table SubLoadArea: mRID, name, LoadArea
    sla_1_1, 1_1, la_1
Table ConformLoadGroup: mRID, name, SubLoadArea
    clg_1_1, 1_1, sla_1_1
# ZIP fractions: PL, IP, YP over p; QL, IQ, -YQ over q (zip_mix)
Table LoadResponseCharacteristic: mRID, exponentModel, pConstantPower, pConstantCurrent, pConstantImpedance, qConstantPower, qConstantCurrent, qConstantImpedance
    zip_1_0_0_1_0_0, false, 1.0, 0.0, 0.0, 1.0, 0.0, 0.0
# untranscribed: owner, interruptible, dgenp, dgenq, dgenf
Table ConformLoad: mRID, name, bus, p (MW), q (MVAr), inService, LoadResponse, LoadGroup, BaseVoltage, EquipmentContainer
    ld_2_1,  2_1,  2,  21.7, 12.7, true, zip_1_0_0_1_0_0, clg_1_1, bv_138kv, sub_2
    ...
  • p, q (RAW-8): p (MW) = PL + IP + YP and q (MVAr) = QL + IQ − YQ, the load at 1 pu voltage, CIM's nominal. Derived by load_p_q. YQ enters with a minus sign because RAW makes YQ negative for an inductive load. WECC240 has 118 loads with YQ < 0 and 16 with YQ > 0; the 16 have q < 0.
  • ZIP mix: the fractions are PL/p, IP/p, YP/p and QL/q, IQ/q, −YQ/q, derived by zip_mix.
  • Each distinct mix is one shared row, zip_ + its six fractions (zip_0.5_0.3_0.2_0.25_0.25_0.5), written before the loads.
  • A side whose components are all 0 counts as constant power. WECC240's mixes are zip_0_1_0_0_0_1 and, for its 5 loads with q = 0, zip_0_1_0_1_0_0.
  • A side whose components cancel (total 0 from nonzero parts) raises.
  • The exporter recovers PL..YQ as p or q × fraction, so a mixed load can differ in the last digit (expected difference).
  • Interim: core's shared zip_constant_pq / _i / _z (cimhub_core.load_response, on rc_1 only) take over the pure mixes once raw-v34 takes rc_1.
  • Class from SCALE: SCALE = 1 (scalable, the default) → ConformLoad in a ConformLoadGroup. SCALE = 0 (fixed) → NonConformLoad in a NonConformLoadGroup. These are CIM's own "follows the system load pattern" split.
  • Area and zone: the hierarchy is RAW's own totalling groups. It uses SubLoadArea.LoadArea, added to the profile 2026-11-08 by the user. Before that there was no list of sub-areas, and ControlArea.EnergyArea is 0..1.
  • Each area that has loads gets one LoadArea la_<area>, with ControlArea = ca_<area>; it is the area's single EnergyArea.
  • Each (area, zone) pair with loads gets a SubLoadArea sla_<area>_<zone> in its LoadArea.
  • The SubLoadArea holds a ConformLoadGroup clg_<area>_<zone> and/or a NonConformLoadGroup nclg_<area>_<zone>.
  • WECC240 has 4 load areas and 14 sub-areas; IEEE14 has 1 and 1. The prefixes are requested (C3).
  • The load's own AREA and ZONE pick its group, so a load assigned elsewhere than its bus keeps both.
  • An AREA with no area-interchange record raises.
  • Blank AREA or ZONE: the bus's, defaulted (the spec's default).
  • The zone is still not an association: a SubLoadArea has no link to the SubGeographicalRegion. So the exporter reads a load's ZONE from its bus's substation Region. A load whose ZONE differs from its bus's sits in its own zone's sub-area, and is also listed on its row as # untranscribed: zone=2 (bus 2 is in zone 1) (CIM 18 gap, "zone of equipment"). Neither public case has one.
  • Not used: a SubLoadArea naming the ControlArea directly. cimtables binds a second one without error and overwrites the 0..1 inverse (request U-RAW-2).
  • Status: inService = STATUS == 1.
  • Name: the key I_ID (a v34 load has no NAME).
  • Untranscribed: OWNER (CIM 18 gap); INTRPT; DGENP/DGENQ/DGENM. The distributed generation behind a load is zero in both public cases.
  • Atom: tests/atoms/load/loads.raw covers a ZIP mix, SCALE 0, an area and zone other than the bus's, and blank AREA/ZONE.
LoadRecord field type samples kind target
bus_number int 10, 11, 12 structural I: bus; BaseVoltage = bus I's bv_; EquipmentContainer = bus I's substation
load_id Optional[str] 1 structural ID: with I the key, mRID ld__, name I_ID
status Optional[int] 1 mapped STATUS: inService = (STATUS == 1); blank: 1 (defaulted)
area Optional[int] 1, 4, 2 structural AREA: the LoadArea la_ (ControlArea ca_) of the load's group; an AREA with no area-interchange record raises; blank: the bus's (defaulted)
zone Optional[int] 1, 3, 10 structural ZONE: the SubLoadArea sla__ of the load's group; the exporter reads ZONE from the bus's substation Region, so a ZONE other than the bus's is also listed untranscribed on the row (CIM 18 gap); blank: the bus's (defaulted)
constant_real_power Optional[float] 9.0, 3.5, 6.1 derived PL: constant power; the sum is p (MW) / q (MVAr) at 1 pu (load_p_q) and its share a ZIP fraction (zip_mix)
constant_imag_power Optional[float] 5.8, 1.8, 1.6 derived QL: constant power; the sum is p (MW) / q (MVAr) at 1 pu (load_p_q) and its share a ZIP fraction (zip_mix)
constant_current_real_power Optional[float] 0.0, 223.71, 2212.664 derived IP: constant current; the sum is p (MW) / q (MVAr) at 1 pu (load_p_q) and its share a ZIP fraction (zip_mix)
constant_current_imag_power Optional[float] 0.0 derived IQ: constant current; the sum is p (MW) / q (MVAr) at 1 pu (load_p_q) and its share a ZIP fraction (zip_mix)
constant_admittance_real_power Optional[float] 0.0 derived YP: constant admittance; the sum is p (MW) / q (MVAr) at 1 pu (load_p_q) and its share a ZIP fraction (zip_mix)
constant_admittance_imag_power Optional[float] 0.0, 583.546, -387.354 derived YQ: constant admittance, negative for an inductive load, so it enters q as -YQ; the sum is p (MW) / q (MVAr) at 1 pu (load_p_q) and its share a ZIP fraction (zip_mix)
owner Optional[int] 1 untranscribed ownership is an asset concept (CIM 18 gap)
scale Optional[int] 1 mapped SCALE: the class, 1 ConformLoad (scalable) in a ConformLoadGroup clg_, 0 NonConformLoad (fixed) in a NonConformLoadGroup nclg_; blank: 1 (defaulted)
interruptible Optional[int] 0 untranscribed INTRPT: no CIM home
dgenp Optional[float] 0.0 untranscribed DGENP: distributed generation behind the load, no CIM home
dgenq Optional[float] 0.0 untranscribed DGENQ: as DGENP
dgenf Optional[int] 0 untranscribed DGENM: as DGENP

Fixed shunt (R2)

Mapper: importer/cimtbl/fixed_shunt.py (map_fixed_shunt). Shape: shunt with bus and no control, like the line shunts of R1 (IEEE14):

Table LinearShuntCompensator: mRID, name, bus, gPerSection (pu system), bPerSection (pu system), nomU (kV), maximumSections, normalSections, sections, inService, BaseVoltage, EquipmentContainer
    cap_9_1, 9_1, 9, 0.0, 0.19, 138.0, 1, 1, 1, true, bv_138kv, sub_4
  • G, B: GL and BL are MW and Mvar at 1 pu voltage, so gPerSection / bPerSection (pu system) = GL / SBASE and BL / SBASE, derived by per_unit_from_mva.
  • cimtables converts them to siemens on nomU = the bus's BASKV and SBASE.
  • BL > 0 is a capacitor in RAW and in CIM, so the sign is unchanged.
  • IEEE14 has one shunt (bus 9, BL = 19.0); WECC240 has none.
  • One section, always in: maximumSections = normalSections = sections = 1.
  • Status: inService = STATUS == 1.
  • Container: the bus's substation.
  • Name: the key I_ID. The ID is trimmed, so IEEE14's ' 1' gives cap_9_1.
  • Atom: tests/atoms/shunt/fixed_shunts.raw: two shunts on one bus, a reactor out of service.
FixedShuntRecord field type samples kind target
bus_number int 9 structural I: bus; nomU (kV) = bus I's BASKV, the (pu system) base; BaseVoltage = bus I's bv_; EquipmentContainer = bus I's substation
shunt_id Optional[str] 1 structural ID: with I the key, mRID cap__, name I_ID
status Optional[int] 1 mapped STATUS: inService = (STATUS == 1); blank: 1 (defaulted)
gl Optional[float] 0.0 derived GL (MW at 1 pu): gPerSection (pu system) = GL / SBASE (per_unit_from_mva); blank: 0 (defaulted)
bl Optional[float] 19.0 derived BL (Mvar at 1 pu, > 0 a capacitor in RAW and CIM): bPerSection (pu system) = BL / SBASE (per_unit_from_mva); blank: 0 (defaulted)

Switched shunt (R2)

Mapper: importer/cimtbl/switched_shunt.py (map_switched_shunt). Shape: shunt with bus. - What a record is: every switched bank at one bus under one controller, as up to 8 blocks of Ni identical steps of Bi Mvar (Bi < 0 a reactor; reactor blocks first). - Per block: to match how the banks are wired and switched (user 2026-11-08), each block is its own LinearShuntCompensator, and all of them name one RegulatingControl. - Order: the control comes first. Its terminal is a busbar's from bus.cimtbl, or for MODSW 3 / 6 a machine's or a FACTS device's, so switched_shunt.cimtbl follows them (R2b); no Update is needed. - An SVC: a MODSW 2 shunt of at most one one-step reactor and one one-step capacitor is one StaticVarCompensator instead of its blocks (R2c).

WECC240:

# untranscribed: adjm, rmpct
# targetValue and targetDeadband in V (voltage) or VAr (reactivePower)
Table RegulatingControl: mRID, name, mode, discrete, enabled, targetValue, targetDeadband, Terminal
    # defaulted: nreg=0
    cc_4001, 4001, voltage, true, true, 500000.0, 500000.0, bb_4001_T1
    ...
# one per block: Ni sections of Bi; sections split from BINIT (block_sections)
Table LinearShuntCompensator: mRID, name, bus, bPerSection (pu system), nomU (kV), maximumSections, sections, inService, controlEnabled, RegulatingControl, BaseVoltage, EquipmentContainer
    swsh_4001_b1, 4001_b1, 4001, 2.0, 500.0, 5, 3.0, true, true, cc_4001, bv_500kv, sub_4001
    ...
  • mRIDs:
  • each block is swsh_<I>_b<k>, in input order (prefix requested, C3);
  • the control is cc_<I>, the shunt shape's prefix;
  • the key is the bus, since a v34 switched shunt has no ID.
  • Blocks (RAW-10): one LinearShuntCompensator per block, up to the first Ni or Bi that is 0 or blank (RAW's end of blocks):
  • maximumSections = Ni and bPerSection (pu system) = Bi / SBASE, derived by per_unit_from_mva;
  • nomU = the bus's BASKV;
  • the bus's substation as the container;
  • a block after the first zero raises.

The block slots are never defaulted: a missing Ni/Bi is the end of blocks, not a value. All 7 WECC240 shunts have one block. NonlinearShuntCompensator is not used: its points hold one sequence of totals with no interpolation (sections must be one of the points), so it can say neither which bank is in nor a continuous state. - Sections: RAW gives only the total in service, BINIT (Mvar at 1 pu). block_sections splits it in RAW's switching order (ADJM = 0): - BINIT < 0 fills the reactor blocks in input order, and BINIT > 0 the capacitor blocks; - each block in turn takes up to its Ni steps; - the block where BINIT runs out takes the rest as a fraction of a step (CIM allows a non-integer sections: MODSW 2, or an ADJM = 1 combination with the same total); - BINIT beyond the blocks' total raises; - normalSections is blank: RAW has no normal state apart from BINIT.

The exporter's BINIT = Σ sections × Bi is exact either way. WECC240's sections are 3, 0, 4, 0, 6, 3, 1. - ADJM: untranscribed: CIM has no switching-order method. The order is kept by _b<k>. - Control (MODSW). The control is always written, so the blocks stay grouped even when locked:

MODSW CIM
0 locked enabled = false, every block controlEnabled = false, discrete blank; the VSWHI/VSWLO target as read (unused)
1 discrete, voltage mode = voltage, discrete = true
2 continuous, voltage mode = voltage, discrete = false
3 discrete, plant Q mode = reactivePower, discrete = true, on the plant's machine (R2b-1)
6 discrete, FACTS shunt Q mode = reactivePower, discrete = true, on the FACTS device (R2b-2)
4 VSC converter Q, 5 another shunt's admittance raise NotImplementedError: no case has one yet
  • Regulated point: Terminal = bb_<SWREG>_T1, or bb_<I>_T1 when SWREG is 0 (RAW-11). NREG ≠ 0 names node NREG of the regulated bus: bb_s<IS>_n<NREG>_T1, that node's busbar (R6).
  • Target: targetValue = (VSWHI + VSWLO)/2 × the regulated bus's BASKV, and targetDeadband = (VSWHI − VSWLO) × BASKV. Both are in V, as the core shape writes them for mode voltage (deadband = the full band, target ± deadband/2). They are derived by volts_from_per_unit, which goes through the units library.
  • The subtraction can leave a last-digit float residue: the atom's 1.04 − 0.98 gives 6900.0000000000055. The value is written as computed, never rounded, and the exporter's VSWHI/VSWLO can differ in the last digit (expected difference).
  • A cimtables targetValue (kV) column binds without error but drops the unit (request U-RAW-3).
  • WECC240's 1.5/0.5 pu bands give target = BASKV and deadband = BASKV.
  • Status: inService = STATUS == 1 on every block.
  • Untranscribed:
  • RMPCT: CIM has no participation share for a shunt (canonical CIM 18's SynchronousMachine.qPercent covers only machines; cim18v17 has it since 2026-11-08); CIM 18 gap; 100 everywhere in both cases;
  • nothing else: RMIDNT names MODSW 6's FACTS device (R2b-2).
  • Atom: tests/atoms/shunt/switched_shunts.raw covers reactor + capacitor blocks with remote regulation, continuous mode with 2.5 steps, and a locked shunt (10 × 1.0 and 5 × 1.5 Mvar, BINIT 13 → 10 and 2 steps).
SwitchedShuntRecord field type samples kind target
bus_number int 4001, 4005, 6104 structural I: the key (a v34 switched shunt has no ID); every block's bus, nomU (kV) = its BASKV, BaseVoltage and EquipmentContainer (its substation)
modsw Optional[int] 1 mapped MODSW: 0 locked (control enabled = false), 1 voltage discrete, 2 voltage continuous (a StaticVarCompensator swsh_ when its blocks are at most one one-step reactor and one one-step capacitor, R2c), 3 plant and 6 FACTS shunt reactivePower discrete (R2b); 4 and 5 raise (no case); blank: 1 (defaulted)
adjm Optional[int] 0 untranscribed ADJM: the switching-order method has no CIM home; the block order is kept by _b
status Optional[int] 1 mapped STATUS: inService = (STATUS == 1) on every block (or the SVC); blank: 1 (defaulted)
vswhi Optional[float] 1.5 derived VSWHI (pu): MODSW 0..2: targetValue = (VSWHI + VSWLO) / 2 and targetDeadband = VSWHI - VSWLO, x the regulated bus's BASKV, in V (volts_from_per_unit); MODSW 3, 6: pu of the device's Q range, in VAr (reactive_band; R2b-1, R2b-2), listed when there is no machine at SWREG; blank: 1.0 (defaulted)
vswlo Optional[float] 0.5 derived VSWLO (pu): as VSWHI
swreg Optional[int] 4001, 4005, 6104 structural SWREG: the regulated bus; the control's Terminal = bb_T1, or bb_T1 when 0 (RAW-11); MODSW 3: the plant's bus, Terminal = its machine's T1 (several machines raise; none: the control disabled on bb_T1, R2b-1); MODSW 6: unused; blank: 0 (defaulted)
rmpct Optional[float] 100.0 untranscribed RMPCT: CIM has no participation share for a shunt (CIM 18 gap)
rmidnt Optional[str] structural RMIDNT: MODSW 6: the FACTS device, Terminal fd__T1 (R2b-2); only MODSW 4 (raises) uses it otherwise
binit Optional[float] 600.0, 0.0, 400.0 derived BINIT (Mvar at 1 pu): split into each block's sections in RAW's switching order (block_sections); an SVC's q (MVAr) = -BINIT (svc_q, R2c); beyond the blocks' total raises; blank: 0 (defaulted)
n1 Optional[int] 5, 6 structural Ni / Bi: block i, a LinearShuntCompensator swsh__b with maximumSections = Ni and bPerSection (pu system) = Bi / SBASE (per_unit_from_mva), up to the first Ni or Bi of 0 (RAW's end of blocks); a block after it raises; an SVC's reactor and capacitor are its inductiveRating and capacitiveRating (pu system) = SBASE / Bi (svc_reactance, R2c); never defaulted
b1 Optional[float] 200.0, 100.0 structural Ni / Bi: block i, a LinearShuntCompensator swsh__b with maximumSections = Ni and bPerSection (pu system) = Bi / SBASE (per_unit_from_mva), up to the first Ni or Bi of 0 (RAW's end of blocks); a block after it raises; an SVC's reactor and capacitor are its inductiveRating and capacitiveRating (pu system) = SBASE / Bi (svc_reactance, R2c); never defaulted
n2 Optional[int] structural Ni / Bi: block i, a LinearShuntCompensator swsh__b with maximumSections = Ni and bPerSection (pu system) = Bi / SBASE (per_unit_from_mva), up to the first Ni or Bi of 0 (RAW's end of blocks); a block after it raises; an SVC's reactor and capacitor are its inductiveRating and capacitiveRating (pu system) = SBASE / Bi (svc_reactance, R2c); never defaulted
b2 Optional[float] structural Ni / Bi: block i, a LinearShuntCompensator swsh__b with maximumSections = Ni and bPerSection (pu system) = Bi / SBASE (per_unit_from_mva), up to the first Ni or Bi of 0 (RAW's end of blocks); a block after it raises; an SVC's reactor and capacitor are its inductiveRating and capacitiveRating (pu system) = SBASE / Bi (svc_reactance, R2c); never defaulted
n3 Optional[int] structural Ni / Bi: block i, a LinearShuntCompensator swsh__b with maximumSections = Ni and bPerSection (pu system) = Bi / SBASE (per_unit_from_mva), up to the first Ni or Bi of 0 (RAW's end of blocks); a block after it raises; an SVC's reactor and capacitor are its inductiveRating and capacitiveRating (pu system) = SBASE / Bi (svc_reactance, R2c); never defaulted
b3 Optional[float] structural Ni / Bi: block i, a LinearShuntCompensator swsh__b with maximumSections = Ni and bPerSection (pu system) = Bi / SBASE (per_unit_from_mva), up to the first Ni or Bi of 0 (RAW's end of blocks); a block after it raises; an SVC's reactor and capacitor are its inductiveRating and capacitiveRating (pu system) = SBASE / Bi (svc_reactance, R2c); never defaulted
n4 Optional[int] structural Ni / Bi: block i, a LinearShuntCompensator swsh__b with maximumSections = Ni and bPerSection (pu system) = Bi / SBASE (per_unit_from_mva), up to the first Ni or Bi of 0 (RAW's end of blocks); a block after it raises; an SVC's reactor and capacitor are its inductiveRating and capacitiveRating (pu system) = SBASE / Bi (svc_reactance, R2c); never defaulted
b4 Optional[float] structural Ni / Bi: block i, a LinearShuntCompensator swsh__b with maximumSections = Ni and bPerSection (pu system) = Bi / SBASE (per_unit_from_mva), up to the first Ni or Bi of 0 (RAW's end of blocks); a block after it raises; an SVC's reactor and capacitor are its inductiveRating and capacitiveRating (pu system) = SBASE / Bi (svc_reactance, R2c); never defaulted
n5 Optional[int] structural Ni / Bi: block i, a LinearShuntCompensator swsh__b with maximumSections = Ni and bPerSection (pu system) = Bi / SBASE (per_unit_from_mva), up to the first Ni or Bi of 0 (RAW's end of blocks); a block after it raises; an SVC's reactor and capacitor are its inductiveRating and capacitiveRating (pu system) = SBASE / Bi (svc_reactance, R2c); never defaulted
b5 Optional[float] structural Ni / Bi: block i, a LinearShuntCompensator swsh__b with maximumSections = Ni and bPerSection (pu system) = Bi / SBASE (per_unit_from_mva), up to the first Ni or Bi of 0 (RAW's end of blocks); a block after it raises; an SVC's reactor and capacitor are its inductiveRating and capacitiveRating (pu system) = SBASE / Bi (svc_reactance, R2c); never defaulted
n6 Optional[int] structural Ni / Bi: block i, a LinearShuntCompensator swsh__b with maximumSections = Ni and bPerSection (pu system) = Bi / SBASE (per_unit_from_mva), up to the first Ni or Bi of 0 (RAW's end of blocks); a block after it raises; an SVC's reactor and capacitor are its inductiveRating and capacitiveRating (pu system) = SBASE / Bi (svc_reactance, R2c); never defaulted
b6 Optional[float] structural Ni / Bi: block i, a LinearShuntCompensator swsh__b with maximumSections = Ni and bPerSection (pu system) = Bi / SBASE (per_unit_from_mva), up to the first Ni or Bi of 0 (RAW's end of blocks); a block after it raises; an SVC's reactor and capacitor are its inductiveRating and capacitiveRating (pu system) = SBASE / Bi (svc_reactance, R2c); never defaulted
n7 Optional[int] structural Ni / Bi: block i, a LinearShuntCompensator swsh__b with maximumSections = Ni and bPerSection (pu system) = Bi / SBASE (per_unit_from_mva), up to the first Ni or Bi of 0 (RAW's end of blocks); a block after it raises; an SVC's reactor and capacitor are its inductiveRating and capacitiveRating (pu system) = SBASE / Bi (svc_reactance, R2c); never defaulted
b7 Optional[float] structural Ni / Bi: block i, a LinearShuntCompensator swsh__b with maximumSections = Ni and bPerSection (pu system) = Bi / SBASE (per_unit_from_mva), up to the first Ni or Bi of 0 (RAW's end of blocks); a block after it raises; an SVC's reactor and capacitor are its inductiveRating and capacitiveRating (pu system) = SBASE / Bi (svc_reactance, R2c); never defaulted
n8 Optional[int] structural Ni / Bi: block i, a LinearShuntCompensator swsh__b with maximumSections = Ni and bPerSection (pu system) = Bi / SBASE (per_unit_from_mva), up to the first Ni or Bi of 0 (RAW's end of blocks); a block after it raises; an SVC's reactor and capacitor are its inductiveRating and capacitiveRating (pu system) = SBASE / Bi (svc_reactance, R2c); never defaulted
b8 Optional[float] structural Ni / Bi: block i, a LinearShuntCompensator swsh__b with maximumSections = Ni and bPerSection (pu system) = Bi / SBASE (per_unit_from_mva), up to the first Ni or Bi of 0 (RAW's end of blocks); a block after it raises; an SVC's reactor and capacitor are its inductiveRating and capacitiveRating (pu system) = SBASE / Bi (svc_reactance, R2c); never defaulted
nreg Optional[int] structural NREG: a node of bus SWREG; nonzero: the control's Terminal is that node's busbar bb_s_n_T1 (R6, RAW-11); blank: 0 (defaulted)

Branches and switched shunts: the forms R1 and R2 raised on (R1b, R2b)

Approved 2026-11-09 (user: "line at bus I's base", "load sign, as spec", "disabled control", "approve, implement") and implemented. Mappers: branch.py, multi_section_line.py, switched_shunt.py. The local case set (29 cases of one network, never committed, counted only) has these in every case: 18 branches between two base voltages, 1 series capacitor with a length, 35 multi-section lines holding a series capacitor, 25 switched shunts with MODSW 3 and 3 or 4 with MODSW 6.

A branch between two base voltages (decision R1b-1)

PSS/E solves in per unit, so a branch's R, X and B on SBASE need no kV. CIM gives an ACLineSegment one BaseVoltage. Of the 18: 10 are out of service, 3 are zero-impedance jumpers, none has X < 0; 10 have a BASKV ratio ≤ 1.095 (labels of one voltage) and 8 one of 1.5 to 2.0. None has a line shunt.

  • The line (or capacitor) keeps its class and bus I's base: BaseVoltage bv_<BASKV(I)>, every (pu system) value and a CurrentLimit on BASKV(I). Its row lists bus J's: # BASKV 240.0 at bus J.
  • The exporter converts back on the line's own base, so the values round-trip exactly.
  • A line shunt keeps its own bus's base: GJ + jBJ is on bus J's BASKV. R1 used the line's base for both ends, which is the same whenever the two buses share one.
  • Not a nominal-ratio transformer: it would invent equipment and have no place for the pi-split B. A kV solve sees the step between the two bases at bus J (expected solve difference).

A series capacitor with a length (decision R1b-2)

A SeriesCompensator is no Conductor, so LEN ≠ 0 is listed on its row (untranscribed: length=1.0), as GTAP is in R3b-4. A series capacitor with B ≠ 0 still raises (no case).

A multi-section line holding a series capacitor (decision R1b-3)

Every capacitor section of the set (44) has both buses in one substation, which the capacitor merges; every line section (39) spans two. A section already in a substation stays contained there, with no EquipmentContainer Update row (an Update only adds, so it clashed with the capacitor's substation at bind time). It joins its Line through CIM's second container association instead, Equipment.AdditionalEquipmentContainer ↔ EquipmentContainer.AdditionalGroupedEquipment (amended 2026-11-09 for the exporter's E1, user: "AdditionalGrouped"), so the Line groups every section wherever it sits in the path:

Update Table SeriesCompensator: mRID, AdditionalEquipmentContainer
    sc_2_3_1, msl_1_4_&1

The Line's row still lists it: # path 1, 2, 3, 4; in substations: sc_2_3_1. The rule is the same for a line section inside one substation (none in the set).

MODSW 3: a plant's reactive power (decision R2b-1)

24 of the 25 regulate the single machine at SWREG: 17 WMOD 1 in service, 7 out of service, none behind a step-up, 22 in another substation than the shunt.

  • RegulatingControl cc_<I>: mode = reactivePower, discrete = true, enabled = true, Terminal = the machine's own <machine>_T1 (sm_ or pec_<SWREG>_<ID>_T1, generator.machine_mrid), where PSS/E measures QG (behind a step-up, still the machine's).
  • Band: VSWLO and VSWHI are pu of the plant's QT − QB. The band runs QB + VSWLO × (QT − QB) to QB + VSWHI × (QT − QB) Mvar, from that machine's QT and QB as written. Its status is ignored, so the exporter inverts exactly.
  • targetValue = −(the band's midpoint) and targetDeadband = its width, in VAr (reactive_band): the terminal's Q under CIM's load sign, as the machine's q = −QG.
  • A plant of several machines at SWREG raises: one terminal measures one machine (no case).
  • No machine at SWREG (1 a case: SWREG = I, a type 1 bus, out of service, VSW 0 / 1). PSS/E requires a type 2 or 3 bus, so it cannot regulate. The control is written disabled (enabled = false, the blocks' controlEnabled = false), with no target, on bb_<SWREG>_T1, and VSWHI / VSWLO off their defaults are listed: untranscribed: vswlo=0.0. The exporter writes MODSW 3 from the mode.

MODSW 6: a FACTS device's shunt reactive power (decision R2b-2)

Each names a shunt-only FACTS device by RMIDNT (J = 0, mapped in P2a; SWREG is unused).

  • mode = reactivePower, discrete = true, enabled = true, Terminal = the StaticSynchronousCompensator's fd_<RMIDNT>_T1.
  • Band: −SHMX + VSWLO × 2 SHMX to −SHMX + VSWHI × 2 SHMX Mvar; the target and deadband as R2b-1. The set's symmetric bands (0.375 / 0.625, 0.4 / 0.6) give a target of 0.
  • An RMIDNT naming no FACTS device raises; so does one with a series element, whose range the bridge transfer reduces (no case).

MODSW 4 (a VSC converter's Q) and 5 (another shunt's admittance) still raise: no case has one.

Order

A control's Terminal must bind before it (an unresolved mRID raises), so switched_shunt.cimtbl follows generator.cimtbl and facts_device.cimtbl in the master's Import order. No golden changes: neither IEEE14 nor IEEE118 has a switched shunt.

Atoms (hand-built)

  • tests/atoms/branch/mixed_base.raw (the multi_section_line.raw frame): 230 kV buses 1-4 and 240 kV bus 5; a multi-section line 1-4 &1 through 2 and 3 whose middle section 2-3 is a series capacitor with LEN 1.0; a line 4-5 between the two bases with B and BJ.
  • tests/atoms/shunt/plant_and_facts.raw (the generators.raw frame): a WMOD 1 machine at bus 1 (QT 50, QB −30) that a MODSW 3 shunt at bus 2 regulates over 0.25 / 0.75 (target −10 Mvar, deadband 40); a MODSW 3 shunt at bus 3 with no plant; a FACTS device SVC-1 at bus 4 (SHMX 100) that a MODSW 6 shunt at bus 5 regulates over 0.4 / 0.6.

Raise tests: MODSW 4 and 5, a plant of two machines, an RMIDNT naming no FACTS device; the series capacitor with B ≠ 0 still raises.

CIM 18 gaps

None new. The line's two base voltages are a RAW labelling; a shunt's participation share (RMPCT) is still a gap.

Results

All 29 local cases map their branches, multi-section lines and switched shunts. One case binds whole in 66 s with only its 50 WMOD 2/3 generators set aside: 14380 ACLineSegments, 66 SeriesCompensators, 35 Lines; of its 28 reactivePower controls, 24 are on machines and 3 on FACTS devices, and 1 (no plant) is disabled.

Switched shunt: a static var compensator (R2c)

User 2026-11-28 ("SVC support for the cimhub_raw importer and exporter"; chose a MODSW 2 switched shunt as the RAW form, and the import rule below). Mapper: importer/cimtbl/switched_shunt.py. RAW v34 has no SVC record: PSS/E models an SVC as a continuous switched shunt, whose susceptance varies between its blocks' limits, so its output scales with V², as an SVC's does. (A shunt-only FACTS device is current-limited, a STATCOM, P2-2.)

Which shunts (decision R2c-1)

A switched shunt is a StaticVarCompensator when MODSW = 2 (continuous voltage control) and its blocks are at most one reactor and one capacitor, each of one step (is_static_var_compensator). That is the whole range CIM's SVC can say, so nothing is lost. Every other shunt stays blocks: several steps, two reactors or two capacitors, MODSW 0, 1, 3, 6. The switched-shunts atom's MODSW 2 shunt (4 × 12.5) stays blocks; neither public case has a MODSW 2 shunt.

Rows

Table StaticVarCompensator: mRID, name, bus, capacitiveRating (pu system), inductiveRating (pu system), q (MVAr), sVCControlMode, inService, controlEnabled, RegulatingControl, BaseVoltage, EquipmentContainer
    swsh_1, 1, 1, 1.0,                -2.0, -40.0, voltage, true,  true, cc_1, bv_230kv, sub_1
    swsh_2, 2, 2, 3.3333333333333335, ,     0.0,   voltage, false, true, cc_2, bv_230kv, sub_2
field target
I mRID swsh_<I> (the blocks' prefix without _b<k>), name I, bus, BaseVoltage, the bus's substation
the capacitor block's Bi capacitiveRating (pu system) = SBASE / Bi (svc_reactance): X = U² / Q at 1 pu, positive
the reactor block's Bi inductiveRating (pu system) = SBASE / Bi: negative, as CIM's rating is
BINIT q (MVAr) = −BINIT (svc_q): the SVC's starting output at 1 pu under the load sign; beyond the blocks' range raises (block_sections)
MODSW 2 sVCControlMode voltage, controlEnabled true; the RegulatingControl cc_<I> as any MODSW 2 shunt's (target, deadband, SWREG, NREG)
STATUS inService
  • A block of no sign is left blank: a capacitor-only SVC has no inductiveRating.
  • voltageSetPoint and slope are blank: the control carries the target, and RAW has no droop.
  • No nomU: the SVC has none, and (pu system) reads the BaseVoltage.
  • ADJM and RMPCT stay untranscribed, as for any switched shunt.

Atom tests/atoms/shunt/svc.raw (hand-built)

The switched-shunts frame (230 kV buses 1-3, 115 kV bus 4): bus 1 MODSW 2 regulating bus 4 over 1.00 / 1.02, 1 × −50 then 1 × 100 Mvar, BINIT 40 (an SVC); bus 2 MODSW 2 out of service, 1 × 30, BINIT 0 (a capacitor-only SVC); bus 3 MODSW 2 with two reactors 1 × −20 and 1 × −10 (blocks); bus 4 MODSW 1 with 1 × −10 and 1 × 20 (blocks).

Export

E6a in EXPORT_MAPPING.md: a reactor-then-capacitor MODSW 2 record, so the atom round-trips with only SWREG 0 → I.

Generator (R3)

Approved 2026-11-08 and implemented. RAW-7, RAW-23, RAW-24, RAW-25. Atom: tests/atoms/generator/.

Mapper: importer/cimtbl/generator.py (map_generator). Shape: synchronous_machine (bus-branch), new (C2), and the der shape's PowerElectronicsConnection with bus. - What a record is: one machine, or several aggregated, at bus I. PSS/E treats VS, IREG and RMPCT as plant quantities: every machine at bus I shares them, and the plant's output and limits are the sums of its in-service machines'. - Class by WMOD (RAW-24): WMOD is PSS/E's own line between a conventional machine (0) and a renewable or infeed one (1-4), whose reactive limits do not come from a synchronous machine.

WMOD CIM, per record
0 conventional SynchronousMachine + GeneratingUnit + ControlAreaGeneratingUnit
1 renewable, limits QT/QB PowerElectronicsConnection + PowerElectronicsUnit (concrete in cim18v17, no kind) + ControlAreaPowerElectronicsUnit
2, 3 renewable, Q limits or Q from WPF as WMOD 1; a WMOD 3 plant's control is powerFactor (R3c, below; raised until then)
4 infeed, fixed Q raise NotImplementedError: no case has one yet
  • CSP vs PV: a concentrating solar thermal plant drives a synchronous generator from a steam turbine. PSS/E models it as a conventional machine, WMOD 0, so it lands on SynchronousMachine + GeneratingUnit. SolarGeneratingUnit is not in cim18v17, and RAW has no fuel anyway. WMOD 1 is a converter-interfaced plant (PV, type 3/4 wind), and PowerElectronicsConnection is its class.
  • WECC240's 37 WMOD 1 machines are its aggregated wind (11) and solar (26) plants. That count comes from the working workbook kept with the earlier CIMHub copy of the case, which does not say PV or CSP. The case is built for a study of high renewable integration.
  • What stays a gap: RAW cannot say PV or wind (so no PhotoVoltaicUnit / PowerElectronicsWindUnit). Nor can it say a type 1/2 wind plant, an induction machine (AsynchronousMachine), entered as WMOD 1.
  • Per plant: one RegulatingControl for all the machines and connections at bus I. This matches the physical joint voltage control, and the switched shunt's form (one control, several pieces of equipment). A plant and a switched shunt regulating the same bus have their own controls: their setpoints differ (a VS and a band). WECC240 has three such buses (4001, 4005, 7001).
  • Order: RegulatingControl; GeneratingUnit, ControlAreaGeneratingUnit, SynchronousMachine; PowerElectronicsConnection, PowerElectronicsUnit, ControlAreaPowerElectronicsUnit. Each reference points backwards, so no Update is needed.

WECC240 (bus 1032: two machines and a converter plant regulating 1002; 3933: the swing plant):

# one per plant (bus I); targetValue in V
Table RegulatingControl: mRID, name, mode, discrete, enabled, targetValue, Terminal
    gc_1032, 1032, voltage, false, true,  349830.0,           bb_1002_T1
    gc_1333, 1333, voltage, false, true,  346724.99999999994, bb_1303_T1
    gc_3933, 3933, voltage, false, true,  20400.0,            bb_3933_T1
    ...
Table GeneratingUnit: mRID, name, maxOperatingP (MW), minOperatingP (MW), EquipmentContainer
    gu_1032_C,  1032_C,  873.0,   0.0,     sub_1032
    ...
Table ControlAreaGeneratingUnit: mRID, name, ControlArea, GeneratingUnit
    cagu_1032_C,  1032_C,  ca_1, gu_1032_C
    ...
# WMOD 0
# untranscribed: zx, o1, o2, o3, o4, f1, f2, f3, f4, wpf
Table SynchronousMachine: mRID, name, bus, p (MW), q (MVAr), maxQ (MVAr), minQ (MVAr), ratedS (MVA), r (ohm), qPercent, referencePriority, inService, controlEnabled, RegulatingControl, GeneratingUnit, BaseVoltage, EquipmentContainer
    # defaulted: wmod=0, nreg=0
    sm_1032_C,  1032_C,  1032, -712.0,    3.332,    200.0,  -200.0,  873.0,   0.0, 100.0, ,  true,  true,  gc_1032, gu_1032_C,  bv_20kv, sub_1032
    ...
    sm_3933_CG, 3933_CG, 3933, -404.88,   -88.652,  363.0,  -82.0,   865.0,   0.0, 100.0, 1, true,  true,  gc_3933, gu_3933_CG, bv_20kv, sub_3903
    ...
# WMOD 1; untranscribed here also: zr, rmpct (no qPercent)
# untranscribed: zx, o1, o2, o3, o4, f1, f2, f3, f4, wpf
Table PowerElectronicsConnection: mRID, name, bus, p (MW), q (MVAr), maxQ (MVAr), minQ (MVAr), ratedS (MVA), inService, controlEnabled, RegulatingControl, BaseVoltage, EquipmentContainer
    pec_1032_S,  1032_S,  1032, -520.0,   3.332,    360.0,  -360.0,  638.0,  true, true, gc_1032, bv_20kv, sub_1032
    ...
Table PowerElectronicsUnit: mRID, name, maxP (MW), minP (MW), PowerElectronicsConnection, EquipmentContainer
    pecu_1032_S,  1032_S,  638.0,  0.0, pec_1032_S,  sub_1032
    ...
Table ControlAreaPowerElectronicsUnit: mRID, name, ControlArea, PowerElectronicsUnit
    capu_1032_S,  1032_S,  ca_1, pecu_1032_S
    ...
  • mRIDs (prefixes requested, C3), all keyed <I>_<ID> with name I_ID:
  • sm_, gu_, cagu_ for WMOD 0, and pec_, pecu_, capu_ for WMOD 1. The der shape's pv_ and <pec>_unit assume the kind (PV) is known, and here it is not;
  • the plant control is gc_<I>. It cannot be cc_<I>, the switched shunt's, since one bus can have both.
  • Sign (RAW-14): p = −PG and q = −QG on both classes, which use the load sign convention ("positive sign means flow out from a node"), so generation is negative.
  • The limits keep the generator convention, as CIM writes them, all copied: maxQ = QT, minQ = QB, and PT/PB → maxOperatingP/minOperatingP (unit) or maxP/minP (power-electronics unit).
  • WECC240 has 5 machines with PB < 0 (pumping), copied as is.
  • Rating: ratedS = MBASE (blank: SBASE, the schema rule, defaulted). ratedU is blank: RAW has no machine voltage.
  • Plant control:
  • mode = voltage, discrete = false, targetValue = VS × the regulated bus's BASKV in V (volts_from_per_unit), targetDeadband blank (PSS/E holds VS exactly). The product can leave a last-digit float residue (1.005 × 345 kV is 346724.99999999994): written as computed, never rounded, so the exporter's VS can differ in the last digit (expected difference). r (ohm) likewise;
  • Terminal = bb_<IREG>_T1, or bb_<I>_T1 when IREG is 0 or I (RAW-11). WECC240: 137 of 146 machines regulate a remote bus, and 7 regulate their own (the swing plant at 3933);
  • enabled = bus I's IDE is 2 or 3, and every member's controlEnabled follows it. An IDE 1 bus has no voltage control (WECC240's machine at 3432 is on one, out of service). The exporter writes IDE 2 for a bus with an enabled plant control and 1 otherwise, so IDE 1/2 round-trip;
  • the plant's records must agree on VS, IREG and RMPCT, as PSS/E requires. A disagreement raises with both IDs;
  • a remote IREG from a swing bus raises (PSS/E would silently regulate bus I instead), and so does an IREG that is no bus. NREG ≠ 0 names node NREG of the regulated bus: bb_s<IS>_n<NREG>_T1, that node's busbar (R6). NREG is a plant quantity, so the plant's records must agree on it too.
  • RMPCT: qPercent on every SynchronousMachine of the plant (added to the profile 2026-11-08). A PowerElectronicsConnection has none, so its row lists RMPCT untranscribed, and the exporter takes the plant's RMPCT from one of its machines, else from a connection's listed RMPCT (R3c-3: listed when not 100), else 100. Gap: the shunt RMPCT gap now covers power-electronics connections too. RMPCT is 100 everywhere in both cases.
  • Swing bus: IDE 3 → referencePriority = 1 on every SynchronousMachine at the bus (added to the profile 2026-11-08; "1 = highest priority" for the angle-reference choice); blank elsewhere. The exporter writes IDE 3 for a bus with such a machine. A swing bus with no in-model SynchronousMachine (only WMOD 1 records) raises; no case has one. The 3933 swing plant has 5 machines and 2 connections.
  • Status: inService = STAT == 1 on the machine or connection. The units carry no status of their own.
  • Area: each unit's control-area membership → ca_<AREA of bus I>. A generator record has no AREA. A bus AREA with no area-interchange record raises, as for loads.
  • ZSORCE (RAW-23): ZR/ZX are the source impedance for switching, fault and dynamic studies (pu on MBASE).
  • ZR → r (ohm) = ZR × BASKV² / MBASE on a SynchronousMachine (ohms_from_per_unit, through the units library);
  • ZX: TODO, a new profile extension. cim18v17's SynchronousMachine has no positive-sequence reactance (the canonical saturated satDirect*X were never in it). It stays untranscribed until the extension lands. The exporter writes the default 1.0 meanwhile, an expected difference for WECC240 (0.2);
  • on a PowerElectronicsConnection, both are untranscribed: a converter has no ZSORCE in CIM. Since R3c-3 a ZR ≠ 0 is listed on its row.
  • Step-up transformer (RAW-25, superseded by R3b below): RT + jXT ≠ 0 (an implicit GSU) raised NotImplementedError until a case had one; both public cases model their GSUs as transformer branches (RT = XT = 0). R3b maps it with the core shape behind_transformer.cimtbl (plan C8).
  • Untranscribed: ZX (TODO extension), O1..F4 (ownership, CIM 18 gap). WPF was too, until R3c mapped WMOD 2/3.
  • Atom tests/atoms/generator/generators.raw:
  • a plant of one WMOD 0 machine and one WMOD 1 connection regulating a remote bus, with one member out of service;
  • a swing plant;
  • a machine on an IDE 1 bus (control disabled);
  • a record with every optional field blank (all defaulted, MBASE = SBASE).

Raise tests: plant records that disagree on VS, IREG, NREG or RMPCT; RT/XT ≠ 0 (until R3b); WMOD 2, 3 (until R3c) and 4; a remote IREG from a swing bus; an IREG that is no bus; a swing bus with only WMOD 1 records. - ratedU (amended 2026-11-09 by the exporter's E3-1, user: "importer writes BASKV"): every SynchronousMachine and PowerElectronicsConnection gets ratedU = BASKV(I). RAW gives no machine kV; MBASE and ZR are on BASKV, and the export getters (get_machine_rating, get_inverter_rating, get_machine_impedance("pu")) require a ratedU. A machine behind a step-up keeps bus I's base too (R3b-2). - Checks: all 151 records bind (IEEE14 5 machines; WECC240 109 machines and 37 connections). In SI, each p = −PG in W, each target = VS × BASKV in V, and each unit reaches its bus's ControlArea. Each plant has one control.

GeneratorRecord field type samples kind target
bus_number int 1032, 1034, 1131 structural I: the machine's bus, BaseVoltage, EquipmentContainer (its substation) and ControlArea (the bus's AREA, through ControlAreaGeneratingUnit or ControlAreaPowerElectronicsUnit); the plant key gc_; IDE 2 or 3 enables the plant control, IDE 3 sets referencePriority = 1 on its SynchronousMachines
gen_id Optional[str] C, G, S structural ID: with I the key, mRIDs sm_/gu_/cagu_ or pec_/pecu_/capu__, name I_ID; blank: 1 (defaulted)
p_output Optional[float] 712.0, 856.0, 520.0 derived PG (MW): p = -PG, load sign convention (generation_p_q, RAW-14); blank: 0 (defaulted)
q_output Optional[float] -3.332, 262.628, -46.791 derived QG (Mvar): q = -QG, load sign convention (generation_p_q, RAW-14); blank: 0 (defaulted)
max_q_output Optional[float] 200.0, 357.0, 360.0 copied SynchronousMachine.maxQ (MVAr), PowerElectronicsConnection.maxQ (MVAr); QT, generator convention as CIM's limit; blank: 9999 (defaulted)
min_q_output Optional[float] -200.0, -357.0, -360.0 copied SynchronousMachine.minQ (MVAr), PowerElectronicsConnection.minQ (MVAr); QB; blank: -9999 (defaulted)
regulated_voltage_setpoint Optional[float] 1.014, 1.03, 1.01 derived VS (pu): targetValue = VS x the regulated bus's BASKV, in V (volts_from_per_unit); a plant quantity, shared by every machine at bus I (they must agree, else raise); blank: 1.0 (defaulted)
regulated_bus_number Optional[int] 1002, 1004, 1101 structural IREG: the plant control's Terminal bb_T1, or bb_T1 when 0 (RAW-11), or the NREG node's busbar; a remote IREG from a swing bus raises; a plant quantity, shared by every machine at bus I (they must agree, else raise); blank: 0 (defaulted)
rated_mva Optional[float] 873.0, 1050.0, 638.0 copied SynchronousMachine.ratedS (MVA), PowerElectronicsConnection.ratedS (MVA); MBASE, with ratedU = bus I's BASKV: RAW gives no machine kV, and MBASE and ZR are on BASKV (E3-1, as R3b-2); blank: SBASE (defaulted)
zr Optional[float] 0.0 derived ZR (pu on MBASE): SynchronousMachine r (ohm) = ZR x BASKV^2 / MBASE (ohms_from_per_unit); listed on a PowerElectronicsConnection's row when not 0 (R3c-3); blank: 0 (defaulted)
zx Optional[float] 0.2 untranscribed ZX: cim18v17 has no positive-sequence machine reactance (TODO: a profile extension, RAW-23)
rt Optional[float] 0.0 derived RT (pu on MBASE): RT + jXT != 0 is an implicit step-up transformer _xf, the machine on its internal node _int (R3b-1); end 1 r (ohm) = RT x BASKV^2 / MBASE (ohms_from_per_unit); blank: 0 (defaulted)
xt Optional[float] 0.0 derived XT (pu on MBASE): as RT, end 1 x (ohm)
gtap Optional[float] 1.0 derived GTAP: with a step-up, a fixed RatioTapChanger _xf_tap1 on end 1, neutralU = GTAP x BASKV (R3b-1, R4b-4), none at 1; without one, PSS/E ignores it and it is listed on the machine row when not 1 (R3b-4); blank: 1.0 (defaulted)
status Optional[int] 1, 0 mapped STAT: inService = (STAT == 1); blank: 1 (defaulted)
rmpct Optional[float] 100.0 copied SynchronousMachine.qPercent; RMPCT, on every SynchronousMachine of the plant; a PowerElectronicsConnection has no qPercent (CIM 18 gap): listed on its row when not 100 (R3c-3); a plant quantity, shared by every machine at bus I (they must agree, else raise); blank: 100 (defaulted)
max_p_output Optional[float] 873.0, 1050.0, 638.0 copied GeneratingUnit.maxOperatingP (MW), PowerElectronicsUnit.maxP (MW); PT, by WMOD; blank: 9999 (defaulted)
min_p_output Optional[float] 0.0, -1006.0, -2841.0 copied GeneratingUnit.minOperatingP (MW), PowerElectronicsUnit.minP (MW); PB, by WMOD; blank: -9999 (defaulted)
o1 Optional[int] 1 untranscribed ownership is an asset concept (CIM 18 gap)
f1 Optional[float] 1.0 untranscribed ownership is an asset concept (CIM 18 gap)
o2 Optional[int] 0 untranscribed ownership is an asset concept (CIM 18 gap)
f2 Optional[float] 1.0 untranscribed ownership is an asset concept (CIM 18 gap)
o3 Optional[int] 0 untranscribed ownership is an asset concept (CIM 18 gap)
f3 Optional[float] 1.0 untranscribed ownership is an asset concept (CIM 18 gap)
o4 Optional[int] 0 untranscribed ownership is an asset concept (CIM 18 gap)
f4 Optional[float] 1.0 untranscribed ownership is an asset concept (CIM 18 gap)
wmod Optional[int] 1 mapped WMOD: the class (RAW-24), 0 conventional a SynchronousMachine + GeneratingUnit, 1 (QT/QB limits), 2 (limits from WPF) and 3 (fixed power factor) renewable a PowerElectronicsConnection + PowerElectronicsUnit; 3 makes the plant control powerFactor (R3c-2); 4 raises until a case has one; blank: 0 (defaulted)
wpf Optional[float] 1.0 mapped WPF: WMOD 2, always listed on the row (no CIM limit follows P, R3c-1); WMOD 3, the plant control's targetValue, signed (positive: q has p's sign, R3c-2); unused otherwise; blank: 1.0 (defaulted)
nreg Optional[int] structural NREG: a node of bus IREG; nonzero: the plant control's Terminal is that node's busbar bb_s_n_T1 (R6, RAW-11); a plant quantity, shared by every machine at bus I (they must agree, else raise); blank: 0 (defaulted)

Generator: the implicit step-up transformer (R3b)

Approved 2026-11-09 (user: "bus I's base", "on the machine as written", "approve, implement") and implemented. Extends R3 (RAW-25). Mapper: generator.py; the core shape behind_transformer.cimtbl (plan C8), already followed by the converter transformer (P2-5). The local case set (29 cases of one network, never committed, counted only) has 213 generators with RT + jXT ≠ 0 in every case: 212 WMOD 0 and 1 WMOD 1, 80 in service, 8 with GTAP ≠ 1, 1 with XT = 0 (RT alone), 13 regulating a remote bus, up to 4 machines a bus. None sits in a node-breaker substation. WMOD 2/3 (50 a case) is the other half of R3b, mapped by R3c below.

The form (decision R3b-1)

The format document's figure of the implicit method puts the ideal ratio GTAP : 1 at the high-voltage bus I and XTRAN (pu on MBASE) between it and the machine. That is an R4 2-winding transformer with CW 1, CZ 2, SBASE1-2 = MBASE, WINDV1 = GTAP, WINDV2 = 1 and COD 0, so the step-up maps the way R4 would map that record:

  • Internal node: TopologicalNode <machine>_int (sm_ or pec_<I>_<ID>_int), named <I>_<ID> terminal, with no busNumber, in bus I's substation. The machine (SynchronousMachine or PowerElectronicsConnection) sits on it.
  • Transformer: PowerTransformer <machine>_xf, named <I>_<ID> step-up, in bus I's substation, always in service (it has no status of its own in RAW, as P2-5).
  • End 1 <machine>_xf_1 on bus I: ratedU = BASKV(I), ratedS = MBASE, r, x = RT, XT × BASKV(I)² / MBASE (ohm; ohms_from_per_unit, R4's CZ 2).
  • End 2 <machine>_xf_2 on the internal node: ratedU = BASKV(I), ratedS = MBASE. No magnetizing branch.
  • GTAP ≠ 1: a fixed RatioTapChanger <machine>_xf_tap1 on end 1 (R4b-4: one step, neutralU = GTAP × BASKV(I) in kV, no control). GTAP = 1 has none (205 of 213).

The internal node's voltage (decision R3b-2)

RAW does not give the machine's terminal voltage: XTRAN and GTAP are in per unit, on MBASE and the system base. So the internal node, end 2 and the machine keep bus I's BaseVoltage, a per-unit equivalent. No BaseVoltage is added, and ZR keeps its R3 conversion on BASKV(I). The machine's terminal kV is missing from RAW, not from CIM. The exporter gets the record back: RT, XT = r, x × ratedS / ratedU1², GTAP = neutralU / ratedU1 (1 without a tap).

Power, limits and control stay on the machine (decision R3b-3)

PG, QG, QT, QB, PT, PB and MBASE map as R3, on the machine and its unit. The plant control gc_<I> stays on bus I's busbar (bb_<I>_T1, or IREG's): the format document makes bus I the regulated bus of the implicit method. PSS/E's power flow injects PG + jQG at bus I and uses XTRAN only in fault analysis and dynamics. A CIM solve that includes the step-up sees its losses (I²X of Mvar), an expected solve difference; the round trip is exact.

GTAP without a step-up (decision R3b-4)

GTAP is used only when RT + jXT ≠ 0. 11 generators a case have GTAP ≠ 1 without one; PSS/E ignores it. It is listed on the machine row (untranscribed: gtap=…) so the exporter can write it back.

Node-breaker terminals (decision R3b-5)

An equipment terminal record (R6) naming a machine with a step-up places the transformer's end-1 terminal <machine>_xf_T1 on its node: the machine's own terminal is on the internal node. None in the set; the atom tests it.

Atom tests/atoms/generator/step_up.raw (hand-built)

The generators.raw frame (230 kV and 13.8 kV buses) with: a machine behind a step-up at GTAP 1; one at GTAP 1.025; an RT-only step-up; a WMOD 1 connection behind a step-up; a plant of two machines, one with a step-up and one without, regulating a remote bus; a machine without a step-up with GTAP 1.02 (listed). Raise tests: none new (a step-up no longer raises); the node-breaker placement is tested on a GSU added to node_breaker_forms.raw in memory.

CIM 18 gaps

None new: the step-up is ordinary CIM. The machine's terminal kV is absent from RAW itself.

Results

All 29 local cases map their 213 step-ups (8 with a fixed tap). One case binds whole in 66 s with only WMOD 2/3 and the R1b/R2b records set aside: its 7653 PowerTransformers are 7402 transformer records, 38 converter transformers and 213 step-ups, and its 18172 TopologicalNodes are 17921 buses and 251 internal nodes.

Generator: renewables with a power factor (R3c, WMOD 2 and 3)

Approved 2026-11-09 (user: "powerFactor control", "WMOD 1 + WPF listed", "all connections", "approve, implement") and implemented. Extends R3 (RAW-24). Mapper: generator.py. The local case set (29 cases of one network, never committed, counted only) has 24 WMOD 2 and 26 WMOD 3 records in every case. Every one is a one-record plant on an IDE 2 bus, with no step-up, no NREG, and no switched shunt regulating it. WMOD 4 (an infeed machine) still raises: no case has one.

What PSS/E does with WPF

Q = |PG| × tan(acos |WPF|). - WMOD 2 regulates voltage like WMOD 1, but PSS/E sets its limits to QT = +Q and QB = −Q from PG. All 696 in the set are written that way already. WPF: 0.95 (19 a case), 1.0 (3, so QT = QB = 0), 0.9 and 0.97 (1 each). - WMOD 3 holds a fixed power factor: QG = Q, with the sign of PG when WPF > 0 and the opposite sign when WPF < 0. It does not regulate voltage. All in-service records are written QT = QB = QG = that Q; 11 in the set are not, all out of service. WPF: 1.0 (23 a case), −0.905 (2), 0.99 (1).

WMOD 2: a WMOD 1 connection with its WPF listed (decision R3c-1)

  • A PowerElectronicsConnection + PowerElectronicsUnit + ControlAreaPowerElectronicsUnit, exactly as WMOD 1: in the plant's voltage control, with maxQ, minQ = QT, QB as written.
  • CIM 18 has no reactive limit that follows P. So the row always lists WPF, even at 1.0 (untranscribed: wpf=0.95), and the exporter writes WMOD 2 for a connection with a listed WPF.
  • At the case's PG the solve is the same. A redispatch of PG would move PSS/E's limits but not CIM's (new gap).

WMOD 3: a power-factor control on the connection (decision R3c-2)

  • The same three rows. The plant control gc_<I> becomes mode = powerFactor, discrete = false, enabled = IDE 2 or 3 (as R3), targetValue = WPF as written.
  • Sign: positive means q has the same sign as p. That reading holds under the generator and the load sign conventions alike (PSS/E's and OpenDSS's pf).
  • Terminal: the connection's own pec_<I>_<ID>_T1, where its power factor is. The connection row points back at the control, so the control row is written with no Terminal, and an Update RegulatingControl: mRID, Terminal row follows the PowerElectronicsConnection table.
  • q = −QG and maxQ, minQ = QT, QB as written (an out-of-service record's mismatched Q round-trips).
  • VS, IREG and NREG are unused by a fixed power factor. When off their defaults they are listed on the control row (untranscribed: regulated_voltage_setpoint=1.02, regulated_bus_number=…): 12 a case have VS ≠ 1, and 2 have a remote IREG.
  • A plant that mixes WMOD 3 with another WMOD raises NotImplementedError (no case): one control holds either a voltage or a power factor.
  • The exporter writes WMOD 3, WPF = targetValue, for a connection under a powerFactor control.

ZR and RMPCT on any connection (decision R3c-3)

R3 left ZR and RMPCT untranscribed on a PowerElectronicsConnection; both public cases have ZR = 0 and RMPCT = 100. The local set does not, on every WMOD:

RMPCT ≠ 100 ZR ≠ 0
WMOD 1, per case about 38 about 66
WMOD 2, per case 5 0
WMOD 3, per case 2 7

Every connection row (WMOD 1, 2 and 3) lists them when off their defaults (untranscribed: zr=0.01, rmpct=50.0), so the exporter gets them back. The public cases list none.

WPF is now mapped, so a blank one is filled and reported like any other (# defaulted: wmod=0, wpf=1.0, nreg=0): the IEEE14 generator golden changes in its comments only.

Atom tests/atoms/generator/renewables.raw (hand-built)

The generators.raw frame, with: - a WMOD 2 at WPF 0.95 (QT, QB = ±PG tan) regulating a remote bus, RMPCT 50; - a WMOD 2 at WPF 1.0 (QT = QB = 0); - a WMOD 3 at WPF 0.99 with VS 1.02 and a remote IREG; - a WMOD 3 at WPF −0.905 with ZR 0.01.

Raise tests: WMOD 4; a plant of a WMOD 3 and a WMOD 0 machine. A MODSW 3 shunt naming a WMOD 2 machine gets its pec_ terminal through generator.machine_mrid (tested).

CIM 18 gaps

  • New: a converter's reactive limits that follow its active power (WMOD 2's WPF), listed.
  • Widened: a converter's ZSORCE and its RMPCT share, now listed on the row rather than lost.

Results

All 29 local cases map their generators: 24 WMOD 2 connections and 26 powerFactor plants a case. One case now binds whole, nothing set aside, in 77 s: 2425 SynchronousMachines, 573 PowerElectronicsConnections and 3921 RegulatingControls (3867 voltage, 26 powerFactor, 28 reactivePower).

Transformer (R4)

Approved 2026-11-08 and implemented. RAW-5, RAW-6. Atom: tests/atoms/transformer/. R4b (below) maps the forms this section lists as raising, except COD ±4 and ±5, CNXA, and a 3-winding unit's TAB. User choices 2026-11-08: impedances and admittances in ohm and S; COD 0, ±1, ±2 now; a control with CONT 0 names the tapped winding's own terminal.

Mapper: importer/cimtbl/transformer.py (map_transformer). Shape: transformer_by_ends with bus on each end, plus the regulator shape's RatioTapChanger + TapChangerControl. The core shape still puts a 2-winding x on a TransformerMeshImpedance. cim18v17 no longer does that (below), so the shape needs an update (request C2). - What a record is: one transformer with two windings (K = 0), or three (K ≠ 0), in one substation (§3.2). - cim18v17's transformer model (user, 2026-11-08). TransformerStarImpedance and TransformerStarAdmittance are deleted. TransformerCore and TransformerWinding are for tanks, not for a balanced bus-branch unit: - 2-winding: end 1 carries r, x, g and b, in ohm and S on its ratedU. End 2 is zero (PowerTransformerEnd's own rule), so it carries only its ratings. - 3-winding: PSS/E gives Z12, Z23 and Z31, which is already a mesh (Delta model). So three TransformerMeshImpedance rows, From 1 To 2, From 2 To 3 and From 1 To 3, each r and x in ohm seen from its From end. There is no star conversion and no star node. g and b go on end 1, and the ends' r and x stay blank. - Order: PowerTransformer, PowerTransformerEnd, TransformerMeshImpedance, TapChangerControl, RatioTapChanger, then the rating sets. A control may name a transformer terminal, which exists only after its end, so the controls come after the ends. Every reference points backwards, so no Update is needed.

WECC240 (1001-1002: a fixed tap at ratio 1; 6103-6104: one of its two voltage controls):

# untranscribed: o1, o2, o3, o4, f1, f2, f3, f4, zcod, vmstar, anstar
# untranscribed off a tie: NMETR (a tie's TieFlows record it; CIM 18 gap, RAW-22)
Table PowerTransformer: mRID, name, vectorGroup, inService, EquipmentContainer
    xf_1001_1002_0_1, 1001_1002_0_1, , true, sub_1001
    xf_6103_6104_0_1, 6103_6104_0_1, , true, sub_6103
    ...
# r, x, g, b on the end's ratedU (transformer_ohms, magnetizing_siemens): a 2-winding unit's all on end 1, end 2 zero; a 3-winding unit's g, b on end 1, r, x on its mesh
Table PowerTransformerEnd: mRID, name, bus, endNumber, ratedU (kV), ratedS (MVA), r (ohm), x (ohm), g (S), b (S), BaseVoltage, PowerTransformer
    xf_1001_1002_0_1_1, 1001_1002_0_1_1, 1001, 1, 500.0, 100.0, 0.00025,  27.5,      0.0, 0.0, bv_500kv, xf_1001_1002_0_1
    xf_1001_1002_0_1_2, 1001_1002_0_1_2, 1002, 2, 345.0, 100.0, 0.0,      0.0,       0.0, 0.0, bv_345kv, xf_1001_1002_0_1
    xf_6103_6104_0_1_1, 6103_6104_0_1_1, 6103, 1, 345.0, 100.0, 0.357075, 21.543525, 0.0, 0.0, bv_345kv, xf_6103_6104_0_1
    xf_6103_6104_0_1_2, 6103_6104_0_1_2, 6104, 2, 230.0, 100.0, 0.0,      0.0,       0.0, 0.0, bv_230kv, xf_6103_6104_0_1
    ...
# targetValue and targetDeadband in V (voltage) or VAr (reactivePower); COD 0 keeps its control, disabled
Table TapChangerControl: mRID, name, mode, discrete, enabled, targetValue, targetDeadband, Terminal
    xf_1001_1002_0_1_ctrl1, 1001_1002_0_1_1, voltage, true, false, 500000.0,           100000.00000000003, bb_1001_T1
    xf_6103_6104_0_1_ctrl1, 6103_6104_0_1_1, voltage, true, true,  235749.99999999997, 34500.00000000003,  bb_6104_T1
    ...
# steps 1..NTP from RMI to RMA; neutralStep nearest ratio 1 at neutralU; stepVoltageIncrement in percent of ratedU (ratio_tap)
Table RatioTapChanger: mRID, name, lowStep, highStep, neutralStep, neutralU (kV), stepVoltageIncrement, step, ltcFlag, controlEnabled, TapChangerControl, TransformerEnd
    xf_1001_1002_0_1_tap1, 1001_1002_0_1_1, 1, 989, 495, 500.0,             0.020242914979757092, 495.0,              false, false, xf_1001_1002_0_1_ctrl1, xf_1001_1002_0_1_1
    xf_6103_6104_0_1_tap1, 6103_6104_0_1_1, 1, 30,  15,  343.8103448275862, 0.6896551724137934,   16.000249999999976, true,  true,  xf_6103_6104_0_1_ctrl1, xf_6103_6104_0_1_1
    ...
# ratings: one set per rated winding, on its terminal xf_<key>_T<k>; a zero RATEn is no limit (RAW-9, RAW-20)
Table OperationalLimitSet: mRID, Terminal
    xf_1002_1003_0_1_1_ratings, xf_1002_1003_0_1_T1
    ...
Table ApparentPowerLimit: mRID, OperationalLimitSet, OperationalLimitType, normalValue (MVA)
    xf_1002_1003_0_1_1_rate3, xf_1002_1003_0_1_1_ratings, olt_rate3, 430.0
    ...

The atom's 3-winding unit D (tests/atoms/transformer/) gives the Delta model:

# 3-winding Z12, Z23, Z31 (Delta model): r, x seen from the From end
Table TransformerMeshImpedance: mRID, name, FromTransformerEnd, ToTransformerEnd, r (ohm), x (ohm)
    xf_1_2_3_1_mesh_12, 1_2_3_1_12, xf_1_2_3_1_1, xf_1_2_3_1_2, 1.19025,  59.5125
    xf_1_2_3_1_mesh_23, 1_2_3_1_23, xf_1_2_3_1_2, xf_1_2_3_1_3, 1.058,    21.16
    xf_1_2_3_1_mesh_13, 1_2_3_1_13, xf_1_2_3_1_1, xf_1_2_3_1_3, 1.785375, 83.3175

IEEE14 4-7 has CONT 0, so its disabled control names the transformer's own terminal xf_4_7_0_1_T1. Its target uses bus 4's BASKV: 138690.0 V, deadband 136620.0 V. Its tap: steps 1-159, neutral 79 at 137.825 kV, step 75.69.

  • mRIDs (prefixes requested, C3). The key is <I>_<J>_<K>_<CKT>:
  • the transformer is xf_<key>;
  • its ends are xf_<key>_<k>;
  • its mesh rows are xf_<key>_mesh_<ij> (12, 23, 13);
  • winding k's tap changer is xf_<key>_tap<k> and its control xf_<key>_ctrl<k>;
  • cimtables generates the terminals xf_<key>_T<k> (sequenceNumber = endNumber).
  • NAME is the transformer's name; a blank NAME gives the key, as for a branch. An end, tap changer or control is named <key>_<k>.
  • Ends:
  • bus is winding k's bus (I, J, K), and BaseVoltage is its BASKV's.
  • ratedU = NOMVk, or the bus's BASKV when NOMVk is 0 (RAW-6). Every public transformer has NOMV = BASKV, except IEEE14's NOMV 0. The exporter writes NOMV = ratedU back, so IEEE14's NOMV 0 comes back as 138.0 (expected difference, the same value to PSS/E).
  • ratedS: on a 2-winding unit, SBASE1-2 on both ends. A 3-winding unit's SBASE1-2, 2-3 and 3-1 are bases of winding pairs, so no end can hold them. They enter the CZ 2/3 derivations below and are not kept otherwise. The exporter writes SBASE (expected difference).
  • PowerTransformer.vectorGroup = VECGRP when not blank (blank in both cases). connectionKind stays blank: a positive-sequence case has no winding connections.
  • Impedance (RAW-5, ohm): one derivation, transformer_ohms, for each pair ij, seen from winding i:
CZ RAW gives r, x (ohm)
1 R, X in pu on SBASE and bus BASKVi R, X × BASKVi² / SBASE
2 R, X in pu on SBASEij and NOMVi R, X × NOMVi² / SBASEij
3 R = load loss in W, X = |Z| in pu on SBASEij and NOMVi r = loss / SBASEij in pu; x = √(|Z|² − r²); both × NOMVi² / SBASEij
  • PSS/E's own conversion between the codes keeps these ohms the same. So the result is one physical impedance, referred to winding i at its ratedU.
  • CZ 3 with |Z| < r raises.
  • The exporter writes CZ 1 back, so the CZ 2/3 atoms come back as CZ 1 (expected difference, the same impedance).
  • Magnetizing (RAW-5, S, end 1): magnetizing_siemens, at winding 1's bus:
CM RAW gives g, b (S)
1 MAG1, MAG2: G, B in pu on SBASE and BASKV1 G, B × SBASE / BASKV1²
2 MAG1 = no-load loss in W, MAG2 = exciting current in pu on SBASE1-2 and NOMV1 g = loss / SBASE1-2 in pu; b = −√(I² − g²); both × SBASE1-2 / NOMV1²
  • The sign is kept: a magnetizing B is negative (inductive), and CIM's b allows either sign.
  • CM 2 with I < g raises.
  • The exporter writes CM 1 back (expected difference).
  • Turns ratio and taps (RAW-6). A winding that has COD data gets a RatioTapChanger on its end: winding 1 of a 2-winding unit, and every winding of a 3-winding one. That covers every public transformer: WECC240 carries NTP, RMA and RMI even with COD 0, and IEEE14's WINDV1 is off-nominal.
  • Winding units: CW gives WINDV, RMA and RMI in pu of the bus's BASKV (1), in kV (2), or in pu of NOMV (3). winding_kv turns each into kV, and dividing by ratedU gives pu of the end's rating. CIM holds no CW, so the exporter writes CW 1 (expected difference).
  • Steps: lowStep = 1 and highStep = NTP, from RMI to RMA in equal steps, so stepVoltageIncrement = (RMA − RMI)/(NTP − 1), in percent of ratedU. NTP < 2 raises.
  • Neutral: neutralStep is the step nearest ratio 1 (a tie takes the upper), and neutralU = ratedU × the ratio at that step.
    • CIM's neutralStep is an integer, and PSS/E's ratio 1 often falls between steps: WECC240 6103-6104's RMI 0.9, RMA 1.1 and NTP 30 put it at step 15.5.
    • A neutralU ≠ ratedU keeps it exact, and the profile allows that. A consumer that assumes neutralU = ratedU is off by at most half a step.
  • Position: step = neutralStep + (WINDV − the neutral ratio) / the step size. It is a float: CIM allows a non-integer step, and PSS/E's WINDV need not sit on a step (IEEE14's do not).
    • A WINDV outside RMI..RMA raises (CIM: lowStep ≤ step ≤ highStep).
    • The exporter's WINDV = neutralU/ratedU + (step − neutralStep) × increment, and its RMI/RMA come from lowStep/highStep. Each can differ in the last digit (expected difference).
  • Winding 2 of a 2-winding unit has only WINDV2. A ratio other than 1 (in winding units) raises until a case has one. The public cases all have 1.
  • Control (COD). A tapped winding always gets its control, so VMA, VMI and CONT survive even when the tap is fixed (R2's locked-shunt pattern):
COD RatioTapChanger TapChangerControl
0 fixed ltcFlag = false, controlEnabled = false mode = voltage, enabled = false; the target as read (unused by PSS/E)
1 / −1 voltage ltcFlag = true, controlEnabled = (COD > 0) mode = voltage, enabled = (COD > 0)
2 / −2 reactive power as ±1 mode = reactivePower, enabled = (COD > 0)
±3 phase shift, ±5 asymmetric phase shift raise NotImplementedError: no case has one yet (a PhaseTapChanger)
±4 DC line control raise NotImplementedError: phase 2 (two-terminal DC)
  • The exporter's COD: 0 when ltcFlag is false; otherwise ±1 or ±2 by mode, signed by enabled. That makes it a round trip.
  • Regulated point: Terminal = bb_<CONT>_T1 (RAW-11). CONT 0 names the tapped winding's own terminal xf_<key>_T<k> (user 2026-11-08). The exporter writes CONT 0 back for an own terminal.
    • COD ±1 with CONT 0 raises: PSS/E needs a controlled bus.
    • COD ±2 measures the flow through the winding, so CONT 0 is its usual form.
    • A negative CONT raises.
    • NODk ≠ 0 names node NODk of bus CONTk: bb_s<IS>_n<NODk>_T1, that node's busbar (R6). NODk with CONT 0 raises.
  • Target: discrete = true (taps step).
    • Voltage: targetValue = (VMA + VMI)/2 × the regulated bus's BASKV and targetDeadband = (VMA − VMI) × BASKV, in V (volts_from_per_unit, as the switched shunt).
    • Reactive power: the same, in VAr from Mvar, through the units library.
    • CONT 0 uses the winding's own bus's BASKV.
  • Raise until a case has one: CRk/CXk ≠ 0 (load-drop compensation, which TapChangerControl.lineDropR/X could take) and CNXAk ≠ 0 (only COD ±5 uses it).
  • TABk ≠ 0 (an impedance correction table) raises until phase 2.
  • Status: STAT 1 → inService = true and 0 → false. STAT 2, 3 and 4 (one winding of a 3-winding unit out) raise until a case has one.
  • Ratings: each winding's nonzero RATEk-n go on terminal xf_<key>_T<k>, in the set xf_<key>_<k>_ratings (RAW-20, through RatingRows). They are ApparentPowerLimits in MVA, or CurrentLimits in kA when XFRRAT > 0 (RAW-9; blank → MVA). WECC240 has 42 units with RATE1-3.
  • Untranscribed:
  • NMETR off a tie: the non-metered end, a CIM 18 gap as branch MET (RAW-22); on a tie its TieFlows record it (R5);
  • O1..F4: ownership (CIM 18 gap);
  • ZCOD: the zero-sequence data is in the sequence file, not the RAW;
  • VMSTAR/ANSTAR: the solved voltage of the star point, which the Delta model omits;
  • CW, CZ, CM: unit codes, applied above; the exporter writes 1.
  • Defaults: RAW's rules apply per record. SBASEij defaults to SBASE. WINDV defaults to 1.0, or to the bus's BASKV under CW 2. RMA/RMI default to 1.1/0.9 under CW 1 or 3 when |COD| is not 3 or 5. VMA/VMI default to 1.1/0.9 when |COD| is 1, and the mapper applies the same to COD 0, whose band PSS/E ignores. A blank with no default raises. A 2-winding unit's 3-winding slots (the schema's serialize_if: k != 0) are never defaulted.
  • Atom: tests/atoms/transformer/transformers.raw holds five units:
  • A: CW 2 + CZ 2 + CM 2, with NOMV1 340 on a 345 kV bus, COD 1 on a remote bus, and two ratings;
  • B: CW 3 + CZ 3, with COD −1;
  • C: COD 2 with CONT 0;
  • D: 3-winding with CZ 1 + CM 1, COD 1 on winding 2, and ratings on windings 1 and 3;
  • E: 3-winding with CZ 2 on pair bases, every winding's tap data defaulted.

It survives a RAW read → write → read with nothing lost, and binds. Every value is checked in SI against PSS/E's conversion. Nineteen raise cases are tested; R0's substation merge already rejects a winding bus that is no bus.

TransformerRecord field type samples kind target
i int 4, 5, 1001 structural I: winding 1's bus (end 1's bus and BaseVoltage); the transformer's EquipmentContainer is its substation
j int 7, 9, 6 structural J: winding 2's bus
x1_2 float 0.20912, 0.55618, 0.25202 derived X1-2: as R1-2, x (ohm)
k Optional[int] 0 structural K: winding 3's bus; 0 is a 2-winding unit; blank: 0 (defaulted)
circuit Optional[str] 1, 2, 3 structural CKT: with I, J and K the key, mRID xf__; blank: 1 (defaulted)
cw Optional[int] 1 mapped CW: the unit of WINDV, RMA and RMI (winding_unit_kv); CIM keeps kV, so the exporter writes CW 1; blank: 1 (defaulted)
cz Optional[int] 1 mapped CZ: the code of R/X (transformer_ohms); CIM keeps ohm, so the exporter writes CZ 1; blank: 1 (defaulted)
cm Optional[int] 1 mapped CM: the code of MAG1/MAG2 (magnetizing_siemens); the exporter writes CM 1; blank: 1 (defaulted)
mag1 Optional[float] 0.0 derived MAG1: end 1's g (S) (magnetizing_siemens, by CM); blank: 0 (defaulted)
mag2 Optional[float] 0.0 derived MAG2: end 1's b (S), negative inductive; blank: 0 (defaulted)
nmetr Optional[int] 2 structural NMETR: the non-metered (home) winding; on a tie (windings' buses in two or more AREAs) each other winding outside the home area carries both TieFlows on its terminal (R5); a code outside 1..windings on a tie raises; elsewhere untranscribed, as branch MET (CIM 18 gap, RAW-22); blank: 2 (defaulted)
name Optional[str] copied PowerTransformer.name; NAME; blank: the key I_J_K_CKT
status Optional[int] 1 mapped STAT: inService = (STAT != 0); 2, 3 and 4 (a 3-winding unit's winding 2, 3 or 1 out): that winding's terminal connected = false, an Update row (R4b-6); blank: 1 (defaulted)
o1 Optional[int] 1 untranscribed ownership is an asset concept (CIM 18 gap)
f1 Optional[float] 1.0 untranscribed ownership is an asset concept (CIM 18 gap)
o2 Optional[int] 0 untranscribed ownership is an asset concept (CIM 18 gap)
f2 Optional[float] 1.0 untranscribed ownership is an asset concept (CIM 18 gap)
o3 Optional[int] 0 untranscribed ownership is an asset concept (CIM 18 gap)
f3 Optional[float] 1.0 untranscribed ownership is an asset concept (CIM 18 gap)
o4 Optional[int] 0 untranscribed ownership is an asset concept (CIM 18 gap)
f4 Optional[float] 1.0 untranscribed ownership is an asset concept (CIM 18 gap)
vecgrp Optional[str] copied PowerTransformer.vectorGroup; VECGRP; blank: none
zcod Optional[int] untranscribed ZCOD: zero-sequence data is in the sequence file, not the RAW
r1_2 Optional[float] 0.0, 1e-07, 0.00028 derived R1-2: with X1-2, r (ohm) seen from winding 1 (transformer_ohms, by CZ); 2-winding: on end 1, 3-winding: on the mesh row; blank: 0 (defaulted)
sbase1_2 Optional[float] 100.0 derived SBASE1-2 (MVA): the pair's base for CZ 2 and 3 (and CM 2 on 1-2); a 2-winding unit's SBASE1-2 is also both ends' ratedS; a 3-winding unit's pair bases have no end to go on; blank: SBASE (defaulted)
r2_3 Optional[float] derived R2-3: with X2-3, r (ohm) seen from winding 2 (transformer_ohms, by CZ); 2-winding: on end 1, 3-winding: on the mesh row; blank: 0 (defaulted)
x2_3 Optional[float] derived X2-3: as R2-3, x (ohm)
sbase2_3 Optional[float] derived SBASE2-3 (MVA): the pair's base for CZ 2 and 3 (and CM 2 on 1-2); a 2-winding unit's SBASE1-2 is also both ends' ratedS; a 3-winding unit's pair bases have no end to go on; blank: SBASE (defaulted)
r3_1 Optional[float] derived R3-1: with X3-1, r (ohm) seen from winding 1 (transformer_ohms, by CZ); 2-winding: on end 1, 3-winding: on the mesh row; blank: 0 (defaulted)
x3_1 Optional[float] derived X3-1: as R3-1, x (ohm)
sbase3_1 Optional[float] derived SBASE3-1 (MVA): the pair's base for CZ 2 and 3 (and CM 2 on 1-2); a 2-winding unit's SBASE1-2 is also both ends' ratedS; a 3-winding unit's pair bases have no end to go on; blank: SBASE (defaulted)
vmstar Optional[float] untranscribed VMSTAR: the solved voltage of the star point, which the Delta model omits
anstar Optional[float] untranscribed ANSTAR: as VMSTAR
windv1 Optional[float] 0.978, 0.969, 0.932 derived WINDV1: the ratio, in CW units: RatioTapChanger step (ratio_tap) on winding 1, or any winding of a 3-winding unit; a fixed RatioTapChanger (neutralU = WINDV in kV, R4b-4) on an off-nominal winding 2 of a 2-winding unit, a COD 0 winding without a usable RMI..RMA, or an off-nominal phase shifter winding; blank: 1.0, or the bus's BASKV for CW 2 (defaulted)
nomv1 Optional[float] 0.0, 500.0, 345.0 derived NOMV1 (kV): PowerTransformerEnd ratedU, or the bus's BASKV when 0 (RAW-6); blank: 0 (defaulted)
ang1 Optional[float] 0.0 derived ANG1 (deg): phaseShift = cim_angle(ANG) on end 1 (R4b-2), or, with
rate1_1 Optional[float] 0.0 structural RATEk-n: winding k's ratings, an ApparentPowerLimit (MVA) or CurrentLimit (kA, XFRRAT > 0) xf_rate in the set xfratings on terminal xf_T; 0 is no limit, no row; blank: 0 (defaulted)
rate1_2 Optional[float] 0.0 structural RATEk-n: winding k's ratings, an ApparentPowerLimit (MVA) or CurrentLimit (kA, XFRRAT > 0) xf_rate in the set xfratings on terminal xf_T; 0 is no limit, no row; blank: 0 (defaulted)
rate1_3 Optional[float] 0.0, 430.0, 2000.0 structural RATEk-n: winding k's ratings, an ApparentPowerLimit (MVA) or CurrentLimit (kA, XFRRAT > 0) xf_rate in the set xfratings on terminal xf_T; 0 is no limit, no row; blank: 0 (defaulted)
rate1_4 Optional[float] 0.0 structural RATEk-n: winding k's ratings, an ApparentPowerLimit (MVA) or CurrentLimit (kA, XFRRAT > 0) xf_rate in the set xfratings on terminal xf_T; 0 is no limit, no row; blank: 0 (defaulted)
rate1_5 Optional[float] 0.0 structural RATEk-n: winding k's ratings, an ApparentPowerLimit (MVA) or CurrentLimit (kA, XFRRAT > 0) xf_rate in the set xfratings on terminal xf_T; 0 is no limit, no row; blank: 0 (defaulted)
rate1_6 Optional[float] 0.0 structural RATEk-n: winding k's ratings, an ApparentPowerLimit (MVA) or CurrentLimit (kA, XFRRAT > 0) xf_rate in the set xfratings on terminal xf_T; 0 is no limit, no row; blank: 0 (defaulted)
rate1_7 Optional[float] 0.0 structural RATEk-n: winding k's ratings, an ApparentPowerLimit (MVA) or CurrentLimit (kA, XFRRAT > 0) xf_rate in the set xfratings on terminal xf_T; 0 is no limit, no row; blank: 0 (defaulted)
rate1_8 Optional[float] 0.0 structural RATEk-n: winding k's ratings, an ApparentPowerLimit (MVA) or CurrentLimit (kA, XFRRAT > 0) xf_rate in the set xfratings on terminal xf_T; 0 is no limit, no row; blank: 0 (defaulted)
rate1_9 Optional[float] 0.0 structural RATEk-n: winding k's ratings, an ApparentPowerLimit (MVA) or CurrentLimit (kA, XFRRAT > 0) xf_rate in the set xfratings on terminal xf_T; 0 is no limit, no row; blank: 0 (defaulted)
rate1_10 Optional[float] 0.0 structural RATEk-n: winding k's ratings, an ApparentPowerLimit (MVA) or CurrentLimit (kA, XFRRAT > 0) xf_rate in the set xfratings on terminal xf_T; 0 is no limit, no row; blank: 0 (defaulted)
rate1_11 Optional[float] 0.0 structural RATEk-n: winding k's ratings, an ApparentPowerLimit (MVA) or CurrentLimit (kA, XFRRAT > 0) xf_rate in the set xfratings on terminal xf_T; 0 is no limit, no row; blank: 0 (defaulted)
rate1_12 Optional[float] 0.0 structural RATEk-n: winding k's ratings, an ApparentPowerLimit (MVA) or CurrentLimit (kA, XFRRAT > 0) xf_rate in the set xfratings on terminal xf_T; 0 is no limit, no row; blank: 0 (defaulted)
cod1 Optional[int] 0, 1 mapped COD1: 0 ltcFlag false, control disabled; +-1 voltage, +-2 reactivePower, +-3 activePower (a PhaseTapChangerLinear, R4b-3), ltcFlag true, controlEnabled and enabled = (COD > 0); +-5 raises (no case), +-4 raises (phase 2); blank: 0 (defaulted)
cont1 Optional[int] 0, 1001, 1002 structural CONT1: the TapChangerControl Terminal bb_<
rma1 Optional[float] 1.5, 1.1 derived RMA1: highStep's ratio, in CW units (ratio_tap: steps 1..NTP from RMI to RMA, stepVoltageIncrement), or angle (deg) for COD +-3 (phase_tap); listed on the row where CIM cannot hold it (R4b-3, -4, -5); blank: 1.1 for CW 1 or 3 and
rmi1 Optional[float] 0.51, 0.9 derived RMI1: lowStep's ratio or angle; as RMA1; blank: 0.9 (defaulted) as RMA1
vma1 Optional[float] 1.5, 1.1 derived VMA1: targetValue = (VMA + VMI) / 2 and targetDeadband = VMA - VMI, in V x the regulated bus's BASKV (volts_from_per_unit) for voltage, in VAr from Mvar (vars_from_mvar) for reactivePower, in W from MW (watts_from_mw) for activePower; blank: 1.1 for COD 0 or +-1 (defaulted), else raises
vmi1 Optional[float] 0.51, 0.9, 0.95 derived VMI1: as VMA1; blank: 0.9 for COD 0 or +-1 (defaulted)
ntp1 Optional[int] 159, 989, 30 derived NTP1: highStep = NTP, lowStep = 1 (the steps of a phase shifter too); below 2 raises; blank: 33 (defaulted)
tab1 Optional[int] 0 structural TAB1: an ImpedanceTapChangerTabular xf_ztab on end 1, naming table ict (R4b-10); a 3-winding unit's raises; blank: 0 (defaulted)
cr1 Optional[float] 0.0 derived CR1 (pu on SBASE): lineDropR = CR x BASKV^2 / SBASE ohm (ohms_from_per_unit, the regulated bus's BASKV), lineDropCompensation true (R4b-9); nonzero off COD +-1 raises; blank: 0 (defaulted)
cx1 Optional[float] 0.0 derived CX1: lineDropX, as CR1
cnxa1 Optional[float] 0.0 structural CNXA1: only COD +-5 uses it; nonzero raises; blank: 0 (defaulted)
nod1 Optional[int] 0 structural NOD1: a node of bus CONT1; nonzero: the TapChangerControl Terminal is that node's busbar bb_s_n_T1 (R6, RAW-11); with CONT1 0 it raises; blank: 0 (defaulted)
windv2 Optional[float] 1.0 derived WINDV2: the ratio, in CW units: RatioTapChanger step (ratio_tap) on winding 1, or any winding of a 3-winding unit; a fixed RatioTapChanger (neutralU = WINDV in kV, R4b-4) on an off-nominal winding 2 of a 2-winding unit, a COD 0 winding without a usable RMI..RMA, or an off-nominal phase shifter winding; blank: 1.0, or the bus's BASKV for CW 2 (defaulted)
nomv2 Optional[float] 0.0, 345.0, 230.0 derived NOMV2 (kV): PowerTransformerEnd ratedU, or the bus's BASKV when 0 (RAW-6); blank: 0 (defaulted)
ang2 Optional[float] derived ANG2 (deg): phaseShift = cim_angle(ANG) on end 2 (R4b-2), or, with
rate2_1 Optional[float] structural RATEk-n: winding k's ratings, an ApparentPowerLimit (MVA) or CurrentLimit (kA, XFRRAT > 0) xf_rate in the set xfratings on terminal xf_T; 0 is no limit, no row; blank: 0 (defaulted)
rate2_2 Optional[float] structural RATEk-n: winding k's ratings, an ApparentPowerLimit (MVA) or CurrentLimit (kA, XFRRAT > 0) xf_rate in the set xfratings on terminal xf_T; 0 is no limit, no row; blank: 0 (defaulted)
rate2_3 Optional[float] structural RATEk-n: winding k's ratings, an ApparentPowerLimit (MVA) or CurrentLimit (kA, XFRRAT > 0) xf_rate in the set xfratings on terminal xf_T; 0 is no limit, no row; blank: 0 (defaulted)
rate2_4 Optional[float] structural RATEk-n: winding k's ratings, an ApparentPowerLimit (MVA) or CurrentLimit (kA, XFRRAT > 0) xf_rate in the set xfratings on terminal xf_T; 0 is no limit, no row; blank: 0 (defaulted)
rate2_5 Optional[float] structural RATEk-n: winding k's ratings, an ApparentPowerLimit (MVA) or CurrentLimit (kA, XFRRAT > 0) xf_rate in the set xfratings on terminal xf_T; 0 is no limit, no row; blank: 0 (defaulted)
rate2_6 Optional[float] structural RATEk-n: winding k's ratings, an ApparentPowerLimit (MVA) or CurrentLimit (kA, XFRRAT > 0) xf_rate in the set xfratings on terminal xf_T; 0 is no limit, no row; blank: 0 (defaulted)
rate2_7 Optional[float] structural RATEk-n: winding k's ratings, an ApparentPowerLimit (MVA) or CurrentLimit (kA, XFRRAT > 0) xf_rate in the set xfratings on terminal xf_T; 0 is no limit, no row; blank: 0 (defaulted)
rate2_8 Optional[float] structural RATEk-n: winding k's ratings, an ApparentPowerLimit (MVA) or CurrentLimit (kA, XFRRAT > 0) xf_rate in the set xfratings on terminal xf_T; 0 is no limit, no row; blank: 0 (defaulted)
rate2_9 Optional[float] structural RATEk-n: winding k's ratings, an ApparentPowerLimit (MVA) or CurrentLimit (kA, XFRRAT > 0) xf_rate in the set xfratings on terminal xf_T; 0 is no limit, no row; blank: 0 (defaulted)
rate2_10 Optional[float] structural RATEk-n: winding k's ratings, an ApparentPowerLimit (MVA) or CurrentLimit (kA, XFRRAT > 0) xf_rate in the set xfratings on terminal xf_T; 0 is no limit, no row; blank: 0 (defaulted)
rate2_11 Optional[float] structural RATEk-n: winding k's ratings, an ApparentPowerLimit (MVA) or CurrentLimit (kA, XFRRAT > 0) xf_rate in the set xfratings on terminal xf_T; 0 is no limit, no row; blank: 0 (defaulted)
rate2_12 Optional[float] structural RATEk-n: winding k's ratings, an ApparentPowerLimit (MVA) or CurrentLimit (kA, XFRRAT > 0) xf_rate in the set xfratings on terminal xf_T; 0 is no limit, no row; blank: 0 (defaulted)
cod2 Optional[int] mapped COD2: 0 ltcFlag false, control disabled; +-1 voltage, +-2 reactivePower, +-3 activePower (a PhaseTapChangerLinear, R4b-3), ltcFlag true, controlEnabled and enabled = (COD > 0); +-5 raises (no case), +-4 raises (phase 2); blank: 0 (defaulted)
cont2 Optional[int] structural CONT2: the TapChangerControl Terminal bb_<
rma2 Optional[float] derived RMA2: highStep's ratio, in CW units (ratio_tap: steps 1..NTP from RMI to RMA, stepVoltageIncrement), or angle (deg) for COD +-3 (phase_tap); listed on the row where CIM cannot hold it (R4b-3, -4, -5); blank: 1.1 for CW 1 or 3 and
rmi2 Optional[float] derived RMI2: lowStep's ratio or angle; as RMA2; blank: 0.9 (defaulted) as RMA2
vma2 Optional[float] derived VMA2: targetValue = (VMA + VMI) / 2 and targetDeadband = VMA - VMI, in V x the regulated bus's BASKV (volts_from_per_unit) for voltage, in VAr from Mvar (vars_from_mvar) for reactivePower, in W from MW (watts_from_mw) for activePower; blank: 1.1 for COD 0 or +-1 (defaulted), else raises
vmi2 Optional[float] derived VMI2: as VMA2; blank: 0.9 for COD 0 or +-1 (defaulted)
ntp2 Optional[int] derived NTP2: highStep = NTP, lowStep = 1 (the steps of a phase shifter too); below 2 raises; blank: 33 (defaulted)
tab2 Optional[int] structural TAB2: an ImpedanceTapChangerTabular xf_ztab on end 2, naming table ict (R4b-10); a 3-winding unit's raises; blank: 0 (defaulted)
cr2 Optional[float] derived CR2 (pu on SBASE): lineDropR = CR x BASKV^2 / SBASE ohm (ohms_from_per_unit, the regulated bus's BASKV), lineDropCompensation true (R4b-9); nonzero off COD +-1 raises; blank: 0 (defaulted)
cx2 Optional[float] derived CX2: lineDropX, as CR2
cnxa2 Optional[float] structural CNXA2: only COD +-5 uses it; nonzero raises; blank: 0 (defaulted)
nod2 Optional[int] structural NOD2: a node of bus CONT2; nonzero: the TapChangerControl Terminal is that node's busbar bb_s_n_T1 (R6, RAW-11); with CONT2 0 it raises; blank: 0 (defaulted)
windv3 Optional[float] derived WINDV3: the ratio, in CW units: RatioTapChanger step (ratio_tap) on winding 1, or any winding of a 3-winding unit; a fixed RatioTapChanger (neutralU = WINDV in kV, R4b-4) on an off-nominal winding 2 of a 2-winding unit, a COD 0 winding without a usable RMI..RMA, or an off-nominal phase shifter winding; blank: 1.0, or the bus's BASKV for CW 2 (defaulted)
nomv3 Optional[float] derived NOMV3 (kV): PowerTransformerEnd ratedU, or the bus's BASKV when 0 (RAW-6); blank: 0 (defaulted)
ang3 Optional[float] derived ANG3 (deg): phaseShift = cim_angle(ANG) on end 3 (R4b-2), or, with
rate3_1 Optional[float] structural RATEk-n: winding k's ratings, an ApparentPowerLimit (MVA) or CurrentLimit (kA, XFRRAT > 0) xf_rate in the set xfratings on terminal xf_T; 0 is no limit, no row; blank: 0 (defaulted)
rate3_2 Optional[float] structural RATEk-n: winding k's ratings, an ApparentPowerLimit (MVA) or CurrentLimit (kA, XFRRAT > 0) xf_rate in the set xfratings on terminal xf_T; 0 is no limit, no row; blank: 0 (defaulted)
rate3_3 Optional[float] structural RATEk-n: winding k's ratings, an ApparentPowerLimit (MVA) or CurrentLimit (kA, XFRRAT > 0) xf_rate in the set xfratings on terminal xf_T; 0 is no limit, no row; blank: 0 (defaulted)
rate3_4 Optional[float] structural RATEk-n: winding k's ratings, an ApparentPowerLimit (MVA) or CurrentLimit (kA, XFRRAT > 0) xf_rate in the set xfratings on terminal xf_T; 0 is no limit, no row; blank: 0 (defaulted)
rate3_5 Optional[float] structural RATEk-n: winding k's ratings, an ApparentPowerLimit (MVA) or CurrentLimit (kA, XFRRAT > 0) xf_rate in the set xfratings on terminal xf_T; 0 is no limit, no row; blank: 0 (defaulted)
rate3_6 Optional[float] structural RATEk-n: winding k's ratings, an ApparentPowerLimit (MVA) or CurrentLimit (kA, XFRRAT > 0) xf_rate in the set xfratings on terminal xf_T; 0 is no limit, no row; blank: 0 (defaulted)
rate3_7 Optional[float] structural RATEk-n: winding k's ratings, an ApparentPowerLimit (MVA) or CurrentLimit (kA, XFRRAT > 0) xf_rate in the set xfratings on terminal xf_T; 0 is no limit, no row; blank: 0 (defaulted)
rate3_8 Optional[float] structural RATEk-n: winding k's ratings, an ApparentPowerLimit (MVA) or CurrentLimit (kA, XFRRAT > 0) xf_rate in the set xfratings on terminal xf_T; 0 is no limit, no row; blank: 0 (defaulted)
rate3_9 Optional[float] structural RATEk-n: winding k's ratings, an ApparentPowerLimit (MVA) or CurrentLimit (kA, XFRRAT > 0) xf_rate in the set xfratings on terminal xf_T; 0 is no limit, no row; blank: 0 (defaulted)
rate3_10 Optional[float] structural RATEk-n: winding k's ratings, an ApparentPowerLimit (MVA) or CurrentLimit (kA, XFRRAT > 0) xf_rate in the set xfratings on terminal xf_T; 0 is no limit, no row; blank: 0 (defaulted)
rate3_11 Optional[float] structural RATEk-n: winding k's ratings, an ApparentPowerLimit (MVA) or CurrentLimit (kA, XFRRAT > 0) xf_rate in the set xfratings on terminal xf_T; 0 is no limit, no row; blank: 0 (defaulted)
rate3_12 Optional[float] structural RATEk-n: winding k's ratings, an ApparentPowerLimit (MVA) or CurrentLimit (kA, XFRRAT > 0) xf_rate in the set xfratings on terminal xf_T; 0 is no limit, no row; blank: 0 (defaulted)
cod3 Optional[int] mapped COD3: 0 ltcFlag false, control disabled; +-1 voltage, +-2 reactivePower, +-3 activePower (a PhaseTapChangerLinear, R4b-3), ltcFlag true, controlEnabled and enabled = (COD > 0); +-5 raises (no case), +-4 raises (phase 2); blank: 0 (defaulted)
cont3 Optional[int] structural CONT3: the TapChangerControl Terminal bb_<
rma3 Optional[float] derived RMA3: highStep's ratio, in CW units (ratio_tap: steps 1..NTP from RMI to RMA, stepVoltageIncrement), or angle (deg) for COD +-3 (phase_tap); listed on the row where CIM cannot hold it (R4b-3, -4, -5); blank: 1.1 for CW 1 or 3 and
rmi3 Optional[float] derived RMI3: lowStep's ratio or angle; as RMA3; blank: 0.9 (defaulted) as RMA3
vma3 Optional[float] derived VMA3: targetValue = (VMA + VMI) / 2 and targetDeadband = VMA - VMI, in V x the regulated bus's BASKV (volts_from_per_unit) for voltage, in VAr from Mvar (vars_from_mvar) for reactivePower, in W from MW (watts_from_mw) for activePower; blank: 1.1 for COD 0 or +-1 (defaulted), else raises
vmi3 Optional[float] derived VMI3: as VMA3; blank: 0.9 for COD 0 or +-1 (defaulted)
ntp3 Optional[int] derived NTP3: highStep = NTP, lowStep = 1 (the steps of a phase shifter too); below 2 raises; blank: 33 (defaulted)
tab3 Optional[int] structural TAB3: an ImpedanceTapChangerTabular xf_ztab on end 3, naming table ict (R4b-10); a 3-winding unit's raises; blank: 0 (defaulted)
cr3 Optional[float] derived CR3 (pu on SBASE): lineDropR = CR x BASKV^2 / SBASE ohm (ohms_from_per_unit, the regulated bus's BASKV), lineDropCompensation true (R4b-9); nonzero off COD +-1 raises; blank: 0 (defaulted)
cx3 Optional[float] derived CX3: lineDropX, as CR3
cnxa3 Optional[float] structural CNXA3: only COD +-5 uses it; nonzero raises; blank: 0 (defaulted)
nod3 Optional[int] structural NOD3: a node of bus CONT3; nonzero: the TapChangerControl Terminal is that node's busbar bb_s_n_T1 (R6, RAW-11); with CONT3 0 it raises; blank: 0 (defaulted)

Transformer: the forms R4 raised on (R4b)

Approved 2026-11-09 (user) and implemented. Extends R4 (RAW-5, RAW-6). Mappers: transformer.py, impedance_correction.py; derived functions cim_angle, phase_tap, usable_tap_range, watts_from_mw, impedance_deviation_percent, is_angle_table (derived.py). R4 raised NotImplementedError on each form below "until a case has one". A local case set now has them: 29 cases of one network, never committed, reported here by count only. Profile additions (user, 2026-11-09): PowerTransformerEnd.phaseShift (AngleDegrees) and ImpedanceTapChangerTabular.TransformerEnd. Atom (new, hand-built): tests/atoms/transformer/forms_r4b.raw.

What one case of the set holds, each condition counted on its own (a record can have several):

form windings R4 today R4b
fixed phase shift ANGk ≠ 0, |CODk| not 3 or 5 ~765 (~730 at a multiple of 30°, 35 not) raises phaseShift on end k
phase shifter COD ±3 66 raises PhaseTapChangerLinear + an activePower TapChangerControl
impedance correction table TABk 49 (all 2-winding: 48 on COD ±3, 1 on COD −2), 32 tables raises ImpedanceTapChangerTable + ImpedanceTapChangerTabular
off-nominal winding 2 of a 2-winding unit 1226 raises a fixed RatioTapChanger on end 2
COD 0 with RMA ≤ RMI (99) or WINDV outside RMI..RMA (694) 793 raises a fixed RatioTapChanger
a phase shifter's winding off nominal 9 (behind the COD raise) a fixed RatioTapChanger
COD ±1 with WINDV outside RMI..RMA 1 raises the step range extended to the step
STAT 2 / 3 (one winding of a 3-winding unit out) 6 / 124 (no STAT 4) raises that end's Terminal connected = false
COD ±1 with CONT 0 90 raises control on the winding's own terminal
CONT < 0 11 raises control on bus |CONT|; the sign listed
load-drop compensation CRk/CXk ≠ 0 14 (all COD 1) raises lineDropR/lineDropX

Still raising: COD ±4 (two-terminal DC, phase 2), COD ±5 and CNXA (none in the set), a 3-winding unit's TAB, a complex impedance factor (Im F ≠ 0; none in the set), CR/CX on a winding that is not a voltage control.

Angles: one sign for CIM (decision R4b-1)

CIM's PhaseTapChanger angles are positive "from the Terminal at the PowerTransformerEnd into the transformer": the voltage inside leads the terminal's. PSS/E's ANGk is positive when winding k's bus leads the transformer's internal (star point) voltage, so a PSS/E angle is the CIM angle with its sign turned: cim_angle(ang) = −ang, a named derived function. The new phaseShift takes the PhaseTapChanger sign (user, 2026-11-09). Its UML text: "Fixed phase angle displacement, in degrees, of the positive-sequence voltage between this end's terminal and the transformer's internal reference, positive from the terminal into the transformer as for PhaseTapChanger angles. It holds only the fixed shift from the winding connection or construction, not any shift from a tap changer; only the differences between a transformer's ends are physically meaningful." So a fixed shift and a tap changer's shift on one end add.

Fixed phase shift (decision R4b-2)

  • PowerTransformerEnd.phaseShift = cim_angle(ANGk) on end k, for each winding whose |CODk| is not 3 or 5. A 2-winding unit has only ANG1, so end 2 stays blank (0).
  • Each end's shift is against the transformer's internal reference, as PSS/E's ANGk is against the star point, so a 3-winding unit's ANG1..3 go on as they are. Only the differences between ends are physical. In the Delta model each mesh impedance joins two ends' internal points, which is where PSS/E's star-point shifts act, so per-end shifts are exact.
  • No windingConfiguration: a positive-sequence case does not say which winding is the delta. VECGRP is still copied to vectorGroup; it is blank on 513 shifted units of the set, so nothing is derived from it.
  • Exporter: ANGk = −phaseShift.

Phase shifters, COD ±3 (decision R4b-3)

  • A PhaseTapChangerLinear xf_<key>_ptap<k> on end k. PSS/E's angle is continuous (NTP is used only for COD ±1 and ±2), but CIM's needs steps, so NTPk sets the grid as written: lowStep 1, highStep NTP, from RMI to RMA (in PSS/E's angle) in equal steps. stepPhaseShiftIncrement = cim_angle((RMA − RMI)/(NTP − 1)).
  • neutralStep is the step nearest PSS/E angle 0 (a tie takes the upper), and step = neutralStep + ANG / ((RMA − RMI)/(NTP − 1)), a float. ANG itself is exact.
  • CIM has no neutral angle (a ratio tap has neutralU), so when 0° falls between steps, the end steps' angles move by that offset. In the set, 56 of 66 have 0° on the grid; the other 10 are off by 0.3°–1.9°. Those rows list untranscribed: rma=…, rmi=…, and the exporter's RMA/RMI differ by the offset (expected difference).
  • ltcFlag true, controlEnabled = (COD > 0). xMax stays blank: PSS/E's impedance does not move with the angle unless TABk says so (below).
  • Its control xf_<key>_ctrl<k>: mode = activePower, discrete = true, enabled = (COD > 0), on the winding's own terminal xf_<key>_T<k> (PSS/E measures the flow into the transformer at winding k's bus, and CIM's terminal flow is positive into the equipment, so there is no sign change). targetValue = (VMA + VMI)/2 and targetDeadband = VMA − VMI, in W from MW through the units library. CONTk is not used.
  • The winding's ratio WINDVk is fixed (RMA/RMI are angles here): ratio 1 gets no RatioTapChanger, an off-nominal ratio a fixed one (next).
  • Exporter: COD ±3 from a PhaseTapChangerLinear with an activePower control, signed by enabled.

Fixed ratios (decision R4b-4)

A winding whose ratio has no usable tap range gets a fixed RatioTapChanger xf_<key>_tap<k>: lowStep = highStep = neutralStep = step = 1, neutralU = WINDVk in kV (winding_kv), stepVoltageIncrement blank, ltcFlag false, controlEnabled false. Its ratio is neutralU / ratedU, exact. Three cases: - Winding 2 of a 2-winding unit, off nominal: end 2's tap changer. It has no COD data, so it has no control. - COD 0 with RMA ≤ RMI, or WINDV outside RMI..RMA. The format document says RMA/RMI are not used at COD 0, so this data is valid. The winding keeps R4's disabled control (R4: COD 0 keeps its control). RMA, RMI and NTP are listed on the row, untranscribed: rma=…, rmi=…, ntp=…, and the exporter writes their defaults (PSS/E ignores them at COD 0). A COD 0 winding with a usable range keeps R4's stepped tap changer. - A phase shifter's winding, off nominal: no control (the phase tap changer has it).

Exporter: WINDVk = neutralU / the winding unit; no RatioTapChanger → the end's ratedU / the winding unit (1 only when NOMV = BASKV; corrected by E4, EXPORT_MAPPING.md#e4-transformer-impedance-correction).

A voltage control's WINDV outside its range (decision R4b-5)

COD ±1 with WINDV outside RMI..RMA (1 winding in the set): CIM needs lowStep ≤ step ≤ highStep. R4's grid and increment stay, and lowStep extends below 1 or highStep above NTP to the first whole step past the position (ratio_tap). The same holds for COD ±2, the other stepped control (none in the set). RMA and RMI are listed on the row, and the exporter's RMA/RMI come from the extended steps (expected difference). Fixed 2026-11-09 (E4): a WINDV exactly at RMA or RMI is that end's step, not an extension; rounding had put its step a hair past the end, so ratio_tap added a step (about 50 local windings a case).

One winding out, STAT 2 / 3 / 4 (decision R4b-6)

PowerTransformer.inService = true, and the out winding's terminal gets connected = false through an Update Table Terminal: mRID, connected row (R6's pattern) after the ends: STAT 2 → xf_<key>_T2, 3 → _T3, 4 → _T1. The exporter reads STAT 2/3/4 from the one disconnected terminal and STAT 0 from inService.

Voltage-control terminals (decisions R4b-7, R4b-8)

  • COD ±1 with CONT 0: the control names the winding's own terminal xf_<key>_T<k>, as COD 0 and ±2 already do. enabled stays as written (COD > 0). The row comment says CONT 0: regulates its own terminal. The exporter writes CONT 0 back for an own terminal (R4), so this round-trips.
  • CONT < 0: the control names bb_<|CONT|>_T1. The sign tells PSS/E to adjust the ratio as if bus |CONT| were on winding 1's side; CIM has no home for it. The control row lists untranscribed: cont=-<CONT>, and the gap is logged. The exporter writes CONT positive (expected difference). It matters to PSS/E only when |CONT| is not I, J or K.

Load-drop compensation (decision R4b-9)

CRk/CXk (pu on system base) → TapChangerControl.lineDropCompensation = true, lineDropR = CR × BASKV² / SBASE and lineDropX = CX × BASKV² / SBASE in ohm (ohms_from_per_unit). BASKV is that of the regulated bus (|CONT|, or the winding's own bus at CONT 0). CR/CX on a winding that is not COD ±1 raise (PSS/E uses them only for COD 1; none in the set).

Impedance correction tables (decision R4b-10)

  • Artifact: impedance_correction.cimtbl moves before transformer.cimtbl in MAPPING_ORDER, because each winding's tabular names its table.
  • One ImpedanceTapChangerTable per RAW table: ict_<I>, name <I>. Its points are ImpedanceTapChangerTablePoint rows with identifier ict_<I>_<n> (n = 1.. in file order).
  • Angle or ratio follows PSS/E's own rule: a table whose first T is below 0.5 or last T above 1.5 is in degrees, otherwise a ratio. In the set, 31 tables are angle tables and 1 is a ratio table.
  • Angle: angle = cim_angle(T).
  • Ratio: T is in pu of the controlling winding's bus base. CIM's ratio is in pu of the end's ratedU, so ratio = T × BASKV / ratedU. Every user of a ratio table must have the same BASKV / ratedU, otherwise it raises. The set's ratio table has one user, with NOMV 230 on a 220 kV bus, so ratio = T × 220/230. A ratio table with no user raises (no base to convert with).
  • step stays blank: PSS/E looks a table up by ratio or angle, not by step.
  • Factor: F scales the impedance, so rEnd1 = xEnd1 = 100 × (Re F − 1), in percent (a 2-winding unit's r and x are on end 1). Im F ≠ 0 raises. rEnd2/3 and xEnd2/3 stay blank.
  • Each winding with TABk: an ImpedanceTapChangerTabular xf_<key>_ztab<k>, with TransformerEnd = end k and ImpedanceTapChangerTable = ict_<TABk>. Its own step fields stay blank: the winding's PhaseTapChanger or RatioTapChanger holds the position, and the table is looked up by its angle or ratio.
  • A 3-winding unit's TAB raises. PSS/E applies it to the T-model's Z_k (ZCOD 0) or to Z_ij (ZCOD 1), and the Delta model needs a rule for that; none in the set.
  • Exporter: TABk from the tabular's table; F = 1 + rEnd1/100. A point with rEnd1 ≠ xEnd1 has no PSS/E form and raises.

Field classification (samples from the R4b atom):

ImpedanceCorrectionRecord field type samples kind target
table_number Union[int, ImpedanceCorrectionRecordTableNumber] 1, 2 structural I: the key, ImpedanceTapChangerTable ict_, named ; a winding's TABk names it (transformer.cimtbl)
points list[ImpedanceCorrectionPoint] 7 and 3 points structural the points (T, F), each an ImpedanceTapChangerTablePoint ict__ (n = 1.. in file order); the 0, 0, 0 point that ends the table is not a point
ImpedanceCorrectionPoint field type samples kind target
t float -30.0, -10.0, 0.0 derived Ti: an angle table's (first T < 0.5 or last T > 1.5, is_angle_table) angle = cim_angle(T) (deg); else a ratio table's ratio = T x BASKV / ratedU of its users' winding (users that disagree, or none, raise); step blank (PSS/E looks a table up by angle or ratio)
f_real float 1.2, 1.05, 1.0 derived Re(Fi): rEnd1 = xEnd1 = 100 x (F - 1) percent of the nominal impedance (impedance_deviation_percent; a 2-winding unit's r and x are on end 1)
f_imag float 0.0 structural Im(Fi): a complex factor has no CIM form (rEnd and xEnd are real); nonzero raises

mRIDs (prefixes requested, C3)

xf_<key>_ptap<k> (phase tap changer), xf_<key>_ztab<k> (impedance tabular), ict_<I> and ict_<I>_<n> (the table and its points). A fixed ratio tap reuses xf_<key>_tap<k>, so winding 2's is xf_<key>_tap2.

Atom tests/atoms/transformer/forms_r4b.raw (hand-built)

One unit per form: - a 2-winding unit with ANG1 30 and COD 1; - a 3-winding unit with ANG2 −13.5 and STAT 3; - a 3-winding unit with STAT 2, and one with STAT 4; - a COD 3 shifter with 0° on its grid, and a COD −3 shifter with 0° off its grid, an off-nominal WINDV1 and an angle table; - a COD −2 unit with NOMV ≠ BASKV and a ratio table; - an off-nominal WINDV2 (CW 1 and CW 2); - COD 0 with RMA = RMI, and COD 0 with WINDV outside RMI..RMA; - COD 1 with WINDV outside RMI..RMA; - COD 1 with CONT 0; COD 1 with a negative CONT; COD 1 with CR/CX; - and the impedance correction section with two tables, one of them running onto a second line.

It survives a RAW read → write → read with nothing lost, and binds. Each value is checked in SI against the formulas above, and the raise list is tested form by form.

Expected export differences

  • A shifter's RMA/RMI, when 0° falls between its steps (by that offset).
  • COD 0 RMA/RMI/NTP that PSS/E ignores come back as their defaults.
  • A negative CONT comes back positive.
  • An extended voltage-control range comes back as its extended steps.

CIM 18 gaps and profile notes

  • Gap: which side of a voltage-controlling winding its controlled bus is on (CONT's sign).
  • Profile note: the inverse of ImpedanceTapChangerTabular.TransformerEnd is spelled TransformerEnd.ImpedanceTabChanger.
  • Profile note: phaseShift's sign is the PhaseTapChanger sign (R4b-1), stated in its UML text.

Results

The atom binds, and each form is checked value by value (tests/test_raw_to_cimtbl.py, R4b). On the local case set, every transformer and impedance correction table maps; one case binds whole once the records still blocked in other slices are set aside (R1b, R2b, R3b, phase 2): 7402 transformers, 9927 ratio and 66 phase tap changers, 32 tables with 303 points, 49 tabulars.

Areas, tie flows and inter-area transfer (R5)

Approved 2026-11-08 and implemented. RAW-2 (the open part: how a bus's AREA is recorded). Atom: tests/atoms/area/. User choices 2026-11-08: a bus's AREA traced on export (no profile extension); inter-area transfers listed untranscribed (no profile class).

Code: importer/cimtbl/tie_flow.py (TieFlowRows, used by branch.py, switch.py and transformer.py), importer/topology.py (untraced_area_buses), importer/cimtbl/interarea_transfer.py (transfer_lines) and derived.net_import.

There is no new artifact. Each device's tie flows go in its own artifact, because MET and NMETR are its fields. The transfers have no CIM home, so they are listed on area_interchange.cimtbl.

netInterchange sign (an R0 fix)

PDES is the area's desired net export. CIM's ControlArea.netInterchange is positive into the area (ControlArea's rule 1: import positive). So netInterchange = -PDES (net_import, written 0.0 - PDES so that 0 stays 0.0). Both public cases have PDES 0, so no golden value changes. The field becomes derived.

cim18v17 marks netInterchange, pTolerance and type ToBeDeleted. Their successor, AreaInterchangeController, carries only pTolerance and an enabled that RAW does not give (area interchange control is a solution option). So both values stay on ControlArea until the profile has a home for the scheduled interchange.

Tie flows

A tie is a branch, switching device or transformer whose terminals' buses are in more than one AREA. - Its home end is the non-metered end, whose area PSS/E charges with the device's losses: - branch MET or switch METERED 1 (bus I metered): J; - MET 2: I; - a transformer's NMETR names the home winding directly (1, 2 or 3; default 2). On a tie, any other value raises. Elsewhere, MET and NMETR stay untranscribed, as before (RAW-22). - At each terminal whose bus is not in the home area, two TieFlows sit on that terminal: - one for the bus's own area, positiveFlowIn = false (flow into the terminal leaves that area); - one for the home area, positiveFlowIn = true.

They sum to zero, as ControlArea's rule 3 asks of a tie seen from both areas. A 3-winding transformer with two windings outside its home area has two pairs. - mRID tf_<AREA>_<terminal>, name <AREA>_<key>_T<k> (prefix requested, C3). The TieFlow table comes last in the device's artifact. It refers back to the terminal and to ca_<AREA>; an AREA with no area-interchange record raises, as it does for loads and generators. - What it recovers: a tie's metered end (the terminal holding the pair). That narrows the MET/NMETR gap to devices inside one area.

WECC240: 23 tie branches give 46 TieFlows. No transformer or switch there spans two areas, and IEEE14 has one area and no tie flows. Branch 1002-6506 has MET 2; branch 1201-2901 has MET 1:

# tie flows: two TieFlows on each tie's metered terminal, positiveFlowIn = false for the terminal's bus's area and true for the home (non-metered) end's area (MET)
Table TieFlow: mRID, name, positiveFlowIn, ControlArea, Terminal
    tf_3_ln_1002_6506_1_T2, 3_1002_6506_1_T2, false, ca_3, ln_1002_6506_1_T2
    tf_1_ln_1002_6506_1_T2, 1_1002_6506_1_T2, true,  ca_1, ln_1002_6506_1_T2
    ...
    tf_1_ln_1201_2901_1_T1, 1_1201_2901_1_T1, false, ca_1, ln_1201_2901_1_T1
    tf_2_ln_1201_2901_1_T1, 2_1201_2901_1_T1, true,  ca_2, ln_1201_2901_1_T1

The atom's 3-winding tie 101-202-302 has NMETR 3, so winding 3 (area 3) is home and windings 1 and 2 are metered:

Table TieFlow: mRID, name, positiveFlowIn, ControlArea, Terminal
    tf_1_xf_101_202_302_1_T1, 1_101_202_302_1_T1, false, ca_1, xf_101_202_302_1_T1
    tf_3_xf_101_202_302_1_T1, 3_101_202_302_1_T1, true,  ca_3, xf_101_202_302_1_T1
    tf_2_xf_101_202_302_1_T2, 2_101_202_302_1_T2, false, ca_2, xf_101_202_302_1_T2
    tf_3_xf_101_202_302_1_T2, 3_101_202_302_1_T2, true,  ca_3, xf_101_202_302_1_T2

The device tables now say where MET/NMETR are still untranscribed:

# untranscribed: o1, f1, o2, f2, o3, f3, o4, f4
# untranscribed off a tie: MET (a tie's TieFlows record it; CIM 18 gap, RAW-22)
Table ACLineSegment: ...

A bus's AREA (RAW-2)

A node or BusbarSection has no ControlArea association (CIM 18 gap). The area is recorded by what CIM already places in an area: generating units (R3) and tie flows. On export the bus's AREA is traced: - Seeds: - a generator's bus has its unit's ControlArea; - a tie terminal's bus has its pair's false area; - each other terminal of a tie has the home area. - Propagation: across every device whose ends are in one area (branch, switch, transformer).

Loads are not seeds, since a load's AREA is its own (R2). The importer runs the same trace on the RAW records. Any bus the trace cannot reach (a component with no generator and no tie) gets untranscribed: area=<AREA> on its TopologicalNode row. In IEEE14 and WECC240, every bus is reached. In the atom, isolated bus 303 is not:

    # untranscribed: area=3 (no generator or tie reaches it)
    303, NORTH ISOL, 303, bv_115kv, sub_303

Area slack bus (ISW)

Unchanged: untranscribed (CIM 18 gap). SynchronousMachine.referencePriority is the angle reference (R3), not an area's interchange slack.

Inter-area transfer

Mapper: importer/cimtbl/interarea_transfer.py (transfer_lines). It writes no artifact. - No home: cim18v17 has no scheduled-transfer class. cim17v40's InterchangeSchedule and its market classes are gone, and TieCorridor / PowerTransferCorridor group ties but carry no schedule. - What is written: each record is listed verbatim on the ControlArea table comment of area_interchange.cimtbl, so the master no longer lists the table as not mapped. - Checks: ARFROM and ARTO must have area-interchange records, else it raises. - Recorded as a CIM 18 gap, with a profile extension as the candidate (the user's).

The atom:

# untranscribed: bus_number
# derived: netInterchange = -PDES (net_import)
# untranscribed: inter-area transfers (CIM 18 gap): 1 -> 2 '1' 30.0 MW; 1 -> 2 'A' 20.0 MW; 3 -> 2 '1' 0.0 MW
# (defaulted: transfer_id, power_transfer)
Table ControlArea: mRID, name, netInterchange (MW), pTolerance (MW)
    ca_1, WEST, -50.0, 5.0
    # defaulted: ptol=10.0
    ca_2, EAST, 50.0,  10.0
    # defaulted: name=
    ca_3, 3,    0.0,   0.0
InterareaTransferRecord field type samples kind target
from_area int untranscribed ARFROM: listed on area_interchange.cimtbl's ControlArea comment (no scheduled-transfer class, CIM 18 gap); with no area-interchange record raises
to_area int untranscribed ARTO: as ARFROM
transfer_id Optional[str] untranscribed TRID: as ARFROM; blank: 1 (defaulted)
power_transfer Optional[float] untranscribed PTRAN (MW, positive = ARFROM selling to ARTO): as ARFROM; blank: 0 (defaulted)

Atom tests/atoms/area/areas.raw

Three areas:

area name ISW PDES PTOL
1 WEST 101 50 5
2 EAST 0 -50 blank
3 blank 0 0 0

Buses: 101 (swing, generator) and 102 in area 1; 201 (generator) and 202 (load) in area 2; 301 (generator), 302 (115 kV) and 303 (115 kV, isolated, no equipment: the untraced bus) in area 3.

Ties: - branch 102-201 circuit 1, MET 1 (pair at T1); - branch 102-201 circuit 2, MET 2 (pair at T2); - branch 202-301, MET blank (defaults to 1); - switch 102-301, METERED 2; - 2-winding transformer 202-302, NMETR 1 (pair at T2); - 3-winding transformer 101-202-302, NMETR 3 (pairs at T1 and T2).

Inside one area: branch 101-102 with MET 2 (stays untranscribed) and transformer 301-302.

Transfers: 1→2 '1' 30 MW, 1→2 'A' 20 MW, and 3→2 with TRID and PTRAN blank.

Exit (met 2026-11-08; 181 tests): - the atom binds; - each tie's two flows sit on one terminal with opposite signs; - MET and NMETR on a tie are recovered from the pair's terminal; - in IEEE14, WECC240 and the atom, the trace over the bound CIM gives every bus's RAW AREA, except bus 303, which carries the comment (the test's _traced_areas is the export rule's first draft); - the master lists nothing as not mapped.

Also fixed: the schema's NMETR description said "metered end"; NMETR is the non-metered end code. Its default 2 names the same end as MET's default 1.

Node-breaker substations (R6)

Approved 2026-11-09 and implemented (drafted 2026-11-08, checked against the RAW v34 format document 2026-11-09). RAW-16, RAW-11 (regulated nodes), §3.2's node-breaker rule. User choices 2026-11-09: LATI = LONG = 0 writes no Location; a busbar only on a node a control regulates (the IEEE118 layouts give no safe busbar rule, below); node STATUS 0 listed on its row.

Code: importer/node_breaker.py (NodeBreaker: the blocks, nodes and bus → block index, and regulated_terminal), importer/topology.py (block edges in substation_groups; substation switching devices in the area trace), importer/cimtbl/substation.py, importer/cimtbl/equipment_terminal.py, and regulated_nodes in generator.py, switched_shunt.py and transformer.py.

Cases: tests/cases/IEEE118/IEEE118_all_hydro_25_clean_4_subs.raw (written by PSS/E 34.9 2026-11-09: IEEE 118 with four buses expanded to node-breaker, below). Atoms: tests/atoms/substation/ (the PSS/E-built two-bus atom, and the hand-built node_breaker_forms.raw). IEEE14 and WECC240 have no SUBSTATION data. Goldens: tests/goldens/IEEE118/ (substation.cimtbl, equipment_terminal.cimtbl).

Load path (RAW-16, resolved)

cimtables already loads a mixed model, so nothing is filed upstream (checked 2026-11-08 on the two-bus atom): - a row with node1 and bus1 puts one Terminal on both its ConnectivityNode and its TopologicalNode (connectivity.add_connectivity; its docstring names PSS/E's substation node data as the case); - a ConnectivityNode row binds TopologicalNode, BaseVoltage and ConnectivityNodeContainer as ordinary associations, and the inverses (TopologicalNode.ConnectivityNodes, ConnectivityNode.Terminals) are filled; - Update Table Terminal: mRID, ConnectivityNode adds a node to a Terminal that already has its TopologicalNode.

An in-memory BusBranchModel and NodeBreakerModel behave the same (they differ only in database loading), so RawImporter.model_cls stays BusBranchModel. A bus outside any SUBSTATION block keeps its bare TopologicalNode; a bus inside one also gets its block's ConnectivityNodes.

Artifacts

The SUBSTATION section's four record classes land in three places, because of bind order:

native class artifact position why there
SubstationRecord bus.cimtbl, its Substation table 3 the bus's TopologicalNode names its substation as ConnectivityNodeContainer, so the substation binds first
SubstationRecord (coordinates), SubstationNodeRecord, StationSwitchingDeviceRecord substation.cimtbl 3a, after bus.cimtbl a node names its bus's TopologicalNode; a regulated node's busbar must exist before the generator, switched shunt and transformer controls that name it
EquipmentTerminalRecord equipment_terminal.cimtbl last, after the phase-2 stubs Update rows on Terminals, which exist only once every equipment artifact is written; the mapper matches each record against the equipment those artifacts wrote

So the equipment mappers stay as they are: they still write bus / bus1 / bus2, and the placement on a node is one reviewable file.

Substations: the block takes precedence (plan §3.2)

topology.substation_groups gains the blocks (NodeBreaker.block_of_bus): - Block edges: every bus a block's nodes name is joined to the block's other buses, alongside the §3.2 merge equipment. - Identity: a group holding a block is sub_s<IS> (prefix C3; bus.block_mrid), named the block's NAME (blank: IS). Its row comment says SUBSTATION block IS: bus(es) ..., plus any merge equipment. A group with no block keeps sub_<lowest bus>. - A free bus merged into a block's group (by a transformer) joins sub_s<IS>: IEEE118's buses 5 and 38. - Raises: a bus with nodes in two blocks; a group holding two blocks (merge equipment between them); a block whose buses are in two zones (a Substation has one Region).

# synthesized: substations, buses merged across switching devices, zero-impedance branches (R = 0, |X| <= THRSHZ
# 0.0001), series capacitors and transformers, within a zone (108 substations, 4 from SUBSTATION blocks (R6))
Table Substation: mRID, name, Region
    ...
    # SUBSTATION block 8: buses 5, 8; xf_8_5_0_1
    sub_s8,   STATION_8, srgn_1

Coordinates follow the OpenDSS spoke's LatLongCoords form: one CoordinateSystem crs_latlong (crsUrn urn:ogc:def:crs:OGC:1.3:CRS84, x = longitude, y = latitude), a Location sub_s<IS>_loc with one PositionPoint sub_s<IS>_loc_1, and Update Table Substation: mRID, Location. A block with LATI = LONG = 0 (the default, as every block of the two-bus atom and IEEE118 writes) gets no Location, and the document comment lists them (user, 2026-11-09). The exporter writes 0, 0 back, so the round trip holds either way.

SubstationRecord field type samples kind target
substation_number Union[int, SubstationRecordSubstationNumber] 100, 37, 49 structural IS: the key, Substation sub_s (in bus.cimtbl, R6); the scope of its node numbers
name Optional[str] GLEN L, EASTLI, PHILO structural NAME: the Substation's name (bus.cimtbl); blank: IS
latitude Optional[float] 0.0, 46.2 copied PositionPoint.yPosition; LATI (deg): the point sub_s_loc_1 of Location sub_s_loc; LATI = LONG = 0 (the default) writes no Location (user, 2026-11-09)
longitude Optional[float] 0.0, -119.1 copied PositionPoint.xPosition; LONG (deg): as LATI
grounding_resistance Optional[float] 0.1, 0.2 untranscribed SGR (ohm): a substation's DC grounding resistance (GIC) has no CIM 18 home (gap)

Nodes

One ConnectivityNode sub_s<IS>_n<NI> per node, in its bus's TopologicalNode and its block's substation, with its bus's BaseVoltage. NodeBreaker raises on a node number twice in a block, a node on no bus, and a bus with nodes in two blocks.

SubstationNodeRecord field type samples kind target
node_number int 1, 10, 11 structural NI: with IS the key, ConnectivityNode sub_s_n; a node number twice in one block raises
bus_number int 100, 37, 49 structural I: TopologicalNode = I (bare), BaseVoltage = bus I's; a bus with nodes in two blocks raises
name Optional[str] GLEN L_100_1, GLEN L_100_10, GLEN L_100_11 copied ConnectivityNode.name; NAME; blank: _
status Optional[int] 1, 0 untranscribed STATUS: a ConnectivityNode has no in-service flag (CIM 18 gap); 0 is listed on the row
vm Optional[float] 1.02 untranscribed VM (pu): SvVoltage attaches only to a TopologicalNode (the bus's VM); a VM other than the default -1.0 (not given) is listed on the row
va Optional[float] -2.5 untranscribed VA (deg): as VM; listed when not 0.0
substation_number Optional[int] 100, 37, 49 structural IS: the enclosing block (filled by the reader); ConnectivityNodeContainer = sub_s

STATUS has no home (a ConnectivityNode has no in-service flag). IEEE118's transfer bus is out of service:

# untranscribed: status, vm, va
Table ConnectivityNode: mRID, name, TopologicalNode, BaseVoltage, ConnectivityNodeContainer
    ...
    sub_s100_n1,  GLEN L_100_1,  100, bv_138kv, sub_s100
    # untranscribed: status=0
    sub_s100_n2,  GLEN L_100_2,  100, bv_138kv, sub_s100

Substation switching devices

Each record becomes a Switch, Breaker or Disconnector by TYPE, with the system switching device's code tables (switch.SWITCH_CLASS, switch.OPEN), node1/node2 on its nodes and bus1/bus2 on their buses, in sub_s<IS>. A device whose nodes' buses are in two AREAs raises (a tie inside a substation: no case). The R5 area trace spreads across these devices like any same-area device; one between two nodes of one bus joins nothing.

StationSwitchingDeviceRecord field type samples kind target
from_node int 1, 2, 3 structural NI: node1 = sub_s_n, bus1 = that node's bus; BaseVoltage = its bus's
to_node int 10, 11, 12 structural NJ: node2, bus2; NI = NJ raises
device_type int 2, 3, 1 mapped TYPE: the class, as a system switching device's STYPE: 1 Switch (generic connector), 2 Breaker, 3 Disconnector; another code raises
circuit Optional[str] 1 structural CKT: with IS, NI and NJ the key, mRID sw_s_; blank: 1 (defaulted)
name Optional[str] SHUNT BREAKER OPEN, GEN BREAKER, LINE DISCONNECT copied Switch.name, Breaker.name, Disconnector.name; NAME; blank: the key _
status Optional[int] 1, 0 mapped STATUS: open = (STATUS == 0); blank: 1 (defaulted)
normal_status Optional[int] 1, 0 mapped NSTAT: normalOpen = (NSTAT == 0); blank: 1 (defaulted)
reactance Optional[float] 0.0001 untranscribed X: as a system switching device's (a Switch has no impedance); the exporter writes the default 0.0001 back
rate1 Optional[float] 0.0, 250.0 structural RATE1..RATE3: as a system switching device's ratings (RatingRows, units by NXFRAT), the set sw_s_ratings on terminal 1; zero is no limit
rate2 Optional[float] 0.0 structural RATE2: as RATE1
rate3 Optional[float] 0.0 structural RATE3: as RATE1
substation_number Optional[int] 100, 37, 49 structural IS: EquipmentContainer = sub_s
# untranscribed: reactance
Table Breaker: mRID, name, node1, node2, bus1, bus2, open, normalOpen, BaseVoltage, EquipmentContainer
    ...
    sw_s100_1_2_1,  100_1_2_1,  sub_s100_n1, sub_s100_n2,  100, 100, true,  true,  bv_138kv, sub_s100

Table Disconnector: mRID, name, node1, node2, bus1, bus2, open, normalOpen, BaseVoltage, EquipmentContainer
    sw_s100_2_3_1,  100_2_3_1,  sub_s100_n2, sub_s100_n3,  100, 100, true, true, bv_138kv, sub_s100
    ...

Regulated nodes (RAW-11: NREG, NOD1..NOD3)

A nonzero generator NREG, switched-shunt NREG or transformer NODk names node NI of the regulated bus (IREG / SWREG / CONTk, or the device's own bus when IREG or SWREG is 0). The control's Terminal is bb_s<IS>_n<NI>_T1 (NodeBreaker.regulated_terminal), the terminal of a BusbarSection bb_s<IS>_n<NI> on that node (node + bus, in sub_s<IS>, named the node's NAME). substation.cimtbl writes one such busbar per node some control names (regulated_nodes of the three mappers), and no others. The bus's own bb_<I> stays as it is, on the bus only, holding the limits and any bus-level regulation. NREG is a plant quantity: a plant's records must agree on it. Raises: the regulated bus has no block, the block has no node NI of that bus, or NODk ≠ 0 with CONTk = 0.

Which nodes are busbars (user, 2026-11-09: none inferred). In IEEE118's four PSS/E-generated layouts the busbars are exactly the nodes with no equipment terminal (double bus double breaker 8: nodes 1, 2; breaker and a half 49: 1, 2; main and transfer 100: 1, 2; ring 37: none), each joined to 5-11 devices. That rule fails on a bay's internal node (a breaker between two disconnectors leaves a terminal-free node too), and the two-bus atom's block 2 has two terminal-free nodes on one breaker each; a degree threshold misses block 1's two-feeder busbars (degree 2).

# one per node a control regulates (NREG, NODk; RAW-11); RAW does not say which nodes are busbars
Table BusbarSection: mRID, name, node, bus, BaseVoltage, EquipmentContainer
    bb_s10_n1,  HV BUS, sub_s10_n1,  1, bv_230kv, sub_s10
    bb_s10_n11, LV BUS, sub_s10_n11, 2, bv_115kv, sub_s10

Equipment terminals

Each record puts the equipment's terminal at bus I on node sub_s<IS>_n<NI>, as an Update Table Terminal: mRID, ConnectivityNode row in equipment_terminal.cimtbl, in (IS, NI) order. The node's bus must be I, and its block IS. The equipment is matched against the mRIDs the earlier artifacts wrote (written_equipment), so the mapper derives no mRID rule of its own: equipment that no mapper wrote, a key that matches two, and a Terminal placed twice raise. A terminal with no record stays on its bus only.

NI = 0 is the format's "bus I has no node-breaker model": the record writes no row, and the table comment counts such records. NI = 0 at a bus that has nodes raises, as does a nonzero NI at a bus that has none.

TYP equipment (key) Terminal(s) updated
L load (I, ID) ld_<I>_<ID>_T1
F fixed shunt (I, ID) cap_<I>_<ID>_T1
M generator (I, ID) sm_<I>_<ID>_T1 (WMOD 0) or pec_<I>_<ID>_T1 (WMOD 1)
B or 2 (one form) a branch or a 2-winding transformer (I, J, CKT) a branch: ln_ / sc_<key>_T1 when I is its from bus, _T2 when its to bus, and that end's line shunt cap_<key>_i / _j on the same node (RAW-13: a node-breaker model says "switched with its line" by placement); a transformer: xf_<key>_T1 or _T2, by which winding I is
3 3-winding transformer (I, J, K, CKT) xf_<key>_T<k>, the winding at I; the buses in any order
S switched shunt (I; no ID in v34) every block's swsh_<I>_b<k>_T1
I, D, V, N, A phase-2 equipment raise (phase 2)

The key is matched in either bus order: I is the end at this record, so the record at a branch's to bus lists it first (IEEE118's ln_9_8_1_T2 at block 8, the two-bus atom's SUB_2). A system switching device is no terminal-record form: a B key that matches only one raises, and the switch stays on its buses.

EquipmentTerminalRecord field type samples kind target
bus_number int 100, 37, 49 structural I: which terminal of the equipment; node NI's bus must be I
node_number int 3, 4, 5 structural NI: the Terminal's ConnectivityNode sub_s_n (an Update row); 0: bus I has no node-breaker model, no row
terminal_type str B, L, M structural TYP: the equipment form, L F M B/2 3 S; B and 2 are one form (a branch or a two-winding transformer); I D V N A raise (phase 2)
j_bus Optional[int] 101, 103, 104 structural J: the other end of a B / 2 / 3 key, in either order
k_bus Optional[int] 4, 1, 2 structural K: the third winding of a 3 key
identifier Optional[str] 1, 2, T structural ID / CKT: the rest of the key; blank: 1 for L F M I B 2 3 (defaulted)
substation_number Optional[int] 100, 37, 49 structural IS: the block whose node NI is meant (filled by the reader)
# each named equipment terminal on its node; 1 record with NI 0 (no node-breaker model) places nothing
Update Table Terminal: mRID, ConnectivityNode
    sm_1_G_T1,      sub_s10_n2
    pec_1_PV_T1,    sub_s10_n2
    ln_1_3_A_T1,    sub_s10_n3
    cap_1_3_A_i_T1, sub_s10_n3
    ...

Cases and atoms

  • two_bus_node_breaker.raw (PSS/E-built, committed in R0): sub_s1, sub_s2; 8 nodes; 7 breakers; the four line ends on nodes 3 and 4 of each block (ln_1_2_1_T1 on sub_s1_n3, ln_1_2_1_T2 on sub_s2_n3, ...).
  • IEEE118 (PSS/E-written; the whole case mapped before R6 apart from its SUBSTATION data):
  • block 8 (OLIVE 345 kV, double bus double breaker): 7 nodes, 10 breakers; terminals L, M, two B, and a 2 to bus 5, which the transformer merges into sub_s8;
  • block 37 (EASTLI 138 kV, ring): 7 nodes, 7 breakers; S, five B, and a 2 to bus 38 (merged into sub_s37);
  • block 49 (PHILO 138 kV, breaker and a half): 16 nodes, 21 breakers; L, M, twelve B (two pairs of parallel lines);
  • block 100 (GLEN L 138 kV, main and transfer): 12 nodes, 11 breakers (1-2 open, normally open) and 10 open disconnectors to the out-of-service transfer bus (node 2, STATUS 0); L, M, eight B.

No NREG, NODk, F or 3; every block at 0, 0. 36 terminals placed, 42 nodes, 108 substations. - node_breaker_forms.raw (hand-built, its content in the folder's README): one block 10 at 46.2 N, 119.1 W holding buses 1 (230 kV) and 2 (115 kV), every TYPE, open and normally-open devices, a rated device, an unnamed node with VM/VA; terminal records for L, F, M (WMOD 0 and 1), B (a line with its line shunt), 2 (a transformer, and a line written as 2), 3 (once with its buses reordered), S, and one with NI = 0 at the free bus 4, which the 3-winding transformer merges into sub_s10; a generator NREG, a switched-shunt NREG and a transformer NOD1 (two controls on one node, so one busbar each for nodes 1 and 11).

Raise tests on it: a bus in two blocks, two blocks in one substation, a block across zones, NI = NJ, a device node outside its block, a terminal on another bus's node, unknown equipment, a Terminal placed twice, NI 0 at a bus with nodes, a phase-2 and an unknown TYP, a B record naming a system switching device, an NREG with no node, NOD1 with CONT1 0.

Exit (met 2026-11-09; 216 tests): - IEEE118 and both atoms bind; every placed Terminal's ConnectivityNode.TopologicalNode is its own TopologicalNode, and every node is in its bus's substation; - the master lists nothing as not mapped for any of them; - IEEE14 and WECC240 output is unchanged (their goldens and counts pass as before); - NREG / NODk no longer raise, except as above; - IEEE118 and the forms atom read → write → read losslessly.

Expected export differences

SGR comes back as the default 0.1; a node's STATUS 0 as 1, and its VM/VA as the defaults (-1.0, 0.0); a terminal record with NI = 0 is not written back (it places nothing); a B/2 record comes back as 2 for a transformer and B for a branch; a substation switching device's X as 0.0001; a block at 0, 0 as 0, 0. A free bus merged into a block's substation (by a transformer) stays outside the block's node data, as it was.

FACTS devices and DC lines (phase 2, P2a / P2b)

P2a approved 2026-11-09 (user: "profiles fixed, continue") and implemented: facts_device.py, vsc_dc.py, dc_topology.py; atom tests/atoms/dc/facts_vsc.raw. P2b approved 2026-11-09 (user: "go ahead and build the converter transformer") and implemented: two_terminal_dc.py, derived converter_transformer_ohms, converter_tap; atom tests/atoms/dc/two_terminal.raw; the converter transformer follows the new core shape behind_transformer.cimtbl (C8, on the core branch c8-behind-transformer). Profile additions (user, 2026-11-09): ACDCConverter.PccTerminal, and VsCapabilityCurve is a Curve. The local case set holds the following, the same in each of its 29 cases (counts only):

table per case forms P2
FACTS device 25 all shunt only (J = 0, MODE 0 or 1); 24 regulate a remote bus; PDES, QDES, SET1, SET2, IMX 0, MNAME blank P2a
VSC DC line 2 both are area ties; converter TYPE 1 + 2, MODE 1; 3 of the 4 converters regulate a remote bus P2a
two-terminal DC line 19 MDC 0 or 1; every converter transformer implicit (IFR = ITR = 0); no capacitor commutation (XCAP 0); 2 are area ties; 3 name a commutating bus ICR P2b
multi-terminal DC, GNE, induction machine 0 stubs stay

The set has no node-breaker substations, so equipment terminal records of TYP A, D and V still raise. Switched shunts with MODSW 6 (they control a FACTS device's shunt output) go with MODSW 3 in R2b: both convert VSWHI/VSWLO from pu of the controlled device's reactive range.

DC topology (decision P2-1)

  • Bus-branch, so DCTopologicalNodes, as AC buses are TopologicalNodes. Each DC line has two: <line>_n1 (converter 1 or the rectifier) and <line>_n2.
  • A DCLine container per line, holding the nodes and one DCLineSegment <line>_seg. Its resistance is RDC (ohm), and its DCTerminals <line>_seg_DC1/_DC2 sit on n1/n2.
  • Each converter has one ACDCConverterDCTerminal <converter>_DC1 (polarity positive) on its node. RAW gives one equivalent pole, so the return path is not modeled. CIM's monopole has a negative terminal as well.
  • RDC = 0 is still a segment, with resistance 0. About 3 lines per case have it; it looks like back-to-back, but no topology is inferred from it.
  • Converters sit in their AC bus's Substation, as all AC equipment does. No DCConverterUnit: RAW says nothing of poles or operating mode.
  • cimtables binds these rows as they are: the DC terminals are explicit rows, and the converters' AC terminals come from the bus column. This was checked on a scratch document, so no core or cimtables request is needed. mRIDs: two-terminal lines dc2_<NAME>, VSC lines vsc_<NAME> (prefixes requested, C3).

FACTS device: shunt only (decision P2-2)

Equipment. StaticSynchronousCompensator fd_<NAME> (a FACTSEquipment, so a RegulatingCondEq), on bus I, in bus I's substation and BaseVoltage. J ≠ 0 raises: series FACTS (SSSC, UPFC, IPFC); there are none in the set, and UPFC/IPFC have no CIM class.

field target
MODE 0: inService false; 1: true; 2..8 need J ≠ 0 and raise
VSET a RegulatingControl fdc_<NAME>: mode voltage, discrete false, enabled true, targetValue = VSET × BASKV(FCREG) (V)
FCREG, NREG the control's Terminal: bb_<FCREG>_T1, or the node busbar (R6, RAW-11); FCREG 0 is bus I
SHMX (MVA at unity voltage) ratedI = SHMX / (√3 × BASKV(I)) kA (ka_from_rating, RAW-9); 0 (5 devices: shunt disabled) stays 0
PDES, QDES, TRMX, VTMN, VTMX, VSMX, IMX, LINX, SET1, SET2, VSREF, MNAME the series element's; a shunt device does not use them; untranscribed, listed on the row when not the default (5 rows in the set)
RMPCT untranscribed, as the switched shunt's (gap); listed when not 100 (3 devices)
OWNER untranscribed (gap)

VSC DC line (decision P2-3)

Line. A DCLine vsc_<NAME> with segment resistance = RDC. MDC 0 sets inService false on the segment and both converters. O1..F4 are untranscribed (ownership gap).

Converters. VsConverter vsc_<NAME>_c1 and _c2 on IBUS. Converter k:

field target
TYPE 0: inService false, DCSET listed; 1: pPccControl udc, targetUdc = DCSET (kV); 2: pPccControl pPcc, targetPpcc = −DCSET (MW; RAW's + feeds the AC network, CIM uses the load sign)
MODE, ACSET 1: qPccControl voltagePcc, targetUpcc = ACSET × BASKV(VSREG or IBUS) (kV); 2: qPccControl powerFactorPcc, targetPowerFactorPcc = ACSET
ALOSS, BLOSS idleLoss (kW) and switchingLoss (kW/A): PSS/E's loss = ALOSS + Idc × BLOSS
MINLOSS no CIM home (gap); listed when not 0
SMAX, IMAX an OperationalLimitSet <converter>_ratings on T1, typed as RATE1: ApparentPowerLimit SMAX (MVA) and CurrentLimit IMAX (A); 0 (unlimited) writes no limit
PWF no CIM home (gap); listed when not 1.0 (all 4 converters are 0.5)
MAXQ, MINQ MODE 1: a VsCapabilityCurve <converter>_qcurve (curveStyle constantYValue, x in MW, y in MVAr) with one CurveData point: x 0, y1 MINQ, y2 MAXQ, so the limits hold at every P. MODE 2 does not use them; listed when not the default
VSREG, NREG MODE 1: PccTerminal = bb_<VSREG>_T1 (bb_<IBUS>_T1 when 0, RAW-11), or the NREG node's busbar (R6); MODE 2: bb_<IBUS>_T1, with VSREG and NREG listed when not 0
RMPCT qShare (PerCent), copied

Ties (both lines). PSS/E makes the DC-voltage (TYPE 1) converter the non-metered home end. The TieFlow pair goes on the other converter's terminal, through R5's TieFlowRows. Its add takes the terminals' mRIDs, since a DC line's two terminals belong to two converters. A tie without exactly one TYPE 1 converter raises.

Two-terminal DC line (decision P2-4)

Line. A DCLine dc2_<NAME>, the segment, and CsConverters dc2_<NAME>_r (operatingMode rectifier, behind IPR) and _i (inverter, behind IPI), each on its internal node (P2-5).

field target
MDC 0 (blocked) inService false on the segment and both converters (the transformers stay in service); the rectifier has no pPccControl; SETVL listed on the DCLine row, since its unit (A or MW) depends on the MDC it was blocked from
MDC 1, SETVL rectifier pPccControl activePower. SETVL > 0 is targetPpcc on the rectifier; SETVL < 0 (most of the set) is targetPpcc on the inverter, as given: the load sign already makes an inverter's injection negative
MDC 2, SETVL rectifier pPccControl dcCurrent, targetIdc = SETVL (A)
VSCHD inverter pPccControl dcVoltage, targetUdc = VSCHD (kV). RCOMP 0 (all the set) puts the compounding point at the inverter; a nonzero RCOMP is listed
VCMOD, RCOMP, DELTI, DCVMIN, CCCITMX, CCCACC no CIM home (gap); listed on the DCLine row when not the default (DELTI is on every line of the set)
METER on a tie, the TieFlow pair sits on the metered converter's transformer terminal at the AC bus (<converter>_xf_T1); the other converter is home (R5)
NBR / NBI numberOfValves = 6 × NB (six valves per bridge)
ANMXR, ANMNR / ANMXI, ANMNI maxAlpha, minAlpha / maxGamma, minGamma (deg)
RC, XC, EBAS, TR, TAP, TMX, TMN, STP the converter transformer (P2-5)
ICR, NDR the firing-angle measuring bus has no CIM home (gap); listed on the converter row when nonzero
IFR, ITR, IDR ≠ 0 raise: an AC transformer used as the converter transformer (COD ±4; none in the set)
XCAPR, XCAPI ≠ 0 raise: capacitor commutated (none in the set)

The converter transformer (decision P2-5)

Every two-terminal converter has a transformer that RAW describes implicitly (EBAS, TR, TAP and its range, RC/XC per bridge). Each becomes the core shape behind_transformer.cimtbl (plan C8, widened to "equipment behind its own transformer"; it serves the step-up generators of R3b too):

  • Internal node: TopologicalNode <converter>_int, with no busNumber. It sits in the AC bus's substation, with the BaseVoltage of EBAS × TR (the valve side). The master's BaseVoltage table adds these voltages (two_terminal_dc.valve_kv). The CsConverter sits on this node.
  • Transformer: a 2-winding PowerTransformer <converter>_xf, always in service.
  • End 1 is on the AC bus, with ratedU = EBAS.
  • End 2 is on the internal node, with ratedU = EBAS × TR.
  • One equivalent per converter. RAW gives RC/XC per bridge on the valve side and does not say how the NB bridges' transformers are built (two 2-winding units or one 3-winding unit). Their AC sides are in parallel, so end 1 r, x = RC, XC / (NB × TR²) (ohm; converter_transformer_ohms). The exporter gets RC/XC back with NB = numberOfValves / 6 and TR = ratedU2 / ratedU1.
  • No ratedS (RAW gives none) and no magnetizing branch.
  • Tap: a RatioTapChanger <converter>_xf_tap1 on end 1, with ltcFlag true, built by ratio_tap (R4) over the STP grid from TMN (converter_tap).
  • stepVoltageIncrement is exactly STP. Step 1 is TMN; highStep is the last whole step at or below TMX. A third of the set's ends have a TMX - TMN that is not a whole number of STP steps, and their TMX is listed on the tap row.
  • neutralStep is the step nearest ratio 1, and the step comes from TAP (a float, since TAP is often off the grid).
  • No TapChangerControl: PSS/E moves TAP to hold the firing angle within ANMN..ANMX, and no CIM mode says that.

Profile requests

  • P2-R1 ACDCConverter.PccTerminal → Terminal: added by the user. It is the AC point a converter's targetUpcc refers to; 3 of the 4 VSC converters in the set name a remote bus.
  • P2-R2 VsCapabilityCurve as a Curve: added by the user. It holds MAXQ / MINQ.
  • P2-R3 qPercent on RegulatingCondEq: not taken. FACTS RMPCT stays a gap, as the switched shunt's does, and is listed on the row when it is not 100.

Atom tests/atoms/dc/facts_vsc.raw (hand-built)

Built on the R5 areas atom's buses and areas (3 areas): - FACTS: STATCOM-LOC, local FCREG; STATCOM-REM, FCREG 301 with TRMX 0 and RMPCT 75 (listed); STATCOM-OUT, MODE 0 with SHMX 0. - VSC-TIE: an area tie. Converter 1 is TYPE 2, MODE 1, with SMAX/IMAX and PWF 0.5; converter 2 is TYPE 1, MODE 2, with MINLOSS. - VSC-OUT: MDC 0. Converter 1 is MODE 1 with remote VSREG 201 and RMPCT 60; converter 2 is TYPE 0.

It survives a read → write → read losslessly and binds. Each value is checked in SI, and the raises are tested form by form (tests/test_raw_to_cimtbl.py, P2a).

Atom tests/atoms/dc/two_terminal.raw (hand-built)

On the same frame: - DC-TIE 102-201, an area tie: MDC 1, SETVL −250 (inverter power), METER I. The rectifier's TMX is off its STP grid. - DC-B2B 202-201: RDC 0, SETVL 150 (rectifier power), ICR 201 (listed). - DC-CURRENT 301-302: MDC 2, SETVL 1000 A, VCMOD 118.1. The inverter's EBAS is 120 kV, on a 115 kV bus. - DC-BLOCKED 101-102: MDC 0.

Every line has DELTI ≠ 0, which is listed. The atom survives a read → write → read losslessly and binds, with values checked in SI and its raises tested (tests/test_raw_to_cimtbl.py, P2b).

Field classification (samples from the P2a atom):

FactsDeviceRecord field type samples kind target
name str STATCOM-LOC, STATCOM-OUT, STATCOM-REM structural NAME: the key, mRID fd_ (control fdc_), name NAME
ibus int 202, 102, 302 structural I: the device's bus, BaseVoltage and EquipmentContainer (its substation)
jbus Optional[int] 0 structural J: 0 is a shunt-only device; nonzero (a series element: SSSC, UPFC, IPFC) raises
mode Optional[int] 1, 0 mapped MODE: inService = (MODE == 1); 2..8 need J != 0; blank: 1 (defaulted)
pdes Optional[float] 0.0 untranscribed PDES: the series element's; a shunt-only device does not use it: listed on the row when not the default
qdes Optional[float] 0.0 untranscribed QDES: the series element's; a shunt-only device does not use it: listed on the row when not the default
vset Optional[float] 1.02, 1.0, 1.01 derived VSET (pu): the control's targetValue = VSET x BASKV(FCREG), in V (volts_from_per_unit); blank: 1.0 (defaulted)
shmx Optional[float] 100.0, 0.0, 50.0 derived SHMX (MVA at unity voltage): ratedI = SHMX / (sqrt(3) x BASKV(I)) kA (ka_from_rating); 0 (no shunt) stays 0; blank: 9999 (defaulted)
trmx Optional[float] 9999.0, 0.0 untranscribed TRMX: the series element's; a shunt-only device does not use it: listed on the row when not the default
vtmn Optional[float] 0.9 untranscribed VTMN: the series element's; a shunt-only device does not use it: listed on the row when not the default
vtmx Optional[float] 1.1 untranscribed VTMX: the series element's; a shunt-only device does not use it: listed on the row when not the default
vsmx Optional[float] 1.0 untranscribed VSMX: the series element's; a shunt-only device does not use it: listed on the row when not the default
imx Optional[float] 0.0 untranscribed IMX: the series element's; a shunt-only device does not use it: listed on the row when not the default
linx Optional[float] 0.05 untranscribed LINX: the series element's; a shunt-only device does not use it: listed on the row when not the default
rmpct Optional[float] 100.0, 75.0 untranscribed RMPCT: a shunt's share of a coordinated voltage control has no CIM home (qPercent is SynchronousMachine's; CIM 18 gap); listed when not 100
owner Optional[int] 1 untranscribed OWNER: ownership is an asset concept (CIM 18 gap)
set1 Optional[float] 0.0 untranscribed SET1: the series element's; a shunt-only device does not use it: listed on the row when not the default
set2 Optional[float] 0.0 untranscribed SET2: the series element's; a shunt-only device does not use it: listed on the row when not the default
vsref Optional[int] 0 untranscribed VSREF: the series element's; a shunt-only device does not use it: listed on the row when not the default
remot Optional[int] 0, 301 structural FCREG: the control's Terminal bb_T1, or bb_T1 when 0 (RAW-11), or the NREG node's busbar; blank: 0 (defaulted)
mname Optional[str] untranscribed MNAME: the series element's; a shunt-only device does not use it: listed on the row when not the default
nreg Optional[int] 0 structural NREG: a node of bus FCREG; nonzero: the control's Terminal is that node's busbar bb_s_n_T1 (R6, RAW-11); blank: 0 (defaulted)
VscDcRecord field type samples kind target
name Union[str, VscDcRecordName] VSC-OUT, VSC-TIE structural NAME: the key; DCLine vsc_, its segment, nodes and converters
rdc float 16.0, 1.58 copied DCLineSegment.resistance (ohm); RDC
ibus_1 int 202, 102 structural IBUS (converter 1): VsConverter vsc__c1 on this bus, its BaseVoltage and EquipmentContainer (its substation)
converter_type_1 int 1, 2 mapped TYPE (converter 1): 0 inService false, 1 pPccControl udc, 2 pPccControl pPcc; on a tie the TYPE 1 converter is the home end (R5)
dcset_1 float 450.0, 96.0 derived DCSET (converter 1): TYPE 1 targetUdc (kV); TYPE 2 targetPpcc = -DCSET (MW: RAW's + feeds the AC network, CIM's load sign); TYPE 0 listed
ibus_2 int 201, 202 structural IBUS (converter 2): VsConverter vsc__c2 on this bus, its BaseVoltage and EquipmentContainer (its substation)
converter_type_2 int 0, 1 mapped TYPE (converter 2): 0 inService false, 1 pPccControl udc, 2 pPccControl pPcc; on a tie the TYPE 1 converter is the home end (R5)
dcset_2 float 100.0, 300.0 derived DCSET (converter 2): TYPE 1 targetUdc (kV); TYPE 2 targetPpcc = -DCSET (MW: RAW's + feeds the AC network, CIM's load sign); TYPE 0 listed
mdc Optional[int] 0, 1 mapped MDC: inService = (MDC == 1) on the segment and both converters; blank: 1 (defaulted)
o1 Optional[int] 1 untranscribed ownership is an asset concept (CIM 18 gap)
f1 Optional[float] 1.0 untranscribed ownership is an asset concept (CIM 18 gap)
o2 Optional[int] 0 untranscribed ownership is an asset concept (CIM 18 gap)
f2 Optional[float] 1.0 untranscribed ownership is an asset concept (CIM 18 gap)
o3 Optional[int] 0 untranscribed ownership is an asset concept (CIM 18 gap)
f3 Optional[float] 1.0 untranscribed ownership is an asset concept (CIM 18 gap)
o4 Optional[int] 0 untranscribed ownership is an asset concept (CIM 18 gap)
f4 Optional[float] 1.0 untranscribed ownership is an asset concept (CIM 18 gap)
mode_1 Optional[int] 1 mapped MODE (converter 1): 1 qPccControl voltagePcc, 2 qPccControl powerFactorPcc; blank: 1 (defaulted)
acset_1 Optional[float] 1.0, 1.02 derived ACSET (converter 1): MODE 1 targetUpcc = ACSET x BASKV(VSREG or IBUS) (kv_from_per_unit); MODE 2 targetPowerFactorPcc = ACSET; blank: 1.0 (defaulted)
aloss_1 Optional[float] 0.0, 1600.0 copied VsConverter.idleLoss (kW); ALOSS (converter 1); blank: 0 (defaulted)
bloss_1 Optional[float] 0.0, 3.4 copied VsConverter.switchingLoss (kW/A); BLOSS (converter 1): loss = ALOSS + Idc x BLOSS; blank: 0 (defaulted)
minloss_1 Optional[float] 0.0 untranscribed MINLOSS (converter 1): no CIM home (CIM 18 gap); listed when not 0
smax_1 Optional[float] 0.0, 360.0 structural SMAX (converter 1): ApparentPowerLimit _smax (MVA) in the set _ratings on its T1, typed RATE1; 0 (unlimited) writes no limit
imax_1 Optional[float] 0.0, 1032.0 structural IMAX (converter 1): CurrentLimit _imax (A), as SMAX
pwf_1 Optional[float] 1.0, 0.5 untranscribed PWF (converter 1): no CIM home (CIM 18 gap); listed when not 1.0
maxq_1 Optional[float] 50.0, 200.0 copied CurveData.y2value (MVAr); MAXQ (converter 1): MODE 1: the VsCapabilityCurve _qcurve's one point (P 0, constantYValue), y2 = MAXQ (MVAr); MODE 2 does not use it (listed when not the default)
minq_1 Optional[float] -50.0, -100.0 copied CurveData.y1value (MVAr); MINQ (converter 1): as MAXQ, y1 = MINQ
vsreg_1 Optional[int] 201, 0 structural VSREG (converter 1): MODE 1: PccTerminal bb_T1, or bbT1 when 0 (RAW-11), or the NREG node's busbar; MODE 2: bb_T1
rmpct_1 Optional[float] 60.0, 100.0 copied VsConverter.qShare; RMPCT (converter 1); blank: 100 (defaulted)
nreg_1 Optional[int] 0 structural NREG (converter 1): a node of bus VSREG; nonzero: PccTerminal is that node's busbar bb_s_n_T1 (R6)
mode_2 Optional[int] 1, 2 mapped MODE (converter 2): 1 qPccControl voltagePcc, 2 qPccControl powerFactorPcc; blank: 1 (defaulted)
acset_2 Optional[float] 1.0, 0.95 derived ACSET (converter 2): MODE 1 targetUpcc = ACSET x BASKV(VSREG or IBUS) (kv_from_per_unit); MODE 2 targetPowerFactorPcc = ACSET; blank: 1.0 (defaulted)
aloss_2 Optional[float] 0.0, 615.0 copied VsConverter.idleLoss (kW); ALOSS (converter 2); blank: 0 (defaulted)
bloss_2 Optional[float] 0.0, 2.527 copied VsConverter.switchingLoss (kW/A); BLOSS (converter 2): loss = ALOSS + Idc x BLOSS; blank: 0 (defaulted)
minloss_2 Optional[float] 0.0, 1110.0 untranscribed MINLOSS (converter 2): no CIM home (CIM 18 gap); listed when not 0
smax_2 Optional[float] 0.0 structural SMAX (converter 2): ApparentPowerLimit _smax (MVA) in the set _ratings on its T1, typed RATE1; 0 (unlimited) writes no limit
imax_2 Optional[float] 0.0 structural IMAX (converter 2): CurrentLimit _imax (A), as SMAX
pwf_2 Optional[float] 1.0 untranscribed PWF (converter 2): no CIM home (CIM 18 gap); listed when not 1.0
maxq_2 Optional[float] 9999.0 copied CurveData.y2value (MVAr); MAXQ (converter 2): MODE 1: the VsCapabilityCurve _qcurve's one point (P 0, constantYValue), y2 = MAXQ (MVAr); MODE 2 does not use it (listed when not the default)
minq_2 Optional[float] -9999.0 copied CurveData.y1value (MVAr); MINQ (converter 2): as MAXQ, y1 = MINQ
vsreg_2 Optional[int] 0 structural VSREG (converter 2): MODE 1: PccTerminal bb_T1, or bbT1 when 0 (RAW-11), or the NREG node's busbar; MODE 2: bb_T1
rmpct_2 Optional[float] 100.0 copied VsConverter.qShare; RMPCT (converter 2); blank: 100 (defaulted)
nreg_2 Optional[int] 0 structural NREG (converter 2): a node of bus VSREG; nonzero: PccTerminal is that node's busbar bb_s_n_T1 (R6)

Two-terminal DC field classification (samples from the P2b atom):

TwoTerminalDCRecord field type samples kind target
name Union[str, TwoTerminalDCRecordName] DC-B2B, DC-BLOCKED, DC-CURRENT structural NAME: the key; DCLine dc2_, its segment, nodes, converters and their transformers
rdc float 0.0, 15.4, 1.78 copied DCLineSegment.resistance (ohm); RDC; 0 is still a segment
setvl float 150.0, -413.1, 1000.0 derived SETVL: MDC 1 targetPpcc (MW, load sign as given): > 0 on the rectifier, < 0 on the inverter; MDC 2 the rectifier's targetIdc (A); MDC 0 listed (its unit depends on the MDC it was blocked from)
vschd float 80.0, 450.0, 150.0 copied CsConverter.targetUdc (kV); VSCHD: the inverter's targetUdc, pPccControl dcVoltage
ipr int 202, 101, 301 structural IPR: the rectifier's AC bus: end 1 of its converter transformer dc2_r_xf, its substation; the CsConverter dc2r sits on the internal node dc2_r_int
nbr int 2 derived NBR: numberOfValves = 6 x NB; the transformer's r, x divide by NB (converter_transformer_ohms)
anmxr float 17.0, 21.0, 24.0 copied CsConverter.maxAlpha (deg); ANMXR
anmnr float 13.0, 15.0, 22.0 copied CsConverter.minAlpha (deg); ANMNR
rcr float 0.0, 0.042, 0.012 derived RCR (ohm per bridge, valve side): end 1 r = RC / (NB x TR^2) (converter_transformer_ohms)
xcr float 1.779, 2.796, 2.1202 derived XCR: end 1 x, as RC
ebasr float 230.0 copied PowerTransformerEnd.ratedU (kV); EBASR: end 1 ratedU; end 2 ratedU = EBAS x TR (valve side), the internal node's BaseVoltage
ipi int 201, 102, 302 structural IPI: the inverter's AC bus: end 1 of its converter transformer dc2_i_xf, its substation; the CsConverter dc2i sits on the internal node dc2_i_int
nbi int 2 derived NBI: numberOfValves = 6 x NB; the transformer's r, x divide by NB (converter_transformer_ohms)
anmxi float 18.0, 21.0, 29.0 copied CsConverter.maxGamma (deg); ANMXI
anmni float 15.0, 18.0, 25.0 copied CsConverter.minGamma (deg); ANMNI
rci float 0.0, 0.042, 0.012 derived RCI (ohm per bridge, valve side): end 1 r = RC / (NB x TR^2) (converter_transformer_ohms)
xci float 1.779, 2.796, 2.1197 derived XCI: end 1 x, as RC
ebasi float 230.0, 120.0 copied PowerTransformerEnd.ratedU (kV); EBASI: end 1 ratedU; end 2 ratedU = EBAS x TR (valve side), the internal node's BaseVoltage
mdc Optional[int] 1, 0, 2 mapped MDC: 0 blocked (inService false on the segment and both converters), 1 the rectifier's pPccControl activePower, 2 dcCurrent; blank: 0 (defaulted)
vcmod Optional[float] 0.0, 118.1 untranscribed VCMOD: no CIM home (CIM 18 gap); listed on the DCLine row when not the default
rcomp Optional[float] 0.0 untranscribed RCOMP: no CIM home (CIM 18 gap); listed on the DCLine row when not the default (0 puts the compounding point at the inverter)
delti Optional[float] 0.1, 0.17, 0.15 untranscribed DELTI: no CIM home (CIM 18 gap); listed on the DCLine row when not the default
meter Optional[str] R, I structural METER: on a tie, the metered converter (R rectifier, I inverter); the other is the home end (R5); blank: I (defaulted)
dcvmin Optional[float] 0.0 untranscribed DCVMIN: no CIM home (CIM 18 gap); listed on the DCLine row when not the default
cccitmx Optional[int] 20 untranscribed CCCITMX: no CIM home (CIM 18 gap); listed on the DCLine row when not the default
cccacc Optional[float] 1.0 untranscribed CCCACC: no CIM home (CIM 18 gap); listed on the DCLine row when not the default
trr Optional[float] 0.1905, 1.0, 0.3143 derived TRR: end 2 ratedU = EBAS x TR; blank: 1.0 (defaulted)
tapr Optional[float] 1.0, 1.09, 1.024 derived TAPR: the RatioTapChanger dc2__r_xf_tap1 on end 1: step from TAP over the STP grid from TMN (converter_tap), ltcFlag true; PSS/E adjusts it to hold the firing angle in range, which no TapChangerControl mode says; blank: 1.0 (defaulted)
tmxr Optional[float] 1.06, 1.12, 1.1875 derived TMXR: highStep = the last whole STP step at or below TMX; a TMX off the grid is listed on the tap row; blank: 1.5 (defaulted)
tmnr Optional[float] 0.94, 0.88, 0.9375 derived TMNR: step 1; blank: 0.51 (defaulted)
stpr Optional[float] 0.012, 0.005, 0.0125 derived STPR: stepVoltageIncrement = STP in percent of EBAS; blank: 0.00625 (defaulted)
icr Optional[int] 201, 0 untranscribed ICR: the firing-angle measuring bus has no CIM home (CIM 18 gap); listed on the converter row when not 0
ifr Optional[int] 0 structural IFR: nonzero (an AC transformer as the converter transformer, COD +-4) raises
itr Optional[int] 0 structural ITR: as IFR
idr Optional[str] 1 untranscribed IDR: used only with IFR / ITR, which raise
xcapr Optional[float] 0.0 structural XCAPR: nonzero (capacitor commutated) raises
ndr Optional[int] 0 untranscribed NDR: a node of ICR, as ICR
tri Optional[float] 0.1905, 1.0, 0.529 derived TRI: end 2 ratedU = EBAS x TR; blank: 1.0 (defaulted)
tapi Optional[float] 1.0, 1.01, 0.9875 derived TAPI: the RatioTapChanger dc2__i_xf_tap1 on end 1: step from TAP over the STP grid from TMN (converter_tap), ltcFlag true; PSS/E adjusts it to hold the firing angle in range, which no TapChangerControl mode says; blank: 1.0 (defaulted)
tmxi Optional[float] 1.06, 1.12, 1.0875 derived TMXI: highStep = the last whole STP step at or below TMX; a TMX off the grid is listed on the tap row; blank: 1.5 (defaulted)
tmni Optional[float] 0.94, 0.88, 0.925 derived TMNI: step 1; blank: 0.51 (defaulted)
stpi Optional[float] 0.012, 0.005, 0.0125 derived STPI: stepVoltageIncrement = STP in percent of EBAS; blank: 0.00625 (defaulted)
ici Optional[int] 0 untranscribed ICI: the firing-angle measuring bus has no CIM home (CIM 18 gap); listed on the converter row when not 0
ifi Optional[int] 0 structural IFI: nonzero (an AC transformer as the converter transformer, COD +-4) raises
iti Optional[int] 0 structural ITI: as IFI
idi Optional[str] 1 untranscribed IDI: used only with IFI / ITI, which raise
xcapi Optional[float] 0.0 structural XCAPI: nonzero (capacitor commutated) raises
ndi Optional[int] 0 untranscribed NDI: a node of ICI, as ICI

Expected export differences

  • A listed field comes back from its row note only if the exporter reads notes; otherwise it comes back as the default.
  • A MODE 2 converter's unused VSREG, NREG, MAXQ and MINQ come back the same way.
  • A TYPE 0 converter's DCSET comes back the same way.
  • P2b: SETVL of a blocked line comes back from its row note, and no MDC beyond 0 is recovered. RC/XC come back exactly from r, x, NB and TR. A TMX off the STP grid comes back from its note, or else as the grid's top.

CIM 18 gaps (in the register and the table under CIM 18 gaps)

  • A FACTS device's series element, UPFC and IPFC (no class; SSSC has StaticSynchronousSeriesCompensator).
  • VSC MINLOSS and PWF.
  • Two-terminal VCMOD, DELTI, RCOMP, DCVMIN, CCCITMX, CCCACC and ICR.
  • RMPCT of a FACTS shunt (P2-R3 not taken).

Owner

No artifact. The Owner table and every owner field on other records (bus OWNER, O1/F1..O4/F4) are untranscribed: CIM keeps ownership in asset management (CIM 18 gap). The master comment counts the owners.

OwnerRecord field type samples kind target
owner_number Union[int, OwnerRecordOwnerNumber] 1 untranscribed ownership is an asset concept (CIM 18 gap); no owner.cimtbl is written
owner_name Optional[str] 1, OWNER1 untranscribed as I

Code tables

IDE and IC are checked in the mapper (above). They are not CIM enums.

STYPE (R1) class
1 generic connector Switch
2 circuit breaker Breaker
3 disconnect switch Disconnector
blank or other raises

MODSW (R2): the table in Switched shunt. WMOD (R3): the table in Generator. CZ, CM and COD (R4): the tables in Transformer; CW is winding_unit_kv (1 pu of BASKV, 2 kV, 3 pu of NOMV).

CIM 18 gaps

Each is logged in the shared register (CIMTBL-Models/distribution/CIM18_GAPS.md) and in the plan's §6a:

gap RAW fields R0 approximation
zone membership of a bus ZONE substations never span two zones
a bus's own control area, and the area slack (equipment is covered: ControlAreaGeneratingUnit, LoadGroup → SubLoadArea, TieFlow) bus AREA, area ISW bus AREA traced on export from generating units and tie flows (R5), a bus the trace cannot reach listed untranscribed: area=; ISW untranscribed
area/zone of machines and DC equipment; zone of a load (the SubLoadArea → LoadArea hierarchy was added to the profile 2026-11-08) induction machine, MTDC bus AREA/ZONE; load ZONE ≠ bus ZONE loads in LoadArea ⊃ SubLoadArea per (area, zone) (R2); the rest untranscribed
ownership of network equipment Owner, OWNER, O1..F4 untranscribed
the metered (loss-allocation) end of a branch (R1) branch, switch and multi-section line MET; transformer NMETR (R4) on a tie, recorded by its TieFlows' terminal (R5); elsewhere, and multi-section line MET, untranscribed
a scheduled transfer between two control areas (R5; cim17v40's InterchangeSchedule is gone, TieCorridor has no schedule) inter-area transfer ARFROM, ARTO, TRID, PTRAN listed on the ControlArea table comment
a shunt switched with its line, in a bus-branch model (R1) branch GI/BI/GJ/BJ a LinearShuntCompensator per end, linked by its mRID only; in a node-breaker substation it sits on its line end's node (R6)
a node's in-service status (R6; a ConnectivityNode has no inService) substation node STATUS 0 listed on the node row (untranscribed: status=0)
a substation's DC grounding resistance, for GIC studies (R6) substation SGR untranscribed
a solved voltage per node of a split bus (R6; SvVoltage attaches only to a TopologicalNode) substation node VM, VA listed on the node row when given
a shunt's or converter's share of a coordinated voltage control (R2, R3) switched shunt RMPCT; generator RMPCT on WMOD 1, 2, 3 untranscribed; on a connection, listed when not 100 (R3c-3)
a converter's reactive limits that follow its active power (R3c) generator WPF on WMOD 2 QT/QB as written; WPF always listed on the row
the kind of a renewable bus-branch generator: PV, wind, or an induction machine (R3) generator WMOD 1, 2, 3 a PowerElectronicsConnection + PowerElectronicsUnit (no kind)
a machine's positive-sequence reactance: TODO, a profile extension (R3) generator ZX untranscribed
which side of a voltage-controlling winding its controlled bus is on (R4b) transformer CONTk's sign |CONT| regulated; the sign listed on the control row
a FACTS device's series element; UPFC and IPFC have no class (P2a) FACTS J ≠ 0, MODE 2..8 raises (none in a case yet); a shunt-only device's series fields are listed when not the default
a FACTS shunt's share of a coordinated voltage control (P2a) FACTS RMPCT listed on the row when not 100
a VSC converter's minimum loss and its power weighting factor (P2a) VSC MINLOSS, PWF listed on the row when not the default
a two-terminal line's mode-switch voltage, margin, compounding, minimum DC voltage, CCC solution settings and commutating bus; its tap control's aim (hold the firing angle) (P2b) VCMOD, DELTI, RCOMP, DCVMIN, CCCITMX, CCCACC, ICR, NDR; TAP's control listed on the DCLine / converter row when not the default; the tap has no TapChangerControl

Not gaps: a bus's voltage limits and its regulation sit on its BusbarSection's terminal. CIM puts limits and regulating controls on terminals by design (RAW-11, RAW-19). RAW not saying which nodes are busbars is a gap in RAW, not CIM: R6 adds a BusbarSection only where a control regulates a node.

Decisions this spec applies

  • RAW-14 (user, 2026-11-08): VM/VA → SvVoltage; generator PG/QG → RotatingMachine.p/q (R3).
  • RAW-17 (recommended): a blank BASFRQ → 60 Hz, defaulted.
  • RAW-18 (recommended): bare bus numbers as node mRIDs, per the translate table (the shape example writes bus_<I>; request C2).
  • RAW-19 (user, 2026-11-08): a BusbarSection per bus; voltage limits in kV on its terminal.
  • R1 (user, 2026-11-08): RAW-9 (rating sets, NXFRAT), RAW-12 (multi-section Line with Update rows), RAW-13 (line shunts as ordinary shunts), RAW-20 (one rating set on terminal 1), RAW-21 (LEN in km), RAW-22 (MET untranscribed, a gap).
  • R2 (user, 2026-11-08): RAW-8 (loads: SCALE → Conform/NonConformLoad; LoadArea ⊃ SubLoadArea per (area, zone)); RAW-10 (a switched shunt's blocks as one LinearShuntCompensator each, under one RegulatingControl).
  • R3 (user, 2026-11-08): RAW-7 (one RegulatingControl per plant), RAW-23 (referencePriority and qPercent added to the profile; ZX a TODO extension), RAW-24 (WMOD 0 a SynchronousMachine, WMOD 1 a PowerElectronicsConnection), RAW-25 (an implicit step-up transformer raised; the builder shape a TODO for an owner).
  • R3b (user, 2026-11-09): R3b-1..R3b-5 (an implicit step-up is the core shape behind_transformer.cimtbl: the machine on an internal node at bus I's base behind an R4-form 2-winding transformer, GTAP a fixed tap on end 1; PG and QG as written on the machine).
  • R3c (user, 2026-11-09): R3c-1..R3c-3 (WMOD 2 a WMOD 1 connection with its WPF always listed; a WMOD 3 plant a powerFactor control on its connection's terminal, targetValue = WPF signed; a connection's ZR and RMPCT listed off their defaults).
  • R4 (user, 2026-11-08): RAW-5 (every CZ/CM code derived to ohm/S; a 2-winding r/x/g/b on end 1; a 3-winding unit's Z12/Z23/Z31 as TransformerMeshImpedance rows with g/b on end 1, no star conversion; cim18v17 has no TransformerStarImpedance/TransformerStarAdmittance); RAW-6 (a RatioTapChanger per tapped winding over steps 1..NTP, neutralStep nearest ratio 1 at an exact neutralU; COD 0/±1/±2 mapped, ±3/±4/±5 raise; CONT 0 names the winding's own terminal).
  • R4b (user, 2026-11-09): angles in CIM's sign (cim_angle; PowerTransformerEnd.phaseShift added to the profile with the PhaseTapChanger sign); fixed shifts on phaseShift, never windingConfiguration; COD ±3 a PhaseTapChangerLinear over NTP steps with an activePower control; fixed ratios as one-step RatioTapChangers; an out-of-range controlled WINDV extends the steps; STAT 2/3/4 a disconnected terminal; CONT 0 the own terminal, a negative CONT's sign listed; CR/CX as lineDropR/lineDropX; impedance tables as ImpedanceTapChangerTable
  • ImpedanceTapChangerTabular (its TransformerEnd link added to the profile).
  • R5 (user, 2026-11-08): RAW-2's open part (a bus's AREA traced on export from generating units and tie flows; no profile extension); tie flows as a pair on each tie's metered terminal; inter-area transfers listed untranscribed (no profile class); netInterchange = -PDES.
  • R6 (user, 2026-11-09): RAW-16 (a mixed model loads through cimtables as it is: node1 + bus1, and Update rows on Terminals); a SUBSTATION block's substation takes precedence over the §3.2 merge; LATI = LONG = 0 writes no Location; a BusbarSection only on a node a control regulates (RAW-11), none inferred from the layout; node STATUS 0 listed on its row; B and 2 one terminal form, as the format document has it.

Reference model and expected differences

The golden artifact directory is IEEE14's (tests/goldens/IEEE14/), generated by the orchestrator and reviewed by hand. WECC240 is the bind and round-trip case.

There is no hand translation to differ from. The earlier CIMHub RAW converter differs by design: - it made one VoltageLevel per bus; - it read none of the transformer controls past RATE1-12, and replaced them with schema defaults (§reader); - it lost 1e-7 values on writing.

Expected export differences from R5: - MET, METERED and NMETR of a device inside one area come back as their defaults (1, 1, 2); - a bus the trace cannot reach (listed untranscribed: area=) needs the exporter's rule (slice E); - inter-area transfers and ISW are lost.

Expected export differences from R6: SGR comes back as 0.1; a node's STATUS 0 as 1 and its VM/VA as the defaults; an equipment terminal record with NI = 0 is not written back; a B/2 record comes back as 2 for a transformer and B for a branch; a substation switching device's X as 0.0001.