Skip to content

Class: SwitchedShuntRecord

Switched shunt compensator data record.

Variable-length format:

- Fixed fields: I, MODSW, ADJM, STAT, VSWHI, VSWLO, SWREG, RMPCT, RMIDNT, BINIT

- Variable blocks: Up to 8 N/B pairs (only non-zero blocks are serialized)

- Final field: NREG (only if remote regulation is used)

Maps to CIM: cim.ShuntCompensator, cim.LinearShuntCompensator

__

URI: raw:SwitchedShuntRecord

 classDiagram
    class SwitchedShuntRecord
    click SwitchedShuntRecord href "../SwitchedShuntRecord/"
      SwitchedShuntRecord : adjm

      SwitchedShuntRecord : b1

      SwitchedShuntRecord : b2

      SwitchedShuntRecord : b3

      SwitchedShuntRecord : b4

      SwitchedShuntRecord : b5

      SwitchedShuntRecord : b6

      SwitchedShuntRecord : b7

      SwitchedShuntRecord : b8

      SwitchedShuntRecord : binit

      SwitchedShuntRecord : bus_number

      SwitchedShuntRecord : modsw

      SwitchedShuntRecord : n1

      SwitchedShuntRecord : n2

      SwitchedShuntRecord : n3

      SwitchedShuntRecord : n4

      SwitchedShuntRecord : n5

      SwitchedShuntRecord : n6

      SwitchedShuntRecord : n7

      SwitchedShuntRecord : n8

      SwitchedShuntRecord : nreg

      SwitchedShuntRecord : rmidnt

      SwitchedShuntRecord : rmpct

      SwitchedShuntRecord : status

      SwitchedShuntRecord : swreg

      SwitchedShuntRecord : vswhi

      SwitchedShuntRecord : vswlo

Slots

Name Cardinality and Range Description Inheritance
bus_number 1
Integer
I - Bus number or extended bus name where the switched shunt is connected direct
modsw 0..1
Integer
MODSW - Control mode (0 locked, 1 discrete local or remote voltage, 2 continu... direct
adjm 0..1
Integer
ADJM - Adjustment method (0 switch in input order, 1 next highest or lowest t... direct
status 0..1
Integer
STAT - Switched shunt status (0=out of service, 1=in service) direct
vswhi 0..1
Float
VSWHI - Voltage upper limit for switching in per-unit direct
vswlo 0..1
Float
VSWLO - Voltage lower limit for switching in per-unit direct
swreg 0..1
Integer
SWREG - Bus number or extended bus name of the regulated bus (0 or own bus fo... direct
rmpct 0..1
Float
RMPCT - Percent of required Mvar contribution (must be positive) direct
rmidnt 0..1
String
RMIDNT - Name of the VSC dc line (MODSW 4) or FACTS device (MODSW 6) direct
binit 0..1
Float
BINIT - Initial switched shunt admittance in Mvar at unity voltage direct
n1 0..1
Integer
N1 - Number of steps for block 1 (0 to 9) direct
b1 0..1
Float
B1 - Admittance increment for each step in block 1 in Mvar at unity voltage direct
n2 0..1
Integer
N2 - Number of steps for block 2 (0 to 9) direct
b2 0..1
Float
B2 - Admittance increment for each step in block 2 in Mvar at unity voltage direct
n3 0..1
Integer
N3 - Number of steps for block 3 (0 to 9) direct
b3 0..1
Float
B3 - Admittance increment for each step in block 3 in Mvar at unity voltage direct
n4 0..1
Integer
N4 - Number of steps for block 4 (0 to 9) direct
b4 0..1
Float
B4 - Admittance increment for each step in block 4 in Mvar at unity voltage direct
n5 0..1
Integer
N5 - Number of steps for block 5 (0 to 9) direct
b5 0..1
Float
B5 - Admittance increment for each step in block 5 in Mvar at unity voltage direct
n6 0..1
Integer
N6 - Number of steps for block 6 (0 to 9) direct
b6 0..1
Float
B6 - Admittance increment for each step in block 6 in Mvar at unity voltage direct
n7 0..1
Integer
N7 - Number of steps for block 7 (0 to 9) direct
b7 0..1
Float
B7 - Admittance increment for each step in block 7 in Mvar at unity voltage direct
n8 0..1
Integer
N8 - Number of steps for block 8 (0 to 9) direct
b8 0..1
Float
B8 - Admittance increment for each step in block 8 in Mvar at unity voltage direct
nreg 0..1
Integer
NREG - Node number of bus SWREG (0 if SWREG is not in a substation) direct

Usages

used by used in type used
RawModel switched_shunt_records range SwitchedShuntRecord

Identifier and Mapping Information

Schema Source

  • from schema: https://gridappsd.org/cimhub/raw_v34

Mappings

Mapping Type Mapped Value
self raw:SwitchedShuntRecord
native raw:SwitchedShuntRecord

LinkML Source

Direct

name: SwitchedShuntRecord
description: 'Switched shunt compensator data record.

  Variable-length format:

  - Fixed fields: I, MODSW, ADJM, STAT, VSWHI, VSWLO, SWREG, RMPCT, RMIDNT, BINIT

  - Variable blocks: Up to 8 N/B pairs (only non-zero blocks are serialized)

  - Final field: NREG (only if remote regulation is used)

  Maps to CIM: cim.ShuntCompensator, cim.LinearShuntCompensator

  '
from_schema: https://gridappsd.org/cimhub/raw_v34
attributes:
  bus_number:
    name: bus_number
    annotations:
      order:
        tag: order
        value: 1
      value_type:
        tag: value_type
        value: int
    description: I - Bus number or extended bus name where the switched shunt is connected
    from_schema: https://gridappsd.org/cimhub/raw_v34/classes/switched_shunt
    domain_of:
    - BusRecord
    - LoadRecord
    - FixedShuntRecord
    - GeneratorRecord
    - AreaInterchangeRecord
    - SwitchedShuntRecord
    - SubstationNodeRecord
    - EquipmentTerminalRecord
    range: integer
    required: true
  modsw:
    name: modsw
    annotations:
      order:
        tag: order
        value: 2
      value_type:
        tag: value_type
        value: int
      raw_default:
        tag: raw_default
        value: 1
    description: MODSW - Control mode (0 locked, 1 discrete local or remote voltage,
      2 continuous voltage, 3-6 reactive power or admittance control)
    from_schema: https://gridappsd.org/cimhub/raw_v34/classes/switched_shunt
    rank: 1000
    domain_of:
    - SwitchedShuntRecord
    range: integer
    required: false
  adjm:
    name: adjm
    annotations:
      order:
        tag: order
        value: 3
      value_type:
        tag: value_type
        value: int
      raw_default:
        tag: raw_default
        value: 0
    description: ADJM - Adjustment method (0 switch in input order, 1 next highest
      or lowest total admittance)
    from_schema: https://gridappsd.org/cimhub/raw_v34/classes/switched_shunt
    rank: 1000
    domain_of:
    - SwitchedShuntRecord
    range: integer
    required: false
  status:
    name: status
    annotations:
      order:
        tag: order
        value: 4
      value_type:
        tag: value_type
        value: int
      raw_default:
        tag: raw_default
        value: 1
    description: STAT - Switched shunt status (0=out of service, 1=in service)
    from_schema: https://gridappsd.org/cimhub/raw_v34/classes/switched_shunt
    domain_of:
    - LoadRecord
    - FixedShuntRecord
    - GeneratorRecord
    - BranchRecord
    - SwitchRecord
    - TransformerRecord
    - SwitchedShuntRecord
    - GneDeviceRecord
    - InductionMachineRecord
    - SubstationNodeRecord
    - StationSwitchingDeviceRecord
    range: integer
    required: false
  vswhi:
    name: vswhi
    annotations:
      order:
        tag: order
        value: 5
      value_type:
        tag: value_type
        value: float
      precision:
        tag: precision
        value: 5
      raw_default:
        tag: raw_default
        value: 1.0
    description: VSWHI - Voltage upper limit for switching in per-unit
    from_schema: https://gridappsd.org/cimhub/raw_v34/classes/switched_shunt
    rank: 1000
    domain_of:
    - SwitchedShuntRecord
    range: float
    required: false
  vswlo:
    name: vswlo
    annotations:
      order:
        tag: order
        value: 6
      value_type:
        tag: value_type
        value: float
      precision:
        tag: precision
        value: 5
      raw_default:
        tag: raw_default
        value: 1.0
    description: VSWLO - Voltage lower limit for switching in per-unit
    from_schema: https://gridappsd.org/cimhub/raw_v34/classes/switched_shunt
    rank: 1000
    domain_of:
    - SwitchedShuntRecord
    range: float
    required: false
  swreg:
    name: swreg
    annotations:
      order:
        tag: order
        value: 7
      value_type:
        tag: value_type
        value: int
      raw_default:
        tag: raw_default
        value: 0
    description: SWREG - Bus number or extended bus name of the regulated bus (0 or
      own bus for local control)
    from_schema: https://gridappsd.org/cimhub/raw_v34/classes/switched_shunt
    rank: 1000
    domain_of:
    - SwitchedShuntRecord
    range: integer
    required: false
  rmpct:
    name: rmpct
    annotations:
      order:
        tag: order
        value: 8
      value_type:
        tag: value_type
        value: float
      precision:
        tag: precision
        value: 4
      raw_default:
        tag: raw_default
        value: 100.0
    description: RMPCT - Percent of required Mvar contribution (must be positive)
    from_schema: https://gridappsd.org/cimhub/raw_v34/classes/switched_shunt
    domain_of:
    - GeneratorRecord
    - FactsDeviceRecord
    - SwitchedShuntRecord
    range: float
    required: false
  rmidnt:
    name: rmidnt
    annotations:
      order:
        tag: order
        value: 9
      value_type:
        tag: value_type
        value: string
      width:
        tag: width
        value: 12
      quote:
        tag: quote
        value: true
      quote_char:
        tag: quote_char
        value: ''''
      raw_default:
        tag: raw_default
        value: ''
    description: RMIDNT - Name of the VSC dc line (MODSW 4) or FACTS device (MODSW
      6)
    from_schema: https://gridappsd.org/cimhub/raw_v34/classes/switched_shunt
    rank: 1000
    domain_of:
    - SwitchedShuntRecord
    range: string
    required: false
  binit:
    name: binit
    annotations:
      order:
        tag: order
        value: 10
      value_type:
        tag: value_type
        value: float
      precision:
        tag: precision
        value: 5
      raw_default:
        tag: raw_default
        value: 0.0
    description: BINIT - Initial switched shunt admittance in Mvar at unity voltage
    from_schema: https://gridappsd.org/cimhub/raw_v34/classes/switched_shunt
    rank: 1000
    domain_of:
    - SwitchedShuntRecord
    range: float
    required: false
    unit:
      ucum_code: MVAr
  n1:
    name: n1
    annotations:
      order:
        tag: order
        value: 11
      value_type:
        tag: value_type
        value: int
      serialize_if:
        tag: serialize_if
        value: custom:n1 != 0
      raw_default:
        tag: raw_default
        value: 0
    description: N1 - Number of steps for block 1 (0 to 9)
    from_schema: https://gridappsd.org/cimhub/raw_v34/classes/switched_shunt
    rank: 1000
    domain_of:
    - SwitchedShuntRecord
    range: integer
    required: false
  b1:
    name: b1
    annotations:
      order:
        tag: order
        value: 12
      value_type:
        tag: value_type
        value: float
      precision:
        tag: precision
        value: 5
      serialize_if:
        tag: serialize_if
        value: custom:n1 != 0
      raw_default:
        tag: raw_default
        value: 0.0
    description: B1 - Admittance increment for each step in block 1 in Mvar at unity
      voltage
    from_schema: https://gridappsd.org/cimhub/raw_v34/classes/switched_shunt
    rank: 1000
    domain_of:
    - SwitchedShuntRecord
    range: float
    required: false
    unit:
      ucum_code: MVAr
  n2:
    name: n2
    annotations:
      order:
        tag: order
        value: 13
      value_type:
        tag: value_type
        value: int
      serialize_if:
        tag: serialize_if
        value: custom:n2 != 0
      raw_default:
        tag: raw_default
        value: 0
    description: N2 - Number of steps for block 2 (0 to 9)
    from_schema: https://gridappsd.org/cimhub/raw_v34/classes/switched_shunt
    rank: 1000
    domain_of:
    - SwitchedShuntRecord
    range: integer
    required: false
  b2:
    name: b2
    annotations:
      order:
        tag: order
        value: 14
      value_type:
        tag: value_type
        value: float
      precision:
        tag: precision
        value: 5
      serialize_if:
        tag: serialize_if
        value: custom:n2 != 0
      raw_default:
        tag: raw_default
        value: 0.0
    description: B2 - Admittance increment for each step in block 2 in Mvar at unity
      voltage
    from_schema: https://gridappsd.org/cimhub/raw_v34/classes/switched_shunt
    rank: 1000
    domain_of:
    - SwitchedShuntRecord
    range: float
    required: false
    unit:
      ucum_code: MVAr
  n3:
    name: n3
    annotations:
      order:
        tag: order
        value: 15
      value_type:
        tag: value_type
        value: int
      serialize_if:
        tag: serialize_if
        value: custom:n3 != 0
      raw_default:
        tag: raw_default
        value: 0
    description: N3 - Number of steps for block 3 (0 to 9)
    from_schema: https://gridappsd.org/cimhub/raw_v34/classes/switched_shunt
    rank: 1000
    domain_of:
    - SwitchedShuntRecord
    range: integer
    required: false
  b3:
    name: b3
    annotations:
      order:
        tag: order
        value: 16
      value_type:
        tag: value_type
        value: float
      precision:
        tag: precision
        value: 5
      serialize_if:
        tag: serialize_if
        value: custom:n3 != 0
      raw_default:
        tag: raw_default
        value: 0.0
    description: B3 - Admittance increment for each step in block 3 in Mvar at unity
      voltage
    from_schema: https://gridappsd.org/cimhub/raw_v34/classes/switched_shunt
    rank: 1000
    domain_of:
    - SwitchedShuntRecord
    range: float
    required: false
    unit:
      ucum_code: MVAr
  n4:
    name: n4
    annotations:
      order:
        tag: order
        value: 17
      value_type:
        tag: value_type
        value: int
      serialize_if:
        tag: serialize_if
        value: custom:n4 != 0
      raw_default:
        tag: raw_default
        value: 0
    description: N4 - Number of steps for block 4 (0 to 9)
    from_schema: https://gridappsd.org/cimhub/raw_v34/classes/switched_shunt
    rank: 1000
    domain_of:
    - SwitchedShuntRecord
    range: integer
    required: false
  b4:
    name: b4
    annotations:
      order:
        tag: order
        value: 18
      value_type:
        tag: value_type
        value: float
      precision:
        tag: precision
        value: 5
      serialize_if:
        tag: serialize_if
        value: custom:n4 != 0
      raw_default:
        tag: raw_default
        value: 0.0
    description: B4 - Admittance increment for each step in block 4 in Mvar at unity
      voltage
    from_schema: https://gridappsd.org/cimhub/raw_v34/classes/switched_shunt
    rank: 1000
    domain_of:
    - SwitchedShuntRecord
    range: float
    required: false
    unit:
      ucum_code: MVAr
  n5:
    name: n5
    annotations:
      order:
        tag: order
        value: 19
      value_type:
        tag: value_type
        value: int
      serialize_if:
        tag: serialize_if
        value: custom:n5 != 0
      raw_default:
        tag: raw_default
        value: 0
    description: N5 - Number of steps for block 5 (0 to 9)
    from_schema: https://gridappsd.org/cimhub/raw_v34/classes/switched_shunt
    rank: 1000
    domain_of:
    - SwitchedShuntRecord
    range: integer
    required: false
  b5:
    name: b5
    annotations:
      order:
        tag: order
        value: 20
      value_type:
        tag: value_type
        value: float
      precision:
        tag: precision
        value: 5
      serialize_if:
        tag: serialize_if
        value: custom:n5 != 0
      raw_default:
        tag: raw_default
        value: 0.0
    description: B5 - Admittance increment for each step in block 5 in Mvar at unity
      voltage
    from_schema: https://gridappsd.org/cimhub/raw_v34/classes/switched_shunt
    rank: 1000
    domain_of:
    - SwitchedShuntRecord
    range: float
    required: false
    unit:
      ucum_code: MVAr
  n6:
    name: n6
    annotations:
      order:
        tag: order
        value: 21
      value_type:
        tag: value_type
        value: int
      serialize_if:
        tag: serialize_if
        value: custom:n6 != 0
      raw_default:
        tag: raw_default
        value: 0
    description: N6 - Number of steps for block 6 (0 to 9)
    from_schema: https://gridappsd.org/cimhub/raw_v34/classes/switched_shunt
    rank: 1000
    domain_of:
    - SwitchedShuntRecord
    range: integer
    required: false
  b6:
    name: b6
    annotations:
      order:
        tag: order
        value: 22
      value_type:
        tag: value_type
        value: float
      precision:
        tag: precision
        value: 5
      serialize_if:
        tag: serialize_if
        value: custom:n6 != 0
      raw_default:
        tag: raw_default
        value: 0.0
    description: B6 - Admittance increment for each step in block 6 in Mvar at unity
      voltage
    from_schema: https://gridappsd.org/cimhub/raw_v34/classes/switched_shunt
    rank: 1000
    domain_of:
    - SwitchedShuntRecord
    range: float
    required: false
    unit:
      ucum_code: MVAr
  n7:
    name: n7
    annotations:
      order:
        tag: order
        value: 23
      value_type:
        tag: value_type
        value: int
      serialize_if:
        tag: serialize_if
        value: custom:n7 != 0
      raw_default:
        tag: raw_default
        value: 0
    description: N7 - Number of steps for block 7 (0 to 9)
    from_schema: https://gridappsd.org/cimhub/raw_v34/classes/switched_shunt
    rank: 1000
    domain_of:
    - SwitchedShuntRecord
    range: integer
    required: false
  b7:
    name: b7
    annotations:
      order:
        tag: order
        value: 24
      value_type:
        tag: value_type
        value: float
      precision:
        tag: precision
        value: 5
      serialize_if:
        tag: serialize_if
        value: custom:n7 != 0
      raw_default:
        tag: raw_default
        value: 0.0
    description: B7 - Admittance increment for each step in block 7 in Mvar at unity
      voltage
    from_schema: https://gridappsd.org/cimhub/raw_v34/classes/switched_shunt
    rank: 1000
    domain_of:
    - SwitchedShuntRecord
    range: float
    required: false
    unit:
      ucum_code: MVAr
  n8:
    name: n8
    annotations:
      order:
        tag: order
        value: 25
      value_type:
        tag: value_type
        value: int
      serialize_if:
        tag: serialize_if
        value: custom:n8 != 0
      raw_default:
        tag: raw_default
        value: 0
    description: N8 - Number of steps for block 8 (0 to 9)
    from_schema: https://gridappsd.org/cimhub/raw_v34/classes/switched_shunt
    rank: 1000
    domain_of:
    - SwitchedShuntRecord
    range: integer
    required: false
  b8:
    name: b8
    annotations:
      order:
        tag: order
        value: 26
      value_type:
        tag: value_type
        value: float
      precision:
        tag: precision
        value: 5
      serialize_if:
        tag: serialize_if
        value: custom:n8 != 0
      raw_default:
        tag: raw_default
        value: 0.0
    description: B8 - Admittance increment for each step in block 8 in Mvar at unity
      voltage
    from_schema: https://gridappsd.org/cimhub/raw_v34/classes/switched_shunt
    rank: 1000
    domain_of:
    - SwitchedShuntRecord
    range: float
    required: false
    unit:
      ucum_code: MVAr
  nreg:
    name: nreg
    annotations:
      order:
        tag: order
        value: 27
      value_type:
        tag: value_type
        value: int
      raw_default:
        tag: raw_default
        value: 0
    description: NREG - Node number of bus SWREG (0 if SWREG is not in a substation)
    from_schema: https://gridappsd.org/cimhub/raw_v34/classes/switched_shunt
    domain_of:
    - GeneratorRecord
    - FactsDeviceRecord
    - SwitchedShuntRecord
    range: integer
    required: false

Induced

name: SwitchedShuntRecord
description: 'Switched shunt compensator data record.

  Variable-length format:

  - Fixed fields: I, MODSW, ADJM, STAT, VSWHI, VSWLO, SWREG, RMPCT, RMIDNT, BINIT

  - Variable blocks: Up to 8 N/B pairs (only non-zero blocks are serialized)

  - Final field: NREG (only if remote regulation is used)

  Maps to CIM: cim.ShuntCompensator, cim.LinearShuntCompensator

  '
from_schema: https://gridappsd.org/cimhub/raw_v34
attributes:
  bus_number:
    name: bus_number
    annotations:
      order:
        tag: order
        value: 1
      value_type:
        tag: value_type
        value: int
    description: I - Bus number or extended bus name where the switched shunt is connected
    from_schema: https://gridappsd.org/cimhub/raw_v34/classes/switched_shunt
    owner: SwitchedShuntRecord
    domain_of:
    - BusRecord
    - LoadRecord
    - FixedShuntRecord
    - GeneratorRecord
    - AreaInterchangeRecord
    - SwitchedShuntRecord
    - SubstationNodeRecord
    - EquipmentTerminalRecord
    range: integer
    required: true
  modsw:
    name: modsw
    annotations:
      order:
        tag: order
        value: 2
      value_type:
        tag: value_type
        value: int
      raw_default:
        tag: raw_default
        value: 1
    description: MODSW - Control mode (0 locked, 1 discrete local or remote voltage,
      2 continuous voltage, 3-6 reactive power or admittance control)
    from_schema: https://gridappsd.org/cimhub/raw_v34/classes/switched_shunt
    rank: 1000
    owner: SwitchedShuntRecord
    domain_of:
    - SwitchedShuntRecord
    range: integer
    required: false
  adjm:
    name: adjm
    annotations:
      order:
        tag: order
        value: 3
      value_type:
        tag: value_type
        value: int
      raw_default:
        tag: raw_default
        value: 0
    description: ADJM - Adjustment method (0 switch in input order, 1 next highest
      or lowest total admittance)
    from_schema: https://gridappsd.org/cimhub/raw_v34/classes/switched_shunt
    rank: 1000
    owner: SwitchedShuntRecord
    domain_of:
    - SwitchedShuntRecord
    range: integer
    required: false
  status:
    name: status
    annotations:
      order:
        tag: order
        value: 4
      value_type:
        tag: value_type
        value: int
      raw_default:
        tag: raw_default
        value: 1
    description: STAT - Switched shunt status (0=out of service, 1=in service)
    from_schema: https://gridappsd.org/cimhub/raw_v34/classes/switched_shunt
    owner: SwitchedShuntRecord
    domain_of:
    - LoadRecord
    - FixedShuntRecord
    - GeneratorRecord
    - BranchRecord
    - SwitchRecord
    - TransformerRecord
    - SwitchedShuntRecord
    - GneDeviceRecord
    - InductionMachineRecord
    - SubstationNodeRecord
    - StationSwitchingDeviceRecord
    range: integer
    required: false
  vswhi:
    name: vswhi
    annotations:
      order:
        tag: order
        value: 5
      value_type:
        tag: value_type
        value: float
      precision:
        tag: precision
        value: 5
      raw_default:
        tag: raw_default
        value: 1.0
    description: VSWHI - Voltage upper limit for switching in per-unit
    from_schema: https://gridappsd.org/cimhub/raw_v34/classes/switched_shunt
    rank: 1000
    owner: SwitchedShuntRecord
    domain_of:
    - SwitchedShuntRecord
    range: float
    required: false
  vswlo:
    name: vswlo
    annotations:
      order:
        tag: order
        value: 6
      value_type:
        tag: value_type
        value: float
      precision:
        tag: precision
        value: 5
      raw_default:
        tag: raw_default
        value: 1.0
    description: VSWLO - Voltage lower limit for switching in per-unit
    from_schema: https://gridappsd.org/cimhub/raw_v34/classes/switched_shunt
    rank: 1000
    owner: SwitchedShuntRecord
    domain_of:
    - SwitchedShuntRecord
    range: float
    required: false
  swreg:
    name: swreg
    annotations:
      order:
        tag: order
        value: 7
      value_type:
        tag: value_type
        value: int
      raw_default:
        tag: raw_default
        value: 0
    description: SWREG - Bus number or extended bus name of the regulated bus (0 or
      own bus for local control)
    from_schema: https://gridappsd.org/cimhub/raw_v34/classes/switched_shunt
    rank: 1000
    owner: SwitchedShuntRecord
    domain_of:
    - SwitchedShuntRecord
    range: integer
    required: false
  rmpct:
    name: rmpct
    annotations:
      order:
        tag: order
        value: 8
      value_type:
        tag: value_type
        value: float
      precision:
        tag: precision
        value: 4
      raw_default:
        tag: raw_default
        value: 100.0
    description: RMPCT - Percent of required Mvar contribution (must be positive)
    from_schema: https://gridappsd.org/cimhub/raw_v34/classes/switched_shunt
    owner: SwitchedShuntRecord
    domain_of:
    - GeneratorRecord
    - FactsDeviceRecord
    - SwitchedShuntRecord
    range: float
    required: false
  rmidnt:
    name: rmidnt
    annotations:
      order:
        tag: order
        value: 9
      value_type:
        tag: value_type
        value: string
      width:
        tag: width
        value: 12
      quote:
        tag: quote
        value: true
      quote_char:
        tag: quote_char
        value: ''''
      raw_default:
        tag: raw_default
        value: ''
    description: RMIDNT - Name of the VSC dc line (MODSW 4) or FACTS device (MODSW
      6)
    from_schema: https://gridappsd.org/cimhub/raw_v34/classes/switched_shunt
    rank: 1000
    owner: SwitchedShuntRecord
    domain_of:
    - SwitchedShuntRecord
    range: string
    required: false
  binit:
    name: binit
    annotations:
      order:
        tag: order
        value: 10
      value_type:
        tag: value_type
        value: float
      precision:
        tag: precision
        value: 5
      raw_default:
        tag: raw_default
        value: 0.0
    description: BINIT - Initial switched shunt admittance in Mvar at unity voltage
    from_schema: https://gridappsd.org/cimhub/raw_v34/classes/switched_shunt
    rank: 1000
    owner: SwitchedShuntRecord
    domain_of:
    - SwitchedShuntRecord
    range: float
    required: false
    unit:
      ucum_code: MVAr
  n1:
    name: n1
    annotations:
      order:
        tag: order
        value: 11
      value_type:
        tag: value_type
        value: int
      serialize_if:
        tag: serialize_if
        value: custom:n1 != 0
      raw_default:
        tag: raw_default
        value: 0
    description: N1 - Number of steps for block 1 (0 to 9)
    from_schema: https://gridappsd.org/cimhub/raw_v34/classes/switched_shunt
    rank: 1000
    owner: SwitchedShuntRecord
    domain_of:
    - SwitchedShuntRecord
    range: integer
    required: false
  b1:
    name: b1
    annotations:
      order:
        tag: order
        value: 12
      value_type:
        tag: value_type
        value: float
      precision:
        tag: precision
        value: 5
      serialize_if:
        tag: serialize_if
        value: custom:n1 != 0
      raw_default:
        tag: raw_default
        value: 0.0
    description: B1 - Admittance increment for each step in block 1 in Mvar at unity
      voltage
    from_schema: https://gridappsd.org/cimhub/raw_v34/classes/switched_shunt
    rank: 1000
    owner: SwitchedShuntRecord
    domain_of:
    - SwitchedShuntRecord
    range: float
    required: false
    unit:
      ucum_code: MVAr
  n2:
    name: n2
    annotations:
      order:
        tag: order
        value: 13
      value_type:
        tag: value_type
        value: int
      serialize_if:
        tag: serialize_if
        value: custom:n2 != 0
      raw_default:
        tag: raw_default
        value: 0
    description: N2 - Number of steps for block 2 (0 to 9)
    from_schema: https://gridappsd.org/cimhub/raw_v34/classes/switched_shunt
    rank: 1000
    owner: SwitchedShuntRecord
    domain_of:
    - SwitchedShuntRecord
    range: integer
    required: false
  b2:
    name: b2
    annotations:
      order:
        tag: order
        value: 14
      value_type:
        tag: value_type
        value: float
      precision:
        tag: precision
        value: 5
      serialize_if:
        tag: serialize_if
        value: custom:n2 != 0
      raw_default:
        tag: raw_default
        value: 0.0
    description: B2 - Admittance increment for each step in block 2 in Mvar at unity
      voltage
    from_schema: https://gridappsd.org/cimhub/raw_v34/classes/switched_shunt
    rank: 1000
    owner: SwitchedShuntRecord
    domain_of:
    - SwitchedShuntRecord
    range: float
    required: false
    unit:
      ucum_code: MVAr
  n3:
    name: n3
    annotations:
      order:
        tag: order
        value: 15
      value_type:
        tag: value_type
        value: int
      serialize_if:
        tag: serialize_if
        value: custom:n3 != 0
      raw_default:
        tag: raw_default
        value: 0
    description: N3 - Number of steps for block 3 (0 to 9)
    from_schema: https://gridappsd.org/cimhub/raw_v34/classes/switched_shunt
    rank: 1000
    owner: SwitchedShuntRecord
    domain_of:
    - SwitchedShuntRecord
    range: integer
    required: false
  b3:
    name: b3
    annotations:
      order:
        tag: order
        value: 16
      value_type:
        tag: value_type
        value: float
      precision:
        tag: precision
        value: 5
      serialize_if:
        tag: serialize_if
        value: custom:n3 != 0
      raw_default:
        tag: raw_default
        value: 0.0
    description: B3 - Admittance increment for each step in block 3 in Mvar at unity
      voltage
    from_schema: https://gridappsd.org/cimhub/raw_v34/classes/switched_shunt
    rank: 1000
    owner: SwitchedShuntRecord
    domain_of:
    - SwitchedShuntRecord
    range: float
    required: false
    unit:
      ucum_code: MVAr
  n4:
    name: n4
    annotations:
      order:
        tag: order
        value: 17
      value_type:
        tag: value_type
        value: int
      serialize_if:
        tag: serialize_if
        value: custom:n4 != 0
      raw_default:
        tag: raw_default
        value: 0
    description: N4 - Number of steps for block 4 (0 to 9)
    from_schema: https://gridappsd.org/cimhub/raw_v34/classes/switched_shunt
    rank: 1000
    owner: SwitchedShuntRecord
    domain_of:
    - SwitchedShuntRecord
    range: integer
    required: false
  b4:
    name: b4
    annotations:
      order:
        tag: order
        value: 18
      value_type:
        tag: value_type
        value: float
      precision:
        tag: precision
        value: 5
      serialize_if:
        tag: serialize_if
        value: custom:n4 != 0
      raw_default:
        tag: raw_default
        value: 0.0
    description: B4 - Admittance increment for each step in block 4 in Mvar at unity
      voltage
    from_schema: https://gridappsd.org/cimhub/raw_v34/classes/switched_shunt
    rank: 1000
    owner: SwitchedShuntRecord
    domain_of:
    - SwitchedShuntRecord
    range: float
    required: false
    unit:
      ucum_code: MVAr
  n5:
    name: n5
    annotations:
      order:
        tag: order
        value: 19
      value_type:
        tag: value_type
        value: int
      serialize_if:
        tag: serialize_if
        value: custom:n5 != 0
      raw_default:
        tag: raw_default
        value: 0
    description: N5 - Number of steps for block 5 (0 to 9)
    from_schema: https://gridappsd.org/cimhub/raw_v34/classes/switched_shunt
    rank: 1000
    owner: SwitchedShuntRecord
    domain_of:
    - SwitchedShuntRecord
    range: integer
    required: false
  b5:
    name: b5
    annotations:
      order:
        tag: order
        value: 20
      value_type:
        tag: value_type
        value: float
      precision:
        tag: precision
        value: 5
      serialize_if:
        tag: serialize_if
        value: custom:n5 != 0
      raw_default:
        tag: raw_default
        value: 0.0
    description: B5 - Admittance increment for each step in block 5 in Mvar at unity
      voltage
    from_schema: https://gridappsd.org/cimhub/raw_v34/classes/switched_shunt
    rank: 1000
    owner: SwitchedShuntRecord
    domain_of:
    - SwitchedShuntRecord
    range: float
    required: false
    unit:
      ucum_code: MVAr
  n6:
    name: n6
    annotations:
      order:
        tag: order
        value: 21
      value_type:
        tag: value_type
        value: int
      serialize_if:
        tag: serialize_if
        value: custom:n6 != 0
      raw_default:
        tag: raw_default
        value: 0
    description: N6 - Number of steps for block 6 (0 to 9)
    from_schema: https://gridappsd.org/cimhub/raw_v34/classes/switched_shunt
    rank: 1000
    owner: SwitchedShuntRecord
    domain_of:
    - SwitchedShuntRecord
    range: integer
    required: false
  b6:
    name: b6
    annotations:
      order:
        tag: order
        value: 22
      value_type:
        tag: value_type
        value: float
      precision:
        tag: precision
        value: 5
      serialize_if:
        tag: serialize_if
        value: custom:n6 != 0
      raw_default:
        tag: raw_default
        value: 0.0
    description: B6 - Admittance increment for each step in block 6 in Mvar at unity
      voltage
    from_schema: https://gridappsd.org/cimhub/raw_v34/classes/switched_shunt
    rank: 1000
    owner: SwitchedShuntRecord
    domain_of:
    - SwitchedShuntRecord
    range: float
    required: false
    unit:
      ucum_code: MVAr
  n7:
    name: n7
    annotations:
      order:
        tag: order
        value: 23
      value_type:
        tag: value_type
        value: int
      serialize_if:
        tag: serialize_if
        value: custom:n7 != 0
      raw_default:
        tag: raw_default
        value: 0
    description: N7 - Number of steps for block 7 (0 to 9)
    from_schema: https://gridappsd.org/cimhub/raw_v34/classes/switched_shunt
    rank: 1000
    owner: SwitchedShuntRecord
    domain_of:
    - SwitchedShuntRecord
    range: integer
    required: false
  b7:
    name: b7
    annotations:
      order:
        tag: order
        value: 24
      value_type:
        tag: value_type
        value: float
      precision:
        tag: precision
        value: 5
      serialize_if:
        tag: serialize_if
        value: custom:n7 != 0
      raw_default:
        tag: raw_default
        value: 0.0
    description: B7 - Admittance increment for each step in block 7 in Mvar at unity
      voltage
    from_schema: https://gridappsd.org/cimhub/raw_v34/classes/switched_shunt
    rank: 1000
    owner: SwitchedShuntRecord
    domain_of:
    - SwitchedShuntRecord
    range: float
    required: false
    unit:
      ucum_code: MVAr
  n8:
    name: n8
    annotations:
      order:
        tag: order
        value: 25
      value_type:
        tag: value_type
        value: int
      serialize_if:
        tag: serialize_if
        value: custom:n8 != 0
      raw_default:
        tag: raw_default
        value: 0
    description: N8 - Number of steps for block 8 (0 to 9)
    from_schema: https://gridappsd.org/cimhub/raw_v34/classes/switched_shunt
    rank: 1000
    owner: SwitchedShuntRecord
    domain_of:
    - SwitchedShuntRecord
    range: integer
    required: false
  b8:
    name: b8
    annotations:
      order:
        tag: order
        value: 26
      value_type:
        tag: value_type
        value: float
      precision:
        tag: precision
        value: 5
      serialize_if:
        tag: serialize_if
        value: custom:n8 != 0
      raw_default:
        tag: raw_default
        value: 0.0
    description: B8 - Admittance increment for each step in block 8 in Mvar at unity
      voltage
    from_schema: https://gridappsd.org/cimhub/raw_v34/classes/switched_shunt
    rank: 1000
    owner: SwitchedShuntRecord
    domain_of:
    - SwitchedShuntRecord
    range: float
    required: false
    unit:
      ucum_code: MVAr
  nreg:
    name: nreg
    annotations:
      order:
        tag: order
        value: 27
      value_type:
        tag: value_type
        value: int
      raw_default:
        tag: raw_default
        value: 0
    description: NREG - Node number of bus SWREG (0 if SWREG is not in a substation)
    from_schema: https://gridappsd.org/cimhub/raw_v34/classes/switched_shunt
    owner: SwitchedShuntRecord
    domain_of:
    - GeneratorRecord
    - FactsDeviceRecord
    - SwitchedShuntRecord
    range: integer
    required: false