Loads and shunts

This page is the conversion reference for the RAW tables that draw power or add susceptance at a bus: Load, Fixed shunt and Switched shunt. For each one it says what the importer writes, what the exporter reads back, what raises and what comes back different after a round trip. The field classes (copied, mapped, structural, derived, untranscribed) and the conventions every section follows are on the reference index. The getters the exporter reads through are on the core site's loads, shunts and compensators page.

RAW table CIM classes .cimtbl artifact and shape Importer Exporter
Load ConformLoad or NonConformLoad, LoadResponseCharacteristic, and the LoadArea, SubLoadArea and load group that hold them load.cimtbl, shape load with bus in place of node importer/cimtbl/load.py exporter/load.py
Fixed shunt LinearShuntCompensator, one section fixed_shunt.cimtbl, shape shunt with bus, no control importer/cimtbl/fixed_shunt.py exporter/fixed_shunt.py
Switched shunt one LinearShuntCompensator per block, and one RegulatingControl for the record; a static var compensator StaticVarCompensator switched_shunt.cimtbl, shape shunt with bus importer/cimtbl/switched_shunt.py exporter/switched_shunt.py

The table shapes are on the core site's shapes page. Source paths are under cimhub_raw/src/cimhub_raw/. The master imports load.cimtbl and fixed_shunt.cimtbl after the branch tables, and switched_shunt.cimtbl after the generator and FACTS device artifacts, because a switched shunt's control can regulate a machine or a FACTS device (see Generators and DC lines and FACTS devices). A bus's BaseVoltage and substation come from the bus tables (Case, buses, areas and zones and Substations and node-breaker data).

Quoted error messages start with the record, as load 1_1: or switched shunt 1:. The key of a load or shunt is its bus number and ID, and the name the importer gives it is <I>_<ID>. A switched shunt has no ID in RAW v34, so its key is its bus number.

The examples run from the repository root with UV_FROZEN=1 uv run python. They convert the public test atoms in cimhub_raw/tests/atoms to CIM and back. Every RAW line printed below is an exported record as the writer formats it.

Load

One ConformLoad or NonConformLoad per RAW load, mRID ld_<I>_<ID>, on bus I, in the substation of bus I and on its BaseVoltage. A v34 load has no NAME, so the name is <I>_<ID>. p and q are the load at 1 pu voltage, CIM's nominal voltage, and the ZIP split is a LoadResponseCharacteristic shared by every load with the same split.

Power. RAW gives each load three parts: constant power (PL, QL), constant current (IP, IQ) and constant admittance (YP, YQ), all in MW and MVAr at 1 pu voltage. The importer sums them:

CIM value Formula
p (MW) PL + IP + YP
q (MVAr) QL + IQ - YQ

YQ enters with a minus sign because RAW writes the reactive part of a constant admittance as a negative number for an inductive load.

ZIP response. The LoadResponseCharacteristic has exponentModel false and the six fractions of the sums:

Side Constant power Constant current Constant admittance
p PL / p IP / p YP / p
q QL / q IQ / q -YQ / q
  • Each distinct set of six fractions is one shared row, mRID zip_ plus the fractions (zip_0_1_0_0_0_1, zip_0.5_0.3_0.2_0.25_0.25_0.5), written before the loads. A plain constant power load is zip_1_0_0_1_0_0.
  • A side whose components are all 0 counts as constant power: its fractions are 1, 0, 0.
  • A side whose nonzero components add to 0 raises, because its fractions would be undefined.

Class from SCALE. SCALE 1, the default, is a ConformLoad in a ConformLoadGroup. SCALE 0, a load that is not scaled, is a NonConformLoad in a NonConformLoadGroup. Any other SCALE raises.

Area and zone. The load's own AREA and ZONE pick its group, so a load assigned to a different area or zone than its bus keeps both. The hierarchy has one row per area and one per (area, zone) pair that has loads:

CIM class mRID Holds
LoadArea la_<AREA> one per area with loads; its ControlArea is ca_<AREA>
SubLoadArea sla_<AREA>_<ZONE> one per area and zone pair, in its LoadArea
ConformLoadGroup clg_<AREA>_<ZONE> the SCALE 1 loads of the pair
NonConformLoadGroup nclg_<AREA>_<ZONE> the SCALE 0 loads of the pair

A blank AREA or ZONE is the bus's, and the row's comment says so (# defaulted: area=2, zone=2). An AREA with no Area interchange record raises. CIM has no link from a SubLoadArea to a zone, so the exporter reads a load's ZONE from its bus's substation region. A load whose ZONE differs from its bus's therefore keeps its group but loses the zone on the way back, and its row says # untranscribed: zone=2 (bus 2 is in zone 1).

Status. inService is true for STATUS 1 and false for STATUS 0. A blank STATUS is 1. Any other value raises.

Load fields

RAW field Import Export
I structural: bus, BaseVoltage, EquipmentContainer of bus I the bus number of the load's terminal
ID structural: key ld_<I>_<ID>, name <I>_<ID>; blank is 1 the ID in the mRID ld_<I>_<ID>, else the next free 1, 2, ... on the bus
STATUS mapped: inService; blank is 1 0 when inService is false, else 1
AREA structural: the group's LoadArea and ControlArea; blank is the bus's the area number of the load's group (LoadGroup, SubLoadArea, LoadArea, ControlArea); blank for a load with no group
ZONE structural: the group's SubLoadArea; blank is the bus's the zone of the bus's substation region
PL, QL derived: part of p (MW), q (MVAr) and of pConstantPower, qConstantPower p, q times the constant power fractions
IP, IQ derived: part of p (MW), q (MVAr) and of pConstantCurrent, qConstantCurrent p, q times the constant current fractions
YP, YQ derived: part of p (MW), q (MVAr) and of pConstantImpedance, qConstantImpedance; YQ enters q as -YQ p times the constant impedance fraction; YQ is minus q times it
SCALE mapped: ConformLoad (1) or NonConformLoad (0); blank is 1 1 for a ConformLoad, 0 for a NonConformLoad, blank for a plain EnergyConsumer
OWNER, INTRPT, DGENP, DGENQ, DGENM untranscribed not exported

Load fail-fast rules

Rule Message
an AREA with no Area interchange record load 1_1: AREA 9 has no area-interchange record (no ControlArea ca_9)
a SCALE or STATUS other than 0 or 1 load 1_1: scale=2 has no mapping (known: 0, 1)
a side of the ZIP split whose parts cancel load 1_1: the q components (5.0, 0.0, -5.0) cancel to 0; their ZIP fractions are undefined
export: an exponent response (exponentModel true) ConformLoad 'x': an exponent load response; a RAW load is ZIP only
export: a load group whose chain stops before the ControlArea ConformLoad 'x': its ConformLoadGroup 'y' reaches no ControlArea through SubLoadArea -> LoadArea
export: a load with no LoadResponse ConformLoad 'x': has no LoadResponse
export: ZIP fractions that do not add to 1 LoadResponseCharacteristic 'z': the p fractions [0.5, 0.3, 0.3] do not sum to 1

Load round trip

What Why
PL to YQ of a mixed load can differ in the last digit the exporter multiplies p and q by the fractions: relative error 1e-9
a blank AREA or ZONE comes back filled the importer gave the load its bus's area and zone, and the exporter writes the group's area and the bus's zone
a ZONE other than the bus's comes back as the bus's a SubLoadArea has no link to a zone
a blank SCALE comes back 1 the importer defaulted it
OWNER, INTRPT, DGENP, DGENQ, DGENM come back blank no CIM home
a side with all parts 0 comes back as constant power 0 its fractions were 1, 0, 0

This example converts the load atom, prints each ConformLoad's totals and the fractions of its p side, and exports the case again.

import cimprofiles.cim18.cim18v17 as cim

import cimhub_raw.schema.raw_v34.raw34_schema as schema
from cimhub_core.getters.load import get_load_response, get_phase_loads
from cimhub_raw.exporter.cim_to_raw import RawExporter
from cimhub_raw.importer.raw_to_cimtbl import raw_to_cim
from cimhub_raw.raw34_reader import Raw34Reader
from cimhub_raw.raw34_writer import Raw34Writer

case = Raw34Reader("cimhub_raw/tests/atoms/load/loads.raw").read_all()
network = raw_to_cim(case, name="atom")

for load in network.graph[cim.ConformLoad].values():
    total = get_phase_loads(load, "MW", "MVAr").total
    response = get_load_response(load)
    print(load.mRID, total.p, total.q, response.p_power, response.p_current, response.p_impedance)

writer = Raw34Writer()
for record in RawExporter().to_model(network).list_by_class(schema.LoadRecord):
    print(writer.serialize(record))
ld_1_1 10.0 5.0 1.0 0.0 0.0
ld_1_2 10.0 4.0 0.5 0.3 0.2
ld_2_A 7.0 2.0 0.0 1.0 0.0
ld_3_1 25.0 10.0 1.0 0.0 0.0
1,'1 ',1,1,1,10.000,5.000,0.000,0.000,0.000,0.000,,1
1,'2 ',1,1,1,5.000,1.000,3.000,1.000,2.000,-2.000,,1
2,'1 ',0,1,1,0.000,0.000,0.000,0.000,4.000,0.000,,0
2,'A ',1,2,1,0.000,0.000,7.000,2.000,0.000,0.000,,1
3,'1 ',1,2,2,25.000,10.000,0.000,0.000,0.000,0.000,,1

The atom's load 2 A is the constant current load written with AREA 2 and ZONE 2 on a bus in zone 1; it comes back with ZONE 1. Load 3 1 was written with only PL and QL, and comes back with AREA 2, ZONE 2 and the zero parts filled. The out-of-service load 2 1 is the NonConformLoad, so it is not in the ConformLoad lines.

Load excerpt

From cimhub_raw/tests/goldens/IEEE14/load.cimtbl, the artifact of the IEEE 14 bus case. Every load is constant power and in one area and zone, so the hierarchy is one row each:

Table LoadArea: mRID, name, ControlArea
    la_1, 1, ca_1

Table SubLoadArea: mRID, name, LoadArea
    sla_1_1, 1_1, la_1

Table ConformLoadGroup: mRID, name, SubLoadArea
    clg_1_1, 1_1, sla_1_1

# ZIP fractions: PL, IP, YP over p; QL, IQ, -YQ over q (zip_mix)
Table LoadResponseCharacteristic: mRID, exponentModel, pConstantPower, pConstantCurrent, pConstantImpedance, qConstantPower, qConstantCurrent, qConstantImpedance
    zip_1_0_0_1_0_0, false, 1.0, 0.0, 0.0, 1.0, 0.0, 0.0

# untranscribed: owner, interruptible, dgenp, dgenq, dgenf
Table ConformLoad: mRID, name, bus, p (MW), q (MVAr), inService, LoadResponse, LoadGroup, BaseVoltage, EquipmentContainer
    ld_2_1,  2_1,  2,  21.7, 12.7, true, zip_1_0_0_1_0_0, clg_1_1, bv_138kv, sub_2
    ld_3_1,  3_1,  3,  94.2, 19.0, true, zip_1_0_0_1_0_0, clg_1_1, bv_138kv, sub_3
    ...

No golden has a mixed load or a fixed load. From the artifact the importer writes for the atom cimhub_raw/tests/atoms/load/loads.raw (the mixed load 1 2, the fixed load 2 1, and the load 2 A that is in another area and zone than its bus):

Table NonConformLoadGroup: mRID, name, SubLoadArea
    nclg_1_1, 1_1, sla_1_1

Table LoadResponseCharacteristic: mRID, exponentModel, pConstantPower, pConstantCurrent, pConstantImpedance, qConstantPower, qConstantCurrent, qConstantImpedance
    zip_0.5_0.3_0.2_0.25_0.25_0.5, false, 0.5, 0.3, 0.2, 0.25, 0.25, 0.5
    ...

Table ConformLoad: mRID, name, bus, p (MW), q (MVAr), inService, LoadResponse, LoadGroup, BaseVoltage, EquipmentContainer
    ld_1_2, 1_2, 1, 10.0, 4.0, true, zip_0.5_0.3_0.2_0.25_0.25_0.5, clg_1_1, bv_69kv, sub_1
    # untranscribed: zone=2 (bus 2 is in zone 1)
    ld_2_A, 2_A, 2, 7.0,  2.0, true, zip_0_1_0_0_1_0,               clg_2_2, bv_69kv, sub_2

Table NonConformLoad: mRID, name, bus, p (MW), q (MVAr), inService, LoadResponse, LoadGroup, BaseVoltage, EquipmentContainer
    ld_2_1, 2_1, 2, 4.0, 0.0, false, zip_0_0_1_1_0_0, nclg_1_1, bv_69kv, sub_2

Fixed shunt

One LinearShuntCompensator per RAW fixed shunt, mRID cap_<I>_<ID>, name <I>_<ID>, on bus I in its substation. It has one section, always in: maximumSections, normalSections and sections are all 1. GL and BL are MW and MVAr at 1 pu voltage, so the importer writes them as admittances in per unit on the system base, gPerSection (pu system) = GL / SBASE and bPerSection (pu system) = BL / SBASE, and nomU (kV) is the bus's BASKV. cimtables turns them into siemens on those two bases. BL above 0 is a capacitor in RAW and in CIM, so its sign is unchanged. A shunt with a negative BL is a reactor.

Fixed shunt fields

RAW field Import Export
I structural: bus, nomU (kV) = BASKV, BaseVoltage, EquipmentContainer the bus number of the shunt's terminal
ID structural: key cap_<I>_<ID>, name <I>_<ID>; the ID is trimmed the ID in the mRID cap_<I>_<ID>, else the next free 1, 2, ... on the bus
STATUS mapped: inService; blank is 1 0 when inService is false, else 1
GL derived: gPerSection (pu system) = GL / SBASE; blank is 0 the shunt's g in pu on its bus base times SBASE, over the sections in service; an unset g is 0
BL derived: bPerSection (pu system) = BL / SBASE; blank is 0 the shunt's b, as GL

A LinearShuntCompensator with no RegulatingControl is a fixed shunt, unless it is a line shunt of an exported branch: those go back in the branch's GI, BI, GJ and BJ (see Branches, switches and multi-section lines). A shunt with a control is a block of a switched shunt.

Fixed shunt fail-fast rules

Rule Message
a STATUS other than 0 or 1 fixed shunt 1_1: status=2 has no mapping (known: 0, 1)
export: nomU is not the shunt's BaseVoltage LinearShuntCompensator 'x': nomU 230.0 kV is not its BaseVoltage 115.0 kV; RAW states a shunt at 1 pu of its bus voltage
export: a NonlinearShuntCompensator no RAW export yet for {'NonlinearShuntCompensator': 1}

Fixed shunt round trip

GL and BL come back as written, up to the last digit of the per-unit round trip. The fixed shunt atom's two shunts, 1 1 (GL + jBL = 1.5 + j20) and 1 2 (a reactor out of service), come back unchanged.

Fixed shunt excerpt

From cimhub_raw/tests/goldens/IEEE14/fixed_shunt.cimtbl:

Table LinearShuntCompensator: mRID, name, bus, gPerSection (pu system), bPerSection (pu system), nomU (kV), maximumSections, normalSections, sections, inService, BaseVoltage, EquipmentContainer
    cap_9_1, 9_1, 9, 0.0, 0.19, 138.0, 1, 1, 1, true, bv_138kv, sub_4

BL 19.0 Mvar on SBASE 100 is bPerSection 0.19.

Switched shunt

One RAW switched shunt is a bus's whole set of switched banks under one controller: up to eight blocks, each Ni identical steps of Bi Mvar, and a mode MODSW that says what controls them. The importer writes one LinearShuntCompensator per block, all naming one RegulatingControl. The control is written first and the blocks second. A locked shunt (MODSW 0) still has its control, disabled, so its blocks stay grouped. The mRIDs are swsh_<I>_b<k> for block k in input order and cc_<I> for the control.

Blocks. The blocks run up to the first Ni or Bi that is 0 or blank, which is RAW's end of the list. For each:

CIM attribute Value
maximumSections Ni
bPerSection (pu system) Bi / SBASE, with nomU (kV) = the BASKV of bus I; a negative Bi is a reactor block
sections the block's share of BINIT, below
inService STATUS == 1, the same on every block
controlEnabled the control's enabled

A block after the first zero raises, and so does a record with no blocks at all. The block slots are never defaulted, because a missing Ni or Bi is the end of the list, not a value.

Sections. RAW gives only the total in service, BINIT in Mvar at 1 pu voltage. The importer splits it in RAW's switching order (ADJM 0): a negative BINIT fills the reactor blocks in input order and a positive one the capacitor blocks. Each block takes up to its Ni steps, and the block where BINIT runs out takes the rest as a fraction of a step (CIM allows a non-integer sections). A BINIT beyond the blocks' total raises. normalSections is not written. ADJM is untranscribed; the order is kept by the _b<k> suffix.

Control. MODSW sets the control's mode:

MODSW RegulatingControl Regulates
0 locked mode voltage, enabled false, discrete blank, and every block controlEnabled false; the target is VSWHI and VSWLO as read, unused bus SWREG
1 discrete, voltage mode voltage, discrete true bus SWREG
2 continuous, voltage mode voltage, discrete false bus SWREG
3 discrete, plant reactive power mode reactivePower, discrete true the one machine of the plant at SWREG
6 discrete, FACTS shunt reactive power mode reactivePower, discrete true the FACTS device named by RMIDNT
4 (a VSC converter's reactive power), 5 (another shunt's admittance) raise NotImplementedError
any other value raises

Regulated bus (MODSW 0, 1, 2). The control's Terminal is the busbar terminal bb_<SWREG>_T1, or bb_<I>_T1 when SWREG is 0. An NREG other than 0 names a node of the regulated bus, and the terminal is that node's busbar (see Substations and node-breaker data). A SWREG that is no bus raises, in every mode, MODSW 6 included.

Voltage target. targetValue is the middle of the band, (VSWHI + VSWLO) / 2 times the regulated bus's BASKV, in volts. targetDeadband is the whole band, (VSWHI - VSWLO) times BASKV, in volts. The subtraction can leave a last-digit residue: 1.04 - 0.98 gives 6900.0000000000055. The value is written as computed.

Plant reactive power (MODSW 3). VSWLO and VSWHI are fractions of the range QB to QT of the plant's machine at SWREG (or at bus I when SWREG is 0). The band runs from QB + VSWLO x (QT - QB) to QB + VSWHI x (QT - QB) Mvar, using the machine's limits as written and ignoring its status. The control's Terminal is the machine's own terminal, sm_<I>_<ID>_T1 or pec_<I>_<ID>_T1, where PSS/E measures the machine's reactive power. targetValue is minus the midpoint of the band and targetDeadband its width, both in VAr: a terminal's q follows the load sign, so a machine's q is minus QG. A plant of several machines at SWREG raises, because one terminal measures one machine. With no machine at SWREG the control is written disabled, with no target, on the busbar terminal bb_<SWREG>_T1, and a VSWLO or VSWHI off its default is listed on the row (# untranscribed: vswlo=0.0).

FACTS reactive power (MODSW 6). The same band over -SHMX to +SHMX of the FACTS device named by RMIDNT, on the device's terminal fd_<RMIDNT>_T1. SWREG is not used. An RMIDNT that names no FACTS device raises, and so does a device with a series element (see DC lines and FACTS devices).

Static var compensator

RAW v34 has no SVC record: PSS/E models one as a continuous switched shunt. A MODSW 2 shunt whose blocks are at most one reactor and one capacitor, each of one step, is one StaticVarCompensator swsh_<I> instead of its blocks. Its control cc_<I> is the same as any MODSW 2 shunt's. Every other shunt stays blocks, MODSW 2 ones with several steps or two blocks of one sign included.

CIM attribute Value
capacitiveRating (pu system) SBASE / Bi of the capacitor block: X = U² / Q at 1 pu, positive; blank with no capacitor
inductiveRating (pu system) SBASE / Bi of the reactor block, negative; blank with no reactor
q (MVAr) -BINIT, the starting output under the load sign; a BINIT beyond the range raises
sVCControlMode voltage
inService, controlEnabled STATUS == 1; true
RegulatingControl cc_<I>, as above

voltageSetPoint and slope are blank: the control carries the target, and RAW has no droop. The exporter writes an SVC back as a MODSW 2 record (MODSW 0 when its control is locked): a one-step reactor block of SBASE / inductiveRating Mvar, then a one-step capacitor block of SBASE / capacitiveRating, BINIT = -q, and VSWHI, VSWLO and SWREG from the control as for a bank. From the atom cimhub_raw/tests/atoms/shunt/svc.raw (230 kV, SBASE 100; bus 1: -50 and 100 Mvar, BINIT 40, regulating bus 4; bus 2: a 30 Mvar capacitor, out of service):

Table StaticVarCompensator: mRID, name, bus, capacitiveRating (pu system), inductiveRating (pu system), q (MVAr), sVCControlMode, inService, controlEnabled, RegulatingControl, BaseVoltage, EquipmentContainer
    swsh_1, 1, 1, 1.0,                -2.0, -40.0, voltage, true,  true, cc_1, bv_230kv, sub_1
    swsh_2, 2, 2, 3.3333333333333335, ,     0.0,   voltage, false, true, cc_2, bv_230kv, sub_2

The SVC export raises on: no RegulatingControl; a control of mode reactive power, or sVCControlMode reactive power; a discrete control; an inductiveRating of 0 or more, or a capacitiveRating of 0 or less; neither rating set; an SVC on a bus that already has a switched shunt.

Switched shunt fields

RAW field Import Export
I structural: the key; every block's bus, nomU (kV) = BASKV, BaseVoltage, EquipmentContainer the bus number of the blocks' terminals; all blocks of one control must be on one bus, and two controls on one bus raise
MODSW mapped: the control's mode, discrete and enabled, as in the table above; blank is 1 from the control (the blocks' controlEnabled must agree): voltage and locked (enabled false, or every block's controlEnabled false) 0, voltage with discrete true or unset 1, voltage with discrete false 2; reactive power on a FACTS device 6; reactive power on a machine, or on anything else when locked, 3; any other mode raises
ADJM untranscribed not written
STATUS mapped: inService of every block; blank is 1 0 when the blocks are out of service; blocks in and out of service on one control raise
VSWHI, VSWLO derived: the control's targetValue and targetDeadband: volts for MODSW 0 to 2, VAr for MODSW 3 and 6; blank is 1.0 the band's top and bottom from the control's target plus or minus half its deadband: kV over the regulated bus's BASKV for voltage, fractions of the machine's minQ to maxQ or of the device's -SHMX to SHMX for MODSW 3 and 6; blank for a disabled control with no target. A machine with the same minQ and maxQ raises
SWREG structural: the control's Terminal, as above; MODSW 3: the plant's bus; MODSW 6: not used, but a nonzero SWREG must still be a bus; blank is 0 the bus number of the control's terminal, its own bus included; blank for MODSW 6
RMIDNT structural: MODSW 6: the FACTS device MODSW 6: the name of the FACTS device at the control's terminal; else blank
BINIT derived: split into the blocks' sections the sum over the blocks of sections times Bi
N1 to N8 structural: maximumSections of block k the blocks in the order of the mRID swsh_<I>_b<k>, else reactors first, then capacitors, each by mRID; more than 8 raise; a maximumSections below 1 raises
B1 to B8 structural: bPerSection (pu system) = Bi / SBASE the block's b per section in pu on its bus base times SBASE; a block with g other than 0 raises
NREG structural: a node of the regulated bus, as above; blank is 0 not written
RMPCT untranscribed: CIM 18 has no participation share for a shunt not written

Switched shunt fail-fast rules

Rule Message
MODSW 4 or 5 switched shunt 1: MODSW 4 (VSC converter reactive power: no case has one yet)
any other MODSW switched shunt 1: modsw=9 has no mapping (known: 0, 1, 2, 3, 6)
a block after the first zero Ni or Bi switched shunt 1: a block after the first zero Ni or Bi (block 2): [(2, -15.0), (0, 0.0), (2, 5.0), ...]
no block at all switched shunt 1: no blocks (N1, B1 = (0, 0.0))
BINIT beyond the blocks' total switched shunt switched shunt 1: BINIT=500.0 is beyond its blocks [(2, -15.0), (3, 10.0), (2, 25.0)]
a SWREG that is no bus switched shunt 1: SWREG 999 is no bus
MODSW 3 with several machines at SWREG switched shunt 2: the plant at bus 1 has 2 machines; one terminal measures one machine (no case)
MODSW 6 naming no FACTS device switched shunt 5: RMIDNT 'NOPE' names no FACTS device
export: the blocks of one control with different controlEnabled RegulatingControl 'x': its blocks' controlEnabled disagree
export: blocks in and out of service on one control RegulatingControl 'x': its blocks are in and out of service; a switched shunt has one status
export: a block with gPerSection set, or a maximumSections below 1 LinearShuntCompensator 'x': gPerSection is set; a switched shunt block has no G
export: blocks of one control on two buses RegulatingControl 'x': controls shunts on buses [(1,), (2,)]; a switched shunt is on one
export: two controls (or an SVC) on one bus bus 1: RegulatingControl 'x' and RegulatingControl 'y' are both switched shunts; a v34 switched shunt's key is its bus
export: more than 8 blocks RegulatingControl 'x': controls 9 shunts; a switched shunt has 8 blocks
export: a control mode other than voltage or reactive power, or reactive power on equipment that is neither a machine nor a FACTS device RegulatingControl 'x': reactive power of ...; MODSW 3 regulates a plant's machine and 6 a FACTS device

Switched shunt round trip

What Why
SWREG 0 comes back as the bus's own number CIM keeps the terminal, not whether RAW wrote 0 or I
VSWHI and VSWLO, Bi and BINIT can differ in the last digit the importer converts through volts or per unit and the exporter converts back (10.000000000000002 for 10); relative error 1e-9
ADJM and RMPCT come back blank no CIM home
NREG comes back blank not written; a control on a substation node is exported against its bus
a MODSW 3 shunt with no plant comes back with VSWHI and VSWLO blank its control has no target; PSS/E reads blank as 1.0
BINIT can differ in the last digit the exporter adds up sections times Bi, which inverts the split

This example converts the switched shunt atom and prints each block's state, each control's target and deadband in kV, and the exported records:

import cimprofiles.cim18.cim18v17 as cim

import cimhub_raw.schema.raw_v34.raw34_schema as schema
from cimhub_core.getters.control import get_regulating_control
from cimhub_raw.exporter.cim_to_raw import RawExporter
from cimhub_raw.importer.raw_to_cimtbl import raw_to_cim
from cimhub_raw.raw34_reader import Raw34Reader
from cimhub_raw.raw34_writer import Raw34Writer

case = Raw34Reader("cimhub_raw/tests/atoms/shunt/switched_shunts.raw").read_all()
network = raw_to_cim(case, name="atom")

for block in network.graph[cim.LinearShuntCompensator].values():
    control = block.RegulatingControl
    print(block.mRID, block.sections, block.maximumSections, control.mRID, control.mode.name, control.enabled)

for control in network.graph[cim.RegulatingControl].values():
    settings = get_regulating_control(control, "kV")
    print(control.mRID, settings.target, settings.deadband)

writer = Raw34Writer()
for record in RawExporter().to_model(network).list_by_class(schema.SwitchedShuntRecord):
    print(writer.serialize(record))
swsh_1_b1 1.0 2 cc_1 voltage True
swsh_1_b2 0.0 3 cc_1 voltage True
swsh_1_b3 0.0 2 cc_1 voltage True
swsh_2_b1 2.5 4 cc_2 voltage True
swsh_3_b1 10.0 10 cc_3 voltage False
swsh_3_b2 2.0 5 cc_3 voltage False
cc_1 116.15 6.900000000000006
cc_2 230.0 13.800000000000011
cc_3 230.0 0.0
1,1,,1,1.04000,0.98000,4,,,-15.00000,2,-15.00000,3,10.000000000000002,2,25.00000
2,2,,1,1.03000,0.97000,2,,,31.25000,4,12.50000
3,0,,1,1.00000,1.00000,3,,,13.00000,10,1.00000,5,1.50000

The atom's bus 1 has a reactor block of two steps of -15 Mvar and two capacitor blocks, with BINIT -15, so the reactor block has one step in. Its control regulates remote bus 4 (115 kV), so the target is 1.01 x 115 kV = 116.15 kV. Bus 2 is continuous (MODSW 2) with BINIT 31.25 over four steps of 12.5, so 2.5 sections. Bus 3 is locked, its blocks 10 x 1.0 and 5 x 1.5 Mvar with BINIT 13 give 10 and 2 steps, and its control is disabled. The exported SWREG of buses 2 and 3 is their own bus; the source had 0. The ADJM 1 of bus 3 comes back blank.

Switched shunt excerpt

From the artifact the importer writes for cimhub_raw/tests/atoms/shunt/switched_shunts.raw; no golden has a switched shunt:

# untranscribed: adjm, rmpct
# targetValue and targetDeadband in V (voltage) or VAr (reactivePower)
Table RegulatingControl: mRID, name, mode, discrete, enabled, targetValue, targetDeadband, Terminal
    # defaulted: nreg=0
    cc_1, 1, voltage, true,  true,  116150.0, 6900.0000000000055, bb_4_T1
    # defaulted: nreg=0
    cc_3, 3, voltage, ,      false, 230000.0, 0.0,                bb_3_T1

# one per block: Ni sections of Bi; sections split from BINIT (block_sections)
Table LinearShuntCompensator: mRID, name, bus, bPerSection (pu system), nomU (kV), maximumSections, sections, inService, controlEnabled, RegulatingControl, BaseVoltage, EquipmentContainer
    swsh_1_b1, 1_b1, 1, -0.15, 230.0, 2, 1.0, true, true, cc_1, bv_230kv, sub_1
    swsh_1_b2, 1_b2, 1, 0.1,   230.0, 3, 0.0, true, true, cc_1, bv_230kv, sub_1
    ...

The reactive power modes are in the artifact for cimhub_raw/tests/atoms/shunt/plant_and_facts.raw. Bus 2's shunt regulates the WMOD 1 machine PV at bus 1 (QT 50, QB -30) over 0.25 to 0.75, so the band is -10 to 30 Mvar, target -10 000 000 VAr and deadband 40 000 000 VAr. Bus 3's shunt has no plant at SWREG. Bus 5's shunt regulates the FACTS device SVC-1 (SHMX 100) over 0.4 to 0.6, a band of -20 to +20 Mvar:

Table RegulatingControl: mRID, name, mode, discrete, enabled, targetValue, targetDeadband, Terminal
    # defaulted: nreg=0
    cc_2, 2, reactivePower, true, true,  -10000000.0, 40000000.0, pec_1_PV_T1
    # defaulted: nreg=0; untranscribed: vswlo=0.0
    cc_3, 3, reactivePower, true, false, ,            ,           bb_3_T1
    # defaulted: nreg=0
    cc_5, 5, reactivePower, true, true,  0.0,         40000000.0, fd_SVC-1_T1

A whole case that holds a FACTS device cannot be exported: see DC lines and FACTS devices.