Generators¶
This page is the conversion reference for the RAW Generator table: the machines at a bus, their voltage control, their limits, the renewable and power factor forms, and the implicit step-up transformer. One RAW record becomes one machine or one converter connection with its unit, and the records at one bus share a plant control. The field classes (copied, mapped, structural, derived, untranscribed) and the conventions every section follows are on the reference index. The getters the exporter reads through, and the generation sign rule they apply, are on the core site's distributed energy resources page.
| RAW table | CIM classes | .cimtbl artifact and shape |
Importer | Exporter |
|---|---|---|---|---|
| Generator, WMOD 0 | SynchronousMachine, GeneratingUnit, ControlAreaGeneratingUnit |
generator.cimtbl, shape synchronous_machine with bus |
importer/cimtbl/generator.py |
exporter/generator.py |
| Generator, WMOD 1, 2, 3 | PowerElectronicsConnection, PowerElectronicsUnit, ControlAreaPowerElectronicsUnit |
generator.cimtbl, shape der with bus |
importer/cimtbl/generator.py |
exporter/generator.py |
| Generator, one per bus | RegulatingControl, the plant's |
generator.cimtbl |
importer/cimtbl/generator.py |
exporter/generator.py |
| Generator, RT + jXT other than 0 | PowerTransformer with two PowerTransformerEnds, an internal TopologicalNode, and a fixed RatioTapChanger when GTAP is not 1 |
generator.cimtbl, shape behind_transformer |
importer/cimtbl/generator.py |
exporter/generator.py |
The table shapes are on the core site's shapes page.
Source paths are under
cimhub_raw/src/cimhub_raw/. The
master imports generator.cimtbl after the load and fixed shunt artifacts and before the transformer ones. A switched
shunt that regulates a plant's reactive power reads the machine from this table (see Loads and shunts). The
bus a machine sits on, its area and its IDE come from the bus tables (see
Case, buses, areas and zones).
Quoted error messages start with the record, as 1_1: or plant 2:. A generator's key is its bus number and ID, and
the name the importer gives it is <I>_<ID>; a blank ID is 1.
The examples run from the repository root with UV_FROZEN=1 uv run python. They convert the public test atoms in
cimhub_raw/tests/atoms/generator
to CIM and back.
Records, plants and classes¶
PSS/E treats VS, IREG and RMPCT as plant quantities: every machine at bus I shares them, and the plant's output and
limits are the sums over its machines in service. The importer follows that. Each bus with generator records gets one
RegulatingControl gc_<I>, and every machine and connection at the bus names it. The control cannot be cc_<I>,
which is the switched shunt's control, because one bus can have both.
WMOD picks the class of each record:
| WMOD | CIM, per record | Plant control |
|---|---|---|
| 0 conventional | SynchronousMachine sm_<I>_<ID>, GeneratingUnit gu_<I>_<ID>, ControlAreaGeneratingUnit cagu_<I>_<ID> |
voltage |
| 1 renewable, limits QT and QB | PowerElectronicsConnection pec_<I>_<ID>, PowerElectronicsUnit pecu_<I>_<ID>, ControlAreaPowerElectronicsUnit capu_<I>_<ID> |
voltage |
| 2 renewable, limits from WPF | as WMOD 1, with WPF listed on the row | voltage |
| 3 renewable, fixed power factor | as WMOD 1 | power factor |
| 4 infeed | raises NotImplementedError |
|
| any other value | raises |
A blank WMOD is 0. The PowerElectronicsUnit has no kind: RAW cannot say whether a converter plant is solar or wind,
so the importer writes neither PhotoVoltaicUnit nor PowerElectronicsWindUnit. A concentrating solar plant that
PSS/E models as a conventional machine is WMOD 0, and lands on SynchronousMachine and GeneratingUnit. RAW cannot
mark a type 1 or 2 wind plant, an induction machine, entered as WMOD 1: it is a converter connection here. Each unit
joins the ControlArea ca_<AREA of bus I>; a generator record has no AREA of its own. A bus AREA with no Area
interchange record raises.
Plant voltage control¶
For WMOD 0, 1 and 2 the plant control is:
RegulatingControl attribute |
Value |
|---|---|
| mRID, name | gc_<I>, <I> |
mode, discrete |
voltage, false |
targetValue |
VS x the BASKV of the regulated bus, in volts (232300.0 for VS 1.01 on 230 kV); blank VS is 1.0 |
targetDeadband |
blank: PSS/E holds VS exactly |
Terminal |
the busbar terminal bb_<IREG>_T1, or bb_<I>_T1 when IREG is 0 or I; NREG other than 0 names a node of bus IREG and the terminal is that node's busbar (see Substations and node-breaker data) |
enabled |
true when the bus's IDE is 2 or 3; every member's controlEnabled follows it |
The product VS x BASKV can leave a last-digit float residue (144209.99999999997 for 1.045 on 138 kV) and is written
as computed. A plant on an IDE 1 bus has its control disabled. IDE 3 is the swing bus: every SynchronousMachine at
the bus gets referencePriority 1, the angle reference's highest priority, and the exporter writes IDE 3 for a bus
with such a machine. A bus with an enabled plant control exports as IDE 2, and any other as IDE 1.
The plant's records must agree on VS, IREG, NREG and RMPCT, as PSS/E requires. A swing bus must regulate itself, because PSS/E would silently regulate bus I instead.
Sign, limits and rating¶
CIM's terminal p and q are positive into the equipment, so a generator's are negative. The importer writes
p (MW) = -PG and q (MVAr) = -QG on both classes, and keeps zero as 0.0. The limits stay in the generator
convention, as CIM defines them, and are copied: maxQ = QT, minQ = QB, and PT and PB are
GeneratingUnit.maxOperatingP and minOperatingP, or PowerElectronicsUnit.maxP and minP. A negative PB, a pumping
machine, is copied as it is. The exporter asks the getters for sign="generation" and so writes PG and QG positive
again.
| CIM value | From |
|---|---|
ratedS (MVA) |
MBASE; a blank MBASE is SBASE |
ratedU (kV) |
BASKV of bus I: RAW has no machine voltage, and MBASE and ZR are on BASKV |
r (ohm), a SynchronousMachine only |
ZR x BASKV^2 / MBASE |
qPercent, a SynchronousMachine only |
RMPCT, on every machine of the plant |
inService |
STAT == 1 on the machine or connection; the unit has no status of its own |
ZX is untranscribed: cim18v17's SynchronousMachine has no positive-sequence reactance. On a
PowerElectronicsConnection, ZR and RMPCT have no CIM attribute; the row lists them when they are not 0 and 100
(# untranscribed: zr=0.01).
Renewable machines¶
A WMOD 1, 2 or 3 record is a PowerElectronicsConnection with its unit, and the three differ in the limits and the
control:
| WMOD | Reactive limits | Plant control | What the row says |
|---|---|---|---|
| 1 | maxQ, minQ = QT, QB |
voltage, as above | nothing extra |
| 2 | maxQ, minQ = QT, QB as written; RAW sets them from PG and WPF, which CIM cannot express, so they do not follow a later change of p |
voltage, as above | # untranscribed: wpf=0.95, always, so the importer's own output tells WMOD 2 from 1 |
| 3 | QT, QB as written | mode powerFactor, discrete false, targetValue = WPF as read, enabled as above |
# untranscribed: regulated_voltage_setpoint=1.02, regulated_bus_number=3 when VS, IREG or NREG is off its default |
A WMOD 3 plant holds the connection's power factor, not a voltage. The sign of WPF is kept: a positive WPF means q
has the sign of p, under the generator or the load sign alike. The control sits on the connection's own terminal,
pec_<I>_<ID>_T1, where its power factor is. The connection row names the control, so the control row is written
with no Terminal and an Update RegulatingControl row after the connection table sets it. VS, IREG and NREG are
not used by a fixed power factor. A plant that mixes WMOD 3 with any other record raises, because one control holds
either a voltage or one connection's power factor.
On export a PowerElectronicsConnection is WMOD 3 with WPF = the control's targetValue when its control is
powerFactor, and WMOD 1 otherwise. WMOD 2 comes back as 1, with WPF blank.
The implicit step-up transformer¶
RT + jXT other than 0 is PSS/E's implicit step-up between bus I and the machine, with GTAP the off-nominal ratio at bus
I. The importer writes the transformer as data, in the core behind_transformer shape, with the machine on an internal
node:
| CIM class | mRID | Attributes |
|---|---|---|
TopologicalNode |
<machine>_int |
name <I>_<ID> terminal; no bus number; bus I's BaseVoltage and substation |
PowerTransformer |
<machine>_xf |
name <I>_<ID> step-up; always in service |
PowerTransformerEnd 1 |
<machine>_xf_1 |
on bus I; ratedU (kV) = BASKV; ratedS (MVA) = MBASE; r (ohm) = RT x BASKV^2 / MBASE; x (ohm) = XT x BASKV^2 / MBASE |
PowerTransformerEnd 2 |
<machine>_xf_2 |
on the internal node; ratedU (kV) = BASKV; ratedS (MVA) = MBASE; no r, x |
RatioTapChanger, GTAP other than 1 |
<machine>_xf_tap1 |
on end 1; one fixed step (lowStep, highStep, neutralStep, step all 1, ltcFlag and controlEnabled false); neutralU (kV) = GTAP x BASKV |
<machine> is sm_<I>_<ID> or pec_<I>_<ID>. The machine's terminal is on the internal node. RAW gives no terminal
voltage for the machine, because XTRAN and GTAP are per unit on MBASE and the system base, so the internal node and end
2 keep bus I's BaseVoltage, a per-unit equivalent. The machine's ratedU is the same. There is no magnetizing
branch.
Power, limits and control stay on the machine. The plant control stays on bus I's busbar, because PSS/E's power flow injects PG + jQG at bus I and uses XTRAN only in fault and dynamics studies. A CIM solve that includes the step-up will therefore see its losses, which the RAW solution does not: an expected difference when solving, not when converting.
GTAP is used only with a step-up. Without one PSS/E ignores it, so the importer lists it on the machine row when it is
not 1 (# untranscribed: gtap=1.02).
On export a machine whose terminal node has no bus number sits behind a step-up, and the exporter folds it back:
| Check | Rule |
|---|---|
| the node | holds the machine and exactly one PowerTransformer whose other end is on a numbered bus |
| the transformer | in service, two windings, no core admittance, winding 1 on the bus and winding 2 on the machine's node |
| the ratings | each end's ratedU equals its node's BaseVoltage |
| the tap | only a fixed RatioTapChanger on winding 1 |
| the values | RT = the windings' r summed, XT = the mesh x, both per unit on MBASE; GTAP = neutralU / ratedU of end 1, or 1 with no tap |
The transformer exporter leaves these transformers out, so each is exported once, as the machine's RT, XT and GTAP. Anything else raises.
Generator fields¶
| RAW field | Import | Export |
|---|---|---|
| I | structural: the machine's bus, BaseVoltage, EquipmentContainer and ControlArea; the plant key gc_<I>; IDE sets enabled and referencePriority |
the bus number of the machine's node, or of the bus across its step-up |
| ID | structural: key for the mRIDs, name <I>_<ID>; blank is 1 |
the ID in the mRID sm_<I>_<ID> or pec_<I>_<ID>, else the next free 1, 2, ... on the bus |
| PG | derived: p (MW) = -PG; blank is 0 |
the machine's p in generation sign |
| QG | derived: q (MVAr) = -QG; blank is 0 |
the machine's q in generation sign |
| QT | copied: maxQ (MVAr) of the machine or connection; blank is 9999 |
maxQ in generation sign; blank when unset |
| QB | copied: minQ (MVAr); blank is -9999 |
minQ in generation sign; blank when unset |
| VS | derived: the plant control's targetValue = VS x BASKV of the regulated bus, in V; blank is 1.0 |
the voltage control's target in kV over the regulated bus's BASKV; blank for WMOD 3 and for a plant with no control |
| IREG | structural: the plant control's Terminal; blank is 0 |
the bus number of the control's terminal, its own bus included (a RAW 0 comes back as I); blank for WMOD 3 and for a plant with no control |
| MBASE | copied: ratedS (MVA), with ratedU (kV) = BASKV; blank is SBASE |
the rating's ratedS |
| ZR | derived: r (ohm) of a SynchronousMachine = ZR x BASKV^2 / MBASE; listed on a connection's row when not 0; blank is 0 |
a machine's r in pu on its ratedU and ratedS; blank for a connection |
| ZX | untranscribed | not written |
| RT, XT | derived: the step-up's end 1 r (ohm), x (ohm); blank is 0 |
the step-up's r and x in pu on MBASE; 0 with no step-up |
| GTAP | derived: the fixed tap's neutralU (kV) = GTAP x BASKV; without a step-up listed when not 1; blank is 1.0 |
neutralU / ratedU of the step-up's tap, 1 with no tap; blank with no step-up |
| STAT | mapped: inService; blank is 1 |
0 when inService is false, else 1 |
| RMPCT | copied: SynchronousMachine.qPercent, on every machine of the plant; a connection lists it when not 100; blank is 100 |
the qPercent of the plant's machines on every record of the plant; blank for a plant of connections only |
| PT | copied: maxOperatingP (MW) or maxP (MW); blank is 9999 |
the unit's maximum in generation sign, as stored |
| PB | copied: minOperatingP (MW) or minP (MW); blank is -9999 |
the unit's minimum in generation sign, as stored, even when it is above PT |
| O1 to O4, F1 to F4 | untranscribed | not written |
| WMOD | mapped: the class, as in the table above; blank is 0 | 0 for a SynchronousMachine; 3 for a connection under a powerFactor control, else 1 |
| WPF | mapped: WMOD 2 always listed; WMOD 3 the control's targetValue; blank is 1.0 |
WMOD 3: the control's targetValue; else blank |
| NREG | structural: a node of bus IREG, as above; blank is 0 | not written |
Generator fail-fast rules¶
| Rule | Message |
|---|---|
| WMOD 4 | generator 1_1: WMOD 4 (infeed, fixed Q: no case has one yet) |
| any other WMOD | 1_1: wmod=9 has no mapping (known: 0, 1, 2, 3) |
| a STAT other than 0 or 1 | 1_1: status=2 has no mapping (known: 0, 1) |
| records of one plant that disagree | plant 2: generators 2_G and 2_PV disagree on (IREG, NREG, VS, RMPCT): (3, 0, 1.05, 100.0) vs (3, 0, 1.01, 100.0); PSS/E treats them as plant quantities |
| an IREG that is no bus | plant 1: IREG 77 is no bus |
| a swing bus that regulates another bus | plant 1: a swing bus regulates remote bus 3 (PSS/E would regulate bus 1 instead) |
| a swing bus with only converter records | plant 1: a swing bus with no SynchronousMachine (only converter records), so no referencePriority |
| a bus AREA with no Area interchange record | plant 1: AREA 9 has no area-interchange record (no ControlArea ca_9) |
| WMOD 3 beside another record | plant 2: WMOD 3 ['2_G'] shares the plant with other records; one control holds either a voltage or one connection's power factor (no case has one yet) |
| export: machines of one plant whose controls disagree | plant 2: its machines' controls disagree on (IREG, VS): [...]; PSS/E treats them as plant quantities |
export: machines whose qPercent disagree |
plant 2: its machines' qPercent disagree: [...]; RMPCT is a plant quantity |
| export: a control that is neither voltage nor a connection's power factor | RegulatingControl 'x' of SynchronousMachine 'y': mode ...; a plant regulates voltage, or a connection its power factor |
| export: a machine on a node with no bus number that is not a step-up | SynchronousMachine 'x': its TopologicalNode 'y' has no busNumber and holds [...]; a step-up's node holds the machine and one transformer |
export: a step-up out of service, with a core, with a moving tap, or rated off its node's BaseVoltage |
the message names the transformer and the rule, such as out of service; a RAW step-up has no status of its own |
One more case is not caught by a message: an explicit MBASE of 0 passes the importer's defaulting (only a blank MBASE
is SBASE) and stops with a bare ZeroDivisionError, in the ZR conversion of a SynchronousMachine or in the r and x of
a step-up. A connection with no step-up takes it through as ratedS 0.
Generator round trip¶
| What | Why |
|---|---|
| IREG 0 comes back as the bus's own number | CIM keeps the terminal, not whether RAW wrote 0 or I |
| a blank MBASE comes back as SBASE | the importer defaulted it |
| WMOD 2 comes back as 1 and its WPF comes back blank | CIM has no reactive limit that follows P; the row's note is not read back |
| a WMOD 3 record comes back without its VS and IREG | a fixed power factor does not use them |
| a WMOD 1 record's WPF other than 1 comes back blank | PSS/E uses WPF only in WMOD 2 and 3 |
| a connection's ZR and, in a plant of connections only, RMPCT come back blank | no CIM attribute |
| a GTAP other than 1 without a step-up comes back blank | PSS/E ignores it, and the row's note is not read back |
| ZX, O1 to O4, F1 to F4 and NREG come back blank | no CIM home, or not written |
| ZR, RT, XT and VS can differ in the last digit | per unit to ohm and per unit to volt conversions: relative error 1e-9 |
| a reversed PT and PB come back as written | the exporter returns the unit's limits as stored |
This example converts the step-up atom. It prints each machine's node and its p in both signs, the transformers, and
the exported records. The machine 2 G2 has GTAP 1.02 but no step-up, so it stays on bus 2:
import cimprofiles.cim18.cim18v17 as cim
import cimhub_raw.schema.raw_v34.raw34_schema as schema
from cimhub_core.getters.der import get_der_output
from cimhub_raw.exporter.cim_to_raw import RawExporter
from cimhub_raw.importer.raw_to_cimtbl import raw_to_cim
from cimhub_raw.raw34_reader import Raw34Reader
from cimhub_raw.raw34_writer import Raw34Writer
case = Raw34Reader("cimhub_raw/tests/atoms/generator/step_up.raw").read_all()
network = raw_to_cim(case, name="atom")
for machine in network.graph[cim.SynchronousMachine].values():
node = machine.Terminals[0].TopologicalNode
load_sign = get_der_output(machine, "MW", "MVAr", sign="load").total
generation_sign = get_der_output(machine, "MW", "MVAr", sign="generation").total
print(machine.mRID, node.mRID, load_sign.p, generation_sign.p)
print(sorted(transformer.mRID for transformer in network.graph[cim.PowerTransformer].values()))
writer = Raw34Writer()
for record in RawExporter().to_model(network).list_by_class(schema.GeneratorRecord):
print(writer.serialize(record))
sm_1_1 sm_1_1_int -150.0 150.0
sm_2_G1 sm_2_G1_int -80.0 80.0
sm_2_G2 2 -30.0 30.0
sm_4_1 sm_4_1_int -10.0 10.0
['pec_2_PV_xf', 'sm_1_1_xf', 'sm_2_G1_xf', 'sm_4_1_xf']
1,'1 ',150.000,20.000,100.000,-50.000,1.02000,1,200.000,0.0030000000000000005,,0.00200,0.12000,1.00000,1,100.0,180.000,0.000,,,,,,,,,0
2,'G1',80.000,15.000,60.000,-30.000,1.01000,3,100.000,0.00200,,0.0015000000000000002,0.10000,1.02500,1,100.0,90.000,-40.000,,,,,,,,,0
2,'G2',30.000,5.000,20.000,-10.000,1.01000,3,40.000,0.00000,,0.00000,0.00000,,1,100.0,35.000,0.000,,,,,,,,,0
2,'PV',40.000,5.000,20.000,-20.000,1.01000,3,50.000,,,0.00000,0.08000,1.00000,1,100.0,45.000,0.000,,,,,,,,,1
4,'1 ',10.000,2.000,8.000,-4.000,1.00000,4,12.000,0.00000,,0.010000000000000002,0.00000,1.00000,0,100.0,12.000,0.000,,,,,,,,,0
RT, XT and GTAP come back from the transformers: 2 G1 has GTAP 1.025 from its fixed tap, and the machine 2 G2 has no
step-up, so its GTAP is blank. The ZX field, just before RT, is blank for every record, and the last field is WMOD:
1 for the converter PV, 0 for the machines. IREG is 1, 3, 3, 3 and 4: the plants at buses 1 and 4 regulate their own
bus, which the source wrote as 0.
This example converts the renewables atom and prints each connection's plant control:
import cimprofiles.cim18.cim18v17 as cim
from cimhub_core.getters.control import get_regulating_control
from cimhub_raw.importer.raw_to_cimtbl import raw_to_cim
from cimhub_raw.raw34_reader import Raw34Reader
case = Raw34Reader("cimhub_raw/tests/atoms/generator/renewables.raw").read_all()
network = raw_to_cim(case, name="atom")
for connection in network.graph[cim.PowerElectronicsConnection].values():
control = connection.RegulatingControl
print(connection.mRID, control.mRID, control.mode.name, get_regulating_control(control).target)
pec_2_W gc_2 voltage 232300.0
pec_4_W1 gc_4 voltage 13800.0
pec_5_S gc_5 powerFactor 0.99
pec_6_S2 gc_6 powerFactor -0.905
pec_2_W and pec_4_W1 are WMOD 2 and hold their plant's voltage (232.3 kV and 13.8 kV); pec_5_S and pec_6_S2 are
WMOD 3 at WPF 0.99 and -0.905.
Generator excerpts¶
From cimhub_raw/tests/goldens/IEEE14/generator.cimtbl, the artifact of the IEEE 14 bus case. Bus 1 is the swing bus
(referencePriority 1):
# one per plant (bus I); targetValue in V (voltage) or a power factor (powerFactor, a WMOD 3 plant)
Table RegulatingControl: mRID, name, mode, discrete, enabled, targetValue, Terminal
gc_1, 1, voltage, false, true, 146280.0, bb_1_T1
gc_2, 2, voltage, false, true, 144209.99999999997, bb_2_T1
...
Table GeneratingUnit: mRID, name, maxOperatingP (MW), minOperatingP (MW), EquipmentContainer
gu_1_1, 1_1, 10000.0, -10000.0, sub_1
...
# WMOD 0
# untranscribed: zx, o1, o2, o3, o4, f1, f2, f3, f4
Table SynchronousMachine: mRID, name, bus, p (MW), q (MVAr), maxQ (MVAr), minQ (MVAr), ratedS (MVA), ratedU (kV), r (ohm), qPercent, referencePriority, inService, controlEnabled, RegulatingControl, GeneratingUnit, BaseVoltage, EquipmentContainer
# defaulted: wmod=0, wpf=1.0, nreg=0
sm_1_1, 1_1, 1, -232.392, 16.549, 0.0, 0.0, 615.0, 138.0, 0.0, 100.0, 1, true, true, gc_1, gu_1_1, bv_138kv, sub_1
# defaulted: wmod=0, wpf=1.0, nreg=0
sm_2_1, 2_1, 2, -40.0, -43.556, 50.0, -40.0, 60.0, 138.0, 0.0, 100.0, , true, true, gc_2, gu_2_1, bv_138kv, sub_2
...
The step-up and the fixed tap, from the artifact the importer writes for cimhub_raw/tests/atoms/generator/step_up.raw
(machine 2 G1: RT + jXT = 0.0015 + j0.1 on MBASE 100, GTAP 1.025, on a 115 kV bus):
Table TopologicalNode: mRID, name, BaseVoltage, ConnectivityNodeContainer
sm_2_G1_int, 2_G1 terminal, bv_115kv, sub_2
Table PowerTransformerEnd: mRID, name, bus, endNumber, ratedU (kV), ratedS (MVA), r (ohm), x (ohm), BaseVoltage, PowerTransformer
sm_2_G1_xf_1, 2_G1_1, 2, 1, 115.0, 100.0, 0.19837500000000002, 13.225, bv_115kv, sm_2_G1_xf
sm_2_G1_xf_2, 2_G1_2, sm_2_G1_int, 2, 115.0, 100.0, , , bv_115kv, sm_2_G1_xf
Table RatioTapChanger: mRID, name, lowStep, highStep, neutralStep, neutralU (kV), step, ltcFlag, controlEnabled, TransformerEnd
sm_2_G1_xf_tap1, 2_G1_1, 1, 1, 1, 117.87499999999999, 1, false, false, sm_2_G1_xf_1
The power factor plants, from the artifact for cimhub_raw/tests/atoms/generator/renewables.raw:
Table RegulatingControl: mRID, name, mode, discrete, enabled, targetValue, Terminal
gc_2, 2, voltage, false, true, 232300.0, bb_3_T1
# untranscribed: regulated_voltage_setpoint=1.02, regulated_bus_number=3
gc_5, 5, powerFactor, false, true, 0.99,
...
Table PowerElectronicsConnection: mRID, name, bus, p (MW), q (MVAr), maxQ (MVAr), minQ (MVAr), ratedS (MVA), ratedU (kV), inService, controlEnabled, RegulatingControl, BaseVoltage, EquipmentContainer
# untranscribed: rmpct=50.0, wpf=0.95
pec_2_W, 2_W, 2, -60.0, -5.0, 19.721, -19.721, 70.0, 13.8, true, true, gc_2, bv_13p8kv, sub_2
pec_5_S, 5_S, 5, -40.0, -5.6997, 5.6997, 5.6997, 45.0, 13.8, true, true, gc_5, bv_13p8kv, sub_5
...
Update Table RegulatingControl: mRID, Terminal
gc_5, pec_5_S_T1
See also¶
- Loads and shunts: the switched shunts that regulate a plant's reactive power.
- Transformers and impedance correction: the transformer records, which the exporter keeps apart from the step-up transformers.
- Import mapping spec and export mapping spec: the design record, with the field-by-field classification.