DC lines and FACTS devices

This page is the conversion reference for the RAW tables that hold power electronics on the network: FACTS devices, two-terminal DC lines and VSC DC lines, and for the three record types the importer does not map yet (multi-terminal DC, GNE devices and induction machines). FACTS devices are imported and exported; the two DC line tables are imported to CIM and are not exported. The last three raise when a case has any. The field classes (copied, mapped, structural, derived, untranscribed) and the conventions every section follows are on the reference index.

RAW table CIM classes .cimtbl artifact Importer Exporter
FACTS device, shunt only StaticSynchronousCompensator, RegulatingControl facts_device.cimtbl importer/cimtbl/facts_device.py exporter/facts_device.py
VSC DC line DCLine, DCLineSegment, DCTopologicalNode, VsConverter, VsCapabilityCurve, limits and tie flows vsc_dc.cimtbl importer/cimtbl/vsc_dc.py raises
Two-terminal DC line DCLine, DCLineSegment, DCTopologicalNode, CsConverter and its converter transformer two_terminal_dc.cimtbl importer/cimtbl/two_terminal_dc.py raises
Multi-terminal DC, GNE device, Induction machine none none importer/cimtbl/multi_terminal_dc.py, gne_device.py, induction_machine.py not applicable

The two DC tables share the DCLine, DCTopologicalNode, DCLineSegment, DCTerminal and ACDCConverterDCTerminal rows of importer/cimtbl/dc_topology.py, described next. The converter transformer of a two-terminal line uses the core behind_transformer shape; see the core site's shapes page. Source paths are under cimhub_raw/src/cimhub_raw/. The master imports the DC artifacts after the transformer artifact and facts_device.cimtbl before switched_shunt.cimtbl, so a switched shunt that regulates a FACTS device finds it (see Loads and shunts).

Quoted error messages start with the record, as FACTS device STATCOM-LOC: or two-terminal DC line DC-TIE:. The key of each table is its NAME, and the mRID prefixes are fd_ (FACTS device), vsc_ (VSC DC line) and dc2_ (two-terminal DC line).

The examples run from the repository root with UV_FROZEN=1 uv run python. They convert the public test atoms in cimhub_raw/tests/atoms/dc to CIM.

DC lines are not exported

The exporter does not write DC lines yet. RawExporter.to_model first checks that every piece of conducting equipment in the network has an exporting module, and it names the ones that do not, with their counts, so nothing is dropped silently. A network with a VSC converter or a current-source converter therefore raises before any record is made; the FACTS devices beside them are no longer named:

import cimprofiles.cim18.cim18v17 as cim

from cimhub_raw.exporter.cim_to_raw import RawExporter
from cimhub_raw.importer.raw_to_cimtbl import raw_to_cim
from cimhub_raw.raw34_reader import Raw34Reader

for atom in ("facts_vsc", "two_terminal"):
    case = Raw34Reader(f"cimhub_raw/tests/atoms/dc/{atom}.raw").read_all()
    network = raw_to_cim(case, name="atom")
    for cim_class in (cim.DCLine, cim.StaticSynchronousCompensator, cim.VsConverter, cim.CsConverter):
        print(cim_class.__name__, sorted(obj.mRID for obj in network.graph.get(cim_class, {}).values()))
    try:
        RawExporter().to_model(network)
    except ValueError as error:
        print(error)
DCLine ['vsc_VSC-OUT', 'vsc_VSC-TIE']
StaticSynchronousCompensator ['fd_STATCOM-LOC', 'fd_STATCOM-OUT', 'fd_STATCOM-REM']
VsConverter ['vsc_VSC-OUT_c1', 'vsc_VSC-OUT_c2', 'vsc_VSC-TIE_c1', 'vsc_VSC-TIE_c2']
CsConverter []
no RAW export yet for {'VsConverter': 4}
DCLine ['dc2_DC-B2B', 'dc2_DC-BLOCKED', 'dc2_DC-CURRENT', 'dc2_DC-TIE']
StaticSynchronousCompensator []
VsConverter []
CsConverter ['dc2_DC-B2B_i', 'dc2_DC-B2B_r', 'dc2_DC-BLOCKED_i', 'dc2_DC-BLOCKED_r', 'dc2_DC-CURRENT_i', 'dc2_DC-CURRENT_r', 'dc2_DC-TIE_i', 'dc2_DC-TIE_r']
no RAW export yet for {'CsConverter': 8}

A DCLine and its segment are not conducting equipment of the AC network, so only the converters are named. A case with any of them cannot be exported as a whole, and the DC tables below have "not exported" in the export column.

DC topology

Each DC line is bus-branch, as the AC buses are TopologicalNodes. For a line <line> (vsc_<NAME> or dc2_<NAME>):

CIM class mRID Attributes
DCLine <line> the container; name NAME
DCTopologicalNode <line>_n1, <line>_n2 <line>_n1 is at converter 1 (the rectifier of a two-terminal line); in the DCLine
DCLineSegment <line>_seg resistance (ohm) = RDC; inService; in the DCLine. An RDC of 0 is still a segment, and no back-to-back topology is inferred from it
DCTerminal <line>_seg_DC1, <line>_seg_DC2 the segment's two terminals on the two nodes
ACDCConverterDCTerminal <converter>_DC1 one per converter, on its node, polarity positive

RAW gives one equivalent pole, so there is no return path, and no DCConverterUnit because RAW says nothing of poles or operating mode. Each converter sits in the substation of its AC bus.

FACTS device

A shunt-only FACTS device, J = 0, is a StaticSynchronousCompensator fd_<NAME> with a voltage control fdc_<NAME>:

CIM attribute Value
bus I, with its BaseVoltage and substation
ratedI (kA) SHMX / (sqrt(3) x BASKV of bus I); SHMX is MVA at unity voltage; 0 stays 0, a device with no shunt; blank SHMX is 9999
inService MODE == 1
controlEnabled true
RegulatingControl fdc_<NAME>: mode voltage, discrete false, enabled true, targetValue = VSET x BASKV of the regulated bus, in volts; Terminal bb_<FCREG>_T1, with FCREG 0 meaning bus I, or the busbar of node NREG of bus FCREG

A device with a series element, J other than 0 (an SSSC, a UPFC or an IPFC), raises: UPFC and IPFC have no CIM 18 class. MODE 2 to 8 need such an element and raise too. A blank MODE is 1.

The exporter (exporter/facts_device.py, EXPORT_MAPPING.md E6a) writes one record per StaticSynchronousCompensator back, with J = 0 and the series element's fields blank. FCREG is the regulated bus's number, I included: an FCREG of 0 comes back as I. The FACTS atom comes back as:

import cimhub_raw.schema.raw_v34.raw34_schema as schema

from cimhub_raw.exporter import facts_device
from cimhub_raw.exporter.cim_to_raw import export_tables
from cimhub_raw.importer.raw_to_cimtbl import raw_to_cim
from cimhub_raw.raw34_reader import Raw34Reader

case = Raw34Reader("cimhub_raw/tests/atoms/dc/facts_vsc.raw").read_all()
for record in export_tables(raw_to_cim(case, name="atom"), (facts_device,)).list_by_class(schema.FactsDeviceRecord):
    print(record.name, record.ibus, record.jbus, record.mode, round(record.vset, 6), round(record.shmx, 6), record.remot)
STATCOM-LOC 202 0 1 1.02 100.0 202
STATCOM-OUT 102 0 0 1.0 0.0 102
STATCOM-REM 302 0 1 1.01 50.0 301

A continuous switched shunt of one reactor and one capacitor step is a StaticVarCompensator, not a FACTS device; see Loads and shunts.

FACTS device fields

RAW field Import Export
NAME structural: key fd_<NAME>, control fdc_<NAME>, name NAME written: name; unset or over 12 characters raises
I structural: bus, BaseVoltage, EquipmentContainer written: the terminal's bus
J structural: nonzero raises rule: 0
MODE mapped: inService = (MODE == 1); 2 to 8 raise; blank is 1 rule: 0 when inService is false, else 1
VSET derived: the control's targetValue = VSET x BASKV(FCREG), in V; blank is 1.0 written: the target over the regulated bus's BASKV
SHMX derived: ratedI (kA) written: sqrt(3) x BASKV x ratedI
FCREG structural: the control's Terminal; blank is 0 written: the regulated bus, I included
NREG structural: a node of bus FCREG; blank is 0 blank (node-breaker export is later)
PDES, QDES, TRMX, VTMN, VTMX, VSMX, IMX, LINX, SET1, SET2, VSREF, MNAME untranscribed: the series element's, which a shunt-only device does not use; listed on the row when not the default blank
RMPCT untranscribed: CIM 18 has no participation share for a shunt; listed on the row when not 100 blank
OWNER untranscribed blank

FACTS device fail-fast rules

Rule Message
J other than 0 FACTS device STATCOM-LOC: J 102, a series element (SSSC, UPFC or IPFC; no case has one yet, and UPFC/IPFC have no CIM 18 class)
MODE 2 to 8, or any value other than 0 and 1 FACTS device STATCOM-LOC: mode=2 has no mapping (known: 0, 1)
an FCREG that is no bus; the message also names I as FCREG when FCREG is 0 FACTS device STATCOM-LOC: FCREG 999 is no bus
export: the name unset or over 12 characters StaticSynchronousCompensator 'fd_X': name ... is no RAW NAME (1 to 12 characters), the FACTS device's key
export: no RegulatingControl, or one not of mode voltage StaticSynchronousCompensator 'fd_X': a FACTS device's shunt holds VSET; it needs a voltage RegulatingControl
export: the control or the device's controlEnabled false StaticSynchronousCompensator 'fd_X': its control is disabled; a shunt-only FACTS device has no locked mode

FACTS device excerpt

No golden has a FACTS device. From the artifact the importer writes for the atom cimhub_raw/tests/atoms/dc/facts_vsc.raw (STATCOM-REM regulates bus 301 and has TRMX 0 and RMPCT 75, both listed; STATCOM-OUT is MODE 0 with SHMX 0):

# one per device; targetValue in V
Table RegulatingControl: mRID, name, mode, discrete, enabled, targetValue, Terminal
    fdc_STATCOM-LOC, STATCOM-LOC, voltage, false, true, 234600.0, bb_202_T1
    fdc_STATCOM-OUT, STATCOM-OUT, voltage, false, true, 230000.0, bb_102_T1
    fdc_STATCOM-REM, STATCOM-REM, voltage, false, true, 232300.0, bb_301_T1

# shunt only (J = 0); ratedI = SHMX / (sqrt(3) x BASKV)
# untranscribed: pdes, qdes, trmx, vtmn, vtmx, vsmx, imx, linx, rmpct, owner, set1, set2, vsref, mname
Table StaticSynchronousCompensator: mRID, name, bus, ratedI (kA), inService, controlEnabled, RegulatingControl, BaseVoltage, EquipmentContainer
    fd_STATCOM-LOC, STATCOM-LOC, 202, 0.25102185616940254, true,  true, fdc_STATCOM-LOC, bv_230kv, sub_202
    fd_STATCOM-OUT, STATCOM-OUT, 102, 0.0,                 false, true, fdc_STATCOM-OUT, bv_230kv, sub_102
    # untranscribed: trmx=0.0, rmpct=75.0
    fd_STATCOM-REM, STATCOM-REM, 302, 0.25102185616940254, true,  true, fdc_STATCOM-REM, bv_115kv, sub_301

VSC DC line

A VSC DC line is the DC topology of vsc_<NAME> and a VsConverter vsc_<NAME>_c1 and _c2 on IBUS 1 and IBUS 2. MDC 0 sets inService false on the segment and on both converters. A blank MDC is 1.

Each converter has its own set of these fields. For converter k:

RAW field CIM
TYPE 0: inService false, DCSET listed on the row; 1: pPccControl udc and targetUdc (kV) = DCSET; 2: pPccControl pPcc and targetPpcc (MW) = -DCSET (RAW's positive DCSET feeds the AC network, and CIM uses the load sign)
MODE, ACSET 1: qPccControl voltagePcc and targetUpcc (kV) = ACSET x BASKV of the regulated bus; 2: qPccControl powerFactorPcc and targetPowerFactorPcc = ACSET; blank MODE is 1 and blank ACSET 1.0
ALOSS, BLOSS idleLoss (kW) and switchingLoss (kW/A), so the converter's loss is ALOSS + Idc x BLOSS
SMAX, IMAX an OperationalLimitSet <converter>_ratings on terminal <converter>_T1, typed as the first rating (olt_rate1), holding an ApparentPowerLimit <converter>_smax (MVA) and a CurrentLimit <converter>_imax (A); a value of 0 means unlimited and writes no limit
MAXQ, MINQ MODE 1: a VsCapabilityCurve <converter>_qcurve, curveStyle constantYValue, with one CurveData point at x = 0 (MW), y1 = MINQ and y2 = MAXQ (MVAr), so the limits hold at every P; MODE 2 does not use them
VSREG, NREG the converter's PccTerminal: MODE 1: bb_<VSREG>_T1, or bb_<IBUS>_T1 when VSREG is 0, or the busbar of node NREG; MODE 2: bb_<IBUS>_T1
RMPCT qShare, copied; blank is 100
MINLOSS, PWF no CIM home: listed on the converter's row when not 0 and 1.0

For a MODE 2 converter, VSREG, NREG, MAXQ and MINQ are not used and are listed when off their defaults.

Ties. A VSC line whose converters are in two areas is a tie. PSS/E makes the DC voltage converter (TYPE 1) the home end, and the two TieFlows go on the other converter's terminal <converter>_T1 (see Case, buses, areas and zones for the tie flows). A tie without exactly one TYPE 1 converter raises.

VSC DC line fields

The converter fields are listed once with k for 1 or 2.

RAW field Import Export
NAME structural: key for the line and its converters not exported
MDC mapped: inService of the segment and both converters; blank is 1 not exported
RDC copied: DCLineSegment.resistance (ohm) not exported
IBUS k structural: the converter's bus, BaseVoltage, EquipmentContainer; an IBUS that is no bus raises not exported
TYPE k mapped: pPccControl, as above; other values raise not exported
DCSET k derived: targetUdc (kV) for TYPE 1, targetPpcc (MW) = -DCSET for TYPE 2 not exported
MODE k mapped: qPccControl; blank is 1; other values raise not exported
ACSET k derived: targetUpcc (kV) or targetPowerFactorPcc not exported
ALOSS k copied: VsConverter.idleLoss (kW); blank is 0 not exported
BLOSS k copied: VsConverter.switchingLoss (kW/A); blank is 0 not exported
SMAX k, IMAX k structural: the limits of <converter>_ratings; 0 writes none not exported
MAXQ k copied: CurveData.y2value (MVAr) not exported
MINQ k copied: CurveData.y1value (MVAr) not exported
VSREG k, NREG k structural: PccTerminal not exported
RMPCT k copied: VsConverter.qShare not exported
MINLOSS k, PWF k untranscribed: listed when not the default not exported
O1 to O4, F1 to F4 untranscribed not exported

VSC DC line fail-fast rules

Rule Message
an IBUS or regulated bus that is no bus VSC DC line VSC-TIE: converter 1 IBUS 999 is no bus
a TYPE or MODE out of range VSC DC line VSC-TIE: converter_type_1=7 has no mapping (known: 0, 1, 2)
a tie without exactly one TYPE 1 converter VSC DC line VSC-TIE: a tie needs exactly one TYPE 1 (DC voltage) converter, its home end; TYPE 1 and 1
export no RAW export yet for {'VsConverter': 4, ...}, with every other unexported class of the network

VSC DC line excerpt

No golden has a VSC DC line. From the artifact the importer writes for the atom cimhub_raw/tests/atoms/dc/facts_vsc.raw. VSC-TIE is a tie between areas 1 and 2: converter 1 is TYPE 2 with limits, converter 2 is TYPE 1 and the home end. VSC-OUT is blocked (MDC 0):

# untranscribed: o1, o2, o3, o4, f1, f2, f3, f4, minloss_1, pwf_1, minloss_2, pwf_2
Table DCLine: mRID, name
    vsc_VSC-OUT, VSC-OUT
    vsc_VSC-TIE, VSC-TIE

# resistance = RDC
Table DCLineSegment: mRID, name, resistance (ohm), inService, EquipmentContainer
    vsc_VSC-OUT_seg, VSC-OUT, 16.0, false, vsc_VSC-OUT
    vsc_VSC-TIE_seg, VSC-TIE, 1.58, true,  vsc_VSC-TIE

# targetPpcc = -DCSET (load sign); targetUpcc = ACSET x BASKV(VSREG or IBUS)
Table VsConverter: mRID, name, bus, inService, pPccControl, targetUdc (kV), targetPpcc (MW), qPccControl, targetUpcc (kV), targetPowerFactorPcc, idleLoss (kW), switchingLoss (kW/A), qShare, PccTerminal, BaseVoltage, EquipmentContainer
    # untranscribed: pwf_1=0.5
    vsc_VSC-TIE_c1, VSC-TIE_1, 102, true,  pPcc, ,      -96.0, voltagePcc,     234.6, ,     1600.0, 3.4,   100.0, bb_102_T1, bv_230kv, sub_102
    # untranscribed: minloss_2=1110.0
    vsc_VSC-TIE_c2, VSC-TIE_2, 202, true,  udc,  300.0, ,      powerFactorPcc, ,      0.95, 615.0,  2.527, 100.0, bb_202_T1, bv_230kv, sub_202
    ...

Table CurveData: identifier, Curve, xvalue, y1value, y2value
    vsc_VSC-TIE_c1_qcurve_1, vsc_VSC-TIE_c1_qcurve, 0.0, -100.0, 200.0

Table TieFlow: mRID, name, positiveFlowIn, ControlArea, Terminal
    tf_1_vsc_VSC-TIE_c1_T1, 1_VSC-TIE_T1, false, ca_1, vsc_VSC-TIE_c1_T1
    tf_2_vsc_VSC-TIE_c1_T1, 2_VSC-TIE_T1, true,  ca_2, vsc_VSC-TIE_c1_T1

Two-terminal DC line

A two-terminal line is the DC topology of dc2_<NAME> and two CsConverters: the rectifier dc2_<NAME>_r on the DC node _n1, and the inverter dc2_<NAME>_i on _n2. Each converter sits behind a converter transformer that RAW gives as data (EBAS, TR, TAP and its range, RC and XC per bridge). The transformer joins the AC bus to an internal valve-side TopologicalNode <converter>_int and the converter sits on that node.

Control. MDC sets what the rectifier holds, and the inverter always holds its DC voltage:

MDC Rectifier pPccControl Order
0 blocked none inService false on the segment and both converters (the transformers stay in service); SETVL is listed on the DCLine row, since its unit depends on the mode it was blocked from
1 power activePower SETVL 0 or above: targetPpcc (MW) on the rectifier; SETVL < 0: targetPpcc = SETVL on the inverter, as given, because the load sign already makes an inverter's injection negative
2 current dcCurrent targetIdc (A) = SETVL on the rectifier

A blank MDC is 0. Any other MDC raises. The inverter's pPccControl is dcVoltage with targetUdc (kV) = VSCHD; a nonzero RCOMP is listed.

Converter. For converter e (R for the rectifier, I for the inverter):

CIM attribute Value
bus the internal node <converter>_int
operatingMode rectifier or inverter
numberOfValves 6 x NBe: six valves per bridge
maxAlpha, minAlpha (deg) the rectifier's ANMXR, ANMNR
maxGamma, minGamma (deg) the inverter's ANMXI, ANMNI
BaseVoltage EBASe x TRe, the valve side; the master adds these voltages to its BaseVoltage table

Converter transformer. One equivalent per converter, <converter>_xf, always in service. RAW gives RC and XC per bridge on the valve side and does not say how the NB bridges' transformers are built, so the importer takes their AC sides as in parallel:

CIM class Value
PowerTransformerEnd 1 <converter>_xf_1 on the AC bus IPe; ratedU (kV) = EBAS; r, x (ohm) = RC, XC / (NB x TR^2)
PowerTransformerEnd 2 <converter>_xf_2 on <converter>_int; ratedU (kV) = EBAS x TR; no ratedS, r or x
RatioTapChanger <converter>_xf_tap1 on end 1, ltcFlag and controlEnabled true; steps from TMN in steps of STP; stepVoltageIncrement = STP in percent; highStep = the last whole step at or below TMX; neutralStep = the step nearest ratio 1; step from TAP

The tap has no TapChangerControl: PSS/E moves TAP to hold the firing angle within its limits, and no CIM mode says that. A TMX that is not a whole number of STP steps above TMN is listed on the tap row (# untranscribed: tmxr=1.12 (the STP grid tops out at 1.1175)). Blank TR is 1.0, TAP 1.0, TMX 1.5, TMN 0.51 and STP 0.00625.

Ties. A line whose rectifier and inverter buses are in two areas is a tie. METER names the metered converter (R or I, blank is I); the TieFlow pair goes on that converter's transformer terminal <converter>_xf_T1 at the AC bus, and the other converter is the home end.

Listed, not mapped. VCMOD, RCOMP, DELTI, DCVMIN, CCCITMX and CCCACC have no CIM home and are listed on the DCLine row when not the default. ICR and NDR, the bus the firing angle is measured at, are listed on the converter row when not 0.

Two-terminal DC line fields

The converter fields are listed once with e for R (rectifier) or I (inverter): IPR and IPI, and so on.

RAW field Import Export
NAME structural: key for the line, its converters and transformers not exported
MDC mapped: the rectifier's pPccControl, as above; blank is 0 not exported
RDC copied: DCLineSegment.resistance (ohm); 0 is still a segment not exported
SETVL derived: targetPpcc (MW) or targetIdc (A), as above not exported
VSCHD copied: the inverter's CsConverter.targetUdc (kV) not exported
VCMOD, RCOMP, DELTI, DCVMIN, CCCITMX, CCCACC untranscribed: listed on the DCLine row when not the default not exported
METER structural: on a tie, the metered converter (R or I); blank is I not exported
IPe structural: end 1 of the converter transformer, its substation; the converter's AC bus not exported
NBe derived: numberOfValves = 6 x NB; divides the transformer's r and x not exported
ANMXR, ANMNR copied: CsConverter.maxAlpha, minAlpha (deg) not exported
ANMXI, ANMNI copied: CsConverter.maxGamma, minGamma (deg) not exported
RCe, XCe derived: end 1 r, x (ohm) = RC, XC / (NB x TR^2) not exported
EBASe copied: end 1 PowerTransformerEnd.ratedU (kV); with TR, end 2 and the internal node's voltage not exported
TRe derived: end 2 ratedU (kV) = EBAS x TR; blank is 1.0 not exported
TAPe derived: the tap's step on the STP grid; blank is 1.0 not exported
TMXe, TMNe, STPe derived: the tap's highStep, step 1 and stepVoltageIncrement; blank is 1.5, 0.51 and 0.00625 not exported
ICe, NDe untranscribed: listed on the converter row when not 0 not exported
IFe, ITe structural: nonzero raises not exported
IDe untranscribed: used only with IFe and ITe, which raise not exported
XCAPe structural: nonzero raises not exported

Two-terminal DC line fail-fast rules

Rule Message
an IPR or IPI that is no bus two-terminal DC line DC-TIE: rectifier IPR 999 is no bus
IFe or ITe other than 0, an AC transformer used as the converter transformer two-terminal DC line DC-TIE: IFR / ITR name an AC transformer as the rectifier transformer (COD +-4; no case has one yet)
XCAPe other than 0, a capacitor commutated converter two-terminal DC line DC-TIE: XCAPR 0.5, capacitor commutated (no case has one yet)
NBe below 1 two-terminal DC line DC-TIE: NBR 0 bridges
EBASe or TRe not above 0 two-terminal DC line DC-TIE: EBASI x TRI = 0.0 x 0.5 gives no valve-side voltage
STPe not above 0 two-terminal DC line DC-TIE: STP 0.0 must be positive
an MDC out of range, or on a tie a METER other than R or I two-terminal DC line DC-TIE: mdc=3 has no mapping (known: 0, 1, 2), two-terminal DC line DC-TIE: meter='X' has no mapping (known: I, R)
export no RAW export yet for {'CsConverter': 8, ...}, with every other unexported class of the network

Two-terminal DC line excerpt

No golden has a DC line. From the artifact the importer writes for the atom cimhub_raw/tests/atoms/dc/two_terminal.raw. DC-TIE is a tie between areas 1 and 2 with SETVL -250 (inverter power) and METER I; its rectifier's TMX is off the STP grid:

# end 1 at the AC bus: ratedU = EBAS, r = RC / (NB x TR^2), x = XC / (NB x TR^2); end 2 at the internal node: ratedU = EBAS x TR
Table PowerTransformerEnd: mRID, name, bus, endNumber, ratedU (kV), r (ohm), x (ohm), BaseVoltage, PowerTransformer
    dc2_DC-TIE_r_xf_1, DC-TIE_r_1, 102,              1, 230.0,              0.05206380797815381, 10.64663770146947, bv_230kv,    dc2_DC-TIE_r_xf
    dc2_DC-TIE_r_xf_2, DC-TIE_r_2, dc2_DC-TIE_r_int, 2, 138.94299999999998, ,                    ,                  bv_138p94kv, dc2_DC-TIE_r_xf
    ...

# TAP on the STP grid from TMN (converter_tap); no TapChangerControl: PSS/E holds the firing angle in range, which no CIM mode says
Table RatioTapChanger: mRID, name, lowStep, highStep, neutralStep, neutralU (kV), stepVoltageIncrement, step, ltcFlag, controlEnabled, TransformerEnd
    # untranscribed: tmxr=1.12 (the STP grid tops out at 1.1175)
    dc2_DC-TIE_r_xf_tap1, DC-TIE_r_1, 1, 20, 11, 231.14999999999998, 1.2499999999999998, 12.52000000000001, true, true, dc2_DC-TIE_r_xf_1
    ...

# on its internal node; numberOfValves = 6 x NB; the rectifier holds MDC's order (targetPpcc on the inverter when SETVL < 0), the inverter VSCHD
Table CsConverter: mRID, name, bus, inService, operatingMode, numberOfValves, maxAlpha (deg), minAlpha (deg), maxGamma (deg), minGamma (deg), pPccControl, targetPpcc (MW), targetIdc (A), targetUdc (kV), BaseVoltage, EquipmentContainer
    dc2_DC-TIE_r,     DC-TIE_r,     dc2_DC-TIE_r_int,     true,  rectifier, 12, 21.0, 17.0, ,     ,     activePower, ,       ,       ,      bv_138p94kv, sub_102
    dc2_DC-TIE_i,     DC-TIE_i,     dc2_DC-TIE_i_int,     true,  inverter,  12, ,     ,     18.0, 18.0, dcVoltage,   -250.0, ,       475.0, bv_115kv,    sub_201
    ...

Table TieFlow: mRID, name, positiveFlowIn, ControlArea, Terminal
    tf_2_dc2_DC-TIE_i_xf_T1, 2_DC-TIE_T2, false, ca_2, dc2_DC-TIE_i_xf_T1
    tf_1_dc2_DC-TIE_i_xf_T1, 1_DC-TIE_T2, true,  ca_1, dc2_DC-TIE_i_xf_T1

Record types that raise

Three RAW record types have no mapping yet. The importer raises for each, so a case that uses one fails at once and names the table instead of losing its records. The table is empty in most cases, and an empty section is read and imported without a message.

RAW table Where it raises Message
Multi-terminal DC the reader, when the section has a record <path>: the MULTI-TERMINAL DC section has <N> record(s); its layout is phase-2 work (...)
GNE device the reader, when the section has a record <path>: the GNE section has <N> record(s); its layout is phase-2 work (...)
Induction machine the importer, when the model has a record RAW InductionMachineRecord: <N> record(s), but the table is phase 2 and not mapped yet (...)

The parenthesis in each message points to the project plan. The importer also has a mapper for the first two (importer/cimtbl/multi_terminal_dc.py, gne_device.py) that raises in the induction machine's form for a model built in memory. Nothing of these tables is exported: none of them exists in CIM yet, so the exporter has nothing to read, and there is no .cimtbl artifact for them.

The raises are in the first two lines of this example, which adds one record of each kind to the IEEE 14 bus case:

from pathlib import Path

from cimhub_raw.importer.raw_to_cimtbl import raw_to_cim
from cimhub_raw.raw34_reader import Raw34Reader

IEEE14 = Path("cimhub_raw/tests/cases/IEEE14/IEEE_14_bus.raw")


def case_with(section_end: str, record: str, path: str) -> Path:
    """Copy the IEEE 14 bus case with one record added before the end of a section."""
    lines = IEEE14.read_text().splitlines()
    position = next(index for index, line in enumerate(lines) if line.startswith(section_end))
    lines.insert(position, record)
    Path(path).write_text("\n".join(lines) + "\n")
    return Path(path)


multi_terminal = case_with("0 / END OF MULTI-TERMINAL DC DATA", "'MT1',2,2,1,1,1", "/tmp/ieee14_mtdc.raw")
induction = case_with("0 / END OF INDUCTION MACHINE DATA", "2,'1 ',1,1,1,1,1,1", "/tmp/ieee14_induction.raw")

try:
    Raw34Reader(multi_terminal).read_all()
except NotImplementedError as error:
    print(str(error).partition(" (")[0])

try:
    raw_to_cim(Raw34Reader(induction).read_all(), name="IEEE14")
except NotImplementedError as error:
    print(str(error).partition(" (")[0])
/tmp/ieee14_mtdc.raw: the MULTI-TERMINAL DC section has 1 record(s); its layout is phase-2 work
RAW InductionMachineRecord: 1 record(s), but the table is phase 2 and not mapped yet

CIM 18 gaps

What CIM 18 cannot hold of these tables, and what the importer does instead:

Gap RAW fields What the importer does
a FACTS device's series element; UPFC and IPFC have no class J other than 0, MODE 2 to 8 raises; a shunt-only device lists its series fields when not the default
a FACTS shunt's share of a coordinated voltage control FACTS RMPCT listed on the row when not 100
a VSC converter's minimum loss and power weighting factor MINLOSS, PWF listed on the row when not the default
a two-terminal line's mode-switch voltage, margin, compounding, minimum DC voltage, constant-current-control settings and commutating bus; the tap's aim of holding the firing angle VCMOD, DELTI, RCOMP, DCVMIN, CCCITMX, CCCACC, ICR, NDR; TAP's control listed on the DCLine or converter row when not the default; the tap has no TapChangerControl
ownership OWNER, O1 to F4 untranscribed