Substations and node-breaker data

Every bus lands in a CIM Substation. Most come from the importer, which groups buses that sit in one substation. A case may also carry SUBSTATION blocks, RAW's node-breaker data: nodes inside a bus, the breakers and disconnectors between them, and the equipment terminals that say which node each device connects to. How to read the tables is on the reference landing page.

RAW table CIM classes Import Export
Synthesized substations (no RAW table: buses and the equipment between them) Substation bus.cimtbl no
Substation (SUBSTATION block) Substation, Location, PositionPoint, CoordinateSystem bus.cimtbl, substation.cimtbl no
Substation node ConnectivityNode substation.cimtbl no
Substation switching device Switch, Breaker, Disconnector substation.cimtbl no
Regulated nodes (NREG, NOD1 to NOD3 on other records) BusbarSection substation.cimtbl no
Equipment terminal Terminal (an Update row) equipment_terminal.cimtbl no

The import is a bus-branch model (TopologicalNodes and BusbarSections) that also holds ConnectivityNodes for the buses a SUBSTATION block covers. A bus outside every block keeps its bare TopologicalNode; a bus inside one also gets its block's nodes, and a device placed on a node sits on both. The export does not write the node-breaker data yet, see Export.

Synthesized substations

RAW has no substation for a bus-branch case, but CIM needs one to contain the busbars and equipment. The importer joins buses that the network treats as one site, and it never joins across a zone boundary. The grouping runs cimtopology's island search over the merge edges, with every bus listed, so a bus on no merge edge is its own substation.

merge edge joins
every system switching device its two buses
a branch with R = 0 and |X| at or below THRSHZ its two buses; THRSHZ is in pu on the system base, from the GENERAL record, default 0.0001
a branch whose CKT starts with @ or * its two buses
a series capacitor, a branch with X < 0 its two buses
every transformer all of its windings' buses
the nodes of a SUBSTATION block every bus the block's nodes name

A merge edge between two zones is skipped, so that equipment sits on the boundary between two substations.

substation mRID name Region
a group that holds a SUBSTATION block sub_s<IS> the block's NAME; blank: IS srgn_<zone of its first bus>
any other group sub_<lowest bus number> that bus's NAME; blank: its number srgn_<zone of the lowest bus>

A group's row comment lists its buses and the equipment that joined them (# buses 4, 7, 9; xf_4_7_0_1, xf_4_9_0_1), and the table comment counts the substations.

Fail fast. A group that holds two SUBSTATION blocks (buses [...] form one substation holding SUBSTATION blocks [...] (merged by ...)). A block whose buses are in two zones, since a Substation has one Region. A branch with a blank R or X, which has no schema default, so the zero-impedance test cannot run.

Counts. IEEE14 gives 11 substations (two of several buses: 4, 7, 9 and 5, 6). WECC240 gives 134, 79 of them of several buses, the largest of seven. IEEE118 with its four blocks gives 108, four of them from blocks.

Export. The Substation is not exported. The exporter reads a bus's ZONE from the Region of the substation its node sits in, and nothing else about it, so the grouping and the substation names do not come back.

Excerpt from cimhub_raw/tests/goldens/IEEE14/bus.cimtbl:

# synthesized: substations, buses merged across switching devices, zero-impedance branches (R = 0, |X| <= THRSHZ 0.0001),
# series capacitors and transformers, within a zone (11 substations)
Table Substation: mRID, name, Region
    sub_1,  BUS 1,  srgn_1
    sub_2,  BUS 2,  srgn_1
    sub_3,  BUS 3,  srgn_1
    # buses 4, 7, 9; xf_4_7_0_1, xf_4_9_0_1
    sub_4,  BUS 4,  srgn_1
    # buses 5, 6; xf_5_6_0_1
    sub_5,  BUS 5,  srgn_1
    ...

Substation blocks

A SUBSTATION block (RAW's SubstationRecord, key IS) is one Substation sub_s<IS>, written in bus.cimtbl because the buses' nodes name their substation. substation.cimtbl adds its location, nodes, switching devices and regulated busbars.

field import export
IS (substation_number) structural: the key, the substation sub_s<IS>, and the scope of its node numbers not exported
NAME (name) structural: the Substation name in bus.cimtbl; blank: IS not exported
LATI (latitude) copied to PositionPoint.yPosition (deg) of the point sub_s<IS>_loc_1 of Location sub_s<IS>_loc not exported
LONG (longitude) copied to PositionPoint.xPosition (deg) not exported
SGR (grounding_resistance) untranscribed: a substation's DC grounding resistance for GIC studies has no CIM 18 home not exported

The CoordinateSystem is one crs_latlong named LatLongCoords, with crsUrn urn:ogc:def:crs:OGC:1.3:CRS84 (x is longitude, y latitude), the same form the OpenDSS spoke writes. LATI = LONG = 0, the default, writes no Location, and the document comment lists the blocks left without one.

Fail fast. A bus with nodes in two blocks. A group holding two blocks, and a block across two zones, as above.

Excerpt from the artifact the importer writes for cimhub_raw/tests/atoms/substation/node_breaker_forms.raw (block 10 at 46.2 N, 119.1 W):

Object CoordinateSystem: mRID=crs_latlong, name=LatLongCoords, crsUrn=urn:ogc:def:crs:OGC:1.3:CRS84

Table Location: mRID, CoordinateSystem=crs_latlong
    sub_s10_loc

# copied: xPosition = LONG, yPosition = LATI (deg)
Table PositionPoint: identifier, Location, sequenceNumber, xPosition, yPosition
    sub_s10_loc_1, sub_s10_loc, 1, -119.1, 46.2

Update Table Substation: mRID, Location
    sub_s10, sub_s10_loc

Substation nodes

One ConnectivityNode sub_s<IS>_n<NI> per node, in its bus's TopologicalNode and its block's substation, with its bus's BaseVoltage.

field import export
IS (substation_number) structural: the enclosing block, filled by the reader; ConnectivityNodeContainer is sub_s<IS> not exported
NI (node_number) structural: with IS the key; a node number given twice in one block raises not exported
NAME (name) copied to ConnectivityNode.name; blank: <IS>_<NI> not exported
I (bus_number) structural: the TopologicalNode and the BaseVoltage of bus I; a node on no bus raises, and so does a bus with nodes in two blocks not exported
STATUS (status) untranscribed: a ConnectivityNode has no in-service flag; STATUS 0 is listed on the row as untranscribed: status=0 not exported
VM (vm) untranscribed: SvVoltage attaches only to a TopologicalNode, which has the bus's VM; a value other than the default -1.0 is listed on the row not exported
VA (va) untranscribed: as VM; listed when not 0.0 not exported

Fail fast. The messages name the block and node: SUBSTATION block 1 node 3: the node number is given twice in the block, ...: bus 7 is no bus, ...: bus 7 also has nodes in block 2.

Excerpt from the artifact the importer writes for cimhub_raw/tests/atoms/substation/node_breaker_forms.raw (node 17 has no name, VM 1.02 and VA -2.5):

# untranscribed: status, vm, va
Table ConnectivityNode: mRID, name, TopologicalNode, BaseVoltage, ConnectivityNodeContainer
    sub_s10_n1,  HV BUS,   1, bv_230kv, sub_s10
    ...
    # untranscribed: vm=1.02, va=-2.5
    sub_s10_n17, 10_17,    2, bv_115kv, sub_s10

Substation switching devices

Each record becomes a Switch, Breaker or Disconnector by TYPE, with node1 and node2 on its nodes and bus1 and bus2 on their buses, in the substation sub_s<IS>. The mRID is sw_s<IS>_<NI>_<NJ>_<CKT>. The code tables are the system switching device's.

field import export
IS (substation_number) structural: EquipmentContainer is sub_s<IS> not exported
NI (from_node) structural: node1 is sub_s<IS>_n<NI> and bus1 that node's bus; BaseVoltage is its bus's not exported
NJ (to_node) structural: node2 and bus2; NI = NJ raises; a node not in the block raises not exported
CKT (circuit) structural: with IS, NI and NJ the key; blank is 1, marked defaulted not exported
NAME (name) copied to name; blank: the key <IS>_<NI>_<NJ>_<CKT> not exported
TYPE (device_type) mapped: 1 Switch (a generic connector), 2 Breaker, 3 Disconnector; any other code raises not exported
STATUS (status) mapped: 1 is closed and 0 is open; any other code raises; blank is 1, marked defaulted not exported
NSTAT (normal_status) mapped: 1 is closed and 0 is normalOpen; any other code raises; blank is 1, marked defaulted not exported
X (reactance) untranscribed: a Switch has no impedance not exported
RATE1 to RATE3 (rate1, rate2, rate3) structural: an OperationalLimitSet sw_s<key>_ratings on terminal 1 with a limit per nonzero rating, typed by the rating sets; units follow NXFRAT not exported

Fail fast. NI = NJ (substation switching device <key>: NI = NJ = 3). A node that is not in the block. A TYPE with no mapping. A device whose two nodes' buses are in different areas, which would be a tie inside a substation: it raises NotImplementedError, since no case has one.

Excerpt from cimhub_raw/tests/goldens/IEEE118/substation.cimtbl:

# untranscribed: reactance
Table Breaker: mRID, name, node1, node2, bus1, bus2, open, normalOpen, BaseVoltage, EquipmentContainer
    sw_s8_1_3_1,    8_1_3_1,    sub_s8_n1,   sub_s8_n3,    8,   8,   false, false, bv_345kv, sub_s8
    ...
    sw_s100_1_2_1,  100_1_2_1,  sub_s100_n1, sub_s100_n2,  100, 100, true,  true,  bv_138kv, sub_s100

Table Disconnector: mRID, name, node1, node2, bus1, bus2, open, normalOpen, BaseVoltage, EquipmentContainer
    sw_s100_2_3_1,  100_2_3_1,  sub_s100_n2, sub_s100_n3,  100, 100, true, true, bv_138kv, sub_s100
    ...

Regulated nodes

A control on another record can regulate one node of a bus: a generator's, switched shunt's or transformer's NREG or NODk, and the same fields on VSC DC and FACTS devices. RAW does not say which nodes are busbars, so the importer writes a BusbarSection only on a node some control regulates, and no others. The control's Terminal is then bb_s<IS>_n<NI>_T1. The bus's own bb_<I> stays on the bus and holds its voltage limits and any bus-level regulation (see buses).

field import export
NREG and NODk, nonzero structural: the control regulates node NI of the regulated bus, and its Terminal is the terminal of BusbarSection bb_s<IS>_n<NI>, with node, bus, BaseVoltage and the container sub_s<IS>, named for the node's NAME not exported
NREG or NODk, zero the bus's own bb_<I>_T1 the control's terminal is on the bus

Fail fast. The regulated bus has no block. The block has no node NI of that bus. NODk is nonzero while CONTk is 0.

Excerpt from the artifact the importer writes for cimhub_raw/tests/atoms/substation/node_breaker_forms.raw:

Table BusbarSection: mRID, name, node, bus, BaseVoltage, EquipmentContainer
    bb_s10_n1,  HV BUS, sub_s10_n1,  1, bv_230kv, sub_s10
    bb_s10_n11, LV BUS, sub_s10_n11, 2, bv_115kv, sub_s10

Equipment terminals

An equipment terminal record says which node of a bus a device's terminal is on. The importer writes one Update row per terminal, in equipment_terminal.cimtbl, which comes last so every equipment document has already written its Terminals. The record is matched against the equipment those documents wrote, so no mRID rule is repeated here. A terminal with no record stays on its bus only.

TYP equipment (key) Terminals updated
L load (I, ID) ld_<I>_<ID>_T1
F fixed shunt (I, ID) cap_<I>_<ID>_T1
M generator (I, ID) sm_<I>_<ID>_T1 (WMOD 0) or pec_<I>_<ID>_T1 (WMOD 1, 2, 3), or the machine's step-up transformer terminal when it has one
B or 2 a branch or a two-winding transformer (I, J, CKT) a branch: ln_ or sc_<key>_T1 when I is its from bus, _T2 when its to bus, and that end's line shunt cap_<key>_i or _j; a transformer: xf_<key>_T1 or _T2, by which winding I is
3 three-winding transformer (I, J, K, CKT) xf_<key>_T<k>, the winding at I; the buses may be in any order
S switched shunt (I) every block's swsh_<I>_b<k>_T1
I, D, V, N, A induction machine, two-terminal DC, VSC DC, multi-terminal DC, FACTS raises (NotImplementedError)

The key is matched in either bus order. B and 2 are one form.

field import export
IS (substation_number) structural: the block whose node NI is meant, filled by the reader not exported
I (bus_number) structural: which terminal of the equipment; node NI's bus must be I not exported
NI (node_number) structural: the terminal's ConnectivityNode sub_s<IS>_n<NI>; 0 means bus I has no node-breaker model and writes no row not exported
TYP (terminal_type) structural: the equipment form in the table above not exported
J (j_bus) structural: the other end of a B, 2 or 3 key not exported
K (k_bus) structural: the third winding of a 3 key not exported
ID or CKT (identifier) structural: the rest of the key; blank is 1 for L, F, M, I, B, 2 and 3, marked defaulted not exported

Fail fast. A TYP that is no equipment form. A phase-2 TYP. Equipment no document wrote (names no load), a key that matches two pieces of equipment, and a Terminal placed twice. NI = 0 at a bus that has nodes, and a nonzero NI at a bus that has none. A node that is in another block than IS. A B key that names only a system switching device, which has no terminal-record form.

Excerpt from cimhub_raw/tests/goldens/IEEE118/equipment_terminal.cimtbl:

# each named equipment terminal on its node
Update Table Terminal: mRID, ConnectivityNode
    ln_9_8_1_T2,     sub_s8_n3
    ln_8_30_1_T1,    sub_s8_n4
    xf_8_5_0_1_T1,   sub_s8_n5
    ld_8_1_T1,       sub_s8_n6
    sm_8_1_T1,       sub_s8_n7
    ...

Export

The exporter writes none of the node-breaker data: no SUBSTATION block, node, switching device or equipment terminal record, and no NREG or NODk (they come back blank). It does not stop: the Substation, ConnectivityNodes and the Switch, Breaker and Disconnectors that sit between two nodes are skipped with one warning on the log that counts the switches (59 switch(es) between two ConnectivityNodes not exported: ...), and the case comes back with its buses, branches, transformers, loads, shunts and generators, each on its bus. A switch on a node at one terminal only raises. The design record, export mapping, lists this as the next export step.

On the IEEE118 case with four node-breaker substations, the import has 4 blocks, 42 nodes, 59 switching devices and 36 equipment terminals; the export has none of them.

Expected differences once the export is written (from the design record): SGR comes back as 0.1, a node's STATUS 0 as 1 and its VM and VA as the defaults (-1.0 and 0.0), a switching device's X as 0.0001, a block at 0, 0 as 0, 0, and an equipment terminal record with NI = 0 is not written. A B or 2 record comes back as 2 for a transformer and B for a branch. A free bus merged into a block's substation by a transformer stays outside the block's node data.