Branches, switches and multi-section lines¶
Everything that joins two buses and is not a transformer: the Non-transformer branch (lines, series capacitors and their
line shunts), the System switching device, the Multi-section line grouping, and the RATE1..RATE12 ratings each of them
carries. Field classes, the .cimtbl header conventions and the full table list are on the
reference landing page.
| RAW table | CIM (cim18v17) | Import (.cimtbl) |
Export module |
|---|---|---|---|
| Non-transformer branch, X >= 0 | ACLineSegment |
branch.cimtbl |
exporter/branch.py |
| Non-transformer branch, X < 0 | SeriesCompensator (compensatorType = capacitor) |
branch.cimtbl |
exporter/branch.py |
| Branch GI, BI, GJ, BJ | LinearShuntCompensator |
branch.cimtbl |
exporter/branch.py |
| System switching device | Switch, Breaker, Disconnector |
switch.cimtbl |
exporter/switch.py |
| Multi-section line grouping | Line holding its sections |
multi_section_line.cimtbl |
exporter/multi_section_line.py |
| RATE1..RATE12, NXFRAT | OperationalLimitSet + ApparentPowerLimit or CurrentLimit |
the three files above | exporter/ratings.py |
The shapes are on the core site's shapes page. The
getters the exporter reads through (get_line_sequence_impedance, get_series_compensator, get_shunt_admittance,
get_switch_state, get_limits_by_type) are described in the core
getters guide.
Try it¶
from cimhub_raw.raw34_reader import Raw34Reader
from cimhub_raw.importer.raw_to_cimtbl import raw_to_cim
from cimhub_raw.exporter.cim_to_raw import RawExporter
import cimhub_raw.schema.raw_v34.raw34_schema as schema
model = Raw34Reader("cimhub_raw/tests/atoms/branch/mixed_base.raw").read_all()
network = raw_to_cim(model, name="mixed_base", artifact_dir="/tmp/raw-branches") # branch.cimtbl, ...
back = RawExporter().to_model(network)
for branch in sorted(back.list_by_class(schema.BranchRecord), key=lambda b: b.ID):
print(branch.ID, branch.r, branch.x, branch.b, branch.length, branch.b_to)
1_2_1 0.001 0.01 0.02 None None
2_3_1 0.0 -0.005 None None None
3_4_1 0.001 0.01 0.02 None None
4_5_1 0.002 0.02 0.02 None 0.01
Branch 2_3_1 has X < 0, so it is a SeriesCompensator and comes back with no B and no length. Branch 4_5_1 joins
a 230 kV bus to a 240 kV bus.
Units¶
RAW states a branch's R, X and B in per unit on the case's SBASE and the bus base voltage. The importer copies the numbers and names the base in the column header:
| header | meaning |
|---|---|
r (pu system), x (pu system), bch (pu system) |
pu on the master's BasePower (SBASE) and the equipment's BaseVoltage, which is bus I's bv_<BASKV> |
gPerSection (pu system), bPerSection (pu system) |
a line shunt: pu on SBASE and its own bus's BASKV |
length (km) |
LEN, copied; RAW's "user-selected units" are taken as km |
normalValue (MVA) |
a rating in MVA, copied |
normalValue (kA) |
a rating "in current expressed as MVA" (NXFRAT > 0): kA = RATEn / (sqrt(3) x BASKV) |
cimtables turns (pu system) into ohm and S when it binds the table, so the mapper does no impedance arithmetic. The
exporter asks the getter for pu on the same two bases (SBASE and the equipment's BaseVoltage) and writes R, X and B as
RAW states them.
A branch between two base voltages. CIM gives an ACLineSegment one BaseVoltage, and a RAW branch whose buses I and J
have different BASKV is still one line. It keeps bus I's base for R, X and B and for a current rating, and its row lists bus
J's base in a comment (# BASKV 240.0 at bus J). The exporter reads pu on the line's own base, so R, X and B round-trip
exactly. A line shunt keeps its own bus's base, so GJ + jBJ stays on bus J's BASKV. No transformer is inserted for the step
between the bases: a solver that works in kV sees that step at bus J.
Branch¶
One row per branch, in (I, J, CKT) order. A branch with X < 0 is a series capacitor and goes to a SeriesCompensator
table, with compensatorType = capacitor and R and X copied as written (X stays negative). Every other branch is an
ACLineSegment. The mRID is ln_<I>_<J>_<CKT> (a capacitor: sc_<I>_<J>_<CKT>), and the name is NAME, or the key
I_J_CKT when NAME is blank.
The container is the substation when both buses are in one (a zero-impedance branch, a series capacitor, a circuit whose ID
starts with @ or *, or a parallel path inside a merged substation). Otherwise the cell is blank, or the multi-section
Line that holds the branch (below). A blank field that the schema gives a default is filled, and the row says so
(# defaulted: ...).
| field | import | export |
|---|---|---|
I (from_bus_number) |
structural: bus1; bv_<BASKV> of bus I is the row's BaseVoltage |
terminal 1's busNumber |
J (to_bus_number) |
structural: bus2 |
terminal 2's busNumber |
CKT (circuit) |
structural: with I and J the mRID key | the mRID key when its buses are I and J in order, else the next free 1, 2, ... on the pair |
R (r) |
ACLineSegment.r, SeriesCompensator.r (pu system) |
get_line_sequence_impedance or get_series_compensator, in pu |
X (x) |
ACLineSegment.x, SeriesCompensator.x (pu system); X < 0 selects the capacitor |
the same getters, in pu |
B (b) |
ACLineSegment.bch (pu system); blank: 0. A series capacitor with B != 0 raises (SeriesCompensator has no bch) |
the line's b in pu; blank for a series capacitor |
NAME (name) |
name; blank: the key |
blank when the name is the key; longer than 40 characters raises |
ST (status) |
mapped: inService = (ST == 1), also on the line shunts; blank: 1 |
0 when inService is false, else 1 |
LEN (length) |
ACLineSegment.length (km); 0 or blank writes no length. A series capacitor's LEN != 0 is listed on its row (SeriesCompensator is no conductor) |
length in km; blank when unset, and blank for a series capacitor |
GI, BI (g_from, b_from) |
structural: a LinearShuntCompensator cap_<key>_i on bus I when either is nonzero |
the shunt cap_<key>_i: g and b in pu on its bus's base |
GJ, BJ (g_to, b_to) |
structural: cap_<key>_j on bus J when either is nonzero |
the shunt cap_<key>_j |
RATE1..RATE12 (ratings) |
structural: Ratings | the limits of types olt_rate1..olt_rate12 |
MET (metered_end) |
structural on a tie (below); elsewhere untranscribed. Blank: 1 | on a tie, the terminal that holds the TieFlow pair; off a tie, blank |
| O1..O4, F1..F4 | untranscribed: ownership is an asset concept (CIM 18 gap) | not exported |
Line shunts. GI + jBI and GJ + jBJ are admittances at 1 pu of their bus's BASKV. Each becomes an ordinary
LinearShuntCompensator with one section, nomU = the bus's BASKV, the bus's BaseVoltage and substation, and
inService = the branch's ST. CIM 18 has no association from a shunt to its line, so the pairing is carried by the mRID
alone: cap_<I>_<J>_<CKT>_i and _j. The exporter takes a shunt with such an mRID, on the matching branch's node, as that
branch's GI/BI or GJ/BJ. The shunt tables skip it.
Ties. When I and J are in two AREAs, MET names the metered end, and the other end is the home end whose area PSS/E
charges with the losses. The importer writes two TieFlows on the metered terminal: the bus's area with
positiveFlowIn = false and the home area with true. The exporter reads MET back from the terminal that holds the pair.
Off a tie MET has no CIM home.
Excerpt from cimhub_raw/tests/goldens/IEEE14/branch.cimtbl (all 17 branches of IEEE 14 are lines with no length and no
rating):
Table ACLineSegment: mRID, name, bus1, bus2, r (pu system), x (pu system), bch (pu system), length (km), inService, BaseVoltage, EquipmentContainer
ln_1_2_1, 1_2_1, 1, 2, 0.01938, 0.05917, 0.0528, , true, bv_138kv,
ln_1_5_1, 1_5_1, 1, 5, 0.05403, 0.22304, 0.0492, , true, bv_138kv,
The rows the importer wrote for the atom cimhub_raw/tests/atoms/branch/mixed_base.raw (a series capacitor with a length,
a line between two base voltages, and the shunt at its bus J):
Table ACLineSegment: mRID, name, bus1, bus2, r (pu system), x (pu system), bch (pu system), length (km), inService, BaseVoltage, EquipmentContainer
ln_1_2_1, 1_2_1, 1, 2, 0.001, 0.01, 0.02, , true, bv_230kv,
ln_3_4_1, 3_4_1, 3, 4, 0.001, 0.01, 0.02, , true, bv_230kv,
# BASKV 240.0 at bus J
ln_4_5_1, 4_5_1, 4, 5, 0.002, 0.02, 0.02, , true, bv_230kv,
Table SeriesCompensator: mRID, name, bus1, bus2, compensatorType, r (pu system), x (pu system), inService, BaseVoltage, EquipmentContainer
# untranscribed: length=1.0
sc_2_3_1, 2_3_1, 2, 3, capacitor, 0.0, -0.005, true, bv_230kv, sub_2
Table LinearShuntCompensator: mRID, name, bus, gPerSection (pu system), bPerSection (pu system), nomU (kV), sections, normalSections, maximumSections, inService, BaseVoltage, EquipmentContainer
cap_4_5_1_j, 4_5_1_j, 5, 0.0, 0.01, 240.0, 1, 1, 1, true, bv_240kv, sub_5
Fail fast, import. A series capacitor (X < 0) with B != 0. An ST that is not 0 or 1. On a tie, a MET that is not 1 or 2, or an AREA with no area-interchange record.
Fail fast, export. A line with gch set (RAW has no line conductance). A branch on a node with no
busNumber. A line shunt whose inService differs from its line's, or whose nomU is not its BaseVoltage (RAW states a
shunt at 1 pu of its bus voltage). A NAME longer than 40 characters. Two branches with one key. TieFlow pairs on both
terminals of one branch. Ratings of both kinds (see Ratings). The exporter reads a line's own lumped r, x and b, so a line with only a per-length impedance raises.
Expected differences. MET 2 off a tie comes back blank, which reads as the default 1. A series capacitor's LEN comes back blank. A SeriesCompensator
with X >= 0 is written as a branch and would import as an ACLineSegment. Owners are not exported.
System switching device¶
switch.cimtbl has one table per class, with the same columns. STYPE picks the class, and the mRID prefix sw_ is the same
for all three, so a change of class keeps the mRID. The switch's BaseVoltage is bus I's and its container is bus I's
substation, since a switch merges its two buses into one substation. A switch across a zone boundary is not a merge edge,
and its container is still bus I's substation.
| field | import | export |
|---|---|---|
I, J (from_bus_number, to_bus_number) |
structural: bus1, bus2 |
terminals 1 and 2's busNumber |
CKT (circuit) |
structural: mRID sw_<I>_<J>_<CKT> |
as a branch's |
STYPE (stype) |
mapped: 1 Switch, 2 Breaker, 3 Disconnector. Blank or another code raises: no default |
by class, the same numbers |
STATUS (status) |
mapped: open = (STATUS == 0); blank: 1 |
get_switch_state actual: open is 0, closed 1 |
NSTATUS (nstat) |
mapped: normalOpen = (NSTATUS == 0); blank: 1 |
get_switch_state normal |
X (x) |
untranscribed: the solver's stand-in for zero impedance; a switch has none | always 0.0001 (the format gives X no default) |
METERED (metered_end) |
structural on a tie, as a branch's MET; elsewhere untranscribed. Blank: 1 | on a tie the terminal that holds the TieFlows, else 1 |
NAME (name) |
name; blank: the key |
as a branch's |
RATE1..RATE12 (ratings) |
structural: Ratings | as a branch's |
Excerpt from cimhub_raw/tests/atoms/branch/switches.raw (one switch of each STYPE, the first rated in current):
Table Breaker: mRID, name, bus1, bus2, open, normalOpen, BaseVoltage, EquipmentContainer
sw_102_103_1, BREAKER, 102, 103, true, false, bv_138kv, sub_101
Table Disconnector: mRID, name, bus1, bus2, open, normalOpen, BaseVoltage, EquipmentContainer
sw_103_104_1, DISCONNECT, 103, 104, false, true, bv_138kv, sub_101
Table CurrentLimit: mRID, OperationalLimitSet, OperationalLimitType, normalValue (kA)
sw_101_102_1_rate1, sw_101_102_1_ratings, olt_rate1, 0.836739520564675
Fail fast. On import, a blank STYPE, and an STYPE, STATUS or NSTATUS outside its codes (a blank STATUS or NSTATUS is 1). On export, a switch with a ConnectivityNode on one
terminal only, and any switch class other than Switch, Breaker and Disconnector (a fuse or a recloser has no RAW form,
and the exporter raises on any conducting equipment it has no module for).
Expected differences. A switch's X other than 0.0001 comes back 0.0001. METERED 2 off a tie comes back 1. A switch with
a ConnectivityNode on both terminals belongs to a node-breaker substation (see Substations); this
exporter leaves it out, and the exporter has no module for node-breaker substations yet, so such switches are not in the
exported case. The export logs a warning that counts them.
Multi-section line¶
A multi-section line record names a path of buses: I, then the dummy buses DUM1..DUM9 that are set, then J. The sections
stay ordinary branches in branch.cimtbl, and the dummy buses stay buses. The record becomes a Line (mRID
msl_<I>_<J>_<ID>, name ID, Region = bus I's zone), and an Update row moves each section into it.
| field | import | export |
|---|---|---|
I, J (i, j) |
structural: the key and the path's ends | the path's ends: from the mRID key when it names them in order, else the lower bus first |
ID (line_id) |
copied to Line.name; part of the key |
the mRID key, else the next free &1, &2, ... |
DUM1..DUM9 (dum1..dum9) |
structural: the path I, DUM1, ..., J names the sections, one branch per step | the path's dummy buses in order, blank past the end |
MET (met) |
untranscribed: the loss-allocation end has no CIM home | not exported |
Each step of the path must be joined by exactly one branch that no earlier record has used, in either direction (a section
may be entered 4-3 for a path from 3 to 4), and each dummy bus must have exactly two branches. A section whose two buses
are in one substation (a series capacitor merges its buses) stays contained by that substation and joins the Line through
the second container association, AdditionalEquipmentContainer. The Line's row lists it:
# path 1, 2, 3, 4; in substations: sc_2_3_1.
Excerpt from cimhub_raw/tests/atoms/branch/mixed_base.raw, a line &1 of three sections through buses 2 and 3, the middle
one a series capacitor:
Table Line: mRID, name, Region
# path 1, 2, 3, 4; in substations: sc_2_3_1
msl_1_4_&1, &1, srgn_1
Update Table ACLineSegment: mRID, EquipmentContainer
ln_1_2_1, msl_1_4_&1
ln_3_4_1, msl_1_4_&1
Update Table SeriesCompensator: mRID, AdditionalEquipmentContainer
sc_2_3_1, msl_1_4_&1
Fail fast, import. A dummy bus with other than two branches. A step of the path with no unused branch, or with more than one (parallel branches between two path buses are ambiguous).
Fallback, export. A Line whose sections are not one path of one to nine dummy buses, each joining exactly two
branches, writes no multi-section record and raises nothing: its sections are still written as branches, and the count of
such lines is logged.
Expected differences. MET is not exported. A record with no dummy bus (I and J joined by one branch) is read by the importer but not written back.
Ratings¶
RATE1..RATE12 are the twelve rating sets of the case. The master table writes twelve OperationalLimitTypes,
olt_rate1..olt_rate12, named from the RATING records (a set with no record is named RATEn and described
RATING SET n).
A device's nonzero ratings go into one OperationalLimitSet <mRID>_ratings on its first terminal <mRID>_T1 (bus I),
one limit per rating, mRID <mRID>_rate<n>, of type olt_rate<n>. A zero rating is PSS/E's "no limit", so it writes no
row, and a device with no nonzero rating has no set. A transformer's ratings are one set per winding; see
Transformers.
| NXFRAT | limit class | normalValue |
value |
|---|---|---|---|
| 0 or less | ApparentPowerLimit |
MVA | RATEn, copied |
| > 0 | CurrentLimit |
kA | RATEn / (sqrt(3) x BASKV), the rating being a current "expressed as MVA" at bus I's BASKV |
A blank NXFRAT is the present option setting, which the importer reads as MVA and notes on the master
(# defaulted: NXFRAT=0). One flag holds for every branch and switch of the case.
The exporter reads RATEn from the limit whose type is olt_rate<n>, with 0 where there is none. A current limit becomes MVA
= sqrt(3) x BASKV x kA on the device's BaseVoltage. It writes NXFRAT 1 when the case's branch and switch ratings are
CurrentLimits, and 0 when they are ApparentPowerLimits or there are none.
Fail fast, export. A limit whose type is not one of olt_rate1..olt_rate12. A device with both
ApparentPowerLimits and CurrentLimits, or a case that holds both kinds among its branches and switches.
Expected differences. A case with no rated branch or switch comes back NXFRAT 0, whatever it was.
Excerpt from cimhub_raw/tests/atoms/branch/line_shunts.raw (RATE1 100 and RATE2 120 MVA on branch 1-2):
Table OperationalLimitSet: mRID, Terminal
ln_1_2_1_ratings, ln_1_2_1_T1
Table ApparentPowerLimit: mRID, OperationalLimitSet, OperationalLimitType, normalValue (MVA)
ln_1_2_1_rate1, ln_1_2_1_ratings, olt_rate1, 100.0
ln_1_2_1_rate2, ln_1_2_1_ratings, olt_rate2, 120.0
Where the rules are specified¶
The per-field classification with its reasons is in the import mapping (sections Branch, System switching device, Multi-section line) and the export mapping (section E1).