Everything that joins two buses and is not a transformer: the Non-transformer branch (lines, series capacitors and their line shunts), the System switching device, the Multi-section line grouping, and the RATE1..RATE12 ratings each of them carries. Field classes, the .cimtbl header conventions and the full table list are on the reference landing page.

RAW table CIM (cim18v17) Import (.cimtbl) Export module
Non-transformer branch, X >= 0 ACLineSegment branch.cimtbl exporter/branch.py
Non-transformer branch, X < 0 SeriesCompensator (compensatorType = capacitor) branch.cimtbl exporter/branch.py
Branch GI, BI, GJ, BJ LinearShuntCompensator branch.cimtbl exporter/branch.py
System switching device Switch, Breaker, Disconnector switch.cimtbl exporter/switch.py
Multi-section line grouping Line holding its sections multi_section_line.cimtbl exporter/multi_section_line.py
RATE1..RATE12, NXFRAT OperationalLimitSet + ApparentPowerLimit or CurrentLimit the three files above exporter/ratings.py

The shapes are on the core site's shapes page. The getters the exporter reads through (get_line_sequence_impedance, get_series_compensator, get_shunt_admittance, get_switch_state, get_limits_by_type) are described in the core getters guide.

Try it

from cimhub_raw.raw34_reader import Raw34Reader
from cimhub_raw.importer.raw_to_cimtbl import raw_to_cim
from cimhub_raw.exporter.cim_to_raw import RawExporter
import cimhub_raw.schema.raw_v34.raw34_schema as schema

model = Raw34Reader("cimhub_raw/tests/atoms/branch/mixed_base.raw").read_all()
network = raw_to_cim(model, name="mixed_base", artifact_dir="/tmp/raw-branches")  # branch.cimtbl, ...
back = RawExporter().to_model(network)
for branch in sorted(back.list_by_class(schema.BranchRecord), key=lambda b: b.ID):
    print(branch.ID, branch.r, branch.x, branch.b, branch.length, branch.b_to)
1_2_1 0.001 0.01 0.02 None None
2_3_1 0.0 -0.005 None None None
3_4_1 0.001 0.01 0.02 None None
4_5_1 0.002 0.02 0.02 None 0.01

Branch 2_3_1 has X < 0, so it is a SeriesCompensator and comes back with no B and no length. Branch 4_5_1 joins a 230 kV bus to a 240 kV bus.

Units

RAW states a branch's R, X and B in per unit on the case's SBASE and the bus base voltage. The importer copies the numbers and names the base in the column header:

header meaning
r (pu system), x (pu system), bch (pu system) pu on the master's BasePower (SBASE) and the equipment's BaseVoltage, which is bus I's bv_<BASKV>
gPerSection (pu system), bPerSection (pu system) a line shunt: pu on SBASE and its own bus's BASKV
length (km) LEN, copied; RAW's "user-selected units" are taken as km
normalValue (MVA) a rating in MVA, copied
normalValue (kA) a rating "in current expressed as MVA" (NXFRAT > 0): kA = RATEn / (sqrt(3) x BASKV)

cimtables turns (pu system) into ohm and S when it binds the table, so the mapper does no impedance arithmetic. The exporter asks the getter for pu on the same two bases (SBASE and the equipment's BaseVoltage) and writes R, X and B as RAW states them.

A branch between two base voltages. CIM gives an ACLineSegment one BaseVoltage, and a RAW branch whose buses I and J have different BASKV is still one line. It keeps bus I's base for R, X and B and for a current rating, and its row lists bus J's base in a comment (# BASKV 240.0 at bus J). The exporter reads pu on the line's own base, so R, X and B round-trip exactly. A line shunt keeps its own bus's base, so GJ + jBJ stays on bus J's BASKV. No transformer is inserted for the step between the bases: a solver that works in kV sees that step at bus J.

Branch

One row per branch, in (I, J, CKT) order. A branch with X < 0 is a series capacitor and goes to a SeriesCompensator table, with compensatorType = capacitor and R and X copied as written (X stays negative). Every other branch is an ACLineSegment. The mRID is ln_<I>_<J>_<CKT> (a capacitor: sc_<I>_<J>_<CKT>), and the name is NAME, or the key I_J_CKT when NAME is blank.

The container is the substation when both buses are in one (a zero-impedance branch, a series capacitor, a circuit whose ID starts with @ or *, or a parallel path inside a merged substation). Otherwise the cell is blank, or the multi-section Line that holds the branch (below). A blank field that the schema gives a default is filled, and the row says so (# defaulted: ...).

field import export
I (from_bus_number) structural: bus1; bv_<BASKV> of bus I is the row's BaseVoltage terminal 1's busNumber
J (to_bus_number) structural: bus2 terminal 2's busNumber
CKT (circuit) structural: with I and J the mRID key the mRID key when its buses are I and J in order, else the next free 1, 2, ... on the pair
R (r) ACLineSegment.r, SeriesCompensator.r (pu system) get_line_sequence_impedance or get_series_compensator, in pu
X (x) ACLineSegment.x, SeriesCompensator.x (pu system); X < 0 selects the capacitor the same getters, in pu
B (b) ACLineSegment.bch (pu system); blank: 0. A series capacitor with B != 0 raises (SeriesCompensator has no bch) the line's b in pu; blank for a series capacitor
NAME (name) name; blank: the key blank when the name is the key; longer than 40 characters raises
ST (status) mapped: inService = (ST == 1), also on the line shunts; blank: 1 0 when inService is false, else 1
LEN (length) ACLineSegment.length (km); 0 or blank writes no length. A series capacitor's LEN != 0 is listed on its row (SeriesCompensator is no conductor) length in km; blank when unset, and blank for a series capacitor
GI, BI (g_from, b_from) structural: a LinearShuntCompensator cap_<key>_i on bus I when either is nonzero the shunt cap_<key>_i: g and b in pu on its bus's base
GJ, BJ (g_to, b_to) structural: cap_<key>_j on bus J when either is nonzero the shunt cap_<key>_j
RATE1..RATE12 (ratings) structural: Ratings the limits of types olt_rate1..olt_rate12
MET (metered_end) structural on a tie (below); elsewhere untranscribed. Blank: 1 on a tie, the terminal that holds the TieFlow pair; off a tie, blank
O1..O4, F1..F4 untranscribed: ownership is an asset concept (CIM 18 gap) not exported

Line shunts. GI + jBI and GJ + jBJ are admittances at 1 pu of their bus's BASKV. Each becomes an ordinary LinearShuntCompensator with one section, nomU = the bus's BASKV, the bus's BaseVoltage and substation, and inService = the branch's ST. CIM 18 has no association from a shunt to its line, so the pairing is carried by the mRID alone: cap_<I>_<J>_<CKT>_i and _j. The exporter takes a shunt with such an mRID, on the matching branch's node, as that branch's GI/BI or GJ/BJ. The shunt tables skip it.

Ties. When I and J are in two AREAs, MET names the metered end, and the other end is the home end whose area PSS/E charges with the losses. The importer writes two TieFlows on the metered terminal: the bus's area with positiveFlowIn = false and the home area with true. The exporter reads MET back from the terminal that holds the pair. Off a tie MET has no CIM home.

Excerpt from cimhub_raw/tests/goldens/IEEE14/branch.cimtbl (all 17 branches of IEEE 14 are lines with no length and no rating):

Table ACLineSegment: mRID, name, bus1, bus2, r (pu system), x (pu system), bch (pu system), length (km), inService, BaseVoltage, EquipmentContainer
    ln_1_2_1,   1_2_1,   1,  2,  0.01938, 0.05917, 0.0528, , true, bv_138kv,
    ln_1_5_1,   1_5_1,   1,  5,  0.05403, 0.22304, 0.0492, , true, bv_138kv,

The rows the importer wrote for the atom cimhub_raw/tests/atoms/branch/mixed_base.raw (a series capacitor with a length, a line between two base voltages, and the shunt at its bus J):

Table ACLineSegment: mRID, name, bus1, bus2, r (pu system), x (pu system), bch (pu system), length (km), inService, BaseVoltage, EquipmentContainer
    ln_1_2_1, 1_2_1, 1, 2, 0.001, 0.01, 0.02, , true, bv_230kv,
    ln_3_4_1, 3_4_1, 3, 4, 0.001, 0.01, 0.02, , true, bv_230kv,
    # BASKV 240.0 at bus J
    ln_4_5_1, 4_5_1, 4, 5, 0.002, 0.02, 0.02, , true, bv_230kv,

Table SeriesCompensator: mRID, name, bus1, bus2, compensatorType, r (pu system), x (pu system), inService, BaseVoltage, EquipmentContainer
    # untranscribed: length=1.0
    sc_2_3_1, 2_3_1, 2, 3, capacitor, 0.0, -0.005, true, bv_230kv, sub_2

Table LinearShuntCompensator: mRID, name, bus, gPerSection (pu system), bPerSection (pu system), nomU (kV), sections, normalSections, maximumSections, inService, BaseVoltage, EquipmentContainer
    cap_4_5_1_j, 4_5_1_j, 5, 0.0, 0.01, 240.0, 1, 1, 1, true, bv_240kv, sub_5

Fail fast, import. A series capacitor (X < 0) with B != 0. An ST that is not 0 or 1. On a tie, a MET that is not 1 or 2, or an AREA with no area-interchange record.

Fail fast, export. A line with gch set (RAW has no line conductance). A branch on a node with no busNumber. A line shunt whose inService differs from its line's, or whose nomU is not its BaseVoltage (RAW states a shunt at 1 pu of its bus voltage). A NAME longer than 40 characters. Two branches with one key. TieFlow pairs on both terminals of one branch. Ratings of both kinds (see Ratings). The exporter reads a line's own lumped r, x and b, so a line with only a per-length impedance raises.

Expected differences. MET 2 off a tie comes back blank, which reads as the default 1. A series capacitor's LEN comes back blank. A SeriesCompensator with X >= 0 is written as a branch and would import as an ACLineSegment. Owners are not exported.

System switching device

switch.cimtbl has one table per class, with the same columns. STYPE picks the class, and the mRID prefix sw_ is the same for all three, so a change of class keeps the mRID. The switch's BaseVoltage is bus I's and its container is bus I's substation, since a switch merges its two buses into one substation. A switch across a zone boundary is not a merge edge, and its container is still bus I's substation.

field import export
I, J (from_bus_number, to_bus_number) structural: bus1, bus2 terminals 1 and 2's busNumber
CKT (circuit) structural: mRID sw_<I>_<J>_<CKT> as a branch's
STYPE (stype) mapped: 1 Switch, 2 Breaker, 3 Disconnector. Blank or another code raises: no default by class, the same numbers
STATUS (status) mapped: open = (STATUS == 0); blank: 1 get_switch_state actual: open is 0, closed 1
NSTATUS (nstat) mapped: normalOpen = (NSTATUS == 0); blank: 1 get_switch_state normal
X (x) untranscribed: the solver's stand-in for zero impedance; a switch has none always 0.0001 (the format gives X no default)
METERED (metered_end) structural on a tie, as a branch's MET; elsewhere untranscribed. Blank: 1 on a tie the terminal that holds the TieFlows, else 1
NAME (name) name; blank: the key as a branch's
RATE1..RATE12 (ratings) structural: Ratings as a branch's

Excerpt from cimhub_raw/tests/atoms/branch/switches.raw (one switch of each STYPE, the first rated in current):

Table Breaker: mRID, name, bus1, bus2, open, normalOpen, BaseVoltage, EquipmentContainer
    sw_102_103_1, BREAKER, 102, 103, true, false, bv_138kv, sub_101

Table Disconnector: mRID, name, bus1, bus2, open, normalOpen, BaseVoltage, EquipmentContainer
    sw_103_104_1, DISCONNECT, 103, 104, false, true, bv_138kv, sub_101

Table CurrentLimit: mRID, OperationalLimitSet, OperationalLimitType, normalValue (kA)
    sw_101_102_1_rate1, sw_101_102_1_ratings, olt_rate1, 0.836739520564675

Fail fast. On import, a blank STYPE, and an STYPE, STATUS or NSTATUS outside its codes (a blank STATUS or NSTATUS is 1). On export, a switch with a ConnectivityNode on one terminal only, and any switch class other than Switch, Breaker and Disconnector (a fuse or a recloser has no RAW form, and the exporter raises on any conducting equipment it has no module for).

Expected differences. A switch's X other than 0.0001 comes back 0.0001. METERED 2 off a tie comes back 1. A switch with a ConnectivityNode on both terminals belongs to a node-breaker substation (see Substations); this exporter leaves it out, and the exporter has no module for node-breaker substations yet, so such switches are not in the exported case. The export logs a warning that counts them.

Multi-section line

A multi-section line record names a path of buses: I, then the dummy buses DUM1..DUM9 that are set, then J. The sections stay ordinary branches in branch.cimtbl, and the dummy buses stay buses. The record becomes a Line (mRID msl_<I>_<J>_<ID>, name ID, Region = bus I's zone), and an Update row moves each section into it.

field import export
I, J (i, j) structural: the key and the path's ends the path's ends: from the mRID key when it names them in order, else the lower bus first
ID (line_id) copied to Line.name; part of the key the mRID key, else the next free &1, &2, ...
DUM1..DUM9 (dum1..dum9) structural: the path I, DUM1, ..., J names the sections, one branch per step the path's dummy buses in order, blank past the end
MET (met) untranscribed: the loss-allocation end has no CIM home not exported

Each step of the path must be joined by exactly one branch that no earlier record has used, in either direction (a section may be entered 4-3 for a path from 3 to 4), and each dummy bus must have exactly two branches. A section whose two buses are in one substation (a series capacitor merges its buses) stays contained by that substation and joins the Line through the second container association, AdditionalEquipmentContainer. The Line's row lists it: # path 1, 2, 3, 4; in substations: sc_2_3_1.

Excerpt from cimhub_raw/tests/atoms/branch/mixed_base.raw, a line &1 of three sections through buses 2 and 3, the middle one a series capacitor:

Table Line: mRID, name, Region
    # path 1, 2, 3, 4; in substations: sc_2_3_1
    msl_1_4_&1, &1, srgn_1

Update Table ACLineSegment: mRID, EquipmentContainer
    ln_1_2_1, msl_1_4_&1
    ln_3_4_1, msl_1_4_&1

Update Table SeriesCompensator: mRID, AdditionalEquipmentContainer
    sc_2_3_1, msl_1_4_&1

Fail fast, import. A dummy bus with other than two branches. A step of the path with no unused branch, or with more than one (parallel branches between two path buses are ambiguous).

Fallback, export. A Line whose sections are not one path of one to nine dummy buses, each joining exactly two branches, writes no multi-section record and raises nothing: its sections are still written as branches, and the count of such lines is logged.

Expected differences. MET is not exported. A record with no dummy bus (I and J joined by one branch) is read by the importer but not written back.

Ratings

RATE1..RATE12 are the twelve rating sets of the case. The master table writes twelve OperationalLimitTypes, olt_rate1..olt_rate12, named from the RATING records (a set with no record is named RATEn and described RATING SET n).

A device's nonzero ratings go into one OperationalLimitSet <mRID>_ratings on its first terminal <mRID>_T1 (bus I), one limit per rating, mRID <mRID>_rate<n>, of type olt_rate<n>. A zero rating is PSS/E's "no limit", so it writes no row, and a device with no nonzero rating has no set. A transformer's ratings are one set per winding; see Transformers.

NXFRAT limit class normalValue value
0 or less ApparentPowerLimit MVA RATEn, copied
> 0 CurrentLimit kA RATEn / (sqrt(3) x BASKV), the rating being a current "expressed as MVA" at bus I's BASKV

A blank NXFRAT is the present option setting, which the importer reads as MVA and notes on the master (# defaulted: NXFRAT=0). One flag holds for every branch and switch of the case.

The exporter reads RATEn from the limit whose type is olt_rate<n>, with 0 where there is none. A current limit becomes MVA = sqrt(3) x BASKV x kA on the device's BaseVoltage. It writes NXFRAT 1 when the case's branch and switch ratings are CurrentLimits, and 0 when they are ApparentPowerLimits or there are none.

Fail fast, export. A limit whose type is not one of olt_rate1..olt_rate12. A device with both ApparentPowerLimits and CurrentLimits, or a case that holds both kinds among its branches and switches.

Expected differences. A case with no rated branch or switch comes back NXFRAT 0, whatever it was.

Excerpt from cimhub_raw/tests/atoms/branch/line_shunts.raw (RATE1 100 and RATE2 120 MVA on branch 1-2):

Table OperationalLimitSet: mRID, Terminal
    ln_1_2_1_ratings, ln_1_2_1_T1

Table ApparentPowerLimit: mRID, OperationalLimitSet, OperationalLimitType, normalValue (MVA)
    ln_1_2_1_rate1, ln_1_2_1_ratings, olt_rate1, 100.0
    ln_1_2_1_rate2, ln_1_2_1_ratings, olt_rate2, 120.0

Where the rules are specified

The per-field classification with its reasons is in the import mapping (sections Branch, System switching device, Multi-section line) and the export mapping (section E1).