Reader and writer¶
Raw34Reader reads a PSS/E RAW v34 file into a GraphModel of the schema's record dataclasses; Raw34Writer writes
such a model back. The two walk the same positional layout (record_layout.py), so they cannot disagree about where
a field sits. These are the only classes in the package that touch a .raw file. The code is
raw34_reader.py,
raw34_writer.py
and
record_layout.py.
import cimhub_raw.schema.raw_v34.raw34_schema as schema
from cimhub_raw.raw34_reader import Raw34Reader
from cimhub_raw.raw34_writer import Raw34Writer
model = Raw34Reader("cimhub_raw/tests/cases/IEEE14/IEEE_14_bus.raw").read_all()
print(model.count(schema.BusRecord), model.count(schema.BranchRecord)) # 14 17
load = model.list_by_class(schema.LoadRecord)[0]
print(load.ID, load.constant_real_power, load.constant_imag_power) # 10_1 9.0 5.8
Raw34Writer().write(model, "/tmp/ieee14_out.raw")
print(Raw34Writer().serialize(load)) # 10,'1 ',1,1,1,9.000,5.800,...
Raw34Reader¶
Raw34Reader(source) binds a path without reading it. read_all() reads the file once and returns the same
GraphModel on every later call. The parsing is in a private class, _FileReader, made for one read of one file: its
lines, a table of bus names for extended bus names, and the line each key was first seen on. A missing file raises
FileNotFoundError.
Sections¶
The sections are positional. After the case identification and the system-wide data, SECTIONS lists the twenty
sections in the v34 file order, each as the name used in the end-of-section comments and its record class:
| Order | Section | Record class |
|---|---|---|
| 1-7 | BUS, LOAD, FIXED SHUNT, GENERATOR, BRANCH, SYSTEM SWITCHING DEVICE, TRANSFORMER | BusRecord, LoadRecord, FixedShuntRecord, GeneratorRecord, BranchRecord, SwitchRecord, TransformerRecord |
| 8-12 | AREA, TWO-TERMINAL DC, VSC DC LINE, IMPEDANCE CORRECTION, MULTI-TERMINAL DC | AreaInterchangeRecord, TwoTerminalDCRecord, VscDcRecord, ImpedanceCorrectionRecord, MultiTerminalDCRecord |
| 13-17 | MULTI-SECTION LINE, ZONE, INTER-AREA TRANSFER, OWNER, FACTS DEVICE | MultiSectionLineRecord, ZoneRecord, InterareaTransferRecord, OwnerRecord, FactsDeviceRecord |
| 18-20 | SWITCHED SHUNT, GNE, INDUCTION MACHINE | SwitchedShuntRecord, GneDeviceRecord, InductionMachineRecord |
The SUBSTATION section (nested blocks) follows and is read by _read_substations. The comment text after a section's
0 is not read: only the position matters, and a section is empty when its first record is the 0. A section whose
terminator is missing raises (the file ends inside the BUS section (no 0 record)).
@! lines are comments and are skipped everywhere except the two title lines, which next_line(verbatim=True) reads
as they are. The case identification record is the first non-comment line; its REV must be 34 or the read raises
(REV is 33.0; this reader reads RAW v34 only).
The system-wide records follow the titles and run up to a 0. RATING records become RatingRecords in the case's
ratings list. The keywords in SYSTEM_WIDE_KEYWORDS (GENERAL, GAUSS, NEWTON, ADJUST, TYSL, SOLVER) are
kept as their text in the slot of the same lower-case name (case.general); a keyword given twice, or any other
keyword, raises.
A Q record ends the data. The reader sets ended, every later section is empty, and what follows Q is not read.
A Q inside a multi-line record, or before an impedance correction table's last point, raises.
Tokens and quoting¶
tokenize(text) splits one record line into Tokens (a str with a quoted flag), or None for a blank field:
from cimhub_raw.raw34_reader import tokenize
print(tokenize("1,'A, B',,3 / comment")) # ['1', 'A, B', None, '3']
- Fields are separated by a comma or by blanks. Two commas in a row, or a comma at the start, make a blank field.
- A quoted field (
'...'or"...") may hold commas, blanks and a/. An unclosed quote raisesValueError, which_tokensturns into aRaw34ParseError. - An unquoted
/starts a comment that runs to the end of the line. This is how0 / END OF BUS DATA, BEGIN LOAD DATAreads as the one token0. - A section ends at a record whose first token is a bare
0(_is_terminator): a quoted'0'is a name.
Fields and the layout¶
A record is a sequence of lines, each a tuple of Slots. record_layout.record_lines(record_class) builds them from
the schema annotations (see The LinkML schema) and caches the result:
import cimhub_raw.schema.raw_v34.raw34_schema as schema
from cimhub_raw.record_layout import line_count, record_lines
for line in record_lines(schema.TransformerRecord):
print(len(line), line[0].name) # five lines (22, 11, 27, 27, 27 slots); the first slot of each
print(line_count(schema.TransformerRecord, {"k": 0})) # 4: no third winding
| Function | Does |
|---|---|
Slot(name, value_type, count, annotations) |
One field position. value_type is int, float or string. count is 1 for a scalar and the list length for a fixed-size list (RATE1..RATE12, count 12), which fills that many positions. |
record_lines(record_class) |
The record's lines in field order. A slot without an order, or marked structural, is not a field of the record text and is left out. Two slots with one order on a line raise. |
line_count(record_class, first_line) |
The number of lines the record has, given the values of its first line. A transformer has its fifth line (the third winding) only when K is set and nonzero. Every other record has all the lines of its layout. |
terminal_slots(terminal_type) |
The slots of an equipment terminal record, which has one field list per equipment form, chosen by TYP (TERMINAL_FORMS). An unknown form raises. |
_values(record_class, slots, tokens, ...) converts the tokens of one line to {slot name: value}:
- More tokens than the line has slots raises (
BusRecord: 14 fields where the record has 13). - A missing or blank field is
None. A list slot takes itscounttokens and isNonewhen all are blank. - An
intslot takes a number with no fraction (1,1.0), else raises; afloatslot takes a finite number, and a quoted one raises; astringslot is the token with its trailing blanks removed. Every error names the record class and slot and the line, with the line's text. - A quoted value in an
intslot is an extended bus name,'NAME kV': the 12-character bus name, then the base kV._bus_numberlooks it up in the table_index_bus_namesbuilds right after the bus section, so every bus reference in the model is a number. A leading-gives the negated number. A name that matches no bus or more than one, or has no kV, raises.
_read_section reads a record's first line, then line_count and record_lines say how many more lines to read and
how to read each; their values are merged into one dict, and the dataclass is built from it. A dataclass that rejects
the values (a required field left blank) raises through _construct, with the line.
The impedance correction table is the one special case (_impedance_correction): its length is not in the layout.
It reads the table number, then points in (T, Re(F), Im(F)) triples, up to POINTS_PER_LINE (six) per line, until a
0, 0, 0 triple. Points after that triple, a partial triple, a blank point field, a Q before the end, or more than
MAX_POINTS (99) raise. The points are ImpedanceCorrectionPoints in the record's points list.
The SUBSTATION section is nested: a substation record, then three parts each ended by its own 0 (the nodes, the
switching devices, the equipment terminals). _read_substations reads the parts in that order and sets the reader-filled
substation_number on each part record (a structural slot). An equipment terminal's slots depend on its TYP, the
third field (_terminal_slots).
Defaults and the defaulted note¶
The reader fills no defaults. A blank or missing field is None, so the model holds what the file said, and the
writer writes it back blank. The importer fills a blank from the slot's raw_default annotation
(records.raw_defaults, fill_keyed_defaults) and lists each value it filled in a defaulted: comment on the row, so
a default is visible in the artifact. The importer has the details.
The one exception is a blank key field, which takes its raw_default when the composite ID is built (next section):
a load with no ID is load 1, so the same load has the same key however the file wrote it. The slot itself stays
None.
Composite IDs¶
GraphModel keys a record on its schema identifier: true slot, else on record.ID. Most RAW records have a
natural key of several fields, so the reader calls
composite_id.assign_composite_id(record)
on every record it adds, which sets record.ID.
KEY_FIELDS lists the fields of each key; the key is their trimmed values joined with _:
| Record | Key fields | Example |
|---|---|---|
| Load, Fixed shunt, Generator | bus_number, load_id / shunt_id / gen_id |
10_1 |
| Branch, System switching device | from_bus_number, to_bus_number, circuit |
1001_1201_1 |
| Transformer | i, j, k, circuit |
1001_1002_0_1 |
| Switched shunt | bus_number |
4001 |
| FACTS device | name |
|
| Induction machine | bus_id, name |
|
| Inter-area transfer | from_area, to_area, transfer_id |
|
| Multi-section line | i, j, line_id |
|
| Substation node | substation_number, node_number |
|
| Station switching device | substation_number, from_node, to_node, circuit |
|
| Equipment terminal | substation_number, bus_number, terminal_type, j_bus, k_bus, identifier |
The other records have a single key slot marked identifier: true: the bus, area, zone, owner, substation and
impedance correction table numbers, a rating set's number, a DC line's name and, for the case identification record,
IC. That slot wins over ID as the graph key, so the case record is keyed '0' even though
assign_composite_id also sets its ID to CASE.
_add also checks the key: a second record with the same type and key raises (duplicate BranchRecord '1_2_1' (first on
line <n>)). The exporter calls the same function on the records it builds (export_tables), so the key that seeds an
mRID on import is the key an exported record has.
Errors¶
Raw34ParseError(message, *, source, line_number, text) is a message prefixed with <file>:<line>: and followed by
the offending line's text. A reader error is one of these:
| Raised for | Where |
|---|---|
| a REV other than 34 | _read_case |
| an unknown or repeated system-wide keyword | _read_case |
| more fields than the record has, a value that does not convert, an unclosed quote | _values, _tokens |
| an extended bus name with no bus, or two | _bus_number |
| a duplicate key | _add |
a missing section terminator, a blank line where a record belongs, the file ending inside a record, data after the last section that is not Q |
_next_record_tokens, _part, read |
| a dataclass that rejects its values | _construct |
A populated MULTI-TERMINAL DC or GNE section raises NotImplementedError (PHASE_2_SECTIONS), naming the section and
the record count. A bus reference to a bus that does not exist is not a reader error: the reader checks only extended
names. A mapper finds it.
Raw34Writer¶
Raw34Writer().write(model, destination) writes "\n".join(lines(model)) + "\n" to the path. serialize(obj) is one
record as RAW text, several lines for a multi-line record. The writer is the reader's mirror: it writes what the
model holds and defaults nothing.
| Function | Does |
|---|---|
format_field(slot, value) |
One field's text. None is blank. An int slot is str(int(value)). A float slot is written with the slot's precision when that reads back as the same number, else with repr (the shortest exact form). A string slot is padded to its width with ljust and, when quote is set, wrapped in its quote_char (default '). |
format_line(slots, record) |
One line: its fields by position, comma-joined. A list slot writes its values then blanks up to count; more values than count raises. Trailing blank fields are dropped, so the line has only what the model held. |
format_record(record) |
Every line of a record: line_count lines, each from format_line. |
format_impedance_correction(record) |
The special case below. |
import cimhub_raw.schema.raw_v34.raw34_schema as schema
from cimhub_raw.raw34_writer import format_field
from cimhub_raw.record_layout import record_lines
slot = record_lines(schema.FixedShuntRecord)[0][1] # shunt_id: width 2, quoted
print(repr(format_field(slot, "1"))) # "'1 '"
The file, in order¶
lines(model) writes:
- The case record line, the two title lines (verbatim, always two; a case with more than two raises), each
system-wide keyword that has text, and a
RATING,line per rating. - For each entry of
SECTIONS, a line0 / END OF <previous> DATA, BEGIN <section> DATA, then that section's records in the model's insertion order (the file order, for a model the reader built). 0 / END OF <last section> DATA, BEGIN SUBSTATION DATA, then each substation record followed by its nodes, a0 / END OF SUBSTATION NODE DATA, BEGIN SUBSTATION SWITCHING DEVICE DATAline, its switching devices, a terminator line, its equipment terminals (each byterminal_slotsof its TYP) and a last terminator. A part whose substation is not in the model raises.0 / END OF SUBSTATION DATAandQ.
A model with no CaseIdentificationRecord raises. Bus references are written as numbers, never as extended names.
The impedance correction special case¶
A table is written number first, then its points (T, Re(F), Im(F)) six to a line, ended by a 0, 0, 0 point; the
number is on the first line only. format_impedance_correction writes each value with a precision of 5.
Phase-2 records¶
A model that holds a record of a phase-2 section (PHASE_2_SECTIONS: MULTI-TERMINAL DC, GNE) makes lines raise
NotImplementedError with the count and class, as the reader does for the same sections.
Round trip¶
The reader and writer are lossless on the committed cases and atoms: test_read_write_read_is_lossless reads a case,
writes it, reads the output and compares every record field. See Testing.