What converts¶
Which PSS/E RAW v34 tables import and export today. The source of truth is the code: the importer's mappers are listed
in MAPPING_ORDER in importer/raw_to_cimtbl.py, the master document it writes first is built in the same file, the
equipment-terminal step runs after the mappers, and the exporter's modules are in EXPORT_ORDER in
exporter/cim_to_raw.py. The tables that only fail fast are in importer/cimtbl/phase2.py. The table below follows
those lists. Field-level detail is in the import mapping and the
export mapping, where every field is classified. Each table links to the
conversion reference page that describes it.
Tables that convert¶
The importer writes one .cimtbl document per RAW table, named for the table (bus.cimtbl), and a master that
imports them in this order: catalogs and containers before the equipment that uses them. A table with no records
writes no document and no Import. The exporter reads the whole network once and each module writes its RAW records.
| RAW table | CIM classes (cim18v17) | Import | Export | Reference |
|---|---|---|---|---|
| Case identification, system-wide data, RATING | BasePower, BaseFrequency, GeographicalRegion, BaseVoltage, OperationalLimitType |
the master | case_identification |
buses |
| Zone | SubGeographicalRegion |
zone.cimtbl |
zone |
buses |
| Area interchange | ControlArea; the inter-area transfers are listed on its comment |
area_interchange.cimtbl |
area_interchange |
buses |
| Bus | Substation, TopologicalNode, BusbarSection, OperationalLimitSet, VoltageLimit, SvVoltage |
bus.cimtbl |
bus |
buses |
| Substation, node, switching device | ConnectivityNode, Switch, Breaker, Disconnector, Location, a BusbarSection per regulated node |
substation.cimtbl |
not exported | substations |
| Non-transformer branch | ACLineSegment, SeriesCompensator, LinearShuntCompensator for line shunts, OperationalLimitSet, TieFlow |
branch.cimtbl |
branch |
branches |
| System switching device | Switch, Breaker, Disconnector |
switch.cimtbl |
switch |
branches |
| Multi-section line grouping | Line |
multi_section_line.cimtbl |
multi_section_line |
branches |
| Load | ConformLoad, NonConformLoad, LoadResponseCharacteristic, LoadArea, SubLoadArea, load groups |
load.cimtbl |
load |
loads |
| Fixed shunt | LinearShuntCompensator |
fixed_shunt.cimtbl |
fixed_shunt |
loads |
| Generator | SynchronousMachine, GeneratingUnit, PowerElectronicsConnection, PowerElectronicsUnit, RegulatingControl, a step-up PowerTransformer |
generator.cimtbl |
generator |
generators |
| Impedance correction | ImpedanceTapChangerTable, ImpedanceTapChangerTablePoint |
impedance_correction.cimtbl |
impedance_correction |
transformers |
| Transformer | PowerTransformer, PowerTransformerEnd, TransformerMeshImpedance, RatioTapChanger, PhaseTapChangerLinear, TapChangerControl, ImpedanceTapChangerTabular |
transformer.cimtbl |
transformer |
transformers |
| Two-terminal DC | DCLine, DCLineSegment, DCTopologicalNode, CsConverter, a converter PowerTransformer |
two_terminal_dc.cimtbl |
not exported | dc |
| VSC DC | DCLine, DCLineSegment, DCTopologicalNode, VsConverter, VsCapabilityCurve |
vsc_dc.cimtbl |
not exported | dc |
| Multi-terminal DC | none | raises | not exported | dc |
| FACTS device | StaticSynchronousCompensator, RegulatingControl |
facts_device.cimtbl |
facts_device |
dc |
| Switched shunt | LinearShuntCompensator per block, RegulatingControl; MODSW 2 of one reactor and one capacitor step: StaticVarCompensator |
switched_shunt.cimtbl |
switched_shunt |
loads |
| GNE device | none | raises | not exported | dc |
| Induction machine | none | raises | not exported | dc |
| Equipment terminal | Terminal (an Update row) |
equipment_terminal.cimtbl, last |
not exported | substations |
The switched shunt follows the FACTS device because a switched shunt that controls a plant's or a FACTS device's
reactive power names that device's terminal. The exporter's modules, in EXPORT_ORDER: case_identification, zone,
area_interchange, bus, branch, switch, multi_section_line, load, fixed_shunt, switched_shunt,
generator, transformer, impedance_correction.
Notes:
- A RAW table that no mapper reads is counted in the master's
not mapped:comment, so a record class never disappears silently. - A case that reaches the exporter with conducting equipment of a class no module writes raises
(
no RAW export yet for {...}). Today that is every DC converter. The substation data is not covered by that check; see the next note. - The exporter writes no node-breaker data. A case with SUBSTATION blocks exports its buses and equipment, each on its bus, and the blocks, nodes, switching devices and equipment terminals are not in the output. The export logs a warning that counts the switches it leaves out.
- Quantities are written in the unit RAW uses and the unit is in the
.cimtblcolumn header. Per-unit values on the system base are written as(pu system)and converted by cimtables on the case'sBasePower.
Untranscribed as a whole¶
These are read, counted or listed in a comment, and have no CIM home in the profile.
| what | where it goes |
|---|---|
| Owner records and every owner field (bus OWNER, O1 to O4 and F1 to F4 on other records) | counted in the master comment; no document; the export writes none |
| Solution options: GAUSS, NEWTON, ADJUST, TYSL, SOLVER | named in the master comment; the GENERAL record is read only for THRSHZ, the substation grouping threshold |
| Case title lines | the first goes on the master comment |
| Inter-area transfers | listed on the ControlArea comment of area_interchange.cimtbl; lost on export |
| An area's slack bus (ISW) | untranscribed |
Records that raise¶
| record | raises |
|---|---|
| Case identification with IC other than 0 | a change case is not a model |
| Multi-terminal DC, GNE device, induction machine | NotImplementedError, naming the table and its record count; a case without them converts |
| FACTS device with a series element (J other than 0) | raises: only a shunt-only device is mapped |
| Equipment terminal of TYP I, D, V, N or A | NotImplementedError; any other unknown TYP is a ValueError |
| A bus with BASKV blank or not positive | raises |
| A network with DC converters, on export | no RAW export yet for {...} |
Unmapped codes (a switching-device TYPE, a transformer CZ or CM, a generator WMOD) and unresolved references (an AREA with no area-interchange record, a node on no bus) raise as well, naming the record and the value.
CIM 18 gaps¶
What the profile cannot hold, and what the importer does instead:
- a bus's zone membership: a substation never spans two zones;
- a bus's own control area and an area's slack bus: the export traces AREA from generating units and tie flows, and lists a bus it cannot reach;
- the area or zone of machines and DC equipment, and a load's zone when it differs from its bus's: loads sit in a
LoadAreaandSubLoadAreaper area and zone, the rest is untranscribed; - ownership of network equipment: untranscribed;
- the metered end of a branch, switch or multi-section line, and a transformer's NMETR: recorded by the
TieFlows of a tie, untranscribed elsewhere; - a scheduled transfer between two control areas: listed on the
ControlAreacomment; - a shunt switched with its line in a bus-branch model: a
LinearShuntCompensatorper end, linked by its mRID; - a node's in-service status, a substation's DC grounding resistance, and a solved voltage per node of a split bus: listed on the row or untranscribed;
- a shunt's or converter's share of a coordinated voltage control (RMPCT): untranscribed, or listed when not 100;
- a converter's reactive limits that follow its active power (WPF on WMOD 2): written as given, WPF listed;
- the kind of a renewable bus-branch generator (PV, wind, induction machine): a
PowerElectronicsConnectionwith no kind; - a machine's positive-sequence reactance (ZX): untranscribed;
- which side of a voltage-controlling winding its controlled bus is on (the sign of CONTk): the magnitude regulates and the sign is listed;
- a FACTS device's series element, and UPFC and IPFC, which have no CIM 18 class: raises;
- a VSC converter's minimum loss and power weighting factor, and a two-terminal DC line's mode-switch, margin, compounding and commutation settings: listed on the row when not the default.
Not gaps: a bus's voltage limits and its regulation sit on its BusbarSection's terminal, because CIM puts limits and
regulating controls on terminals. RAW does not say which nodes of a substation are busbars, so the importer adds a
BusbarSection only on a node a control regulates.