Generators

This page is the conversion reference for the RAW Generator table: the machines at a bus, their voltage control, their limits, the renewable and power factor forms, and the implicit step-up transformer. One RAW record becomes one machine or one converter connection with its unit, and the records at one bus share a plant control. The field classes (copied, mapped, structural, derived, untranscribed) and the conventions every section follows are on the reference index. The getters the exporter reads through, and the generation sign rule they apply, are on the core site's distributed energy resources page.

RAW table CIM classes .cimtbl artifact and shape Importer Exporter
Generator, WMOD 0 SynchronousMachine, GeneratingUnit, ControlAreaGeneratingUnit generator.cimtbl, shape synchronous_machine with bus importer/cimtbl/generator.py exporter/generator.py
Generator, WMOD 1, 2, 3 PowerElectronicsConnection, PowerElectronicsUnit, ControlAreaPowerElectronicsUnit generator.cimtbl, shape der with bus importer/cimtbl/generator.py exporter/generator.py
Generator, one per bus RegulatingControl, the plant's generator.cimtbl importer/cimtbl/generator.py exporter/generator.py
Generator, RT + jXT other than 0 PowerTransformer with two PowerTransformerEnds, an internal TopologicalNode, and a fixed RatioTapChanger when GTAP is not 1 generator.cimtbl, shape behind_transformer importer/cimtbl/generator.py exporter/generator.py

The table shapes are on the core site's shapes page. Source paths are under cimhub_raw/src/cimhub_raw/. The master imports generator.cimtbl after the load and fixed shunt artifacts and before the transformer ones. A switched shunt that regulates a plant's reactive power reads the machine from this table (see Loads and shunts). The bus a machine sits on, its area and its IDE come from the bus tables (see Case, buses, areas and zones).

Quoted error messages start with the record, as 1_1: or plant 2:. A generator's key is its bus number and ID, and the name the importer gives it is <I>_<ID>; a blank ID is 1.

The examples run from the repository root with UV_FROZEN=1 uv run python. They convert the public test atoms in cimhub_raw/tests/atoms/generator to CIM and back.

Records, plants and classes

PSS/E treats VS, IREG and RMPCT as plant quantities: every machine at bus I shares them, and the plant's output and limits are the sums over its machines in service. The importer follows that. Each bus with generator records gets one RegulatingControl gc_<I>, and every machine and connection at the bus names it. The control cannot be cc_<I>, which is the switched shunt's control, because one bus can have both.

WMOD picks the class of each record:

WMOD CIM, per record Plant control
0 conventional SynchronousMachine sm_<I>_<ID>, GeneratingUnit gu_<I>_<ID>, ControlAreaGeneratingUnit cagu_<I>_<ID> voltage
1 renewable, limits QT and QB PowerElectronicsConnection pec_<I>_<ID>, PowerElectronicsUnit pecu_<I>_<ID>, ControlAreaPowerElectronicsUnit capu_<I>_<ID> voltage
2 renewable, limits from WPF as WMOD 1, with WPF listed on the row voltage
3 renewable, fixed power factor as WMOD 1 power factor
4 infeed raises NotImplementedError
any other value raises

A blank WMOD is 0. The PowerElectronicsUnit has no kind: RAW cannot say whether a converter plant is solar or wind, so the importer writes neither PhotoVoltaicUnit nor PowerElectronicsWindUnit. A concentrating solar plant that PSS/E models as a conventional machine is WMOD 0, and lands on SynchronousMachine and GeneratingUnit. RAW cannot mark a type 1 or 2 wind plant, an induction machine, entered as WMOD 1: it is a converter connection here. Each unit joins the ControlArea ca_<AREA of bus I>; a generator record has no AREA of its own. A bus AREA with no Area interchange record raises.

Plant voltage control

For WMOD 0, 1 and 2 the plant control is:

RegulatingControl attribute Value
mRID, name gc_<I>, <I>
mode, discrete voltage, false
targetValue VS x the BASKV of the regulated bus, in volts (232300.0 for VS 1.01 on 230 kV); blank VS is 1.0
targetDeadband blank: PSS/E holds VS exactly
Terminal the busbar terminal bb_<IREG>_T1, or bb_<I>_T1 when IREG is 0 or I; NREG other than 0 names a node of bus IREG and the terminal is that node's busbar (see Substations and node-breaker data)
enabled true when the bus's IDE is 2 or 3; every member's controlEnabled follows it

The product VS x BASKV can leave a last-digit float residue (144209.99999999997 for 1.045 on 138 kV) and is written as computed. A plant on an IDE 1 bus has its control disabled. IDE 3 is the swing bus: every SynchronousMachine at the bus gets referencePriority 1, the angle reference's highest priority, and the exporter writes IDE 3 for a bus with such a machine. A bus with an enabled plant control exports as IDE 2, and any other as IDE 1.

The plant's records must agree on VS, IREG, NREG and RMPCT, as PSS/E requires. A swing bus must regulate itself, because PSS/E would silently regulate bus I instead.

Sign, limits and rating

CIM's terminal p and q are positive into the equipment, so a generator's are negative. The importer writes p (MW) = -PG and q (MVAr) = -QG on both classes, and keeps zero as 0.0. The limits stay in the generator convention, as CIM defines them, and are copied: maxQ = QT, minQ = QB, and PT and PB are GeneratingUnit.maxOperatingP and minOperatingP, or PowerElectronicsUnit.maxP and minP. A negative PB, a pumping machine, is copied as it is. The exporter asks the getters for sign="generation" and so writes PG and QG positive again.

CIM value From
ratedS (MVA) MBASE; a blank MBASE is SBASE
ratedU (kV) BASKV of bus I: RAW has no machine voltage, and MBASE and ZR are on BASKV
r (ohm), a SynchronousMachine only ZR x BASKV^2 / MBASE
qPercent, a SynchronousMachine only RMPCT, on every machine of the plant
inService STAT == 1 on the machine or connection; the unit has no status of its own

ZX is untranscribed: cim18v17's SynchronousMachine has no positive-sequence reactance. On a PowerElectronicsConnection, ZR and RMPCT have no CIM attribute; the row lists them when they are not 0 and 100 (# untranscribed: zr=0.01).

Renewable machines

A WMOD 1, 2 or 3 record is a PowerElectronicsConnection with its unit, and the three differ in the limits and the control:

WMOD Reactive limits Plant control What the row says
1 maxQ, minQ = QT, QB voltage, as above nothing extra
2 maxQ, minQ = QT, QB as written; RAW sets them from PG and WPF, which CIM cannot express, so they do not follow a later change of p voltage, as above # untranscribed: wpf=0.95, always, so the importer's own output tells WMOD 2 from 1
3 QT, QB as written mode powerFactor, discrete false, targetValue = WPF as read, enabled as above # untranscribed: regulated_voltage_setpoint=1.02, regulated_bus_number=3 when VS, IREG or NREG is off its default

A WMOD 3 plant holds the connection's power factor, not a voltage. The sign of WPF is kept: a positive WPF means q has the sign of p, under the generator or the load sign alike. The control sits on the connection's own terminal, pec_<I>_<ID>_T1, where its power factor is. The connection row names the control, so the control row is written with no Terminal and an Update RegulatingControl row after the connection table sets it. VS, IREG and NREG are not used by a fixed power factor. A plant that mixes WMOD 3 with any other record raises, because one control holds either a voltage or one connection's power factor.

On export a PowerElectronicsConnection is WMOD 3 with WPF = the control's targetValue when its control is powerFactor, and WMOD 1 otherwise. WMOD 2 comes back as 1, with WPF blank.

The implicit step-up transformer

RT + jXT other than 0 is PSS/E's implicit step-up between bus I and the machine, with GTAP the off-nominal ratio at bus I. The importer writes the transformer as data, in the core behind_transformer shape, with the machine on an internal node:

CIM class mRID Attributes
TopologicalNode <machine>_int name <I>_<ID> terminal; no bus number; bus I's BaseVoltage and substation
PowerTransformer <machine>_xf name <I>_<ID> step-up; always in service
PowerTransformerEnd 1 <machine>_xf_1 on bus I; ratedU (kV) = BASKV; ratedS (MVA) = MBASE; r (ohm) = RT x BASKV^2 / MBASE; x (ohm) = XT x BASKV^2 / MBASE
PowerTransformerEnd 2 <machine>_xf_2 on the internal node; ratedU (kV) = BASKV; ratedS (MVA) = MBASE; no r, x
RatioTapChanger, GTAP other than 1 <machine>_xf_tap1 on end 1; one fixed step (lowStep, highStep, neutralStep, step all 1, ltcFlag and controlEnabled false); neutralU (kV) = GTAP x BASKV

<machine> is sm_<I>_<ID> or pec_<I>_<ID>. The machine's terminal is on the internal node. RAW gives no terminal voltage for the machine, because XTRAN and GTAP are per unit on MBASE and the system base, so the internal node and end 2 keep bus I's BaseVoltage, a per-unit equivalent. The machine's ratedU is the same. There is no magnetizing branch.

Power, limits and control stay on the machine. The plant control stays on bus I's busbar, because PSS/E's power flow injects PG + jQG at bus I and uses XTRAN only in fault and dynamics studies. A CIM solve that includes the step-up will therefore see its losses, which the RAW solution does not: an expected difference when solving, not when converting.

GTAP is used only with a step-up. Without one PSS/E ignores it, so the importer lists it on the machine row when it is not 1 (# untranscribed: gtap=1.02).

On export a machine whose terminal node has no bus number sits behind a step-up, and the exporter folds it back:

Check Rule
the node holds the machine and exactly one PowerTransformer whose other end is on a numbered bus
the transformer in service, two windings, no core admittance, winding 1 on the bus and winding 2 on the machine's node
the ratings each end's ratedU equals its node's BaseVoltage
the tap only a fixed RatioTapChanger on winding 1
the values RT = the windings' r summed, XT = the mesh x, both per unit on MBASE; GTAP = neutralU / ratedU of end 1, or 1 with no tap

The transformer exporter leaves these transformers out, so each is exported once, as the machine's RT, XT and GTAP. Anything else raises.

Generator fields

RAW field Import Export
I structural: the machine's bus, BaseVoltage, EquipmentContainer and ControlArea; the plant key gc_<I>; IDE sets enabled and referencePriority the bus number of the machine's node, or of the bus across its step-up
ID structural: key for the mRIDs, name <I>_<ID>; blank is 1 the ID in the mRID sm_<I>_<ID> or pec_<I>_<ID>, else the next free 1, 2, ... on the bus
PG derived: p (MW) = -PG; blank is 0 the machine's p in generation sign
QG derived: q (MVAr) = -QG; blank is 0 the machine's q in generation sign
QT copied: maxQ (MVAr) of the machine or connection; blank is 9999 maxQ in generation sign; blank when unset
QB copied: minQ (MVAr); blank is -9999 minQ in generation sign; blank when unset
VS derived: the plant control's targetValue = VS x BASKV of the regulated bus, in V; blank is 1.0 the voltage control's target in kV over the regulated bus's BASKV; blank for WMOD 3 and for a plant with no control
IREG structural: the plant control's Terminal; blank is 0 the bus number of the control's terminal, its own bus included (a RAW 0 comes back as I); blank for WMOD 3 and for a plant with no control
MBASE copied: ratedS (MVA), with ratedU (kV) = BASKV; blank is SBASE the rating's ratedS
ZR derived: r (ohm) of a SynchronousMachine = ZR x BASKV^2 / MBASE; listed on a connection's row when not 0; blank is 0 a machine's r in pu on its ratedU and ratedS; blank for a connection
ZX untranscribed not written
RT, XT derived: the step-up's end 1 r (ohm), x (ohm); blank is 0 the step-up's r and x in pu on MBASE; 0 with no step-up
GTAP derived: the fixed tap's neutralU (kV) = GTAP x BASKV; without a step-up listed when not 1; blank is 1.0 neutralU / ratedU of the step-up's tap, 1 with no tap; blank with no step-up
STAT mapped: inService; blank is 1 0 when inService is false, else 1
RMPCT copied: SynchronousMachine.qPercent, on every machine of the plant; a connection lists it when not 100; blank is 100 the qPercent of the plant's machines on every record of the plant; blank for a plant of connections only
PT copied: maxOperatingP (MW) or maxP (MW); blank is 9999 the unit's maximum in generation sign, as stored
PB copied: minOperatingP (MW) or minP (MW); blank is -9999 the unit's minimum in generation sign, as stored, even when it is above PT
O1 to O4, F1 to F4 untranscribed not written
WMOD mapped: the class, as in the table above; blank is 0 0 for a SynchronousMachine; 3 for a connection under a powerFactor control, else 1
WPF mapped: WMOD 2 always listed; WMOD 3 the control's targetValue; blank is 1.0 WMOD 3: the control's targetValue; else blank
NREG structural: a node of bus IREG, as above; blank is 0 not written

Generator fail-fast rules

Rule Message
WMOD 4 generator 1_1: WMOD 4 (infeed, fixed Q: no case has one yet)
any other WMOD 1_1: wmod=9 has no mapping (known: 0, 1, 2, 3)
a STAT other than 0 or 1 1_1: status=2 has no mapping (known: 0, 1)
records of one plant that disagree plant 2: generators 2_G and 2_PV disagree on (IREG, NREG, VS, RMPCT): (3, 0, 1.05, 100.0) vs (3, 0, 1.01, 100.0); PSS/E treats them as plant quantities
an IREG that is no bus plant 1: IREG 77 is no bus
a swing bus that regulates another bus plant 1: a swing bus regulates remote bus 3 (PSS/E would regulate bus 1 instead)
a swing bus with only converter records plant 1: a swing bus with no SynchronousMachine (only converter records), so no referencePriority
a bus AREA with no Area interchange record plant 1: AREA 9 has no area-interchange record (no ControlArea ca_9)
WMOD 3 beside another record plant 2: WMOD 3 ['2_G'] shares the plant with other records; one control holds either a voltage or one connection's power factor (no case has one yet)
export: machines of one plant whose controls disagree plant 2: its machines' controls disagree on (IREG, VS): [...]; PSS/E treats them as plant quantities
export: machines whose qPercent disagree plant 2: its machines' qPercent disagree: [...]; RMPCT is a plant quantity
export: a control that is neither voltage nor a connection's power factor RegulatingControl 'x' of SynchronousMachine 'y': mode ...; a plant regulates voltage, or a connection its power factor
export: a machine on a node with no bus number that is not a step-up SynchronousMachine 'x': its TopologicalNode 'y' has no busNumber and holds [...]; a step-up's node holds the machine and one transformer
export: a step-up out of service, with a core, with a moving tap, or rated off its node's BaseVoltage the message names the transformer and the rule, such as out of service; a RAW step-up has no status of its own

One more case is not caught by a message: an explicit MBASE of 0 passes the importer's defaulting (only a blank MBASE is SBASE) and stops with a bare ZeroDivisionError, in the ZR conversion of a SynchronousMachine or in the r and x of a step-up. A connection with no step-up takes it through as ratedS 0.

Generator round trip

What Why
IREG 0 comes back as the bus's own number CIM keeps the terminal, not whether RAW wrote 0 or I
a blank MBASE comes back as SBASE the importer defaulted it
WMOD 2 comes back as 1 and its WPF comes back blank CIM has no reactive limit that follows P; the row's note is not read back
a WMOD 3 record comes back without its VS and IREG a fixed power factor does not use them
a WMOD 1 record's WPF other than 1 comes back blank PSS/E uses WPF only in WMOD 2 and 3
a connection's ZR and, in a plant of connections only, RMPCT come back blank no CIM attribute
a GTAP other than 1 without a step-up comes back blank PSS/E ignores it, and the row's note is not read back
ZX, O1 to O4, F1 to F4 and NREG come back blank no CIM home, or not written
ZR, RT, XT and VS can differ in the last digit per unit to ohm and per unit to volt conversions: relative error 1e-9
a reversed PT and PB come back as written the exporter returns the unit's limits as stored

This example converts the step-up atom. It prints each machine's node and its p in both signs, the transformers, and the exported records. The machine 2 G2 has GTAP 1.02 but no step-up, so it stays on bus 2:

import cimprofiles.cim18.cim18v17 as cim

import cimhub_raw.schema.raw_v34.raw34_schema as schema
from cimhub_core.getters.der import get_der_output
from cimhub_raw.exporter.cim_to_raw import RawExporter
from cimhub_raw.importer.raw_to_cimtbl import raw_to_cim
from cimhub_raw.raw34_reader import Raw34Reader
from cimhub_raw.raw34_writer import Raw34Writer

case = Raw34Reader("cimhub_raw/tests/atoms/generator/step_up.raw").read_all()
network = raw_to_cim(case, name="atom")

for machine in network.graph[cim.SynchronousMachine].values():
    node = machine.Terminals[0].TopologicalNode
    load_sign = get_der_output(machine, "MW", "MVAr", sign="load").total
    generation_sign = get_der_output(machine, "MW", "MVAr", sign="generation").total
    print(machine.mRID, node.mRID, load_sign.p, generation_sign.p)

print(sorted(transformer.mRID for transformer in network.graph[cim.PowerTransformer].values()))

writer = Raw34Writer()
for record in RawExporter().to_model(network).list_by_class(schema.GeneratorRecord):
    print(writer.serialize(record))
sm_1_1 sm_1_1_int -150.0 150.0
sm_2_G1 sm_2_G1_int -80.0 80.0
sm_2_G2 2 -30.0 30.0
sm_4_1 sm_4_1_int -10.0 10.0
['pec_2_PV_xf', 'sm_1_1_xf', 'sm_2_G1_xf', 'sm_4_1_xf']
1,'1 ',150.000,20.000,100.000,-50.000,1.02000,1,200.000,0.0030000000000000005,,0.00200,0.12000,1.00000,1,100.0,180.000,0.000,,,,,,,,,0
2,'G1',80.000,15.000,60.000,-30.000,1.01000,3,100.000,0.00200,,0.0015000000000000002,0.10000,1.02500,1,100.0,90.000,-40.000,,,,,,,,,0
2,'G2',30.000,5.000,20.000,-10.000,1.01000,3,40.000,0.00000,,0.00000,0.00000,,1,100.0,35.000,0.000,,,,,,,,,0
2,'PV',40.000,5.000,20.000,-20.000,1.01000,3,50.000,,,0.00000,0.08000,1.00000,1,100.0,45.000,0.000,,,,,,,,,1
4,'1 ',10.000,2.000,8.000,-4.000,1.00000,4,12.000,0.00000,,0.010000000000000002,0.00000,1.00000,0,100.0,12.000,0.000,,,,,,,,,0

RT, XT and GTAP come back from the transformers: 2 G1 has GTAP 1.025 from its fixed tap, and the machine 2 G2 has no step-up, so its GTAP is blank. The ZX field, just before RT, is blank for every record, and the last field is WMOD: 1 for the converter PV, 0 for the machines. IREG is 1, 3, 3, 3 and 4: the plants at buses 1 and 4 regulate their own bus, which the source wrote as 0.

This example converts the renewables atom and prints each connection's plant control:

import cimprofiles.cim18.cim18v17 as cim

from cimhub_core.getters.control import get_regulating_control
from cimhub_raw.importer.raw_to_cimtbl import raw_to_cim
from cimhub_raw.raw34_reader import Raw34Reader

case = Raw34Reader("cimhub_raw/tests/atoms/generator/renewables.raw").read_all()
network = raw_to_cim(case, name="atom")

for connection in network.graph[cim.PowerElectronicsConnection].values():
    control = connection.RegulatingControl
    print(connection.mRID, control.mRID, control.mode.name, get_regulating_control(control).target)
pec_2_W gc_2 voltage 232300.0
pec_4_W1 gc_4 voltage 13800.0
pec_5_S gc_5 powerFactor 0.99
pec_6_S2 gc_6 powerFactor -0.905

pec_2_W and pec_4_W1 are WMOD 2 and hold their plant's voltage (232.3 kV and 13.8 kV); pec_5_S and pec_6_S2 are WMOD 3 at WPF 0.99 and -0.905.

Generator excerpts

From cimhub_raw/tests/goldens/IEEE14/generator.cimtbl, the artifact of the IEEE 14 bus case. Bus 1 is the swing bus (referencePriority 1):

# one per plant (bus I); targetValue in V (voltage) or a power factor (powerFactor, a WMOD 3 plant)
Table RegulatingControl: mRID, name, mode, discrete, enabled, targetValue, Terminal
    gc_1, 1, voltage, false, true, 146280.0,           bb_1_T1
    gc_2, 2, voltage, false, true, 144209.99999999997, bb_2_T1
    ...

Table GeneratingUnit: mRID, name, maxOperatingP (MW), minOperatingP (MW), EquipmentContainer
    gu_1_1, 1_1, 10000.0, -10000.0, sub_1
    ...

# WMOD 0
# untranscribed: zx, o1, o2, o3, o4, f1, f2, f3, f4
Table SynchronousMachine: mRID, name, bus, p (MW), q (MVAr), maxQ (MVAr), minQ (MVAr), ratedS (MVA), ratedU (kV), r (ohm), qPercent, referencePriority, inService, controlEnabled, RegulatingControl, GeneratingUnit, BaseVoltage, EquipmentContainer
    # defaulted: wmod=0, wpf=1.0, nreg=0
    sm_1_1, 1_1, 1, -232.392, 16.549,  0.0,  0.0,   615.0, 138.0, 0.0, 100.0, 1, true, true, gc_1, gu_1_1, bv_138kv, sub_1
    # defaulted: wmod=0, wpf=1.0, nreg=0
    sm_2_1, 2_1, 2, -40.0,    -43.556, 50.0, -40.0, 60.0,  138.0, 0.0, 100.0, ,  true, true, gc_2, gu_2_1, bv_138kv, sub_2
    ...

The step-up and the fixed tap, from the artifact the importer writes for cimhub_raw/tests/atoms/generator/step_up.raw (machine 2 G1: RT + jXT = 0.0015 + j0.1 on MBASE 100, GTAP 1.025, on a 115 kV bus):

Table TopologicalNode: mRID, name, BaseVoltage, ConnectivityNodeContainer
    sm_2_G1_int, 2_G1 terminal, bv_115kv, sub_2

Table PowerTransformerEnd: mRID, name, bus, endNumber, ratedU (kV), ratedS (MVA), r (ohm), x (ohm), BaseVoltage, PowerTransformer
    sm_2_G1_xf_1, 2_G1_1, 2,           1, 115.0, 100.0, 0.19837500000000002, 13.225, bv_115kv, sm_2_G1_xf
    sm_2_G1_xf_2, 2_G1_2, sm_2_G1_int, 2, 115.0, 100.0, ,                    ,       bv_115kv, sm_2_G1_xf

Table RatioTapChanger: mRID, name, lowStep, highStep, neutralStep, neutralU (kV), step, ltcFlag, controlEnabled, TransformerEnd
    sm_2_G1_xf_tap1, 2_G1_1, 1, 1, 1, 117.87499999999999, 1, false, false, sm_2_G1_xf_1

The power factor plants, from the artifact for cimhub_raw/tests/atoms/generator/renewables.raw:

Table RegulatingControl: mRID, name, mode, discrete, enabled, targetValue, Terminal
    gc_2, 2, voltage,     false, true, 232300.0, bb_3_T1
    # untranscribed: regulated_voltage_setpoint=1.02, regulated_bus_number=3
    gc_5, 5, powerFactor, false, true, 0.99,
    ...

Table PowerElectronicsConnection: mRID, name, bus, p (MW), q (MVAr), maxQ (MVAr), minQ (MVAr), ratedS (MVA), ratedU (kV), inService, controlEnabled, RegulatingControl, BaseVoltage, EquipmentContainer
    # untranscribed: rmpct=50.0, wpf=0.95
    pec_2_W, 2_W, 2, -60.0, -5.0,    19.721, -19.721, 70.0, 13.8, true, true, gc_2, bv_13p8kv, sub_2
    pec_5_S, 5_S, 5, -40.0, -5.6997, 5.6997, 5.6997,  45.0, 13.8, true, true, gc_5, bv_13p8kv, sub_5
    ...

Update Table RegulatingControl: mRID, Terminal
    gc_5, pec_5_S_T1