Import: RAW to CIM¶
from cimhub_raw.importer.raw_to_cimtbl import raw_to_cim
from cimhub_raw.raw34_reader import Raw34Reader
model = Raw34Reader("cimhub_raw/tests/cases/IEEE14/IEEE_14_bus.raw").read_all()
network = raw_to_cim(model, name="IEEE14", artifact_dir="artifacts/IEEE14")
network is a cim18v17 cim-graph BusBranchModel. artifact_dir keeps the .cimtbl text it was built from.
What happens¶
Raw34Reader(path).read_all()parses the.rawand returns aGraphModelof typed records, one class per RAW table.RawImporter(name).to_cimtbl(model)works out the case-wide facts once (the system base, each bus's zone, area and base voltage, the substations), then runs one mapper per RAW table. Each mapper turns records into a.cimtbldocument. It does not build CIM objects.raw_to_cimwrites the documents and cimtables binds them into a network.
The .cimtbl text is the only input to CIM. If a value is wrong in the network, it is wrong in the text, and you can
read it there.
Reading a .raw¶
Raw34Reader(source) takes the path of the .raw. read_all() reads the file once and returns the same model on
later calls. It raises FileNotFoundError if the file is missing, Raw34ParseError for anything it cannot read as
v34, and NotImplementedError for a populated multi-terminal DC or GNE section.
The file is read by position, in the order RAW v34 fixes:
| Part of the file | What the reader does |
|---|---|
| first line | IC, SBASE, REV, XFRRAT, NXFRAT, BASFRQ. A REV other than 34 raises: REV is 33.0; this reader reads RAW v34 only |
| two title lines | Kept as written, in titles |
| system-wide data | GENERAL, GAUSS, NEWTON, ADJUST, TYSL and SOLVER records are kept as text, each at most once. A RATING record names a rating set. Any other keyword raises: unknown system-wide data record 'SOLVERX' |
| sections | Bus, load, fixed shunt, generator, branch, system switching device, transformer, area, two-terminal DC, VSC DC line, impedance correction, multi-terminal DC, multi-section line, zone, inter-area transfer, owner, FACTS device, switched shunt, GNE and induction machine, then the substation section. Each ends with a record whose first field is 0; the text after it (/ END OF BUS DATA, BEGIN LOAD DATA) is a comment |
| substation section | One block per substation: its record, its nodes, its switching devices, its equipment terminals, each part ended by its own 0 record |
Q |
Ends the data. Every later section is empty |
Rules that matter when a case does not read as you expect:
- Fields are separated by a comma or by blanks. Two commas in a row leave a field blank, and a record may stop
early. A blank or missing field is
Nonein the record. - Comments. A line that starts with
@!is skipped. An unquoted/starts a comment that runs to the end of the line. A quoted field may hold commas, blanks and slashes. - Names lose their trailing blanks. A bus is
'BUS 1 'in the file andBUS 1in the record. - Extended bus names. A quoted value in an integer field is an extended bus name,
'NAME kV': the 12-character bus name, then its base kV. The reader resolves it to the bus number, so every bus reference in the model is a number. A leading-gives the negated number. A name that matches no bus, or two, raises. - Keys. Every record has a key built from its own fields, for example
10_1for the load with ID1on bus 10. A second record with the same key raises:duplicate BranchRecord '1_2_1' (first on line <n>). - A parse error names the file and line, and shows the line:
case.raw:2: REV is 33.0; this reader reads RAW v34 only. - Multi-terminal DC and GNE. A case that has records in either section raises
NotImplementedErroras soon as it is read. Induction machine records are read, but the importer raises on them (below).
The reader does not fill defaults. A blank field stays None in the record, and the importer fills it from the schema's
default when it maps the record.
Options¶
raw_to_cim(model, *, name, authority=..., network=None, artifact_dir=None).
RawImporter(name, *, authority=...) takes the same keywords except network and artifact_dir, which go to its
to_cim method.
| Argument | Meaning |
|---|---|
name |
Required. The master document's Model and file stem, and the name of the case's GeographicalRegion (its mRID is rgn_ and the name in lower case). Do not use the name of a part file (bus, load, zone, ...): document names must be distinct, so the importer raises document names repeat: ['bus']. |
artifact_dir |
Keep the .cimtbl files here. Without it they go to a temporary directory that is removed after loading. |
network |
An existing cim18v17 network to bind onto, to merge several models. |
authority |
The master's Authority. Defaults to https://github.com/PNNL-CIM-Tools/CIMHub. |
To get the documents without binding them, call RawImporter(name).to_cimtbl(model). It returns a DocumentSet with a
master and a list of parts, and touches no files.
The artifacts¶
artifact_dir holds the master, <name>.cimtbl, and one file per RAW table the case has records in. A table with no
records writes no file and no Import. The master Imports the files in this order, so that a catalog comes before
what uses it. The IEEE 14-bus case writes zone, area_interchange, bus, branch, load, fixed_shunt,
generator and transformer.
| Part file | From |
|---|---|
zone.cimtbl |
zone records (and a zone a bus names that has no record) |
area_interchange.cimtbl |
area records, with the inter-area transfers listed in a comment |
bus.cimtbl |
buses: substations, nodes, busbars, voltage limits, solved voltages |
substation.cimtbl |
SUBSTATION blocks: nodes, switching devices |
branch.cimtbl |
non-transformer branches, series capacitors, line shunts |
switch.cimtbl |
system switching devices |
multi_section_line.cimtbl |
multi-section lines |
load.cimtbl |
loads |
fixed_shunt.cimtbl |
fixed shunts |
generator.cimtbl |
generators, with their plant controls and step-up transformers |
impedance_correction.cimtbl |
impedance correction tables |
transformer.cimtbl |
two- and three-winding transformers |
two_terminal_dc.cimtbl |
two-terminal DC lines |
vsc_dc.cimtbl |
VSC DC lines |
facts_device.cimtbl |
FACTS devices |
switched_shunt.cimtbl |
switched shunts. It follows the generators and FACTS devices because a shunt can regulate their reactive power |
equipment_terminal.cimtbl |
equipment terminals of the SUBSTATION blocks. It comes last, after every equipment file |
Owner records have no file: CIM 18 has no home for them, and the master's comment lists their count
(untranscribed: Owner 1).
Read the files the way you would a table. This is the head of IEEE 14's branch.cimtbl:
Table ACLineSegment: mRID, name, bus1, bus2, r (pu system), x (pu system), bch (pu system), length (km), inService, BaseVoltage, EquipmentContainer
ln_1_2_1, 1_2_1, 1, 2, 0.01938, 0.05917, 0.0528, , true, bv_138kv,
ln_1_5_1, 1_5_1, 1, 5, 0.05403, 0.22304, 0.0492, , true, bv_138kv,
A comment above a table lists what the importer left out (# untranscribed: o1, f1, ...) and above a row what it
defaulted (# defaulted: wmod=0, wpf=1.0, nreg=0). The master's comment lists every RAW class no mapper reads, as
not mapped: <class> <count>, so nothing disappears silently.
The system base¶
The master's first object is BasePower, copied from SBASE in MVA. Every column headed (pu system) is a value copied
in per unit on that base, and cimtables converts it to ohms or siemens when it binds the network. The importer does no unit
arithmetic. A blank SBASE is 100 MVA, and the master says so: defaulted: SBASE=100.
| Master object | From |
|---|---|
BasePower |
SBASE |
BaseFrequency |
BASFRQ. A blank is 60 Hz, marked defaulted: BASFRQ=60 |
GeographicalRegion |
the case: its name is name |
BaseVoltage |
one per distinct BASKV, highest first, named like bv_138kv and bv_13p8kv |
OperationalLimitType |
the four bus voltage-limit types, then the twelve rating sets olt_rate1 to olt_rate12, named by the RATING records (else RATE1, RATING SET 1) |
NXFRAT and XFRRAT say what a branch's and a transformer's RATEn are: at 0 or below, MVA (an ApparentPowerLimit); above 0,
a current expressed as MVA (a CurrentLimit in kA). A blank is MVA, and the master says defaulted: NXFRAT=0 or
defaulted: XFRRAT=0.
Buses, substations and node-breaker data¶
Every bus is a TopologicalNode whose mRID is its bus number and whose name is its NAME, with a BusbarSection that holds its voltage limits and its
solved voltage (VM times BASKV, and VA). Every bus is also in a Substation. Buses that equipment inside a substation
joins share one, never across a zone boundary:
- every system switching device;
- a zero-impedance branch, R = 0 and |X| at most THRSHZ (from the
GENERALrecord, default 0.0001); - a branch whose CKT starts with
@or*; - a series capacitor, X below 0;
- every transformer, all of its windings' buses.
The substation is named sub_ and its lowest bus number. IEEE 14 has 11 substations, two of them of several buses:
4, 7 and 9, and 5 and 6. Its bus.cimtbl lists the buses and the equipment that merged them.
A SUBSTATION block (node-breaker data) takes precedence. It joins every bus its nodes name into one substation sub_s<IS>,
and each node is a ConnectivityNode sub_s<IS>_n<NI> inside its bus's TopologicalNode. The block's switching devices
become Switch, Breaker or Disconnector by their type, and its equipment terminals place each piece of equipment on
a node. The IEEE 118 case has four such substations. A block that is split across two zones, a node on no bus, a node
number given twice in a block, or a bus in two blocks raises.
A bus's AREA has no place in CIM, so the importer records it through what CIM can hold: generating units and the tie
flows of equipment between two areas. A bus that no generator or tie reaches is listed on its row as
untranscribed: area=<AREA>, and its AREA comes back blank on export.
What raises¶
| Case holds | Result |
|---|---|
| IC other than 0 (a change case) | ValueError: only a base case maps |
| no buses | ValueError: the RAW model has no buses |
| a BASKV that is blank or 0 or below | ValueError: bus 1: BASKV=None is no base voltage |
| multi-terminal DC records | NotImplementedError from the reader |
| GNE device records | NotImplementedError from the reader |
| induction machine records | NotImplementedError from the importer: RAW InductionMachineRecord: 1 record(s), but the table is phase 2 and not mapped yet |
| a generator with WMOD 4 | NotImplementedError |
| a FACTS device with a series element (J other than 0) | NotImplementedError |
| a load or generator in an AREA with no area record | ValueError: AREA 5 has no area-interchange record |
| an unmapped code (a switching device with a blank or unknown STYPE, ...) | ValueError naming the record, the field and the known values |
| a series capacitor (X below 0) with B other than 0 | ValueError |
| a plant whose generators disagree on VS, IREG or RMPCT | ValueError naming both IDs |
| a generator with WMOD 3 that shares its bus with another generator record | NotImplementedError |
| a swing bus whose only generator records are converter-interfaced (WMOD 1 to 3) | ValueError |
| a remote IREG from a swing bus | ValueError |
| a multi-section line whose dummy buses do not have exactly two branches | ValueError |
| a two-terminal DC line whose IF/IT name an AC transformer, or with a commutating capacitor (XCAP) | NotImplementedError |
| a two-terminal DC line with no bridges (NB below 1) or no valve-side voltage (EBAS x TR not above 0) | ValueError |
Every message names the record, by its key, so you can find it in the file. The multi-terminal DC, GNE and induction machine tables are the only tables with no mapping at all. The conversion reference lists the rest of each table's rules, and What converts what each RAW table becomes.
A branch, transformer or other record that names a bus that is not in the case is not checked by the reader. Check your
case's references before you import it: the importer's first failure may be a bare KeyError on the bus number.