Conversion reference

What happens to each PSS/E RAW v34 table when a .raw case becomes CIM and when CIM becomes a .raw case. The pages are lookup tables, one section per RAW table. For the steps of a conversion see the user guide; for the code behind it, the developer docs; for the complete design records, the import mapping and the export mapping.

The core site documents what the spoke is built on: the getters, the .cimtbl contract, the canonical shapes, the units rules and its reference. All CIM names here are cim18v17.

How to read these pages

The five field classes. The importer classifies every field of every RAW record in one of five ways. A test checks that the classification covers every field of the schema.

class meaning
copied the value lands in one .cimtbl column unchanged, in the unit RAW uses, and the unit is in the column header
mapped the value picks something through a code table (a CIM class, an enum, a flag), or sets how other values are read
structural the value is an identifier, a key or a link (a bus number, a substation number, an ID), not a quantity
derived the importer computes the value from RAW fields (a sign flip, a pu voltage times its base), and the formula is on the table comment
untranscribed CIM 18 has no home for it. The value is listed in a comment of the .cimtbl document, or the field is dropped and the page says so

Units. A .cimtbl column header carries the unit of the RAW value, as in normalValue (kV) or pTolerance (MW). A per-unit value on the system base is written verbatim with the header (pu system); cimtables converts it on the BasePower the master writes first. The importer does no unit math of its own, except the derived pu-times-base values named in each section. The exporter reads every quantity through a core getter or cimtables.graph_write.get_qty, which returns it in the unit the RAW field uses.

Raises. A rule that "raises" is fail fast: the importer or exporter stops with an error that names the record, the field and the value. Nothing is skipped or guessed. Unknown codes, unresolved references and records the converter cannot place all raise.

Defaults. A blank RAW field is read as None. The importer fills it from the schema's default and marks the row # defaulted: field=value, so a default is never silent.

Section layout. Each section starts with the CIM classes and .cimtbl shape a RAW table becomes, then a table with one row per RAW field:

column says
field the RAW field name, with the schema's Python slot name in backticks where it differs
import the CIM class and attribute it reaches, with the header unit; or untranscribed; or raises when ...
export how it is written back, and through which getter; or not exported

After the table come the fail-fast rules, what a round trip changes, and a short excerpt copied from a golden file in cimhub_raw/tests/goldens/ or from the artifact the importer writes for a hand-built atom in cimhub_raw/tests/atoms/.

Which tables convert

Import is the importer's MAPPING_ORDER plus the equipment-terminal step that follows it and the master document; export is the exporter's EXPORT_ORDER. The phase-2 stubs are the tables whose mapper exists only to fail fast. A RAW record class that is in none of these is counted in the master's not mapped: comment, so nothing disappears silently.

RAW table CIM classes Import Export Page
Case identification (IC, SBASE, REV, XFRRAT, NXFRAT, BASFRQ) BasePower, BaseFrequency, GeographicalRegion, BaseVoltage yes (IC other than 0 raises) yes buses
System-wide options (GENERAL, GAUSS, NEWTON, ADJUST, TYSL, SOLVER) none; THRSHZ steers the substation grouping untranscribed no buses
Rating sets (RATING) OperationalLimitType olt_rate1 to olt_rate12 yes yes buses
Bus TopologicalNode, BusbarSection, OperationalLimitSet, VoltageLimit, SvVoltage, Substation yes yes buses
Zone SubGeographicalRegion yes yes buses
Area interchange ControlArea yes yes buses
Inter-area transfer none (listed on the ControlArea comment) untranscribed no buses
Owner none untranscribed no buses
Tie flows (MET, METERED, NMETR on a tie) TieFlow yes yes buses
Substation (SUBSTATION block) Substation, Location, PositionPoint, CoordinateSystem yes no substations
Substation node ConnectivityNode, BusbarSection (regulated nodes only) yes no substations
Substation switching device Switch, Breaker, Disconnector yes no substations
Equipment terminal Terminal (an Update row) yes (TYP I, D, V, N, A raise) no substations
Branch ACLineSegment, SeriesCompensator, LinearShuntCompensator (line shunts), OperationalLimitSet, TieFlow yes yes branches
System switching device Switch, Breaker, Disconnector yes yes branches
Multi-section line grouping Line yes yes branches
Load ConformLoad, NonConformLoad, LoadResponseCharacteristic, LoadArea, SubLoadArea, load groups yes yes loads
Fixed shunt LinearShuntCompensator yes yes loads
Switched shunt LinearShuntCompensator per block, RegulatingControl; a StaticVarCompensator for MODSW 2 of one reactor and one capacitor step yes yes loads
Generator SynchronousMachine, GeneratingUnit, PowerElectronicsConnection, PowerElectronicsUnit, RegulatingControl, a step-up PowerTransformer yes yes generators
Transformer PowerTransformer, PowerTransformerEnd, TransformerMeshImpedance, RatioTapChanger, PhaseTapChangerLinear, TapChangerControl yes yes transformers
Impedance correction ImpedanceTapChangerTable, ImpedanceTapChangerTablePoint yes yes transformers
Two-terminal DC DCLine, DCLineSegment, DCTopologicalNode, CsConverter, converter PowerTransformer yes no dc
VSC DC DCLine, DCLineSegment, DCTopologicalNode, VsConverter, VsCapabilityCurve yes no dc
FACTS device StaticSynchronousCompensator, RegulatingControl (a shunt-only device; a series element raises) yes yes dc
Multi-terminal DC none raises no dc
GNE device none raises no dc
Induction machine none raises no dc

"Export no" for the node-breaker rows and the DC rows is the state of the exporter today, not a CIM limit. On export, conducting equipment of a class no exporter module writes raises (no RAW export yet for {...}), so a case with a DC line stops instead of losing it. The node-breaker substation data is the exception: see the substations page.

Pages

page covers
Case, buses, areas and zones case identification and system-wide data, rating sets, bus, zone, area interchange, inter-area transfer, tie flows, owner
Substations and node-breaker data the substations the importer synthesizes from buses, SUBSTATION blocks with their nodes, switching devices and equipment terminals
Branches, switches and multi-section lines branch, system switching device, multi-section line, ratings
Transformers and impedance correction two- and three-winding transformers, impedance correction tables
Loads and shunts load, fixed shunt, switched shunt
Generators generators, renewables, the implicit step-up transformer
DC lines and FACTS devices two-terminal DC, VSC DC, FACTS, and the record types that raise