Transformers and impedance correction

Two- and three-winding transformers, with their windings, ratings, tap changers and controls, and the impedance correction tables that windings name. Field classes, the .cimtbl header conventions and the full table list are on the reference landing page.

RAW table CIM (cim18v17) Import (.cimtbl) Export module
Transformer PowerTransformer, a PowerTransformerEnd per winding, TransformerMeshImpedance (three windings) transformer.cimtbl exporter/transformer.py
Transformer tap data, COD 0, +-1, +-2 RatioTapChanger + TapChangerControl transformer.cimtbl exporter/transformer.py
Transformer tap data, COD +-3 PhaseTapChangerLinear + TapChangerControl (mode activePower) transformer.cimtbl exporter/transformer.py
ANG PowerTransformerEnd.phaseShift transformer.cimtbl exporter/transformer.py
RATEk-1..RATEk-12 OperationalLimitSet per winding transformer.cimtbl exporter/transformer.py, exporter/ratings.py
Impedance correction ImpedanceTapChangerTable + ImpedanceTapChangerTablePoint; ImpedanceTapChangerTabular per winding impedance_correction.cimtbl, transformer.cimtbl exporter/impedance_correction.py

The CIM 18 transformer model has no star impedance, so a two-winding unit keeps r, x, g and b on end 1 and a three-winding unit keeps its three pair impedances as a mesh. The core getter the exporter reads is get_transformer_model, with get_tap_changer_control, get_tap_steps, get_tap_voltage, get_phase_tap_steps and get_impedance_table; see the core transformers reference and shapes page. Generator step-up transformers belong to Generators and DC converter transformers to DC lines and FACTS devices; the transformer exporter skips both.

Try it

from cimhub_raw.raw34_reader import Raw34Reader
from cimhub_raw.importer.raw_to_cimtbl import raw_to_cim
from cimhub_raw.exporter.cim_to_raw import RawExporter
import cimhub_raw.schema.raw_v34.raw34_schema as schema

model = Raw34Reader("cimhub_raw/tests/atoms/transformer/forms_r4b.raw").read_all()
network = raw_to_cim(model, name="forms_r4b", artifact_dir="/tmp/raw-transformers")  # transformer.cimtbl, ...
back = RawExporter().to_model(network)
for xf in sorted(back.list_by_class(schema.TransformerRecord), key=lambda t: t.ID)[:4]:
    print(xf.ID, xf.cw, xf.cz, xf.cm, xf.r1_2, xf.x1_2, xf.ang1, xf.cod1)
1_2_0_F 1 1 1 0.002 0.08 30.0 1
1_2_3_G 1 1 1 0.001 0.05 0.0 0
1_2_4_H 1 1 1 0.001 0.05 0.0 0
1_3_4_I 1 1 1 0.001 0.05 0.0 0

The exporter always writes CW = CZ = CM = 1 (pu on SBASE and the bus base), whatever codes the case used.

Units and codes

A transformer's values are in units that depend on three codes. The importer converts them, and the .cimtbl carries ohm and S on each winding's ratedU, not per unit:

code value meaning
CW 1 WINDV, RMA, RMI pu of the bus's BASKV
CW 2 WINDV, RMA, RMI kV
CW 3 WINDV, RMA, RMI pu of the winding's NOMV (BASKV when NOMV is 0)
CZ 1 R, X pu on SBASE and bus i's BASKV
CZ 2 R, X pu on the pair's SBASEij and NOMVi
CZ 3 R, X R is the load loss in W and X is |Z| in pu on SBASEij and NOMVi; r = loss / SBASEij and x = sqrt(|Z|^2 - r^2)
CM 1 MAG1, MAG2 G and B in pu on SBASE and bus 1's BASKV
CM 2 MAG1, MAG2 the no-load loss in W and the exciting current in pu on SBASE1-2 and NOMV1; g = loss / SBASE1-2 and b = -sqrt(I^2 - g^2) (inductive)

The ohm is the same whichever code the case used. The table headers say so: r (ohm), x (ohm), g (S), b (S), ratedU (kV), ratedS (MVA). The impedance of a pair is "seen from" winding i (the lower-numbered winding of the pair), on that winding's ratedU.

The exporter inverts only CZ 1, CM 1 and CW 1. The getter reads each value in pu on SBASE and the winding's ratedU, and the exporter moves it to the bus's BASKV by the voltage ratio alone: an impedance times (ratedU / BASKV)^2, an admittance times (BASKV / ratedU)^2. That is the identity when NOMV = BASKV.

Blank fields take the schema's defaults, and the row lists each one it filled (# defaulted: ...). The ones that matter here: CW, CZ, CM 1; WINDV 1.0, or the bus's BASKV for CW 2; SBASEij the case SBASE; RMA 1.1 and RMI 0.9 for CW 1 or 3 unless COD is +-3 or +-5; VMA 1.1 and VMI 0.9 for COD 0 and +-1; NTP 33; COD, CONT, TAB, CR, CX and NOD 0; NMETR 2. A blank RMA or RMI at CW 2 or COD +-3, or a blank VMA or VMI at COD +-2 or +-3, has no default and raises.

Transformer

One PowerTransformer per record, mRID xf_<I>_<J>_<K>_<CKT> (K is 0 for two windings), name NAME or the key, in the substation of bus I. Each winding is a PowerTransformerEnd xf_<key>_<k> with endNumber k, the winding's bus and that bus's BaseVoltage. Its ratedU is NOMVk, or the bus's BASKV when NOMVk is 0.

Form PowerTransformerEnd values Other rows
two windings (K = 0) end 1: r, x (ohm), g, b (S) and ratedS = SBASE1-2; end 2: r, x, g, b all 0, ratedS = SBASE1-2 none
three windings end 1: g, b (S); r, x and ratedS blank on every end TransformerMeshImpedance rows From 1 To 2, From 2 To 3, From 1 To 3: r, x (ohm) seen from the From end

There is no star node: PSS/E's three pair impedances Z12, Z23 and Z31 are already a mesh. The three-winding pair bases (SBASE2-3, SBASE3-1) have no end to sit on, so on export they come back as SBASE.

field import export
I, J, K (i, j, k) structural: windings 1, 2, 3's buses; K = 0 is a two-winding unit the buses of ends 1, 2, 3; K = 0 for two ends
CKT (circuit) structural: with I, J, K the mRID key; blank: 1 the mRID key, else the next free ID on the buses
NAME (name) PowerTransformer.name; blank: the key blank when the name is the key; longer than 40 characters raises
STAT (status) mapped: inService = (STAT != 0). STAT 2, 3, 4 (winding 2, 3, 1 of a three-winding unit out) keep the unit in service and set that end's terminal connected = false through an Update Table Terminal row. STAT 2, 3, 4 on a two-winding unit raises 0 when inService is false; 2, 3, 4 when exactly winding 2, 3, 1 of a three-winding unit is disconnected; else 1. Two windings out raises
VECGRP (vecgrp) PowerTransformer.vectorGroup; blank: none vectorGroup, blank when unset
CW, CZ, CM (cw, cz, cm) mapped: the code of WINDV/RMA/RMI, R/X, MAG1/MAG2; any other value raises rule: always 1
R1-2, X1-2 (r1_2, x1_2) derived: end 1's r, x (ohm) for two windings; the mesh row's r, x for three r of both ends plus the mesh r, in pu on SBASE, moved to bus 1's BASKV
R2-3, X2-3, R3-1, X3-1 (r2_3, x2_3, r3_1, x3_1) derived: the mesh rows 2-3 and 1-3 the same, from winding 2 (2-3) and winding 1 (3-1)
SBASE1-2, SBASE2-3, SBASE3-1 derived: the pair's base for CZ 2 and 3 and for CM 2 on 1-2; a two-winding unit's SBASE1-2 is also both ends' ratedS; blank: SBASE a two-winding unit's ratedS (both ends must agree, else raises); three windings: SBASE
MAG1, MAG2 (mag1, mag2) derived: end 1's g, b (S), by CM; blank: 0 the core's g, b, moved to bus 1's BASKV, sign kept
NMETR (nmetr) structural on a tie (windings in two or more AREAs): the non-metered home winding; each other winding outside the home area carries the TieFlow pair. A code outside 1..windings on a tie raises. Elsewhere untranscribed. Blank: 2 on a tie, the winding whose terminal holds no TieFlow (the lower of two); off a tie, blank
NOMVk (nomv1..nomv3) derived: ratedU of end k (kV); 0: the bus's BASKV the end's ratedU
ZCOD, VMSTAR, ANSTAR untranscribed: zero-sequence data is in the sequence file; the star point's solved voltage, which the mesh omits not exported
O1..O4, F1..F4 untranscribed: ownership is an asset concept (CIM 18 gap) not exported
RATEk-1..RATEk-12 (rate1_1..rate3_12) structural: Ratings the limits of types olt_rate<n> on winding k's terminal

Tap changers and controls

Each winding that has COD data (winding 1 of a two-winding unit, every winding of a three-winding unit) gets a TapChangerControl xf_<key>_ctrl<k> and one tap changer on its end. Winding 2 of a two-winding unit has only WINDV2 and NOMV2.

On export, a two-winding unit from another source may carry a tap on end 2. A stepped tap there without a control writes its actual step as WINDV2, and its range is lost; the export logs a warning that counts those units. When end 2 holds the unit's only tap control, the unit is written with its windings swapped (end 2 as winding 1, I and J swapped), so the control becomes COD1 and CONT1. Every value is in pu on SBASE and each winding's ratedU, so nothing else changes.

COD tap changer control mode enabled
0 RatioTapChanger, ltcFlag false voltage false: the control is kept, disabled
+-1 RatioTapChanger, ltcFlag true voltage COD > 0
+-2 RatioTapChanger, ltcFlag true reactivePower COD > 0
+-3 PhaseTapChangerLinear, ltcFlag true activePower COD > 0
+-4, +-5 none: raises (two-terminal DC phase 2; asymmetric phase shift)

discrete is true on every control.

field import export
CODk (cod1..cod3) mapped: the table above; controlEnabled = (COD > 0). Another value raises from the controlled tap changer: a ratio tap with ltcFlag false 0; ltcFlag true +-1 (voltage) or +-2 (reactivePower); a PhaseTapChangerLinear under activePower +-3; sign + when the control is enabled (the tap's controlEnabled must agree). No controlled tap: 0
WINDVk (windv1..windv3) derived: the ratio, in CW units, as the tap's step (below), or a fixed tap's neutralU = WINDV in kV the tap's voltage at its step / bus k's BASKV; with no ratio tap, ratedU / BASKV
RMAk, RMIk, NTPk derived: the ratio tap's highStep ratio, lowStep ratio and number of steps, or for COD +-3 the angles the tap's highStep and lowStep voltages / BASKV, and highStep - lowStep + 1; for a shifter the larger and smaller end angle. A fixed or missing tap: blank
CONTk (cont1..cont3) structural: the control's Terminal, below 0 for the winding's own terminal, else the busNumber of the control's node; blank for COD +-3
NODk structural: with CONTk, the busbar of that node of the regulated bus; NODk with CONTk 0 raises not exported (node-breaker data)
VMAk, VMIk derived: targetValue = (VMA + VMI) / 2, targetDeadband = VMA - VMI, in V (voltage, times the regulated bus's BASKV), VAr (reactivePower, from Mvar) or W (activePower, from MW) targetValue +- targetDeadband / 2, as pu of the regulated bus's BASKV, Mvar or MW; blank with no control
CRk, CXk derived: lineDropCompensation true, lineDropR, lineDropX (ohm) = CR, CX x BASKV^2 / SBASE, with the regulated bus's BASKV; nonzero on a COD other than +-1 raises lineDropR, lineDropX as pu on SBASE and the regulated bus's BASKV, when lineDropCompensation is true; else blank
CNXAk structural: nonzero raises (only COD +-5 uses it) not exported
ANGk (ang1..ang3) derived: see Angles see below
TABk (tab1..tab3) structural: an ImpedanceTapChangerTabular xf_<key>_ztab<k> on end k, naming ict_<TAB>; TAB names no table, or TAB on a three-winding unit, raises the table's number from the end's tabular; none: blank

Ratio taps

A stepped RatioTapChanger xf_<key>_tap<k> runs from step 1 at RMI to step NTP at RMA in equal steps:

column value
lowStep, highStep 1 and NTP; widened to the first whole step past WINDV when WINDV lies outside RMI..RMA
stepVoltageIncrement (RMA - RMI) / (NTP - 1), in percent of ratedU
neutralStep, neutralU the step nearest ratio 1 (a tie takes the upper), and that step's voltage in kV: CIM's neutral step is an integer and PSS/E's ratio 1 often falls between steps
step neutralStep + (WINDV - the neutral ratio) / the step size, a float; a WINDV exactly at RMA or RMI is step NTP or 1

NTP below 2, or RMA <= RMI, raises. When WINDV is outside RMI..RMA the row lists RMA and RMI.

A fixed RatioTapChanger has one step: lowStep = highStep = neutralStep = step = 1, neutralU = WINDV in kV, no increment, ltcFlag and controlEnabled false. It is written for:

  • winding 2 of a two-winding unit whose WINDV2 is off its NOMV2 (no control);
  • a COD 0 winding whose RMI..RMA is not a range holding WINDV (RMA <= RMI, or WINDV outside it); the row lists RMA, RMI and NTP, and the winding keeps its disabled control;
  • the winding of a phase shifter whose ratio is off nominal (no control; the phase tap holds it).

Winding 2 of a two-winding unit and the winding of a phase shifter, at their nominal ratio, get no ratio tap changer; the exporter then writes WINDV = ratedU / BASKV.

Control terminal

CONTk the control's Terminal
0 the winding's own terminal xf_<key>_T<k> (the row says CONT 0: regulates its own terminal for COD +-1)
a bus that bus's busbar terminal bb_<CONT>_T1
a bus and NODk that node's busbar terminal, in a node-breaker substation (see Substations)
negative as the bus; the sign tells PSS/E to treat the bus as on winding 1's side, which CIM has no place for, so the row lists untranscribed: cont1=-2. The exporter writes CONT positive
COD +-3 always the winding's own terminal

A CONT that names no bus raises.

Angles and phase shifters

PSS/E's ANGk is positive when winding k's bus leads the transformer's internal voltage. CIM's phaseShift and phase tap angles are positive from the terminal into the transformer, the opposite sign, so the importer writes the negated angle and the exporter turns it back.

  • Fixed shift. For every winding whose |COD| is not 3, a nonzero ANGk is PowerTransformerEnd.phaseShift (deg) on end k. A two-winding unit has only ANG1, so end 2 stays blank. Only the differences between ends are physical, so the exporter writes a two-winding unit's ANG1 as -(phaseShift of end 1 - that of end 2). The phaseShift column appears in PowerTransformerEnd only when some end has one.
  • Phase shifter, COD +-3. A PhaseTapChangerLinear xf_<key>_ptap<k> from step 1 at RMI to step NTP at RMA, in PSS/E angles, with stepPhaseShiftIncrement = the negated (RMA - RMI) / (NTP - 1), neutralStep the step nearest 0 degrees, and step = neutralStep + ANG / the step size, so ANG itself is exact. CIM has no neutral angle, so when 0 degrees falls between steps the end steps' angles move by that offset; the row lists RMA and RMI and says by how far. An ANG outside RMI..RMA raises. The control is on the winding's own terminal; its targetValue and targetDeadband are VMA and VMI in MW converted to W. The exporter writes ANGk as -(phaseShift + (step - neutralStep) x the increment), RMA and RMI from the end steps, and a stepped ratio tap beside a phase tap changer raises.

Impedance correction tables

TABk makes the winding's tabular xf_<key>_ztab<k> name the table. The table side is impedance_correction.cimtbl, which comes before the transformer file because the tabular names it.

field import export
I (table_number) structural: ImpedanceTapChangerTable ict_<I>, named I the number from the mRID ict_<I>, else the next free number
Ti (t) derived. An angle table (first T below 0.5 or last T above 1.5) gives angle (deg) = the negated T. A ratio table gives ratio = T x BASKV / ratedU of its users' winding; step stays blank an angle point's T is the negated angle; a ratio point's T = ratio x ratedU / BASKV of its users' winding
Re(Fi) (f_real) derived: rEnd1 = xEnd1 = 100 x (F - 1), in percent F = 1 + rEnd1 / 100
Im(Fi) (f_imag) structural: nonzero raises (CIM's deviations are real) rule: 0
the closing 0, 0, 0 point not a point not written

Points are numbered ict_<I>_<n> in file order, and the exporter returns them in ascending T. Excerpt from the atom cimhub_raw/tests/atoms/transformer/forms_r4b.raw, whose table 1 is an angle table on a phase shifter and whose table 2 is a ratio table on a 240 kV winding at a 230 kV bus:

Table ImpedanceTapChangerTabular: mRID, name, TransformerEnd, ImpedanceTapChangerTable
    xf_2_5_0_K_ztab1, 2_5_0_K_1, xf_2_5_0_K_1, ict_1
    xf_2_6_0_L_ztab1, 2_6_0_L_1, xf_2_6_0_L_1, ict_2

Table ImpedanceTapChangerTable: mRID, name
    # angle table
    ict_1, 1
    # ratio table
    ict_2, 2

Table ImpedanceTapChangerTablePoint: identifier, ImpedanceTapChangerTable, ratio, rEnd1, xEnd1
    ict_2_1, ict_2, 0.8625,             -5.000000000000004, -5.000000000000004
    ict_2_2, ict_2, 0.9583333333333334, 0.0,                0.0
    ict_2_3, ict_2, 1.0541666666666667, 8.000000000000007,  8.000000000000007

Fail fast, import (impedance correction). A table with fewer than two points. A complex factor (Im F != 0). A ratio table that no winding uses, or whose users have different BASKV / ratedU (one table cannot hold both).

Fail fast, export (impedance correction). A point with both or neither of ratio and angle, or a table that mixes them. A point whose rEnd1 differs from xEnd1, or that sets rEnd2, rEnd3, xEnd2 or xEnd3. A ratio table with no user, or whose users' ratedU / BASKV differ. A tabular that names no table.

Ratings

A transformer's ratings are per winding. Each nonzero RATEk-n is a limit xf_<key>_<k>_rate<n> of type olt_rate<n> in the set xf_<key>_<k>_ratings on winding k's terminal xf_<key>_T<k>. A two-winding unit has ratings on winding 1 only. The exporter writes them from whichever one terminal holds limits (an MVA, or a current as MVA at its bus, is the same value from either side) and raises when both are rated. As for branches, a zero rating is no limit, and the flag XFRRAT decides the class: 0 gives ApparentPowerLimit in MVA, and XFRRAT > 0 gives CurrentLimit in kA = RATEn / (sqrt(3) x BASKV), the BASKV of that winding's bus. The exporter writes XFRRAT 1 when the transformer ratings are CurrentLimits, reading each winding's terminal on its own, and raises when both kinds occur. See Branches for the branch flag.

Excerpts

From cimhub_raw/tests/goldens/IEEE14/transformer.cimtbl, the first of three two-winding units (CW = CZ = CM = 1, COD 0). End 1 holds x and end 2 is zero; the control is kept, disabled, and the tap has 159 steps:

Table PowerTransformer: mRID, name, vectorGroup, inService, EquipmentContainer
    xf_4_7_0_1, 4_7_0_1, , true, sub_4

Table PowerTransformerEnd: mRID, name, bus, endNumber, ratedU (kV), ratedS (MVA), r (ohm), x (ohm), g (S), b (S), BaseVoltage, PowerTransformer
    xf_4_7_0_1_1, 4_7_0_1_1, 4, 1, 138.0, 100.0, 0.0, 39.8248128,         0.0, 0.0, bv_138kv, xf_4_7_0_1
    xf_4_7_0_1_2, 4_7_0_1_2, 7, 2, 138.0, 100.0, 0.0, 0.0,                0.0, 0.0, bv_138kv, xf_4_7_0_1

Table TapChangerControl: mRID, name, mode, discrete, enabled, targetValue, targetDeadband, Terminal
    xf_4_7_0_1_ctrl1, 4_7_0_1_1, voltage, true, false, 138690.0, 136620.0, xf_4_7_0_1_T1

Table RatioTapChanger: mRID, name, lowStep, highStep, neutralStep, neutralU (kV), stepVoltageIncrement, step, ltcFlag, controlEnabled, TapChangerControl, TransformerEnd
    xf_4_7_0_1_tap1, 4_7_0_1_1, 1, 159, 79, 137.8253164556962, 0.6265822784810127, 75.69090909090909, false, false, xf_4_7_0_1_ctrl1, xf_4_7_0_1_1

From the atom cimhub_raw/tests/atoms/transformer/transformers.raw, unit D, a three-winding unit (1-2-3) with CZ 1: g and b on end 1, the pair impedances as a mesh, and a rating on windings 1 and 3:

Table PowerTransformerEnd: mRID, name, bus, endNumber, ratedU (kV), ratedS (MVA), r (ohm), x (ohm), g (S), b (S), BaseVoltage, PowerTransformer
    xf_1_2_3_1_1, 1_2_3_1_1, 1, 1, 345.0, ,      ,                    ,                  4.2007981516488137e-07, -1.6803192606595255e-06, bv_345kv,  xf_1_2_3_1
    xf_1_2_3_1_2, 1_2_3_1_2, 2, 2, 230.0, ,      ,                    ,                  ,                       ,                        bv_230kv,  xf_1_2_3_1
    xf_1_2_3_1_3, 1_2_3_1_3, 3, 3, 69.0,  ,      ,                    ,                  ,                       ,                        bv_69kv,   xf_1_2_3_1

Table TransformerMeshImpedance: mRID, name, FromTransformerEnd, ToTransformerEnd, r (ohm), x (ohm)
    xf_1_2_3_1_mesh_12, 1_2_3_1_12, xf_1_2_3_1_1, xf_1_2_3_1_2, 1.19025,             59.5125
    xf_1_2_3_1_mesh_23, 1_2_3_1_23, xf_1_2_3_1_2, xf_1_2_3_1_3, 1.058,               21.16
    xf_1_2_3_1_mesh_13, 1_2_3_1_13, xf_1_2_3_1_1, xf_1_2_3_1_3, 1.785375,            83.3175

Table OperationalLimitSet: mRID, Terminal
    xf_1_2_3_1_1_ratings, xf_1_2_3_1_T1
    xf_1_2_3_1_3_ratings, xf_1_2_3_1_T3

From the atom cimhub_raw/tests/atoms/transformer/forms_r4b.raw, unit K, a phase shifter (COD -3, 0 degrees off the step grid) with a fixed off-nominal ratio and an impedance correction table. The row lists the RMA and RMI that CIM cannot hold:

Table TapChangerControl: mRID, name, mode, discrete, enabled, targetValue, targetDeadband, Terminal, lineDropCompensation, lineDropR (ohm), lineDropX (ohm)
    xf_2_5_0_K_ctrl1, 2_5_0_K_1, activePower,   true, false, 70000000.0,  20000000.0,         xf_2_5_0_K_T1, ,     ,

Table RatioTapChanger: mRID, name, lowStep, highStep, neutralStep, neutralU (kV), stepVoltageIncrement, step, ltcFlag, controlEnabled, TapChangerControl, TransformerEnd
    # fixed: a phase shifter's off-nominal ratio
    xf_2_5_0_K_tap1, 2_5_0_K_1, 1, 1,  1,  234.6,              ,                   1,                  false, false, ,                 xf_2_5_0_K_1

Table PhaseTapChangerLinear: mRID, name, lowStep, highStep, neutralStep, stepPhaseShiftIncrement (deg), step, ltcFlag, controlEnabled, TapChangerControl, TransformerEnd
    # untranscribed: rma1=40.0, rmi1=-30.0 (0 deg lies 0.6451612903225765 deg off the step grid)
    xf_2_5_0_K_ptap1, 2_5_0_K_1, 1, 32, 14, -2.2580645161290325, 9.571428571428573, true, false, xf_2_5_0_K_ctrl1, xf_2_5_0_K_1

Fail fast and expected differences

Fail fast, import.

  • STAT 2, 3 or 4 on a two-winding unit.
  • COD +-4 or +-5, and a nonzero CNXA.
  • TAB on a three-winding unit, or a TAB that names no impedance correction table.
  • CR or CX nonzero on a COD other than +-1.
  • A blank RMA, RMI, VMA or VMI that has no default.
  • NOD without CONT, and a CONT that is no bus.
  • CW, CZ or CM outside its codes; CZ 3 with |Z| below r; CM 2 with an exciting current below g.
  • NTP below 2, RMA <= RMI on a stepped tap, and an ANG outside RMI..RMA on a phase shifter.
  • On a tie, an NMETR that names no winding.

Fail fast, export.

  • A transformer that is not two or three ends, a model not given by ends, or an end on a node with no busNumber (that is neither a generator step-up nor a converter transformer).
  • Ends whose ratedS differ on a two-winding unit; ratings on both windings of a two-winding unit.
  • A tap control on both windings of a two-winding unit, or a phase or impedance tap changer on its winding 2.
  • A phase tap changer that is not linear; both tap changers controlled; a stepped ratio tap beside a phase tap changer.
  • A control mode other than voltage, reactive power or active power; a ratio tap under an active power control, or a phase tap under another mode; a controlEnabled that disagrees with the control's enabled.
  • A control whose terminal is on a node with no busNumber.
  • TAB on a three-winding unit.
  • More than one winding disconnected, or one disconnected on a two-winding unit.
  • TieFlows on every winding.
  • Ratings in MVA and in current in one case.

Expected differences.

  • CW, CZ and CM come back 1, and R, X, MAG1, MAG2, WINDV, RMA, RMI are in pu on SBASE and the bus base, which are the same physical values. A three-winding unit's SBASE2-3 and SBASE3-1 come back as SBASE.
  • A blank that was defaulted comes back as its default value.
  • A COD 0 winding with an unusable tap range (a fixed tap) comes back with RMA, RMI and NTP blank, and a COD +-1 winding whose WINDV was outside RMI..RMA comes back with RMA and RMI from the widened steps.
  • A phase shifter whose 0 degrees was off the step grid comes back with RMA and RMI moved by the listed offset.
  • A negative CONT comes back positive.
  • A two-winding unit's ANG1 comes back as the difference of the two ends' shifts.
  • NMETR off a tie comes back blank (RAW's default is 2); on a tie it is the lowest-numbered home winding.
  • Impedance correction points come back in ascending T.
  • NODk is not exported (the node-breaker export is not written yet), and owners, ZCOD, VMSTAR and ANSTAR are not exported.

Where the rules are specified

The per-field classification with its reasons is in the import mapping (sections Transformer and Transformer: the forms it raises on) and the export mapping (section E4).