Loads and shunts¶
This page is the conversion reference for the RAW tables that draw power or add susceptance at a bus: Load, Fixed shunt and Switched shunt. For each one it says what the importer writes, what the exporter reads back, what raises and what comes back different after a round trip. The field classes (copied, mapped, structural, derived, untranscribed) and the conventions every section follows are on the reference index. The getters the exporter reads through are on the core site's loads, shunts and compensators page.
| RAW table | CIM classes | .cimtbl artifact and shape |
Importer | Exporter |
|---|---|---|---|---|
| Load | ConformLoad or NonConformLoad, LoadResponseCharacteristic, and the LoadArea, SubLoadArea and load group that hold them |
load.cimtbl, shape load with bus in place of node |
importer/cimtbl/load.py |
exporter/load.py |
| Fixed shunt | LinearShuntCompensator, one section |
fixed_shunt.cimtbl, shape shunt with bus, no control |
importer/cimtbl/fixed_shunt.py |
exporter/fixed_shunt.py |
| Switched shunt | one LinearShuntCompensator per block, and one RegulatingControl for the record; a static var compensator StaticVarCompensator |
switched_shunt.cimtbl, shape shunt with bus |
importer/cimtbl/switched_shunt.py |
exporter/switched_shunt.py |
The table shapes are on the core site's shapes page.
Source paths are under
cimhub_raw/src/cimhub_raw/.
The master imports load.cimtbl and fixed_shunt.cimtbl after the branch tables, and switched_shunt.cimtbl after
the generator and FACTS device artifacts, because a switched shunt's control can regulate a machine or a FACTS
device (see Generators and DC lines and FACTS devices). A bus's BaseVoltage and
substation come from the bus tables (Case, buses, areas and zones and
Substations and node-breaker data).
Quoted error messages start with the record, as load 1_1: or switched shunt 1:. The key of a load or shunt is its
bus number and ID, and the name the importer gives it is <I>_<ID>. A switched shunt has no ID in RAW v34, so its
key is its bus number.
The examples run from the repository root with UV_FROZEN=1 uv run python. They convert the public test atoms in
cimhub_raw/tests/atoms to CIM and
back. Every RAW line printed below is an exported record as the writer formats it.
Load¶
One ConformLoad or NonConformLoad per RAW load, mRID ld_<I>_<ID>, on bus I, in the substation of bus I and on
its BaseVoltage. A v34 load has no NAME, so the name is <I>_<ID>. p and q are the load at 1 pu voltage, CIM's
nominal voltage, and the ZIP split is a LoadResponseCharacteristic shared by every load with the same split.
Power. RAW gives each load three parts: constant power (PL, QL), constant current (IP, IQ) and constant admittance (YP, YQ), all in MW and MVAr at 1 pu voltage. The importer sums them:
| CIM value | Formula |
|---|---|
p (MW) |
PL + IP + YP |
q (MVAr) |
QL + IQ - YQ |
YQ enters with a minus sign because RAW writes the reactive part of a constant admittance as a negative number for an inductive load.
ZIP response. The LoadResponseCharacteristic has exponentModel false and the six fractions of the sums:
| Side | Constant power | Constant current | Constant admittance |
|---|---|---|---|
| p | PL / p | IP / p | YP / p |
| q | QL / q | IQ / q | -YQ / q |
- Each distinct set of six fractions is one shared row, mRID
zip_plus the fractions (zip_0_1_0_0_0_1,zip_0.5_0.3_0.2_0.25_0.25_0.5), written before the loads. A plain constant power load iszip_1_0_0_1_0_0. - A side whose components are all 0 counts as constant power: its fractions are 1, 0, 0.
- A side whose nonzero components add to 0 raises, because its fractions would be undefined.
Class from SCALE. SCALE 1, the default, is a ConformLoad in a ConformLoadGroup. SCALE 0, a load that is not
scaled, is a NonConformLoad in a NonConformLoadGroup. Any other SCALE raises.
Area and zone. The load's own AREA and ZONE pick its group, so a load assigned to a different area or zone than its bus keeps both. The hierarchy has one row per area and one per (area, zone) pair that has loads:
| CIM class | mRID | Holds |
|---|---|---|
LoadArea |
la_<AREA> |
one per area with loads; its ControlArea is ca_<AREA> |
SubLoadArea |
sla_<AREA>_<ZONE> |
one per area and zone pair, in its LoadArea |
ConformLoadGroup |
clg_<AREA>_<ZONE> |
the SCALE 1 loads of the pair |
NonConformLoadGroup |
nclg_<AREA>_<ZONE> |
the SCALE 0 loads of the pair |
A blank AREA or ZONE is the bus's, and the row's comment says so (# defaulted: area=2, zone=2). An AREA with no
Area interchange record raises. CIM has no link from a SubLoadArea to a zone, so the exporter reads a load's ZONE
from its bus's substation region. A load whose ZONE differs from its bus's therefore keeps its group but loses the
zone on the way back, and its row says # untranscribed: zone=2 (bus 2 is in zone 1).
Status. inService is true for STATUS 1 and false for STATUS 0. A blank STATUS is 1. Any other value raises.
Load fields¶
| RAW field | Import | Export |
|---|---|---|
| I | structural: bus, BaseVoltage, EquipmentContainer of bus I |
the bus number of the load's terminal |
| ID | structural: key ld_<I>_<ID>, name <I>_<ID>; blank is 1 |
the ID in the mRID ld_<I>_<ID>, else the next free 1, 2, ... on the bus |
| STATUS | mapped: inService; blank is 1 |
0 when inService is false, else 1 |
| AREA | structural: the group's LoadArea and ControlArea; blank is the bus's |
the area number of the load's group (LoadGroup, SubLoadArea, LoadArea, ControlArea); blank for a load with no group |
| ZONE | structural: the group's SubLoadArea; blank is the bus's |
the zone of the bus's substation region |
| PL, QL | derived: part of p (MW), q (MVAr) and of pConstantPower, qConstantPower |
p, q times the constant power fractions |
| IP, IQ | derived: part of p (MW), q (MVAr) and of pConstantCurrent, qConstantCurrent |
p, q times the constant current fractions |
| YP, YQ | derived: part of p (MW), q (MVAr) and of pConstantImpedance, qConstantImpedance; YQ enters q as -YQ |
p times the constant impedance fraction; YQ is minus q times it |
| SCALE | mapped: ConformLoad (1) or NonConformLoad (0); blank is 1 |
1 for a ConformLoad, 0 for a NonConformLoad, blank for a plain EnergyConsumer |
| OWNER, INTRPT, DGENP, DGENQ, DGENM | untranscribed | not exported |
Load fail-fast rules¶
| Rule | Message |
|---|---|
| an AREA with no Area interchange record | load 1_1: AREA 9 has no area-interchange record (no ControlArea ca_9) |
| a SCALE or STATUS other than 0 or 1 | load 1_1: scale=2 has no mapping (known: 0, 1) |
| a side of the ZIP split whose parts cancel | load 1_1: the q components (5.0, 0.0, -5.0) cancel to 0; their ZIP fractions are undefined |
export: an exponent response (exponentModel true) |
ConformLoad 'x': an exponent load response; a RAW load is ZIP only |
export: a load group whose chain stops before the ControlArea |
ConformLoad 'x': its ConformLoadGroup 'y' reaches no ControlArea through SubLoadArea -> LoadArea |
export: a load with no LoadResponse |
ConformLoad 'x': has no LoadResponse |
| export: ZIP fractions that do not add to 1 | LoadResponseCharacteristic 'z': the p fractions [0.5, 0.3, 0.3] do not sum to 1 |
Load round trip¶
| What | Why |
|---|---|
| PL to YQ of a mixed load can differ in the last digit | the exporter multiplies p and q by the fractions: relative error 1e-9 |
| a blank AREA or ZONE comes back filled | the importer gave the load its bus's area and zone, and the exporter writes the group's area and the bus's zone |
| a ZONE other than the bus's comes back as the bus's | a SubLoadArea has no link to a zone |
| a blank SCALE comes back 1 | the importer defaulted it |
| OWNER, INTRPT, DGENP, DGENQ, DGENM come back blank | no CIM home |
| a side with all parts 0 comes back as constant power 0 | its fractions were 1, 0, 0 |
This example converts the load atom, prints each ConformLoad's totals and the fractions of its p side, and exports
the case again.
import cimprofiles.cim18.cim18v17 as cim
import cimhub_raw.schema.raw_v34.raw34_schema as schema
from cimhub_core.getters.load import get_load_response, get_phase_loads
from cimhub_raw.exporter.cim_to_raw import RawExporter
from cimhub_raw.importer.raw_to_cimtbl import raw_to_cim
from cimhub_raw.raw34_reader import Raw34Reader
from cimhub_raw.raw34_writer import Raw34Writer
case = Raw34Reader("cimhub_raw/tests/atoms/load/loads.raw").read_all()
network = raw_to_cim(case, name="atom")
for load in network.graph[cim.ConformLoad].values():
total = get_phase_loads(load, "MW", "MVAr").total
response = get_load_response(load)
print(load.mRID, total.p, total.q, response.p_power, response.p_current, response.p_impedance)
writer = Raw34Writer()
for record in RawExporter().to_model(network).list_by_class(schema.LoadRecord):
print(writer.serialize(record))
ld_1_1 10.0 5.0 1.0 0.0 0.0
ld_1_2 10.0 4.0 0.5 0.3 0.2
ld_2_A 7.0 2.0 0.0 1.0 0.0
ld_3_1 25.0 10.0 1.0 0.0 0.0
1,'1 ',1,1,1,10.000,5.000,0.000,0.000,0.000,0.000,,1
1,'2 ',1,1,1,5.000,1.000,3.000,1.000,2.000,-2.000,,1
2,'1 ',0,1,1,0.000,0.000,0.000,0.000,4.000,0.000,,0
2,'A ',1,2,1,0.000,0.000,7.000,2.000,0.000,0.000,,1
3,'1 ',1,2,2,25.000,10.000,0.000,0.000,0.000,0.000,,1
The atom's load 2 A is the constant current load written with AREA 2 and ZONE 2 on a bus in zone 1; it comes back
with ZONE 1. Load 3 1 was written with only PL and QL, and comes back with AREA 2, ZONE 2 and the zero parts
filled. The out-of-service load 2 1 is the NonConformLoad, so it is not in the ConformLoad lines.
Load excerpt¶
From cimhub_raw/tests/goldens/IEEE14/load.cimtbl, the artifact of the IEEE 14 bus case. Every load is constant
power and in one area and zone, so the hierarchy is one row each:
Table LoadArea: mRID, name, ControlArea
la_1, 1, ca_1
Table SubLoadArea: mRID, name, LoadArea
sla_1_1, 1_1, la_1
Table ConformLoadGroup: mRID, name, SubLoadArea
clg_1_1, 1_1, sla_1_1
# ZIP fractions: PL, IP, YP over p; QL, IQ, -YQ over q (zip_mix)
Table LoadResponseCharacteristic: mRID, exponentModel, pConstantPower, pConstantCurrent, pConstantImpedance, qConstantPower, qConstantCurrent, qConstantImpedance
zip_1_0_0_1_0_0, false, 1.0, 0.0, 0.0, 1.0, 0.0, 0.0
# untranscribed: owner, interruptible, dgenp, dgenq, dgenf
Table ConformLoad: mRID, name, bus, p (MW), q (MVAr), inService, LoadResponse, LoadGroup, BaseVoltage, EquipmentContainer
ld_2_1, 2_1, 2, 21.7, 12.7, true, zip_1_0_0_1_0_0, clg_1_1, bv_138kv, sub_2
ld_3_1, 3_1, 3, 94.2, 19.0, true, zip_1_0_0_1_0_0, clg_1_1, bv_138kv, sub_3
...
No golden has a mixed load or a fixed load. From the artifact the importer writes for the atom
cimhub_raw/tests/atoms/load/loads.raw (the mixed load 1 2, the fixed load 2 1, and the load 2 A that is in
another area and zone than its bus):
Table NonConformLoadGroup: mRID, name, SubLoadArea
nclg_1_1, 1_1, sla_1_1
Table LoadResponseCharacteristic: mRID, exponentModel, pConstantPower, pConstantCurrent, pConstantImpedance, qConstantPower, qConstantCurrent, qConstantImpedance
zip_0.5_0.3_0.2_0.25_0.25_0.5, false, 0.5, 0.3, 0.2, 0.25, 0.25, 0.5
...
Table ConformLoad: mRID, name, bus, p (MW), q (MVAr), inService, LoadResponse, LoadGroup, BaseVoltage, EquipmentContainer
ld_1_2, 1_2, 1, 10.0, 4.0, true, zip_0.5_0.3_0.2_0.25_0.25_0.5, clg_1_1, bv_69kv, sub_1
# untranscribed: zone=2 (bus 2 is in zone 1)
ld_2_A, 2_A, 2, 7.0, 2.0, true, zip_0_1_0_0_1_0, clg_2_2, bv_69kv, sub_2
Table NonConformLoad: mRID, name, bus, p (MW), q (MVAr), inService, LoadResponse, LoadGroup, BaseVoltage, EquipmentContainer
ld_2_1, 2_1, 2, 4.0, 0.0, false, zip_0_0_1_1_0_0, nclg_1_1, bv_69kv, sub_2
Fixed shunt¶
One LinearShuntCompensator per RAW fixed shunt, mRID cap_<I>_<ID>, name <I>_<ID>, on bus I in its substation.
It has one section, always in: maximumSections, normalSections and sections are all 1. GL and BL are MW and
MVAr at 1 pu voltage, so the importer writes them as admittances in per unit on the system base, gPerSection (pu
system) = GL / SBASE and bPerSection (pu system) = BL / SBASE, and nomU (kV) is the bus's BASKV. cimtables turns
them into siemens on those two bases. BL above 0 is a capacitor in RAW and in CIM, so its sign is unchanged. A shunt
with a negative BL is a reactor.
Fixed shunt fields¶
| RAW field | Import | Export |
|---|---|---|
| I | structural: bus, nomU (kV) = BASKV, BaseVoltage, EquipmentContainer |
the bus number of the shunt's terminal |
| ID | structural: key cap_<I>_<ID>, name <I>_<ID>; the ID is trimmed |
the ID in the mRID cap_<I>_<ID>, else the next free 1, 2, ... on the bus |
| STATUS | mapped: inService; blank is 1 |
0 when inService is false, else 1 |
| GL | derived: gPerSection (pu system) = GL / SBASE; blank is 0 |
the shunt's g in pu on its bus base times SBASE, over the sections in service; an unset g is 0 |
| BL | derived: bPerSection (pu system) = BL / SBASE; blank is 0 |
the shunt's b, as GL |
A LinearShuntCompensator with no RegulatingControl is a fixed shunt, unless it is a line shunt of an exported
branch: those go back in the branch's GI, BI, GJ and BJ (see Branches, switches and multi-section
lines). A shunt with a control is a block of a switched shunt.
Fixed shunt fail-fast rules¶
| Rule | Message |
|---|---|
| a STATUS other than 0 or 1 | fixed shunt 1_1: status=2 has no mapping (known: 0, 1) |
export: nomU is not the shunt's BaseVoltage |
LinearShuntCompensator 'x': nomU 230.0 kV is not its BaseVoltage 115.0 kV; RAW states a shunt at 1 pu of its bus voltage |
export: a NonlinearShuntCompensator |
no RAW export yet for {'NonlinearShuntCompensator': 1} |
Fixed shunt round trip¶
GL and BL come back as written, up to the last digit of the per-unit round trip. The fixed shunt atom's two shunts, 1 1 (GL + jBL = 1.5 + j20) and 1 2 (a
reactor out of service), come back unchanged.
Fixed shunt excerpt¶
From cimhub_raw/tests/goldens/IEEE14/fixed_shunt.cimtbl:
Table LinearShuntCompensator: mRID, name, bus, gPerSection (pu system), bPerSection (pu system), nomU (kV), maximumSections, normalSections, sections, inService, BaseVoltage, EquipmentContainer
cap_9_1, 9_1, 9, 0.0, 0.19, 138.0, 1, 1, 1, true, bv_138kv, sub_4
BL 19.0 Mvar on SBASE 100 is bPerSection 0.19.
Switched shunt¶
One RAW switched shunt is a bus's whole set of switched banks under one controller: up to eight blocks, each Ni
identical steps of Bi Mvar, and a mode MODSW that says what controls them. The importer writes one
LinearShuntCompensator per block, all naming one RegulatingControl. The control is written first and the blocks
second. A locked shunt (MODSW 0) still has its control, disabled, so its blocks stay grouped. The mRIDs are
swsh_<I>_b<k> for block k in input order and cc_<I> for the control.
Blocks. The blocks run up to the first Ni or Bi that is 0 or blank, which is RAW's end of the list. For each:
| CIM attribute | Value |
|---|---|
maximumSections |
Ni |
bPerSection (pu system) |
Bi / SBASE, with nomU (kV) = the BASKV of bus I; a negative Bi is a reactor block |
sections |
the block's share of BINIT, below |
inService |
STATUS == 1, the same on every block |
controlEnabled |
the control's enabled |
A block after the first zero raises, and so does a record with no blocks at all. The block slots are never defaulted, because a missing Ni or Bi is the end of the list, not a value.
Sections. RAW gives only the total in service, BINIT in Mvar at 1 pu voltage. The importer splits it in RAW's
switching order (ADJM 0): a negative BINIT fills the reactor blocks in input order and a positive one the capacitor
blocks. Each block takes up to its Ni steps, and the block where BINIT runs out takes the rest as a fraction of a step
(CIM allows a non-integer sections). A BINIT beyond the blocks' total raises. normalSections is not written. ADJM
is untranscribed; the order is kept by the _b<k> suffix.
Control. MODSW sets the control's mode:
| MODSW | RegulatingControl |
Regulates |
|---|---|---|
| 0 locked | mode voltage, enabled false, discrete blank, and every block controlEnabled false; the target is VSWHI and VSWLO as read, unused |
bus SWREG |
| 1 discrete, voltage | mode voltage, discrete true |
bus SWREG |
| 2 continuous, voltage | mode voltage, discrete false |
bus SWREG |
| 3 discrete, plant reactive power | mode reactivePower, discrete true |
the one machine of the plant at SWREG |
| 6 discrete, FACTS shunt reactive power | mode reactivePower, discrete true |
the FACTS device named by RMIDNT |
| 4 (a VSC converter's reactive power), 5 (another shunt's admittance) | raise NotImplementedError |
|
| any other value | raises |
Regulated bus (MODSW 0, 1, 2). The control's Terminal is the busbar terminal bb_<SWREG>_T1, or bb_<I>_T1
when SWREG is 0. An NREG other than 0 names a node of the regulated bus, and the terminal is that node's busbar
(see Substations and node-breaker data). A SWREG that is no bus raises, in every mode, MODSW 6 included.
Voltage target. targetValue is the middle of the band, (VSWHI + VSWLO) / 2 times the regulated bus's BASKV, in
volts. targetDeadband is the whole band, (VSWHI - VSWLO) times BASKV, in volts. The subtraction can leave a
last-digit residue: 1.04 - 0.98 gives 6900.0000000000055. The value is written as computed.
Plant reactive power (MODSW 3). VSWLO and VSWHI are fractions of the range QB to QT of the plant's machine at SWREG
(or at bus I when SWREG is 0). The band runs from QB + VSWLO x (QT - QB) to QB + VSWHI x (QT - QB) Mvar, using the
machine's limits as written and ignoring its status. The control's Terminal is the machine's own terminal,
sm_<I>_<ID>_T1 or pec_<I>_<ID>_T1, where PSS/E measures the machine's reactive power. targetValue is minus
the midpoint of the band and targetDeadband its width, both in VAr: a terminal's q follows the load sign, so
a machine's q is minus QG. A plant of several machines at SWREG raises, because one terminal measures one
machine. With no machine at SWREG the control is written disabled, with no target, on the busbar terminal
bb_<SWREG>_T1, and a VSWLO or VSWHI off its default is listed on the row (# untranscribed: vswlo=0.0).
FACTS reactive power (MODSW 6). The same band over -SHMX to +SHMX of the FACTS device named by RMIDNT, on the device's
terminal fd_<RMIDNT>_T1. SWREG is not used. An RMIDNT that names no FACTS device raises, and so does a device with a
series element (see DC lines and FACTS devices).
Static var compensator¶
RAW v34 has no SVC record: PSS/E models one as a continuous switched shunt. A MODSW 2 shunt whose blocks are at most
one reactor and one capacitor, each of one step, is one StaticVarCompensator swsh_<I> instead of its blocks. Its
control cc_<I> is the same as any MODSW 2 shunt's. Every other shunt stays blocks, MODSW 2 ones with several steps
or two blocks of one sign included.
| CIM attribute | Value |
|---|---|
capacitiveRating (pu system) |
SBASE / Bi of the capacitor block: X = U² / Q at 1 pu, positive; blank with no capacitor |
inductiveRating (pu system) |
SBASE / Bi of the reactor block, negative; blank with no reactor |
q (MVAr) |
-BINIT, the starting output under the load sign; a BINIT beyond the range raises |
sVCControlMode |
voltage |
inService, controlEnabled |
STATUS == 1; true |
RegulatingControl |
cc_<I>, as above |
voltageSetPoint and slope are blank: the control carries the target, and RAW has no droop. The exporter writes an
SVC back as a MODSW 2 record (MODSW 0 when its control is locked): a one-step reactor block of SBASE /
inductiveRating Mvar, then a one-step capacitor block of SBASE / capacitiveRating, BINIT = -q, and VSWHI, VSWLO and
SWREG from the control as for a bank. From the atom cimhub_raw/tests/atoms/shunt/svc.raw (230 kV, SBASE 100; bus 1:
-50 and 100 Mvar, BINIT 40, regulating bus 4; bus 2: a 30 Mvar capacitor, out of service):
Table StaticVarCompensator: mRID, name, bus, capacitiveRating (pu system), inductiveRating (pu system), q (MVAr), sVCControlMode, inService, controlEnabled, RegulatingControl, BaseVoltage, EquipmentContainer
swsh_1, 1, 1, 1.0, -2.0, -40.0, voltage, true, true, cc_1, bv_230kv, sub_1
swsh_2, 2, 2, 3.3333333333333335, , 0.0, voltage, false, true, cc_2, bv_230kv, sub_2
The SVC export raises on: no RegulatingControl; a control of mode reactive power, or sVCControlMode reactive
power; a discrete control; an inductiveRating of 0 or more, or a capacitiveRating of 0 or less; neither rating
set; an SVC on a bus that already has a switched shunt.
Switched shunt fields¶
| RAW field | Import | Export |
|---|---|---|
| I | structural: the key; every block's bus, nomU (kV) = BASKV, BaseVoltage, EquipmentContainer |
the bus number of the blocks' terminals; all blocks of one control must be on one bus, and two controls on one bus raise |
| MODSW | mapped: the control's mode, discrete and enabled, as in the table above; blank is 1 |
from the control (the blocks' controlEnabled must agree): voltage and locked (enabled false, or every block's controlEnabled false) 0, voltage with discrete true or unset 1, voltage with discrete false 2; reactive power on a FACTS device 6; reactive power on a machine, or on anything else when locked, 3; any other mode raises |
| ADJM | untranscribed | not written |
| STATUS | mapped: inService of every block; blank is 1 |
0 when the blocks are out of service; blocks in and out of service on one control raise |
| VSWHI, VSWLO | derived: the control's targetValue and targetDeadband: volts for MODSW 0 to 2, VAr for MODSW 3 and 6; blank is 1.0 |
the band's top and bottom from the control's target plus or minus half its deadband: kV over the regulated bus's BASKV for voltage, fractions of the machine's minQ to maxQ or of the device's -SHMX to SHMX for MODSW 3 and 6; blank for a disabled control with no target. A machine with the same minQ and maxQ raises |
| SWREG | structural: the control's Terminal, as above; MODSW 3: the plant's bus; MODSW 6: not used, but a nonzero SWREG must still be a bus; blank is 0 |
the bus number of the control's terminal, its own bus included; blank for MODSW 6 |
| RMIDNT | structural: MODSW 6: the FACTS device | MODSW 6: the name of the FACTS device at the control's terminal; else blank |
| BINIT | derived: split into the blocks' sections |
the sum over the blocks of sections times Bi |
| N1 to N8 | structural: maximumSections of block k |
the blocks in the order of the mRID swsh_<I>_b<k>, else reactors first, then capacitors, each by mRID; more than 8 raise; a maximumSections below 1 raises |
| B1 to B8 | structural: bPerSection (pu system) = Bi / SBASE |
the block's b per section in pu on its bus base times SBASE; a block with g other than 0 raises |
| NREG | structural: a node of the regulated bus, as above; blank is 0 | not written |
| RMPCT | untranscribed: CIM 18 has no participation share for a shunt | not written |
Switched shunt fail-fast rules¶
| Rule | Message |
|---|---|
| MODSW 4 or 5 | switched shunt 1: MODSW 4 (VSC converter reactive power: no case has one yet) |
| any other MODSW | switched shunt 1: modsw=9 has no mapping (known: 0, 1, 2, 3, 6) |
| a block after the first zero Ni or Bi | switched shunt 1: a block after the first zero Ni or Bi (block 2): [(2, -15.0), (0, 0.0), (2, 5.0), ...] |
| no block at all | switched shunt 1: no blocks (N1, B1 = (0, 0.0)) |
| BINIT beyond the blocks' total | switched shunt switched shunt 1: BINIT=500.0 is beyond its blocks [(2, -15.0), (3, 10.0), (2, 25.0)] |
| a SWREG that is no bus | switched shunt 1: SWREG 999 is no bus |
| MODSW 3 with several machines at SWREG | switched shunt 2: the plant at bus 1 has 2 machines; one terminal measures one machine (no case) |
| MODSW 6 naming no FACTS device | switched shunt 5: RMIDNT 'NOPE' names no FACTS device |
export: the blocks of one control with different controlEnabled |
RegulatingControl 'x': its blocks' controlEnabled disagree |
| export: blocks in and out of service on one control | RegulatingControl 'x': its blocks are in and out of service; a switched shunt has one status |
export: a block with gPerSection set, or a maximumSections below 1 |
LinearShuntCompensator 'x': gPerSection is set; a switched shunt block has no G |
| export: blocks of one control on two buses | RegulatingControl 'x': controls shunts on buses [(1,), (2,)]; a switched shunt is on one |
| export: two controls (or an SVC) on one bus | bus 1: RegulatingControl 'x' and RegulatingControl 'y' are both switched shunts; a v34 switched shunt's key is its bus |
| export: more than 8 blocks | RegulatingControl 'x': controls 9 shunts; a switched shunt has 8 blocks |
| export: a control mode other than voltage or reactive power, or reactive power on equipment that is neither a machine nor a FACTS device | RegulatingControl 'x': reactive power of ...; MODSW 3 regulates a plant's machine and 6 a FACTS device |
Switched shunt round trip¶
| What | Why |
|---|---|
| SWREG 0 comes back as the bus's own number | CIM keeps the terminal, not whether RAW wrote 0 or I |
| VSWHI and VSWLO, Bi and BINIT can differ in the last digit | the importer converts through volts or per unit and the exporter converts back (10.000000000000002 for 10); relative error 1e-9 |
| ADJM and RMPCT come back blank | no CIM home |
| NREG comes back blank | not written; a control on a substation node is exported against its bus |
| a MODSW 3 shunt with no plant comes back with VSWHI and VSWLO blank | its control has no target; PSS/E reads blank as 1.0 |
| BINIT can differ in the last digit | the exporter adds up sections times Bi, which inverts the split |
This example converts the switched shunt atom and prints each block's state, each control's target and deadband in kV, and the exported records:
import cimprofiles.cim18.cim18v17 as cim
import cimhub_raw.schema.raw_v34.raw34_schema as schema
from cimhub_core.getters.control import get_regulating_control
from cimhub_raw.exporter.cim_to_raw import RawExporter
from cimhub_raw.importer.raw_to_cimtbl import raw_to_cim
from cimhub_raw.raw34_reader import Raw34Reader
from cimhub_raw.raw34_writer import Raw34Writer
case = Raw34Reader("cimhub_raw/tests/atoms/shunt/switched_shunts.raw").read_all()
network = raw_to_cim(case, name="atom")
for block in network.graph[cim.LinearShuntCompensator].values():
control = block.RegulatingControl
print(block.mRID, block.sections, block.maximumSections, control.mRID, control.mode.name, control.enabled)
for control in network.graph[cim.RegulatingControl].values():
settings = get_regulating_control(control, "kV")
print(control.mRID, settings.target, settings.deadband)
writer = Raw34Writer()
for record in RawExporter().to_model(network).list_by_class(schema.SwitchedShuntRecord):
print(writer.serialize(record))
swsh_1_b1 1.0 2 cc_1 voltage True
swsh_1_b2 0.0 3 cc_1 voltage True
swsh_1_b3 0.0 2 cc_1 voltage True
swsh_2_b1 2.5 4 cc_2 voltage True
swsh_3_b1 10.0 10 cc_3 voltage False
swsh_3_b2 2.0 5 cc_3 voltage False
cc_1 116.15 6.900000000000006
cc_2 230.0 13.800000000000011
cc_3 230.0 0.0
1,1,,1,1.04000,0.98000,4,,,-15.00000,2,-15.00000,3,10.000000000000002,2,25.00000
2,2,,1,1.03000,0.97000,2,,,31.25000,4,12.50000
3,0,,1,1.00000,1.00000,3,,,13.00000,10,1.00000,5,1.50000
The atom's bus 1 has a reactor block of two steps of -15 Mvar and two capacitor blocks, with BINIT -15, so the reactor block has one step in. Its control regulates remote bus 4 (115 kV), so the target is 1.01 x 115 kV = 116.15 kV. Bus 2 is continuous (MODSW 2) with BINIT 31.25 over four steps of 12.5, so 2.5 sections. Bus 3 is locked, its blocks 10 x 1.0 and 5 x 1.5 Mvar with BINIT 13 give 10 and 2 steps, and its control is disabled. The exported SWREG of buses 2 and 3 is their own bus; the source had 0. The ADJM 1 of bus 3 comes back blank.
Switched shunt excerpt¶
From the artifact the importer writes for cimhub_raw/tests/atoms/shunt/switched_shunts.raw; no golden has a
switched shunt:
# untranscribed: adjm, rmpct
# targetValue and targetDeadband in V (voltage) or VAr (reactivePower)
Table RegulatingControl: mRID, name, mode, discrete, enabled, targetValue, targetDeadband, Terminal
# defaulted: nreg=0
cc_1, 1, voltage, true, true, 116150.0, 6900.0000000000055, bb_4_T1
# defaulted: nreg=0
cc_3, 3, voltage, , false, 230000.0, 0.0, bb_3_T1
# one per block: Ni sections of Bi; sections split from BINIT (block_sections)
Table LinearShuntCompensator: mRID, name, bus, bPerSection (pu system), nomU (kV), maximumSections, sections, inService, controlEnabled, RegulatingControl, BaseVoltage, EquipmentContainer
swsh_1_b1, 1_b1, 1, -0.15, 230.0, 2, 1.0, true, true, cc_1, bv_230kv, sub_1
swsh_1_b2, 1_b2, 1, 0.1, 230.0, 3, 0.0, true, true, cc_1, bv_230kv, sub_1
...
The reactive power modes are in the artifact for cimhub_raw/tests/atoms/shunt/plant_and_facts.raw. Bus 2's shunt
regulates the WMOD 1 machine PV at bus 1 (QT 50, QB -30) over 0.25 to 0.75, so the band is -10 to 30 Mvar, target
-10 000 000 VAr and deadband 40 000 000 VAr. Bus 3's shunt has no plant at SWREG. Bus 5's shunt regulates the FACTS
device SVC-1 (SHMX 100) over 0.4 to 0.6, a band of -20 to +20 Mvar:
Table RegulatingControl: mRID, name, mode, discrete, enabled, targetValue, targetDeadband, Terminal
# defaulted: nreg=0
cc_2, 2, reactivePower, true, true, -10000000.0, 40000000.0, pec_1_PV_T1
# defaulted: nreg=0; untranscribed: vswlo=0.0
cc_3, 3, reactivePower, true, false, , , bb_3_T1
# defaulted: nreg=0
cc_5, 5, reactivePower, true, true, 0.0, 40000000.0, fd_SVC-1_T1
A whole case that holds a FACTS device cannot be exported: see DC lines and FACTS devices.
See also¶
- Generators: the machines a MODSW 3 shunt regulates.
- Import mapping spec and export mapping spec: the design record, with the field-by-field classification.
- Round trip and What converts: the task-level view.