cim18v17 → PSS/E RAW v34 export spec

Plan and decisions: .development/RAW_REWRITE_PLAN.md §9 (X1-X7, approved 2026-11-09). One section per sub-slice, each approved before its code. The exporter reads values only through the core getters (skill export-getters). The model it returns has the shape Raw34Reader.read_all() returns, so Raw34Writer writes a case that the reader and the importer read back. The import spec is CIMTBL_MAPPING.md; its "the exporter writes ..." notes are settled here, sub-slice by sub-slice.

E0: framework, case data, bus, zone, area (spec approved 2026-11-09; done 2026-11-09; E0-1 dead bays, requested by cim-topology 2026-11-28, user's choice for a stub's controlled shunt)

Layout

cimhub_raw/src/cimhub_raw/exporter/
    cim_to_raw.py           RawExporter(FormatExporter), EXPORT_ORDER, export_tables, cim_to_raw(network, path)
    identity.py             bus numbers, keyed IDs and numbers (X2), names (X2)
    area_trace.py           a bus's AREA from generating units and tie flows (R5, X5)
    case_identification.py  BasePower, BaseFrequency, rating-set OperationalLimitTypes -> the case record
    zone.py                 SubGeographicalRegion -> Zone
    area_interchange.py     ControlArea -> Area
    bus.py                  TopologicalNode (+ its BusbarSection, SvVoltage) -> Bus
  • RawExporter().to_model(network) -> GraphModel, which Raw34Writer writes. It checks that every conducting equipment class is exported, then calls export_tables(network, EXPORT_ORDER). A class with no module raises with the counts (no RAW export yet for {'ACLineSegment': 20, ...}), so nothing is dropped silently while the sub-slices land. The tests call export_tables with the modules that have landed so far.
  • Each module has NATIVE_CLASS, SLOTS and export(context) -> list[record] over the whole network. A module works over the whole network rather than object by object, because IDs are allocated per bus and AREA is a trace.
  • SLOTS moves to core. The DSS exporter's slots.py (Slot, KINDS, check_slots, with_default, slots_table) has nothing DSS-specific in it, so it moves to cimhub_core/export_slots.py, and DSS imports it from there (a second consumer, not a copy). The kinds:
  • written: from a getter;
  • rule: a CIM None that RAW needs;
  • unset: no CIM home, left None and written blank, so PSS/E applies its default (X1);
  • not mapped.

A test checks that SLOTS lists every schema slot, and the tables below are generated from it. - Consistency test: every field the importer's FIELDS marks untranscribed is unset here, unless this spec recovers it. The one recovered so far is bus AREA, through the R5 trace. - context (ExportContext) holds the network, the bus numbers, the per-unit bases (SBASE; each node's BASKV) and the AREA trace. Nothing else is shared between modules. - The records are sorted by key (X6). ID is the reader's composite_id, so a record compares by key.

Identity and names (X2)

  • Bus number: TopologicalNode.busNumber. A node without one is internal to a device (see Bus). A number used twice raises, and so does a model where no node has one (numbering a model from another format waits for a consumer).
  • A keyed ID (load, machine and shunt ID; branch and transformer CKT) comes from the importer's mRID, <prefix>_<buses>_<ID>. It is accepted only when the prefix is the module's and the bus numbers are the equipment's own, in order. Otherwise the ID is the next free 1, 2, ... on that bus (or bus pair). This is the one fallback, and each use is logged once per module with a count. The keyed modules arrive in E1-E4.
  • Zone and area numbers: srgn_<n> / ca_<n>, by the same rule. Otherwise the next number above the largest one taken.
  • NAME = the CIM name. It is written blank when it equals the importer's blank-NAME key (the bus number, the zone or area number), so a blank comes back blank. A NAME written as its own number comes back blank too (IEEE118's areas and zones). A name longer than its field raises: 12 characters for a bus, zone or area. The name_source switch (DSS E1) does not apply, because RAW's identity is the number.

Case identification

The RATING records come from olt_rate<n> (name, description), or from the types a caller's rating_sets names; the importer writes all twelve. A blank BASFRQ, XFRRAT or NXFRAT on import is the importer's 60 Hz and MVA, so writing them is no difference.

WECC240 writes no RATING records, so it gains the twelve default ones. That is an expected difference, the same values after defaults.

Zone, area, owner

  • Zone: one per SubGeographicalRegion: I by X2; ZONAME = name.
  • Area: one per ControlArea: I by X2; ARNAME = name; PDES = −netInterchange (MW, the inverse of net_import; a derived.net_export); PTOL = pTolerance (MW). ISW is unset (no ControlArea slack association, CIM 18 gap).
  • Owner: none written. Owner is untranscribed on import, so the section is empty and every OWNER/O1 field is blank (PSS/E's default is owner 1).

Bus

One Bus per TopologicalNode with a busNumber. A node that is internal to a mapped device (the R3b step-up's <machine>_int, P2b's valve-side nodes) has none, and is folded back by its device's sub-slice (E3, E6); the TopologicalNodes without a number are counted on the log line.

  • NAME: the node's busName when set (what a topology processor writes), else its name; blank when it is the bus number. Longer than 12 characters raises.
  • Connectors: a BusbarSection or a Junction on the node writes nothing of its own (a Junction is the connector a topology processor seeds a bus from when it has no busbar); both classes are listed so to_model does not raise on them.

  • IDE: 3 when a SynchronousMachine on the bus has referencePriority set (import R3). Otherwise 2 when the RegulatingControl of a machine or connection on the bus is enabled, in any mode (import R3: enabled = IDE 2/3; a WMOD 3 plant's control is powerFactor). Otherwise 1. A device on an internal node counts for the one numbered node across its transformers (bus.raw_bus). IDE 4 (isolated) has no CIM home on import and comes back as 1.

  • ZONE: the zone number of the Region of the node's Substation (ConnectivityNodeContainer).
  • VM, VA: get_node_voltage(node, "kV", "deg") (new core getter, getters/voltage.py: the node's one balanced SvVoltage, None without one). VM = v / BASKV (derived.per_unit_from_kv). With no SvVoltage they are blank (PSS/E's 1.0, 0.0).
  • NVHI..EVLO: get_voltage_limits(equipment, "kV") (new core getter, the pattern of get_current_limits, whose set-finding and agreement helpers it shares: VoltageLimits(normal_high, normal_low, emergency_high, emergency_low), kind by the limit type's durationKind and direction; two that disagree raise; a seasonal or short-term voltage limit raises), in pu as for VM.

The bus's limits are those of the one BusbarSection on the node that holds any: the importer's bb_<I>. A node-breaker block's node busbars (R6: bb_s<IS>_n<NI>) carry none. Two busbars with limits on one bus raise.

Dead bays (E0-1). A bay switched off at its breaker (busbar, open breaker, a generator, load or shunt) is a TopologicalNode of its own: cim-topology keeps it a bus, because its sensors say it is one, and sets its units out of service (an SvStatus). PSS/E has no bus for it, so the exporter folds it into the bus it hangs from: - Which: identity.folded_stubs keeps each stub of cim-topology's stub_hosts(network) (a cluster of buses holding only connectors, units and open switches that reaches exactly one real bus) whose switches are all between two ConnectivityNodes. A stub behind a bus-to-bus switch (a system switching device) keeps its bus, so a bus-branch case's own buses and switches come back. - No Bus record: a folded stub is left out of bus_numbers (ExportContext.stub_hosts maps it to its host), whether or not it has a busNumber. - Its units go on the host: raw_bus and identity.terminal_buses map a stub to its host first, so every device on it (load, fixed and switched shunt, machine, SVC, FACTS device) and every control at it (SWREG, IREG, FCREG) is written on the host. Their status is 0, from inService. A stub's machine is never taken for a step-up's internal node. - IDE: a unit on a stub leaves its host's IDE alone (it is out of service with its bay). - A controlled shunt beside a switched shunt: a v34 switched shunt is keyed by its bus alone. A stub's controlled shunts whose host bus holds another switched shunt (a live bank, an SVC or another stub's bank) go out as Fixed shunts, status 0, with the B of their sections in service (switched_shunt.stub_banks; the user's choice, 2026-11-28). Their control band and blocks are not written. - Keys: a stub device's mRID key carries its own bus, so on the host it takes the next free ID there (X2's fallback, after every keyed ID: no collision, in mRID order).

A bus's AREA (area_trace.py, R5)

The importer's untraced_area_buses runs over RAW records. Here, the same rule runs over the bound CIM: - Seeds: - the bus of every SynchronousMachine or PowerElectronicsConnection, with its unit's ControlArea (ControlAreaGeneratingUnit, ControlAreaPowerElectronicsUnit); - each terminal that holds a TieFlow pair, with its bus taking the pair's positiveFlowIn = false area; - every other terminal of that device, which takes the pair's true (home) area. - Spreading: across every device with two or more terminals and no TieFlow (a device that R5 found inside one area), using cimtopology.core.Topology(...).islands() as the importer does. There is no union-find here. - Two areas meeting in one island raise, naming both seeds. An island with no seed is untraced, and its buses' AREA is left blank. That is an expected difference, the row the importer listed (untranscribed: area=). In the area atom it is isolated bus 303.

Tests (E0)

  • export_tables(network, (case_identification, zone, area_interchange, bus)) on IEEE14, WECC240, IEEE118 and every committed atom. Each is compared with the RAW as read: the case record, the RATING records, Zone, Area and Bus, by key. unset slots are skipped. Both sides are filled with fill_defaults (blank = default), and floats are compared at rel 1e-9. The expected differences are one dict in the test, mirroring the list below.
  • RawExporter().to_model(IEEE14) raises, naming the classes not yet exported.
  • New getters: get_node_voltage and get_voltage_limits, tested on the core line_bus_branch shape with hand numbers. export_slots covers DSS as before; the DSS suite must stay green.
  • The writer writes the E0 model, and the reader reads it back with the same records.
  • E0-1: atoms/substation/dead_bay.cimtbl, a CIM-only node-breaker fixture whose buses cim-topology builds and numbers: four stubs left out of the buses and mapped to their hosts; a stranded machine and load on the host with status 0, IREG on the host, and the host's IDE unchanged; a stub bank beside a live bank a Fixed shunt, status 0, and one alone a switched shunt. switches.raw with 103-104 opened: a stub cluster behind system switches keeps its buses and its three switches.

Expected differences (E0)

tests/test_cim_to_raw.py EXPECTED mirrors this list, fixture by fixture: - IEEE14 ISW 2 comes back blank (0): unset, not compared. - An untraced bus's AREA comes back blank (1): isolated bus 303 in three atoms; the loads atom's bus 3 (area 2), one of the three buses the importer lists untranscribed: area=. - IDE 4 comes back as 1: bus 303. - WECC240 gains the twelve default RATING records. - A zone that buses name without a Zone record comes back as a record (import synthesized it): every atom. - NXFRAT > 0 (current ratings) came back 0 until E1, which settles it (see E1). - An area or zone NAME equal to its number comes back blank: IEEE118's three areas and three zones. - The Owner section comes back empty (not compared: no Owner module). - VM and the voltage limits can differ in the last digit (pu → kV → pu); compared at rel 1e-9.

Results

IEEE14, WECC240, IEEE118 and all 18 atoms: every compared slot of the case record, the RATING records, Zone, Area and Bus equals the RAW as read, except the list above. The written E0 tables read back unchanged. RawExporter().to_model raises on IEEE14, naming the 17 ACLineSegments and the other classes not yet exported.

Slots (generated from SLOTS)

CaseIdentificationRecord

RAW slot kind from / why
new_case_flag rule IC 0: a base case
system_base_mva written SBASE: BasePower.basePower (MVA), the one BasePower
revision rule REV 34
transformer_ratings_units rule XFRRAT 1 when the transformer ratings are CurrentLimits, else 0
branch_ratings_units rule NXFRAT 1 when the branch and switch ratings are CurrentLimits, else 0
system_base_frequency written BASFRQ: the network's base frequency (Hz)
titles unset two blank lines: the importer lists the titles on the master's comment
general unset solution options; THRSHZ only steered the import's substation merge
gauss unset solution options: no home in the network profile parts
newton unset solution options: no home in the network profile parts
adjust unset solution options: no home in the network profile parts
tysl unset solution options: no home in the network profile parts
solver unset solution options: no home in the network profile parts
ratings written a RATING record per olt_rate OperationalLimitType

RatingRecord

RAW slot kind from / why
rating_set_number written n of the type's mRID olt_rate
rating_name written OperationalLimitType.name
rating_description written OperationalLimitType.description

ZoneRecord

RAW slot kind from / why
zone_number written I: the srgn_ key (X2)
zone_name written ZONAME: name; blank when it is the number

AreaInterchangeRecord

RAW slot kind from / why
area_number written I: the ca_ key (X2)
bus_number unset ISW: no ControlArea slack association (CIM 18 gap)
pdes written PDES = -netInterchange (MW, net_export)
ptol written PTOL: pTolerance (MW)
name written ARNAME: name; blank when it is the number

BusRecord

RAW slot kind from / why
bus_number written I: busNumber
name written NAME: busName, else name; blank when it is the bus number
base_voltage written BASKV: get_base_voltage (kV, LL)
bus_type rule IDE: 3 with a referencePriority machine, 2 with an enabled plant control, else 1; a folded stub's units leave it alone (E0-1)
area written AREA: the R5 trace; blank when untraced
zone written ZONE: the number of its Substation's Region
owner unset OWNER: ownership is an asset concept (CIM 18 gap)
voltage_magnitude written VM: get_node_voltage v / BASKV
voltage_angle written VA: get_node_voltage angle (deg)
normal_voltage_magnitude_high_limit written NVHI: normal high on the bus's BusbarSection (get_voltage_limits), pu of BASKV
normal_voltage_magnitude_low_limit written NVLO: normal low on the bus's BusbarSection (get_voltage_limits), pu of BASKV
emergency_voltage_magnitude_high_limit written EVHI: emergency high on the bus's BusbarSection (get_voltage_limits), pu of BASKV
emergency_voltage_magnitude_low_limit written EVLO: emergency low on the bus's BusbarSection (get_voltage_limits), pu of BASKV
## E1: branch, series capacitor, switch, multi-section line, ratings (spec approved 2026-11-09: E1-1 grouped sections (amended from "close the gap"), E1-2 line shunts by mRID; done 2026-11-09)

Modules: branch.py (ACLineSegment, SeriesCompensator → Non-transformer branch, with its line shunts), switch.py (Switch, Breaker, Disconnector → System switching device), multi_section_line.py (Line → Multi-section line), ratings.py (shared: RATE1..RATE12 and the units flag). EXPORT_ORDER gains them after bus. Import spec: CIMTBL_MAPPING.md#branch, #system-switching-device, #multi-section-line, R1b, R5.

Buses and keys

  • I, J: the busNumber of terminal 1's and terminal 2's TopologicalNode (get_terminal_nodes(..., topological=True)), in that order. A terminal on an unnumbered node raises.
  • CKT (X2): from the mRID ln_<I>_<J>_<CKT> / sc_ / sw_ when I and J are the terminals' buses in order; otherwise the next free 1, 2, ... on the bus pair, in either order (PSS/E's key). Two branches with one key raise.
  • NAME: name, blank when it is the importer's key I_J_CKT; longer than 40 characters raises.

Branch

RAW from
R, X, B ACLineSegment: get_line_sequence_impedance(line, "pu", base_power=...), lumped values only (derive LUMPED: a per-length or matrix line waits for a consumer, E7); pu on the line's BaseVoltage, bus I's on import (R1b-1). A set gch raises (RAW has no line conductance). SeriesCompensator: get_series_compensator(compensator, "pu", base_power=...) (the getter gains the line getter's unit / base_power; ohm stays its default); B blank. A compensator with X ≥ 0 is written as is and comes back an ACLineSegment (none on import).
ST get_in_service(which="actual"): 1 when true or unset, 0 when false
MET on a tie: the terminal holding its TieFlow pair, 1 or 2 (R5); pairs on both terminals raise. Off a tie: blank (1): the loss end has no CIM home (RAW-22)
LEN ACLineSegment.length in km; blank when unset. A series capacitor's is lost (R1b-2 listed it on the row)
GI, BI, GJ, BJ the branch's line shunts (decision E1-2)
RATE1..12 ratings, below
O1..F4 unset (CIM 18 gap)

Line shunts (decision E1-2): a LinearShuntCompensator whose mRID is cap_<I>_<J>_<CKT>_i / _j of an exported branch, on that end's bus, is the branch's GI + jBI / GJ + jBJ: the same mRID key rule as X2, and the only link the importer could give it (RAW-13, CIM 18 gap). G and B come from a new core getter get_shunt_admittance(shunt, unit, *, sections, base_power=None) (total g, b of the sections in service; "pu" on the shunt's nomU and base_power, nomU checked against its BaseVoltage since E2; E2 reads fixed and switched shunts with it too). One section is read (sections='actual'). Its inService must equal the branch's, else it raises. E2 skips the shunts claimed here (branch.line_shunts(network)). The alternative, every line shunt a fixed shunt, solves the same while the line is in service but loses the pairing and "switched with its line".

Series capacitor in the branch table

Only R, X, ST, MET, the key, NAME and the ratings: SeriesCompensator has no bch, length or shunts.

System switching device

  • Which switches: a Switch, Breaker or Disconnector with no ConnectivityNode on either terminal. One on two ConnectivityNodes is a substation switching device (R6), which E5 is to export; until then it is left out, and the export logs one warning that counts them (the case keeps its buses, not those switches or their states). One on a node at only one terminal raises. Another Switch subclass (fuse, recloser, load-break switch, ...) has no module, so to_model raises on it: RAW has STYPE 1-3 only.
  • STYPE by class: Switch 1, Breaker 2, Disconnector 3 (the importer's SWITCH_CLASS inverted).
  • STATUS / NSTAT: get_switch_state(which="actual") / "normal": open is 0, closed 1; unset raises (semantic rule 1).
  • X and METERED have no default in the format, so neither is left blank (amended at implementation):
  • X is 0.0001 (a rule: a Switch has no impedance; the substation switching device's default). The import spec's "the exporter writes THRSHZ back" now says so (THRSHZ is an unset solution option, E0).
  • METERED is a branch's MET on a tie, and 1 off a tie.
  • Ratings as a branch's.

Multi-section line

One record per Line whose sections form one path I, DUM1, ..., J: - Sections: the ACLineSegments and SeriesCompensators the Line contains (Equipments) or groups (AdditionalGroupedEquipment). Each dummy bus joins exactly two branches, as on import; one to nine dummy buses. - A section in one substation (decision E1-1, amended at implementation): R1b-3 kept such a section (every series-capacitor section of the local set, 44) contained by its substation. The approved rule closed the gap it left in the Line through the one branch joining two loose ends. The local set showed the case it misses: a capacitor at an end of the path leaves no gap, so the Line held one section and the record lost its DUM1. The user chose CIM's own association instead ("AdditionalGrouped"): the importer now groups the section in its Line (AdditionalEquipmentContainer, import R1b-3 amended), and the exporter reads both lists. No gap rule remains. - I, J and ID (X2): from the mRID msl_<I>_<J>_<ID> when it names the path's ends; otherwise I is the lower end bus, and ID is the next free &1, &2, ... on the pair (the draft's "name when it is & and one more character" was dropped at implementation: X2's one fallback). - A Line that is still not one path (a branching or a CGMES-style line) writes no record and is counted on the log line: a multi-section line is a grouping, and its sections are written as branches either way. This is the one fallback. - MET is unset (RAW-22).

Ratings (ratings.py)

  • New core getter get_limits_by_type(equipment, limit_class, unit) -> {OperationalLimitType: value} (getters/limits_by_type.py): every limit_class limit in the equipment's sets (equipment_limit_sets), one value per type (agreed_limit), normalValue required.
  • RATEn = the limit whose type's mRID is olt_rate<n> (E0's rule); 0 where there is none. A model whose types are not the importer's names its sets: RawExporter(rating_sets={"olt_normal": 1, "olt_emergency": 2}) (also cim_to_raw(..., rating_sets=...)), OperationalLimitType mRID → n, each n distinct in 1..12, and only those types count. A limit of a type that is no rating set raises, either way.
  • NXFRAT: 1 when the case's branch and switch ratings (every ACLineSegment, SeriesCompensator and Switch, E5's included) are CurrentLimits, 0 when they are ApparentPowerLimits or there are none. Both kinds in one case raise, and so do both on one device. A CurrentLimit is written as RATEn = kA × √3 × the device's BaseVoltage in kV (new derived.rating_from_ka, the inverse of ka_from_rating). ExportContext gains branch_ratings_in_current, read by the case record and the rated modules.

Tests (E1)

tests/test_cim_to_raw.py: the round trip over every fixture with the E1 modules added (Branch, System switching device, Multi-section line compared by key and slot, RATE1..RATE12 value by value at rel 1e-9), and: - the switches atom's NXFRAT 1 comes back; - the mixed-base atom's &1 comes back whole, its capacitor grouped (AdditionalGroupedEquipment); a grouped section at the end of the path (the multi-section atom's 1-2 moved to the grouped list); a Line made a loop (that atom's &1 with its parallel 1-4 2 added) writes no record; - keyed_ids: a keyed ID, a reversed pair, a fallback, an ID too long for the field, two devices with one key; - raises: a NAME of 41 characters, a gch, a line shunt out of service with its line in, a switch on one ConnectivityNode, ratings in MVA and in current in one case; - the written WECC240, mixed-base and switches models read back with the same records; - core (test_getters_bus_branch_units.py, an inline atom with hand numbers): get_limits_by_type, get_shunt_admittance, and get_series_compensator in pu.

Expected differences (E1)

  • MET / METERED 2 off a tie comes back 1 (RAW-22): computed in the test from the RAW as read (a device whose buses share an AREA, _metered_off_a_tie): WECC240 74 of its 81 MET 2, IEEE118 77 of 83, one branch in each of the areas, FACTS/VSC, two-terminal and line-shunt atoms, and the switches atom's disconnector. The ties' MET comes back.
  • The mixed-base atom's series capacitor LEN 1.0 comes back 0 (R1b-2 listed it on the row).
  • A system switching device's X other than 0.0001 comes back 0.0001 (untranscribed; one a local case; none in the committed fixtures).
  • The two-bus node-breaker atom's NXFRAT 1 comes back 0: nothing in it is rated, so the flag says nothing.
  • Owners and the multi-section line's MET: unset, not compared.

Results

IEEE14, WECC240, IEEE118 and all 18 atoms: every compared slot of Branch, System switching device and Multi-section line equals the RAW as read, except the list above, and the E0 tables are as before. The switches atom's NXFRAT 1 now comes back. The written WECC240, mixed-base and switches models read back unchanged.

Local case set (29 v34 cases of one network, never committed; 3 run, counts only): every branch (about 14450 a case), system switching device (6 or 7) and multi-section line (35 of 35, their 44 grouped capacitor sections included) comes back keyed as on import, each case in about 70 s. Per case the E1 differences are: MET 2 off a tie (about 6150), the one series capacitor's LEN, and one switch's X ≠ 0.0001. The bus table shows only E0's: untraced AREA (about 179) and IDE 4 → 1 (615 to 827, all IDE 4).

Slots (generated from SLOTS)

BranchRecord

RAW slot kind from / why
from_bus_number written I: terminal 1's busNumber
to_bus_number written J: terminal 2's busNumber
r written R: get_line_sequence_impedance / get_series_compensator r (pu)
x written X: get_line_sequence_impedance / get_series_compensator x (pu)
circuit written CKT: the ln_ / sc_ key, else the next free (X2)
b written B: get_line_sequence_impedance b (pu); blank for a series capacitor
name written NAME: name; blank when it is the key I_J_CKT
ratings written RATE1..RATE12: the olt_rate limits (ratings.device_ratings)
g_from written GI: the line shunt cap__i (mRID key, E1-2): get_shunt_admittance g (pu on the bus base)
b_from written BI: the line shunt cap__i (mRID key, E1-2): get_shunt_admittance b (pu on the bus base)
g_to written GJ: the line shunt cap__j (mRID key, E1-2): get_shunt_admittance g (pu on the bus base)
b_to written BJ: the line shunt cap__j (mRID key, E1-2): get_shunt_admittance b (pu on the bus base)
status rule ST: 0 when inService is false, else 1
metered_end written MET: on a tie, the terminal holding its TieFlow pair (R5); else blank (RAW-22)
length written LEN: ACLineSegment.length (km); blank for a series capacitor (R1b-2)
o1 unset ownership is an asset concept (CIM 18 gap)
f1 unset ownership is an asset concept (CIM 18 gap)
o2 unset ownership is an asset concept (CIM 18 gap)
f2 unset ownership is an asset concept (CIM 18 gap)
o3 unset ownership is an asset concept (CIM 18 gap)
f3 unset ownership is an asset concept (CIM 18 gap)
o4 unset ownership is an asset concept (CIM 18 gap)
f4 unset ownership is an asset concept (CIM 18 gap)

SwitchRecord

RAW slot kind from / why
from_bus_number written I: terminal 1's busNumber
to_bus_number written J: terminal 2's busNumber
circuit written CKT: the sw_ key, else the next free (X2)
x rule X 0.0001: a Switch has no impedance, and the format gives X no default
ratings written RATE1..RATE12: the olt_rate limits (ratings.device_ratings)
status written STATUS: get_switch_state actual, open 0
nstat written NSTATUS: get_switch_state normal, open 0
metered_end rule METERED: on a tie, the terminal holding its TieFlow pair (R5); else 1 (no default in the format; RAW-22)
stype written STYPE by class: Switch 1, Breaker 2, Disconnector 3
name written NAME: name; blank when it is the key I_J_CKT

MultiSectionLineRecord

RAW slot kind from / why
i written I: the path's first bus (by the msl_ key, else the lower end)
j written J: the path's last bus
dum1 written DUM1: the path's first dummy bus
line_id written ID: the msl_ key, else the next free &1, &2, ... (X2)
met unset MET: the loss-allocation end has no CIM home (CIM 18 gap, RAW-22)
dum2 written the path's next dummy bus, blank past its end
dum3 written the path's next dummy bus, blank past its end
dum4 written the path's next dummy bus, blank past its end
dum5 written the path's next dummy bus, blank past its end
dum6 written the path's next dummy bus, blank past its end
dum7 written the path's next dummy bus, blank past its end
dum8 written the path's next dummy bus, blank past its end
dum9 written the path's next dummy bus, blank past its end

E2: load, fixed shunt, switched shunt (spec approved 2026-11-09: E2-1 bus's Region, E2-2 SWREG I; done 2026-11-09)

Modules: load.py (ConformLoad, NonConformLoad, EnergyConsumer → Load), fixed_shunt.py and switched_shunt.py (LinearShuntCompensator → Fixed shunt or Switched shunt, split by control). EXPORT_ORDER gains them after multi_section_line. Import spec: CIMTBL_MAPPING.md#load-r2, #fixed-shunt-r2, #switched-shunt-r2, R2b. A NonlinearShuntCompensator has no module, so to_model raises on it (the import never writes one).

Which shunt is which

Every LinearShuntCompensator goes to exactly one record: 1. a line shunt of an exported branch (branch.line_shunts, E1-2): the branch's GI/BI/GJ/BJ; 2. one with a RegulatingControl: a block of the Switched shunt of that control; 3. any other: a Fixed shunt; so is a dead bay's controlled shunt whose host bus holds another switched shunt (switched_shunt.stub_banks, E0-1).

Per unit on the bus base. RAW's GL, BL and Bi are MW / Mvar at 1 pu of the bus's BASKV. The pu admittance of get_shunt_admittance(..., "pu", base_power=...) is on the shunt's nomU, so a shunt whose nomU differs from its BaseVoltage raises (the importer writes nomU = BASKV; a shunt rated off its bus voltage waits for a consumer). The same check now guards E1's line shunts (E1's text said "on the shunt's BaseVoltage": it is nomU). MW / Mvar = pu × SBASE through a new derived.mva_from_per_unit, the inverse of per_unit_from_mva.

Load

RAW from
I, ID the terminal's bus; ID from the mRID ld_<I>_<ID>, else the next free 1, 2, ... on the bus (X2)
STATUS get_in_service(which="actual"): 1 when true or unset, 0 when false
AREA the load's group: LoadGroup → SubLoadArea → LoadArea → ControlArea → its number. No group: blank (PSS/E: the bus's). A group whose chain breaks raises
ZONE its bus's substation Region (E2-1), as the bus's ZONE
PL, IP, YP p × the p fractions: get_phase_loads(load, "MW", "MVAr").total and get_load_response (constant power, current, impedance)
QL, IQ, YQ q × the q fractions; YQ = −(q × the impedance fraction), RAW's sign (import RAW-8)
SCALE by class: ConformLoad 1, NonConformLoad 0, a plain EnergyConsumer blank (PSS/E: 1)
OWNER, INTRPT, DGENP, DGENQ, DGENM unset (no CIM home)

An exponent response (exponentModel true) raises: a v34 load is ZIP only. A load without a LoadResponse raises (the getter's rule). A zero side comes back 0, 0, 0 whatever its fractions.

Fixed shunt

RAW from
I, ID the terminal's bus; ID from the mRID cap_<I>_<ID>, else the next free (X2)
STATUS get_in_service(which="actual"), as a load's
GL, BL get_shunt_admittance(shunt, "pu", sections="actual") × SBASE

Switched shunt

One record per RegulatingControl over the shunts that name it; they must sit on one bus (else it raises), and two records on one bus raise (a v34 switched shunt's key is its bus). A StaticVarCompensator is a switched shunt too, one record each (E6a); the key rule covers it with the banks.

RAW from
I the blocks' bus
N1, B1 .. N8, B8 one block per shunt, in the order of the mRID swsh_<I>_b<k>; otherwise reactors first, then capacitors, each by mRID. Ni = maximumSections; Bi = get_shunt_admittance(block, "pu", sections="maximum")'s b per section × SBASE. More than 8 blocks raise; a block with g ≠ 0 raises (RAW has no G here)
BINIT Σ over the blocks of sections × Bi (sections="actual"): the import's block_sections split, inverted exactly
STATUS the blocks' inService, which must agree (else it raises)
MODSW from the control (below)
VSWHI, VSWLO from the control's target and deadband (below)
SWREG the busNumber of the control's terminal (decision E2-2); MODSW 6: unset
RMIDNT MODSW 6: the name of the FACTS device at the control's terminal; else unset
NREG unset in E2: a terminal on a node of a node-breaker block is E5's (node numbers)
ADJM, RMPCT unset (no CIM home)

MODSW (the import's CONTROL_MODE inverted):

control MODSW
mode voltage, locked (enabled false, or every block's controlEnabled false) 0
mode voltage, discrete true or unset 1
mode voltage, discrete false 2
mode reactivePower on a SynchronousMachine or PowerElectronicsConnection terminal, or disabled on any other (R2b-1's no-plant case) 3
mode reactivePower on a StaticSynchronousCompensator terminal 6
any other mode raises (MODSW 4 and 5 have no import either)

Blocks whose controlEnabled disagree raise.

VSWHI, VSWLO from get_regulating_control (target ± deadband / 2; an unset deadband is 0): - mode voltage: in kV, as pu of the regulated bus's BASKV (per_unit_from_kv). - MODSW 3: the band low..high in Mvar under the output sign (−target ∓ deadband / 2) as fractions of the machine's QB..QT, its minQ..maxQ (generation sign as stored): VSWLO = (low − QB) / (QT − QB). A new derived.band_fractions, the inverse of reactive_band. QT = QB raises, and so does a target on equipment that is no machine. Amended at implementation: the draft named get_machine_rating / get_inverter_rating, but both require ratedU, which the RAW import does not write (a RAW machine has no rated kV), so the two limits are read with get_qty. Undone by E3-1: the importer now writes ratedU = BASKV, and QT..QB are read through get_machine_rating / get_inverter_rating. - MODSW 6: the same over −SHMX..SHMX, SHMX = rating_from_ka(ratedI, BASKV) of the FACTS device. - A disabled control with no target (R2b-1's no-plant case): blank (PSS/E: 1.0, 1.0).

Decisions

  • E2-1. A load's ZONE: the bus's substation Region (user 2026-11-09), as the import spec planned. A SubLoadArea is one (area, zone) pair with no link to a zone. EnergyArea holds only ControlArea. The new ConnectedArea has no link to a zone or a ControlArea, and a zone ConnectedArea would duplicate each zone's SubGeographicalRegion. A load whose ZONE differs from its bus's comes back as the bus's (none in the committed cases; the loads atom 1; 2505 to 5090 a local case). This goes to the IEC committee with the rest of the ControlArea family's gaps (plan §6a). A bus's AREA from a transmissionArea ConnectedArea is a later slice (plan §9.1).
  • E2-2. SWREG of a shunt regulating its own bus: I, always (user 2026-11-09): the busNumber of the control's terminal. RAW writes 0 or I for the same meaning, and CIM keeps neither. WECC240's 7 and the local set's (about 1100 a case, none 0) come back; IEEE118's 13 and 4 atom shunts' 0 come back I.

Tests (E2)

tests/test_cim_to_raw.py: the round trip with the E2 modules added, and: - the loads atom (a ZIP mix, SCALE 0 and blank, an area and zone off the bus's, blank AREA/ZONE), the fixed-shunts atom (GL ≠ 0, a reactor out of service), the switched-shunts atom (reactor + capacitor blocks with remote regulation, MODSW 2 with 2.5 steps, a locked shunt), the plant-and-facts atom (MODSW 3 with and without a plant, MODSW 6); - the line-shunts atom's shunts stay on their branches (no Fixed shunt); - raises: a NonlinearShuntCompensator, an exponent load, a shunt with nomU off its BaseVoltage, blocks of one control on two buses, two controls on one bus, more blocks than the record holds, a block with g ≠ 0, blocks in and out of service; - the written loads, switched-shunts and plant-and-facts models read back with the same records; - derived: mva_from_per_unit, band_fractions against reactive_band.

Expected differences (E2)

  • PL..YQ of a mixed load can differ in the last digit (p × fraction; rel 1e-9).
  • VSWHI/VSWLO in the last digit (the import's float residue).
  • A blank load AREA or ZONE comes back filled: AREA its group's (the importer gives every load one), ZONE its bus's, the same meaning (the loads atom's 3 1).
  • A load ZONE off its bus's comes back as the bus's (E2-1): the loads atom's 2 A.
  • SWREG 0 comes back I (E2-2), computed in the test (_own_bus_swreg; MODSW 6 keeps its blank): IEEE118 13, the switched-shunts atom 2, the plant-and-facts atom 1 (no plant), the node-breaker forms atom 1.
  • ADJM and RMPCT are unset, not compared: ADJM 1 (the switched-shunts atom 1, 115 a local case) and RMPCT ≠ 100 (46 a local case) come back as the defaults 0 and 100.
  • The no-plant MODSW 3 shunt's VSWLO 0 comes back 1.0 (R2b-1 listed it).
  • NREG is unset until E5, not compared: the node-breaker forms atom's 11 comes back blank.
  • OWNER, INTRPT, DGEN* of a load: unset, not compared.

Results

IEEE14, WECC240, IEEE118 and all 18 atoms: every compared slot of Load, Fixed shunt and Switched shunt equals the RAW as read, except the list above; the E0 and E1 tables are as before. The written loads, switched-shunts and plant-and-facts models read back unchanged.

Local case set (29 v34 cases of one network, never committed; 3 run, counts only): every load (6980 to 9566 a case, 755 SCALE 0), fixed shunt (806 to 811) and switched shunt (1387 to 1389: MODSW 0, 1, 2, 3 and 6, up to 8 blocks) comes back keyed as on import, each case in about 72 s. Every PL..YQ, GL, BL, Ni, Bi, BINIT, MODSW, VSWHI, VSWLO and RMIDNT matches at rel 1e-9. Per case the E2 differences are only: load ZONE off its bus's (E2-1: 2505, 5055, 5090, each exactly the case's count of such loads), SWREG 0 → I where present, and in one case the no-plant MODSW 3 shunt's VSWLO (R2b-1). The E0 and E1 differences are unchanged.

Slots (generated from SLOTS)

LoadRecord

RAW slot kind from / why
bus_number written I: the terminal's busNumber
load_id written ID: the ld__ key, else the next free (X2)
status rule STATUS: 0 when inService is false, else 1
area written AREA: LoadGroup -> SubLoadArea -> LoadArea -> ControlArea; blank without a group
zone written ZONE: its bus's (E2-1; a SubLoadArea has no link to a zone, CIM 18 gap)
constant_real_power written PL: p (get_phase_loads total, MW) x the constant power fraction (get_load_response)
constant_imag_power written QL: q (get_phase_loads total, Mvar) x the constant power fraction (get_load_response)
constant_current_real_power written IP: p (get_phase_loads total, MW) x the constant current fraction (get_load_response)
constant_current_imag_power written IQ: q (get_phase_loads total, Mvar) x the constant current fraction (get_load_response)
constant_admittance_real_power written YP: p (get_phase_loads total, MW) x the constant impedance fraction (get_load_response)
constant_admittance_imag_power written YQ: -(q (get_phase_loads total, Mvar) x the constant impedance fraction (get_load_response)), RAW's sign
owner unset ownership is an asset concept (CIM 18 gap)
scale written SCALE by class: ConformLoad 1, NonConformLoad 0, EnergyConsumer blank
interruptible unset no CIM home
dgenp unset no CIM home
dgenq unset no CIM home
dgenf unset no CIM home

FixedShuntRecord

RAW slot kind from / why
bus_number written I: the terminal's busNumber
shunt_id written ID: the cap__ key, else the next free (X2)
status rule STATUS: 0 when inService is false, else 1
gl written GL (MW at 1 pu): get_shunt_admittance g of the sections in service (pu on the bus base) x SBASE
bl written BL (Mvar at 1 pu): get_shunt_admittance b of the sections in service (pu on the bus base) x SBASE

SwitchedShuntRecord

RAW slot kind from / why
bus_number written I: the blocks' busNumber (a v34 switched shunt's key)
modsw written MODSW from the control: voltage 0 locked, 1 discrete, 2 continuous; reactivePower 3 on a machine (or disabled elsewhere), 6 on a FACTS device; an SVC 2, or 0 locked
adjm unset ADJM: the switching-order method has no CIM home
status rule ST: 0 when the blocks' (or the SVC's) inService is false, else 1
vswhi written VSWHI: the band's top from get_regulating_control target +- deadband / 2: voltage in kV over the regulated bus's BASKV; MODSW 3 and 6 as fractions of the machine's minQ..maxQ or the FACTS device's -SHMX..SHMX (band_fractions); blank for a disabled control with no target
vswlo written VSWLO: the band's bottom from get_regulating_control target +- deadband / 2: voltage in kV over the regulated bus's BASKV; MODSW 3 and 6 as fractions of the machine's minQ..maxQ or the FACTS device's -SHMX..SHMX (band_fractions); blank for a disabled control with no target
swreg written SWREG: the busNumber of the control's terminal, its own bus included (E2-2); blank for MODSW 6
rmpct unset RMPCT: a shunt's participation share has no CIM home (CIM 18 gap)
rmidnt written RMIDNT: MODSW 6: the name of the FACTS device at the control's terminal
binit written BINIT: the sum over the blocks of get_shunt_admittance b of the sections in service (pu on the bus base) x SBASE; an SVC's -q in Mvar (svc_binit), blank when unset
n1 written Ni / Bi: block i, maximumSections and get_shunt_admittance b per section (pu on the bus base) x SBASE; in the swsh__b order, else reactors first, each by mRID; an SVC: one step of SBASE / inductiveRating, then of SBASE / capacitiveRating (pu system, svc_block_mvar)
b1 written Ni / Bi: block i, maximumSections and get_shunt_admittance b per section (pu on the bus base) x SBASE; in the swsh__b order, else reactors first, each by mRID; an SVC: one step of SBASE / inductiveRating, then of SBASE / capacitiveRating (pu system, svc_block_mvar)
n2 written Ni / Bi: block i, maximumSections and get_shunt_admittance b per section (pu on the bus base) x SBASE; in the swsh__b order, else reactors first, each by mRID; an SVC: one step of SBASE / inductiveRating, then of SBASE / capacitiveRating (pu system, svc_block_mvar)
b2 written Ni / Bi: block i, maximumSections and get_shunt_admittance b per section (pu on the bus base) x SBASE; in the swsh__b order, else reactors first, each by mRID; an SVC: one step of SBASE / inductiveRating, then of SBASE / capacitiveRating (pu system, svc_block_mvar)
n3 written Ni / Bi: block i, maximumSections and get_shunt_admittance b per section (pu on the bus base) x SBASE; in the swsh__b order, else reactors first, each by mRID; an SVC: one step of SBASE / inductiveRating, then of SBASE / capacitiveRating (pu system, svc_block_mvar)
b3 written Ni / Bi: block i, maximumSections and get_shunt_admittance b per section (pu on the bus base) x SBASE; in the swsh__b order, else reactors first, each by mRID; an SVC: one step of SBASE / inductiveRating, then of SBASE / capacitiveRating (pu system, svc_block_mvar)
n4 written Ni / Bi: block i, maximumSections and get_shunt_admittance b per section (pu on the bus base) x SBASE; in the swsh__b order, else reactors first, each by mRID; an SVC: one step of SBASE / inductiveRating, then of SBASE / capacitiveRating (pu system, svc_block_mvar)
b4 written Ni / Bi: block i, maximumSections and get_shunt_admittance b per section (pu on the bus base) x SBASE; in the swsh__b order, else reactors first, each by mRID; an SVC: one step of SBASE / inductiveRating, then of SBASE / capacitiveRating (pu system, svc_block_mvar)
n5 written Ni / Bi: block i, maximumSections and get_shunt_admittance b per section (pu on the bus base) x SBASE; in the swsh__b order, else reactors first, each by mRID; an SVC: one step of SBASE / inductiveRating, then of SBASE / capacitiveRating (pu system, svc_block_mvar)
b5 written Ni / Bi: block i, maximumSections and get_shunt_admittance b per section (pu on the bus base) x SBASE; in the swsh__b order, else reactors first, each by mRID; an SVC: one step of SBASE / inductiveRating, then of SBASE / capacitiveRating (pu system, svc_block_mvar)
n6 written Ni / Bi: block i, maximumSections and get_shunt_admittance b per section (pu on the bus base) x SBASE; in the swsh__b order, else reactors first, each by mRID; an SVC: one step of SBASE / inductiveRating, then of SBASE / capacitiveRating (pu system, svc_block_mvar)
b6 written Ni / Bi: block i, maximumSections and get_shunt_admittance b per section (pu on the bus base) x SBASE; in the swsh__b order, else reactors first, each by mRID; an SVC: one step of SBASE / inductiveRating, then of SBASE / capacitiveRating (pu system, svc_block_mvar)
n7 written Ni / Bi: block i, maximumSections and get_shunt_admittance b per section (pu on the bus base) x SBASE; in the swsh__b order, else reactors first, each by mRID; an SVC: one step of SBASE / inductiveRating, then of SBASE / capacitiveRating (pu system, svc_block_mvar)
b7 written Ni / Bi: block i, maximumSections and get_shunt_admittance b per section (pu on the bus base) x SBASE; in the swsh__b order, else reactors first, each by mRID; an SVC: one step of SBASE / inductiveRating, then of SBASE / capacitiveRating (pu system, svc_block_mvar)
n8 written Ni / Bi: block i, maximumSections and get_shunt_admittance b per section (pu on the bus base) x SBASE; in the swsh__b order, else reactors first, each by mRID; an SVC: one step of SBASE / inductiveRating, then of SBASE / capacitiveRating (pu system, svc_block_mvar)
b8 written Ni / Bi: block i, maximumSections and get_shunt_admittance b per section (pu on the bus base) x SBASE; in the swsh__b order, else reactors first, each by mRID; an SVC: one step of SBASE / inductiveRating, then of SBASE / capacitiveRating (pu system, svc_block_mvar)
nreg unset NREG: a node of a node-breaker block, written by E5

E3: generator (spec approved 2026-11-09: E3-1 ratedU = BASKV, E3-2 the getter reads a star x, E3-3 a fixed tap's increment None, E3-4 IREG I; E3-5 at implementation, reversed P limits as stored; done 2026-11-09)

Module: generator.py (SynchronousMachine, PowerElectronicsConnection → Generator). EXPORT_ORDER gains it after switched_shunt. Import spec: CIMTBL_MAPPING.md#generator-r3, R3b (step-ups), R3c (WMOD 2, 3), R6 (NREG). PowerTransformer stays E4's class: E3 exposes step_ups(context) (step-up → machine), which E4 leaves out, as E1's branch.line_shunts is for E2.

Machines, plants and keys

RAW from
I, ID the machine's bus: its terminal's node, or for a machine behind a step-up the node across it (raw_bus); ID from the mRID sm_<I>_<ID> / pec_<I>_<ID>, else the next free (X2)
PG, QG get_der_output(machine, "MW", "MVAr", sign="generation").total
QT, QB get_machine_rating / get_inverter_rating(..., sign="generation") max_q, min_q; unset: blank (PSS/E: ±9999)
MBASE their rated_s (MVA)
PT, PB get_unit_limits(unit, "MW", sign="generation") (new, getters/der.py): a GeneratingUnit's maxOperatingP/minOperatingP or a PowerElectronicsUnit's maxP/minP, as (min, max), as stored even when the minimum is above the maximum (E3-5); the unit is the machine's GeneratingUnit or the connection's one unit (get_inverter_unit); none: blank
ZR a SynchronousMachine: get_machine_impedance(machine, "pu").r, on its ratedU and ratedS (BASKV, MBASE; E3-1); a connection: blank (R3c-3 listed it; X1)
ZX untranscribed (no machine reactance in cim18v17, UPSTREAM U13)
RT, XT, GTAP the step-up, below; without one: 0, 0, blank (R3b-4's listed GTAP is lost, X1)
STAT get_in_service(which="actual"): 1 when true or unset, 0 when false
RMPCT the qPercent of the plant's SynchronousMachines (get_machine_rating), on every record of the plant, so a connection beside machines gets it back; a plant of connections only: blank (R3c-3, X1). Refined at implementation: the draft blanked every connection's
WMOD SynchronousMachine 0; PowerElectronicsConnection 3 when its control is mode powerFactor, else 1 (WMOD 2 comes back 1, X1)
WPF WMOD 3: the control's targetValue (signed, R3c-2); else blank
IREG the busNumber of raw_bus of the control's terminal node, its own bus included (E3-4, as E2-2); blank without a control and for WMOD 3
VS mode voltage: get_regulating_control(control, "kV") target as pu of the regulated bus's BASKV (per_unit_from_kv); blank for WMOD 3 and without a control
NREG unset in E3: E5's (node numbers), as the switched shunt's
O1..O4, F1..F4 unset (no CIM home)

A plant is the machines whose bus is I. As on import, IREG, VS and RMPCT are plant quantities: machines of one plant that disagree on them raise. A control in any mode but voltage and powerFactor raises, and so does a powerFactor control on a SynchronousMachine (the import writes none). The bus's IDE (E0) is unchanged.

The step-up folded back (R3b inverted)

A machine whose terminal node has no busNumber sits behind a step-up. The node must hold only the machine and one 2-winding PowerTransformer whose other end is on a numbered bus; anything else raises (two machines behind one step-up, a third terminal, a converter). The transformer must be in service (RAW gives it no status) and have no core admittance. With model = get_transformer_model(step_up, "pu", base_power=machine.ratedS) and winding 1 the end on bus I (else it raises): - RT = r₁ + r₂, XT = the mesh (1, 2) x (pu on MBASE). Both ends' ratedU must equal their nodes' BaseVoltage (R3b-2's per-unit form; another raises until a consumer has one). - GTAP = neutralU / ratedU₁ of the fixed RatioTapChanger on end 1 (get_tap_steps, E3-3); 1 without a tap; a tap that moves (lowStep ≠ highStep) or a tap on end 2 raises.

Decisions

  • E3-1. A RAW machine's ratedU: the importer writes BASKV(I) (user 2026-11-09) on every SynchronousMachine and PowerElectronicsConnection, amending R3 (CIMTBL_MAPPING.md#generator-r3). get_machine_rating, get_inverter_rating and get_machine_impedance("pu") require it, and RAW has no machine kV. R3b-2 already puts the machine at bus I's base, and the step-up's ends carry ratedU = BASKV. ZR comes back through the getter (pu on BASKV, MBASE), and E2's switched shunt reads QT/QB through get_machine_rating / get_inverter_rating again (its get_qty amendment is undone). The IEEE14 generator golden gains the column. Not chosen: an optional ratedU in the getters (a core contract change for DSS, GDM, GLM), or RAW reading get_qty beside the getters.
  • E3-2. A star impedance on a PowerTransformerEnd: the getter reads it (user 2026-11-09). get_transformer_model refused PowerTransformerEnd.x (G6b), but the RAW import writes every 2-winding unit's r, x on end 1, step-ups (R3b-1) and transformer records (R4) alike, as the core shape behind_transformer and CGMES do. Now, with no mesh impedance, the ends' x add by pair: (i, j) x = xᵢ + xⱼ (an unset end x is 0), each on its own end's base moved to the model's; the mesh r is None, since r is per winding either way. A unit with both an end x and a mesh impedance raises. E4 reads every RAW transformer this way. Not chosen: the importer writing a TransformerMeshImpedance.
  • E3-3. A fixed tap's increment: None (user 2026-11-09). get_tap_steps and get_tap_ratio require stepVoltageIncrement except on a fixed tap (lowStep = highStep, R4b-4), which has no step to increment; its ratio at its one position is 1 (its voltage is its neutralU). E4's fixed taps read the same.
  • E3-4. IREG of a plant regulating its own bus: I, always (approved with the spec), as E2-2's SWREG. RAW writes 0 or I for the same meaning. The local set writes I (about 2400 a case, none 0); 20 atom generators' 0 come back I (WMOD 3's excepted).
  • E3-5. P limits reversed: as stored (user 2026-11-09, found at implementation). One local case has 2 WMOD 0 records out of service with PB above PT. The import copies them, and the draft's get_unit_limits raised through the shared order check (der._limits: a minimum above its maximum is a producer that wrote the load sign). get_unit_limits now returns a unit's active power limits as stored; the reactive limits keep the check. Not chosen: raising in the exporter (that case could not be exported) or at import.

Tests (E3)

tests/test_cim_to_raw.py: the round trip with E3 added, and: - the generators atom (a machine and a connection in one plant, a remote IREG, a machine out of service, blank MBASE/QT/PT, a plant on an IDE 1 bus), the renewables atom (WMOD 2 and 3, a connection with ZR and RMPCT listed), the step-up atom (GTAP 1 and 1.025, RT only, a WMOD 1 connection behind one, a plant of three, GTAP without a step-up), the plant-and-facts atom (a WMOD 1 plant of a MODSW 3 shunt); - step_ups(context) holds exactly the 4 step-ups of the step-up atom; - raises: plant members that disagree on (IREG, VS), a mode reactivePower plant control, two machines behind one step-up, a step-up out of service, a step-up tap that moves, a step-up end rated off its node's BaseVoltage; - reversed PT/PB come back as written (E3-5); - the written generators, renewables and step-up models read back with the same records; - core (cimhub_core/tests): get_unit_limits, the star impedance (2 and 3 windings, star + mesh raises), the fixed tap, against hand numbers.

Expected differences (E3)

  • IREG 0 comes back I (E3-4), computed in the test (_own_bus_ireg, as _own_bus_swreg): 20 atom generators; none in IEEE14, IEEE118, WECC240 or the local set.
  • A blank MBASE comes back SBASE, the same meaning (the generators atom's 5 1).
  • WMOD 2 comes back 1 (R3c-1, X1): the renewables atom's 2 W (with its WPF, and its RMPCT: a plant of one connection) and 4 W1 (WPF 1.0 already).
  • WMOD 3's listed IREG and VS are not written (R3c-2): the renewables atom's 5 S.
  • A connection's ZR comes back blank (R3c-3, X1): the renewables atom's 6 S2.
  • A WMOD 1 record's WPF other than 1 comes back blank: PSS/E uses WPF only for WMOD 2 and 3, and the import carries it nowhere (R3c, "unused otherwise"). None in the committed cases; 18 a local case.
  • GTAP without a step-up comes back blank (R3b-4, X1): the step-up atom's 2 G2.
  • NREG is unset until E5, not compared: the node-breaker forms atom's 2.
  • RT, XT, GTAP of a step-up and ZR, VS: rel 1e-9 (per unit → ohm, V → per unit).
  • ZX, O1..O4, F1..F4: unset, not compared.

Results

IEEE14, WECC240, IEEE118 and all 18 atoms: every compared Generator slot equals the RAW as read, except the list above; the E0, E1 and E2 tables are as before. The written generators, renewables and step-up models read back unchanged. The 4 step-ups of the step-up atom (GTAP 1 and 1.025, RT only, a connection behind one) come back RT, XT, GTAP at rel 1e-9. IEEE14's to_model now names only its 3 PowerTransformers as not yet exported (E4).

Local case set (29 v34 cases of one network, never committed; 3 run, counts only): every generator (2997 to 2998 a case: WMOD 0, 1, 2 and 3, plants of up to 8, 213 step-ups with 8 fixed taps) comes back keyed as on import, each case in about 70 s. Every PG, QG, QT, QB, MBASE, PT, PB, ZR (machines), RT, XT, GTAP (step-ups), STAT, IREG, VS and RMPCT (plants with a machine) matches at rel 1e-9. Per case the E3 differences are only the X1 and R3c ones: GTAP without a step-up 11, WMOD 2 → 1 24, WPF 39 (WMOD 2's 21, WMOD 1's 18), RMPCT of a connection-only plant 45, a connection's ZR 73 or 74, and WMOD 3's listed IREG 26 and VS 12. No IREG 0 in the set. The E0, E1 and E2 differences are unchanged.

Slots (generated from SLOTS)

GeneratorRecord

RAW slot kind from / why
bus_number written I: the busNumber of the machine's node, or of the bus across its step-up (raw_bus)
gen_id written ID: the sm_ / pec_ key, else the next free (X2)
p_output written PG: get_der_output(sign='generation').total p (MW)
q_output written QG: get_der_output(sign='generation').total q (Mvar)
max_q_output written QT: get_machine_rating / get_inverter_rating(sign='generation').max_q (Mvar)
min_q_output written QB: get_machine_rating / get_inverter_rating(sign='generation').min_q (Mvar)
regulated_voltage_setpoint written VS: a voltage control's get_regulating_control target as pu of the regulated bus's BASKV; blank for WMOD 3; a plant quantity: the machines at bus I must agree, else it raises
regulated_bus_number written IREG: the busNumber of raw_bus of the voltage control's terminal, its own bus included (E3-4); blank for WMOD 3; a plant quantity: the machines at bus I must agree, else it raises
rated_mva written MBASE: the rating's rated_s (MVA)
zr written ZR: a SynchronousMachine's get_machine_impedance('pu').r, on its ratedU and ratedS (BASKV, MBASE; E3-1); a connection's has no CIM home (R3c-3)
zx unset ZX: cim18v17 has no positive-sequence machine reactance (UPSTREAM U13)
rt written RT: the step-up's winding r summed, pu on MBASE (get_transformer_model); 0 without one
xt written XT: the step-up's mesh (1, 2) x, pu on MBASE (get_transformer_model); 0 without one
gtap written GTAP: neutralU / ratedU1 of the step-up's fixed tap (get_tap_steps), 1 without a tap; blank without a step-up (R3b-4's GTAP has no CIM home)
status rule STAT: 0 when inService is false, else 1
rmpct written RMPCT: the qPercent of the plant's SynchronousMachines (get_machine_rating), on every record of the plant; a plant of connections only has no CIM home (R3c-3); a plant quantity: the machines at bus I must agree, else it raises
max_p_output written PT: get_unit_limits(sign='generation').max_p of the GeneratingUnit or the connection's PowerElectronicsUnit (MW)
min_p_output written PB: get_unit_limits(sign='generation').min_p (MW)
o1 unset ownership is an asset concept (CIM 18 gap)
f1 unset ownership is an asset concept (CIM 18 gap)
o2 unset ownership is an asset concept (CIM 18 gap)
f2 unset ownership is an asset concept (CIM 18 gap)
o3 unset ownership is an asset concept (CIM 18 gap)
f3 unset ownership is an asset concept (CIM 18 gap)
o4 unset ownership is an asset concept (CIM 18 gap)
f4 unset ownership is an asset concept (CIM 18 gap)
wmod written WMOD: SynchronousMachine 0; PowerElectronicsConnection 3 under a powerFactor control, else 1 (WMOD 2 has no CIM home, R3c-1)
wpf written WPF: WMOD 3: the powerFactor control's target, as stored (signed, R3c-2); else blank
nreg unset NREG: a node of a node-breaker bus, written by E5

E4: transformer, impedance correction (spec approved 2026-11-09: E4-1 the getter reads on base_power, E4-2 a zero end holds no core, E4-3 get_tap_voltage; done 2026-11-09)

Modules: transformer.py (PowerTransformer → Transformer) and impedance_correction.py (ImpedanceTapChangerTable → Impedance correction). EXPORT_ORDER gains them after generator. Import spec: CIMTBL_MAPPING.md#transformer-r4, R4b (the forms R4 raised on), R5 (NMETR on a tie), R6 (NODk), P2-5 (converter transformers). CW = CZ = CM = 1 (plan §9.1).

Which transformers

  • Every PowerTransformer whose ends are all on numbered buses is one record, in the BY_ENDS form with 2 or 3 windings (get_transformer_model); tanks, 1 or 4+ windings raise.
  • E3's step-ups (generator.step_ups) are left out, as are converter transformers (P2-5: an end on an internal node holding an ACDCConverter), which are E6's. Any other end on a node without a busNumber raises.

Keys, status, names

RAW from
I, J, K the busNumbers of ends 1, 2, 3 (by endNumber); K 0 for a 2-winding unit
CKT from the mRID xf_<I>_<J>_<K>_<CKT>, else the next free (X2)
NAME X2; blank when it equals the key <I>_<J>_<K>_<CKT>
STAT 0 when inService is false; else 2, 3 or 4 when exactly winding 2, 3 or 1 of a 3-winding unit has its terminal connected = false (R4b-6); else 1. Two windings out, or one out of a 2-winding unit, raise
VECGRP vectorGroup, blank when unset
NMETR on a tie (R5): the winding whose terminal holds no TieFlow; of two such (a 3-winding unit with two windings in the home area) the lower-numbered. Off a tie: blank (RAW-22, as branch MET)
CW, CZ, CM 1
O1..F4, ZCOD, VMSTAR, ANSTAR unset (no CIM home; R4)
NODk unset in E4: E5's, as NREG

Impedance and magnetizing (X4)

model = get_transformer_model(unit, "pu", base_power=SBASE, voltage_unit="kV") gives each value in pu on SBASE and the winding's ratedU (a mesh impedance on its From end's; per-unit values on rated bases are the same seen from either end). RAW's CZ 1 and CM 1 are on the bus BASKV, so each moves by the voltage only, with new named derived functions: an impedance × (ratedU / BASKV)², an admittance × (BASKV / ratedU)². This is the importer's transformer_ohms / magnetizing_siemens (CZ 1, CM 1) inverted, and it is the identity when NOMV = BASKV.

  • R_ij, X_ij for each pair (1-2; 2-3 and 3-1 on a 3-winding unit), seen from winding i as on import (MESH_PAIRS: 1-2 and 3-1 from winding 1, 2-3 from winding 2): R = rᵢ + rⱼ + the mesh r (unset 0), X = the mesh x. This covers the importer's two forms, a 2-winding unit's r, x on end 1 (E3-2's star reading) and a 3-winding unit's mesh, and a CGMES-style star.
  • MAG1, MAG2: model.core g, b on winding 1 (RAW's only place), sign kept.
  • SBASE1-2: a 2-winding unit's ratedS (MVA; the two ends must agree). A 3-winding unit's SBASE1-2, 2-3, 3-1: SBASE, since no end holds a pair base (R4). Amended at implementation: the draft left them blank, but RAW's blank is SBASE only by a rule the comparison's static defaults cannot hold, so SBASE is written.
  • NOMVk: winding k's ratedU (kV).

Taps and control (per winding)

Each winding has at most one controlled tap changer (one with a TapChangerControl), and may have a fixed RatioTapChanger beside a phase tap changer (R4b-3).

RAW from
WINDVk the winding's RatioTapChanger voltage at its step (get_tap_voltage, below) / bus k's BASKV (CW 1); no ratio tap: ratedU / BASKV. Amended at implementation: the draft (and R4b-4's note) had 1, which holds only when NOMV = BASKV; the import writes no tap at ratio NOMV, so such a winding is at its ratedU (about 600 local windings a case with NOMV ≠ BASKV)
ANGk −(phaseShift + the phase tap changer's angle at its step): Winding.phase_shift (new) plus get_phase_tap_steps (step − neutral) × increment (R4b-1, -2, -3). A 2-winding unit has only ANG1: −(θ₁ − θ₂), only the difference being physical (R4b-1's UML text)
CODk the controlled tap changer: a RatioTapChanger with ltcFlag false 0; ltcFlag true ±1 (voltage) or ±2 (reactivePower); a PhaseTapChangerLinear under an activePower control ±3; + when the control is enabled (tap controlEnabled must agree). Any other pairing raises; no controlled tap: 0
CONTk the control's terminal: the winding's own terminal 0; else its node's busNumber (none raises). COD ±3: blank (unused). A negative CONT comes back positive (R4b-8)
RMAk, RMIk ratio: the voltages at highStep and lowStep / BASKV; phase shifter: the larger and smaller PSS/E angle at the end steps; a fixed tap (lowStep = highStep, R4b-4) or none: blank
NTPk highStep − lowStep + 1 of the stepped tap; a fixed tap or none: blank
VMAk, VMIk get_tap_changer_control target ± deadband / 2: voltage in kV / the regulated bus's BASKV (CONT 0: the winding's own bus); reactivePower in Mvar; activePower in MW. No control: blank
CRk, CXk line_drop r, x (ohm) as pu on SBASE and the regulated bus's BASKV (a new per_unit_from_ohms, ohms_from_per_unit inverted), when lineDropCompensation is true; else blank
CNXAk blank (0; COD ±5 is not mapped)
TABk the number of the table of the end's ImpedanceTapChangerTabular (below); a 3-winding unit's raises (as on import); none: blank
RATEk-n winding k's limits on its own terminal (ratings.py, per terminal); a 2-winding unit's are winding 1's, from whichever one terminal holds limits (an MVA, or a current as MVA at its bus, is one value from either side; both rated raise). XFRRAT (E0's transformer_ratings_units) 1 when the transformer ratings are CurrentLimits, each winding's terminal read on its own (ratings_in_current(per_terminal=True))

Winding 2 of a 2-winding unit has only WINDV2: its RatioTapChanger at the actual step (the tap voltage / BASKV₂) or none (ratedU / BASKV₂). A stepped tap there loses its range, and the export logs a warning that counts those units. A unit whose only tap control is on end 2 is written with its windings swapped (end 2 as winding 1, I and J swapped), so the control is COD1 / CONT1; its values are in pu on SBASE and each winding's ratedU, so they keep. A control on both windings, or a phase or impedance tap changer on winding 2, raises.

Impedance correction

One record per ImpedanceTapChangerTable: I from the mRID ict_<I>, else the next free. The points, by T ascending (PSS/E's order), from get_impedance_table: - an angle point: T = −angle (cim_angle inverted); a ratio point: T = ratio × ratedU / BASKV of its users' winding (users that disagree raise; a ratio table without a user raises, as on import); - F = 1 + rEnd1 / 100. rEnd1 ≠ xEnd1, a set rEnd2/3 or xEnd2/3, a point with both or neither of ratio and angle, and a table mixing them raise. Im F is 0.

Getter changes (core, on this branch)

  • get_transformer_model: with a declared base_power, an impedance or admittance is read on that power directly (get_qty(power_base=)), so an end needs no ratedS (E4-1); an end whose g and b are zero holds no core (E4-2); Winding.phase_shift (deg) from PowerTransformerEnd.phaseShift.
  • get_tap_voltage(tap, *, which, voltage_unit) (tap_changer.py, E4-3): a RatioTapChanger's voltage at a position: neutralU + (position − neutralStep) × stepVoltageIncrement / 100 × the end's ratedU; a fixed tap's is its neutralU. get_tap_ratio keeps its meaning (the ratio about the neutral).
  • get_phase_tap_steps(tap, angle_unit="deg"): a PhaseTapChangerLinear's low, high, neutral, normal, step and stepPhaseShiftIncrement (all required but normal).
  • get_impedance_table(table): each point's step, ratio, angle, rEnd1..3, xEnd1..3 (percent).
  • get_limits_by_type(..., terminal=): the limits on one terminal (a transformer's are per winding).

Decisions

  • E4-1. A 3-winding unit's ends have no ratedS (R4: the pair bases fit no end), and get_transformer_model required one. User 2026-11-09: the getter reads on the declared base_power directly, needing only ratedU (the ohms and siemens are on the end's ratedU, and the power is the caller's). Not recommended: the importer writing ratedS = SBASE on 3-winding ends (a nameplate the case does not give).
  • E4-2. End 2's zeros. The import writes end 2's r, x, g, b as 0 (R4, CIM's "the secondary end is zero"), and the getter counted two ends holding a core. User 2026-11-09: an end whose g and b are zero holds no core (zeros on several ends are one zero core). Not recommended: the importer leaving end 2 blank (an R4 change; the goldens change).
  • E4-3. A tap's voltage when neutralU ≠ ratedU (R4: the neutral nearest ratio 1, e.g. WECC240 6103-6104). get_tap_ratio is 1 + (position − neutral) × increment, the ratio about the neutral. User 2026-11-09: a new core get_tap_voltage (above), as CIM defines the increment in percent of the end's ratedU. Not recommended: the exporter computing it from get_tap_steps.

Tests (E4)

tests/test_cim_to_raw.py: the round trip with E4 added, over every fixture, and: - the transformers atom (A to E: CW/CZ/CM 2 and 3, a 3-winding unit, COD ±1 and 2, CONT 0, ratings on windings 1 and 3), the R4b atom (F to T and tables 1 and 2), IEEE14 (NOMV 0, off-nominal WINDV1), WECC240 (122 units with ratings), IEEE118; - the step-up atom's 4 step-ups and the two-terminal atom's 8 converter transformers are left out; - the R4b atom's L (NOMV1 240 on a 230 kV bus, CZ 1): its end holds the ohms on 240 kV, and X1-2 comes back on 230 kV; - to_model exports IEEE14 whole, and raises on the two-terminal atom's CsConverters (E6); - a stepped tap on a 2-winding unit's winding 2 writes its actual step, with the warning; a control on end 2 only comes back as the same record with the ends renumbered; - raises: an end off a numbered bus that is neither, two windings out, a control on both windings of a 2-winding unit, a control on a phase tap changer in voltage mode, a 3-winding unit's tabular, a table point with rEnd1 ≠ xEnd1; - the written transformers and R4b models read back with the same records; - core: each getter change against hand numbers on the core shapes.

Expected differences (E4)

  • CW, CZ, CM 2 or 3 come back 1, with their values in CW/CZ/CM 1 units (the transformers atom's A, B, E; R4).
  • NOMV 0 comes back BASKV, the end's ratedU (R4): IEEE14's three units and most atom windings, computed in the test (_nominal_zero).
  • A 3-winding unit's SBASE1-2, 2-3, 3-1 come back SBASE: the transformers atom's E (R4).
  • Blank RMA/RMI and VMA/VMI take RAW's defaults that hang on CW and COD (1.1/0.9, R4), which the schema's static defaults do not hold: the test fills them (IMPORT_DEFAULTS), and they come back written (E).
  • A shifter's RMA/RMI with 0° off its grid come back moved by the offset (the R4b atom's K; R4b-3).
  • COD 0 RMA/RMI/NTP that no tap holds come back blank (defaults; O; P's were blank; R4b-4).
  • A voltage control's extended range comes back as its extended steps' RMA/RMI/NTP (Q; R4b-5).
  • A negative CONT comes back positive (S; R4b-8); a COD ±3 CONT comes back blank.
  • NMETR off a tie comes back blank (2; RAW-22): none in the committed fixtures; about 2165 a local case.
  • WINDV, RMA, RMI, VMA, VMI, R, X, MAG, CR, CX and the table T, F: rel 1e-9.
  • ZCOD, VMSTAR, ANSTAR, O1..F4, NODk: unset, not compared.

Import fix found by the export (R4b-5)

ratio_tap extended a range when WINDV sat exactly at RMA or RMI: rounding put the step a hair past NTP or 1, and ceil/floor added a step, so the tap came back one step wider (RMA/RMI) with NTP + 1. About 50 local windings a case. The extension now applies only to a WINDV outside RMI..RMA (R4b-5's rule), and a WINDV at an end is that end's step. No golden changed; test_ratio_tap_at_an_end_of_its_range_is_not_extended.

Results

All 18 atoms, IEEE14, WECC240 and IEEE118: every compared Transformer and Impedance correction slot equals the RAW as read, except the list above; the E0 to E3 tables are as before. The transformers and R4b atoms write and read back unchanged. to_model exports IEEE14 whole. Put in CW = CZ = CM = 1 by the importer's own conversions (transformer_ohms, magnetizing_siemens, winding_unit_kv; a scratch check, not a test), the atoms' CW/CZ/CM 2 and 3 units (A, B, E, N) come back at rel 1e-9.

Local case set (29 v34 cases of one network, never committed; 3 run, counts only): every transformer (7391 to 7402 a case, about 680 of them 3-winding, 66 phase shifters, 49 tabulars) and all 32 impedance correction tables come back keyed as on import, each case in about 80 s. About 40 % of the units have CW, CZ or CM 2 or 3 and so come back in other units; put in CW = CZ = CM = 1 as above, every R, X, SBASE, MAG, NOMV, WINDV, ANG, COD, VMA, VMI, CR, CX, TAB, STAT and RATE matches at rel 1e-9. Per case the differences left are only the listed ones: NMETR off a tie 2163 to 2168; COD 0 RMA/RMI/NTP that no tap holds, which come back as defaults (R4b-4: about 650 to 700 windings); a shifter's RMA/RMI with 0° off its grid 10 (R4b-3); a COD ±3 CONT 18 and a negative CONT 11 (R4b-8); the one extended voltage-control range (R4b-5). Two defects surfaced and are fixed: WINDV of a winding without a tap (above) and the import's spurious range extension. The E0 to E3 differences are unchanged.

Slots (generated from SLOTS)

TransformerRecord

RAW slot kind from / why
i written I: end 1's busNumber
j written J: end 2's busNumber
k written K: end 3's busNumber; 0 for a 2-winding unit
circuit written CKT: the xf__ key, else the next free (X2)
cw rule CW 1: WINDV, RMA, RMI in pu of the bus's BASKV
cz rule CZ 1: R, X in pu on SBASE and the bus's BASKV
cm rule CM 1: MAG1, MAG2 in pu on SBASE and bus 1's BASKV
mag1 written MAG1: get_transformer_model core g, moved to bus 1's BASKV (admittance_on_bus_base)
mag2 written MAG2: the core b, as MAG1
nmetr written NMETR: on a tie, the winding whose terminal holds no TieFlow (the lower of two); off a tie blank (RAW-22)
name written NAME: X2; blank when it is the key I_J_K_CKT
status rule STAT: 0 when inService is false; 2, 3, 4 when winding 2, 3, 1 alone is disconnected (R4b-6); else 1
o1 unset ownership is an asset concept (CIM 18 gap)
f1 unset ownership is an asset concept (CIM 18 gap)
o2 unset ownership is an asset concept (CIM 18 gap)
f2 unset ownership is an asset concept (CIM 18 gap)
o3 unset ownership is an asset concept (CIM 18 gap)
f3 unset ownership is an asset concept (CIM 18 gap)
o4 unset ownership is an asset concept (CIM 18 gap)
f4 unset ownership is an asset concept (CIM 18 gap)
vecgrp written VECGRP: vectorGroup
zcod unset ZCOD: zero-sequence data is in the sequence file
r1_2 written R1-2: r1 + r2 + the mesh r, pu on SBASE moved to bus 1's BASKV (impedance_on_bus_base; CZ 1); 2-winding
x1_2 written X1-2: the mesh (1, 2) x, as R1-2
sbase1_2 written SBASE1-2: a 2-winding unit's ratedS (MVA); a 3-winding unit's SBASE, since no end holds a pair base (R4)
r2_3 written R2-3: r2 + r3 + the mesh r, pu on SBASE moved to bus 2's BASKV (impedance_on_bus_base; CZ 1); 3-winding
x2_3 written X2-3: the mesh (2, 3) x, as R2-3
sbase2_3 written SBASE2-3: a 2-winding unit's ratedS (MVA); a 3-winding unit's SBASE, since no end holds a pair base (R4)
r3_1 written R1-3: r1 + r3 + the mesh r, pu on SBASE moved to bus 1's BASKV (impedance_on_bus_base; CZ 1); 3-winding
x3_1 written X1-3: the mesh (1, 3) x, as R1-3
sbase3_1 written SBASE1-3: a 2-winding unit's ratedS (MVA); a 3-winding unit's SBASE, since no end holds a pair base (R4)
vmstar unset VMSTAR: the star point's solved voltage, which the Delta model omits
anstar unset ANSTAR: as VMSTAR
windv1 written WINDV1: get_tap_voltage(actual) of the end's RatioTapChanger / bus 1's BASKV (CW 1); without one, ratedU / BASKV (the import writes no tap at ratio NOMV)
nomv1 written NOMV1: winding 1's ratedU (kV)
ang1 written ANG1: -(phaseShift + the PhaseTapChangerLinear's (step - neutral) x increment) (raw_angle); a 2-winding unit's ANG1 is winding 1's less winding 2's
rate1_1 written RATE1-1: the olt_rate1 limit on winding 1's terminal (device_ratings)
rate1_2 written RATE1-2: the olt_rate2 limit on winding 1's terminal (device_ratings)
rate1_3 written RATE1-3: the olt_rate3 limit on winding 1's terminal (device_ratings)
rate1_4 written RATE1-4: the olt_rate4 limit on winding 1's terminal (device_ratings)
rate1_5 written RATE1-5: the olt_rate5 limit on winding 1's terminal (device_ratings)
rate1_6 written RATE1-6: the olt_rate6 limit on winding 1's terminal (device_ratings)
rate1_7 written RATE1-7: the olt_rate7 limit on winding 1's terminal (device_ratings)
rate1_8 written RATE1-8: the olt_rate8 limit on winding 1's terminal (device_ratings)
rate1_9 written RATE1-9: the olt_rate9 limit on winding 1's terminal (device_ratings)
rate1_10 written RATE1-10: the olt_rate10 limit on winding 1's terminal (device_ratings)
rate1_11 written RATE1-11: the olt_rate11 limit on winding 1's terminal (device_ratings)
rate1_12 written RATE1-12: the olt_rate12 limit on winding 1's terminal (device_ratings)
cod1 written COD1: the controlled tap changer: a RatioTapChanger with ltcFlag false 0, else +-1 voltage, +-2 reactivePower; a PhaseTapChangerLinear under activePower +-3; + when the control is enabled
cont1 written CONT1: the busNumber of the control's terminal; the winding's own 0; blank for COD +-3
rma1 written RMA1: the stepped tap's highStep voltage / BASKV, or a shifter's larger end angle (deg); blank for a fixed tap
rmi1 written RMI1: as RMA1, at lowStep or the smaller end angle
vma1 written VMA1: the control's target + deadband / 2: pu of the regulated bus's BASKV, Mvar or MW by mode
vmi1 written VMI1: as VMA1, target - deadband / 2
ntp1 written NTP1: highStep - lowStep + 1 of the stepped tap
tab1 written TAB1: the number of the end's ImpedanceTapChangerTabular's table
cr1 written CR1: lineDropR as pu on SBASE and the regulated bus's BASKV (per_unit_from_ohms)
cx1 written CX1: lineDropX, as CR1
cnxa1 unset CNXA1: only COD +-5 uses it, which is not mapped
nod1 unset NOD1: a node of a node-breaker bus, written by E5
windv2 written WINDV2: a 2-winding unit's RatioTapChanger at its actual step / bus 2's BASKV, ratedU / BASKV without one; a 3-winding unit's as WINDV1
nomv2 written NOMV2: winding 2's ratedU (kV)
ang2 written ANG2: -(phaseShift + the PhaseTapChangerLinear's (step - neutral) x increment) (raw_angle); a 2-winding unit's ANG1 is winding 1's less winding 2's (3-winding only)
rate2_1 written RATE2-1: the olt_rate1 limit on winding 2's terminal (device_ratings)
rate2_2 written RATE2-2: the olt_rate2 limit on winding 2's terminal (device_ratings)
rate2_3 written RATE2-3: the olt_rate3 limit on winding 2's terminal (device_ratings)
rate2_4 written RATE2-4: the olt_rate4 limit on winding 2's terminal (device_ratings)
rate2_5 written RATE2-5: the olt_rate5 limit on winding 2's terminal (device_ratings)
rate2_6 written RATE2-6: the olt_rate6 limit on winding 2's terminal (device_ratings)
rate2_7 written RATE2-7: the olt_rate7 limit on winding 2's terminal (device_ratings)
rate2_8 written RATE2-8: the olt_rate8 limit on winding 2's terminal (device_ratings)
rate2_9 written RATE2-9: the olt_rate9 limit on winding 2's terminal (device_ratings)
rate2_10 written RATE2-10: the olt_rate10 limit on winding 2's terminal (device_ratings)
rate2_11 written RATE2-11: the olt_rate11 limit on winding 2's terminal (device_ratings)
rate2_12 written RATE2-12: the olt_rate12 limit on winding 2's terminal (device_ratings)
cod2 written COD2: the controlled tap changer: a RatioTapChanger with ltcFlag false 0, else +-1 voltage, +-2 reactivePower; a PhaseTapChangerLinear under activePower +-3; + when the control is enabled (3-winding only)
cont2 written CONT2: the busNumber of the control's terminal; the winding's own 0; blank for COD +-3 (3-winding only)
rma2 written RMA2: the stepped tap's highStep voltage / BASKV, or a shifter's larger end angle (deg); blank for a fixed tap (3-winding only)
rmi2 written RMI2: as RMA2, at lowStep or the smaller end angle (3-winding only)
vma2 written VMA2: the control's target + deadband / 2: pu of the regulated bus's BASKV, Mvar or MW by mode (3-winding only)
vmi2 written VMI2: as VMA2, target - deadband / 2 (3-winding only)
ntp2 written NTP2: highStep - lowStep + 1 of the stepped tap (3-winding only)
tab2 written TAB2: the number of the end's ImpedanceTapChangerTabular's table (3-winding only)
cr2 written CR2: lineDropR as pu on SBASE and the regulated bus's BASKV (per_unit_from_ohms) (3-winding only)
cx2 written CX2: lineDropX, as CR2 (3-winding only)
cnxa2 unset CNXA2: only COD +-5 uses it, which is not mapped
nod2 unset NOD2: a node of a node-breaker bus, written by E5
windv3 written WINDV3: get_tap_voltage(actual) of the end's RatioTapChanger / bus 3's BASKV (CW 1); without one, ratedU / BASKV (the import writes no tap at ratio NOMV)
nomv3 written NOMV3: winding 3's ratedU (kV)
ang3 written ANG3: -(phaseShift + the PhaseTapChangerLinear's (step - neutral) x increment) (raw_angle); a 2-winding unit's ANG1 is winding 1's less winding 2's (3-winding only)
rate3_1 written RATE3-1: the olt_rate1 limit on winding 3's terminal (device_ratings)
rate3_2 written RATE3-2: the olt_rate2 limit on winding 3's terminal (device_ratings)
rate3_3 written RATE3-3: the olt_rate3 limit on winding 3's terminal (device_ratings)
rate3_4 written RATE3-4: the olt_rate4 limit on winding 3's terminal (device_ratings)
rate3_5 written RATE3-5: the olt_rate5 limit on winding 3's terminal (device_ratings)
rate3_6 written RATE3-6: the olt_rate6 limit on winding 3's terminal (device_ratings)
rate3_7 written RATE3-7: the olt_rate7 limit on winding 3's terminal (device_ratings)
rate3_8 written RATE3-8: the olt_rate8 limit on winding 3's terminal (device_ratings)
rate3_9 written RATE3-9: the olt_rate9 limit on winding 3's terminal (device_ratings)
rate3_10 written RATE3-10: the olt_rate10 limit on winding 3's terminal (device_ratings)
rate3_11 written RATE3-11: the olt_rate11 limit on winding 3's terminal (device_ratings)
rate3_12 written RATE3-12: the olt_rate12 limit on winding 3's terminal (device_ratings)
cod3 written COD3: the controlled tap changer: a RatioTapChanger with ltcFlag false 0, else +-1 voltage, +-2 reactivePower; a PhaseTapChangerLinear under activePower +-3; + when the control is enabled (3-winding only)
cont3 written CONT3: the busNumber of the control's terminal; the winding's own 0; blank for COD +-3 (3-winding only)
rma3 written RMA3: the stepped tap's highStep voltage / BASKV, or a shifter's larger end angle (deg); blank for a fixed tap (3-winding only)
rmi3 written RMI3: as RMA3, at lowStep or the smaller end angle (3-winding only)
vma3 written VMA3: the control's target + deadband / 2: pu of the regulated bus's BASKV, Mvar or MW by mode (3-winding only)
vmi3 written VMI3: as VMA3, target - deadband / 2 (3-winding only)
ntp3 written NTP3: highStep - lowStep + 1 of the stepped tap (3-winding only)
tab3 written TAB3: the number of the end's ImpedanceTapChangerTabular's table (3-winding only)
cr3 written CR3: lineDropR as pu on SBASE and the regulated bus's BASKV (per_unit_from_ohms) (3-winding only)
cx3 written CX3: lineDropX, as CR3 (3-winding only)
cnxa3 unset CNXA3: only COD +-5 uses it, which is not mapped
nod3 unset NOD3: a node of a node-breaker bus, written by E5

ImpedanceCorrectionRecord

RAW slot kind from / why
table_number written I: the ict_ key, else the next number (X2)
points written the table's points (get_impedance_table), by T ascending

ImpedanceCorrectionPoint

RAW slot kind from / why
t written Ti: an angle point's raw_angle(angle) (deg), or a ratio point's ratio x ratedU / BASKV of its users' winding (users that disagree, or none, raise)
f_real written Re(Fi): 1 + rEnd1 / 100 (impedance_factor); rEnd1 != xEnd1, or rEnd2/3, xEnd2/3 set, raise
f_imag rule Im(Fi): 0 (CIM's deviations are real)

E6a: FACTS device and static var compensator (user 2026-11-28: "SVC support for the cimhub_raw importer and exporter"; done 2026-11-28)

The first part of E6 (plan §9: phase 2 as imported). A shunt-only FACTS device (P2-2) was imported but raised on export; a CIM StaticVarCompensator had neither an import nor an export. RAW v34 has no SVC record, so an SVC is a MODSW 2 switched shunt, and the import makes one back from that form (R2c, CIMTBL_MAPPING.md).

FACTS device, shunt only

exporter/facts_device.py: one record per StaticSynchronousCompensator, P2-2 inverted.

RAW from
NAME the device's name, the record's key; unset or over 12 characters raises
I the busNumber of its terminal
J 0: a StaticSynchronousCompensator has no series element
MODE 0 when inService is false, else 1
VSET get_regulating_control target in kV over the regulated bus's BASKV (per_unit_from_kv)
SHMX rating_from_ka(ratedI, BASKV(I)), MVA at unity voltage; an unset ratedI raises
FCREG the busNumber of the control's terminal, its own bus included (E6a-1)
NREG unset until E5 (a node of a node-breaker block)
PDES .. MNAME unset: the series element's; RMPCT and OWNER unset (no CIM home)

A device with no RegulatingControl, one not of mode voltage, or a disabled one (enabled or controlEnabled false) raises: a shunt-only FACTS device always holds VSET, and RAW has no locked mode for one. A control's targetDeadband is not written (RAW has none). MODSW 6's RMIDNT is the same name, so the shunt finds its device.

Static var compensator

exporter/switched_shunt.py: one Switched shunt per StaticVarCompensator, R2c inverted.

RAW from
I the busNumber of its terminal
N1, B1 1 step of SBASE / inductiveRating (pu system: get_qty(..., "pu", base="system"); svc_block_mvar), when set
N2, B2 (or N1, B1 with no reactor) 1 step of SBASE / capacitiveRating, when set
BINIT −q in Mvar (svc_binit); blank when q is unset
STATUS 0 when inService is false, else 1
MODSW 2 under its voltage RegulatingControl; 0 when locked (enabled or the SVC's controlEnabled false)
VSWHI, VSWLO, SWREG from the control, as a voltage bank's (target ± deadband / 2 over the regulated bus's BASKV; SWREG I for its own bus, E2-2)

Reactor first, as the bank fallback orders blocks. Raises: no RegulatingControl; a control of mode reactivePower or an sVCControlMode of reactivePower (MODSW 2 holds a voltage); a discrete control; an inductiveRating ≥ 0 or a capacitiveRating ≤ 0 (CIM's signs); neither rating set; an SVC on a bus that already has a switched shunt (the key rule above). voltageSetPoint and slope are not read: the control carries the target, and RAW has no droop.

Decisions

  • E6a-1. FCREG of a device regulating its own bus: I, always, as E2-2 (SWREG) and E3-4 (IREG). RAW writes 0 or I for the same meaning, and CIM keeps neither.

Tests (E6a)

tests/test_cim_to_raw.py: the round trip with facts_device added, over every fixture (the FACTS atom facts_vsc, plant_and_facts's SVC-1, and the new svc atom), and: - the SVC atom's two SVCs come back as a reactor-then-capacitor and a capacitor-only record; a locked SVC is MODSW 0; - raises: an SVC with no control, ratings of the wrong sign or none, a discrete or a reactive-power control, an SVC and a bank on one bus; a STATCOM whose name is unset or too long, with no voltage control, locked, or with no ratedI; - the written svc and facts_vsc models read back with the same records; - derived: svc_block_mvar and svc_binit against svc_reactance and svc_q.

Expected differences (E6a)

  • FCREG 0 comes back I (E6a-1), computed in the test (_own_bus_fcreg): the FACTS atom's STATCOM-LOC and STATCOM-OUT, the plant-and-facts atom's SVC-1.
  • The series element's fields, RMPCT and OWNER are unset, not compared (P2-2 lists them when not the default).
  • An SVC whose capacitor block came before its reactor comes back reactor first (none in the fixtures).
  • SHMX can differ in the last digit (kA × √3 × kV; rel 1e-9).

Results

IEEE14, WECC240, IEEE118 and all 19 atoms: every compared slot of FACTS device and Switched shunt equals the RAW as read, except the list above. A case with a shunt-only FACTS device no longer raises on export; one with a VSC or two-terminal DC line still does (E6). The local case set was not swept (CIMHUB_RAW_SWEEP_DIR does not exist yet): its MODSW 2 shunts of one one-step reactor and capacitor, if any, are now SVCs.

Slots (generated from SLOTS)

FactsDeviceRecord

RAW slot kind from / why
name written NAME: the device's name, the record's key (unset or over 12 characters raises)
ibus written I: the busNumber of the device's terminal
jbus rule J: 0, shunt only (a StaticSynchronousCompensator has no series element)
mode rule MODE: 0 when inService is false, else 1
pdes unset PDES: the series element's; a shunt-only device has none
qdes unset QDES: the series element's; a shunt-only device has none
trmx unset TRMX: the series element's; a shunt-only device has none
vtmn unset VTMN: the series element's; a shunt-only device has none
vtmx unset VTMX: the series element's; a shunt-only device has none
vsmx unset VSMX: the series element's; a shunt-only device has none
imx unset IMX: the series element's; a shunt-only device has none
linx unset LINX: the series element's; a shunt-only device has none
set1 unset SET1: the series element's; a shunt-only device has none
set2 unset SET2: the series element's; a shunt-only device has none
vsref unset VSREF: the series element's; a shunt-only device has none
mname unset MNAME: the series element's; a shunt-only device has none
vset written VSET: get_regulating_control target in kV over the regulated bus's BASKV
shmx written SHMX: rating_from_ka(ratedI, BASKV of I), MVA at unity voltage
rmpct unset RMPCT: a shunt's participation share has no CIM home (CIM 18 gap)
owner unset OWNER: ownership is an asset concept (CIM 18 gap)
remot written FCREG: the busNumber of the control's terminal, its own bus included (E6a-1)
nreg unset NREG: a node of a node-breaker block, written by E5